INTRODUCTION
CAM OPERATED ROTARY SWITCHES are defined as set of contacts arranged to
make and break in a sequential fashion by which the connected outputs will either
close or open the circuits.
The main areas of operation are in making, breaking and isolation of power circuits and
switching of auxiliary circuits.
The Cam which does the function of closing & opening of the contacts have multiple
positions ( Rotary Movement) which allows multiple circuit functions controlled through
a single operation.
These switches are suitable for AC as well as DC applications. By virtue of CAM
design functions like Make Before Break type of contacts can be easily achieved. The
number of positions and the switching angle are flexible and will offer the user a
choice to decide based on the requirement.
Another advantage, which can be derived, is the flexibility in the Contact block selection,
which gives the user the option to select the number of contacts as per his requirement.
The choice also covers the rating of the applicable Operational Duty. This will ensure
that the right switch is chosen for the application. CAM operated rotary switches also
offers design flexibility to assemble complex switching programmes to customize any
switching application.
The basic operating mechanism of these switches depends on the type of application.
Quick-Make, Quick-Make-Quick-Break and Spring return operating mechanisms can be
chosen.
Usage of high quality engineering materials for various components ensure that the
switches have long life with higher degree of Electrical and Mechanical endurance.
Double Butt contacts with silver bimetal on copper ensure better making and breaking
over conventional knife-edge switches. Usage of high-grade engineering plastics like
Nylon and Celcon for the components and glass filled polyamide construction provides
greater mechanical strength to the switches.
These Cam operated rotary switches have versatile mounting options to suit any kind
of application. Special mounting options like single hole, door interlocking and padlocking
are also available.
Greater importance is attached to the aesthetics of the switches. These switches
come with attractive combination of knobs and front plates to render greater compatibility
to the panel design. User defined marking on the script plate with different sizes of
script plates eliminate the need to label the switch on the panel.
The enclosed sheets will give an indepth view into the various types of switches,
Mountings, Switching Programmes, Optional Accessories and the Ordering procedure
for CAM OPERATED ROTARY SWITCH.
CONTENTS
CAM ASSEMBLY
CONTACT ASSEMBLY
Salzer switches S, TP & RT series are designed to accomodate two isolated Double break silver alloy contacts per stage at 180 degree
disposition. AC Switches are characterised by Quick make-slow break action by the inbuilt feature in our latching device and cam
construction, these switches can be applied for DC Switching also by Derating and by adding additional contacts in series according to the
DC Switching voltage.
Contacts
S SERIES
STANDARD
Operating Temp
: -25OC to 55oC
Operating Frequency
: Upto 10KHz
