NO.
DESCRIPTION
PCM
AUTHOR.
BY
DATE
Owner
VIVEK
24th Sept 09
CHECK
Choong
REFERENCE PLANS
NO.
TITLE
PLAN NO.
PLAN BY
This document and the information which it contains are confidential and are the property of Keppel-FELS Ltd. It is loaned to you for the limited purpose of
assisting you with operation and maintenance of the equipment which you have purchased from Keppel-FELS Ltd. It remains the property of Keppel-FELS Ltd. It
may not be reproduced in whole or in part without Keppel-FELS prior written consent. It may not be disclosed to persons not having need of disclosure for the loan
and it is to be returned to Keppel-FELS Ltd upon completion of the use for which it was loaned.
PRINT RECORD
29-Sep-09
JOB:
DATE :
SCALE :
N.T.S
DESIGNED BY :
Keppel FELS
HULL/JOB NO :
B309
DRAWN BY :
JAI
CHECKED BY :
YANG
APPROVED BY :
APPROVED BY :
OWNER
CLASS
1
QGOG
TITLE:
CHOONG
DATE :
14-AUG-09
SHEET 1 OF 46 SHEETS
K-FELS
DRAWING NO :
OWNER
DRAWING NO :
TM-M001
ALT. NO.
A4 (285 X 199)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
1.0
Page 2 of 46
Alt. 1
Date: 24-Sep-09
REFERENCE
No.
Description
1.1
Main specification for construction and outfitting of the DSS 38 - DP2, deep water of 9000
feet development Semi Submersible.
ME 20-710G9B-T1Electro Motive Diesel engine - Operation and Maintenance Manual.
1.2
1.3
1.4
1.5
KFELS
Commissioning
Supervisor
Keppel FELS drawing no. M101-10 Machinery Arrangement Generator Room No.1
(Stbd/Lower & Tween Deck).
Keppel FELS drawing no. M101-11 Machinery Arrangement Generator Room No.2
(Port/Lower & Tween Deck).
Keppel FELS drawing no. M201-05 Ventilation Arrangement and Details Generator
Room No.1 (Stbd/Lower & Tween Deck).
1.6
Keppel FELS drawing no. M201-06 Ventilation Arrangement and Details Generator
Room No.2 (Port/Lower & Tween Deck).
1.7
KEPPEL FELS drawing no. P107 Piping Diagram - Fuel Oil System
1.8
Keppel FELS drawing no. P113-1 Piping Diagram Central Cooling System (Sea Water).
1.9
Keppel FELS drawing no. P114 Piping Diagram Engine Exhaust System.
1.10
Keppel FELS drawing no. P116-1 Piping Diagram Rig Air System
1.11
Keppel FELS drawing no. P117 Piping Diagram Starting Air System
1.12
Keppel FELS drawing no. P118-1 Piping Diagram Lube Oil System
1.13
Keppel FELS drawing no. P118-2 Piping Diagram Waste Oil System
1.14
Keppel FELS drawing no. E052, One Line Diagram 480VAC Main Switchboard A-B.
1.15
1.16
Keppel FELS drawing no.E059 One Line Diagram 220 / 127 VAC Main Switchboard
- 2.
Keppel FELS drawing no. E051, One Line Diagram 11 KVAC Main Switch board.
1.17
Keppel FELS drawing no. E301, Schematic & Arrangement Main Generator controls
2.0
3.0
PURPOSE
2.1
2.2
2.3
SYSTEM DESCRIPTION
3.1 System:
The purpose of the main generators is to supply power to the whole rig. The system consists of Ten
generator sets and a main switchboard. In order for the generator sets to function properly, the starting air
system, sea water cooling system, ventilation system inside engine room, fuel oil system and lube oil system
play an integral part.
3.2
Mechanical:
It consists of Ten (10) (ME 20-710G9B-T1) x EMD diesel engines with NOV Baylor generator ( Model no
855ZXT rated 3580 eKW ) as prime mover of the system, design output of each generator set is 3560 eKW
@ 900 rpm. The diesel engine and the alternator are coupled by flexible coupling.
3.3
Piping:
It consists of starting air piping, diesel piping, lube oil & waste oil piping, exhaust piping and cooling water
piping system.
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
3.4
4.0
Page 3 of 46
Alt. 1
Date: 24-Sep-09
EQUIPMENT REQUIRED
No.
