prosonic T
FMU 230/231
Ultrasonic Level Measurement

Operating Instructions

Short Instructions

Prosonic T FMU 230/231

Short Instructions
Quick and easy
without display
1. Unlock device:

2. Reset:

BD

V
or

3. Adjust level to 0%,


wait 35 s, confirm
(s. upper figure):

0%

4. Adjust level to 100%,


wait 35 s, confirm
(s. lower figure):

H
BD

5. Lock device:

100%

or

More functions with


plugged-in display

Operation matrix
Matrix
Position

Parameter

1.660

VH

02

Basic calibration (Chap. 6.1)


1. Reset instrument V9H5
Input: 333
2. Length unit V8H2
Input: 0: m
1: ft
3. Empty calibration V0H1
Input: E (m/ft)

Selection of matrix position:

4. Full calibration V0H2


Input: F (m/ft)

5. Application V0H3
Input:
0: Liquid

1: Rapid level
change

2: Dome cover

H0 H1 H2 H3 H4

V V0
V1
V2
V3
V4

3: Bulk solids
BD
100%

: Increases the parameter value

: Decreases the parameter value


V

4: Conveyor belt
E

or H : Confirms the entry


0%

After Basic calibration:


Linearization (Chap. 6.2)
Set current output (Chap. 6.3)

Endress+Hauser

Prosonic T FMU 230/231

Table of Contents

Table of Contents
Short Instructions . . . . . . . . . . . . . . . . . . . . . . . 2

Trouble shooting . . . . . . . . . . . . . . . . . 16

Safety instructions . . . . . . . . . . . . . . . . . 4

Accessories . . . . . . . . . . . . . . . . . . . . . . . 18

Installation . . . . . . . . . . . . . . . . . . . . . . . . . 5

Technical Data . . . . . . . . . . . . . . . . . . . 20

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Display and operating elements . . . 7

Operating Matrix FMU 230/231 . . . . . . . . 22

Commissioning without
display module . . . . . . . . . . . . . . . . . . . . 8

Commissioning with
display module . . . . . . . . . . . . . . . . . . . . 9

6.1
6.2
6.3
6.4
6.5
6.6

Basic calibration . . . . . . . . . . . . . . . . . . . . . .
Linearization . . . . . . . . . . . . . . . . . . . . . . . . . .
Current output . . . . . . . . . . . . . . . . . . . . . . . .
Additional parameters . . . . . . . . . . . . . . . . . .
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . .
Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Endress+Hauser

10
11
13
14
15
15

1 Safety instructions

Prosonic T FMU 230/231

Safety instructions

The compact transmitters Prosonic T FMU have been designed to operate safely in
accordance with current technical and safety standards and must be installed by
qualified personnel according to the instructions in this manual. The manufacturer
accepts no responsibility for any damage arising from incorrect use, insatallation or
operation of the equipment. Changes or modifications to the equipment not expressly
approved in the operating instructions or by the bodies responsible for compliance may
make the users authority to use the equipment null and void. Damaged instruments
which may be a safety hazard must not be operated and are to be marked as defective.
Use in hazardous areas

When used in explosion hazardous areas, the equipment must be installed in


accordance with local regulations as well as with technical and safety requirements on
the measuring point as specified in the accompanying certificates.

Installation and
Commissioning

Installation, electrical connection, commissioning, operation and maintenance may only


be carried out by trained and authorized personnel. The personnel must read and
understand these operating instructions before carrying them out.

Operation

The instruments may only be operated by trained personnel authorized by the plant
operator. The instructions given in this manual are to be followed exactly.

Safety conventions and


symbols

In this operating instructions, safety-relevant information is indicated by the following


symbols:
Symbol

Meaning

Note!
"Note" indicates activities which - if improperly executed - could have an indirect impact
on operation or trigger unexpected device actions.

"

Caution!
"Caution" indicates activities or processes which - if improperly executed - could lead to
personal injury or to incorrect functioning of the device.

#
%
&
)
*

Warning!
"Warning" indicates activities or processes which - if improperly executed - could lead to
serious injury to persons, to a safety risk or to destruction of the device.

Equipotential terminal
A connection which must be connected to the grounding system of the equipment: this
can, for example, be a potential matching line of a star-shaped grounding system,
depending on national or company code of practice.

DC voltage
A terminal at which DC voltage is applied or through which DC flows.
Alternating current
A terminal at which (sinusoidal) alternating voltage is applied or through which AC flows.
Ground connection
A grounded terminal, which, from the user's point of view, is already grounded by a
grounding system.
Protective earth connection
A terminal which must be grounded before other connections may be made.

Endress+Hauser

Prosonic T FMU 230/231

2 Installation

Installation

Installation variants

Installation with sleeve

Installation with counter nut

counter nut (PA)


supplied for G 1 "
and G 2" instruments

Installation with adapter flange

Installation with installation bracket

seal

adapter flange

Blocking distance

BD
seal

max.

adapter flange

FMU 230 with Display


D [mm]
max.L [mm]
50
80
80
240
100
300
FMU 231 with Display
D [mm]
max.L [mm]
80
240
100
300

L
D

Sensor

Blocking distance

FMU 230
FMU 231

0,25m
0,4m

FMU 230/231
without Display:
Dmin = 100 mm
Lmax = 150 mm

Level echos from the blocking distance (BD) cannot be evaluated due to the transient
characteristics of the sensor. Install the Prosonic T at a height so that the blocking
distance BD is not undershot, even at maximum fill level. Use a pipe nozzle if you cannot
maintain the blocking distance in any other way. The interior of the nozzle must be
smooth and may not contain any edges or welded joints. In particular, there should be
no burr on the inside of the tank side nozzle end. Note the specified limits for nozzle
diameter and length.

