and characteristics
Dependability
Integration of protection functions in an ASIC electronic component used in all
Micrologic control units guarantees a high degree of reliability and immunity to
conducted or radiated disturbances.
On Micrologic A, P and H control units, advanced functions are managed by an
independent microprocessor.
Current protection
Micrologic 2: basic protection
X: type of protection
c 2 for basic protection
c 5 for selective protection
c 6 for selective + earth-fault protection
c 7 for selective + earth-leakage protection
Y: control-unit generation
Identification of the control-unit generation.
0 signifies the first generation.
Z: type of measurement
c A for ammeter
c P for power meter
c H for harmonic meter.
E46019
X Y
Protection:
0
Ir
Isd
2.0 A
Protection:
056411
Ir
Isd
Ii
t
E46033
E46020
Protection:
Ir
Isd
Ii
Ig
long time
+ short time
+ instantaneous
+ earth fault
t
E46034
E46020
Protection:
16
Ir
Isd
Ii
Masterpact
In
long time
+ short time
+ instantaneous
+ earth leakage
Schneider Electric
H: P + harmonics
2.0 A
E46251
c power quality: fundamentals, distortion, amplitude and phase of harmonics up to the 31st
order
c waveform capture after fault, alarm or on request
c enhanced alarm programming: thresholds and actions
100 %
40 %
E46256
E46255
6.0 H
7.0 H
E46256
7.0 P
E46255
6.0 P
5.0 H
E46256
5.0 P
E46256
5.0 A
E46252
menu
100 %
40 %
6.0 A
E46253
menu
100 %
40 %
7.0 A
E46253
menu
100 %
40 %
menu
17
Masterpact
Schneider Electric
Control units
Micrologic A ammeter
E46028
Functions
and characteristics
Micrologic 6.0 A
9
10
t= In=
tsd= tr=
Isd=
Ii= Ir=
Ig=
tg=
MAX
s
kA
11
100 %
12
40 %
13
menu
long time
Ir
.7
.6
.5
.4
x In
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
.4 .4 .3
.2
.3
.1
.2
.1 2 0
on
setting
Ig
D
C
B
A
I t
off
delay
tg
F
G
H
J
Ii
(s)
(s)
on
.2
.1
2
I t
6 8 10
12
15
off
2
x In
test
.4 .4 .3
.3
.2
.1
4
3
menu
Communication option
In conjunction with the COM communication option, the control unit transmits the
following:
c setting values
c all ammeter measurements
c tripping causes
c maximeter reset.
instantaneous
tsd
@ 6 Ir
short time
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
Protection thresholds and delays are set using the adjustment dials.
The selected values are momentarily displayed in amperes and in seconds.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
The long-time rating plug OFF enables to cancel the overload protection.
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth fault protection
Residual or source ground return.
Selection of I2t type (ON or OFF) for delay.
Residual earth-leakage protection (Vigi).
Operation without an external power supply.
d Protected against nuisance tripping.
k DC-component withstand class A up to 10 A.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 In (4P 3d + N/2),
neutral protection at In (4P 4d).
Zone selective interlocking (ZSI)
A ZSI terminal block may be used to interconnect a number of control units to
provide total discrimination for short-time and earth-fault protection, without a delay
before tripping.
6
8
0
off
ground fault
1
2
3
4
5
6
7
8
9
10
11
12
13
Note.
Micrologic A control units come with a transparent leadseal cover as standard.
