CP2-0000-00-JI-SPE-0006
Rev G2
Page 1 of 39
CP2-0000-00-JI-SPE-0006
DISTRIBUTION LISTING
Copy Number
Master (signed
electronic)
Master
(electronic)
Document Holder
Document Control Centre (DCC)
TeamBinder
Distribution List
001
002
003
004
005
006
007
008
009
010
REVISION CONTROL
Issue
Description of Change
Date
REV A1
Interdisciplinary Check
14/4/2010
REV G1
27/5/2010
REV G2
6/8/2010
Rev G2
Page 2 of 39
CP2-0000-00-JI-SPE-0006
ABBREVIATIONS
Rev G2
AWA
EPC
EPR
GSWA
GSWB
ITP
LSZH
LV
PVC
QA
SDRL
SHF2
XLPE
Page 3 of 39
CP2-0000-00-JI-SPE-0006
PREFACE
Purpose
The purpose of this specification is to detail the minimum requirement of Instrument Cables for
Cendor Phase 2 Field Development Project in accordance with Petrofac Group practice.
Review and Update
The Technical Authority for this document is the Project Engineering Manager who should also be
consulted if further information on the subject matter is required. The Technical Authority is also
responsible for the accuracy of information contained within this document.
This document will be re-issued before the award of EPC contracts.
The project management system permits continuous update to the document.
Responsibility of Copyholders
The master copy of this document is held within project records and electronic copy is accessible
to all project personnel. Paper copies shall be issued to external parties in Petrofac and
Contractors as registered copy holders.
It is the responsibility of the registered copyholder(s) to maintain the accuracy of this document by
ensuring that all updates are promptly incorporated and acknowledged.
Furthermore, the registered copyholder must at all times maintain custody of this document unless
prior approval is given by the Document Owner.
Rev G2
Page 4 of 39
CP2-0000-00-JI-SPE-0006
TABLE OF CONTENTS
DISTRIBUTION LIST
REVISION CONTROL
ABBREVIATIONS
PREFACE
1.0
INTRODUCTION.................................................................................. 6
1.1
1.2
Scope of Supply.................................................................................. 6
1.3
1.4
Definitions ........................................................................................ 7
1.5
Order of Precedence............................................................................ 7
1.6
1.7
Language.......................................................................................... 8
2.0
2.1
2.2
Regulations ......................................................................................10
3.0
3.1
3.2
Environmental Conditions.....................................................................11
3.3
Materials .........................................................................................11
3.4
HSE Requirements..............................................................................11
3.5
4.0
4.1
5.0
5.1
5.2
6.0
6.1
6.2
Inspection .......................................................................................33
6.3
Testing ...........................................................................................33
7.0
8.0
9.0
GUARANTEE.................................................................................... 38
10.0
DOCUMENTATION ............................................................................. 39
Rev G2
Page 5 of 39
1.0
INTRODUCTION
1.1
Scope of Specification
CP2-0000-00-JI-SPE-0006
This document together with the referenced document, defines the minimum
requirements for the design, manufacture, construction, tests and delivery of instrument
cables for Cendor Phase 2 Development Project.
The Supplier shall ensure that the cables supplied are complying with requirement stated
in codes and standards stated here in; which form an integral part of this specification.
The Supplier shall ensure that all equipment and services supplied are meeting the
requirements of this specification, codes and standards nominated here in whether the
equipment are supplied by Supplier directly or by Suppliers Sub-Contractor.
1.2
Scope of Supply
The supplier shall, wherever possible, draw upon his existing, pre-engineered or standard
designs to satisfy the requirements of the specifications.
The scope of supply shall include but not limited to the following:
a)
Performance Testing.
b)
c)
All the identified certificates including but not limited to materials and design
verification.
d)
e)
f)
g)
Supplier may quote alternate arrangements and specifications if they are equal to or
exceed the general requirements of this specification. These alternates shall be clearly
highlighted in Suppliers bid for Purchaser evaluation and approval.
