Вы находитесь на странице: 1из 32

ESTUDIO DE FLUJO DE POTENCIA

REVISIN 2

Proyecto:

PROYECTO CONSTANCIA
Cliente:
HUDBAY PERU S.A.C.

Reemplaza a:
Modificacin

Pg./tem

Documento

De Fecha:

COPIA CONTROLADA N
DISTRIBUCIN
Distribucin electrnica
SIEMENS IC LMV: J. Orozco; J. Snchez

DISTRIBUCIN
NOMBRE/SIGLA
J. OROZCO / IC LMV MS

FIRMA

FECHA

NOMBRE/SIGLA

07/11/14

J. SANCHEZ / IC LMV MS

Infraestructura & ciudades


IC LMV MS

Siemens

Elabor

E. LLANQUI

Revis

B. CORRALES

Aprob

J. OROZCO

FIRMA

FECHA
07/11/14

Fecha emisin:
07/11/2014
Cdigo Documento:

ESTUDIO DE FLUJO DE POTENCIA

(4) G69173-D1001-U106
V-2172-0504B-0234 Rev. 5

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 1 de 32

TABLA DE CONTENIDO

1.0. ASPECTOS GENERALES.............................................................................. 3


1.1. OBJETIVO ...................................................................................................... 3
1.2. ALCANCE ....................................................................................................... 4
2.0. SOFTWARE UTILIZADO. ............................................................................... 4
3.0. DESCRIPCIN DEL SISTEMA ELCTRICO. ................................................ 4
3.1. PARAMETROS ELECTRICOS. ...................................................................... 5
3.2. METODOLOGA. ............................................................................................ 7
3.3. CALCULO DE FLUJO DE POTENCIA. .......................................................... 7
4.0. ASUNCIONES................................................................................................. 7
5.0. RESULTADOS ................................................................................................ 9
5.1. ESCENARIO INICIAL - SIN COMPENSACION REACTIVA. ......................... 9
5.2. ESCENARIO INICIAL - CON COMPENSACION REACTIVA. ..................... 11
5.3. ESCENARIO 1 - SIN COMPENSACION REACTIVA. .................................. 13
5.4. ESCENARIO 1 - CON COMPENSACION REACTIVA. ................................ 15
5.5. ESCENARIO 2 - SIN COMPENSACION REACTIVA. .................................. 17
5.6. ESCENARIO 2 - CON COMPENSACION REACTIVA. ................................ 19
5.7. ESCENARIO 2 - CON COMPENSACION REACTIVA SALA 3220-LC-201
FUERA DE SERVICIO. ........................................................................................ 21
5.8. ESCENARIO CARGAS CRITICAS PRIORIDAD 1 Y 2. ............................... 23
5.9. ESCENARIO CARGAS CRITICAS PRIORIDAD 1 Y 3. ............................... 24
6.0. CONCLUSIONES.......................................................................................... 25
7.0. RECOMENDACIONES ................................................................................. 31
ANEXOS .............................................................................................................. 32

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 2 de 32

1.0. ASPECTOS GENERALES


1.1. OBJETIVO
El objetivo principal del presente estudio es alcanzar los lineamientos y
consideraciones para determinar las condiciones ms adecuadas de
operacin verificando las tensiones en las distintas barras de la red, flujos de
potencia activa y reactiva en todas las lneas, prdidas en los
transformadores, factor de potencia, etc. y evaluar las sobrecargas de los
componentes elctricos del sistema elctrico de la planta minera Constancia
en media y baja tensin
Simular en base a 04 escenarios posibles de operacin del sistema:
Escenario Inicial: Operacin normal de los transformadores de 75/125MVA,
45MVA y transformadores menores a 45MVA en tap 0 en el primario con y sin
compensacin reactiva en las barras 5761-LC-001-A y 5761-LC-001-B e
interruptor de acople abierto en ambos casos.
Escenario 1: Operacin normal de los transformadores 5721-TX-001 y 5721TX-002, Regulacin de taps de transformadores segn tablas de cargabilidad
de los transformadores del sistema elctrico de la planta minera Constancia
con y sin compensacin reactiva en las barras 5761-LC-001-A y 5761-LC001-B e interruptor de acople abierto en ambos casos.
Escenario

2:

Operacin

normal

de

transformador

5721-TX-001,

funcionamiento ONAF (125MVA) y falla en el transformador 5721-TX-002,


Regulacin de taps de transformadores segn tablas de cargabilidad de los
transformadores con y sin compensacin reactiva en las barras 5761-LC-001A y 5761-LC-001-B e interruptor de acople cerrado en ambos casos.
En el escenario 2 con compensacin reactiva, se tiene un tercer sub
escenario donde se deja fuera de servicio la subestacin 3220-LC-201
(Molinos 3221-ML-001-M1, Molinos 3221-ML-001-M2).
Escenario de cargas crticas: Operacin de acuerdo a lista de cargas
crticas y operacin de grupos electrgenos para prioridad 1-2 y prioridad 1-3
Sin operacin de los transformadores 5721-TX-001 y 5721-TX-002, y sin
compensacin reactiva en las barras 5761-LC-001-A y 5761-LC-001-B e
interruptor de acople cerrado en ambos casos.

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 3 de 32

1.2. ALCANCE
El mbito en el que se desarrollar el presente estudio abarca el sistema
elctrico de la planta minera Constancia, desde las barras principales en
220kV - hasta las cargas finales segn diagrama unifilar (2) G69173-D1001P135 Pagina 1 y 2.
El presente estudio realizado es para los escenarios segn el punto 1.1:

Para mxima demanda el cual est de acuerdo a la lista de


arrancadores 2172-5700-LST-004 Rev. 3. Constancia Project
Electrical Starter List (25-06-2013).

Para Lista de cargas crticas Emergency power load list.

2.0. SOFTWARE UTILIZADO.


El software utilizado para realizar el anlisis, simulaciones de flujo de carga y
cortocircuito es el ETAP Power Station versin 12 bajo entorno Windows, que es
una poderosa herramienta de ingeniera que permite simular redes elctricas
de potencia y de distribucin para facilitar su planificacin, diseo y operacin.
ETAP Power Station permite realizar en toda la red y de manera simultnea
estudios de cada de tensin, flujo de carga y corrientes de cortocircuito en
sistemas equilibrados o desequilibrados. Otra particularidad es que se pueden
trazar en pantalla los perfiles de tensin y de corrientes de cortocircuito. Las
funciones de ubicacin ptima de condensadores, de balance de carga de
sistemas elctricos, sugiere al ingeniero maneras para minimizar prdidas y
gracias a la funcin de crecimiento de carga es posible representar la carga de
las redes para los aos futuros.
3.0. DESCRIPCIN DEL SISTEMA ELCTRICO.
El suministro de energa hacia todas las instalaciones de la planta se obtendr
para un escenario de mxima demanda a partir de la barra constancia 220kV,
conectada a la red equivalente del SEIN.
Para el equivalente de red - SEIN al 2022, Subestacin - Constancia 220 kV, la
potencia de cortocircuito trifsico (Aporte de la Red) es 936.65 MVA y la potencia
de cortocircuito monofsico (Aporte de la Red) es 236.14 MVA (Fuente: Estudio
de Pre-operatividad del Proyecto Minero Constancia CESEL Ingenieros doc.
CSL-119500-6-MD-001 Rev. B; Al ao 2022 cuadros 7.11-7.13 y Reporte de
Unifilares Cortocircuito al 2022 con Proyecto Pg.228 y 230).

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 4 de 32

Para el equivalente de red - SEIN al 2015, Subestacin - Constancia 220 kV, la


potencia de cortocircuito trifsico (Aporte de la Red) es 619.95 MVA y la potencia
de cortocircuito monofsico (Aporte de la Red) es 185.36 MVA (Fuente: Estudio
de Operatividad Suministro Elctrico en 220kV Proyecto Minero Constancia
EdP Electricidad de Potencia S.A.C, Volumen: Anlisis de Flujos de Potencia y
Cortocircuito al ao 2015, EDP-049-14 Rev. C; Anexo N6 Pg. 71-72).
As mismo se considera dos transformadores de 75/125 MVA, ONAN/ONAF
220/22.9kV, los que alimentarn a los interruptores principales de la SS.EE
elctrica de 5761-SS-001 (Procces Plant 22.9 kV Sub-Station) de las barras
5761-LC-001A y 5761-LC-001B respectivamente en 22.9kV. Estas dos barras
estarn conectadas por un interruptor de acoplamiento, el que en condiciones
normales debe estar abierto y en condicin de falla de un transformador de
75/125 MVA estar cerrado.
Los transformadores mostrados en el Anexo 1 - Base de datos de los
transformadores, presentan regulacin de tap segn los escenarios inicial, 1 y 2.
Los transformadores de 75/125 MVA operan sus taps con regulacin automtica
bajo carga en el primario y los transformadores de 45MVA operan con tensin
secundaria en 1.0 P.U bajo carga.
3.1. PARAMETROS ELECTRICOS.
En todos los escenarios analizados se considera lo siguiente:

Datos tcnicos de los transformadores segn hojas tcnicas de equipos


(Ver anexo 01).

Datos tcnicos de los generadores segn hoja tcnica de equipos. (Ver


anexo 02).

Datos de potencia de acuerdo a la lista de arrancadores 2172-5700-LST004 Rev. 3. Constancia Project Electrical Starter List (25-06-2013). (Ver
anexo 03).

Datos de potencia de acuerdo a la lista de cargas criticas Emergency


power load list. (Ver anexo 04).

Los datos de estado (Continuous, Intermittent, Spare) de las cargas


elctricas estn de acuerdo a Memoria de Clculo de Mxima Demanda
(4) G69173-D1001-U109.

Para las potencias de facilidades se consideran equivalentes a partir del


Informe de Flujo de Carga y Coordinacin de las Protecciones Diseo,
(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 5 de 32

Suministro y Construccin de Lneas Areas 22.9kV Rev. 0 elaborado por


CAMESA (CAM-136-010-EL-AS-02 ), donde:
o

Salida +H31 =HZ71 (840) Mina y Taller (plano (1) G69173-D1001P135 (1 de 2) La mxima demanda proyectada es 2.853 MW con
un factor de potencia de 0.95 en rgimen de operacin normal, sin
aporte al cortocircuito al sistema elctrico.

Salida +H30 =HZ71 (820) Agua Recuperada (plano (1) G69173D1001-P135 (1 de 2) La mxima demanda proyectada es 6.048
MW con un factor de potencia de 0.95 en rgimen de operacin
normal, sin aporte al cortocircuito al sistema elctrico.

Salida +H08 =HZ71 (800) Campamento y Agua fresca (plano (1)


G69173-D1001-P135 (2 de 2) La mxima demanda proyectada es
3.804 MW con un factor de potencia de 0.95 en rgimen de
operacin normal, sin aporte al cortocircuito al sistema elctrico.

Para las potencias de las cargas de la Sala 900 se considera la


Informacin alcanzada por Ausenco:
o

Proyecto Constancia, Almacn de Reactivos - Esquema Unifilar


Elctrico y Cuadro de Cargas Elctricas 2172-2530-06-A-04-05
Rev.A elaborado por Tcnicas Metlicas Ingenieros S.A.C.

Proyecto Constancia, Taller/Almacn - Esquema Unifilar Elctrico y


Cuadro

de

Cargas

Elctricas

2172-2530-05-A-04-05

Rev.A

elaborado por Tcnicas Metlicas Ingenieros S.A.C


o

Las caractersticas de los Transformadores 5130-TX-912 y 5130TX-913 son acorde al Diagrama Unifilar General Constancia Media
y Baja Tensin (1)G69173-D1001-P135_Rev A2.

En el escenario inicial todos los transformadores estn regulados en tap 0.

En los escenarios 1 y 2 los taps de los transformadores de 75/125MVA


tienen regulacin automtica y los transformadores de 45MVA operan con
tensin secundaria bajo carga (la regulacin de tensin en las barras de
13.8kV es 1.0 P.U respectivamente). Los taps de los transformadores
estn regulados segn tablas 6, 8, 10 y 12.

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 6 de 32

3.2. METODOLOGA.
Las simulaciones de flujo de potencia nos permiten observar el
comportamiento del sistema en estado estacionario determinndose los
niveles de tensiones en las barras, la distribucin de los flujos de potencia
activa y reactiva en cables y transformadores de distribucin.
Para evaluar los resultados de los flujos de potencia se ha considerado como
criterio de calidad y confiabilidad la capacidad del sistema para satisfacer las
siguientes condiciones de niveles de tensiones admisibles en barra:

Operacin Normal: 5% Vnom.

Operacin ante Contingencias: 7.5% Vnom.