18
Masterpact
Schneider Electric
Micrologic 2.0 A
long time
current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
time setting (s)
time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %)
thermal memory
(1) 0 to - 40 % - (2) 0 to - 60 %
1.5
Ir
tr
2.5
10
menu
Micrologic 2.0 A
I2
I3
IN
I1
no auxiliary source (where I > 20 % In)
I1 max I2 max I3 max IN max
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
20
500
20
13.8
24
600
24
16.6
Ir
tr
Isd
tsd
Ii
Isd = Ir x
1.5
2.5
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
Ii = In x
settings
0.98
E46023
long time
current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
time setting (s)
time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %
thermal memory
(1) 0 to - 40 % - (2) 0 to - 60 %
10
10
12
15
off
Ammeter
continuous current measurements
display from 20 to 200 % of In
accuracy: 1.5 % (including sensors)
maximeters
Micrologic 6.0 A
A
B
C
0.3
0.3
0.4
0.2
0.3
0.4
500
640
720
0
0.1
0.2
0.1
0.2
20
80
140
80
140
200
D
0.5
0.5
800
0.3
0.3
230
320
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
Micrologic 7.0 A
0.5
1
2
60
60
140
350
350
500
800
800
1000
140
140
200
230
230
320
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
E46024
earth fault
pick up (A)
accuracy: 10 %
24
600
24
16.6
Protection
instantaneous
pick-up (A)
accuracy: 10 %
time delay
20
500
20
13.8
0
Isd = Ir x
Isd
Ammeter
short time
pick-up (A)
accuracy: 10 %
time setting (s)
0.98
I t on
Ig
2
tg
I t off
10
20
30
E46243
instantaneous
pick-up (A)
accuracy: 10 %
time delay
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
0.4
0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
0.5 1
2
4
8
12
16
12.5 25
50
100
200
300
400
0.7(1) 1
2
4
8
12
16
0.7(2) 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping
E46022
Protection
In
t
I
menu
I1
I2
I3
IN
Ig
In
no auxiliary source (where I > 20 % In)
I1 max I2 max I3 max IN max Ig max In max
Note.
All current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the
battery.
19
Masterpact
Schneider Electric
Control units
Micrologic P power
E46017
Functions
and characteristics
Micrologic 6.0 P
9
10
I (A)
Trip
2000A
11
24s
20 kA
0.4s
Off
13
14
12
15
long time
.7
.6
.5
.4
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
16
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
D
C
B
A
on
I t
off
delay
tg
F
G
H
J
Ii
(s)
setting
Ig
Depending on the thresholds and time delays set using the keypad or remotely
using the COM option, the Micrologic P control unit monitors currents and voltage,
power, frequency and the phase sequence. Each threshold overrun is signalled
remotely via the COM option. Each threshold overrun may be combined with
tripping (protection) or an indication carried out by an optional M2C or M6C
programmable contact (alarm), or both (protection and alarm).
Ir
(s)
on
.2
.1
2
I t
6 8 10
12
15
off
2
x In
test
.4 .4 .3
.3
.2
.1
4
3
6
8
0
off
ground fault
Load shedding and reconnection parameters may be set according to the power or
the current flowing through the circuit breaker. Load shedding is carried out by a
supervisor via the COM option or by an M2C or M6C programmable contact.
Measurements .......................................................................
The Micrologic P control unit calculates in real time all the electrical values (V, A,
W, VAR, VA, Wh, VARh, VAh, Hz), power factors and crest factors.
The Micrologic P control unit also calculates demand current and demand power
over an adjustable time period. Each measurement is associated with a minimeter
and a maximeter.
In the event of tripping on a fault, the interrupted current is stored. The optional
external power supply makes it possible to display the value with the circuit breaker
open or not supplied.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Note.
Micrologic P control units come with a non-transparent
lead-seal cover as standard.
20
Masterpact
Schneider Electric
instantaneous
pick-up (A)
accuracy: 10 %
time delay
earth fault
pick-up (A)
accuracy: 10 %
1.5
2.5
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
Ii = In x
24
600
24
16.6
Ig = In x
In i 400 A
400 A < In i 1200 A
In > 1200 A
settings
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
tr
Isd
IDMTL
10
10
12
15
OFF
Micrologic 6.0 P
A
B
C
0.3
0.3
0.4
0.2
0.3
0.4
500
640
720
0
0.1
0.2
0.1
0.2
20
80
140
80
140
200
tsd
D
0.5
0.5
800
0.3
0.3
230
320
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
Micrologic 7.0 P
0.5
1
2
10
60
60
140
350
350
500
800
800
1000
G
0.8
0.8
1040
H
0.9
0.9
1120
I t on
Ig
J
1
1
1200
I t off
tg
20
30
In
t
140
140
200
230
230
320
Iunbalance
Imax demand: I1, I2, I3, IN
threshold
0.05 to 0.6 Iaverage
0.2 In to In
time delay
1 to 40 s.