"

Endress+Hauser

Caution!
If the blocking distance is undershot, it may cause device malfunction.

2 Installation

Prosonic T FMU 230/231

Installation position
2

5
1/3 R

Sensor
FMU 230
FMU 231

L
5m
7m

r
0,38 m
0,67m

/2 = 5,5

Do not install the sensor in the middle of the tank (3). We recommend leaving a
distance between the sensor and the tank wall (1) measuring 1/3 of the tank radius.
Use a protective cover (page 18), in order to protect the device from direct sun or rain
(2).
Avoid measurements through the filling curtain (4).
Make sure that equipment (5) such as limit switches, temperature sensors, etc. are not
located within the emitting angle . In particular, symmetrical equipment (6) such as
heating coils, baffles etc. can influence measurement.
Align the sensor so that it is vertical to the product surface.
Never install two ultrasonic measuring devices in a tank.

!
Installation

Note!
Make use of the echo quality display (page 14) to find the best installation position.

Screw the Prosonic T at the screw-in piece using an 60 AF spanner. In order to facilitate
the wiring the housing is rotatable after installation.

housing
turnable after
installation

AF 60

60

Caution!
Use only the hexagonal
nut to screw in the
Prosonic T

max torque
20 Nm

Endress+Hauser

Prosonic T FMU 230/231

3 Wiring

Wiring
1. Open the housing cover.
2. Insert cable through gland, make
connection according to the figure.
3. Tighten cable gland.

Supply voltage:
12 ... 36 VDC

Note!
Use screened two-core instrumentation
cable.
For optimal protection against
electromagnetic interference, the
screen should be grounded in the
control room or the nearest earthing
point.
A good connection to ground is
essential to good screening.

Display and operating elements

Operating elements
matrix position

parameters

VH

+
4

segmented bar diagram

plug-in display

green LED:
confirm entry
V

operating keys

The operating elements are located under the cover of the housing.
LED

Pressing of a key is confirmed by a flash of the green LED.

Display module
(optional)

When the display module is used, the Prosonic T is operated via an operating matrix.
The current matrix position and the associated parameter (e.g. measured value) are
displayed on the module. The bargraph represents the measured value or the echo
quality, depending on the matrix position.
The basic functions for simple applications (empty and full calibration, locking and
unlocking) are accesible without the display module.

Endress+Hauser

5 Commissioning without display module

Prosonic T FMU 230/231

Commissioning without display module

When operated without the display module, the empty- and full-distance are detected
by the instrument itself and have to be confirmed by a key combination.
Methods of calibration

after installation: The vessel is emptied to 0% and filled to 100% afterwards.


before installation: The respective levels are simulated by directing the Prosonic T at
the appropriate distance to a plain wall.

The procedure
1. Unlock device:

2. Reset:

BD

V
or

3. Adjust level to 0%,


wait 35 s, confirm
(s. upper figure):

0%

4. Adjust level to 100%,


wait 35 s, confirm
(s. lower figure):

V
5. Lock device:

H
BD
100%
or

Reset

A reset causes most of the instrument settings to return to the factory settings. The
following parameters are not affected by a reset:
all linearisation parameters
the m/ft selection (V8H2)
The factory settings are included in the operating matrix on page 22.

Locking

Locking protects the entries against unwanted and unauthorized changes.

Current output

After calibration the Prosonic T outputs a current according to the measured value. The
complete measuring range (0% ... 100%) is mapped to the current interval 4 ... 20 mA.

Endress+Hauser

Prosonic T FMU 230/231

6 Commissioning with display module

Commissioning with display module

Operating matrix

When the display module is used, the Prosonic T is operated via an operating matrix.
Each matrix field represents an operating parameter. The matrix can be accessed via
the keys. The meaning of the matrix fields is summarised on page 22.
Key operation with
plugged-in display

Selecting the matrix field

V
H
V and H

Increases the vertical matrix position by 1.


Increases the horizontal matrix position by 1.
Resets the display to V0H0 (measured value).
Entering parameters

+ or -

Activates the selected matrix position. The smallest digit flashes.

+ or -

Increases or decreases the flashing digit.


To enter large parameter changes hold the key pressed.
When the decimal is exceeded (for the first or second time), the digit retains
the value 0 and the next digit begins to change. If you release the key, the
smallest digit can be edited again.

+ and -

Resets the parameter to its original value, if it has not yet been confirmed.
Confirming the entry

Confirms the entry and selects the next matrix position (vertically).

H
V and H

Confirms the entry and selects the next matrix position (horizontally).
Confirms the entry and resets the display to V0H0.
Locking/unlocking the matrix

+ and V
- and H

Endress+Hauser

Locks the matrix.


Unlocks the matrix.

6 Commissioning with display module

6.1

Prosonic T FMU 230/231

Basic calibration

Reset
(V9H5)

1. Enter "333" into the matrix position V9H5.


This sets all matrix positions back to the factory settings. Only the linearisation parameters (V2H0 ... V2H3) and the length unit (V8H2) retain their current values.

Length unit
(V8H2)

2. In V8H2, select the length unit for all subsequent inputs:


V8H2
0 (Default)
1

"
Empty distance (V0H1)
Span (V0H2)

Unit
m
ft

Caution!
Change the unit only immediately after a reset. If you change the length unit at a later
point, all subsequent entries have to be repeated in the new unit.
3. Enter the empty distance E into V0H1 and the span F into V0H2. Use the units, which
have been selected in V8H2.

