18 OD X 71.2 KMS
WORK PROCEDURE
FOR
FALSE CEILING
CLIENT
CONSULTANT
: TRACTEBEL ENGINEERING
CONTRACTOR
CHECKED BY
GAIL / TRACTEBEL
REVIEWED
BY
APPROVED
BY
NAME
DESIGNATION
SIGN
DATE
DOCUMENT NO.
REV
FALSE CEILING
Page 1 of 4
JPL/GAIL/TPPL/QC/WP/CIVIL/03
00
CONTENT
SR.
DESCRIPTION
PAGE NO.
Purpose
Scope
Controlling Specification
Documentation
ITP
Inspection Report
DOCUMENT NO.
REV
FALSE CEILING
Page 2 of 4
JPL/GAIL/TPPL/QC/WP/CIVIL/03
00
1.
PURPOSE
The purpose covers supervision and method of record keeping for false floor and false ceiling.
2.
SCOPE
This procedure covers material, supervision and method of executing the false floor and false
ceiling
3.
CONTROLLING SPECIFICATION
TE Specification
4.
GTS Z / 02 /0017
Main Runner
Main runner shall be of hot dipped galvanized steel and T shaped of 24 mm x 38 mm
size, 0.33 mm thickness with double rotary stitching.
B)
Cross Runner
Cross runner shall be of hot dipped galvanized steel and T shaped of 24 mm x 30 mm
size, 0.25 mm thickness, 1200 mm long and 24 mm x 25 mm size, 0.25 mm thickness,
600 mm long with double rotary stitching.
C)
Perimeter Section
Material shall same as runners. Sections shall be 22 mm x 22 mm size of 0.45 mm
thickness. Exposed areas of all the metallic members shall be power coated. (25 Micron).
ERECTION
Main runner shall be placed at the spacing of maximum 1200 mm c/c. Cross runners shall be
fixed @ maximum 600 mm to obtain a grid of 600 mm x 600 mm.
The grid shall be suspended by means of 4 mm dia MS wire, 6 mm thick MS cleat of 25 mm
section, dash fasteners and level adjustors.
The overall grid system shall be rigid by self-locking joints, in accordance with false ceiling
patterns perfectly leveled and aligned at desirable height as per drawings.
DOCUMENT NO.
REV
FALSE CEILING
Page 3 of 4
JPL/GAIL/TPPL/QC/WP/CIVIL/03
00
5.
Mineral fiber false ceiling tiles shall be with durable regular edging having NRC value of
minimum 0.50, Light reflectance value of minimum 80%, K value of 0.052 to 0.057
w/m deg C and fire performance conforming to class I as per BS:476. The tiles shall be
of 600 mm x 600mm x 15 mm size. The tiles shall have fissured or granulated texture
on the front side as specified. Backside shall be provided with protective coating.
6.
DOCUMENTATION
Inspection Report
Inspection & Test Plan
:
:
NOTE: In case of any conflict between this procedures and contract specification the
latter supercede this procedure.
DOCUMENT NO.
REV
FALSE CEILING
Page 4 of 4
JPL/GAIL/TPPL/QC/WP/CIVIL/03
00