and produces an extremely Air Tests
stable signal. 2%
Water Tests
0.5 Percent
Error Band ± 1/2 Percent
1%
0%
-1%
-2%
-3%
0% 5% 10% 15% 20% 25%
Percent Blockage
www.measurIT.com
measurIT technologies
has been
Fluid: Water at 60 deg F
Serial No: V1000.05.1
0.74
thoroughly .073
tested at 0.72
independent 0.71
±1.0%
flow laboratories K 0.70
0.68
multiple pipe sizes, 0.67
www.measurIT.com
Velocity (fps)
measurIT technologies
Verabar Models
and Options for Power and Plant Utilities
High Pressure Steam, Boiler Feed Water, Condensate, Cooling Water, Fuel…
The Verabar maximizes efficiency with the lowest permanent pressure loss. Due to its non-
constricting design, the Verabar is one of the most cost efficient flow sensors. The Verabar
produces an extremely low permanent pressure loss, typically less than .1 psig. An orifice plate
constricts the flow, causing a typical permanent pressure loss of over 2 psig. When compared
to an orifice plate, the Verabar can reduce the operating cost by over 97%.
Optional
Instrument Valves
High Pressure Steam
Flanges
900# Single
1500#
or 2500#
Double
Standard Verabar Models Model V400 installed in a 10” boiler feed water line, Suction side,
Regular, Hot Tap and Flanged models are available permanent pressure drop of only .54” (.02 PSI)
for measurement of gas, liquids and steam.
Mass Integral
Transmount Transmount RTD
Multivariable
Transmitter
V110 V510 Outputs: DP, T, P
Regular Flanged compensated flow
Opposite side Opposite side
support support
www.measurIT.com
measurIT technologies
Air to Pulverizer
Old pitot devices
Flexible Installation Locations
The Verabar can span
either the Width (W)
or the Height (H)
of the duct.
Alternate side
location (W Span)
H
requires drip Span
(condensate) legs
for moist gases.
W
Span
Pictured below:
Verabars replace Venturi in large air duct
and provide lower permanent pressure drop, Duct Height to Width Ratio
higher accuracy and repeatability.
When the duct Height to Width Ratio
exceeds a ratio of 2:1. Two Verabars
are manifolded to a single transmitter.
{H}
{W(<2H )}
www.measurIT.com
measurIT technologies
7D 3D
W
D H
<5D <5H
2D 3D 2H 2H
Minimum Straight-Run
90º Elbow Position
Minimum Straight-Run
±3.0% Accuracy ±3.0% Repeatability 90º Bend Position
Consult Factory
Consult Factory
Gas L iq u id & S te a m D u c ts
Recommended Requires collection Recommended
Top of Pipe of entrained gas and Top of Duct
Alternate periodic venting
160º (Top of Pipe)
160º
Condensate drains
back to pipe
Entrained gas
moves back to pipe
160º
Alternate 160º
(Bottom of Pipe)
Recommended
Requires collection of Bottom of Pipe
condensate and
periodic venting
www.measurIT.com
measurIT technologies
Flanged
V500 V510 V550 V500 (Single Support)
V510 (Double Support)
Specialized Mounting
Flanged Spring-Lock •PVC • Concrete
V550 (No opposite •FRP • Cast Iron Pipe
support required)
www.measurIT.com
measurIT technologies
Quality Assurance This can result in a significant undetec- average velocity. In actual industrial appli-
table loss in accuracy. cations, sensors are located downstream
Veris manufactures its own leak-proof, of disturbances, such as elbows or valves,
solid one-piece sensor. Our primary Verabar is designed to meet or exceed which produce non-uniform velocity pro-
goal is to provide the highest quality applicable ANSI and ASME codes. files. This makes it virtually impossible to
and most accurate sensor in the The Verabar is available to meet B31.1, locate a single point that represents the
industry. B31.3, B31.8, NACE MR-01-75, etc. average velocity.
Additional QA capabilities include Result: Inaccuracy ranging from ±10%
code welding, hydrostatic and other to ±20%.
H L H L H L non-destructive testing.
Verabar
Actual profiles