Description
KFELS
Commissioning
Supervisor
4.1
Voltmeters*: 0-1500 volt, 0-1000 volt, 0-250 volt, 0-25 volt (2% accuracy)
4.2
Ammeter *
4.3
Ohmmeter *
4.4
4.5
Thermometer *
4.6
Tachometer *
4.7
Stopwatch
4.8
Load banks for load testing the generators ( 10680 KW, 13350 KVA)
4.9
Walkie Talkie
*NOTE: All test instruments shall bear certificate of calibration dated within 12 months of test.
5.0
PRE-OPERATIONAL CHECK
No.
Description
5.1
5.2
5.3
5.5
5.6
KFELS
Commissioning
Supervisor
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Page 4 of 46
Alt. 1
Date: 24-Sep-09
No.
Description
5.7
The lube oil piping system has been installed as per KFELS drawing no. P118-1 Piping
Diagram - Lube Oil System and P118-2 Piping Diagram Waste Oil System, hydro-tested,
reinstalled, accepted by QGOG/ABS and documented by KFELS QA.
Lube oil sump low level alarm is tested before filling lube oil and documented by KFELS
QA. Engine lube oil sump is filled up with manufacturer recommended lube oil.
Pre-lube oil pump is operated and checking has been done for leaks within the skid.
Lubrication NDE/DE Alternator shall be connected to 230 V UPS and 480 VAC Main.
Starting Air system test is installed as per KFELS drawing no P116-1 Rig Air System and
P117 Starting Air system, hydro tested, reinstated, accepted by QGOG/ABS and documented
by KFELS QA.
The electrical system has been installed as per KFELS drawing no. E051 One line diagram
11KVAC Main Switchboard, E052, One line diagram - 480VAC Main Switchboard A-B,
E059, One line diagram - 220 / 127 VAC Main Switchboard 1-2., E301 Schematic &
Arrangement Main Generator controls. Continuity checks and megger checks have been
done and the installation is accepted by QGOG/ABS and documented by KFELS QA.
Entire switchboard and transformers have been thoroughly cleaned and all foreign materials
removed. Commissioning team has completed the pre-commissioning of all AC modules.
All preservation items such as silicon packages within engine and switchboard have been
removed. All non-essential items blocking the passages and equipment inside engine room
have been removed.
All penetrations for instruments, pipe works have completed before diesel filling into the FO
(day) tanks as per KFELS drawing no. H701-03 Settling & Day Tank Detail in Aux Mech
Room No-1 (Stbd). All fuel tanks and temporary tanks are cleaned and free from foreign
matters.
Permanent FO tanks to be properly treated and witness by QGOG.
Starting air system is ready and operational. Check air pressure on the receiver after charging
is 145 psi.
Portable fire extinguishers are readily available inside the engine room if C02 fire fighting
system is not ready.
Insulation Resistance inspected and verified by vendor:
a) Stator insulation resistance not less than 1.6 M ohms, Actual value:
5.8
5.9
5.10
5.11
5.12
5.13
5.14
b) Rotor insulation resistance not less than 1.6 M ohms, Actual value:
c) Field insulation resistance not less than 1 M ohms, Actual value:
d) PMG Stator insulation resistance not less than 1.6 M ohms, Actual value:
e) PMG Rotor insulation resistance not less than 1.6 M ohms, Actual value:
f) Cable insulation resistance not less than 1000 M ohms, Actual value:
5.15
5.16
5.17
g) Insulation resistance between switchboard bus bars not less than 1.6 M ohms, Actual
value:
h) Insulation resistance between transformer difference phases not less than 1.6 M ohms,
Actual value:
Filters and strainers are checked.
Generator space heaters should be powered for at least 24 hours prior to operation as per
manufacturers recommendation.
Important:
Confirmation of generator breaker setting and generator breaker operational test are to be
satisfactorily carried out including, but not limited to overload protection, prime mover
shutdown, under voltage protection and reverse power protection before start of item
6.3, 6.4.
KFELS
Commissioning
Supervisor
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
6.0
Page 5 of 46
Alt. 1
Date: 24-Sep-09
TEST PROCEDURE
All works are to be suspended on the Main Switchboard before the Engine start up.
All non-essential personnel need to vacate from the Main voltage switchboard room during the testing.