3.3. CALCULO DE FLUJO DE POTENCIA.


El mtodo utilizado por el software ETAP Power Station para realizar los
clculos es de Newton Raphson.
Se espera como resultado del flujo de carga, la visualizacin de los
parmetros elctricos principales en la generacin, transformacin,
transmisin y cargas finales tales como potencia activa, potencia reactiva,
potencia aparente, factor de potencia, tensiones en barras, corrientes en
barras, cargas y prdidas en todo el sistema elctrico.
El perfil de tensin hallado segn flujo de carga se presenta en Tablas 1, 3, 5,
7, 9, 11, 13, 15 y 17.
4.0. ASUNCIONES

Los datos de estado (Continuous, Intermittent, Spare) es de acuerdo a


Memoria de Clculo de Mxima Demanda (4) G69173-D1001-U109.

Las cargas de los servicios auxiliares en baja tensin se modelan como


una carga equivalente, que en condiciones normales opera a un 80% de la
potencia nominal del transformador de servicios auxiliares.

Los valores de compensacin reactiva y filtro de armnicos para este


estudio son segn memoria de clculo de compensacin reactiva y filtro de
armnicos (4) G69173-D1001-U120.

Los datos de entrada de los transformadores en AT/MT/BT son de acuerdo


a Hojas Tcnicas de equipos mostrados en Anexo 1.

En la simulacin de flujo de carga en estado estacionario, No se considera


los transformadores del sistema de arranque de los Molinos SAG (3221(4)G69173-D1001-U106_2.doc

Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 7 de 32

TX-203, 3221-TX-204, 3223-TX-253, 3223-TX-254), por ser parte de un


sistema de regeneracin.

Este estudio de flujo de carga no contempla el arranque de motores para


seleccin de transformadores.

El factor de asimetra X/R, impedancias de cortocircuito y las prdidas de


los transformadores de potencia 75/125MVA, transformadores menores a
75 MVA fueron ingresados al modelo del ETAP, segn librera del software
ETAP, norma IEC 60076-5, Hoja de datos de transformadores (4)G69173D1001-M118 y AREVA CH.5 Equivalent circuits and parameters of power
system plant (Ver anexo 1).

Los conductores de media tensin y baja tensin son ingresados al modelo


de ETAP de acuerdo a la memoria de clculo de conductores de media
tensin (4) G69173-D1001-U110 y memoria de clculo de conductores de
baja tensin (4) G69173-D1001-U117.

La lista de cargas criticas Emergency power load list fueron referenciadas


a la lista de arrancadores 2172-5700-LST-004 Rev. 3. Constancia Project
Electrical Starter List (25-06-2013), prevaleciendo este ltimo respecto a
las datos elctricos de las cargas en mencin.

La regulacin de Taps de los transformadores para los escenarios de


cargas crticas, se mantienen de acuerdo a la regulacin de taps segn
escenarios 1 y 2 descritos en el punto 1.1.

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 8 de 32

5.0. RESULTADOS
5.1. ESCENARIO INICIAL - SIN COMPENSACION REACTIVA.
Tabla 1: Resultados del nivel de tensin en barras principales en operacin.
TAG
3100-DB-101
3100-LC-101
3100-MC-102
3100-RU-100
3210-DB-105
3210-MC-151
3220-DB-201
3220-DB-202
3220-DB-206
3220-DB-206
3220-LC-201
3220-LC-251
3220-MC-205-1
3220-MC-205-2
3220-MC-255-1
3220-MC-255-2
3220-RU-205
3220-RU-255
3220-SB-205
3220-SB-255
3250-DB-301
3250-LC-301
3250-MC-302-1
3250-MC-302-2
3250-MC-303-1
3250-MC-303-2
3250-MC-304-1
3250-MC-304-2
3250-RU-301
3250-SB-302
3250-SB-303
3250-SB-304
3250-SB-501
3260-DB-401
3260-LC-401
3260-MC-402-1
3260-MC-402-2
3260-RU-400
3260-SB-402
3280-DB-501
3280-MC-501-1
3280-MC-501-2
3290-DB-601
3290-LC-601
3290-MC-602-1
3290-MC-602-2
3290-RU-600
3290-SB-602
3300-DB-701
3300-MC-701-1
3300-MC-701-2
3300-RU-700
3300-SB-701
5130-DB-901
5130-MC-912
5761-DB-001
5761-LC-001-A
5761-LC-001-B
CONSTANCIA 220kV

CUADRO DE DEMANDA MXIMA Y NIVEL DE TENSIN


kvar Loading
Nominal (kV)
Voltage (%)
kW Loading
0.4
88.93
134
83.329
4.16
91.34
1470
684
0.48
91.63
740
405
22.9
94.26
2233
1212
0.4
89.85
137
85.057
0.48
92.58
567
265
0.4
95.53
310
192
0.4
88.6
133
82.702
0.4
88.56
133
82.636
0.4
88.56
133
82.636
13.8
98.32
35078
21669
13.8
98.25
35140
21487
0.48
91.28
898
540
0.48
91.28
965
626
0.48
91.22
1000
598
0.48
91.22
861
558
22.9
94.29
1879
1273
22.9
94.21
1878
1263
0.48
91.28
1863
1166
0.48
91.22
1861
1157
0.4
88.29
312
7.637
4.16
91.25
2479
1558
0.48
90.08
908
482
0.48
90.08
934
514
0.48
90.07
1385
655
0.48
90.07
1264
738
0.48
89.62
1159
696
0.48
89.62
1077
696
22.9
94.18
9327
6024
0.48
90.08
1842
996
0.48
90.07
2649
1393
0.48
89.62
2236
1392
0.48
91.02
1702
905
0.4
89.86
161
7.909
4.16
91.06
3162
2028
0.48
91.93
500
159
0.48
91.93
552
266
22.9
94.23
3187
2226
0.48
91.93
1052
425
0.4
88.34
133
82.221
0.48
91.02
868
461
0.48
91.02
834
444
0.4
88.63
134
82.767
4.16
91.76
7968
3118
0.48
91.32
675
439
0.48
91.32
317
200
22.9
94.25
8999
4339
0.48
91.32
992
639
0.4
88.02
132
81.632
0.48
90.67
853
560
0.48
90.67
717
472
22.9
94.31
1591
1136
0.48
90.67
1571
1032
0.4
95.57
87.509
42.383
0.46
97.04
540
265
0.4
91.58
285
177
22.9
94.25
54649
37264
22.9
94.33
57629
36457
220
100
112520
87369

Amp Loading
256.7
246.4
1107
67.94
259.4
812.4
551.5
255.8
255.7
255.7
1754
1754
1381
1515
1537
1354
60.69
60.57
2896
2890
509.8
445.3
1373
1424
2045
1955
1814
1721
297.2
2797
3996
3535
2548
259.4
572.5
686.8
801.2
104
1484
255
1299
1249
255.9
1294
1061
493
267.2
1554
254.1
1354
1139
52.25
2493
146.8
778
528.7
1769
1823
373.9

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 9 de 32

Tabla 2: Cargabilidad de los Transformadores.


CARGABILIDAD DE TRANSFORMADORES
TAG

Relacin de
Transformacin
(kV)

Potencia
Aparente
(kVA)

kW
Flow

kvar
Flow

Amp
Flow

% PF

3100-TX-101

22.9 / 4.16 kV

2500 kVA

1485

771

44.75

88.75

66.9

2.9

14.505

87.03

3100-TX-102

22.9 / 0.48 kV

1500 kVA

748

441

23.21

86.15

57.9

2.32

5.574

33.444

3100-TX-103

0.48 / 0.4 kV

250 kVA

137

87.541 213.9

84.31

65.1

2.6

2.808

4.212

3210-TX-151

22.9 / 0.48 kV

1500 kVA

570

17.03

89.55

31.9

1.56

18

3210-TX-152

0.48 / 0.4 kV

250 kVA

140

89.356 216.1

84.31

66.5

2.62

2.866

4.299

3220-TX-201

22.9 / 13.8 kV

45000 kVA

35192

25565

1163

80.9

96.7

4.13

85.728

3858

3220-TX-202

13.8 / 0.4 kV

500 kVA

317

202

15.99

84.31

75.1

2.79

6.48

9.719

3220-TX-205

22.9 / 0.48 kV

4000 kVA

1879

1273

60.69

82.8

56.7

2.7

11.849

101

284

%
kW
% Loading Voltage
Losses
Drop

Taps
kvar
Regulation
Losses
Prim. (%)

3220-TX-206

0.48 / 0.4 kV

250 kVA

136

86.882 213.1

84.31

64.6

2.59

2.787

4.18

3220-TX-251

22.9 / 13.8 kV

45000 kVA

35256

25383

1163

81.15

96.5

4.16

85.664

3855

3220-TX-252

13.8 / 0.4 kV

500 kVA

379

19.02

16.14

99.87

75.8

1.81

6.605

9.907

3220-TX-255

22.9 / 0.48 kV

4000 kVA

1878

1263

60.57

82.97

56.6

2.68

11.803

100

86.813 213.1

3220-TX-256

0.48 / 0.4 kV

250 kVA

136

84.31

64.6

2.59

2.784

4.177

3250-TX-301

22.9 / 4.16 kV

5000 kVA

2497

1702

80.89

82.62

60.4

2.88

16.84

143

3250-TX-303

22.9 / 0.48 kV

4000 kVA

2686

1605

83.77

85.85

78.2

3.43

22.572

192

3250-TX-304

22.9 / 0.48 kV

3500 kVA

2270

1583

74.09

82.03

79.1

3.79

20.179

172

3250-TX-305

0.48 / 0.4 kV

500 kVA

317

15.94

424.8

99.87

63.5

1.65

5.535

8.303

3252-TX-302

22.9 / 0.48 kV

3000 kVA

1873

1134

58.62

85.55

73

3.44

20.735

124

3260-TX-401

22.9 / 4.16 kV

6000 kVA

3187

2226

104

81.98

64.8

3.13

23.198

197

3260-TX-402

22.9 / 0.48 kV

2000 kVA

1062

474

31.11

91.33

58.2

1.99

7.511

45.068

3260-TX-403

0.48 / 0.4 kV

250 kVA

164

12.209 216.2

99.72

65.8

1.74

2.867

4.3

3280-TX-501

22.9 / 0.48 kV

3000 kVA

1718

53.4

86.11

66.5

2.91

12.23

104

3280-TX-502

0.48 / 0.4 kV

250 kVA

135

86.376 212.5

84.31

64.3

2.58

2.77

4.156

3290-TX-601

22.9 / 4.16 kV

14000 kVA

7996

3647

235.1

90.98

62.8

2.47

26.366

527

3290-TX-602

22.9 / 0.48 kV

2000 kVA

1002

691

32.57

82.32

60.9

2.65

8.232

49.391

3290-TX-603

0.48 / 0.4 kV

250 kVA

136

86.951 213.2

84.31

64.7

2.59

2.789

4.183

3300-TX-701

22.9 / 0.48 kV

3000 kVA

1591

52.25

81.39

65.1

3.35

16.477

98.86

3300-TX-702

0.48 / 0.4 kV

250 kVA

134

85.758 211.8

84.31

63.8

2.57

2.751

4.126

5130-TX-912

22.9 / 0.48 kV

2000 kVA

543

16.31

88.98

30.5

1.19

2.15

12.897

5130-TX-913

0.46 / 0.4 kV

250 kVA

88.428 43.761 127.7

89.63

39.5

1.41

0.919

1.378

5761-TX-010

22.9 / 0.4 kV

500 kVA

291

186

9.235

84.31

69

2.67

5.954

8.931

220 kV

75000 kVA

57754

43484

189.7

79.89

57.8

5.66

122

7019

5721-TX-001

22.9 kV

75000 kVA

57632

36465

1823

84.51

54.6

5.66

122

7019

13.2 kV

15000 kVA

32.65

5.66

122

7019

220 kV

75000 kVA

54766

43885

184.2

78.04

56.1

5.74

115

6615

22.9 kV

75000 kVA

54651

37270

1769

82.62

52.9

5.74

115

6615

13.2 kV

15000 kVA

-99.65

5.74

115

6615

5721-TX-002

1015

1136

278

Fuente: Elaborado por BISA

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 10 de 32

5.2. ESCENARIO INICIAL - CON COMPENSACION REACTIVA.


Tabla 3: Resultados del nivel de tensin en barras principales en operacin.
TAG
3100-DB-101
3100-LC-101
3100-MC-102
3100-RU-100
3210-DB-105
3210-MC-151
3220-DB-201
3220-DB-202
3220-DB-206
3220-DB-206
3220-LC-201
3220-LC-251
3220-MC-205-1
3220-MC-205-2
3220-MC-255-1
3220-MC-255-2
3220-RU-205
3220-RU-255
3220-SB-205
3220-SB-255
3250-DB-301
3250-LC-301
3250-MC-302-1
3250-MC-302-2
3250-MC-303-1
3250-MC-303-2
3250-MC-304-1
3250-MC-304-2
3250-RU-301
3250-SB-302
3250-SB-303
3250-SB-304
3250-SB-501
3260-DB-401
3260-LC-401
3260-MC-402-1
3260-MC-402-2
3260-RU-400
3260-SB-402
3280-DB-501
3280-MC-501-1
3280-MC-501-2
3290-DB-601
3290-LC-601
3290-MC-602-1
3290-MC-602-2
3290-RU-600
3290-SB-602
3300-DB-701
3300-MC-701-1
3300-MC-701-2
3300-RU-700
3300-SB-701
5130-DB-901
5130-MC-912
5761-DB-001
5761-LC-001-A
5761-LC-001-B
CONSTANCIA 220kV

