A.

SUB-STATION DETAILS
Name of Substation:

Type of
substation
(AIS / GIS/
Hybrid)

Voltage level &


transformation
capacity

XYZ

Type of CB at
Switching Scheme
different
(BH /DMT / DMB / MT/
Voltage
levels
SB/Any other)

Voltage
level
AIS

(400/220/33kV, 400kV
1x315 MVA) +
(220/132kV,
1x160MVA)

Scheme
BH

(SF6 / MOCB/
ABCB/ VCB),
Short time
current&
duration(kA,
Sec.), and
Provision of
PIR(Y/N)

Type: SF6
Short time
current: 40kA
for 1 Sec.
Provision of
PIR: Y

No. of line No. of


Bays
Transf.
bays

Bus
Coupler
bay

Bus
Transfer
Bay

Bus
Availab-- Provision of
reactor ility of
Bus Bar
(MVAR) Synchr- protection
& No. onising
of bays facility

(Y/N)
1

MVAR:
50

No. of
bays:
- 1

220kV

DMT

Type: SF6
Short time
current: 40kA
for 1 Sec.
Provision of
PIR: N

132kV

MT

Type: SF6
Short time
current:
31.5kA for 1
Sec. Provision
of PIR: N

66kV
33kV

Voltag
e level (Y/N)
400kV

220kV

132kV

AIS : Air Insulated Substation


GIS : Gas Insulated Substation
TSE : Time Synchronising Equipment
DR : Disturbance Recorder
EL : Event Logger
SAS : Substation Automation Scheme
SCADA : Supervisory Control and Data Acquision System
EMS : Enery Management System
VRLA : Valve Regulated Lead Acid
AH : Ampere Hour
EM : Electro Mechanical
BB: Bus Bar

BH : Breaker & Half Switching Scheme


DMT : Double Main & Transfer Bus Switching Scheme (with Bus coupler
DMB : Double Main Bus Switching Scheme (with Bus coupler)
MT : Main & Transfer Bus Switching Scheme (with Bus coupler)
SB : Single Bus Switching Scheme
ABCB : Air Blast Circuit Breaker
MOCB : Minimum Oil Circuit Breaker
VCB : Vacuum Circuit Breaker
PIR: Pre Insertion Resistor
NA : Not Available
LBB: Local Breaker Backup

A. SUB-STATION DETAILS

DC Syst

SCADA, EMS,SAS,TSE,DR & EL details


(Provision of )
Provision
of LBB

Type of relays
[EM/Static/
Numerical/
Numerical
(IEC61850)],
make, model &
setting of relay
for LBB
Protection

No. of
Bus PT /
CVT
cores &
ratio

TSE

DR

EL

SAS

SCADA &
EMS

(Y/N)

(Y/N,
Stand
alone/ in
built)

(Y/N,
Stand
alone /
in built)

(Y/N)

(Y/N)

Y, Inbuilt

Y, inbuilt

(Y/N)
Y

Type:
Num(IEC61850)
Make: ABB
Model: REB 670
LBB : 200MS

Type:
Num(IEC61850)
Make: ABB
Model: REB 670
Setting of

LBB : 200MS

Station DC battery bank


Battery
No. of
No. of
Type of
bank
Station Charger
battery
[Voltage
DC
Sets
(Flooded/
(220/110V battery
(one/
VRLA)
), AH
Bank
two)
rating]
(one/
two)

220V,
500AH

Two

Two

VRLA

s coupler & Bus Transfer)

DC System Details
Communication DC battery bank
Lead
Battery
Acid/ Ni
bank
Cd / any [Voltage,
other
AH
type
rating]

Lead acid 48V,


150AH

No. of
No. of
Type of
DC
Charger
battery
battery
Sets
(Flooded/
Bank
(one/
VRLA)
(one/
two)
two)

Lead Acid/
Ni Cd /
any other
type

Two

Lead acid

Two

VRLA

B. TRANSMISSION LINE DETAIL IN S/S


Name of Substation:

Sl.
No.

