Академический Документы
Профессиональный Документы
Культура Документы
One of the Worlds largest cable manufacturing plants currently built to suit the global demand in the field of Energy and Telecommunications.
It is also a nations leading environment-friendly plant that can not only manufacture wide range of Power Cables from MV/LV to EHV but is
also able to produce all sort of telecommunication cables and industrial products at all levels.
Through more than 56 years of its core business in the field of power and telecommunication cables, TAIHAN is gearing up to be a global
leading solution provider.
Based on its corporate values of harmony and trust, we will share our vision with our stakeholders, employees, customers and our investors.
TAIHAN will definitely bring a more prosperous future in the years to come.
7
8
XLPE Cable
Design and Construction of XLPE Cable
10
Manufacturing
Manufacturing Process
VCV Line
CDCC System
Quility Assurance & Test Requirement
20
21
22
24
Engineering
System Design and Engineering Work
Installation
25
27
Accessories
29
Diagnosis System
34
Appendix
Certificates
38
Having led the establishment of the nations power network for the half-century, TAIHAN has led the development of
extra high voltage cables since the 1970s and been recognized for the world class technology in XLPE underground
cable. We have continued to increase its technology to 230kV and 345kV XLPE cables through advancement of
technology and facilities. In step with the ever increasing power consumption and the expansion of extra high
voltage cable demand, we reinforced the production capacity by equipping the 125 meters high VCV Tower, to
produce high quality extra high voltage XLPE cable up to 500kV grade. Furthermore, we produce and supply quality
accessories and joints materials for extra high voltage cables. From raw materials, production process, testing of
products, to network design & installation, we have strictly controlled the quality of products and elevated ourselves
to an extra high voltage cable specialist trusted by the worlds major markets including Asia, Middle East, US, and
Australia.
XLPE(Cross-Linked Polyethylene) insulated cables have been widely used for electric power distribution of voltage
up to 30kV grade since they were develpoed in 1960 to replace the paper insulated cables and other thermoplastic
insulated cables. XLPE cables have many excellent characteristics, especially for use in higher operating
temperature. Generally PE insulated cables can be used in maximum operating temperature of 70C and paper
insulated cables in 85C, but XLPE cables, which have more compact crystallity than PE by cross-linking process,
can be used up to 90C in normal condition.
The major merits of XLPE cables can be illustrated as follows;
Excellent electrical properties
Higher operating temperature, higher current capacity
Excellent physical and mechanical properties
Anti-chemical properties
Ease of jointing, installation and maintenance
XLPE cables, however, had been scarcely used for extra high voltage exceeding 30kV grade because of its
weakness for water treeing phenomena which occurs in the insulation in long-term operating situation. Water
treeing is a phenomena of gradual insulation destroying due to water concentration onto some weak points in the
insulation.
The water can be invaded through the polymeric materials in gaseous states and /or contained in insulation
materials together with small voids and impurities during extrusion, steam-curing and cooling process. These
waters can be con-centrated onto weak points due to high electric intensity and repeating switching operation, and
eventually formed a treeshaped tunnel from inside to outer surface of insulation.
But nowadays, with the aid of technical development in cable manufacturing field, water treeing phenomena
cannot be an obstacle any more to extent the voltage grade higher. Water invasion from the outside of cable can be
prevented by adopting water-proof seamless metal sheath and water contents in insulation during manufacturing
process can be practically minimized by adopting dry curing cross-linking process instead of steam-curing method.
Many researches and develpoments are accomplished in many develpoed countries including ourselves and it
shows excellent operating experiences. 66kV and 77kV grade XLPE cables have already been used since early
1970s and now XLPE cables up to and including 230kV grade are popularly being adopted for power transmission
lines. 345kV grade and 500kV grade cables are also developed and under operations.
Fig.1
Scope
This specification applies to materials and constructions of cross-linked
polyethylene(XLPE) cables for extra high voltage transmission of rated voltage
from 66kV grade upto and including 500kV grade. This specification deals
manufacturers standard models of the cable, however any other models as for
buyers standard are also available.
Conductor
The conductor shall be formed from plain copper or aluminum complying with
Korean Standard KS C 3101, British Standard 6360/6791, IEC Publication 60228
or ICEA S-108-720. The conductor shall be stranded circular, compacted circular,
or segmental compacted circular. Segmental compacted circular conductors shall
be applied to cables of conductor nominal cross-sectional areas of 800mm2 and
above.
Conductor Shielding
Conductor shielding of an extruded semi-conducting thermosetting compound
shall be applied over the conductor. One or two layer of semi-conducting tape(s)
may be applied with a proper lapping between the conductor and the extruded
semi-conducting layer.
Insulation
The insulation shall be of dry-cured XLPE compound with a thickness to meet
dimensional, electrical and physical requirements specified. The compound
shall be high quality, heat-,moisture-, ozone- and resitant. This insulation shall
be suitable for operation in wet or dry locations at conductor temperature not
exceeding 90C for normal condition, 130C for emergency overload conditions
and 250C for short circuit conditions.