15 to 1500 s.
t
threshold
20 A to 1200 A
1 to 10 s.
voltage
voltage unbalance
minimum voltage
maximum voltage
Uunbalance
Umin
Umax
1 to 40 s.
1.2 to 5 s.
1.2 to 5 s.
power
reverse power
rP
5 to 500 kW
0.2 to 20 s.
frequency
minimum frequency
maximum frequency
Fmin
Fmax
45 to Fmax
Fmin to 440 Hz
1.2 to 5 s.
1.2 to 5 s.
phase sequence
sequence (alarm)
1/2/3 or 1/3/2
0.3 s.
threshold
delay
delay
0
I
P
I/U/P/F
time delay
20% tr to 80% tr.
10 to 3600 s.
E46016
Ir
Ii
current
current unbalance
maximum demand current
20
500
20
13.8
E46024
Isd = Ir x
settings
0.98
E46243
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
E46015
E46021
Protection
t
threshold
threshold
delay
delay
I/P
Note.
All current-based protection functions require no auxiliary source.
Voltage-based protection functions are connected to AC power via a voltage
measurement input built into the circuit breaker.
21
Masterpact
Schneider Electric
Control units
Micrologic P power
3850A
E46261
E46258
Functions
and characteristics
Imax
instant.
N 1 2 3
100
I1
I2
=
=
4800A
4600A
I3
4000A
IN
=
=
200A
13A
50
Reset ( + / - )
Navigation from one display to another is intuitive. The six buttons on the keypad
provide access to the menus and easy selection of values. When the setting cover
is closed, the keypad may no longer be used to access the protection settings, but
still provides access to the displays for measurements, histories, indicators, etc.
Measurements .......................................................................
Instantaneous values
The value displayed on the screen is refreshed every second.
Minimum and maximum values of measurements are stored in memory
(minimeters and maximeters).
currents
Default display
Display of a maximum
current
I rms
U inst.
U12 =
U23 =
U31 =
U1N =
U2N =
U3N =
E46263
E46262
I max rms
400V
404V
401V
230V
229V
233V
Pinst.
P
(kW)
+2180
(kVAR)
-650
(kVA)
+2280
A
A
A
A
1
2
e-fault
1
2
e-fault
3
N
e-leakage
3
N
e-leakage
V
V
V
%
12
23
31
1N
2N
3N
(U12 + U23 + U31) / 3
voltages
U rms
V rms
U average rms
U unbalance
power, energy
P active, Q reactive, S apparent
E active, E reactive, E apparent
W, Var, VA
Wh, VARh, VAh
power factor
PF
totals
totals consumed - supplied
totals consumed
totals supplied
total
frequencies
F (Hz)
Display of a power
E46265
E47305
Display of a voltage
P
Pdemand
demande
PActive P (kW)
2180 kW +2180
QRactive (kVAR)
Q
- 650 kVAR -650
60.0
S
(kVA)
Apparente+2280
S
2280 kVA
Display of a frequency
Hz
Demand metering
The demand is calculated over a fixed or sliding time window that may be
programmed from 5 to 60 minutes. According to the contract signed with the power
supplier, an indicator associated with a load shedding function makes it possible to
avoid or minimise the costs of overrunning the subscribed power. Maximum
demand values are systematically stored and time stamped (maximeter).
currents
I demand
I max demand
A
A
A
A
1
2
e-fault
1
2
e-fault
3
N
e-leakage
3
N
e-leakage
power
P, Q, S demand
P, Q, S max demand
W, Var, VA
W, Var, VA
totals
totals
Trip
history
Ir
03/08/1999
Isd
27/07/1999
Umax
30/06/1999
E46260
E46259
Histories .................................................................................