Note: Operation of the governor will comply to Part 4-3-4/ 3.19.1
Ensure generator being loaded / unloaded is on the opposite bus as load to allow the full amount of current to
pass through the tie breaker.
No.
Description
6.1
6.1.1
6.1.2
6.1.3
6.1.4
6.1.5
6.2
N.A
N.A
N.A
N.A
N.A
N.A
N.A
N.A
N.A
N.A
N.A
N.A
No.
Description
6.2.1
6.2.2
KFELS
QGOG
ABS (where
Commissioning Representative applicable)
Supervisor
6.2.3
6.2.4
KFELS
QGOG
ABS (where
Commissioning Representative applicable)
Supervisor
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Page 6 of 46
Alt. 1
Date: 24-Sep-09
No.
Description
KFELS
QGOG
ABS (where
Commissioning Representative applicable)
Supervisor
6.2.5
6.2.6
Repeat the steps 6.2.1 to 6.2.5 for all the 10 generators and
record the results in Table 2.1 to 2.10.
Alarm Test
6.2.7
6.3
No.
Description
KFELS
Commissioning
Supervisor
Carry out the following procedures and record data in Table 3.1 ~ 3.10.
Engine power = 3730 bKW, Generator design output = 3560 ekW.
Load bank = 3 x 3560= 10680 kW, (13350kVA), 11 KVA for parallel operation.
6.3.1
6.3.2
Preset the load at 10% full load. Start the unit and let the
controller warm up the engine at idle speed. Raise the
engine to full speed till we reach the operating
temperature.
6.3.3
6.3.4
Measure the diesel level in the Fuel Oil Tank before and
after the 100% load test to determine the specific fuel
consumption. Record the results in Table 1.0.
6.3.5
6.3.6
6.3.7
QGOG
ABS (where
Representative applicable)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
6.4
Page 7 of 46
Alt. 1
Date: 24-Sep-09
Parallel Tests
The following tests will demonstrate the capabilities of generator sets to share the load on the bus bar.
Carry out the following procedures and record data in Table 4.1 ~ Table 4.13.
Automatic synchronizing shall be function tested during the test.
Load on any generator is not to differ more than 15% of the rated output of the generator during these tests as per
ABS requirement:
1) Part 4-3-4 Section 3.21.2 on Steady State Condition
2) Part 4-3-4 Section 3.21.3 on Parallel Operation
3) Part 4-3-4 Section 3.21.3a on Reactive Load Sharing
Note: Load percentage described below is the percentage of rated output power of one generator unit.
No.
Description
6.4.
1
Run generator no. 1, close breaker to the main switch board bus
and increase load gradually to 100%.
6.4.
2
Start generator no. 2, synchronize and parallel with the bus. Load
up to 7120kW (2 generators running full load)
Observe the load sharing at 2x50% (7120/2=3560 kW).
Record load and current on each generator in Table 4.1 for
2x50% load. <Generator 1& 2 in parallel>
6.4.
3
6.4.
4
6.4.
5
6.4.
6
6.4.
7
6.4.
8
KFELS
Commissioning
Supervisor
QGOG
ABS
Representative (Where
applicable)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
No.
Description
6.4.
9
6.4.
10
Start generator no. 10, synchronize and parallel with the bus.
6.4.
11
Remove load from generator no. 1 and disconnect it from the bus.
Record load and current on each generator in Table 4.10 for 9x
11.11% load. <Generator 2 to 10 in parallel>
6.4.
12
Remove load from generator no. 2 and disconnect it from the bus.
Record load and current on each generator in Table 4.11 for 8x
12.5% load. <Generator 3 to 10 in parallel>
6.4.
13
Remove load from generator no. 3 and disconnect it from the bus.
Record load and current on each generator in Table 4.12 for 7x
14.28% load. <Generator 4 to 10 in parallel>
6.4.
14
Remove load from generator no. 4 and disconnect it from the bus.
Record load and current on each generator in Table 4.13 for
6x16.67%. <Generator 5 to 10 in parallel>
6.4.
15
Remove load from generator no. 5 and disconnect it from the bus.
Record load and current on the remaining generator 4 in Table
4.14 for 5x20% load.<Generator 6 to 10 in parallel>
6.4.
16
Remove load from generator no. 6 and disconnect it from the bus.
Record load and current on each generator in Table 4.15 for 4x
25% load. <Generator 7 to 10 in parallel>
6.4.