The Supplier shall submit full technical details of his equipment which meets the
requirements detailed herein. Aspects of the requirements, which cannot be met, shall
be identified and the variances explained.
The cables shall be DNV, ABS or LR approved for marine application.
1.3
Project Specifications
Equipment shall be designed in accordance with the latest edition of the following
project specifications:
PETROFAC Project Documents
CP2-0000-00-ST-SPE-0001
Rev G2
Page 6 of 39
CP2-0000-00-ST-SPE-0002
CP2-0000-00-ME-DBM-0001
1.4
CP2-0000-00-JI-SPE-0006
Definitions
The following definitions (including abbreviations) shall apply throughout this document:
1.5
COMPANY
PML
PMT
CP2
Contractor
Sub-Contractor
Supplier
Shall
Should
May
Purchaser
Order of Precedence
In the event of any conflict arising between this Specification and other documents listed
herein, refer comments to the Purchaser for clarification before design or fabrication
commences. The order of precedence that applies is as follows:
Rev G2
1.
2.
3.
Project Datasheets.
Page 7 of 39
1.6
CP2-0000-00-JI-SPE-0006
4.
This Specification.
5.
Equipment specification
6.
Project Drawings.
7.
Project Specifications.
8.
9.
Supplier Exceptions
The Supplier shall be responsible to submit, together with the Tender, a list of deviations
or exceptions to this Specification. In the absence of any exceptions, it will be construed
that the Supplier fully complies with this Specification.
1.7
Language
All documentation and communications shall be in the English language.
Rev G2
Page 8 of 39
2.0
CP2-0000-00-JI-SPE-0006
2.1
Rev G2
Page 9 of 39
2.2
CP2-0000-00-JI-SPE-0006
Regulations
All equipment shall comply with the requirements of the appointed Classification Society
which is a member of IACS. The following classification societies are considered
acceptable:
Rev G2
DNV
BV
Bureau Veritas
ABS
LR
Page 10 of 39
3.0
GENERAL REQUIREMENTS
3.1
CP2-0000-00-JI-SPE-0006
The cables shall be designed for minimum life duration of 10 years for FPSO and 20 years
for Wellheads Platforms, in the environment and for the duty specified herein and on the
Project Data Sheets.
3.2
Environmental Conditions
Cables shall be installed on FPSO and Wellheads for all environmental conditions specified
in Design Basis Memorandum CP2-0000-00-ME-DBM-0001.
3.3
Materials
The cables manufactured shall also be a product regularly manufactured by the Supplier.
The cable drum radius should not be less than 125% of the minimum bending radius of
the cables.
Cables shall be manufactured in one continuous length as per ordered drum length.
Cable conductors shall be made of tinned concentric stranded, continuous copper
conductor made up from fully annealed round copper wires free from imperfections in
accordance to IEC 60092. Non-hygroscopic fillers shall be used to maintain a circular
formation.
The cable inner and outer sheath shall be extruded over the insulation and armour. They
shall be resistant to scuffing, rough handling, UV radiation, heat, crude oil, diesel, and
natural gas corrosive agents normally found in crude oil processing facility.
Specific for wellhead applications, cables supplied and manufactured shall be mudresistance of SHF2-Mud type in accordance with NEK 606.
The cable outer sheath shall be coloured according to the cable type and embossed with
the cable identification at one (1) meter intervals.
For non-critical equipment or circuits, cables shall as a minimum be flame retardant
complying with IEC 60332 Part 2 Cat A for instrumentation and communication cables
with the oxygen index of not less than 30 and acidic emission less than 0.5% in
accordance with IEC 60754.
3.4
HSE Requirements
The Supplier shall be responsible for ensuring that the goods and services supplied meet
all applicable regulations on health, safety and environmental issues.