CUADRO DE DEMANDA MXIMA Y NIVEL DE TENSIN


kvar Loading
Nominal (kV)
Voltage (%)
kW Loading
0.4
92.13
144
89.423
4.16
94.75
1470
684
0.48
94.92
767
423
22.9
97.56
2258
1223
0.4
93.05
147
91.228
0.48
95.88
583
275
0.4
97.01
320
198
0.4
91.84
143
88.873
0.4
91.83
143
88.838
0.4
91.83
143
88.838
13.8
99.85
35088
21675
13.8
99.8
35152
21487
0.48
94.63
912
550
0.48
94.63
990
643
0.48
94.58
1025
616
0.48
94.58
876
568
22.9
97.59
1918
1297
22.9
97.53
1917
1288
0.48
94.63
1902
1193
0.48
94.58
1901
1184
0.4
91.67
336
8.232
4.16
94.56
2577
1621
0.48
93.53
914
486
0.48
93.53
941
519
0.48
93.52
1411
658
0.48
93.52
1273
744
0.48
93.12
1158
695
0.48
93.12
1075
696
22.9
97.5
9466
6071
0.48
93.53
1855
1005
0.48
93.52
2685
1402
0.48
93.12
2233
1391
0.48
94.39
1734
927
0.4
93.15
173
8.498
4.16
94.5
3162
2027
0.48
95.29
515
162
0.48
95.29
559
270
22.9
97.55
3185
2212
0.48
95.29
1074
432
0.4
91.61
143
88.415
0.48
94.39
892
477
0.48
94.39
842
450
0.4
91.86
143
88.905
4.16
95.16
7968
3118
0.48
94.65
693
451
0.48
94.65
328
207
22.9
97.55
9026
4319
0.48
94.65
1021
657
0.4
91.29
142
87.802
0.48
94.04
873
574
0.48
94.04
726
479
22.9
97.61
1618
1153
0.48
94.04
1599
1053
0.4
98.97
92.588
44.842
0.46
100.47
564
277
0.4
94.8
306
189
22.9
97.57
55077
37118
22.9
97.63
58299
36401
220
100
113547
38120

Amp Loading
266
237.5
1109
66.36
268.6
809.4
560.1
265.1
265.1
265.1
1728
1727
1354
1500
1521
1328
59.82
59.7
2854
2848
529.3
446.9
1332
1382
2003
1897
1744
1654
290.8
2714
3895
3398
2506
268.9
551.6
681.1
784
100.2
1461
264.4
1289
1217
265.2
1248
1051
492.6
258.6
1544
263.5
1336
1113
51.33
2449
150
785.3
547.3
1716
1775
314.3

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 11 de 32

Tabla 4: Cargabilidad de los Transformadores.


CARGABILIDAD DE TRANSFORMADORES

TAG

Relacin de
Transformacin
(kV)

Potencia
Aparente
(kVA)

kW
Flow

kvar
Flow

Amp
Flow

% PF

3100-TX-101

22.9 / 4.16 kV

2500 kVA

1484

765

43.14

88.89

66.8

2.79

13.477

80.86

3100-TX-102

22.9 / 0.48 kV

1500 kVA

774

458

23.25

86.07

60

2.33

5.593

33.556

3100-TX-103

0.48 / 0.4 kV

250 kVA

147

93.943 221.6

84.31

69.9

2.69

3.013

4.52

3210-TX-151

22.9 / 0.48 kV

1500 kVA

587

16.97

89.42

32.8

1.56

2.978

17.866

294

%
Taps
kW
kvar
% Loading Voltage
Regulation
Losses Losses
Drop
Prim. (%)

3210-TX-152

0.48 / 0.4 kV

250 kVA

150

95.839 223.9

84.31

71.3

2.72

3.074

4.611

3220-TX-201

22.9 / 13.8 kV

45000 kVA

35195

25287

1120

81.21

96.3

2.35

79.434

3575

3220-TX-202

13.8 / 0.4 kV

500 kVA

327

208

16.24

84.31

77.5

2.83

6.682

10.024

3220-TX-205

22.9 / 0.48 kV

4000 kVA

1918

1297

3220-TX-206

0.48 / 0.4 kV

250 kVA

146

3220-TX-251

22.9 / 13.8 kV

45000 kVA

35260

3220-TX-252

13.8 / 0.4 kV

500 kVA

391

3220-TX-255

22.9 / 0.48 kV

4000 kVA

1917

3220-TX-256

0.48 / 0.4 kV

250 kVA

146

3250-TX-301

22.9 / 4.16 kV

5000 kVA

2595

1766

3250-TX-303

22.9 / 0.48 kV

4000 kVA

2720

3250-TX-304

22.9 / 0.48 kV

3500 kVA

3250-TX-305

0.48 / 0.4 kV

500 kVA

3252-TX-302

22.9 / 0.48 kV

3260-TX-401
3260-TX-402

59.82

82.84

57.9

2.66

11.511

97.839

93.365 220.9

84.31

69.5

2.68

2.995

4.492

25097

1119

81.47

96.2

2.38

79.335

3570

19.624 16.39

99.87

78.2

1.84

6.814

10.222

59.7

83.02

57.7

2.64

11.466

97.465

93.328 220.9

84.31

69.4

2.68

2.993

4.49

81.18

82.67

62.8

2.89

16.959

144

1603

81.64

86.16

78.9

3.32

21.443

182

2265

1567

71.22

82.24

78.7

3.64

18.649

159

342

17.182

441

99.87

68.5

1.72

5.967

8.95

3000 kVA

1884

1135

56.88

85.67

73.3

3.34

19.526

117

22.9 / 4.16 kV

6000 kVA

3185

2211

100.2

82.14

64.6

3.01

21.536

183

22.9 / 0.48 kV

2000 kVA

1084

479

30.63

91.45

59.3

1.95

7.279

43.675

3260-TX-403

0.48 / 0.4 kV

250 kVA

176

13.118 224.1

99.72

70.8

1.8

3.08

4.62

3280-TX-501

22.9 / 0.48 kV

3000 kVA

1750

52.53

86.12

67.7

2.86

11.836

101

92.884 220.4

1287

1033

3280-TX-502

0.48 / 0.4 kV

250 kVA

146

84.31

69.1

2.67

2.979

4.469

3290-TX-601

22.9 / 4.16 kV

14000 kVA

7994

3610

226.7

91.14

62.7

2.37

24.511

490

3290-TX-602

22.9 / 0.48 kV

2000 kVA

1032

709

32.36

82.41

62.6

2.63

8.123

48.741

3290-TX-603

0.48 / 0.4 kV

250 kVA

146

93.398

221

84.31

69.5

2.68

2.996

4.494

3300-TX-701

22.9 / 0.48 kV

3000 kVA

1618

1153

51.33

81.43

66.2

3.3

15.901

95.404

3300-TX-702

0.48 / 0.4 kV

250 kVA

145

92.24

219.6

84.31

68.6

2.67

2.959

4.438

5130-TX-912

22.9 / 0.48 kV

2000 kVA

567

291

16.46

88.96

31.9

1.2

2.19

13.138

5130-TX-913

0.46 / 0.4 kV

250 kVA

93.547 46.281 130.5

89.63

41.7

1.44

0.959

1.438

5761-TX-010

22.9 / 0.4 kV

500 kVA

312

199

9.56

84.31

74

2.77

6.381

9.571

220 kV

75000 kVA

58389

18927

161.1

95.13

49.1

2.37

87.858

5060

22.9 kV

75000 kVA

58301

13867

1547

97.29

47.9

2.37

87.858

5060

13.2 kV

15000 kVA

-3.86

2.37

87.858

5060

5721-TX-001

5721-TX-002

220 kV

75000 kVA

55159

19192

153.3

94.45

46.7

2.43

79.541

4581

22.9 kV

75000 kVA

55079

14612

1472

96.66

45.6

2.43

79.541

4581

13.2 kV

15000 kVA

-10.41

2.43

79.541

4581

Fuente: Elaborado por BISA

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 12 de 32

5.3. ESCENARIO 1 - SIN COMPENSACION REACTIVA.


Tabla 5: Resultados del nivel de tensin en barras principales en operacin.
TAG
3100-DB-101
3100-LC-101
3100-MC-102
3100-RU-100
3210-DB-105
3210-MC-151
3220-DB-201
3220-DB-202
3220-DB-206
3220-DB-206
3220-LC-201
3220-LC-251
3220-MC-205-1
3220-MC-205-2
3220-MC-255-1
3220-MC-255-2
3220-RU-205
3220-RU-255
3220-SB-205
3220-SB-255
3250-DB-301
3250-LC-301
3250-MC-302-1
3250-MC-302-2
3250-MC-303-1
3250-MC-303-2
3250-MC-304-1
3250-MC-304-2
3250-RU-301
3250-SB-302
3250-SB-303
3250-SB-304
3250-SB-501
3260-DB-401
3260-LC-401
3260-MC-402-1
3260-MC-402-2
3260-RU-400
3260-SB-402
3280-DB-501
3280-MC-501-1
3280-MC-501-2
3290-DB-601
3290-LC-601
3290-MC-602-1
3290-MC-602-2
3290-RU-600
3290-SB-602
3300-DB-701
3300-MC-701-1
3300-MC-701-2
3300-RU-700
3300-SB-701
5130-DB-901
5130-MC-912
5761-DB-001
5761-LC-001-A
5761-LC-001-B
CONSTANCIA 220kV

CUADRO DE DEMANDA MXIMA Y NIVEL DE TENSIN


kvar Loading
Nominal (kV)
Voltage (%)
kW Loading
0.4
99.27
168
104
4.16
99.75
1470
684
0.48
99.73
816
454
22.9
99.86
2306
1248
0.4
100.23
171
106
0.48
100.7
618
297
0.4
99.24
335
208
0.4
99.07
167
103
0.4
99.06
167
103
0.4
99.06
167
103
13.8
99.59
35103
21685
13.8
100.03
35174
21488
0.48
99.53
934
565
0.48
99.53
1037
674
0.48
99.48
1073
647
0.48
99.48
898
584
22.9
99.89
1987
1341
22.9
99.83
1986
1331
0.48
99.53
1971
1240
0.48
99.48
1971
1231
0.4
99.06
392
9.612
4.16
99.4
2728
1717
0.48
98.55
924
494
0.48
98.55
951
525
0.48
98.53
1472
664
0.48
98.53
1287
752
0.48
98.23
1156
694
0.48
98.23
1074
695
22.9
99.81
9700
6157
0.48
98.55
1876
1019
0.48
98.53
2759
1416
0.48
98.23
2230
1389
0.48
99.29
1792
966
0.4
100.44
202
9.881
4.16
99.52
3162
2027
0.48
100.19
547
166
0.48
100.19
571
277
22.9
99.85
3182
2193
0.48
100.19
1118
444
0.4
98.83
166
103
0.48
99.29
937
508
0.48
99.29
855
458
0.4
99.05
167
103
4.16
100.15
7967
3118
0.48
99.5
730
474
0.48
99.5
345
218
22.9
99.85
9076
4305
0.48
99.5
1075
691
0.4
98.52
165
102
0.48
98.96
911
602
0.48
98.96
740
489
22.9
99.9
1669
1188
0.48
98.96
1650
1091
0.4
101.33
96.222
46.602
0.46
102.85
581
286
0.4
99.52
337
209
22.9
99.87
55589
37152
22.9
99.92
58879
36474
220
100
114690
86111

Amp Loading
286.6
225.5
1126
66.2
289.3
818.9
573
286
286
286
1733
1724
1319
1495
1514
1295
60.5
60.39
2814
2809
571.9
450
1279
1326
1971
1820
1651
1566
290.2
2605
3786
3217
2466
289.9
523.7
686.7
761.6
97.58
1444
285.3
1291
1175
285.9
1186
1052
493.3
253.6
1545
284.4
1327
1078
51.71
2405
152.3
790.7
574.6
1688
1748
376.4

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 13 de 32

Tabla 6: Cargabilidad de los Transformadores.