BD

E: Empty distance
F: Measuring range
(span)

100%

The Empty distance E is the


distance from the sensor diaphragm
to the 0% level.
The Span F is the distance from the
0% to the 100% level.

E
F

0%

Application parameter
(V0H3)

4. In V0H3 enter the application parameter according to the following table:

Measured value display

5. Now the instrument is measuring. You can read out the following values:

V0H3
0
1
2
3
4

Matrixfeld
V0H0
V0H8
V0H9

Application
Liquid
Liquid with rapid level change
Liquid in vessels with dome ceiling
Coarse bulk solids
Conveyor belt

Display
Level in %
Distance D from sensor diaphragm to product
surface (m or ft)
Level in m or ft

Check, if the displayed values match the actual level.


If the displayed distance D (V0H8) is too small: Perform an interference echo suppression (page 14).
If al false level is displayed: Adjust empty distance and span.
Current output
(V9H8)

10

6. After the basic calibration the Prosonic T outputs the level in the form of a current signal. The complete measuring range (0% ... 100%) is mapped to the current interval
4 ... 20 mA. The current value (mA) is displayed in matrix position V9H8.

Endress+Hauser

Prosonic T FMU 230/231

6 Commissioning with display module

6.2

Linearization

After the basic calibration, the measured value is displayed in V0H0 as a percentage of
the span. The value can be converted into any other unit by the linearization function.
Four different modes of linearization can be selcted in V2H0.
Linearization mode
"Level" (V2H0=0)

Use this mode, if you want to display the level in the length unit, which has been
selected in V8H2 (m or ft).

Linearization mode
"linear"(V2H0=5, Default)

Use this mode, if you want to measure:


the level in any unit other than m, ft or
%.
the volume or weight, if the volume-tolevel relationship of your vessel is
linear.

Step
1
2
3

Matrix
position
V2H0
V2H0
V2H5

Entry / Meaning
"4": Deletes a linearization table that might be present
"5": Linearization mode "linear"
Maximum level F (or appropriate volume or weight, respectively) in the desired unit.

Note!
The factory setting is V2H5=100. That means, the level is expressed in % by default.

Linearization mode
"manual" (V2H0=2)

Use this mode, if you want to measure


the volume or weight, and if a sufficient
number of value pairs level/volume or
level/weight are known.
You can enter up to 11 value pairs into
the linearization table. The table must be
monotonically increasing.

Step

Matrix
Entry / Meaning
position
1
V2H0
"4": Deletes a linearization table that might be present
2
V2H0
"2": Linearization mode "manual"
3
V2H1
number of the value pair (1 ... 11)
4
V2H2
Level of the value pair (unit according to V8H2, m or ft)
5
V2H3
Volume or weight of the value pair (in the desired unit)
Repeat steps 3 to 5 for all value pairs
6
V2H0
"1": Activates the table

Endress+Hauser

11

6 Commissioning with display module

Linearization mode
"semi-automatic"
(V2H0=3)

Prosonic T FMU 230/231

Use this linearization mode, if you want to measure the volume or weight, while the value
pairs level/volume or level weight are not yet known.
The vessel is emptied in steps. At each step, the Prosonic T automatically registers the
level. The associated volume or weight must be entered manually.
Step

Matrix
Entry / Meaning
position
Fill the vessel to a level of 100%
1
V2H0
"4": Deletes a linearization table that might be present
2
V2H0
"3": Linearisation mode "semi-automatic"
3
V2H1
number of the value pair (1 ... 11)
4
V2H2
Check the displayed level and confirm by pressing H .
5
V2H3
Enter the associated volume or weight (in the desired unit)
Empty the vessel stepwise and repeat steps 3 ... 5 for each point
6
V2H0
"1": Activates the table

Exception: cylincrical
horizontal tank

The linearization for a cylindrical horizontal


tank is performed in the following way:
1. Determine the diameter D and the total
volume Vtot of the tank.
2. Multiply this value by the factors given
in the table below.
3. Enter these values into the instrument
as described above (Linearization
mode "manual").

V2H1
1
2
3
4
5
6
7
8
9
10
11

V2H2 (m or ft)
0
D x 0,1 =
D x 0,2 =
D x 0,3 =
D x 0,4 =
D x 0,5 =
D x 0,6 =
D x 0,7 =
D x 0,8 =
D x 0,9 =
D=

V2H3 (desired unit)


0
Vtot x 0,052 =
Vtot x 0,1424 =
Vtot x 0,2523 =
Vtot x 0,3735 =
Vtot x 0,5 =
Vtot x 0,6164 =
Vtot x 0,7477 =
Vtot x 0,8576 =
Vtot x 0,9479 =
Vtot =

Error message

As long as a linearization table is being entered, the current output indicates an error
message. The error disappears as soon as the table is complete and activated.

Measured value display

When the table has been activated, the following measured values can be read out:
Matrix position
V0H0
V0H8
V0H9

Current output

12

Display
Volume or weight in the unit of the linearization
Distance D from sensor diaphragm to product surface (m or ft)
Level in m or ft

The current output always follows the measured value V0H0. Therefore, the
4 mA value (V0H5) and the 20 mA value (V0H6) must be adapted to the new units (see
chapter 6.3).

