BS6724 SWA/LSZH Cable IEC 60502 600/1000V

Applications:

Conductor identification:

Conductor stranding:

Conductors:
Insulation:
Bedding:
Armour/Protection:
Sheath/Jacket:
Colour:
Voltage:
Operating temperature:
Minimum bending radius:
Standards:

Notes:

Power cable suitable for power networks, where fire emission of smoke and toxic
fumes creates a serious potential threat. Suitable for direct burial. Armoured LSZH
mains cable to British Standard BS6724 & IEC60502 suitable for power networks.
Two Core Brown, Blue
Three Core Brown, Black & Grey (Optional: Brown, Blue & Green/Yellow)
Four Core Brown, Black, Grey & Blue (Optional: Brown, Black, Grey &
Green/Yellow)
Five Core Numbered Cores (Optional: Brown, Black, Grey, Blue + Green/Yellow)
Six Core and Above Numbered Cores (optional numbered + Green and Yellow)
Class 2 stranded copper:
2 circular or circular compacted conductors
2* shaped or circular conductors or circular compacted conductors.
2S shaped conductors
(Dimensions and weights based on circular)
Plain annealed stranded copper
XLPE (Cross linked polyethylene)
LSZH (Low smoke zero halogen)
SWA (Single wire armour)
LSZH (Low smoke zero halogen)
Black
600/1000v
Maximum 90C. Minimum bending 0C
1.5 sq.mm 16 sq.mm 6 x overall diameter (circular cond.)
25 sq.mm and above 8 x overall diameter (shaped cond.)
BS6724: Electric cables. Thermosetting insulated, armoured cables for voltages of
600/1000V and 1900/3300V, having low emission of smoke and corrosive gases
when affected by fire
BSEN50267-1Common test methods for cables under fire conditions. Tests on gases
evolved during combustion of materials from cables. Apparatus
BSEN50267-2-1:Common test methods for cables under fire conditions. Tests on
gases evolved during combustion of materials from cables. Procedures.
Determination of the amount of halogen acid gas
BSEN50266-1Common test methods for cables under fire conditions. Test for
vertical flame spread of vertically-mounted bunched wires or cables
IEC60502: Power cables with extruded insulation and their accessories for rated
voltages from 1kV to 30kV
BSEN/IEC60332-1-2: Tests on electric and optical fibre cables under fire conditions
Part 1: test for vertical flame propagation for a single insulated wire or cable Section
2: procedure for 1kW pre-mixed flame
BSEN61034-2:2005 Measurement of smoke density of cables burned under defined
conditions. Test procedure and requirements
Flame Propagation Test to BS EN 60332-1-2:2004 for single cable and BS EN 603323-24:2009 (Cat C) for multiple cables
If you are considering installing in high UV exposure and/or high/low ambient
temperatures i.e. desert/arctic conditions then special sheathing may be required