17
Remove load from generator no. 7 and disconnect it from the bus.
Record load and current on each generator in Table 4.16 for
3x33.3%. <Generator 8 to 10 in parallel>
6.4.
18
Remove load from generator no. 8 and disconnect it from the bus.
Record load and current on the remaining generator in Table 4.17
for 2x50% load.<Generator 9&10 in parallel >
6.4.
20
Remove the load from the generators slowly and shut down the
generators.
6.4.
21
Page 8 of 46
Alt. 1
Date: 24-Sep-09
KFELS
Commissioning
Supervisor
QGOG
ABS
Representative (Where
applicable)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Page 9 of 46
Alt. 1
Date: 24-Sep-09
No.
Description
6.4.
23
6.5
KFELS
Commissioning
Supervisor
QGOG
ABS
Representative (Where
applicable)
No.
Description
6.5.1
6.5.2
6.5.3
6.5.4
6.5.5
6.5.6
KFELS
Commissioning
Supervisor
QGOG
ABS
Representative (Where
applicable)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
6.6
Page 10 of 46
Alt. 1
Date: 24-Sep-09
No.
Description
6.6.1
6.6.2
6.6.3
6.6.4
6.6.5
6.6.6
Repeat steps 6.6.1 to 6.6.5 for the rest of the generator sets.
6.7
Description
6.7.1
6.7.3
6.7.4
QGOG
ABS (where
Representative applicable)
No.
6.7.2
KFELS
Commissioning
Supervisor
KFELS
Commissioning
Supervisor
QGOG
ABS (where
Representative applicable)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Page 11 of 46
Alt. 1
Date: 24-Sep-09
DATA SHEET
Table 1.0
ENGINE DATA
Make/Model
Engine rated power
Generator Model
Generator rated power
Generator set output
Specific fuel consumption
Description
Gen.Set
No.1
:
:
:
:
:
:
Gen.Set
No.2
EMD / ME 20-710G9B-T1
3730 bkW @ 900 rpm
855ZXT
3580 ekW (11KVA/3ph/60Hz)
3560 ekW (11KVA/3ph/60Hz)
Gen.Set
No.3
Gen.Set
No.4
Gen.Set
No.5
Gen.Set
No.6
Gen.Set
No.7
Tag No.
Engine S.No.
Alternator
S.No.
Output
Power (kW)
Specific Fuel
Consumption
(g/kWh)
Cooler No.
Governor
Alternator
lubricating
unit (Drive
End)
Alternator
lubricating
Unit(Non
Drive End)
Note: All engine/generator tests will be performed utilizing fuel conforming to Grade DF-2
Gen.Set
No.8
Gen.Set
No.9
Gen.Set
No.10
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.1
Page 12 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.2
Page 13 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.3
Page 14 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.4
Page 15 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.5
Page 16 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.6
Page 17 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.7
Page 18 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.8
Page 19 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.9
Page 20 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 2.10
Page 21 of 46
Alt. 1
Date: 24-Sep-09
Min Max
Set Point
215 F
190-212 F
27 PSIG
40-100 PSIG
1 H2O
0.8-1.3
H2O
[switch]
[switch]
[switch]
[switch]
210 F
200215 F
6 PSIG
830 PSIG
10 PSIG
15-30 PSIG
14 H2O
6-10 H2O
Emergency Stop
[switch]
[switch]
80 F
85-100 F
Description
High Jacket Water Temperature
990
Observed Set
Alarm
point
220 F
X
X
899-902
3 attempts
3 attempts
[switch]
[switch]
[switch]
[switch]
[switch]
[switch]
1200 F
8501100 F
37 PSIG
40100
PSIG
205 F
190 212 F
35 PSIG
4060 PSIG
25 PSIG
30-60 PSIG
25 PSIG
30-60 PSIG
20 PSIG
5-15 PSIG
10 PSIG
4-7 PSIG
270 F
200-260 F
284 F
270-280 F
194 F
180-190 F
70 PSIG
75-125 PSIG
140 F
113-130 F
[switch]
Shutdown
X
X
X
X
290 F
X
X
X
Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 3.1
Page 22 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue
5.
L2
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
Analogue
Digital
9.
Actuator (mA)
10.
Field
excitation
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Table 3.2
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Page 23 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue
5.
L2
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
Analogue
Digital
9.
Actuator (mA)
10.