Endress+Hauser

Prosonic T FMU 230/231

6 Commissioning with display module

6.3

Current output

In V8H1 you can define the mode of the current output. You have got the following
options:
Continuous output
(V8H1=0, Default)

Measured
value
100%

V0H6
F

V0H0
V0H5

0%

4 mA

Continuous output with


4 mA threshold
(V8H1=1)

Binary output
4/20mA (V8H1=2) or
8/16mA (V8H1=3)

Current
20 mA

In the continuous mode, the output


directly follows the measured value
V0H0.
V0H5 and V0H6 define the interval of the
measuring range which is mapped to
the current interval 4 ... 20 mA. The
factory settings (V0H5=0, V0H6=100)
can only be used if no linearization is
present. In any other case these values
must be specified in the unit of the
linerization.
If V0H5 is larger than V0H6, then the
current output is inverted. That means
the current decreases if the level
increases and vice versa.

In addition to the linear scaling the 4 mA threshold becomes effective in this option. It
makes sure, that the current output does not fall below 4 mA even if the measured value
is less than V0H5. Use this option, if your control system can not handle currents below
4 mA.

If binary output is selected, the current


only assumes two possible values:
It jumps to 20mA (or 16mA), as soon as
the measured value exceeds V0H6.
It jumps to 4mA (or 8mA), as soon as the
measured value falls below V0H5.

Measured
value
100%

V0H6

F
V0H5
0%

Current
4 mA
8 mA

20 mA
16 mA

Current on Fault
(V0H7)

In V0H7 specify the behaviour of the current output for the case of an error.

Display of the current


output (V9H8)

The current output (mA) is displayed in matrix positon V9H8.

Endress+Hauser

V0H7
0
1
2

Output on error
3,8mA
22 mA (Default)
hold last value

13

6 Commissioning with display module

6.4
Echo Quality
(V3H2)

Prosonic T FMU 230/231

Additional parameters

The echo quality of the ultrasonic signal is displayed in V3H3 in steps from 1 to 10.
Additionally it is indicated by the bargraph in the matrix positions V0H8 and V0H9. Use
this display in order to find the best installation position. For a sound measurement, the
echo quality should be at least 5.

Interference echo
suppression (V3H0)

The interference echo suppression is used


when the level echo is not detected
because a fitting is generating a stronger
interference echo. Up to three interfernece
echos can be suppressed. The
suppression should be activated with the
tank as empty as possible.

Step
1

Matrix
position
V0H8

V3H0

V0H8

Entry / Meaning
Check the displayed distance between sensor diaphragm and product surface. An
interference echo suppression is necessary, if the displayed value is too low.
Enter the actual distance between sensor diaphragm and product surface. Confirm
by pressing H. Wait approx. 40 s. The interference echo is suppressed.
Check the displayed distance between sensor diaphragm and product surface. If
the displayed value is still to low, a furhter interference echo must be suppressed.
Therefore, repeat Step 2.

Temperature
(V3H5)

The actual temperature at the sensor is shown in V3H5. If the limit of 80C has been
exceeded once, the highest value ever reached remains stored (drag indicator).

Lost echo delay time


(V8H3)

The lost echo delay time makes sure that no alarm will be output if the echo becomes
lost for a short period of time (for example due to foam). Values between 0 and 255 s
can be entered. The dafault setting is 60 s. For standard applications the lost echo delay
time should be not less than 30 s.

Actual level
(V3H1)

Falsifications in height in V0H9 (e.g. by temperature effects) can be corrected by


entering the correct height - the actual height - in V3H1. Entering the actual height then
automatically corrects the empty calibration.

First Echo Factor


(V3H4)

Vessels with tightly rounded roofs (dome covers) can cause double echos giving rise to
a display showing a level which is too low. Double echos can be excluded by increasing
the first echo factor to "maximum".

Output damping
(V0H4)

14

V3H4

First Echo Factor

off

medium

maximum

The effect of the output damping is to attenuate the analogue output and the measurand
indication on the display of the Prosonic T. When the liquid surface is not steady, a
steady reading can be obtained with the aid of the output damping. Values from 0 to
255 s can be entered. The default setting is 3 s. Please note, that the Prosonic T can not
resolve level changes faster than the output damping.

Endress+Hauser

Prosonic T FMU 230/231

6 Commissioning with display module

6.5

Simulation

V0H0: main value


(level, volume, weight)

Output
scaling

Linearization

V0H9
Level

V9H8
Current output

external
instruments

The measured value is processed by the Prosonic T in two steps and subsequently
output to external instruments. With the simulation function the correct operation of each
of these steps can be checked.
Level simulation
(V9H6=1)

Use the level simulation to check the linearisation:


1. Set V9H6=1
2. In V9H7, enter a level. Use the unit, which has been selected in V8H2 (m or ft).
3. Check if V0H0 assumes the correct value.
4. Set V9H6=0 to return to the ordinary operation mode.

Volume simulation
(V9H6=2)

Use the volume simulation, to check the scaling of the output value:
1. Set V9H6=2
2. In V9H7, enter a main value (level, volume or weight).
3. Check if the output current (V9H8) assumes the correct value.
4. Set V9H6=0 to return to the ordinary operation mode.

Current simulation
(V9H6=3)

Use the current simulation to check correct operation of the external instruments:
1. Set V9H6=3
2. In V9H7, enter a current (in mA).
3. Now, the specified current is present at the output. Check, if the external instruments
respond correctly to this current.
4. Set V9H6=0 to return to the ordinary operation mode.

6.6
Locking via the keyboard

Locking via the matrix


(V9H9)

Endress+Hauser

Locking

Key combination

Meaning

+ and V
- and H

Locking of the instrument against parameter


changes
Unlocking of the instrument

V9H9

Meaning

333

Locking of the instrument against parameter


changes

333

Unlocking of the instrument

Note!
If the instrument has been locked via the keyboard, it can only be unlocked again via
the keyboard. Unlocking via the matrix is not possible in this case.