www.batt.co.uk
battindustrial.sales@batt.co.uk

Size
Sq.mm

Class of
conductor

RT of insulation

Diameter over
laid up cores mm

RT of bedding
mm

Diameter over
bedding mm

Diameter of
armour wire mm

Diameter over
armour mm

Approx overall
diameter mm

Weight kg/km

BATT CABLES
part no

BW Gland size/
type

Gland part no

BATT CABLES part


no Green and
Yellow Core

TWO CORE: REF 6942 XWL

1.5
2.5
4
6

2
2
2
2

0.6
0.7
0.7
0.7

6.0
6.8
7.9
9.1

0.8
0.8
0.8
0.8

7.7
8.5
9.7
10.7

0.9
0.9
0.9
0.9

9.6
10.4
11.6
12.6

12.3
13.6
14.7
15.9

300
360
420
500

55131
55132
55134
55145

20S
20S
20S
20S

88344
88344
88344
88344

10
16
25
35

2
2
2*
2*

0.7
0.7
0.9
0.9

10.9
12.9
16.8
19.3

0.8
0.8
0.8
1.0

12.7
14.5
18.4
21.3

0.9
1.25
1.25
1.6

14.6
17.0
20.9
24.5

18.0
20.0
24.1
27.9

650
910
1060
1480

55147
55149
56428
56429

20
25
25
32

88345
88346
88346
88283

50
70
95
120

2S
2S
2S
2S

1.0
1.1
1.1
1.2

17.0
20.0
22.7
25.5

1.0
1.0
1.2
1.2

19.0
22.0
25.1
27.9

1.6
1.6
2.0
2.0

22.2
25.2
29.1
31.9

25.8
29.0
33.1
36.1

1800
2300
3170
3800

56430
56431
56432
56433

25
32
32
40

88346
88283
88283
88284

150
185
240
300
400

2S
2S
2S
2S
2S

1.4
1.6
1.7
1.8
2.0

28.5
32.1
36.2
40.1
45.2

1.2
1.4
1.4
1.6
1.6

30.9
34.9
39.0
43.3
48.4

2.0
2.5
2.5
2.5
2.5

34.9
39.9
44.0
48.3
53.4

39.3
44.7
59.0
53.5
59.0

4500
5800
7280
8750
10700

56434
56435
56436
56437
56438

40
50S
50
50
63

88284
88349
88350
88350
88352

THREE CORE: REF 6943 XWL


Size
Sq.mm

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

1.5
2.5
4
6

2
2
2
2

0.8
0.8
0.8
0.8

8.2
9.1
10.4
11.5

0.9
0.9
0.9
0.9

10.1
11.0
12.3
13.4

12.8
14.1
15.3
16.6

341
405
495
600

55151
55154
55155
55159

BATT
CABLES
part no
Green and
Yellow
Core
55264
55170
55179
55171

10
16
25
35

2
2
2*
2*

0.8
0.8
1.0
1.0

13.7
15.5
20.1
22.8

1.25
1.25
1.6
1.6

16.4
18.0
23.3
26.0

19.5
21.2
26.7
29.6

900
1080
1750
2100

55160
55161
56474
56475

50
70
95
120

2S
2S
2S
2S

1.0
1.0
1.2
1.2

21.7
25.2
28.8
32.0

1.6
1.6
2.0
2.0

24.9
28.4
32.8
36.0

28.5
32.2
37.0
40.4

2350
3150
4300
5250

150
185
240
300
400

2S
2S
2S
2S
2S

1.4
1.4
1.4
1.6
1.6

35.9
40.0
44.9
49.8
55.4

2.5
2.5
2.5
2.5
2.5

40.9
45.0
49.9
54.8
60.6

45.5
49.8
55.1
60.2
66.6

6720
8040
10150
12320
15090

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter
mm

Weight
kg/km

BATT
CABLES
part no

www.batt.co.uk
battindustrial.sales@batt.co.uk

BW Gland
size/ type

Gland part
no

20S
20S
20S
20

88344
88344
88344
88345

55291
55372
56747

20
25
25
32

88345
88346
88346
88283

56476
56477
56478
56479

32
32
40
40

88283
88283
88284
88284

56480
56481
56482
56483
56484

50S
50
63
63
75S

88349
88350
88352
88352
88354

FOUR CORE: REF 6944 XWL


Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

1.5
2.5
4
6

2
2
2
2

0.8
0.8
0.8
0.8

9.0
10.0
11.5
12.7

0.9
0.9
0.9
0.9

10.9
11.9
13.4
15.3

13.5
15.0
16.4
18.7

390
465
579
820

55162
55175
55193
55194

BATT
CABLES
part no
Green and
Yellow Core
55321
55322
55327
55333

10
16
25
35

2
2
2*
2*

0.8
0.8
1.0
1.0

15.1
17.2
22.3
25.3

1.25
1.25
1.6
1.6

17.6
19.7
25.5
28.5

21.1
22.9
28.9
32.1

1090
1400
2100
2580

55195
55196
56496
56497

50
70
95
120

2S
2S
2S
2S

1.0
1.2
1.2
1.4

25.0
29.5
33.3
37.5

1.6
2.0
2.0
2.0

28.2
33.5
37.3
42.5

32.0
37.7
41.7
47.1

3000
4300
5510
7150

150
2S
1.4
41.6
2.5
185
2S
1.4
46.4
2.5
240
2S
1.6
52.6
2.5
300
2S
1.6
58.0
2.5
400
2S
1.8
64.8
3.15
*Core colours are brown, black, grey and green/yellow