Where required by the procurement documentation, the Supplier shall complete HSE
questionnaires and provide information that may include:
Rev G2
Page 11 of 39
3.5
CP2-0000-00-JI-SPE-0006
Transportation Loads
Supplier to ensure the cables are able to withstand without damage during transfer
handling and the forces during transportation through proper packaging, supports, etc as
defined in CP2-0000-00-ST-SPE-0001, General Design Requirements for Fixed Offshore
Structure and CP2-0000-00-ST-SPE-0002, General Design Requirements for Floating Deck
Structure
Rev G2
Page 12 of 39
CP2-0000-00-JI-SPE-0006
4.0
4.1
4.1.1
I2
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
Outer sheath
Colour
Cable identification:
4.1.2
1.0mm2
10
1.0mm2
20
1.0mm2
Core Identification
Black and White
Black, White and
number
Black, White and
number
Black, White and
number
Black, White and
number
Rev G2
Cable type
I3
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Page 13 of 39
CP2-0000-00-JI-SPE-0006
Screen
Bedding
SHF2
Armour
Outer sheath
Outer sheath
Colour
Cable identification:
4.1.3
1.0mm2
10
1.0mm2
20
1.0mm2
Core Identification
Black and White
Black, White and
number
Black, White and
number
Black, White and
number
Black, White and
number
I4
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
Outer sheath
Colour
Cable identification:
Rev G2
Page 14 of 39
CP2-0000-00-JI-SPE-0006
4.1.4
1.0mm2
10
1.0mm2
20
1.0mm2
Core Identification
Black and White
Black, White and
number
Black, White and
number
Black, White and
number
Black, White and
number
I5
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
Outer sheath
Colour
Cable identification:
Rev G2
1.0mm2
10
1.0mm2
Core Identification
Red, Black and White
Red, Black and White and each core printed
with triad numbers
Red, Black and White and each core printed
with triad numbers
Red, Black and White and each core printed
with triad numbers
Page 15 of 39
4.1.5
CP2-0000-00-JI-SPE-0006
I6
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
Outer sheath
Colour
Cable identification:
4.1.6
1.0mm2
10
1.0mm2
Core Identification
Red, Black and White
Red, Black and White and each core printed
with triad numbers
Red, Black and White and each core printed
with triad numbers
Red, Black and White and each core printed
with triad numbers
Rev G2
Cable type
I7
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Page 16 of 39
Outer sheath
CP2-0000-00-JI-SPE-0006
Outer sheath
Colour
Cable identification:
4.1.7
1.0mm2
10
1.0mm2
Core Identification
Red, Black and White
Red, Black and White and each core printed
with triad numbers
Red, Black and White and each core printed
with triad numbers
Red, Black and White and each core printed
with triad numbers
Fire and Gas, Vital Services and Fire Survival (Fire Resistant and Flame Retardant)
Type F2
Fire survival multi-pair individually screened cable for use in fixed installation, indoors
and outdoors.
Fire resistant characteristics tested as per IEC 60331.
Flame retardant characteristics tested to IEC 60332-3 Category A
Cable type
F2
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
:
halogen free
Outer sheath
Colour
Cable identification:
Rev G2
Page 17 of 39
CP2-0000-00-JI-SPE-0006
4.1.8
1.5mm2
10
1.5mm2
20
1.5mm2
Core Identification
Black and White
Black, White and
numbers
Black, White and
numbers
Black, White and
numbers
Black, White and
numbers
Fire and Gas, Vital Services and Fire Survival (Fire Resistant and Flame Retardant)
Type F3
Fire survival multi-pair collectively screened cable for use in fixed installation, indoors
and outdoors.
Fire resistant characteristics tested as per IEC 60331.
Flame retardant characteristics tested to IEC 60332-3 Category A
Cable type
F3
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
:
halogen free
Outer sheath
Colour
Cable identification:
Rev G2
Page 18 of 39
CP2-0000-00-JI-SPE-0006
4.1.9
1.5mm2
10
1.5mm2
20
1.5mm2
Core Identification
Black and White
Black, White and
numbers
Black, White and
numbers
Black, White and
numbers
Black, White and
numbers
Fire and Gas, Vital Services and Fire Survival (Fire Resistant and Flame Retardant)
Type F4
Fire survival multi-pair individually and collectively screened cable for use in fixed
installation, indoors and outdoors.