15

7 Trouble shooting

Prosonic T FMU 230/231

7
Types of error messages

Trouble shooting

The self monitoring system of the Prosonic T distinguishes beween alarms and
warnings.
Alarm
The bargraph flashes (if the display is plugged in)
The current output adopts a preselected value (page 13)
An error code is output in V9H0.
Warning
The instrument continues to measure.
An error code is output in V9H0.

Error codes

16

V9H0

Type

Cause

Removal

E101 ...
E103

Alarm/
Warning

Initialisation

Appears after switching on. If error remains,


contact Endress-Hauser service.

E106

Alarm

Download in progress

Wait until completed.

E110 ...
E121

Alarm

Electronics error

Reset instrument (V9H5 = 333). If error


remains, contact Endress+Hauser service.

E125

Alarm

Defective sensor

Check sensor connection, contact Endress+Hauser service if error remains

E261

Alarm

Error in temperature sensor

Contact Endress+Hauser service

E501

Alarm

Sensor electronics not recognised

Contact Endress+Hauser service

E602

Warning

Linearisation curve is not rising


continuously

Check manual linearisation curve. Does the


volume increase with height?

E604

Warning

Linearisation curve has less than


2 points

Enter more points

E605

Alarm

Linearisation table not available

Activate the linearisation curve after entering


all points.

E613

Warning

Simulation activated

Switch to normal operation after simulation is


completed (V9H6=0).

E620

Warning

Current outside range

Check calibration and setting of the current


output.

E641

Alarm

No usable echo

Check, if a better position of the sensor is possible.

E661

Warning

High temperature (greater than


80C/176F)

Check measuring conditions.

Endress+Hauser

Prosonic T FMU 230/231

7 Trouble shooting

Fault analysis
Output current
too large or
too small

Check V0H0:
Is the displayed measured
value correct?

yes

Adjust output
scaling
(s. chap. 6.3)

no
V0H0 to large or
V0H0 to small, see below.

Main value V0H0


too small or
jumps occasionally to small
values

Check V0H8 :
Is the displayed distance
between sensor diaphragm
and product surface
too large?

yes

Contact
service

Multiple echos
- V0H3: Select "2" (dome cover)
- V3H4: increase first echo factor

Adjust linearisation
(s. chap. 6.2)

Check V0H8:
Is the displayed distance
between sensor diaphragm
and product surface
too small?

yes

no

no

Main value V0H0


too large

Gas layering?

yes

Interference echos
- fittings in vessel removable?
- nozzle too long?
- V0H3: Select "0" (liquid) or "2" (dome
cover)
- Perform Interference echo suppression

yes

- Agitator blades in measuring range?


- Increase output damping
- V0H3: Select "0" (liquid) or "2" (dome
cover)

no
Adjust linearisation
(s. chap. 6.2)

Endress+Hauser

Main value V0H0


vacillates

Turbulent surface?

Matrix can not


be edited

Unlock matrix
(s. chap. 6.6)

17

8 Accessories

Prosonic T FMU 230/231

Accessories

Protective cover

Order Code: 942665-0000

Adapter flange
sealing ring
EPDM
(supplied)

adapter flange

nozzle

sensor

FAU70E Process connection


12
14
15

FAU70E-

FAU70A Process connection

DN50 PN 16
DN80 PN16
DN100 PN16

22 ANSI 2" 150 psi


44 ANSI 3" 150 psi
25 ANSI 4" 150 psi

Sensor connection

Sensor connection

3 G 1 1/2" ISO 228


4 G 2" ISO 228

5 NPT 1 1/2 - 11,5


6 NPT 2 - 11,5

Material

Material

2
7

2
7

1.4435
Polypropylene,
PPS
Order Code

FAU70A-

1.4435
Polypropylene,
PPS
Order Code

Mounting bracket
for FMU 230:
G 1 1/2, A=55 mm
Order code: 942669-0000
for FMU 231
G2, A=66 mm
Order code: 942669-0001
Material: 14301 (SS 304)
suited for NPT 1 1/2" and
2" as well

18

Endress+Hauser

Prosonic T FMU 230/231

8 Accessories

Cantilever

50
100

20

20
C

25

35

75

100

35

A
585

B
250

C
2

D
200

for Sensor
FMU 40

Material
1.4301 (AISI 304)
galv. steel
1.4301 (AISI 304)
galv. steel
1.4301 (AISI 304)
galv. steel
1.4301 (AISI 304)
galv. steel

FMU 41
1085

750

300

15

6.5

105

22

50/
62

75

M8

FMU 40
FMU 41

Order Code
52014132
52014131
52014136
52014135
52014134
52014133
52014138
52014137

100
25

Mounting Frame or
Wall Bracket
for Cantilever

13

The 50 mm or 62 mm orifices serve for the mounting of the FMU 40 or FMU 41 sensor,
respecitvely.
The 22 mm orifice may be used for an additional sensor.