46.6
51.4
57.6
63.0
71.3

51.4
56.6
63.0
68.8
78.1

Size
Sq.
mm

BW Gland
size/ type

Gland part
no

20S
20S
20
20

88344
88344
88345
88345

55334
55277
56755*
56774*

25
25
32
32

88346
88346
88283
88283

56498
56499
56500
56501

56823*
56775*

32
40
50S
50

88283
88284
88349
88350

8500
10300
13000
15750
20450

56502
56503
56504
56505
56506

50
63
63
75S
75

88350
88352
88352
88353
88354

BW Gland
size/ type

Gland part
no

20S
20S
20

88344
88344
88345

FIVE CORE: REF 6945 XWL


Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

1.5
2.5
4

2
2
2

0.8
0.8
0.8

9.9
11.0
12.7

0.9
0.9
1.25

11.8
12.9
15.3

14.2
16.0
18.4

433
530
775

55158
55507
55509

BATT
CABLES
part no
Green and
Yellow Core
55274
55278
55275

6
10
16
25

2
2
2
2

0.8
1.0
1.0
1.0

14.0
17.1
19.8
24.5

1.25
1.25
1.6
1.6

16.6
19.7
23.1
27.8

19.7
23.2
26.6
31.7

929
1300
1880
2670

55512
55478
55203
56214

55318
55319
55339
56674

20
25
25
32

88345
88346
88346
88283

35
50
70
95

2
2
2
2

1.2
1.2
1.2
1.2

26
26
30
34.9

1.6
1.6
2
2

29.6
29.6
34.4
39.3

32.8
32.8
37.8
43.1

2950
2950
3827
5101

56219
56352
56403
56561

56695
56696
56697
-

120
150
185
240

2
2
2
2

1.4
1.4
1.4
1.6

39.4
43.7
48.5
-

2.5
2.5
2.5
2.5

44.8
49.1
53.4
-

48.8
53.5
58.5
75

7333
8920
10693
16800

56404
56386
56617
56618

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

BW Gland
size/ type

Gland part
no

20S
20
20

88344
88345
88345

20
25
32
40

88345
88346
88283
88284

Size
Sq.
mm

SIX CORE: REF 6946 XWL


Size
Sq.
mm

Class of
conductor

RT of
bedding
mm

1.5
2.5
4

2
2
2

0.8
0.8
0.8

10.9
12.1
13.9

0.9
0.9
0.9

12.8
14.0
16.5

15.2
17.1
19.7

497
609
886

BATT
CABLES
part no
Green and
Yellow Core
-

6
10
16
25

2
2
2
2

0.8
1.0
1.0
1.0

15.4
18.8
21.8
26.9

1.25
1.6
1.6
1.6

18.0
22.1
25.1
30.2

21.3
25.6
28.8
34.1

1070
1650
2190
3090

www.batt.co.uk
battindustrial.sales@batt.co.uk

SEVEN CORE: REF 6947 XWL


Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

1.5
2.5
4

2
2
2

0.8
0.8
0.8

10.9
12.1
13.9

0.9
0.9
1.25

12.8
14.0
16.5

15.2
17.1
19.7

506
618
907

55157
55364
55510

BATT
CABLES
part no
Green and
Yellow Core
-

6
10
16

2
2
2

0.8
1.0
1.0

15.4
18.8
21.8

1.25
1.25
1.6

18.0
22.1
25.1

21.3
25.6
28.8

1110
1720
2300

55052
55137
55167

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

Size
Sq.
mm

BW Gland
size/ type

Gland part
no

20S
20
20

88344
88345
88345

25
25
32

88346
88346
88283

BW Gland
size/ type

Gland part
no

20
20

88345
88345

25
25
32

88346
88346
88283

BW Gland
size/ type

Gland part
no

20
25

88345
88346

25
32

88346
88283

BW Gland
size/ type

Gland part
no

25
25

88346
88346

25
32

88346
88283

BW Gland
size/ type

Gland part
no

25
25
32
32

88346
88346
88283
88283

EIGHT CORE: REF 6948 XWL


Size
Sq.
mm

Class of
conductor

RT of
bedding
mm

1.5
2.5

2
2

0.8
0.8

11.9
13.1

1.25
1.25

14.5
15.7

17.6
18.8

663
793

55381
55025

BATT
CABLES
part no
Green and
Yellow Core
-

4
6
10

2
2
2

0.8
1.0
1.0

15.3
17.3
20.7

1.25
1.6
1.6

17.9
20.6
24.0

21.2
24.1
27.7

1030
1440
1960

55519
-