Fire resistant characteristics tested as per IEC 60331.
Flame retardant characteristics tested to IEC 60332-3 Category A
Cable type
F4
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
:
halogen free
Outer sheath
Colour
Cable identification:
Rev G2
Page 19 of 39
CP2-0000-00-JI-SPE-0006
4.1.10
1.5mm2
10
1.5mm2
20
1.5mm2
Core Identification
Black and White
Black, White and
numbers
Black, White and
numbers
Black, White and
numbers
Black, White and
numbers
Fire and Gas, Vital Services and Fire Survival (Fire Resistant and Flame Retardant)
Type F5
Fire survival individually triad screened multitriad cable for use in fixed installation,
indoors and outdoors.
Fire resistant characteristics tested as per IEC 60331.
Flame retardant characteristics tested to IEC 60332-3 Category A
Cable type
F5
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
:
halogen free
Outer sheath
Colour
Cable identification:
Rev G2
Page 20 of 39
CP2-0000-00-JI-SPE-0006
1.5mm2
10
1.5mm2
Core Identification
Red, Black and White
Red, Black and White and each core printed with
triad numbers
Red, Black and White and each core printed with
triad numbers
Red, Black and White and each core printed with
triad numbers
Triplets shall be identified by having the triple number printed on the insulation in
contrasting colour.
4.1.11
Fire and Gas, Vital Services and Fire Survival (Fire Resistant and Flame Retardant)
Type F6
Fire survival collectively triad screened multitriad cable for use in fixed installation,
indoors and outdoors.
Fire resistant characteristics tested as per IEC 60331.
Flame retardant characteristics tested to IEC 60332-3 Category A
Cable type
F6
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
:
halogen free
Outer sheath
Colour
Cable identification:
Rev G2
Page 21 of 39
CP2-0000-00-JI-SPE-0006
1.5mm2
10
1.5mm2
Core Identification
Red, Black and White
Red, Black and White and each core printed with
triad numbers
Red, Black and White and each core printed with
triad numbers
Red, Black and White and each core printed with
triad numbers
Triplets shall be identified by having the triple number printed on the insulation in
contrasting colour.
4.1.12
Fire and Gas, Vital Services and Fire Survival (Fire Resistant and Flame Retardant)
Type F7
Fire survival collectively and individually triad screened multitriad cable for use in fixed
installation, indoors and outdoors.
Fire resistant characteristics tested as per IEC 60331.
Flame retardant characteristics tested to IEC 60332-3 Category A
Cable type
F7
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
:
halogen free
Outer sheath
Colour
Cable identification:
Rev G2
Page 22 of 39
CP2-0000-00-JI-SPE-0006
1.5mm2
10
1.5mm2
Core Identification
Red, Black and White
Red, Black and White and each core printed with
triad numbers
Red, Black and White and each core printed with
triad numbers
Red, Black and White and each core printed with
triad numbers
Triplets shall be identified by having the triple number printed on the insulation in
contrasting colour.
4.1.13
Fire and Gas, Vital Services and Fire Survival (Fire Resistant and Flame Retardant)
Type F8
Fire survival pair collectively screened cable for addressable fire alarm system, indoors
and outdoors.
Fire resistant characteristics tested as per IEC 60331.
Flame retardant characteristics tested to IEC 60332-3 Category A
Cable type
F8
Rated voltage
150/250V
Construction
IEC 60092
Conductors
Insulation
Screen
Bedding
SHF2
Armour
Outer sheath
:
halogen free
Outer sheath
Colour
Cable identification:
Rev G2
Core Identification
Black and White
Page 23 of 39
4.1.14
CP2-0000-00-JI-SPE-0006
P5
Rated Voltage
Conductors :
Insulation :
Bedding
Armour
Outer sheath
colour.