Humidity 95% Rh
: 48 hours
TP SERIES
TOUCH PROOF
RT SERIES
REAR TERMINATION
AC Duty Rating
Category
DC Duty Rating
Typical AC Application
Category
Typical DC Application
AC-1
DC-1
AC-3
DC-22
DC-13
Control of DC electromagnets
AC-21A
AC-15
DC-23
AC-23-A
----
-----
"
0.7
1.5
0.7
1.5
M3
0.5
1.5
4
1
2.5
M3.5
0.8
1.5
4
1
2.5
M3.5
0.8
1.5
4
1
2.5
M3.5
0.8
0.7
1.5
0.7
1.5
M3
0.5
mm2
mm2
mm2
mm2
Metric
Nm
Note :-
120V
240V
120V
240V
480V
600V
S10
10
300
0.33
0.75
1
1
-
S6
6
300
0.25
0.5
0.75
1
-
Unit
A
V
HP
HP
HP
HP
HP
HP
3 Phase
Ampere Rating
Operational Voltage
HP Rating
1 Phase
AC Rating Code
CSA / UL RATINGS
15
300
0.33
1
1
2
-
S16
TP16
RT16
20
440
0.33
1
1
2
-
RT20
20
600
1
3
2
5
10
15
S25
TP25
RT25
30
600
1
3
2
5
10
15
S32
TP32
RT32
40
600
2
5
5
10
20
24
55
600
3
7.5
7.5
15
30
40
S40
S63
RT40 RT63
70
600
10
20
40
50
S80
95
600
15
25
50
50
S100
1.5
4
1
2.5
M4
1.2
S200
175
600
20
25
50
50
125
600
15
25
50
50
2.5
10
2.5
6
M5
2
S125
2.5
6
1.5
4
M4
1.2
4
16
2.5
10
M5
2
US
10
35
10
25
2xM5
2.5
US
10
50
10
35
2xM5
2.5
10
70
10
50
M10
2.5
Indian
: IS 13947-1/3/5, 1993
North
CSA 22.2 No.14-1991
American : UL 508 (1994)
6
25
6
16
2xM5
2.5
20
140
20
100
M10
4
250
250
160
160
125
125
100
100
80
80
63
63
40
40
32
32
25
25
20
20
16
16
16
16
10
6
6
4
A
A
400
50
200
25
125
25
100
25
80
25
63
20
40
20
32
10
25
10
20
5
16
5
16
5
10
3
6
3
A
KA
37
55
45
22
45
45
31
45
41
8.3
17.2
37
37
30
41
37
22
33
33
22
33
30
18.5
22
22
15
22
22
3
15
18.5
18.5
11
18.5
18.5
2.5
7.5
15
15
7.5
15
15
2.2
5.5
11
11
5.5
11
11
1.5
4
7.5
7.5
320
690
690
6
425
200
690
690
6
225
125
690
690
6
150
100
690
690
6
125
80
690
690
6
100
3
7.5
7.5
0.55
2.2
5.5
5.5
3
7.5
7.5
0.55
2.2
5.5
5.5
3
7.5
7.5
0.55
2.2
5.5
5.5
1.8
3
0.37
1.5
3
-
1
2.2
0.25
0.8
1.5
-
KW
KW
KW
KW
KW
KW
KW
20
690
415
6
25
16
690
415
6
20
A
V
V
kV
A
S400
S200
S125
S100
S80
S63
RT63
63
690
500
6
80
S40
RT40
40
690
500
6
50
S32
RT32
32
690
415
6
40
S25
RT25
25
690
415
6
32
RT20
RT16
S16
TP16
16
690
415
6
20
S10
TP10
10
440
250
4
12
S6
TP6
6
440
250
4
8
UNIT
Switch Life (Under standard Operating conditions) Mechanical Life : 1 lac Operations @ 300 cycles / hour
Electrical Life : 10,000 Operations at 100 % Rated duty at 120 cycles / hour
AC RATING CODE
TECHNICAL SPECIFICATION
CONNECTING DIAGRAM
1
11 13 15
17 19 21
10 12 14 16 18
20 22
23
24
1 to 12 pole
STAYPUT
60 Degree
90 Degree
Description
Programme Code
Programme Code
Programme Code
No of Stage
1 Pole
2 Pole
3 Pole
4 Pole
5 Pole
6 Pole
7 Pole
8 Pole
9 Pole
10 Pole
11 Pole
12 Pole
61001
61002
61003
61004
61005
61006
61007
61008
61009
61010
61011
61012
61191
61192
61199
61194
61906
-
61195
61198
61197
61196
-
1
1
2
2
3
3
4
4
5
5
6
6
Script Plate
Marking
10
4 to 5 pole
Description
Programme code
61194
No of
Stage
2
2
3
2
1 to 4 pole
Description
Programme code
No of
Stage
1
1
2
2
CONNECTING DIAGRAM
Without Jumper
A1 A2
B1 B2 C1 C2 D1 D2
E1 E2 F1 F2 G1 G2 H1 H2
1 3
10
5 7
12
9 11
1 to 3 Pole
1 to 8 pole
STAYPUT
90 Degree
60 Degree
Description
1 pole
2 pole
3 pole
4 pole
5 pole
6 pole
7 pole
8 pole
No of
Description
Stage
1
1 pole
2
2 pole
3
3 pole
4
4 pole
5
6
7
8
Rating: 6,10,16,25,32,40,63,80,100,125,200 & 400 Amps
Programme code
61025
61026