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

TEN CORE: REF 694/10 XWL


Size
Sq.
mm

Class of
conductor

RT of
bedding
mm

1.5
2.5

2
2

0.8
0.8

13.9
15.5

1.25
1.25

16.5
18.1

19.8
21.4

812
989

55208
-

BATT
CABLES
part no
Green and
Yellow Core
-

4
6

2
2

1.0
1.0

18.3
20.3

1.6
1.6

21.6
23.6

25.1
27.3

1410
1680

TWELVE CORE: REF 694/12 XWl


Size
Sq.
mm

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

1.5
2.5

2
2

0.8
0.8

14.3
16.0

1.25
1.25

16.9
18.6

19.4
22.4

854
1080

55166
55352

BATT
CABLES
part no
Green and
Yellow Core
55356
-

4
6

2
2

1.0
1.0

18.9
21.0

1.6
1.6

22.2
24.3

27.7
28.0

1550
1920

55511
-

SIXTEEN CORE: REF 694/16 XWL


Size
Sq.
mm
1.5
2.5
4
6

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

2
2
2
2

0.8
0.8
1.0
1.0

16.0
18.2
22.1
23.4

1.25
1.6
1.6
1.6

18.6
21.5
25.4
26.7

21.9
25.0
29.1
30.4

1020
1430
1950
2300

www.batt.co.uk
battindustrial.sales@batt.co.uk

BATT
CABLES
part no
Green and
Yellow Core
-

NINETEEN CORE: REF 694/19 XWL


Size
Sq.
mm
1.5
2.5
4

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

2
2
2

1.0
1.0
1.0

17.3
19.3
22.3

1.25
1.6
1.6

19.9
22.6
25.6

23.2
26.1
29.3

1120
1570
2050

55451
55363
55051

BATT
CABLES
part no
Green and
Yellow Core
-

BW Gland
size/ type

Gland part
no

25
25
32

88346
88346
88283

BW Gland
size/ type

Gland part
no

32
32
40

88283
88283
88284

BW Gland
size/ type

Gland part
no

32
32
40

88283
88283
88284

BW Gland
size/ type

Gland part
no

32
32

88283
88283

BW Gland
size/ type

Gland part
no

32
40

88283
88284

BW Gland
size/ type

Gland part
no

32
40

88283
88284

BW Gland
size/ type

Gland part
no

40
40

88284
88284

TWENTY TWO CORE: REF 694/22 XWL


Size
Sq.
mm
1.5
2.5
4

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

2
2
2

1.0
1.0
1.0

20.3
22.7
26.3

1.6
1.6
1.6

23.6
26.0
29.6

27.3
29.7
33.5

1560
1930
2530

BATT
CABLES
part no
Green and
Yellow Core
-

TWENTY SEVEN CORE: REF 694/27 XWL


Size
Sq.
mm
1.5
2.5
4

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

2
2
2

1.0
1.0
1.0

20.7
23.2
26.9

1.6
1.6
1.6

24.0
26.5
30.2

27.9
30.2
34.4

1630
2050
2740

55504
55353
55231

BATT
CABLES
part no
Green and
Yellow Core
-

THIRTY CORE: REF 694/30 XWL


Size
Sq.
mm
1.5
2.5

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

2
2

1.0
1.0

21.5
24.1

1.6
1.6

24.8
27.4

28.5
31.3

1730
2200

BATT
CABLES
part no
Green and
Yellow Core
-

THIRTY SEVEN CORE: REF 694/37 XWL


Size
Sq.
mm
1.5
2.5

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

2
2

1.0
1.0

23.3
26.1

1.6
1.6

26.6
29.4

30.6
33.8

1970
2540

55505
55355

BATT
CABLES
part no
Green and
Yellow Core
-

FORTY CORE: REF 694/40 XWL


Size
Sq.
mm

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

1.5
2.5

2
2

1.0
1.0

24.3
27.7

1.6
1.6

27.6
31.8

31.5
35.9

2080
2970

BATT
CABLES
part no
Green and
Yellow Core
-

FORTY EIGHT CORE: REF 694/48 XWL


Size
Sq.
mm

Class of
conductor

RT of
bedding
mm

Diameter
over
bedding
mm

Diameter
of armour
wire mm

Diameter
over
armour
mm

Approx
overall
diameter mm

Weight