Trip
03/08/1999
12:02:36
Ir =
1000A
I1 =
1200A
I2 =
I3 =
1430A
1060A
IN =
53A
The last ten trips and alarms are recorded in two separate history files that may be
displayed on the screen.
c tripping history:
v type of fault
v date and time
v values measured at the time of tripping (interrupted current, etc.).
c alarm history:
v type of alarm
v date and time
v values measured at the time of the alarm.
22
Masterpact
Schneider Electric
E47070
Reports
Time
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
Ready
5 seconds
Event
08:49:06
08:49:01
08:48:38
08:48:30
08:46:16
08:39:19
08:39:06
08:39:06
08:38:57
08:30:44
08:24:31
08:24:30
08:24:15
08:18:07
07:54:05
07:53:55
07:53:54
07:51:46
07:51:33
07:51:29
07:50:17
07:50:17
07:49:13
07:48:57
07:48:38
07:48:22
07:46:54
07:44:59
07:44:59
Module
User : master
User : master
User : master
User : master
User : master
User : master
Key Status : Key Found
User : master
PowerLogic Network
SMS-3000 Client
Alarm Setup
Alarm Setup
Alarm Setup
SMS-3000 Client
PowerLogic Network
Level : 1
PowerLogic Network
Event/Alarm/Network
User : master
Level : 1
PowerLogic Network
Key Status : Key Found
PowerLogic Network
User : master
Level : 1
PowerLogic Network
Event/Alarm/Network
User : NA
Err : 109
SMS-3000 Client
User : -1
Logger Template Devices Logger Setup
User : -1
Logger Template Topics Logger Setup
User : -1
Logger Templates
Logger Setup
User : master
Analog Levels Assigned Alarm Setup
User : master
Analog Levels Template Alarm Setup
User : master
Functions
Alarm Setup
User : master
Digital Levels Assigned
Alarm Setup
User : master
Analog Levels Assigned Alarm Setup
Device : MicroLogic Breaker User :master
Device Setup
Device : MicroLogic Breaker User :master
Device Setup
Device : Transformer Temp User : master
Device Setup
Device : Transformer Temp User :master
Device Setup
User : master
User Level : 1
SMS-3000 Client
Key Status : Key Found
PowerLogic Network
User :master
Level : 1
PowerLogic Network
ONLINE: DEMO
Level : 1
User level : 1
TOD Event Tasks
Tasks
TOD Events
User level : 1
No working system
9:30
23
Masterpact
Schneider Electric
Control units
Micrologic H harmonics
E46257
Functions
and characteristics
Measurements .......................................................................
(A)
The Micrologic H control unit offers all the measurements carried out by Micrologic
P, with in addition:
c phase by phase measurements of:
v power, energy
v power factors
c calculation of:
v current and voltage total harmonic distortion (THD)
v current, voltage and power fundamentals
v current and voltage harmonics up to the 31st order.
Instantaneous values displayed on the screen
(V)
I rms
Micrologic 7.0 H
I
U
P
E
currents
(kW)
I max rms
(kWh)
A
A
A
A
1
2
e-fault
1
2
e-fault
3
N
e-leakage
3
N
e-leakage
V
V
V
%
12
23
31
1N
2N
3N
(U12 + U23 + U31) / 3
voltages
U rms
V rms
U average rms
U unbalance
Harmonics
power, energy
P active, Q reactive, S apparent
E active, E reactive, E apparent
W, Var, VA
Wh, VARh, VAh
power factor
PF
totals 1
2
3
totals consumed - supplied
totals consumed
totals supplied
total 1
2
3
frequencies
F
long time
Ir
.7
.6
.5
.4
x In
power-quality indicators
instantaneous
short time
tsd
(s)
2
1
.5
.4 .4 .3
.2
.1
0
I t off
.3
.2
.1
on
setting
delay
(ms)
230
350
10
140
20
30
60
800
Ii
6 8 10
4
12
3
15
off
2
x In
U I
U I
3 5
%
amplitude
P Q S
7
11 13
test
In
(A)
total fundamentals
THD
U and I harmonics
@ 6 Ir
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Hz
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
currents
I demand
earth leakage
I max demand
A
A
A
A
1
2
e-fault
1
2
e-fault
3
N
e-leakage
3
N
e-leakage
power
P, Q, S demand
P, Q, S max demand
W, Var, VA
W, Var, VA
totals
totals
Maximeters
Only the current maximeters may be displayed on the screen.