Name of line

XYZ - ABC

XYZ

Voltage
level
(kV)

No. of
Conductor
CirLength
(ACSR /
cuits
(km) AAAC / any
(SC/
other type)
DC)

400 DC

250 ACSRMoose

Line
Reactor
(MVAR)

Type of Protection at Substation end & Relay


[EM/Static/Num/Num(IEC61850)], make, model &
settings of relay

Dist-1 Dist-2

O/C &
Dir. E/F
E/F

(Y/N)

(Y/N)

(Y/N)

(Y/N)

OV

SPAR

(Y/N) (Y/N)

(Y/N)

Setting Setting Setti Dead


s
s
ngs time:
O/C
E/F
St.I 1 Sec.
E/F
St. II

N
Setting
s
St.I :
St. II :
St. III:
St. IV:

50 MVAR Y (Num- Y

IEC6185 (Num0) Make: IEC618


ABB
50)
Make:
ABB

Model:
REL 670
Settings
Z1:
80-85%,
Inst.
Z2:
120% L,
500ms

Model:
REL
670
Settings
Z1:
8085%,
Z3:120% Inst.
L+ LL,
Z2:
1 Sec. 120% L,
Z4
500ms
Z3:120
%L+ LL,
1
Sec.
Z4

U/F

Commun.
Link (PLCC /
Carrier
FO / MV /
Intertrip
MOB/ No
facility
Link), No. of
available
protection
or not
Cannel and
No. of data+
speech
channels

(Y/N)
FO, 2
Protection
Channel +
one data &
Speech
cahannel

XYZ - DEF

220 DC

Y (NumIEC6185
0) Make:
ABB

300 ACSRZebra

Y
(NumIEC618
50)
Make:
ABB

Setting Setting Setti Dead


s
s
ngs time:
O/C
E/F
St.I 1 Sec.
E/F
St. II

N
Setting
s
St.I :
St. II :
St. III:
St. IV:

FO, 2
Protection
Channel +
one data &
Speech
cahannel

N
Setting
s
St.I :
St. II :
St. III:
St. IV:

No
Protection
Channel /
data &
Speech
cahannel

Model:
REL 670
Settings
Z1:
80-85%,
Inst.
Z2:
120% L,
500ms

Model:
REL
670
Settings
Z1:
8085%,
Z3:120% Inst.
L+ LL,
Z2:
1 Sec. 120% L,
Z4
500ms

XYZ - IGH

132 DC

120 ACSRPanther

Z3:120
%L+ LL,
Y (Num- N
IEC6185
0) Make:
ABB

Model:
REL 670
Settings
Z1:
80-85%,
Inst.
Z2:
120% L,
500ms
Z3:120%
L+ LL,
1 Sec.

Y
N
Setting Setting Setti Dead
s
s
ngs time:
O/C
E/F
St.I 1 Sec.
E/F
St. II

SC

Single Circuit

FO

Fobre Optic

DC
O/C
E/F
Dir. E/F
OV
SPAR
U/F

Double Circuit
Overcurrent
Earthfault
Directional E/F
Overvoltage
Single Phase Auto Reclosure
Under Frequency

MV
MOB
EM
SA

Microwave
Mobile
Electro Mechanical
Surge Arrester

CC

Coupling Capacitor

St. I, St. II, St. III & St. IV corresponds to 49.0 Hz, 48.8Hz, 48.6Hz, 48.4Hz
LL

Longest Line

Type of
SA
(Gapless
SA
No. of
MO /
provid
Gapped
CT
cores
ed
SiC) ,
& ratio
rated
voltage
(kV)

No. of PT /
CVT cores
& ratio,
capacitanc
e of CVT (if
provided),
CVT (with /
without
CC)

(Y/N)
Y

Gapless 5 cores
MO,
2000390kV 1000500/1-11-1-1

CVT ,
3
cores
400kV/
Sqrt(3):
110V/
Sqrt(3),
8800pF
CVT(with
CC)

Gapless 5 cores
MO,
1600198kV 800400/1-11-1-1

CVT,
3
cores
220kV/
Sqrt(3):
110V/
Sqrt(3),
4400pF
CVT(with
CC)

Gapless 5 cores
MO,
1200120kV 600300/1-11-1-1

CVT,
3
cores
132kV/
Sqrt(3):
110V/
Sqrt(3),
4400pF
CVT(witho
ut CC)

C. TRANSFORMER DETAILS
Name of Substation:
Sl.
Transformer
No. Details
(3-Phase /
1-phase,

XYZ
MVA
rating

Voltage
Ratio

Two winding /
Auto
transformer)

1 3-Phase, Auto
Transformer

OLTC
(Tap
Range
& No.
of
steps)

Vector
Group

315 MVA 400/220


+/Yna0d11
/33kV
10% ,
16
Steps

Type of
%
Cooling Imped(ONAN/
ance
ONAF/
OFAF/
ONAN1/O
NAN2/OD
AF)

ONAN/
ONAF/
OFAF

12.5

Tertiary
winding
Provided

Type of Protection & Relay


[EM/Static/Num/Num(IEC61850)],
make, model & type of relay
Diff.