kg/km

BATT
CABLES
part no

1.5
2.5

2
2

1.0
1.0

26.7
30.4

1.6
2.0

30.0
34.5

33.9
38.8

2390
3430

55506
55508

www.batt.co.uk
battindustrial.sales@batt.co.uk

BATT
CABLES
part no
Green and
Yellow Core
-

Technical Information
Single Core
Size

Max conductor
resistance at 20C
Ohms/km

Conductor short
circuit rating (1 sec)
kA

150
185
240
300
400
500
630
800
1000

0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.176

21.4
26.4
34.3
42.9
57.2
71.5
90.1
114
143

Current Rating Single


phase AC horizontal flat
speed free air
Amps
566
643
749
842
929
1032
1139
1204
1289

Current Rating Three


phase AC trefoil touching
free air
Amps
463
529
625
720
815
918
1027
1119
1214

Volt drop single


phase AC spaced
mV/A/m

Volt drop three


phase AC trefoil
mV/A/m

0.45
0.40
0.35
0.32
0.30
0.29
0.27
0.27
0.25

0.33
0.28
0.24
0.21
0.195
0.18
0.17
0.165
0.155

Three Core
Size

1.5
2.5
4
6
10
16
25
35
50*
70*
95*
120*
150*
185*
240*
300*
400*

Max conductor
resistance at 20C
Ohms/km
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.00991
0.0754
0.0601
0.047

Conductor short circuit


rating (1 sec) kA
0.20
0.35
0.57
0.86
1.4
2.2
3.6
5.0
7.1
10.0
13.6
17.2
21.4
26.5
34.3
42.9
57.2

Current Rating Single phase AC


horizontal flat speed free air
Amps
23
31
42
53
73
94
124
152
187
238
289
335
386
441
520
599
673

Current Rating Three phase


AC trefoil touching free air
Amps
25
33
44
56
78
99
131
162
197
251
304
353
406
463
546
628
728

Volt drop three phase


AC trefoil mV/A/m

Current Rating Single phase AC


horizontal flat speed free air
Amps
23
31
42
53
73
94
124
152
187
238
289
335
386
441
520
599
673

Current Rating Three phase


AC trefoil touching free air
Amps
25
33
44
56
78
99
131
162
197
251
304
353
406
463
546
628
728

Volt drop three phase


AC trefoil mV/A/m

27
16
10
6.8
4
2.5
1.65
1.15
0.87
0.6
0.45
0.37
0.3
0.26
0.21
0.185
0.165

Four Core
Size

1.5
2.5
4
6
10
16
25
35
50*
70*
95*
120*
150*
185*
240*
300*
400*

Max conductor
resistance at 20C
Ohms/km
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.00991
0.0754
0.0601
0.047

Conductor short circuit


rating (1 sec) kA
0.20
0.35
0.57
0.86
1.4
2.2
3.6
5.0
7.1
10.0
13.6
17.2
21.4
26.5
34.3
42.9
57.2

*shaped conductors, all others are circular conductors

www.batt.co.uk
battindustrial.sales@batt.co.uk

27
16
10
6.8
4
2.5
1.65
1.15
0.87
0.6
0.45
0.37
0.3
0.26
0.21
0.185
0.165

Five Core
Size

1.5
2.5
4
6
10
16
25
35

Max conductor
resistance at 20C
Ohms/km
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524

Conductor short circuit


rating (1 sec) kA
0.20
0.35
0.57
0.86
1.4
2.2
3.6
5.0

Current Rating Single phase AC


horizontal flat speed free air
Amps
23
31
42
53
73
94
124
154

Current Rating Three phase


AC trefoil touching free air
Amps
25
33
44
56
78
99
131
162

Volt drop three phase


AC trefoil mV/A/m
27
16
10
6.8
4
2.5
1.65
1.15

Two Core
Size

1.5
2.5
4
6
10
16
25
35
50*
70*
95*
120*
150*
185*
240*
300*
400*

Max conductor
resistance at 20C
Ohms/km
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.00991
0.0754
0.0601
0.047