Field
excitation
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Table 3.3
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Page 24 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue
5.
L2
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
Analogue
Digital
9.
Actuator (mA)
10.
Field
excitation
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Table 3.4
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Page 25 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue
5.
L2
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
Analogue
Digital
9.
Actuator (mA)
10.
Field
excitation
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 3.5
Page 26 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue
5.
L2
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
9.
Actuator (mA)
10.
Field
excitation
Analogue
Digital
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 3.6
Page 27 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue
5.
L2
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
9.
Actuator (mA)
10.
Field
excitation
Analogue
Digital
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 3.7
Page 28 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue L2
5.
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
9.
Actuator (mA)
10.
Field
excitation
Analogue
Digital
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 3.8
Page 29 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue
5.
L2
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
Analogue
Digital
9.
Actuator (mA)
10.
Field
excitation
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 3.9
Page 30 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue
5.
L2
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
Analogue
Digital
9.
Actuator (mA)
10.
Field
excitation
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 3.10
Page 31 of 46
Alt. 1
Date: 24-Sep-09
Load (%)
Power Factor
Duration (min)
1.
2.
3.
4.
0.8
25
0.8
50
0.8
75
0.8
100
0.8
100
0.8
100
0.8
110
0.8
15
15
15
60
60
60
15
L1
Analogue
5.
L2
L3
Alternator
current (A)
L1
Digital
L2
L3
6.
Alternator
output
(kW)
Analogue
Digital
7.
8.
Alternator
output
(kVAR)
Analogue
Digital
9.
Actuator (mA)
10.
Field
excitation
Current (A)
A1 (oC)
A4 (oC)
11.
Winding temp.
(from swbd)
(max)
B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)
12.
Bearing temp.
(max)
13.
Power (Kw)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
N/A
N/A
N/A
N/A
N/A
26.
N/A
N/A
N/A
N/A
N/A
Non-Drive (oF)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 4.0
Page 32 of 46
Alt. 1
Date: 24-Sep-09
All Load Test are to be made with load bank set at 0.8 power factor.
Table 4.1
(kW)
Remarks
(kW)
(A)
(A)
Item
Units
(kW)
(kW)
(33.33%x10680=3560 kW)
Gen. Set No.2
Actual Load
Remarks
(A)
(kW)
(33.33%x10680=3560 kW)
Gen. Set No.3
(A)
(kW)
(33.33%x10680=3560 kW)
Table 4.3
Actual Load
(kW)
Units
(A)
Units
Actual Load
(kW)
(kW)
(25%x10680=2670 kW)
Gen. Set No.2
(25%x10680=2670 kW)
Gen. Set No.3
(25%x10680=2670 kW)
Gen. Set No.4
(25%x10680=2670 kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 4.4
Page 33 of 46
Alt. 1
Date: 24-Sep-09
Units
Actual Load
(kW)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
Remarks
(A)
(kW)
(A)
Units
Actual Load
(kW)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 4.6
Page 34 of 46
Alt. 1
Date: 24-Sep-09
Units
Actual Load
(kW)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
Table 4.7
Remarks
(A)
Units
Actual Load
(kW)
(kW)
(12.5%x10680=1335 kW)
Gen. Set No.2