61027
61028
61029
61030
61031
61032
Feasible Ampere
Programme code
61151
61152
61153
61154
-
SPRING RETURN
Spring Return from 1 to 0
Description
1 pole
2 pole
3 pole
No of
Description
Stage
61361
1
1 pole
61362
2
2 pole
61363
3
3 pole
Feasible Ampere Rating: 6,10,16,25,32,40 & 63 Amps
Programme code
Programme code
61364
61365
61369
WITHOUT JUMPER
45 Degree Spring return without Jumper
Description
1 pole
without jumper
2 pole
without jumper
3 pole
without jumper
No of
Stage
Description
Programme code
62625
1 pole
without jumper
61761
61626
2 pole
without jumper
61762
61627
Programme code
CONNECTING DIAGRAM
A1
B1
C1
D1
E1 F1
F1
H1
J1
K1
L1
M1
A2 B2
C2
D2
E2 F2
F2
H2
J2
K2
L2
M2
2 4
Without Jumper
6 8
10 12 14 16
1 3
5 7
1 to 12 pole
9 11
13 15
1 to 4 Pole
STAYPUT
90 Degree Complete Rotation
No of
Stage
5
6
7
8
9
10
11
12
No of
Description
Programme code
Stage
61037
1
5 pole
61041
61038
2
6 pole
61042
61039
3
61043
7 pole
61040
4
8 pole
61044
--9 pole
61045
--61046
10 pole
--11 pole
61047
--12 pole
61048
Feasible Ampere Rating Applicable : 6,10,16,25,32,40,63,80,100,125,200 & 400 Amps
Description
1
2
3
4
60 Degree
Programme code
pole
pole
pole
pole
-----
SPRING RETURN
45 Degree Spring Return
Description
Programme code
1 pole
61371
2 pole
61372
3 pole
61373
Feasible Ampere Rating: 6,10,16,25,32,40 & 63 Amps
No of
Stage
1
2
3
WITHOUT JUMPER
45 Degree Spring return without Jumper
Description
1
2
3
4
pole
pole
pole
pole
without
without
without
without
Programme code
jumper
61637
61638
jumper
jumper
61639
jumper
61640
Feasible Ampere Rating :
6,10,16,25,32,40,63,80,100,125,200 & 400 Amps
No of
Stage
1
2
3
4
Description
Programme code
61771
-
PROG
NO.
DESCRIPTION
61059
1 Pole-2 Way
61079
2 Pole-2 Way
61099
3 Pole-2 Way
61130
4 Pole-2 Way
61060
1 Pole-3 Way
61080
2 Pole-3 Way
61100
3 Pole-3 Way
61131
4 Pole-3 Way
61061
1 Pole-4 Way
CONNECTING DIAGRAM /
TERMINAL MARKING
1
oA1
2 WAY - 600
61081
2 Pole-4 Way
61101
3 Pole-4 Way
61132
4 Pole-4 Way
61062
1 Pole-5 Way
61082
2 Pole-5 Way
61102
3 Pole-5 Way
61063
1 Pole-6 Way
61083
2 Pole-6 Way
61103
3 Pole-6 Way
61064
1 Pole-7 Way
NO OF
STAGES
oB1
oA2
oC1
oB2
oD1
oC2
oD2
3
1 to 4 pole
4
2
A3o 1
3 WAY - 900
o A1 B3 o 2
o
A2
o B1 C3o 3
o
B2
o C1 D3 o 4
o
C2
o D1
o
D2
o B1
4 WAY - 600
o C1
A4 o
o A2
B4 o
A3 o
o B2
C4 o
B3 o
o D1
4
o C2 D4 o
C3 o
o D2
D3 o
o A1
1
5 WAY - 600
A4 o
o A2
B5 o
2
B4 o
o
A3
6 WAY - 450
o A2
o A3
o C1
3
C4 o
o B2
o C2
o
C3
o B1
B6 o 2
B5 o
C5o
o
B3
o A1
1
A5 o
o
A4
o B1
1 to 3 pole
A6 o
1 to 4 pole
A5 o
5
6
1 to 4 pole
o A1
o C1
o B2
o
B4
1 to 3 pole
C6 o 3
o B3
o
C4
o C2
oC3
C5 o
3
6
9
4
7 WAY - 450
61084
2 Pole-7 Way
7
1 to 2 pole
61065
1 Pole-8 Way
8 WAY - 300
61066
1 Pole-9 Way
9 WAY - 300
61067
1 Pole-10 Way
10 WAY - 300
61068
1 Pole-11 Way
11 WAY - 300
Feasible ampere ratings : 6, 10, 16, 25, 32, 40, 63, 80, 100, 125 & 200 Amps
&
DESCRIPTION
61049
1 Pole-3 Way
61069
2 Pole-3 Way
61089
3 Pole-3 Way
61120
4 Pole-3 Way
61124
5 Pole-3 Way
61126
6 Pole-3 Way
61050
1 Pole-4 Way
61070
2 Pole-4 Way
CONNECTING DIAGRAM /
TERMINAL MARKING
NO OF
STAGES
5
3 WAY - 600
6
8
1 to 6 pole
9
2
4
4 WAY - 900
61090
3 Pole-4 Way
61121
4 Pole-4 Way
61051
1 Pole-5 Way
61071