3.2

55

33.7

25

13
76
100
200

130

Height
700 mm
700 mm
1400 mm
1400 mm

Endress+Hauser

110

60

700/1400

45
6.5

20

150

33.7

213

180

6.5
3.2

88

110
150

100
150

Material
galv. steel
1.4301 (AISI
304)
galv. steel
1.4301 (AISI
304)

Order Code
919791-0000
919791-0001

Material
galv. steel
1.4301 (AISI
304)

Order Code
919792-0000
919792-0001

919791-0002
919791-0003

19

9 Technical Data

Prosonic T FMU 230/231

9
Input variables

Output variables

Measuring accuracy

Application conditions

Technical Data

Measuring range

Type

in liquids

in solids

FMU 230

0,25 ... 4 m

0,25 ... 2 m

FMU 231

0,4 ... 7 m

0,4 ... 3,5 m

Blocking distance

FMU 230: 0,25m; FMU 231: 0,4m

Operating frequency

FMU 230: approx. 70 kHz; FMU 231: approx. 55 kHz

Pulse frequency

0,5 ... 1 Hz depending on sensor and electronic version

Current output

4 ... 20 mA

Output damping

0 ... 255 s

Load

max. 600

Reference conditions

Ideal reflection from a calm surface at 20 C

Measuring uncertainty

0,25 % for max. measuring span


(includes linearity, reproducibility and hysteresis)

Resolution

3 mm

Process temperature

40+80 C (built-in temperature sensor)

Operating temperature

20+60 C

Storage temperature

40+80 C

Operating pressure pabs

3 bar

Climatic class

IEC 68 T2-30Db

Type of protection

IP 67 (NEMA 6), with housing cover open: IP 20

Vibration resistance

IEC 68 T2-6 Tab. 2.C (10...55 Hz)

Electromagnetic compati- Interference emmission according to EN 61326 ; apparatus of class B;


bility
Interference immunity according to EN 61326 ; Appendix A (industrial are) and
NAMUR recommendation EMV (NE 21)
Use screened cable for wiring. Installation hints for screened cables and general notes on EMC test conditions: see TI 241F

Mechanical construction

Material

Housing: PBT (glass reinforced, flame-retended)


Threaded boss and sensor: PVDF

Seals

between threaded boss and sensor, internal: EPDM seal


on threaded boss, external: EPDM seal

Process connection

FMU 230: G 1 or NPT 1 , FMU 231: G 2 or NPT 2

Dimensions
(The housing dimensions
are the same for both variants)

Display and operating


elements
Power supply

20

Display LCD (optional)

4 character display with segment display of current

LED

for entry acknowledgement

Operation

via four keys: , +, V, H

Supply voltage

12 ... 36 VDC

Power consumption

< 2,5 W

Endress+Hauser

Prosonic T FMU 230/231

Index

Index
A

Actual level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Adapter flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Application parameter . . . . . . . . . . . . . . . . . . . . . . . 10

LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Length unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Level simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Linearization mode. . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Lost echo delay time . . . . . . . . . . . . . . . . . . . . . . . . . 14

B
Binary output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Blocking distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

C
Cantilever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Continuous output. . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Current on Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Current output . . . . . . . . . . . . . . . . . . . . . . . . . 8, 10, 12
Current simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
cylincrical horizontal tank . . . . . . . . . . . . . . . . . . . . . 12

Measured value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Measured value display. . . . . . . . . . . . . . . . . . . . . . . 12
Methods of calibration . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mounting bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Mounting Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Display module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operating matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Output damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Echo Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Empty distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error message. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14
10
16
12

Protective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

R
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 10

Fault analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
First Echo Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Span. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Threshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation position . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation variants . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Interference echo suppression . . . . . . . . . . . . . . . . . 14

V
Volume simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Key operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Wall Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Endress+Hauser

21

Operating Matrix FMU 230/231

Prosonic T FMU 230/231

Operating Matrix FMU 230/231


H0
Measured
V0
value
Basic
Calibration

User unit

H1

H2

H3

Empty
calibration

Full
calibration

4mA value
Application
Output
Default: 0%
0: liquid.
damping
1: fast
Default: 3 s switch point
for
2: dome cov..
4 mA (8mA)
3: solids
4: conveyor

m/ft

m/ft

V2
Linearisation

Linearisation Table
0: height
Line-No.
1. activate
2: manual
3: automatic.
4. cancel
5: linear

Table
Level

V3
Ext. parameter

Range automatic suppression


Default: 0,0

Echo Quality
0 ... 10

V8
Operating
parameter

V9
Service/
Simulat.

diagnostic
code

Entry field

Actual level
Default: 0,0

seconds
Table:
Volume/
Weight

Lost echo
delay time
0 ... 255 s
Default: 60 s

last diagnostic code

Instrument &
Software No.

H5

User unit

H6

H7

H8

H9

20mA value
Default:
100%
switch point
for
20mA(16mA)

Output on
Alarm
0: 3,8mA
1: 22mA
2: hold

Measured
diestance
(Bargraph:
Echo Quality

Level
(Bargraph:
Echo Quality)

m/ft

m/ft

Current
output

Locking
333:
unlocked
333:
locked

unser unit

Volume max.
Default: 100

First echo
factor
0: none
1: medium
2: max.

Current outp. Select unit


0: 4 ... 20mA 0: m
1: 4 ... 20mA 1: ft
+threshold
2: 4/20mA
3: 8/16mA
Type of sensor/electronics

H4

Temperature

Reset
333

Simulation
0: off
1: level
2: volume
3: current

Simualtion
value

bold: factory settings


italic: units

Display field

22

Endress+Hauser

(UNOlUXQJ]XU.RQWDPLQDWLRQ
Lieber Kunde,
Aufgrund der gesetzlichen Bestimmungen und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen
bentigen wir die unterschriebene Erklrung zur Kontamination, bevor Ihr Auftrag bearbeitet werden kann.
Legen Sie diese vollstndig ausgefllte Erklrung unbedingt den Versandpapieren bei. Dies gilt auch fr
zustzliche Sicherheitsdatenbltter und/oder spezielle Handhabungsvorschriften.
Gerte- / Sensortyp: __________________________________

Seriennummer: _____________________________

Medium / Konzentr.: __________________________________

Temperatur:

________

Druck:

Gereinigt mit:

Leitfhigkeit:

________

Viskositt: _______

__________________________________

_______

:DUQKLQZHLVH]XP0HGLXP

SAFE

radioaktiv

explosiv

tzend

giftig

gesundheitsschdlich

biogefhrlich

brandfrdernd

unbedenklich

Kreuzen Sie bitte zutreffende Warnhinweise an.