(12.5%x10680=1335 kW)
Gen. Set No.3
(12.5%x10680=1335 kW)
Gen. Set No.4
(12.5%x10680=1335 kW)
Gen. Set No.5
(12.5%x10680=1335 kW)
Gen. Set No.6
(12.5%x10680=1335 kW)
Gen. Set No.7
(12.5%x10680=1335 kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Item
Page 35 of 46
Alt. 1
Date: 24-Sep-09
Actual Load
Remarks
Units
Actual Load
Remarks
(kW)
(kW)
(kW)
(12.5%x10680=1335 kW)
Table 4.8
Units
(A)
(11.11%x10680=1186.6 kW)
Gen. Set No.2
(11.11%x10680=1186.6 kW)
Gen. Set No.3
(11.11%x10680=1186.6 kW)
Gen. Set No.4
(11.11%x10680=1186.6 kW)
Gen. Set No.5
(11.11%x10680=1186.6 kW)
Gen. Set No.6
(11.11%x10680=1186.6 kW)
Gen. Set No.7
(11.11%x10680=1186.6 kW)
Gen. Set No.8
(11.11%x10680=1186.6 kW)
Gen. Set No.9
(11.11%x10680=1186.6 kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 4.9
Page 36 of 46
Alt. 1
Date: 24-Sep-09
Units
Actual Load
(kW)
(kW)
(10%x10680=1068 kW)
Gen. Set No.2
(A)
(kW)
(10%x10680=1068 kW)
Gen. Set No.3
(A)
(kW)
(10%x10680=1068 kW)
Gen. Set No.4
(A)
(kW)
(10%x10680=1068 kW)
Gen. Set No.5
(A)
(kW)
(10%x10680=1068 kW)
Gen. Set No.6
(A)
(kW)
(10%x10680=1068 kW)
Gen. Set No.7
(A)
(kW)
(10%x10680=1068 kW)
Gen. Set No.8
(A)
(kW)
(10%x10680=1068 kW)
Gen. Set No.9
(A)
(kW)
(10%x10680=1068 kW)
Gen. Set No.10
(10%x10680=1068 kW)
Table 4.10
Remarks
(A)
(kW)
(A)
Units
Actual Load
(kW)
(kW)
(11.11%x10680=1186.6 kW)
Gen. Set No.3
(11.11%x10680=1186.6 kW)
Gen. Set No.4
(11.11%x10680=1186.6 kW)
Gen. Set No.5
(11.11%x10680=1186.6 kW)
TM-M001 R1 Main Generator
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Item
Page 37 of 46
Alt. 1
Date: 24-Sep-09
Actual Load
Remarks
Units
Actual Load
Remarks
(kW)
(kW)
(kW)
(11.11%x10680=1186.6 kW)
Gen. Set No.7
(A)
(kW)
(11.11%x10680=1186.6 kW)
Gen. Set No.9
(A)
(kW)
(11.11%x10680=1186.6 kW)
Gen. Set No.10
(11.11%x10680=1186.6 kW)
(A)
(kW)
(A)
(12.5%x10680=1335 kW)
Gen. Set No.4
(A)
(kW)
(12.5%x10680=1335 kW)
Gen. Set No.5
(A)
(kW)
(12.5%x10680=1335 kW)
Gen. Set No.6
(A)
(kW)
(12.5%x10680=1335 kW)
Gen. Set No.7
(A)
(kW)
(12.5%x10680=1335 kW)
Gen. Set No.8
(A)
(kW)
(12.5%x10680=1335 kW)
Gen. Set No.9
(A)
(kW)
(12.5%x10680=1335 kW)
Gen. Set No.10
(12.5%x10680=1335 kW)
Table 4.12
(A)
(kW)
(11.11%x10680=1186.6 kW)
Table 4.11
Units
(A)
(kW)
(A)
Units
Actual Load
(kW)
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Item
Page 38 of 46
Alt. 1
Date: 24-Sep-09
Actual Load
Remarks
Units
Actual Load
Remarks
(kW)
(kW)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
Units
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(A)
Units
Actual Load
(kW)
(kW)
(A)
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Item
Page 39 of 46
Alt. 1
Date: 24-Sep-09
Actual Load
Remarks
Units
Actual Load
Remarks
(kW)
(kW)
Units
(kW)
(A)
(kW)
(A)
(kW)
(kW)
Table 4.15
(A)
(A)
(25%x10680=2670 kW)
Gen. Set No.8
(A)
(kW)
(25%x10680=2670 kW)
Gen. Set No.9
(A)
(kW)
(25%x10680=2670 kW)
Gen. Set No.10
(kW)
(25%x10680=2670 kW)
Table 4.16
(A)
(A)
Units
Actual Load
(kW)
(kW)
(33.33%x10680=3560 kW)
Gen. Set No.9
(33.33%x10680=3560 kW)
Gen. Set No.10
(33.33%x10680=3560 kW)
(A)
(kW)
(A)
(kW)
(A)
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 4.17
Page 40 of 46
Alt. 1
Date: 24-Sep-09
Units
Actual Load
(kW)
(kW)
(A)
(kW)
Remarks
(A)
Note : This test can be performed during load test of Gen Set No.4 and No.5.
Item
Total Load On Line /
Actual Load
Gen. Set No.4
(50% of 7120=3560 kW)
Gen. Set No.5
(kW)
Actual Load
Remarks
(kW)
(A)
(kW)
Units
(A)
Note : This test can be performed during load test of Gen Set No. 6 and No.7.