Back up
Dir. O/C
& E/F

REF

OF

Tertiary
Protection
Provided

OL Buchho
Alarm
lz

(Y/N)

(Y/N)

(Y/N)

(Y/N)

(Y/N)

(Y/N)

(Y/N)

(Y/N)

Y, Num
(IEC
61850)
Make:
ABB
Model:
RET
670

Y, Num
(IEC
61850)Ma
ke: ABB
Model:
Settings
O/C

Y,
Num
(IEC
61850)
Make:
ABB
Model:

Y,
Num
(IEC
61850)
Make:
ABB
Model:
Settings

Y,
Num
(IEC
61850)
Make:
ABB
Model:

Y,
Num
(IEC
61850)
Make:
ABB
Model:
Settings

E/F

2 3-Phase, Auto
Transformer

160 MVA 220/132


/11kV

- 5 to Yna0d11
+
15% ,
16
Steps

ONAN/
ONAF/
OFAF

12.5

Y, Num
(IEC
61850)
Make:
ABB
Model:
RET
670

Y, Num
(IEC
61850)Ma
ke: ABB
Model:
Settings
O/C
E/F

SA
Diff.

Surge Arrester
Diffrential

O/C
E/F
OF
REF

Overcurrent
Earthfault
Overflux
Restricted Earth fault

OL
WTI
OTI
PRD
OSR
OLTC

Overload
Winding temperature Indicator
Oil temperature Indicator
Pressure Relief device
Oil Surge Relay
On Load Tap Changer

Provision of

WTI

OTI

PRD

OSR
for
OLTC

(Y/N) (Y/N) (Y/N) (Y/N)

SA (MO/
any other
type), rated
voltage

(Y/N)

Y, MO,
390 kV
(on
400kV
side)
198kV(o
n 220kV
side)

Y, MO,
198 kV
(on
220kV
side)
120kV(o
n 132kV
side)

D. REACTOR DETAIL
Name of Substation:
Sl.
No.

Line Reactor Details


[Name of Line,
MVAR, Voltage
Level(kV), 3-Phase /
1-Phase, Switchable /
Non-switchable]

XYZ

1 XYZ- ABC LIne, 50MVAR,


400kV, 3 phase,
Switchable

Type of Protection & Relay


[EM/Static/Num/ Num(IEC61850)],
make & model & setting of relay

NGR
Bus Reactor Details
(MVAR) [in
[MVAR,
case of Voltage Level(kV),
line
3-Phase /
reactor]
1-Phase]

Diff.

REF

Impedance
or Back up
O/C & E/F

Buchhloz

WTI

OTI

MOG

(Y/N)

(Y/N)

(Y/N)

(Y/N)

(Y/N)

(Y/N)

(Y/N)

Y
Type:
Make:
Model:
Setting
O/C:
E/F:

Y
Type:
Make:
Model:
Setting
O/C:
E/F:

Type:
Num(IEC
61850)

Type:
Num(IEC
61850)

Make:

Make:

Model:
Bus Reactor,
Y
50MVAR, 400kV, 3
Type:
phase
Num(IEC
61850)

Provision of

Model:
Y
Type:
Num(IEC
61850)

Make:

Make:

Model:

Model:

SA
Diff.

Surge Arrester
Diffrential

O/C
E/F
WTI
OTI
MOG
MO
SiC

Overcurrent
Earthfault
Winding temperature Indicator
Oil temperature Indicator
Magnetic Oil Gauge
Metal Oxide
Silicon Carbide

SA for reactor & NGR(in case


of line reactor) and the
type(gapless MO/ Gapped
SiC), rated voltage

(Y/N)
Y, MO, 390kV &
120kV(for NGR)

Y, MO, 390kV