CARGABILIDAD DE TRANSFORMADORES

TAG

Relacin de
Transformacin
(kV)

Potencia
Aparente
(kVA)

kW
Flow

kvar
Flow

3100-TX-101

22.9 / 4.16 kV

2500 kVA

1482

757

42.02 89.06

66.6

0.08

12.156

72.938

-2.5

3100-TX-102

22.9 / 0.48 kV

1500 kVA

824

491

24.21 85.89

63.9

0.18

5.766

34.593

-2.5

3100-TX-103

0.48 / 0.4 kV

250 kVA

171

109

244.9 84.31

81.1

0.34

3.498

5.247

-2.5

3210-TX-151

22.9 / 0.48 kV

1500 kVA

622

316

17.61 89.14

34.9

0.97

3.048

18.29

-2.5

250 kVA

174

111

247.3 84.31

82.7

0.35

3.567

5.35

-2.5

1092

81.4

96.1

0.2

75.519

3398

Automtico

17.03 84.31

81.1

0.34

6.993

10.49

-2.5

Amp
Flow

%
Taps
kW
kvar
% PF % Loading Voltage
Regulation
Losses Losses
Drop
Prim. (%)

3210-TX-152

0.48 / 0.4 kV

3220-TX-201

22.9 / 13.8 kV

3220-TX-202

13.8 / 0.4 kV

500 kVA

342

218

3220-TX-205

22.9 / 0.48 kV

4000 kVA

1987

1341

60.5

82.89

59.9

0.06

11.192

95.129

-2.5

3220-TX-206

0.48 / 0.4 kV

250 kVA

170

109

244.4 84.31

80.8

0.34

3.484

5.226

-2.5

3220-TX-251

22.9 / 13.8 kV

96

0.31

75.413

3394

Automtico

3220-TX-252

13.8 / 0.4 kV

500 kVA

413

82.7

0.68

7.201

10.802

-2.5

3220-TX-255

22.9 / 0.48 kV

4000 kVA

1986

1331

60.39 83.07

59.8

0.05

11.152

94.793

-2.5

3220-TX-256

0.48 / 0.4 kV

250 kVA

170

109

244.4 84.31

80.8

0.34

3.483

5.225

-2.5

3250-TX-301

22.9 / 4.16 kV

5000 kVA

2746

1865

83.85 82.73

66.4

0.35

17.201

146

-2.5

3250-TX-303

22.9 / 0.48 kV

4000 kVA

2793

1606

81.39 86.69

80.5

0.63

20.259

172

-2.5

3250-TX-304

22.9 / 0.48 kV

3500 kVA

2259

1547

69.16

78.2

0.88

16.715

142

-2.5

3250-TX-305

0.48 / 0.4 kV

500 kVA

399

80

0.67

6.967

10.45

-2.5

3252-TX-302

22.9 / 0.48 kV

3000 kVA

1902

1138

85.81

73.9

0.64

17.993

108

-2.5

3260-TX-401

22.9 / 4.16 kV

6000 kVA

3182

2193

97.58 82.34

64.4

0.29

19.411

165

-2.5

3260-TX-402

22.9 / 0.48 kV

2000 kVA

1128

490

31.04 91.71

61.5

0.65

7.106

42.637

-2.5

3260-TX-403

0.48 / 0.4 kV

250 kVA

205

15.252 247.8 99.72

82.3

0.62

3.581

5.372

-2.5

3280-TX-501

22.9 / 0.48 kV

3000 kVA

1808

11.462

97.427

-2.5

45000 kVA 35206 25121

45000 kVA 35278 24921

1091

81.68

20.738 17.29 99.87

82.5

20.062 488.8 99.87


56

1068

53.02 86.09

70

0.27

3280-TX-502

0.48 / 0.4 kV

250 kVA

170

108

243.9 84.31

80.4

0.34

3.468

5.202

-2.5

3290-TX-601

22.9 / 4.16 kV

14000 kVA

7991

3562

220.9 91.34

62.5

0.32

22.127

443

-2.5

3290-TX-602

22.9 / 0.48 kV

2000 kVA

1085

743

33.21 82.52

65.8

0.07

8.136

48.817

-2.5

3290-TX-603

0.48 / 0.4 kV

250 kVA

170

109

244.4 84.31

80.8

0.34

3.483

5.224

-2.5

3300-TX-701

22.9 / 0.48 kV

3000 kVA

1669

1188

51.71 81.47

68.3

0.68

15.338

92.027

-2.5

3300-TX-702

0.48 / 0.4 kV

250 kVA

168

107

243.1 84.31

79.9

0.34

3.446

5.169

-2.5

5130-TX-912

22.9 / 0.48 kV

2000 kVA

584

300

16.57 88.94

32.8

1.21

2.22

13.32

-2.5

5130-TX-913

0.46 / 0.4 kV

250 kVA

97.21

48.084 132.4 89.63

43.4

1.46

0.988

1.482

5761-TX-010

22.9 / 0.4 kV

500 kVA

344

5721-TX-001

5721-TX-002

10.29 84.31

81.6

0.35

7.033

10.549

220 kV

75000 kVA 58993 42933

191.5 80.85

58.4

0.07

112

6452

Automtico

22.9 kV

75000 kVA 58881 36480

1748

85.01

55.4

0.07

112

6452

13.2 kV

15000 kVA

8.02

0.07

112

6452

219

220 kV

75000 kVA 55696 43178

184.9 79.03

56.4

0.12

105

6020

22.9 kV

75000 kVA 55592 37158

1688

83.14

53.5

0.12

105

6020

13.2 kV

15000 kVA

22.87

0.12

105

6020

Automtico

Fuente: Elaborado por BISA

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 14 de 32

5.4. ESCENARIO 1 - CON COMPENSACION REACTIVA.


Tabla 7: Resultados del nivel de tensin en barras principales en operacin.
TAG
3100-DB-101
3100-LC-101
3100-MC-102
3100-RU-100
3210-DB-105
3210-MC-151
3220-DB-201
3220-DB-202
3220-DB-206
3220-DB-206
3220-LC-201
3220-LC-251
3220-MC-205-1
3220-MC-205-2
3220-MC-255-1
3220-MC-255-2
3220-RU-205
3220-RU-255
3220-SB-205
3220-SB-255
3250-DB-301
3250-LC-301
3250-MC-302-1
3250-MC-302-2
3250-MC-303-1
3250-MC-303-2
3250-MC-304-1
3250-MC-304-2
3250-RU-301
3250-SB-302
3250-SB-303
3250-SB-304
3250-SB-501
3260-DB-401
3260-LC-401
3260-MC-402-1
3260-MC-402-2
3260-RU-400
3260-SB-402
3280-DB-501
3280-MC-501-1
3280-MC-501-2
3290-DB-601
3290-LC-601
3290-MC-602-1
3290-MC-602-2
3290-RU-600
3290-SB-602
3300-DB-701
3300-MC-701-1
3300-MC-701-2
3300-RU-700
3300-SB-701
5130-DB-901
5130-MC-912
5761-DB-001
5761-LC-001-A
5761-LC-001-B
CONSTANCIA 220kV

CUADRO DE DEMANDA MXIMA Y NIVEL DE TENSIN


kvar Loading
Nominal (kV)
Voltage (%)
kW Loading
0.4
99.78
169
105
4.16
100.29
1470
684
0.48
100.24
820
457
22.9
100.37
2311
1250
0.4
100.75
173
107
0.48
101.22
621
299
0.4
99.32
335
208
0.4
99.59
169
104
0.4
99.58
169
104
0.4
99.58
169
104
13.8
99.67
35104
21685
13.8
99.64
35171
21488
0.48
100.05
936
567
0.48
100.05
1042
677
0.48
100.01
1077
650
0.48
100.01
901
585
22.9
100.4
1994
1345
22.9
100.34
1993
1336
0.48
100.05
1978
1244
0.48
100.01
1977
1235
0.4
99.6
397
9.718
4.16
99.92
2744
1728
0.48
99.09
925
495
0.48
99.09
953
526
0.48
99.07
1477
664
0.48
99.07
1289
753
0.48
98.77
1156
694
0.48
98.77
1073
695
22.9
100.32
9725
6166
0.48
99.09
1878
1020
0.48
99.07
2766
1418
0.48
98.77
2230
1389
0.48
99.82
1798
969
0.4
100.97
204
9.985
4.16
100.06
3161
2027
0.48
100.72
550
167
0.48
100.72
572
278
22.9
100.36
3182
2191
0.48
100.72
1122
445
0.4
99.36
168
104
0.48
99.82
941
510
0.48
99.82
857
459
0.4
99.57
169
104
4.16
100.68
7967
3118
0.48
100.03
733
476
0.48
100.03
347
219
22.9
100.36
9081
4303
0.48
100.03
1080
694
0.4
99.05
167
103
0.48
99.49
914
605
0.48
99.49
741
491
22.9
100.41
1674
1191
0.48
99.49
1655
1095
0.4
101.86
97.038
46.998
0.46
103.38
585
288
0.4
100.03
340
211
22.9
100.38
55691
37140
22.9
100.43
59021
36475
220
100
114876
35167

Amp Loading
288
224.3
1127
65.99
290.8
818.8
573.4
287.5
287.5
287.5
1732
1731
1316
1494
1513
1292
60.39
60.28
2809
2804
575
450.4
1273
1321
1966
1812
1642
1557
289.4
2594
3773
3199
2461
291.5
520.9
686.2
759.4
97.05
1441
286.8
1290
1171
287.4
1179
1051
493.4
252.4
1544
285.9
1325
1075
51.59
2400
152.8
791.9
577.5
1681
1742
315.3

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 15 de 32

Tabla 8: Cargabilidad de los Transformadores.


CARGABILIDAD DE TRANSFORMADORES

TAG

Relacin de
Transformacin
(kV)

Potencia
Aparente
(kVA)

kW
Flow

kvar
Flow

Amp
Flow

%
Taps
kW
kvar
% PF % Loading Voltage
Regulation
Losses Losses
Drop
Prim. (%)