2 Pole-5 Way
61091
3 Pole-5 Way
61122
4 Pole-5 Way
10
61052
1 Pole-6 Way
61072
2 Pole-6 Way
61092
3 Pole-6 Way
61053
1 Pole-7 Way
61073
2 Pole-7 Way
61093
3 Pole-7 Way
61054
1 Pole-8 Way
61074
2 Pole-8 Way
61094
3 Pole-8 Way
61055
1 Pole-9 Way
61056
1 to 4 pole
8
3
5
5 WAY - 600
1 to 4 pole
3
6 WAY - 60
1 to 3 pole
9
4
7
7 WAY - 450
1 to 3 pole
11
4
8
8 WAY - 450
1 to 3 pole
12
9 WAY - 300
1 Pole-10 Way
10 WAY - 300
61057
1 Pole-11 Way
11 WAY - 300
61058
1 Pole-12 Way
12 WAY - 300
61649
1 Pole-3 Way
Without Off
Without Jumper
61650
1 Pole-4 Way
Without Off
Without Jumper
61670
2 Pole-4 Way
Without Off
Without Jumper
4 WAY - 900
2
4 WAY - 900
4
1 to 2 pole
'
DESCRIPTION
61312
3 ph Line to Line
61313
61314
3 ph Line to Line
Line to Neutral &
without Off
61317
61318
3 ph Line to Line
2 Sources
61311
3 ph Line to Neutral
61319
3 ph Line to Line
Without Off
CONNECTING DIAGRAM/
TERMINAL MARKING
NO OF
STAGES
DESCRIPTION
61336
3 Voltages
Line - Line &
3 Currents
61337
4 Voltages &
3 Currents
61338
3 Voltages
Line to Neutral
& 3 Currents
CONNECTING DIAGRAM /
TERMINAL MARKING
NO OF
STAGES
DESCRIPTION
61325
1 Pole-3
Transformer
With OFF
61321
1 Pole-1
Transformer
61331
CONNECTING DIAGRAM /
TERMINAL MARKING
1 Pole-2
Transformer
NO OF
STAGES
61384
1 Pole-3
Transformer
Without OFF
61326
1 Pole-4
Transformer
With OFF
61327
2 Pole-2
Transformer
W3ith OFF
61328
3 Pole-3
Transformer
With OFF
61329
3 Pole-3
Transformer
Without OFF
61330
4 Pole-4
Transformer
Without OFF
71000
Direct Ammeter
Selector
Without Current
Transformer
2
One Voltage
Transformer
Two Current
Transformer
WATTMETER SWITCH
73071
Two Wattmeter
Method
3 WAY- 900
:
DESCRIPTION
61210
2 POLE
61211
3 POLE
61253
3 POLE SPRING
RETURN
CONNECTING DIAGRAM/
TERMINAL MARKING
Spring
Return
to 0
NO OF
STAGES
DESCRIPTION
CONNECTING DIAGRAM/
TERMINAL MARKING
61200
OFF-STAR-DELTA
61201
Spring Return
From STAR to OFF
61203
Standard
61239
Star Delta
with Sequence
Locking & LMD
Contacts
61240
NO OF
STAGES
DESCRIPTION
61212
2 Speed
Single Winding
61213
2 Speed
Single Winding
61215
2 Speed
Single Winding
For use with
Contactors
61217
2 Speed
Single Winding
Reversing
61219
2 Speed
2 Seperate
Windings
61226
3 Speed
2 Windings
(O-A-B-A)
61243
3 Speed
2 Windings
(O-A-B-B)
CONNECTING DIAGRAM/
TERMINAL MARKING
NO OF
STAGES
DESCRIPTION
CONNECTING DIAGRAM/
TERMINAL MARKING
NO OF
STAGES
Split-phase Start
Split-phase Start
Reversing
61270
Split-phase Start
Reversing
Switching
!
Applications: In Railway coaches for controling the Battery supply, In Dept of Telecommunication panels and special application circuits.
PROG
NO.
DESCRIPTION
61109
CONNECTING DIAGRAM/
TERMINAL MARKING
NO OF
STAGES
1
2 GANG
61117
2
600
61111
61110
61118
3 GANG
3
900
61112
61113
2 Gang, Series
With OFF 1 Pole
2 GANG SERIES
1
61115
2 Gang, Series
With OFF 2 Pole
900
61114
2 Gang, Series
With OFF 3 Pole
3
2 GANG SERIES PARALLEL
61116
2 Gang
Series-Parallel
With OFF 2 Pole
2
0
90
"
Applications: Control switches are a unique alternative for many of the Push Button stations, where it is preferred to control a system with
one switch instead of many Push Buttons. Many positions of the switch are possible to derive combinations.