Note.
Micrologic H control units come with a non-transparent
lead-seal cover as standard.
24
Masterpact
Schneider Electric
E47071
Reports
Time
Event
Module
1,20
Harmonics(RMS)
Fundamental:
1,00
RMS:
RMS-H:
% Fundamental
0,80
Peak:
CF:
THD:
H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
H5: 0.45
H6: 0.04
H7: 1.27
H8: 0.05
H9: 0.42
H10: 0.01
H11: 1.03
H12: 0.07
0,60
OK
0,40
0,20
0,00
H2
H3
H4
H5
H6
H7
H8
H9
H10
H11
H12
Harmonics
ONLINE: DEMO
Ready
No working system
9:30
E47072
File
Phase A Current
167
642
83
321
0
17
-83
33
50
66
17
-321
33
50
66
-167
-642
Harmonics(RMS)
Fundamental:
118.08
RMS:
118.11
RMS-H:
167
2.38
Peak:
83
166.86
CF:
1.41
0
17
-83
33
THD:
50
2.02
-167
H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
H5: 0.45
H6: 0.04
H7: 1.27
H8: 0.05
H9: 0.42
H10: 0.01
H11: 1.03
H12: 0.07
OK
ONLINE: DEMO
Ready
No working system
9:30
E47070
Waveform capture
POWERLOGIC System Manager Demo
File Edit View Setup Control Display
Time
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
Ready
Log
5 seconds
Event
08:49:06
08:49:01
08:48:38
08:48:30
08:46:16
08:39:19
08:39:06
08:39:06
08:38:57
08:30:44
08:24:31
08:24:30
08:24:15
08:18:07
07:54:05
07:53:55
07:53:54
07:51:46
07:51:33
07:51:29
07:50:17
07:50:17
07:49:13
07:48:57
07:48:38
07:48:22
07:46:54
07:44:59
07:44:59
Module
User : master
User : master
User : master
User : master
User : master
User : master
Key Status : Key Found
User : master
PowerLogic Network
SMS-3000 Client
Alarm Setup
Alarm Setup
Alarm Setup
SMS-3000 Client
PowerLogic Network
Level : 1
PowerLogic Network
Event/Alarm/Network
User : master
Level : 1
PowerLogic Network
Key Status : Key Found
PowerLogic Network
User : master
Level : 1
PowerLogic Network
Event/Alarm/Network
User : NA
Err : 109
SMS-3000 Client
User : -1
Logger Template Devices Logger Setup
User : -1
Logger Template Topics Logger Setup
User : -1
Logger Templates
Logger Setup
User : master
Analog Levels Assigned Alarm Setup
User : master
Analog Levels Template Alarm Setup
User : master
Functions
Alarm Setup
User : master
Digital Levels Assigned
Alarm Setup
User : master
Analog Levels Assigned Alarm Setup
Device : MicroLogic Breaker User :master
Device Setup
Device : MicroLogic Breaker User :master
Device Setup
Device : Transformer Temp User : master
Device Setup
Device : Transformer Temp User :master
Device Setup
User : master
User Level : 1
SMS-3000 Client
Key Status : Key Found
PowerLogic Network
User :master
Level : 1
PowerLogic Network
ONLINE: DEMO
Level : 1
User level : 1
TOD Event Tasks
Tasks
TOD Events
User level : 1
No working system
9:30
25
Masterpact
Schneider Electric
E47477
059476
056467
Functions
and characteristics
056412
Rectangular sensor
External sensors
External sensor for earth-fault and neutral protection
The sensors, used with the 3P circuit breakers, are installed on the neutral
conductor for:
c neutral protection (with Micrologic P and H)
c residual type earth-fault protection (with Micrologic A, P and H)..