3100-TX-101

22.9 / 4.16 kV

2500 kVA

1482

3100-TX-102

22.9 / 0.48 kV

1500 kVA

828

756

41.8

89.08

66.6

0.05

12.026

72.158

-2.5

494

24.23 85.88

64.3

0.19

5.773

34.639

-2.5

3100-TX-103

0.48 / 0.4 kV

250 kVA

173

110

246.2 84.31

82

0.35

3.535

5.302

-2.5

3210-TX-151

22.9 / 0.48 kV

1500 kVA

625

318

17.6

89.11

35.1

0.98

3.048

18.286

-2.5

248.6 84.31

83.6

0.35

3.604

5.405

-2.5

1085

81.44

96.1

0.63

74.68

3361

Automtico

3210-TX-152

0.48 / 0.4 kV

250 kVA

176

112

3220-TX-201

22.9 / 13.8 kV

45000 kVA

35206

25083

3220-TX-202

13.8 / 0.4 kV

500 kVA

342

218

17.05 84.31

81.2

0.34

7.004

10.507

-2.5

3220-TX-205

22.9 / 0.48 kV

4000 kVA

1994

1345

60.39

82.9

60.1

0.04

11.153

94.797

-2.5

3220-TX-206

0.48 / 0.4 kV

250 kVA

172

110

245.7 84.31

81.7

0.35

3.521

5.282

-2.5

3220-TX-251

22.9 / 13.8 kV

45000 kVA

35275

24883

1085

95.9

0.6

74.561

3355

Automtico

3220-TX-252

13.8 / 0.4 kV

500 kVA

410

82

0.68

7.145

10.717

-2.5

3220-TX-255

22.9 / 0.48 kV

4000 kVA

1993

1336

60.28 83.07

60

0.03

11.113

94.464

-2.5

3220-TX-256

0.48 / 0.4 kV

250 kVA

172

110

245.7 84.31

81.7

0.35

3.521

5.281

-2.5

3250-TX-301

22.9 / 4.16 kV

5000 kVA

2763

1876

83.93 82.73

66.8

0.34

17.231

146

-2.5

3250-TX-303

22.9 / 0.48 kV

4000 kVA

2799

1606

81.12 86.73

80.7

0.6

20.121

171

-2.5

3250-TX-304

22.9 / 0.48 kV

3500 kVA

2258

1545

68.76 82.53

78.2

0.84

16.525

140

-2.5

3250-TX-305

0.48 / 0.4 kV

500 kVA

404

20.283 491.5 99.87

80.8

0.67

7.043

10.565

-2.5

3252-TX-302

22.9 / 0.48 kV

3000 kVA

1904

1139

55.77 85.82

74

0.61

17.842

107

-2.5

3260-TX-401

22.9 / 4.16 kV

6000 kVA

3182

2191

97.05 82.36

64.4

0.26

19.202

163

-2.5

3260-TX-402

22.9 / 0.48 kV

2000 kVA

1131

491

30.98 91.73

61.7

0.67

7.079

42.473

-2.5

3260-TX-403

0.48 / 0.4 kV

250 kVA

207

15.414 249.1 99.72

83.1

0.62

3.619

5.429

-2.5

3280-TX-501

22.9 / 0.48 kV

3000 kVA

1813

11.415

97.032

-2.5

81.71

20.575 17.22 99.87

1072

52.91 86.09

70.2

0.25

3280-TX-502

0.48 / 0.4 kV

250 kVA

171

109

245.2 84.31

81.3

0.34

3.505

5.257

-2.5

3290-TX-601

22.9 / 4.16 kV

14000 kVA

7990

3557

219.7 91.36

62.5

0.35

21.892

438

-2.5

3290-TX-602

22.9 / 0.48 kV

2000 kVA

1090

746

33.19 82.53

66.1

0.06

8.127

48.764

-2.5

3290-TX-603

0.48 / 0.4 kV

250 kVA

172

110

245.7 84.31

81.6

0.35

3.519

5.279

-2.5

3300-TX-701

22.9 / 0.48 kV

3000 kVA

1674

1191

51.59 81.48

68.5

0.66

15.269

91.615

-2.5

3300-TX-702

0.48 / 0.4 kV

250 kVA

170

109

244.4 84.31

80.8

0.34

3.483

5.224

-2.5

5130-TX-912

22.9 / 0.48 kV

2000 kVA

588

302

16.6

88.94

33.1

1.21

2.227

13.362

-2.5

5130-TX-913

0.46 / 0.4 kV

250 kVA

98.033

48.49

132.9 89.63

43.7

1.46

0.995

1.492

5761-TX-010

22.9 / 0.4 kV

500 kVA

347

222

10.35 84.31

82.4

0.35

7.105

10.657

220 kV

75000 kVA

59107

17478

161.8 95.89

49.3

0.44

84.222

4850

Automtico

22.9 kV

75000 kVA

59023

12628

1515

97.79

48.3

0.44

84.222

4850

13.2 kV

15000 kVA

11.33

0.44

84.222

4850

5721-TX-001

5721-TX-002

220 kV

75000 kVA

55768

17688

153.5 95.32

46.8

0.38

75.882

4370

22.9 kV

75000 kVA

55692

13318

1438

97.26

45.8

0.38

75.882

4370

13.2 kV

15000 kVA

7.76

0.38

75.882

4370

Automtico

Fuente: Elaborado por BISA

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 16 de 32

5.5. ESCENARIO 2 - SIN COMPENSACION REACTIVA.


Tabla 9: Resultados del nivel de tensin en barras principales en operacin.
TAG
3100-DB-101
3100-LC-101
3100-MC-102
3100-RU-100
3210-DB-105
3210-MC-151
3220-DB-201
3220-DB-202
3220-DB-206
3220-DB-206
3220-LC-201
3220-LC-251
3220-MC-205-1
3220-MC-205-2
3220-MC-255-1
3220-MC-255-2
3220-RU-205
3220-RU-255
3220-SB-205
3220-SB-255
3250-DB-301
3250-LC-301
3250-MC-302-1
3250-MC-302-2
3250-MC-303-1
3250-MC-303-2
3250-MC-304-1
3250-MC-304-2
3250-RU-301
3250-SB-302
3250-SB-303
3250-SB-304
3250-SB-501
3260-DB-401
3260-LC-401
3260-MC-402-1
3260-MC-402-2
3260-RU-400
3260-SB-402
3280-DB-501
3280-MC-501-1
3280-MC-501-2
3290-DB-601
3290-LC-601
3290-MC-602-1
3290-MC-602-2
3290-RU-600
3290-SB-602
3300-DB-701
3300-MC-701-1
3300-MC-701-2
3300-RU-700
3300-SB-701
5130-DB-901
5130-MC-912
5761-DB-001
5761-LC-001-A
5761-LC-001-B
CONSTANCIA 220kV

CUADRO DE DEMANDA MXIMA Y NIVEL DE TENSIN


kvar Loading
Nominal (kV)
Voltage (%)
kW Loading
0.4
99.22
167
104
4.16
99.71
1470
684
0.48
99.68
815
454
22.9
99.81
2306
1248
0.4
100.19
171
106
0.48
100.65
618
297
0.4
99.19
335
207
0.4
99.02
167
103
0.4
99.07
167
103
0.4
99.07
167
103
13.8
99.54
35103
21684
13.8
99.56
35170
21488
0.48
99.48
934
565
0.48
99.48
1037
674
0.48
99.49
1073
647
0.48
99.49
898
584
22.9
99.84
1986
1340
22.9
99.84
1986
1331
0.48
99.48
1971
1239
0.48
99.49
1971
1231
0.4
99.07
392
9.614
4.16
99.41
2728
1718
0.48
98.56
924
494
0.48
98.56
951
525
0.48
98.54
1472
664
0.48
98.54
1287
752
0.48
98.24
1156
694
0.48
98.24
1074
695
22.9
99.82
9701
6157
0.48
98.56
1876
1019
0.48
98.54
2759
1416
0.48
98.24
2230
1389
0.48
99.3
1792
966
0.4
100.45
202
9.883
4.16
99.53
3162
2027
0.48
100.2
547
166
0.48
100.2
571
277
22.9
99.86
3182
2193
0.48
100.2
1118
444
0.4
98.84
166
103
0.48
99.3
937
508
0.48
99.3
855
458
0.4
99
167
103
4.16
100.1
7967
3118
0.48
99.46
729
473
0.48
99.46
345
217
22.9
99.8
9076
4305
0.48
99.46
1075
691
0.4
98.48
165
102
0.48
98.91
911
602
0.48
98.91
739
489
22.9
99.86
1669
1188
0.48
98.91
1650
1091
0.4
101.29
96.151
46.568
0.46
102.81
581
286
0.4
99.53
337
209
22.9
99.88
55587
37152
22.9
99.88
114456
73626
220
100
114899
98586

Amp Loading
286.4
225.6
1126
66.22
289.2
818.9
572.7
285.9
286
286
1734
1732
1320
1495
1514
1295
60.51
60.39
2814
2809
572
450.1
1279
1326
1971
1820
1651
1566
290.2
2605
3786
3217
2466
290
523.7
686.6
761.6
97.57
1444
285.3
1291
1175
285.8
1186
1052
493.3
253.7
1545
284.3
1327
1078
51.72
2406
152.2
790.6
574.7
1688
3435
397.3

Fuente: Elaborado por BISA


(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 17 de 32

Tabla 10: Cargabilidad de los Transformadores.


CARGABILIDAD DE TRANSFORMADORES

TAG

Relacin de
Transformacin
(kV)

Potencia
Aparente
(kVA)

kW
Flow

kvar
Flow

3100-TX-101

22.9 / 4.16 kV

2500 kVA

1482

757

42.04 89.06

66.6

0.08

12.168

73.007

-2.5

3100-TX-102

22.9 / 0.48 kV

1500 kVA

823

491

24.21

85.9

63.9

0.18

5.765

34.589

-2.5

3100-TX-103

0.48 / 0.4 kV

250 kVA

171

109

244.8 84.31

81.1

0.34

3.495

5.243

-2.5

3210-TX-151

22.9 / 0.48 kV

1500 kVA

622

316

17.61 89.14

34.9

0.97

3.048

18.29

-2.5

247.2 84.31

82.6

0.35

3.563

5.345

-2.5

1092

96.1

0.21

75.593

3402

Automtico

Amp
Flow

%
Taps
kW
kvar
% PF % Loading Voltage
Regulation
Losses Losses
Drop
Prim. (%)

3210-TX-152

0.48 / 0.4 kV

250 kVA

174

111

3220-TX-201

22.9 / 13.8 kV

45000 kVA

35206

25124

3220-TX-202

13.8 / 0.4 kV

500 kVA

342

218

17.03 84.31

81

0.34

6.986

10.479

-2.5

3220-TX-205

22.9 / 0.48 kV

4000 kVA

1986

1340

60.51 82.89

59.9

0.06

11.195

95.159

-2.5

3220-TX-206

0.48 / 0.4 kV

250 kVA

170

109

244.3 84.31

80.7

0.34

3.481

5.221

-2.5

3220-TX-251

22.9 / 13.8 kV

45000 kVA

35275

24920

96

0.17

75.387

3392

Automtico

3220-TX-252

13.8 / 0.4 kV

500 kVA

409

81.9

0.68

7.134

10.701

-2.5

3220-TX-255

22.9 / 0.48 kV

4000 kVA

1986

1331

60.39 83.07

59.8

0.05

11.151

94.787

-2.5

3220-TX-256

0.48 / 0.4 kV

250 kVA

170

109

244.4 84.31

80.8

0.34

3.484

5.226

-2.5

3250-TX-301

22.9 / 4.16 kV

5000 kVA

2746

1865

83.85 82.73

66.4

0.35

17.201

146

-2.5

3250-TX-303

22.9 / 0.48 kV

4000 kVA

2793

1606

81.39 86.69

80.6

0.63

20.256

172

-2.5

3250-TX-304

22.9 / 0.48 kV

3500 kVA

2259

1547

69.15 82.51

78.2

0.88

16.711

142

-2.5

3250-TX-305

0.48 / 0.4 kV

500 kVA

399

80

0.67

6.968

10.452

-2.5

3252-TX-302

22.9 / 0.48 kV

3000 kVA

1902

1138

85.81

73.9

0.64

17.99

108

-2.5

3260-TX-401

22.9 / 4.16 kV

6000 kVA

3182

2193

97.57 82.34

64.4

0.29

19.407

165

-2.5

3260-TX-402

22.9 / 0.48 kV

2000 kVA

1128

490

31.04 91.71

61.5

0.65

7.106

42.634

-2.5

3260-TX-403

0.48 / 0.4 kV

250 kVA

205

15.255 247.8 99.72

82.3

0.62

3.582

5.373

-2.5

3280-TX-501

22.9 / 0.48 kV

3000 kVA

1808

11.461

97.42

-2.5

1091

81.4

81.67

20.545 17.21 99.87

20.067 488.9 99.87


56

1068

53.02 86.09

70

0.27

243.9 84.31

3280-TX-502

0.48 / 0.4 kV

250 kVA

170

108

3290-TX-601

22.9 / 4.16 kV

14000 kVA

7991

3562

80.4

0.34

3.468

5.203

-2.5

91.34

62.5

0.32

22.148

443

-2.5

3290-TX-602

22.9 / 0.48 kV

2000 kVA

1085

743

33.21 82.51

65.7

0.07

8.137

48.822

-2.5

3290-TX-603

0.48 / 0.4 kV

250 kVA

170

108

244.3 84.31

80.7

0.34

3.479

5.219

-2.5

3300-TX-701

22.9 / 0.48 kV

3300-TX-702

0.48 / 0.4 kV

3000 kVA

1669

1188

51.72 81.47

250 kVA

168

107

5130-TX-912

22.9 / 0.48 kV

2000 kVA

584

300

5130-TX-913

0.46 / 0.4 kV

250 kVA

97.138

5761-TX-010

22.9 / 0.4 kV

500 kVA

344

5721-TX-001

221

68.3

0.68

15.344

92.063

-2.5

84.31

79.8

0.34

3.443

5.164

-2.5

16.57 88.94

32.8

1.21

2.219

13.316

-2.5

48.049 132.4 89.63


219

243

10.3

43.3

1.46

0.987

1.481

84.31

81.6

0.35

7.034

10.551

0
Automtico

220 kV

75000 kVA 114899

98586

397.3 75.89

121.1

0.1

433

24934

22.9 kV

75000 kVA 114466

73651

3435

84.1

108.9

0.1

433

24934

13.2 kV

15000 kVA

-98.9

0.1

433

24934

Fuente: Elaborado por BISA

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 18 de 32

5.6. ESCENARIO 2 - CON COMPENSACION REACTIVA.


Tabla 11: Resultados del nivel de tensin en barras principales en operacin.
TAG
3100-DB-101
3100-LC-101
3100-MC-102
3100-RU-100
3210-DB-105
3210-MC-151
3220-DB-201
3220-DB-202
3220-DB-206
3220-DB-206
3220-LC-201
3220-LC-251
3220-MC-205-1
3220-MC-205-2
3220-MC-255-1
3220-MC-255-2
3220-RU-205
3220-RU-255
3220-SB-205
3220-SB-255
3250-DB-301
3250-LC-301
3250-MC-302-1
3250-MC-302-2
3250-MC-303-1
3250-MC-303-2
3250-MC-304-1
3250-MC-304-2
3250-RU-301
3250-SB-302
3250-SB-303
3250-SB-304
3250-SB-501
3260-DB-401
3260-LC-401
3260-MC-402-1
3260-MC-402-2
3260-RU-400
3260-SB-402
3280-DB-501
3280-MC-501-1
3280-MC-501-2
3290-DB-601
3290-LC-601
3290-MC-602-1
3290-MC-602-2
3290-RU-600
3290-SB-602
3300-DB-701
3300-MC-701-1
3300-MC-701-2
3300-RU-700
3300-SB-701
5130-DB-901
5130-MC-912
5761-DB-001
5761-LC-001-A
5761-LC-001-B
CONSTANCIA 220kV