*UXQGGHU(LQVHQGXQJ
________________________________________________________________________
________________________________________________________________________
$QJDEHQ]XU)LUPD

Firma:

_________________________

Ansprechpartner:

_________________________

Adresse:

_______________________
_______________________

_________________________

Abteilung:

_______________________

_________________________

Telefon-Nummer:

_______________________

_________________________

Fax / E-Mail:

_______________________

_________________________

Ihre Auftrags-Nr.:

_______________________

Hiermit besttigen wir, dass die zurckgesandten Teile gereinigt wurden und frei sind von jeglichen Gefahr- oder
Giftstoffen entsprechend den Gefahren-Schutzvorschriften.
BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
(Ort, Datum)

Allgemeine Informationen zu Service und Reparaturen:


www.services.endress.com

BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
(Firmenstempel und rechtsverbindliche Unterschrift)

Europe
Austria
Endress+Hauser Ges.m.b.H.
Wien
Tel. (01) 88056-0, Fax (01) 88056-35
Belarus
Belorgsintez
Minsk
Tel. (0172) 263166, Fax (0172) 263111
Belgium / Luxembourg
Endress+Hauser N.V.
Brussels
Tel. (02) 2480600, Fax (02) 2480553
Bulgaria
INTERTECH-AUTOMATION
Sofia
Tel. (02) 664869, Fax (02) 9631389
Croatia
Endress+Hauser GmbH+Co.
Zagreb
Tel. (01) 6637785, Fax (01) 6637823
Cyprus
I+G Electrical Services Co. Ltd.
Nicosia
Tel. (02) 484788, Fax (02) 484690
Czech Republic
Endress+Hauser GmbH+Co.
Praha
Tel. (026) 6784200, Fax (026) 6784179
Denmark
Endress+Hauser A/S
Sborg
Tel. (70) 131132, Fax (70) 132133
Estonia
ELVI-Aqua
Tartu
Tel. (7) 441638, Fax (7) 441582
Finland
Endress+Hauser Oy
Espoo
Tel. (09) 8676740, Fax (09) 86767440
France
Endress+Hauser S.A.
Huningue
Tel. (389) 696768, Fax (389) 694802
Germany
Endress+HauserMesstechnik GmbH+Co.
Weil am Rhein
Tel. (07621) 975-01, Fax (07621) 975-555
Great Britain
Endress+Hauser Ltd.
Manchester
Tel. (0161) 2865000, Fax (0161) 9981841
Greece
I & G Building Services Automation S.A.
Athens
Tel. (01) 9241500, Fax (01) 9221714
Hungary
Mile Ipari-Elektro
Budapest
Tel. (01) 2615535, Fax (01) 2615535
Iceland
BIL ehf
Reykjavik
Tel. (05) 619616, Fax (05) 619617
Ireland
Flomeaco Company Ltd.
Kildare
Tel. (045) 868615, Fax (045) 868182
Italy
Endress+Hauser S.p.A.
Cernusco s/N Milano
Tel. (02) 921921, Fax (02) 92107153
Latvia
Rino TK
Riga
Tel. (07) 312897, Fax (07) 312894
Lithuania
UAB "Agava"
Kaunas
Tel. (07) 202410, Fax (07) 207414
Unternehmen der Endress+Hauser-Gruppe

BA 259F/00/de/07.02
52014980
FM+SGML 6.0

Netherland
Endress+Hauser B.V.
Naarden
Tel. (035) 6958611, Fax (035) 6958825

Bolivia
Tritec S.R.L.
Cochabamba
Tel. (042) 56993, Fax (042) 50981

Pakistan
Speedy Automation
Karachi
Tel. (021) 7722953, Fax (021) 7736884

Norway
Endress+Hauser A/S
Tranby
Tel. (032) 859850, Fax (032) 859851

Brazil
Samson Endress+Hauser Ltda.
Sao Paulo
Tel. (011) 50313455, Fax (011) 50313067

Papua-Neuguinea
SBS Electrical Pty Limited
Port Moresby
Tel. 3251188, Fax 3259556

Poland
Endress+Hauser Polska Sp. z o.o.
Warszawy
Tel. (022) 7201090, Fax (022) 7201085

Canada
Endress+Hauser Ltd.
Burlington, Ontario
Tel. (905) 6819292, Fax (905) 6819444

Philippines
Endress+Hauser Philippines Inc.
Metro Manila
Tel. (2) 3723601-05, Fax (2) 4121944

Chile
Endress+Hauser Chile Ltd.
Santiago
Tel. (02) 3213009, Fax (02) 3213025

Singapore
Endress+Hauser (S.E.A.) Pte., Ltd.
Singapore
Tel. 5668222, Fax 5666848

Colombia
Colsein Ltda.
Bogota D.C.
Tel. (01) 2367659, Fax (01) 6104186

South Korea
Endress+Hauser (Korea) Co., Ltd.
Seoul
Tel. (02) 6587200, Fax (02) 6592838