Item
Total Load On Line /
Actual Load
Gen. Set No.6
(50% of 7120=3560 kW)
Gen. Set No.7
(50% of 7120=3560 kW)
Units
(kW)
(kW)
(A)
(kW)
(A)
Actual Load
2x50% (7120 kW/8900 KVA Total)
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 5.0
Page 41 of 46
Alt. 1
Date: 24-Sep-09
5.1
Item
Description
1.
2.
3.
Percentage reverses
power before tripping
(%)
4.
5.
Remarks
Gen. Set #1
Gen. Set #2
Gen. Set #3
Gen. Set #4
Gen. Set #5
Gen. Set #6
Gen. Set #7
Gen. Set #8
Gen. Set #9
5.2
Item
Description
1.
2.
3.
Percentage reverses
power before tripping
(%)
4.
5.
Remarks
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 6.0
Page 42 of 46
Alt. 1
Date: 24-Sep-09
Common Data
Engine Rated Speed :
Output Power (100%) :
Output Power (50%):
900 rpm
3560 ekW (11KVA/3ph/60Hz)
1780 ekW (11KVA/3ph/60Hz)
Load
Condition
Status
Voltage
Dev
Freq.
Dev
Control
Panel
(%)
(Hz)
Analog
Panel
Meter
(%)
(V)
Generator
No. 1
Generator
No.2
Generator
No.3
Generator
No.4
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Momentary
100%
Final
100%
Initial
100% to 0%.
Momentary
0%
Final
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Final
100%
Final
100%
Initial
100% to 0%.
Momentary
0%
Final
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Momentary
100%
Final
100%
Initial
100% to 0%.
Momentary
0%
Final
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Momentary
100%
Final
100%
Initial
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Load
Condition
Page 43 of 46
Alt. 1
Date: 24-Sep-09
Status
Voltage
Dev
Freq.
Dev
Control
Panel
(%)
(Hz)
Analog
Panel
Meter
(%)
(V)
Generator
No.5
Generator
No.6
Generator
No.7
Generator
No.8
100% to 0%.
Momentary
0%
Final
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Momentary
100%
Final
100%
Initial
100% to 0%.
Momentary
0%
Final
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Momentary
100%
Final
100%
Initial
100% to 0%.
Momentary
0%
Final
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Momentary
100%
Final
100%
Initial
100% to 0%.
Momentary
0%
Final
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Momentary
100%
Final
100%
Initial
100% to 0%.
Momentary
0%
Final
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Load
Condition
Page 44 of 46
Alt. 1
Date: 24-Sep-09
Status
Voltage
Dev
Freq.
Dev
Control
Panel
(%)
(Hz)
Analog
Panel
Meter
(%)
(V)
Generator
No.9
Generator
No.10
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Momentary
100%
Final
100%
Initial
100% to 0%.
Momentary
0%
Final
0%
Initial
0% to 50%
Momentary
50%
Final
50%
Initial
50% to 100%
Momentary
100%
Final
100%
Initial
100% to 0%.
Momentary
0%
Final
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
Table 7.0
Page 45 of 46
Alt. 1
Date: 24-Sep-09
Gen.
Set
No.2
Gen.
Set
No.3
Gen.
Set
No.4
Gen.
Set
No.5
Gen.
Set
No.6
Gen.
Set
No.7
Gen.
Set
No.8
Gen.
Set
No.9
Gen.
Set
No.10
KFELS
Comm.
Supervisor
Temperature
meter (0 - 100
C)
Ammeter
Kilowatt meter
Running Hour
timer
kVAR meter
Voltmeter
Ammeter
Selector
Switch
Voltmeter
Selector
Switch
Selector
Switch
Heater On
Lamp (Blue)
Heater Switch
Speed
Adjustment
Potentiometer
Voltage
Adjustment
Potentiometer
All Control
Panel Bearings
8.0
TEST ACCEPTANCE
The units and system covered under this test memo have been tested accordingly and found to be satisfactory in
accordance with test procedures.
REPRESENTATIVES
ABS
Electro Motive Diesel
QGOG
KFELS Commissioning
Supervisor
NAME
SIGNATURE
DATE
Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator
9.0
Page 46 of 46
Alt. 1
Date: 24-Sep-09
COMMENTS
SL. NO.
COMMENTS / OBSERVATIONS
SIGNATURE