PROG
NO.
DESCRIPTION
61300
1 Pole STOP-START
With Spring Return
61388
2 Pole STOP-START
With Spring Return
CONNECTING DIAGRAM/
TERMINAL MARKING
NO OF
STAGES
1
spring return
61301
61701
61307
1 Pole STOP-START
With Spring Return
From START to RUN
Without Jumper
STOP-START SWITCH
With Spring Return
to run for 2 units
61707
Without Jumper
61366
Contactor Control
With Spring Return
to OFF
spring
return from
start to 1
spring return
from start
spring
return to 0
61271
Motor Voltage
Control Switch
Description
Front Mounting S25/S32 Switches with 48x48 plate
Rear/Back Mounting with Standard Front Plate
Front Mounting, Standard Mounting Plate
Rear/Back Mounting with next size plate
Front Mounting with next size plate
Single Hole Mounting 48x48 plate for S6 to S32
Single Hole Mounting 32x32 plate for S6 & S10
Din Rail Mounting on 35 mm Rail
Front Mounting with Rectangular padlock
Rear/Back Mounting, Door Interlock + Rectangular Padlock (B42+B30)
Front Mounting with Round padlock
Rear Mounting, Door Interlock + Round Padlock (B33+B42)
Rear Mounting with Door Clutch Mechanism (Door Opens in both pos)
Rear Mounting with Door Interlock
Single Hole Mounting, Key operated without Front Plate
Single Hole Mounting, Key operated with Front Plate
Front Mounting, Knob/handle Operatable, Lockable with Key
Front Mounting with Centre Key Lock
Door Clutch + Rectangular Padlock Mounting Plate at Front
Door Clutch without Padlock, Mounting Plate at Front
Door Clutch, Front Plate of Next size, Mounting Plate at Front
SS Enclosure
Max stages
Aluminium Enclosure
Max stages
PVC/ABS Enclosure
Max stages
PVC/ABS Enclosure with Round Padlock
Max stages
S6/10
S16
Feasibility -
S25/32 S40/63 S80/100/125
S200/400
#
Drilling plan
B3
Drilling plan
6/10 Amps only
B2
3
QB
QD
SQF
2
B
B1
SQ B1
B1
B2
B3
20
36
48
68
68
68
68
9
12
12
15
15
15
15
4.5
4.5
5.5
5.5
5.5
5.5
5.5
24
29
36
46
46
46
46
33
46
52
76
92
88
88
32
48
64
88
88
88
88
9.5 18.5
12
26
15
27
21
33
26
40
32
40
64
40
MAX
12
21
15
10
10
10
4
Features : - * Single hole mounting with std dia 22.5 mm * Eleminates the need for screws / Hardware for panel fixing * Easy Termination *
Suitable upto 32 Ampere
Locking lever
3
13
3 Max.
Panel gap
23
Length L = No of Stages x S + W
TYPE
S6/S10/TP6/TP10
S16/TP16/RT16
S25/S32/RT25/RT32
CODE
B19
B14
B19
B19
33
33
46
52
32
48
48
48
9.5
9.5
12
15
10
13
13
13
28.5
28.5
36
37
MA-X
12
12
21
15
Features : - * Key Operated safety switch, prevents operational access to unauthorised personnel., * Available with or without Front plate
* Suitable up to 32 Ampere.
Length L = No of Stages x S + W
3 to 5
Panel gap
Drilling plan
B3
B2
$
B1
FRONT PLATE
B1
B2
B3
MAX
23
23
13.5
13.5
2.5
2.5
46
52
28
28
12
15
37
38
5
5
Length L = No of Stages x S + W
B1
B2
B3
MAX
36
36
68
68
68
68
12
12
15
15
15
15
4.5
4.5
5.5
5.5
5.5
5.5
46
52
76
92
88
88
65
65
95
95
95
95
26
26
31
31
31
31
12
15
21
26
32
64
26
27
33
40
40
40
12
8
6
6
6
3
Features : - * Four Hole Rectangular Padlockable mounting * Secure with max four padlocks in OFF position.* Prevents Operational Acess
to Unauthorised Personnel * Suitable for switches with 900 Switching angle .
