Вы находитесь на странице: 1из 2

The ANSUL R-102 Restaurant Fire Suppression System is an automatic, preengineered fire suppression system designed to protect areas

associated with
ventilating equipment including hoods, ducts, plenums and filters. The system also
protects auxiliary grease extraction equipment and cooking equipment.

Application
Use of the R-102 system is limited to interior applications only. The
regulated release and tank assemblies must be mounted in an area
where the air temperature will not fall below 32F (0 C) or exceed
130F (54 C). The system must be designed and installed within the
guidelines of the UL/ULC Listed Design, Installation, Recharge, and
Maintenance Manual.

System Description
The restaurant fire suppression system is a pre-engineered, wet chemical, cartridge-operated, regulated pressure type with
a fixed nozzle agent distribution network. It is listed with Underwriters Laboratories, Inc. (UL/ULC). The system is capable of
automatic detection and actuation and/or remote manual actuation. Additional equipment is available for building fire alarm
panels connections, electrical shutdown and/or interface, and mechanical or electrical gas line shut-off applications.
The detection portion of the fire suppression system allows for automatic detection by means of specific temperature-rated
alloy type fusible links, which separate when the temperature exceeds the rating of the link, allowing the regulated release to
actuate.
A system owner's guide is available containing basic information pertaining to system operation and maintenance. A
detailed technical manual including system description, design, installation, recharge, and maintenance procedures is
available. The system is installed and serviced by authorized distributors that are trained by the manufacturer.
The basic system consists of an ANSUL AUTOMAN regulated release assembly which includes a regulated release
mechanism and a wet chemical storage tank housed within a single enclosure. Nozzles with blow-off caps, detectors,
cartridges, agent, fusible links, and pulley elbows are supplied in separate packages in the quantities needed for fire
suppression system arrangements.
Additional equipment includes remote manual pull station, mechanical and electrical gas valves, pressure switches, and
electrical switches for automatic equipment and gas line shut-off. Accessories can be added such as alarms, warning lights,
etc., to installations where required.
Additional tanks and corresponding equipment can be used in multiple arrangements to allow for larger hazard coverage.
Each tank is limited to a listed maximum amount of flow numbers.

Components
Wet Chemical Agent
Agent Tank
Regulated Release Mechanism
Regulated Actuator Assembly
Discharge Nozzles
Agent Distribution Hose
Flexible Conduit
Pull Station Assembly

Approvals
Applicable Standards: ULI listed under EX- 3470; ULC listed under CEX-747; meets requirements of NFPA 96 (Standard for
the Installation of Equipment for the Removal of Smoke and Grease-Laden Vapors from Commercial Cooking Equipment);
NFPA 17A (Standard on Wet Chemical Extinguishing Systems).

Ordering Information
Order all system components through your local authorized Ansul Distributor
ANSUL FIRE PROTECTION
MARINETTE, WI 54143-2542
715-735-7411