Академический Документы
Профессиональный Документы
Культура Документы
Calculator-1
Known variables: Equipment Elevation (meters or feet), Standard Equipment Impulse Voltage (kV), and Power Frequency Withstand Voltage (kV)
95
36
meters
* Obtain Impulse and Withstand Voltage Values from Tables 1 and 2 for IEC Standards, and
Table 3 for ANSI Standards
101.01
38.28
100.00
37.89
Where:
Up = Rated lightning impule withstand voltage [kV (peak value)]
Ud = Rated short-duration power-frequency withstand voltage (kV (r.m.s. value))
Ur = Rated voltage (kV (r.m.s. value))
http://nepsi.com/resources/calculators/altitude-correction.htm
1/3
1/4/2016
Note: the correction factors should only be applied to the impulse and withstand voltages and not to the rated voltages.
Background
Medium-voltage metal-enclosed harmonic filter banks are designed and built with components that are based on application under "usual service
conditions" as defined by IEC and ANSI standards. Generally, the "usual service conditions" defined in standards encompass ambient temperature,
altitude, solar radiation, and environmental considerations.
The insulating property of air decreases as the altitude increases, therefore this phenomenon must be taken into account for air insulated
components applied at altitudes greater than 1000 meters (3300 feet). ANSI/IEEE and IEC standards provide a methodology for determining the
impulse withstand voltage, and power frequency withstand voltage for medium-voltage components used in metal-enclosed harmonic filter banks at
high altitude.
IEC STANDARDS
In accordance with IEC 60694, the rated insulation level for switchgear and control gear is selected from the values given in tables 1 and 2,
depending on location. In these tables, the withstand voltages are based on a standardized reference atmosphere (i.e. sea level). The standards
state the rated withstand voltage values for lightning impulse voltage (Up) and power-frequency withstand voltage (Ud) shall be selected without
crossing the horizontal marked lines based on the rated voltage of the switchgear or control gear, or in NEPSI's case, the harmonic filter or
capacitor bank.
For most of the rated voltages, several rated insulation levels exists to allow for application of different overvoltage performance criteria. The choice
of insulation level for a give rated voltage should be made considering the degree of exposure to fast-front and slow-front over-voltages, the type of
neutral earthing of the system, and the type of overvoltage limiting devices. Medium-voltage metal-enclosed harmonic filter banks equipped with
lightning arresters are considered to have a lower degree of exposure and therefore the lower withstand voltage is most often chosen. Metalenclosed banks are considered to have lower exposer.
Table 1 - IEC Rated Insulation Levels for Rated Voltages
Non-North American Apparatus
http://nepsi.com/resources/calculators/altitude-correction.htm
2/3
1/4/2016
http://nepsi.com/resources/calculators/altitude-correction.htm
3/3