:
600/1000V
Cable identification
No. of cores
2 (L1,N) or (L1,L2)
3 (L1,L2,L3)
4 (L1,L2,L3,N)
5 and above
4.1.15
Core Identification
Black with numbering 1 and 2
Brown, Black, Grey
Brown, Black, Grey, Blue
Black number on while sheath
TC
Conductors
Copper-Constantant
Insulation
Polyethylene
Drain Wire
Tinned Copper
Screen
Binding
PETP tape
Bedding
Polyethylene black
Armour
Sheath
Rev G2
Page 24 of 39
Cable identification
CP2-0000-00-JI-SPE-0006
Outersheath colour
Black
Certification
applicable drums
No. of Min. Conductor size
pairs
10
0.5 mm2
20
0.5 mm2
4.1.16
Type T1-Fixed Installation for Telecom Control, Alarm & other mandatory systems.
Multipair cable, collective screened, armoured,
outersheath, Aluminium foil screen and drain wires.
Polyethylene
insulated,
Cable type
T1
Construction
Voltage Rating
100 V (Min)
Conductors
Insulation
Silicon rubber
Drain Wire
Tinned Copper
Armour
PVC
Sheath
:
Flame retardant, PVC outer sheath. Oxygen index
greater than 30 by ASTM D2863-74 test, HCL emission
when burned not
greater than 17% by weight
Cable identification
Outersheath colour
Black
Rev G2
Page 25 of 39
4.1.17
CP2-0000-00-JI-SPE-0006
Type T2-Fixed Installation for Telecom Control, Alarm & other mandatory systems.
Armoured, Individual pair, Silicon rubber insulated, Colour coded twisted pair
individually screened aluminium foil screen with tinned copper drain wire EMA/EVA
sheathed SWB.
Cable type
:
T2
Construction
:
Colour coded twisted together. Pairs shall be laid up
and individually screened. Aluminium foil screen/EMA sheath over tinned copper drain
wire. Pairs shall be identified by numbers.
Voltage Rating
100 V (Min)
Conductors
Insulation
Silicon rubber
Drain Wire
Armour
Sheath
:
Flame retardant, EMA sheathed to IEC 60 332 part 3
Cat. A. Both EMA bedding and outer sheath shall be the type with oxygen index not less
than 30, temperature index not less than 260 Deg. C and HCL emission of maximum 0.5 %
( by weight ).
Cable identification
4.1.18
Core identification
Outersheath colour
Black
No of Pairs
1
2
5
10
1
2
5
10
2.5
2.5
2.5
2.5
Type CAT5e - For low speed/high speed data in fixed installations indoor for Telecom
circuits
Collective screened, multipair cable, braided, Polyethylene insulated and Steel Wire
Braided (SWB)
Rev G2
Cable type
CAT5e
Construction
Page 26 of 39
CP2-0000-00-JI-SPE-0006
Voltage Rating
600V
Temperature Rating
Construction
TIA/EIA-568-B.2-1
Conductors
Insulation
HD Polyethylene
Collective Screen
Outer Sheath
Armour
Flame Test :
Cable identification
Outersheath colour
Black
Frequency
100 Hz
Attenuation
22 dB @100 MHz
Crosstalk (ELFEXT)
Return Loss
Delay skew
Nominal impedence
Wire Colour
Pair No.
Pair 1
Pair 2
Pair 3
Pair 4
4.1.19
A-wire
White
White
White
White
B-wire
Blue
Orange
Green
Brown
Rev G2
Multimode fibre
IEC 60793
Page 27 of 39
CP2-0000-00-JI-SPE-0006
O2
Armour
Inner Sheath
Polyethylene
Outer sheath
Flame retardant (IEC 60332 Part 1), low smoke, zero halogen
thermoset
Black
Outersheath
colour
Single Mode Fibre
Core diameter
9 microns
Cladding diameter
125 microns
Coating diameter
250 microns
Attenuation
Bandwidth
~ 100 Terahertz
Dispersion (max)
Multimode Fibre
Core Diameter
62.5 microns
Cladding Diameter
125 microns
Coating Diameter
250 microns
Attenuation
Bandwidth
Note:Supplier shall quote in the tender the termination and joints suitable for the type
of the FO cable specified.