Portugal
Tecnisis - Tecnica de Sistemas Industriais
Linda-a-Velha
Tel. (21) 4267290, Fax (21) 4267299
Romania
Romconseng S.R.L.
Bucharest
Tel. (01) 4101634, Fax (01) 4101634
Russia
Endress+Hauser Moscow Office
Moscow
Tel. (095) 1587564, Fax (095) 1589871
Slovakia
Transcom Technik s.r.o.
Bratislava
Tel. (7) 44888684, Fax (7) 44887112
Slovenia
Endress+Hauser D.O.O.
Ljubljana
Tel. (061) 1592217, Fax (061) 1592298
Spain
Endress+Hauser S.A.
Sant Just Desvern
Tel. (93) 4803366, Fax (93) 4733839
Sweden
Endress+Hauser AB
Sollentuna
Tel. (08) 55511600, Fax (08) 55511655
Switzerland
Endress+Hauser AG
Reinach/BL 1
Tel. (061) 7157575, Fax (061) 7111650
Turkey
Intek Endstriyel lc ve Kontrol SistemleriIstanbul
Tel. (0212) 2751355, Fax (0212) 2662775
Ukraine
Photonika GmbH
Kiev
Tel. (44) 26881, Fax (44) 26908
Yugoslavia Rep.
Meris d.o.o.
Beograd
Tel.(11) 4441966, Fax (11) 4441966

Africa
Egypt
Anasia
Heliopolis/Cairo
Tel. (02) 4179007, Fax (02) 4179008
Morocco
Oussama S.A.
Casablanca
Tel. (02) 241338, Fax (02) 402657
South Africa
Endress+Hauser Pty. Ltd.
Sandton
Tel. (011) 4441386, Fax (011) 4441977
Tunisia
Controle, Maintenance et Regulation
Tunis
Tel. (01) 793077, Fax (01) 788595

Costa Rica
EURO-TEC S.A.
San Jose
Tel. (02) 961542, Fax (02) 961542
Ecuador
Insetec Cia. Ltda.
Quito
Tel. (02) 269148, Fax (02) 461833
Guatemala
ACISAAutomatizacionYControlIndustrial S.A.
Ciudad de Guatemala, C.A.
Tel. (03) 345985, Fax (03) 327431
Mexico
Endress+Hauser S.A. de C.V.
Mexico City
Tel. (5) 5682405, Fax (5) 5687459
Paraguay
Incoel S.R.L
.Asuncion
Tel. (021) 213989, Fax (021) 226583
Uruguay
Circular S.A.
Montevideo
Tel. (02) 925785, Fax (02) 929151
USA
Endress+Hauser Inc.
Greenwood, Indiana
Tel. (317) 535-7138, Fax (317) 535-8498
Venezuela
Controval C.A.
Caracas
Tel. (02) 9440966, Fax (02) 9444554

Asia
China
Endress+Hauser Shanghai
Instrumentation Co. Ltd.
Shanghai
Tel. (021) 54902300, Fax (021) 54902303
Endress+Hauser Beijing Office
Beijing
Tel. (010) 68344058, Fax: (010) 68344068
Hong Kong
Endress+Hauser HK Ltd.
Hong Kong
Tel. 25283120, Fax 28654171
India
Endress+Hauser (India) Pvt Ltd.
Mumbai
Tel. (022) 8521458, Fax (022) 8521927
Indonesia
PT Grama Bazita
Jakarta
Tel. (21) 7975083, Fax (21) 7975089

America

Japan
Sakura Endress Co. Ltd.
Tokyo
Tel. (0422) 540613, Fax (0422) 550275

Argentina
Endress+Hauser Argentina S.A.
Buenos Aires
Tel. (01) 145227970, Fax (01) 145227909

Malaysia
Endress+Hauser (M) Sdn. Bhd.
Petaling Jaya, Selangor Darul Ehsan
Tel. (03) 7334848, Fax (03) 7338800

Taiwan
Kingjarl Corporation
Taipei R.O.C.
Tel. (02) 27183938, Fax (02) 27134190
Thailand
Endress+Hauser Ltd.
Bangkok
Tel. (2) 9967811-20, Fax (2) 9967810
Vietnam
Tan Viet Bao Co. Ltd.
Ho Chi Minh City
Tel. (08) 8335225, Fax (08) 8335227
Iran
PATSA Co.
Tehran
Tel. (021) 8754748, Fax(021) 8747761
Israel
Instrumetrics Industrial Control Ltd.
Tel-Aviv
Tel. (03) 6480205, Fax (03) 6471992
Jordan
A.P. Parpas Engineering S.A.
Amman
Tel. (06) 4643246, Fax (06) 4645707
Kingdom of Saudi Arabia
Anasia Ind. Agencies
Jeddah
Tel. (02) 6710014, Fax (02) 6725929
Lebanon
Network Engineering
Jbeil
Tel. (3) 944080, Fax (9) 548038
Sultanate of Oman
Mustafa & Jawad Sience & Industry Co. L.L.C.
Ruwi
Tel. 602009, Fax 607066
United Arab Emirates
Descon Trading EST.
Dubai
Tel. (04) 2653651, Fax (04) 2653264
Yemen
YemenCompany for Ghee andSoapIndustry
Taiz
Tel. (04) 230664, Fax (04) 212338

Australia + New Zealand


Australia
ALSTOM Australia Limited
Milperra
Tel. (02) 97747444, Fax (02) 97744667
New Zealand
EMC Industrial Group Limited
Auckland
Tel. (09) 4155110, Fax (09) 4155115

All other countries


Endress+Hauser GmbH+Co.
Instruments International
D-Weil am Rhein
Germany
Tel. (07621) 975-02, Fax (07621) 975345

Вам также может понравиться