CUADRO DE DEMANDA MXIMA Y NIVEL DE TENSIN


kvar Loading
Nominal (kV)
Voltage (%)
kW Loading
0.4
99.75
169
105
4.16
100.26
1470
684
0.48
100.21
820
457
22.9
100.33
2310
1250
0.4
100.72
172
107
0.48
101.18
621
299
0.4
99.77
338
210
0.4
99.56
169
104
0.4
99.6
169
105
0.4
99.6
169
105
13.8
100.11
35107
21687
13.8
100.14
35175
21488
0.48
100.02
936
567
0.48
100.02
1041
677
0.48
100.03
1077
650
0.48
100.03
901
585
22.9
100.36
1993
1345
22.9
100.36
1993
1336
0.48
100.02
1977
1244
0.48
100.03
1978
1235
0.4
99.62
397
9.722
4.16
99.94
2745
1728
0.48
99.11
925
495
0.48
99.11
953
526
0.48
99.09
1477
664
0.48
99.09
1289
753
0.48
98.8
1156
694
0.48
98.8
1073
695
22.9
100.34
9725
6167
0.48
99.11
1878
1020
0.48
99.09
2766
1418
0.48
98.8
2230
1389
0.48
99.84
1798
970
0.4
100.99
204
9.989
4.16
100.08
3161
2027
0.48
100.74
550
167
0.48
100.74
572
278
22.9
100.38
3182
2191
0.48
100.74
1122
445
0.4
99.38
168
104
0.48
99.84
941
511
0.48
99.84
857
459
0.4
99.53
168
104
4.16
100.65
7967
3118
0.48
99.99
733
476
0.48
99.99
347
219
22.9
100.32
9081
4303
0.48
99.99
1080
694
0.4
99.02
167
103
0.48
99.45
914
604
0.48
99.45
741
491
22.9
100.38
1674
1191
0.48
99.45
1655
1095
0.4
101.82
96.985
46.972
0.46
103.35
585
288
0.4
100.05
340
211
22.9
100.4
55697
37140
22.9
100.4
114714
49781
220
100
115041
44394

Amp Loading
288
224.4
1127
66
290.7
818.8
576
287.4
287.5
287.5
1724
1722
1316
1494
1513
1292
60.4
60.28
2809
2804
575.1
450.5
1273
1320
1966
1812
1642
1557
289.4
2594
3773
3198
2461
291.5
520.8
686.1
759.3
97.03
1441
286.9
1290
1171
287.3
1180
1051
493.4
252.5
1544
285.8
1325
1075
51.6
2400
152.8
791.8
577.6
1681
3140
323.6

Fuente: Elaborado por BISA


(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 19 de 32

Tabla 12: Cargabilidad de los Transformadores.


CARGABILIDAD DE TRANSFORMADORES

TAG

Relacin de
Transformaci
n (kV)

Potencia
Aparente
(kVA)

kW
Flow

kvar
Flow

3100-TX-101

22.9 / 4.16 kV

2500 kVA

1482

756

41.81 89.08

66.6

0.05

12.035

72.208

-2.5

3100-TX-102

22.9 / 0.48 kV

1500 kVA

828

494

24.23 85.88

64.3

0.19

5.773

34.636

-2.5

3100-TX-103

0.48 / 0.4 kV

250 kVA

173

110

246.1 84.31

81.9

0.35

3.532

5.298

-2.5

3210-TX-151

22.9 / 0.48 kV

1500 kVA

625

318

17.6

35

0.98

3.048

18.286

-2.5

248.5 84.31

83.5

0.35

3.601

5.402

-2.5

1086

81.44

96.1

0.15

74.746

3364

Automtico

17.12 84.31

81.9

0.35

7.067

10.6

-2.5

Amp
Flow

%
Taps
kW
kvar
% PF % Loading Voltage
Regulation
Losses Losses
Drop
Prim. (%)

89.12

3210-TX-152

0.48 / 0.4 kV

250 kVA

176

112

3220-TX-201

22.9 / 13.8 kV

45000 kVA

35209

25088

3220-TX-202

13.8 / 0.4 kV

500 kVA

345

220

3220-TX-205

22.9 / 0.48 kV

4000 kVA

1993

1345

60.4

82.9

60.1

0.05

11.155

94.818

-2.5

3220-TX-206

0.48 / 0.4 kV

250 kVA

172

110

245.6 84.31

81.6

0.35

3.519

5.278

-2.5

3220-TX-251

22.9 / 13.8 kV

45000 kVA

35278

24882

1084

81.72

95.9

0.11

74.541

3354

Automtico

3220-TX-252

13.8 / 0.4 kV

500 kVA

414

20.782

17.3

99.87

82.8

0.68

7.217

10.825

-2.5

3220-TX-255

22.9 / 0.48 kV

4000 kVA

1993

1336

60.28 83.07

60

0.03

11.112

94.451

-2.5

3220-TX-256

0.48 / 0.4 kV

250 kVA

172

110

245.8 84.31

81.7

0.35

3.522

5.283

-2.5

3250-TX-301

22.9 / 4.16 kV

5000 kVA

2763

1876

83.93 82.73

66.8

0.34

17.232

146

-2.5

3250-TX-303

22.9 / 0.48 kV

4000 kVA

2799

1606

81.1

86.73

80.7

0.6

20.115

171

-2.5

3250-TX-304

22.9 / 0.48 kV

3500 kVA

2258

1545

68.75 82.53

78.2

0.84

16.518

140

-2.5

3250-TX-305

0.48 / 0.4 kV

500 kVA

404

20.291 491.6 99.87

80.9

0.67

7.046

10.569

-2.5

3252-TX-302

22.9 / 0.48 kV

3000 kVA

1904

1139

55.76 85.82

74

0.61

17.837

107

-2.5

3260-TX-401

22.9 / 4.16 kV

6000 kVA

3182

2191

97.03 82.36

64.4

0.26

19.194

163

-2.5

3260-TX-402

22.9 / 0.48 kV

2000 kVA

1132

491

30.98 91.73

61.7

0.67

7.078

42.467

-2.5

3260-TX-403

0.48 / 0.4 kV

250 kVA

207

15.42

249.2 99.72

83.2

0.62

3.62

5.431

-2.5

3280-TX-501

22.9 / 0.48 kV

3000 kVA

1813

1072

52.91 86.09

70.2

0.25

11.414

97.017

-2.5

3280-TX-502

0.48 / 0.4 kV

250 kVA

171

109

245.2 84.31

81.3

0.34

3.506

5.259

-2.5

3290-TX-601

22.9 / 4.16 kV

14000 kVA

7990

3557

219.8 91.36

62.5

0.35

21.908

438

-2.5

3290-TX-602

22.9 / 0.48 kV

2000 kVA

1090

746

33.2

66

0.06

8.128

48.768

-2.5

3290-TX-603

0.48 / 0.4 kV

250 kVA

172

110

245.6 84.31

81.6

0.35

3.517

5.276

-2.5

3300-TX-701

22.9 / 0.48 kV

3000 kVA

1674

1191

51.6

81.48

68.5

0.66

15.274

91.642

-2.5

3300-TX-702

0.48 / 0.4 kV

250 kVA

170

109

244.3 84.31

80.7

0.34

3.48

5.221

-2.5

5130-TX-912

22.9 / 0.48 kV

2000 kVA

588

302

16.6

33

1.21

2.227

13.359

-2.5

5130-TX-913

0.46 / 0.4 kV

250 kVA

97.979

5761-TX-010

22.9 / 0.4 kV

500 kVA

347

5721-TX-001

82.53

88.94

48.463 132.8 89.63

43.7

1.46

0.994

1.491

222

10.35 84.31

82.4

0.35

7.107

10.661

0
Automtico

220 kV

75000 kVA 115041

44394

323.6 93.29

98.6

0.41

320

18429

22.9 kV

75000 kVA 114721

25964

2953

97.53

94.1

0.41

320

18429

13.2 kV

15000 kVA

20.95

0.41

320

18429

Fuente: Elaborado por BISA

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 20 de 32

5.7. ESCENARIO 2 - CON COMPENSACION REACTIVA SALA 3220-LC-201


FUERA DE SERVICIO.
Tabla 13: Resultados del nivel de tensin en barras principales en operacin.
TAG
3100-DB-101
3100-LC-101
3100-MC-102
3100-RU-100
3210-DB-105
3210-MC-151
3220-DB-202
3220-DB-206
3220-DB-206
3220-LC-251
3220-MC-205-1
3220-MC-205-2
3220-MC-255-1
3220-MC-255-2
3220-RU-205
3220-RU-255
3220-SB-205
3220-SB-255
3250-DB-301
3250-LC-301
3250-MC-302-1
3250-MC-302-2
3250-MC-303-1
3250-MC-303-2
3250-MC-304-1
3250-MC-304-2
3250-RU-301
3250-SB-302
3250-SB-303
3250-SB-304
3250-SB-501
3260-DB-401
3260-LC-401
3260-MC-402-1
3260-MC-402-2
3260-RU-400
3260-SB-402
3280-DB-501
3280-MC-501-1
3280-MC-501-2
3290-DB-601
3290-LC-601
3290-MC-602-1
3290-MC-602-2
3290-RU-600
3290-SB-602
3300-DB-701
3300-MC-701-1
3300-MC-701-2
3300-RU-700
3300-SB-701
5130-DB-901
5130-MC-912
5761-DB-001
5761-LC-001-A
5761-LC-001-B
CONSTANCIA 220kV

CUADRO DE DEMANDA MXIMA Y NIVEL DE TENSIN


kvar Loading
Nominal (kV)
Voltage (%)
kW Loading
0.4
99.75
169
105
4.16
100.26
1470
684
0.48
100.22
820
457
22.9
100.34
2310
1250
0.4
100.72
172
107
0.48
101.19
621
299
0.4
99.56
169
104
0.4
99.61
169
105
0.4
99.61
169
105
13.8
99.66
35171
21488
0.48
100.02
936
567
0.48
100.02
1041
677
0.48
100.03
1077
650
0.48
100.03
901
585
22.9
100.37
1993
1345
22.9
100.37
1993
1336
0.48
100.02
1978
1244
0.48
100.03
1978
1235
0.4
99.62
397
9.723
4.16
99.95
2745
1729
0.48
99.12
925
495
0.48
99.12
953
526
0.48
99.1
1477
664
0.48
99.1
1289
753
0.48
98.8
1156
694
0.48
98.8
1073
695
22.9
100.34
9726
6167
0.48
99.12
1878
1020
0.48
99.1
2766
1418
0.48
98.8
2230
1389
0.48
99.84
1798
970
0.4
100.99
204
9.99
4.16
100.08
3161
2027
0.48
100.75
550
167
0.48
100.75
572
278
22.9
100.39
3182
2191
0.48
100.75
1122
445
0.4
99.39
168
104
0.48
99.84
941
511
0.48
99.84
857
459
0.4
99.54
168
104
4.16
100.65
7967
3118
0.48
100
733
476
0.48
100
347
219
22.9
100.33
9081
4303
0.48
100
1080
694
0.4
99.02
167
103
0.48
99.46
914
604
0.48
99.46
741
491
22.9
100.38
1674
1191
0.48
99.46
1655
1095
0.4
101.83
96.994
46.976
0.46
103.35
585
288
0.4
100.06
340
211
22.9
100.4
55694
37140
22.9
100.4
79498
24676
220
100
79647
9267

Amp Loading
288
224.4
1127
66
290.8
818.8
287.4
287.5
287.5
1730
1316
1494
1513
1292
60.4
60.28
2809
2804
575.2
450.5
1273
1320
1966
1812
1642
1557
289.4
2594
3773
3198
2461
291.5
520.7
686.1
759.3
97.02
1441
286.9
1290
1171
287.3
1180
1051
493.4
252.5
1544
285.8
1325
1075
51.6
2400
152.8
791.9
577.7
1681
2090
210.4

Fuente: Elaborado por BISA


(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 21 de 32

Tabla 14: Cargabilidad de los Transformadores.