Current Rating DC or single phase


AC clipped direct Amps

Current Rating DC or single


phase AC free air Amps

Volt drop DC
mV/A/m

Volt drop single phase AC


touching mV/A/m

27
36
49
62
85
110
146
180
219
279
338
392
451
515
607
698
787

29
39
52
66
90
115
152
188
228
291
354
410
472
539
636
732
847

31
19
12
7.9
4.7
2.9
1.85
1.35
0.98
0.67
0.49
0.39
0.31
0.25
0.195
0.155
0.12

31
19
12
7.9
4.7
2.9
1.9
1.35
1.0
0.69
0.52
0.42
0.35
0.29
0.24
0.21
0.19

Current Rating DC or single phase


AC clipped direct Amps

Current Rating DC or single


phase AC free air Amps

Volt drop DC
mV/A/m

Volt drop single phase AC


touching mV/A/m

27
36
49

29
39
52

31
19
12

31
19
12

Current Rating DC or single phase


AC clipped direct Amps

Current Rating DC or single


phase AC free air Amps

Volt drop DC
mV/A/m

Volt drop single phase AC


touching mV/A/m

27
36
49

29
39
52

31
19
12

31
19
12

Current Rating DC or single phase


AC clipped direct Amps

Current Rating DC or single


phase AC free air Amps

Volt drop DC
mV/A/m

Volt drop single phase AC


touching mV/A/m

27
36
49

29
39
52

31
19
12

31
19
12

Current Rating DC or single phase


AC clipped direct Amps

Current Rating DC or single


phase AC free air Amps

Volt drop DC
mV/A/m

Volt drop single phase AC


touching mV/A/m

27

29

31

31

Seven Core
Size

1.5
2.5
4

Max conductor
resistance at 20C
Ohms/km
12.1
7.41
4.61

Twelve Core
Size

1.5
2.5
4

Max conductor
resistance at 20C
Ohms/km
12.1
7.41
4.61

Nineteen Core
Size

1.5
2.5
4

Max conductor
resistance at 20C
Ohms/km
12.1
7.41
4.61

Twenty Seven Core


Size

1.5

Max conductor
resistance at 20C
Ohms/km
12.1

www.batt.co.uk
battindustrial.sales@batt.co.uk

2.5
4

7.41
4.61

36
49

39
52

19
12

19
12

Current Rating DC or single phase


AC clipped direct Amps

Current Rating DC or single


phase AC free air Amps

Volt drop DC
mV/A/m

Volt drop single phase AC


touching mV/A/m

27
36
49

29
39
52

31
19
12

31
19
12

Thirty seven Core


Size

1.5
2.5
4

Max conductor
resistance at 20C
Ohms/km
12.1
7.41
4.61

Forty eight Core


Size

Max conductor
Current Rating DC or single phase
Current Rating DC or single
Volt drop DC
Volt drop single phase AC
resistance at 20C
AC clipped direct Amps
phase AC free air Amps
mV/A/m
touching mV/A/m
Ohms/km
1.5
12.1
27
29
31
31
2.5
7.41
36
39
19
19
4
4.61
49
52
12
12
*shaped conductors, all others are circular conductors
7, 12, 19, 27, 37 and 48 core current ratings: the tabulated rating is as a two core and may be used where the number of cores carrying current does not exceed
the square root of the total number of cores.

Temperature rating factors


Ambient Temperature C
Rating factor

25
1.02

30
1.00

35
0.96

40
0.91

45
0.87

50
0.82

55
0.76

60
0.71

No of circuits
Single layer clipped direct (touching)
Single layer clipped direct (spaced*)
Single layer/perf. Cab. Tray horz. Or vert. (touching)
Single layer / perf. Cab. tray horz. Or vert. (spaced*)

2
0.85
0.94
0.86
0.91

3
0.79
0.90
0.81
0.89

4
0.75
0.90
0.77
0.88

5
0.73
0.90
0.75
0.87

6
0.72
0.90
0.74
0.87

7
0.71
0.90
0.73
-

8
0.71
0.90
0.73
-

9
0.70
0.90
0.72
-

Note: The factors in this table are applicable to groups of cables all of one size. If, due to known operating conditions, a cable is expected to carry not more than
30% of its grouped rating, it may be ignored for the purposes of obtaining the rating factor for the rest of the group.
When cables having differing conductor operating temperatures are grouped together, the current rating shall be based upon the lowest operating temperature
in the group.
*Spaced by a clearance between adjacent surfaces of at least one cable diameter. Where the horizontal clearances between adjacent cables exceeds 2 cable
diameters no correction factor need be applied.
If current rating in ground/duct is required then reference should be to ERA69-30 part V. Alternatively ratings are as BS5467 cables.

www.batt.co.uk