Length L = No of Stages x S + W
B1
B2
F1
F2
F3
MAX
S16/TP16/RT16
S25/S32/RT25/RT32
S40/S63/RT40/RT63
S80/S100/S125
S200
S400
48
48
68
68
68
68
12
12
15
15
15
15
46
52
76
92
88
88
75
75
98
98
98
98
102
102
126
126
126
126
13.5
13.5
16
16
16
16
23
23
25
255
25
25
12
15
21
26
32
64
26
27
33
40
40
40
12
8
6
6
6
2
Features : - * Knob / handle operatable Switch * With Key lockable Assembly prevents switching by unauthorised personnel. *Key lock / Key
removable only in OFF position * Lock Assembly can also be provided on top
TYPE
S16/TP16/RT16
S25/S32/RT25/RT32
S40/S63/RT40/RT63
Length L = No of Stages x S + W
B2
B4
B5
MAX
15
15
15
23
23
23
43.5
43.5
43.5
46
52
76
64
64
64
12
15
21
45
45
47
12
12
6
%
B 31
TYPE
S16/TP16/RT16
S25/S32/RT25/RT32
S40/S63/RT40/RT63
42
42
48
110
125
175
80
100
125
66
70
90
60
90
80 115
105 155
STAGES
3
2
2
Features : - * Switches Mounted in sheet metal enclosures *Provides protection from dust & hazardous enviorement. *Knob / Handle
operatable * Suitable for switches upto 32 Ampere
M 17
TYPE
S6/S10/TP6/TP10
S16/TP16/RT16
S25/S32/RT25/RT32
16 Ampere For/ Reverse
A1
A2
A3
D1
D2
D3
70
70
70
81
60
60
60
65
4
4
4
5
85
85
85
75
89
89
89
75
98
98
98
110
MAX
4
4
3
-
Features : - * Four hole base mounted on Rear side of the Panel * Knob/ Handle operatable
Length L = No of Stages x S + W
S6/S10/TP6/TP10
S16/TP16/RT16
S25/S32/RT25/RT32
S40/S63/RT40/RT63
S80/S100/S125
S200
S400
&
A1
A2
B1
B2
B3
MAX
36
48
48
68
81
81
81
M5
M5
M5
M6
M6
M6
M6
36
36
48
68
68
68
68
9
12
12
15
15
15
15
4.5
4.5
4.5
5.5
5.5
5.5
5.5
48
60
60
84
101
101
101
32
48
64
88
88
88
88
4.5
3.5
3.5
5
5
5
8
9.5
12
15
21
26
32
64
22
30
31
41
48
48
48
10
12
8
6
6
6
3
Length L = No of Stages x S + W
TYPE
S6/S10/TP6/TP10
S16/TP16/RT16
S25/S32/RT25/RT32
B1
B2
B3
MAX
20
36
48
9
12
12
4.5
4.5
5.5
33
46
52
32
48
64
9.5
12
15
28.5
37
38
10
12
8
Features : - * Mounted on Rear side of the panel and operated from the front door * Door interlockable mechanism & panel door openable
only in OFF position. * Provides a safety feature.* Knob / Handle operatable
Length L = No of Stages x S + W
A1
A2
B1
B2
B3
MAX
48
48
81
81
81
81
M5
M5
M6
M6
M6
M6
48
48
68
68
68
68
15
15
18
18
18
18
4.5
4.5
5.5
5.5
5.5
5.5
60
60
101
101
101
101
64
64
88
88
88
88
3.5
3.5
5
5
5
5
45
41
46
46
46
46
22
22
26
26
26
34
12
15
21
26
32
64
54
55
66
72
72
72
8
8
6
6
6
3
Features : - * Mounted on rear side of the panel and operated from the front door * Door interlockable mechanism & door openable only in
OFF position. with round padlockable device.* Secure with max 3 Padlocks in OFF position
Length L = No of Stages x S + W
B 34
* IP 55 Protection front
TYPE
A1
A2
B1
B2
B3
MAX
S16/TP16/RT16