CARGABILIDAD DE TRANSFORMADORES

TAG

Relacin de
Transformaci
n (kV)

Potencia
Aparente
(kVA)

kW
Flow

kvar
Flow

Amp
Flow

% PF

%
Taps
kW
kvar
% Loading Voltage
Regulation
Losses Losses
Drop
Prim. (%)

3100-TX-101

22.9 / 4.16 kV

2500 kVA

1482

756

41.81

89.08

66.6

0.05

12.033

72.2

-2.5

3100-TX-102

22.9 / 0.48 kV

1500 kVA

828

494

24.23

85.88

64.3

0.19

5.773

34.637

-2.5

3100-TX-103

0.48 / 0.4 kV

250 kVA

173

110

246.1

84.31

81.9

0.35

3.533

5.299

-2.5

3210-TX-151

22.9 / 0.48 kV

1500 kVA

625

318

17.6

89.12

35

0.98

3.048

18.286

-2.5

3210-TX-152

0.48 / 0.4 kV

250 kVA

176

112

248.5

84.31

83.5

0.35

3.602

5.402

-2.5

3220-TX-205

22.9 / 0.48 kV

4000 kVA

1993

1345

60.4

82.9

60.1

0.04

11.155

94.815

-2.5

3220-TX-206

0.48 / 0.4 kV

250 kVA

172

110

245.7

84.31

81.6

0.35

3.519

5.279

-2.5

3220-TX-251

22.9 / 13.8 kV

1084

81.72

95.9

0.59

74.521

3353

Automtico

3220-TX-252

13.8 / 0.4 kV

500 kVA

410

20.586 17.22

99.87

82.1

0.68

7.148

10.723

-2.5

3220-TX-255

22.9 / 0.48 kV

4000 kVA

1993

1336

60.28

83.07

60

0.03

11.112

94.448

-2.5

3220-TX-256

0.48 / 0.4 kV

250 kVA

172

110

245.8

84.31

81.7

0.35

3.522

5.284

-2.5

3250-TX-301

22.9 / 4.16 kV

5000 kVA

2763

1876

83.93

82.73

66.8

0.34

17.232

146

-2.5

3250-TX-303

22.9 / 0.48 kV

4000 kVA

2799

1606

81.1

86.73

80.7

0.6

20.114

171

-2.5

3250-TX-304

22.9 / 0.48 kV

3500 kVA

2258

1545

68.75

82.53

78.2

0.84

16.516

140

-2.5

3250-TX-305

0.48 / 0.4 kV

500 kVA

404

20.294 491.6

99.87

80.9

0.67

7.047

10.57

-2.5

3252-TX-302

22.9 / 0.48 kV

3000 kVA

1904

1139

55.76

85.82

74

0.61

17.835

107

-2.5

3260-TX-401

22.9 / 4.16 kV

6000 kVA

3182

2191

97.02

82.36

64.4

0.26

19.192

163

-2.5

3260-TX-402

22.9 / 0.48 kV

2000 kVA

1132

491

30.98

91.73

61.7

0.67

7.078

42.465

-2.5

15.422 249.2

45000 kVA 35275 24881

3260-TX-403

0.48 / 0.4 kV

250 kVA

207

99.72

83.2

0.62

3.621

5.431

-2.5

3280-TX-501

22.9 / 0.48 kV

3000 kVA

1813

1072

52.91

86.09

70.2

0.25

11.413

97.013

-2.5

3280-TX-502

0.48 / 0.4 kV

250 kVA

171

109

245.2

84.31

81.3

0.34

3.507

5.26

-2.5

3290-TX-601

22.9 / 4.16 kV

14000 kVA

7990

3557

219.8

91.36

62.5

0.35

21.905

438

-2.5

3290-TX-602

22.9 / 0.48 kV

2000 kVA

1090

746

33.2

82.53

66

0.06

8.128

48.767

-2.5

3290-TX-603

0.48 / 0.4 kV

250 kVA

172

110

245.6

84.31

81.6

0.35

3.517

5.276

-2.5

3300-TX-701

22.9 / 0.48 kV

3000 kVA

1674

1191

51.6

81.48

68.5

0.66

15.273

91.637

-2.5

3300-TX-702

0.48 / 0.4 kV

250 kVA

170

109

244.3

84.31

80.7

0.34

3.481

5.221

-2.5

5130-TX-912

22.9 / 0.48 kV

2000 kVA

588

302

16.6

88.94

33

1.21

2.227

13.36

-2.5

48.467 132.8

89.63

43.7

1.46

0.994

1.491

5130-TX-913

0.46 / 0.4 kV

250 kVA

97.98
8

5761-TX-010

22.9 / 0.4 kV

500 kVA

347

5721-TX-001

222

10.35

84.31

82.4

0.35

7.108

10.662

99.33

64.1

0.41

146

8420

Automtico

220 kV

75000 kVA 79647

9267

210.4

22.9 kV

75000 kVA 79501

846

1996

99.99

63.6

0.41

146

8420

13.2 kV

15000 kVA

-99.37

0.41

146

8420

Fuente: Elaborado por BISA

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 22 de 32

5.8. ESCENARIO CARGAS CRITICAS PRIORIDAD 1 Y 2.


Tabla 15: Resultados del nivel de tensin en barras principales en operacin.
TAG
3210-MC-151
3220-MC-205-1
3220-MC-205-2
3220-MC-255-2
3220-RU-205
3220-RU-255
3220-SB-205
3220-SB-255
3250-LC-301
3250-MC-302-1
3250-MC-303-1
3250-MC-303-2
3250-RU-301
3250-SB-302
3250-SB-303
3260-MC-402-1
3260-MC-402-2
3260-SB-402
3290-LC-601
3290-MC-602-1
3290-MC-602-2
3290-RU-600
3290-SB-602
3300-MC-701-1
3300-MC-701-2
3300-RU-700
3300-SB-701
5761-LC-001-A
5761-LC-001-B

CUADRO DE DEMANDA MXIMA Y NIVEL DE TENSIN


kvar Loading
Nominal (kV)
Voltage (%)
kW Loading
0.48
99.35
12.848
9.176
0.48
99.15
33.676
21.304
0.48
99.15
124
87.986
0.48
99.37
19.071
13.578
22.9
96.91
158
110
22.9
96.92
19.073
13.588
0.48
99.15
158
109
0.48
99.37
19.071
13.578
4.16
99.08
290
186
0.48
99.34
22.291
16.601
0.48
99.04
53.859
34.102
0.48
99.04
163
111
22.9
96.91
529
351
0.48
99.34
22.291
16.601
0.48
99.04
217
145
0.48
99.23
38.348
27.521
0.48
99.23
21.43
14.063
0.48
99.23
59.778
41.583
4.16
98.02
5328
1918
0.48
98.3
188
126
0.48
98.3
188
126
22.9
96.87
5716
2368
0.48
98.3
377
252
0.48
99.32
14.894
17.064
0.48
99.32
18.861
11.077
22.9
96.92
33.764
28.188
0.48
99.32
33.755
28.141
22.9
96.92
6531
2923
22.9
96.92
5922
2517

Amp Loading
19.11
48.34
184.3
28.34
5.001
0.609
232.6
28.34
48.24
33.65
77.42
239.4
16.52
33.65
316.7
57.22
31.07
88.27
801.7
277.1
277.3
161
554.5
27.43
26.49
1.144
53.22
186.1
167.4

Fuente: Elaborado por BISA


Tabla 16: Cargabilidad de los Transformadores.
CARGABILIDAD DE TRANSFORMADORES
Relacin de
Transf. (kV)

Potencia
Aparente
(kVA)

kW
Flow

kvar
Flow

Amp
Flow

%
Taps
kW
kvar
% PF % Loading Voltage
Regulation
Losses Losses
Drop
Prim. (%)

3210-TX-151 22.9 / 0.48 kV

1500 kVA

12.85

9.186

0.411

81.35

0.8

2.44

0.002

0.01

-2.5

3220-TX-205 22.9 / 0.48 kV

4000 kVA

158

110

5.001

82.01

4.8

2.26

0.076

0.65

-2.5

3220-TX-255 22.9 / 0.48 kV

4000 kVA

19.073 13.588 0.609

81.44

0.6

2.46

0.001

0.01

-2.5

3250-TX-301 22.9 / 4.16 kV

5000 kVA

290

187

8.988

84

6.9

2.18

0.198

1.68

-2.5

3250-TX-303 22.9 / 0.48 kV

4000 kVA

217

146

6.81

82.89

6.5

2.18

0.142

1.205

-2.5

3252-TX-302 22.9 / 0.48 kV

3000 kVA

22.296 16.621 0.723

80.17

0.9

2.44

0.003

0.018

-2.5

3260-TX-402 22.9 / 0.48 kV

2000 kVA

59.814 41.756 1.898

TAG

82

3.6

2.33

0.027

0.159

-2.5

3290-TX-601 22.9 / 4.16 kV 14000 kVA

5338

2109

149.4

93

41

1.17

9.523

190

-2.5

3290-TX-602 22.9 / 0.48 kV

2000 kVA

378

259

11.92

82.52

22.9

1.53

1.048

6.288

-2.5

3300-TX-701 22.9 / 0.48 kV

3000 kVA

33.764 28.188 1.144

76.76

1.5

2.41

0.008

0.045

-2.5

5761-TX-901 0.48 / 22.9 kV

2000 kVA

2212

1184

3036

88.17

125.4

2.47

34.848

209

-2.5

5761-TX-902 0.48 / 22.9 kV

2000 kVA

2212

1184

3036

88.17

125.4

2.47

34.848

209

-2.5

5761-TX-903 0.48 / 22.9 kV

2000 kVA

2212

1184

3036

88.17

125.4

2.47

34.848

209

-2.5

Fuente: Elaborado por BISA


(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 23 de 32

5.9. ESCENARIO CARGAS CRITICAS PRIORIDAD 1 Y 3.


Tabla 17: Resultados del nivel de tensin en barras principales en operacin.
TAG
3210-MC-151
3220-MC-205-1
3220-MC-205-2
3220-MC-255-1
3220-MC-255-2
3220-RU-205
3220-RU-255
3220-SB-205
3220-SB-255
3250-MC-303-1
3250-MC-303-2
3250-MC-304-2
3250-RU-301
3250-SB-303
3250-SB-304
3250-SB-501
3260-MC-402-1
3260-MC-402-2
3260-SB-402
3280-MC-501-1
3300-MC-701-1
3300-MC-701-2
3300-RU-700
3300-SB-701
5761-LC-001-A
5761-LC-001-B

CUADRO DE DEMANDA MXIMA Y NIVEL DE TENSIN


kvar Loading
Nominal (kV)
Voltage (%)
kW Loading
0.48
102.45
12.835
9.174
0.48
100.97
446
265
0.48
100.97
628
384
0.48
101.17
432
254
0.48
101.17
518
307
22.9
99.92
1078
677
22.9
99.92
954
583
0.48
100.97
1074
649
0.48
101.17
950
561
0.48
102.15
53.774
34.09
0.48
102.15
163
111
0.48
102.43
31.822
22.651
22.9
99.93
249
169
0.48
102.15
217
145
0.48
102.43
31.822
22.651
0.48
102.33
90.488
56.487
0.48
102.27
38.321
27.515
0.48
102.27
41.157
28.594
0.48
102.27
79.478
56.109
0.48
102.33
90.488
56.487
0.48
102.34
45.707
39.831
0.48
102.34
21.055
13.093
22.9
99.93
66.795
53.091
0.48
102.34
66.762
52.924
22.9
99.93
2531
1605
22.9
99.93
1158
740

Amp Loading
18.52
618.3
876.4
596.2
715.7
32.13
28.2
1495
1312
74.97
231.9
45.87
7.582
306.8
45.87
125.4
55.49
58.94
114.4
125.4
71.26
29.14
2.153
100.1
75.6
34.67

Fuente: Elaborado por BISA


Tabla 18: Cargabilidad de los Transformadores.
CARGABILIDAD DE TRANSFORMADORES
Potencia
Aparente
(kVA)

kW
Flow

kvar
Flow

Amp
Flow

3210-TX-151 22.9 / 0.48 kV

1500

12.837

9.184

0.398 81.33

0.8

2.52

0.002

0.009

-2.5

3220-TX-205 22.9 / 0.48 kV

4000

1078

677

32.13 84.68

31.8

1.21

3.157

26.838

-2.5

3220-TX-255 22.9 / 0.48 kV

4000

954

583

28.2

27.9

1.39

2.432

20.673

-2.5

3250-TX-303 22.9 / 0.48 kV

4000

217

146

6.596 82.89

6.5

2.27

0.133

1.131

-2.5

3250-TX-304 22.9 / 0.48 kV

3500

31.827 22.683 0.986 81.44

1.1

2.51

0.003

0.029

-2.5

3260-TX-402 22.9 / 0.48 kV

2000

79.539

81.57

4.9

2.36

0.045

0.268

-2.5

3280-TX-501 22.9 / 0.48 kV

3000

90.528 56.752 2.696 84.73

3.6

2.41

0.03

0.252

-2.5

3300-TX-701 22.9 / 0.48 kV

3000

66.795 53.091 2.153 78.28

2.8

2.42

0.027

0.16

-2.5

5761-TX-901 0.48 / 22.9 kV

2000

849

569

1233

83.06

51.1

0.19

5.748

34.49

-2.5

5761-TX-902 0.48 / 22.9 kV

2000

849

569

1233

83.06

51.1

0.19

5.748

34.49

-2.5

5761-TX-903 0.48 / 22.9 kV

2000

849

569

1233

83.06

51.1

0.19

5.748

34.49

-2.5

TAG

Relacin de
Transf. (kV)

56.4

2.46

%
PF

%
Taps
kW
kvar
% Loading Voltage
Regulation
Losses Losses
Drop
Prim. (%)

