RCCB-ID B type
b
v
v
v
062075N_SE-33
PB101616_SE-35
16766
B type
The RCCB-ID B type residual current circuit breakers provide:
b protection in the event of a continuous fault current on three-phase networks
generated by:
v controllers and variable speed drives,
v battery chargers and inverters,
v backed-up power supplies.
16940
PB100572-18
16939
OFsp auxiliary
Accessories
Catalogue numbers
RCCB-ID B type residual current circuit breakers
Type
Width in 9 mm
module
4P
Sensitivity 30 mA
DB123726
Rating
16750
16752
16756
16760
16763
25 A
40 A
63 A
80 A
125 A
300 mA
300 mA s 500 mA
16751
16753
16757
16761
16764
16754
16758
16762
16765
16755
16759
16766
230/400 V
50 Hz
Auxiliary
Type
Width in 9 mm
module
E91415
Contact OFsp
22
12
21
14
Contact
Voltage
1A
110 V DC
6A
230 V AC (AC15)
16940
11
Accessory
Type
Number of pole
4P
version: 1.1
16939
CM902002E.indd
Protection
Earth leakage protection
Connection
Copper cables
Rigid
Flexible or ferrule
6,5 mm
PZ2
RCCB-ID B type
3 N.m
OFsp
0.8 N.m
DB112805
11 mm
Tightening
torque
DB112804
DB123736
Type
1 x 1.5 to 50 mm2
2 x 1.5 to 16 mm2
1 to 1.5 mm2
1 x 1.5 to 35 mm2
2 x 1.5 to 16 mm2
1 to 1.5 mm2
Technical data
OFsp contact status, depending on the
position of the residual current circuit
breaker
400 V
Type
Pollution degree
4 kV
RCCB-ID
B type
Open
Tripped on fault
22/21
Open
12/11
14/11
Closed
Closed
Closed
Open
Open
DB122842
Contact
OFsp
Closed
Electrical characteristics
According to IEC 60947
25/40 A
500 A
63/80 A
800 A
125 A
1250 A
No selective s
250
Selective s
3 k
10,000 A
10,000 A
10,000 A
Additional characteristics
Degree of protection
Device only
Electrical
IP20
IP40 with screw shield
IP40
Insulation classe II
> 2 000 cycles
Mechanical
Operating temperature
-25C to +40C
Storage temperature
-40C to +85C
Weight (g)
Residual current circuit breakers and auxiliary
Type
4P
RCCB-ID B type
OFsp
450
40
1040302_1
DB122838
Dimensions (mm)
2P
RCCB-ID B type
CM902002E.indd
4P
Contact OFsp
version: 1.1