S25/S32/RT25/RT332
S40/S63/RT40/RT63
S80/S100/S125
S200
S400
48
48
68
81
81
81
M5
M5
M6
M6
M6
M6
36
36
68
68
68
68
15
15
18
18
18
18
4.5
4.5
5.5
5.5
5.5
5.5
60
60
84
101
101
101
65
65
95
95
95
95
3.5
3.5
5
5
5
5
45
41
46
46
46
46
24.5
24.5
33.5
33.5
33.5
33.5
12
15
21
26
32
64
54
55
66
72
72
72
6
6
6
6
6
3
'
KNOBS/HANDLE COLOURS
RED
BLACK
TD - TEAR DROP
CODE - TD
S6/S10/TP6/TP10
S16/TP16/RT16
S25/S32/RT25/RT32
S40 & ABOVE
27
27
36
50
41
41
52
70
25
25
31
42
21
21
25
33
CODE - FL
S6/S10/TP6/TP10
S16/TP16/RT16
S25/S32/RT25/RT32
S40 & ABOVE
16.5
27
36
50
22
39
50
68
13.75
24
27
42.5
18
24
25
32
LV - LEVER HANDLE
90
FL - FLAG KNOB
CODE - PG
Applicable for
S16 / TP16 / RT16
S25 / S32 / RT25 / RT32
S40 / S63
CODE - BG
Applicable for
S16 / TP16 / RT16
S25 / S32 / RT25 / RT32
S40 / S63
CODE - LV
Applicable for
S80 / S100 / S125
S200 / S400
ACCESSORIES
EXTENDED TERMINALS
S16
S25
S63
S400
PUSH ON TERMINALS
S16
BIGGER
STYLE
FRAME SIZE
S6/S10
TP6/TP10
ACCESSORIES
--
SHROUDING COVERS
Rectangular
S16
TP16
RT16
S6/S10
TP6/TP10
L
S16
TP16
RT16
S25/S32
RT25/RT32
TYPE
S25/S32
RT25/RT32
S63
S200
--
175
210
175
210
115
200
110
200
100
90
115
100
NO. OF
STAGES
3
3
3
3
S16
TP16
RT16
--
64 x 80
D
S25/S32
RT25/RT32
S16
TP16
RT16
TYPE
S25/S32
S63
65+0.2
89+0.2
H
2 STAGE
48
118
3 STAGE
63
182
CODE - YR
CODE - GB
CODE - BB
CODE - AB
(d) Each position should be identified and Script plate marking required
in those postions should be mentioned .
Switch Positions
NIGHT LAMP
"
Programme Code
Example:-
Type
Ampere
Mounting
Knob
Type Selection
Type
S-Series
Touch Proof
Rear Acess Termination
DC Switches
Phase Selector only for
1 pole 3 way with OFF
Prog Code
Pg 3
Pg 4
Pg 5
Pg6
Pg 7
Pg 8 & 9
Pg 10 & 11
Pg 12
Pg 13
Ampere Selection
Color
25 to 63 Amps
Mounting Selection
For Mounting Styles
Refer Table on Page 13
Ampere
6
10
16
20
25
32
40
50
63
80
100
125
160
200
250
300
400
500
600
800
Code
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
CODE - FH
CODE - PG
CODE - BG
CODE - LV
TEAR DROP
FLAG KNOB
PISTOL GRIP
BALL GRIP
LEVER HANDLE
CODE - GB
CODE - BB
CODE - AB
OPERATIONS
LMD operations
DESCRIPTION
UNIT
Ue
Uimp
Ith
Ie
20-240V AC
380-440V AC
min
max
min
max
Flexible wire
Terminal Screw
Terminal Tightening Torque
CSA / UL RATINGS
Voltage Rating
Ampere Rating
V ac
V dc
kV
A
SG25
690
250
6
32
SG32
690
250
6
40
A
A
8
5
14
6
25
32
kA
10
10
1.5
4
1
2.5
M4
1.2Nm
2.5
6
1.5
4
M4
1.2Nm
mm2
mm2
V
A
VA Rating
SIL Operations
This device fitted along with this breaker
control switch will act as a blocking device
for consecutive closing of the switch, will
prevent closing coil of the breaker getting
charged repeatedly and hence eliminates
burning of this closing coil.