4.1.20
Rev G2
Conductors
Video
: Coaxial, 75
Telemetry
Power
Page 28 of 39
4.1.21
CP2-0000-00-JI-SPE-0006
Composition
Video
: 1 coaxial
Telemetry
Power
: 3 cores
Colour coding
Insulation
Insulation resistance
: 5000 M / km minimum
Insulation thickness
Flame retardant
: LSZH
Armour
: Black
Construction
Voltage Rating
300V RMS
Conductors
Insulation
Screen
Inner Sheath (Shield)
Outer Sheath
Armour
Core Identification
Cable Marking
Rev G2
polyethylene
Page 29 of 39
CP2-0000-00-JI-SPE-0006
Oil Resistance
IEC 60092-359
UV Resistance
UL 1581, Abs.1200
Temperature Rating
-40C to +105c
10 x Cable O.D.
Max. Tension
90N
: 23.5/km
: 100 10
: < 3 dB/km
: 36.6/km
: 4.8pF/m
: 300V
Test Voltage
: 1500V
Rev G2
Page 30 of 39
CP2-0000-00-JI-SPE-0006
5.0
5.1
Marking on Cables
The following information shall be indelibly printed in English (all dimension in metric),
on the surface of the cable jacket at regular interval over the entire length of the cable
for each of the identification.
Voltage Grade
Cable type
Number of Conductors
Conductor Size/Sizes
IEC Standard
Suppliers name
Year of Manufacture
Marking on Drums
RED paint shall be applied on both sides of cable drums for cables intended for FPSO,
while BLUE paint on both sides of cable drums for cables intended for wellhead
platforms.
The non-returnable wooden drums shall be marked with the following information:
Rev G2
Drum number
Cable type
Voltage grade
Insulation type
Page 31 of 39
CP2-0000-00-JI-SPE-0006
The text shall be printed on stainless steel plate and stapled or fixed to both sided of the
drum.
Actual cable length on the reel should be 3% more than specified on the purchase order.
No negative tolerance shall be allowed
Rev G2
Page 32 of 39
CP2-0000-00-JI-SPE-0006
6.0
6.1
Quality Assurance
Supplier specific project quality plan shall make reference to and reflect the
requirements of Companys Project Quality Plan CP2-0000-00-QA-QPL-0001. The
Supplier, and his Sub-Suppliers, shall operate a quality system satisfying the applicable
provision(s) of ISO 9000 (series), or agreed equivalent standard, commensurate with the
goods and services provided.
The Supplier shall ensure that his sub-suppliers operate a quality system meeting the
specified conformance criteria to ISO 9000. The Suppliers Quality System will be subject
to the Purchasers approval prior to issue of a Purchase Order. Major Sub-Suppliers will
be subject to the same approvals. The Purchaser reserves the right to conduct a Quality
Audit at the Suppliers /Sub-Suppliers facilities at any stage during manufacture.
The Supplier shall provide facilities for, and cooperate with, Purchaser and Inspectors
during manufacturing, assembly and testing.
6.2
Inspection
Inspection and testing shall be carried out in accordance with the approved Project
Quality Plan CP2-0000-00-QA-QPL-0001and shall comply with the requirements of this
specification, the data sheets and other referenced documentation forming part of the
Purchase Order.
The Purchaser or his nominated consultant reserves the right to carry out its own
inspection at the manufacturers works. The Supplier shall provide free access to his
works, and to that of his Sub-Suppliers, for both the Purchaser and his authorized
representative(s). All necessary certification documents relating to materials, shop test
data, etc., shall be made available to verify that the requirements of the purchase order
are being met.