85.33

Fuente: Elaborado por BISA

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 24 de 32

6.0. CONCLUSIONES
Con la lista de arrancadores 2172-5700-LST-004 Rev. 3. Constancia
Project Electrical Starter List (25-06-2013) se increment las potencias de
los trasformadores 3250-TX-303 de 3.0MVA a 4.0MVA y 3280-TX-501 de
2.5MVA a 3.0MVA de acuerdo a la memoria de mxima demanda (4)
G69173-D1001-U109.
Escenario inicial sin compensacin reactiva:
El perfil de tensin en todas las barras de 13.8kV son mayores a
95% de la tensin nominal que estn en un rango aceptado, y en
las barras de 22.9kV, 0.48kV y 0.4 kV son menores a 95% de la
tensin nominal, que est debajo de los niveles de tensin
admisible en operacin normal segn el punto 3.2 (ver tabla 01).
Todos los transformadores

estn operando sin sobrecarga (ver

tabla 02).
Escenario inicial con compensacin reactiva:
El perfil de tensin en todas las barras de 22.9kV, 13.8kV, 3290LC-601 en 4.16kV, 3210-MC-151, 3260-MC-402-1, 3260-MC-402-2,
3260-SB-402 en 0.48kV y 3220-DB-201, 3220-DB-201 en 0.40kV
son mayores a 95% de la tensin nominal que estn en un rango
aceptado y en el resto de las barras de 4.16kV, 0.48kV y 0.4 kV el
perfil de tensin es menor a 95% de la tensin nominal; que estn
debajo de los niveles de tensin admisible en operacin normal
segn el punto 3.2 (ver tabla 03).
Todos los transformadores

estn operando sin sobrecarga (ver

tabla 04).
Primer escenario sin compensacin reactiva:
Los transformadores 5721-TX-001 y 5721-TX-002
tienen la
capacidad de asumir todas las cargas que alimentan sin presentar
sobrecargas bajo este primer escenario sin compensacin (ver
tabla 06).
Todos los transformadores

estn operando sin sobrecarga (ver

tabla 06).
(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 25 de 32

El perfil de tensin en todas las barras de 22.9kV, 13.8kV, 0.48kV y


0.4 kV son superiores a 95% de la tensin nominal, que es superior
a los niveles de tensin admisible en operacin normal segn el
punto 3.2 (ver tabla 05).
El perfil de tensin de las barras principales en 22.9kV (5761-LC001-A, 5761-LC-001-B) es de 99.87% y 99.92% de su nominal;
Esta se encuentra en el rango de tensin admisible por la
regulacin automtica bajo carga en los transformadores 5721-TX001 y 5721-TX-002 operando en tap -5% en ambos casos (ver
tabla 05 y 06).
El perfil de tensin de las barras en 13.8kV (3220-LC-201 3220-LC251) es de 99.59% y 100.03% de su nominal, esta se encuentra en
el rango de tensin admisible; Los transformadores 3220-TX-201 y
3220-TX-251 operan con tensin secundaria bajo carga, esto
quiere decir que garantizan un perfil de tensin de 1.0 p.u (ver tabla
05).
Los transformadores 3220-TX-201 y 3220-TX-251 se encuentra al
96.1% y 96% de su potencia nominal, este se encuentra en un
rango de cargabilidad aceptable (ver tabla 06).
Para mejorar el perfil de tensin de todas las barras de 4.16 kV,
0.48kV y 0.40kV, se regulan la mayora de los taps de los
transformadores menores a 45MVA en -2.5% (ver tabla 5 y 6).
El factor de potencia en barras principales de 22.9kV (5761-LC001-A, 5761-LC-001-B) es 85% y 83.1% respectivamente (Ver
anexo 5- Reporte ETAP Unifilares).
Primer escenario con compensacin reactiva:
Del anlisis se tiene que los transformadores 5721-TX-001 y 5721TX-002 tienen la capacidad de asumir todas las cargas que
alimentan sin presentar sobrecargas bajo este primer escenario con
compensacin (ver tabla 08).
El perfil de tensin en todas las barras de 22.9kV, 13.8kV, 0.48kV y
0.4 kV son superiores a 95% de la tensin nominal; Estos son

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 26 de 32

superiores a los niveles de tensin admisible en operacin normal


segn el punto 3.2 (ver tabla 07).
El perfil de tensin de las barras principales en 22.9kV (5761-LC001-A, 5761-LC-001-B) es 100.38% y 100.43% de su nominal, esta
se encuentra en el rango de tensin aceptable por la regulacin
automtica bajo carga de los transformadores 5721-TX-001 y 5721TX-002 operando en tap -2.5% en ambos casos (ver tabla 07 y 08).
El perfil de tensin de las barras en 13.8kV (3220-LC-201 3220-LC251) es 99.67% y 99.64% de su nominal, esta se encuentra en el
rango de tensin aceptable; Los transformadores 3220-TX-201 y
3220-TX-251 operan con tensin secundaria bajo carga, esto
quiere decir que garantizan un perfil de tensin de 1.0 p.u (ver tabla
07).
Los transformadores 3220-TX-201 y 3220-TX-251 se encuentra en
un rango de cargabilidad aceptable de 96.1% y 95.9% de su
potencia nominal respectivamente (ver tabla 08).
Para mejorar el perfil de tensin de todas las barras de 4.16 kV,
0.48kV y 0.40kV, se regulan la mayora de los taps de los
transformadores menores a 45MVA en -2.5% (ver tabla 7 y 8).
El factor de potencia en las barras principales de 22.9kV (5761-LC001-A, 5761-LC-001-B) es de 97.0 y 97.1% respectivamente (Ver
anexo 5- Reporte ETAP Unifilares).

Segundo escenario sin compensacin reactiva (Solo el transformador


5721-TX-001 en operacin):
El transformador 5721-TX-001 esta sobrecargado en 121.1% de su
potencia nominal en el primario y 108.9% en el secundario, la
refrigeracin del transformador es ONAF (ver tabla 10).
El perfil de tensin en todas las barras de 22.9kV, 13.8kV, 0.48kV y
0.4 kV son superiores a 95% de la tensin nominal, superior a los
niveles de tensin admisible en operacin normal segn el punto
3.2 (ver tabla 09).

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 27 de 32

El sistema elctrico de la planta minera constancia no puede


operar bajo estas condiciones de transformador sobrecargado.

Segundo

escenario

con

compensacin

reactiva

(Solo

el

transformador 5721-TX-001 en operacin):


El transformador 5721-TX-001 est operando al 98.6% de su
potencia nominal en el primario y en el secundario su cargabilidad
es 94.1%, la refrigeracin del transformador es ONAF; Se concluye
que tiene la capacidad de asumir todas las cargas que alimentan
sin presentar sobrecarga, bajo este segundo escenario con
compensacin (ver tabla 12).
El perfil de tensin en todas las barras de 22.9kV, 13.8kV, 0.48kV y
0.4 kV son superiores a 95% de la tensin nominal, superior a los
niveles de tensin admisible en operacin normal segn el punto
3.2 (ver tabla 11).
El perfil de tensin en las barras principales de 22.9kV (5761-LC001-A, 5761-LC-001-B) es de 100.4% de su nominal, esta se
encuentra en el rango de tensin aceptable, por la regulacin
automtica bajo carga de los transformadores 5721-TX-001
operando en tap -5% (ver tabla 11 y 12).
El perfil de tensin en las barras de 13.8kV (3220-LC-201 3220-LC251) es de 100.11% y 100.14% de su nominal, esta se encuentra
en el rango de tensin aceptable; Los transformadores 3220-TX201 y 3220-TX-251 operan con tensin secundaria bajo carga, esto
quiere decir que garantizan un perfil de tensin de 1.0 p.u (ver tabla
11).
Los transformadores 3220-TX-201 y 3220-TX-251 se encuentra en
un rango de cargabilidad aceptable de 96.1 y 95.9 % de su
potencia nominal respectivamente (ver tabla 12).
Para mejorar el perfil de tensin de todas las barras de 4.16 kV,
0.48kV y 0.40kV se regulan la mayora de los taps de los
transformadores menores a 45MVA operando en tap -2.5% (ver
tabla 11 y 12).

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 28 de 32

El factor de potencia en las barras principales de 22.9kV (5761-LC001-A, 5761-LC-001-B) es de 97.0% respectivamente (Ver anexo
5- Reporte ETAP Unifilares).
Segundo

escenario

con

compensacin

reactiva,

solo

el

transformador 5721-TX-001 en operacin y fuera de servicio la


subestacin 3220-LC-201 (Molinos 3221-ML-001-M1, Molinos 3221-ML001-M2):
El transformador 5721-TX-001 est operando al 64.1% de su
potencia nominal en el primario y en el secundario su cargabilidad
es 63.6%, la refrigeracin del transformador es ONAF; Se concluye
que tiene la capacidad de asumir todas las cargas que alimentan
sin presentar sobrecarga, bajo este segundo escenario con
compensacin (ver tabla 14).
El perfil de tensin en todas las barras de 22.9kV, 13.8kV, 0.48kV y
0.4 kV son superiores a 95% de la tensin nominal, superior a los
niveles de tensin admisible en operacin normal segn el punto
3.2 (ver tabla 13).
El perfil de tensin en las barras principales de 22.9kV (5761-LC001-A, 5761-LC-001-B) es de 100% de su nominal, esta se
encuentra en el rango de tensin aceptable, por la regulacin
automtica bajo carga de los transformadores 5721-TX-001 que
est operando en tap -1.25% (ver tabla 13 y 14).
El perfil de tensin en la barra de 13.8kV (3220-LC-251) es de
99.662% de su nominal, esta se encuentra en el rango de tensin
aceptable; El transformador 3220-TX-251 operan con tensin
secundaria bajo carga, esto quiere decir que garantizan un perfil de
tensin de 1.0 p.u (ver tabla 13).
E transformador

3220-TX-251 se encuentra en un rango de

cargabilidad aceptable de 95.9 % de su potencia nominal (ver tabla


14).
Para mejorar el perfil de tensin de todas las barras de 4.16 kV,
0.48kV y 0.40kV se regulan la mayora de los taps de los
transformadores menores a 45MVA operando en tap -2.5% (ver
tabla 13 y 14).
(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 29 de 32

El factor de potencia en las barras principales de 22.9kV (5761-LC001-A, 5761-LC-001-B) es de 99.9% (Ver anexo 5- Reporte ETAP
Unifilares).
El factor de potencia en las barras principales de 22.9kV (5761-LC001-A, 5761-LC-001-B) es de 95.4%, para el variante con
compensacin solo en la barra 5761-LC-001-B (Ver anexo 5Reporte ETAP Unifilares).
Escenario con cargas crticas con prioridad 1 y 2 sin compensacin
reactiva (Solo generadores en operacin):
Los transformadores 5761-TX-901, 5761-TX-902, 5761-TX-903
esta sobrecargado en 125.4% de su potencia nominal en el
primario (ver tabla 16).
El perfil de tensin en todas las barras de 22.9kV, 0.48kV y 0.4 kV
son superiores a 95% de la tensin nominal, superior a los niveles
de tensin admisible en operacin normal segn el punto 3.2 (ver
tabla 15).
El sistema elctrico de la planta minera constancia no puede operar
bajo estas condiciones de transformadores sobrecargados.
Escenario con cargas crticas con prioridad 1 y 3 sin compensacin
reactiva (Solo generadores en operacin):
Los transformadores 5761-TX-901, 5761-TX-902, 5761-TX-903
estn operando al 51.1% de su potencia nominal en el primario; Se
concluye que tiene la capacidad de asumir todas las cargas que
alimentan sin presentar sobrecarga (ver tabla 18).
El perfil de tensin en todas las barras de 22.9kV, 0.48kV y 0.4 kV
son superiores a 95% de la tensin nominal, superior a los niveles
de tensin admisible en operacin normal segn el punto 3.2 (ver
tabla 17).
Para mejorar el perfil de tensin de todas las barras de 4.16 kV,
0.48kV y 0.40kV se regulan los taps de los transformadores
menores a 45MVA operando en tap -2.5%, condicin inicial antes
de que opere bajo el escenario de cargas criticas (ver tabla 17 y
18).
(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 30 de 32

El factor de potencia en las barras principales de 22.9kV (5761-LC001-A, 5761-LC-001-B) es de 84.5% respectivamente (Ver anexo
6- Reporte ETAP Unifilar - cargas criticas).
7.0. RECOMENDACIONES
Segn el flujo de carga para el escenario 2 con compensacin reactiva, la
potencia activa del sistema elctrico de la planta minera Constancia es
115.05MW, este valor es superior a 96MW considerado en el estudio de
pre operatividad, por lo que se recomienda actualizar las potencias segn
memoria de clculo de mxima demanda de las reas de facilidades
mencionadas en el punto 3.1 (Salida +H30 =HZ71 Poza de relaves y
bombas de pozo, Salida +H31 =HZ71 Tajo, Salida +H08 =HZ71 Camp
Site), ya que la suma de sus mximas demandas es 12.71 MW, Que
sobrecarga el transformador de potencia en el segundo escenario sin
compensacin reactiva.
Se recomienda para la condicin crtica (escenario 2 con y sin
compensacin reactiva), el rechazo de carga subestacin 3220-LC-201
(Molinos 3221-ML-001-M1, Molinos 3221-ML-001-M2), en estas
condiciones saldra una lnea de armnicos del sistema elctrico de la
planta minera Constancia.
Se recomienda para el escenario con cargas crticas con prioridad 1 y 2 sin
compensacin reactiva (Slo generadores en operacin), considerar el
incremento de un generador y transformador de iguales caractersticas a
los existentes para asumir la potencia demandada en este escenario.
//Fin de documento.

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 31 de 32

ANEXOS

(4)G69173-D1001-U106_2.doc
Formato base: F4206001.001

Siemens AG 2012 All Rights Reserved


Pgina 32 de 32