TECHNICAL SPECIFICATION
GENERAL :ENDURANCE
Mechanical * - 1 Lac Operations at 300
cycles /hour
Electrical * - 10,000 Operations at 120
cycles/ hour
600
600
20
30
AC-720 VA
DC-275 VA
SG 25
No of
Voltage Contacts in
series
50 V
125 V
250 V
1
2
3
1
2
3
1
2
3
Resistive
Amps
20
3
20
1.0
5
20
SG 32
Inductive L / R Amps
10
m sec
20
m sec
40
m sec
20
2.5
15
20
0.5
2
10
15
20
1.5
10
20
0.3
1.0
4
6
14
20
1.0
5
10
0.2
0.5
1
Resistive
Amps
25
5
25
1.2
6
25
Inductive L / R Amps
10
m sec
20
m sec
40
m sec
25
3
18
25
0.6
2.5
12
18
25
2
12
25
0.4
1.2
5
8
18
25
1.2
6
12
0.3
0.6
1.2
B03
seq.locking
&LMD
13
17.50
LxW
LMD
Contacts
MxW
Main
Contacts
Panel gap
3 to 5
65
SQ64
12
5.5
50
NEUTRAL
C
L
O
S
E
T
R
I
P
80
SALZER
SQ48
spring return
stayput 15
DRILLING PLAN
TYPE
SG25
SG32
D
58
62
W
14
16
B90
17.50
LxW
LMD
Contacts
MxW
Main
Contacts
Panel gap
3 to 5
55
SQ64
12
5.5
40
NEUTRAL
T
R
I
P
C
L
O
S
E
75
SALZER
SQ48
spring return
stayput 15
R
DRILLING PLAN
TYPE
SG25
SG32
D
58
62
W
14
16
Example:-
10
Digit 1
Digit 5
Digit 2
Sequence Locking
If required
Not required
Code
Q
O
Digit 3
Latching Mechanism
Spring Return
Stayput
Code
S
C
Digit 6
No of LMD Contacts
Position
Description
1 Contact
2 Contact
3 Contact
4 Contact
5 Contact
6 Contact
If not required
in Close
Code
L
D
Code
E
F
Digit 8, 9, 10
Mounting
Standard Front Mounting
Barrei Lock with Centre
Key
&
Code
1
2
3
4
5
6
0
Digit 7
Ampere Rating
25 Ampere
32 Ampere
Digit 4
LMD Contacts
If required
Not required
Code
B03
B90
'
DC SWITCHES
Features
Applications;
DC power circuits
D16 D63
3 to 5
Panel gap
Drilling plan
B3
SQ F
B2
TYPE
D16
D25/32
D40/63
Stages
D16
D25/32
D40/63
Length in
mm
SQ B1
B1
48
48
68
B2
12
12
15
B3
5.5
5.5
5.5
D
50
50
70
F
64
64
64
S
12
15
21
10
11
12
62
65
69
74
80
90
86
95
111
98
110
132
110
125
153
122
140
174
134
155
195
146
170
216
158
185
237
170
200
258
182
215
279
194
230
300
TECHNICAL SPECIFICATION
DC
RATINGS
DESCRIPTION
GENERAL
250V
460V
48V
70V
180V
250V
380-440V
D16
D25
D32
D40
D63
20
32
40
50
80
16
25
32
40
63
10
16
25
32
40
Hp
10
14
20
25
16
25
32
40
63
Fuse Protection
16
25
32
40
63
kA
10
10
20
20
[Rigid] min
mm2
1.5
1.5
1.5
1.5
1.5
[Flex]
mm2
10
16
Nm
0.8
1.2
1.2
16
10
10
Terminal
Cross Section
Tightening Torque
Maximum Contact Stages
!
110V
UNIT
max
DC SWITCHES
Features
Applications
CPRI Tested.
170PCD
D100 - D500
236.00
24
S
0.8
1.5
3.1
1.5
138.5
D40 R
UNIT
D100
D200
D300
D400
D500
VDC
VAC
A
A
Deg
250
460
100
125
90
9
250
460
200
250
90
9
250
460
300
375
90
9
250
460
400
500
90
9
250
460
500
625
90
9
170PCD
1
236.00
DESCRIPTION
DUTY RATING - DC 22A L/R 2M sec
Operational Voltage
Voltage for AC Rating
Operational Current
Thermal Current ? I th ?
Switching Angle
Maximum Contact Stages
24
S
0.8
1.5
1.5
L
3.1
138.5
!
D16 - D63
TYPE
B1
48
48
68
D16
D25 / D32
D40 / D63
Stages
Length in
mm
D100 - D500
D16
D25/32
D40/63
1
62
65
69
2
74
80
90
3
86
95
111
B2
12
12
15
4
98
110
132
B3
5.5
5.5
5.5
5
110
125
153
6
122
140
174
D
50
50
70
7
134
155
195
F
64
64
64
8
146
170
216
S
12
15
21
9
158
185
237
10
170
200
258
11
182
215
279
12
194
230
300