The responsibility for inspection rests with the Supplier. The approval of any work by the
Purchaser, or their authorized representative, and the release of equipment for
shipment shall in no way relieve the Supplier of any responsibility for carrying out the
provisions of this specification.
The Supplier shall furnish a representative quality plan detailing his normal scope of
inspection and testing with the bid.
6.3
Testing
All testing shall be carried out at the manufacturers test facility. Test equipment shall
be supplied by the manufacturer and shall be calibrated within six months of the test
date. The minimum scope of testing is summarised below. The Supplier shall supply an
ITP with the Tender.
The Supplier shall provide the Purchaser with at least 14 calendar days advance notice to
witness tests performed in either the Suppliers shop or his sub-Suppliers shops.
Arrangement for 3rd party witness/Surveyors shall be by Supplier.
Rev G2
Page 33 of 39
6.3.1
CP2-0000-00-JI-SPE-0006
Visual Tests
Visual inspection for general workmanship, cable construction such as concentricity,
dimension checks, cable marking, colour coding and so on shall be performed.
6.3.2
Type Tests
Non-electrical
Bending test
Electrical
6.3.3
6.3.4
Rev G2
Insulation test
Immersion test.
Routine Tests
Insulation resistance
Conductor resistance
Special Tests
Armour resistance
Page 34 of 39
CP2-0000-00-JI-SPE-0006
Upon completion of inspection and testing, sample of cable from each reel shall be
provided to Purchaser
After testing, the ends of the cables or wires shall be sealed to prevent the ingress of
moisture. Three copies of certified test reports shall be submitted to Purchaser or their
designated representative for each reel of cable.
Sample of typical cables shall be provided prior to purchase for Purchaser inspection. A
short section of each cable type/size shall be stripped at time of inspection and gland
shall be made off to demonstrate that it forms a certifiable seal. Similarly
crimp/compression connectors shall be made off on the test piece.
If the test shows the cable is not acceptable then the cable shall be rejected and
immediately replaced with suitable cable. If suitable cable is not available then Supplier
shall be responsible for all costs in replacing the cable with suitable cable without
slippage including customs duties and any resultant loss of cost recovery.
Fibre optics bandwidth and attenuation tests shall be performed in accordance to
International standards.
Rev G2
Page 35 of 39
7.0
CP2-0000-00-JI-SPE-0006
Rev G2
Page 36 of 39
8.0
CP2-0000-00-JI-SPE-0006
Number and size of conductors making up the cross-sectional areas of each core
together with cross-sectional view.
Cable diameter, under armour, over armour as well as overall cable diameter
and tolerance on overall diameter
Insulation resistance
Information on the cable resistance to crude oil, natural gas, diesel, solar
radiation (UV) over an extended period of time
Fabrication of any equipment shall not commence until the Purchaser has reviewed and
approved calculations, drawings and any other design documentation.
Rev G2
Page 37 of 39
9.0
CP2-0000-00-JI-SPE-0006
GUARANTEE
The Supplier shall guarantee all equipment furnished to be in compliance with this
specification and drawings.
The Supplier shall guarantee all material against defect, damage or non-conformity and
or workmanship.
If any defect or mal-performance occurs during the guarantee period of 12 months after
commissioning, the Supplier shall make all necessary alteration, repair and replacement
immediately and at no charge to Purchaser.
Rev G2
Page 38 of 39
10.0
CP2-0000-00-JI-SPE-0006
DOCUMENTATION
As a minimum, Supplier is responsible to provide documentation for the equipment items
as defined in Supplier data requirements in Section 8.0. Supplier is responsible for all
documentation in strict accordance with the requirements of the specifications.
The Supplier shall furnish soft copies of drawing/documents that are of suitable
professional quality. Drawings that are, in Purchasers opinion not of suitable quality will
be returned to the Supplier for resubmission or at Purchasers option may be redrafted
by Purchaser or their representatives at Suppliers expense.
The electronics documents required shall be in Microsoft Office 2003 or Adobe PDF file
format.
Rev G2
Page 39 of 39