The rating of the sensor (CT) must be compatible with the rating of the circuit
breaker:
c NT06 to NT16: TC 400/1600
c NW08 to NW20: TC 400/2000
c NW25 to NW40: TC 1000/4000
c NW40b to NW63: TC 2000/6300.
For oversized neutral protection the sensor rating must be compatible with the
measurement range: 1,6 x IN (available up to NW 40 and NT 16).
Rectangular sensor for earth-leakage protection
The sensor is installed around the busbars (phases + neutral) to detect the zerophase sequence current required for the earth-leakage protection. Rectangular
sensors are available in two sizes.
Inside dimensions (mm)
c 280 x 115 up to 1600 A for Masterpact NT and NW
c 470 x 160 up to 4000 A for Masterpact NW.
External sensor for source ground return protection
The sensor is installed around the connection of the transformer neutral point to
earth and connects to the Micrologic 6.0 control unit via an MDGF module to
provide the source ground return (SGR) protection.
Voltage measurement inputs
Voltage measurement inputs are required for power measurements (Micrologic P
or H) and for earth-leakage protection (Micrologic 7...).
As standard, the control unit is supplied by internal voltage measurement inputs
placed downstream of the pole for voltages between 100 and 690 V AC. On
request, it is possible to replace the internal voltage measurement inputs by an
external voltage input (PTE option) which enables the control unit to draw power
directly from the distribution system upstream of the circuit breaker. An 3 m cable
with ferrite comes with this PTE option.
Ir = In x
Ir = In x
Ir = In x
025171
025173
Important: Long-time rating plugs must always be removed before carrying out
insulation or dielectric withstand tests.
Battery module
The battery module makes it possible to use the display even if the power supply to
the Micrologic control unit is interrupted and still commucating with the supervisor.
Characteristics:
c battery run-time: 12 hours (approximately)
c mounted on vertical backplate or symmetrical rail
26
Masterpact
Schneider Electric
056413
These contacts are optional equipment for the Micrologic P and H control units.
They are described with the indication contacts for the circuit breakers.
characteristics
minimum load
breaking
capacity (A)
p.f.: 0.7
M2C
M6C
M2C/M6C
V AC
V DC
240
380
24
48
125
250
10mA/24V
5
3
1.8
1.5
0.4
0.15
056429
Spare parts
Lead-seal covers
A lead-seal cover controls access to the adjustment dials.
When the cover is closed:
c it is impossible to modify settings using the keypad unless the settings lockout
pin on the cover is removed.
c the test connector remains accessible.
c the test button for the earth-fault and earth-leakage protection function remains
accessible.
Characteristics
c transparent cover for basic Micrologic and Micrologic A control units
c non-transparent cover for Micrologic P and H control units.
Spare battery
A battery supplies power to the LEDs identifying the tripping causes. Battery
service life is approximately ten years.
A test button on the front of the control unit is used to check the battery condition.
The battery may be replaced on site when discharged.
Lead-seal cover
056466
Test equipment
Mini test kit
The autonomous hand-held mini test kit may be used to:
c check operation of the control unit and the tripping and pole-opening system by
sending a signal simulating a short-circuit
c supply power to the control units for settings via the keypad when the circuitbreaker is open (Micrologic P and H control units).
Power source: standard LR6-AA battery.
Portable test kit
The portable test kit can be used alone or with a supporting personal computer.
The portable test kit without PC may be used to check:
c the mechanical operation of the circuit breaker
c the electrical continuity of the connection between the circuit breaker and the
control unit
c operation of the control unit:
v display of settings
v automatic and manual tests on protection functions
v test on the zone-selective interlocking (ZSI) function
v inhibition of the earth-fault protection
v inhibition of the thermal memory.
The portable test kit with PC offers in addition:
c comparison of the real tripping curve with the catalogue curves available on the
PC
c reset of the M2C / M6C contacts and indications
c reading and modification of settings and counters
c reading of histories and logs
c waveform capture
c analysis of harmonics.
27
Masterpact
Schneider Electric