Sheath
Insulation Thickness
The insulation thickness of XLPE cable must be based on its ability to withstand
lightening impulse voltage as well as operating voltage throughout its expected
life. For the design of XLPE cable, the nominal thickness of insulation is
determined by AC withstand voltage(VAC) or impulse withstand voltage(Vimp), that
can be determined by following formula. Larger value of TAC and Timp should be
determined as minimum thickness of insulation.
Insulation Shielding
The insulation shielding shall be applied direct upon the insulation and shall
consist of either a semiconducting tape or a layer of extruded semi-conducting
compound, or combination of these materials. The extruded semiconducting
compound shall be a ther-mosetting or thermosetting compound and firmly and
totally bonded to the insulation.
Matallic Layer
The metallic layer can be applied over the insulation shielding to reinforce the
capability of carrying fault current specified, if required. The metallic layer will be
one of the next forms; (Fig.1)
Outer Jacket
The outer jacket shall consist of thermoplastic compound(PVC, PE or similar materials) extruded continuously over
the metallic layer or moisture barrier. A bituminous compound primer shall be applied under the outer jacket to
protect the sheath against local corrosion when corrugated aluminum sheath or lead alloy sheath is adopted.
Lead Sheath
When the lead alloy sheath is required, it shall be applied by a continuous screw extrusion in high quality, smooth
surface and free from pinholes and any other imperfections including one associated with oxide inclusions. When
the lead sheath is applied directly over the extruded semi-conducting layer or inner plastic bedding, suitable nonmagnetic tape(s) can be applied under the lead sheath to prevent heat transfer onto the plastic material during the
manufacturing. The composition of lead alloy of composition of Cu 0.04%, Te 0.04% and the remainder for lead
will be applied.
XLPE Cable
Design and Construction of XLPE Cable
Construction
TAC = VAC/EL(AC), Timp = Vimp/EL(imp)
Where,
VAC : AC withstand voltage
Vimp : Impulse withstand voltage
1) Value of EL
EL(AC) : minimum breakdown stress obtained from weibull distribution plot for AC.
[kV/mm]
EL(imp): minimum breakdown stress obtained from weibull distribution for impulse.
[kV/mm]
2) Value of VAC
*VAC = E0 x 1.1 x K1 x K2 xK3
3 1.15
Where,
E0 : Nominal voltage[kV]
K1 : Safety factor
K2 : Deterioration coefficient of XLPE cable under electrical stresses
K3: Temperature coefficient corresponding to the ratio of break down stresses of the
cable at room temperature to those at maximum permissible temperature(90C)
3) Value of Vimp
Vimp = BIL x K'1 x K'2 x K'3
Where,
BIL : Basic impulse level [kV]
K'1 : Safety factor
K'2 : Deterioration coefficient of XLPE cable under electrical stresses
K'3 : Temperature coefficient corresponding to the ratio of breakdown stresses of the
cable at room temperature to those at maximum permissible temperature (90C)
10
Construction : Copper Conductor / XLPE Insulation / Aluminum Sheath / PVC (or PE) Outer Jacket
Conductor
Nominal
Area Shape
[mm]
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Conductor Insulation Insulation
[mm]
Shield
Shield
[mm]
[mm]
Thickness
of
Sheath
[mm]
Thickness
of
Jacket
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
200
C.C
1.0
11.0
1.5
1.5
3.5
64.0
5.2
250
C.C
1.0
11.0
1.5
1.6
3.5
67.0
5.9
325
C.C
1.0
11.0
1.5
1.6
3.5
70.0
7.0
400
C.C
1.0
11.0
1.5
1.7
3.5
74.0
8.1
500
C.C
1.0
11.0
1.5
1.7
3.5
76.0
9.1
600
C.C
1.0
11.0
1.5
1.8
3.5
80.0
10.4
800
SEG
2.0
11.0
1.5
1.9
3.5
87.0
13.2
1000
SEG
2.0
11.0
1.5
2.0
3.5
92.0
15.6
1200
SEG
2.0
11.0
1.5
2.1
3.5
98.0
18.0
1400
SEG
2.0
11.0
1.5
2.1
3.5
101.0
20.3
1600
SEG
2.0
11.0
1.5
2.2
3.5
105.0
22.5
1800
SEG
2.0
11.0
1.5
2.3
3.5
108.0
24.5
2000
SEG
2.0
11.0
1.5
2.3
3.5
111.0
26.9
Approx.
Approx.
Thickness Thickness Thickness No.
of
of
of
of
Nominal
Conductor Insulation Insulation Wire
Area Shape
[mm]
Shield
Shield
[mm]
[mm]
[mm]
[mm]
Dia. Thickness
of
of
Jacket
Wire
[mm]
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
200
C.C
1.0
11.0
1.5
40
1.2
3.5
56.0
4.5
250
C.C
1.0
11.0
1.5
40
1.2
3.5
58.0
5.1
325
C.C
1.0
11.0
1.5
40
1.2
3.5
60.0
5.9
400
C.C
1.0
11.0
1.5
40
1.2
4.0
64.0
6.9
500
C.C
1.0
11.0
1.5
40
1.2
4.0
67.0
8.0
600
C.C
1.0
11.0
1.5
40
1.2
4.0
69.0
9.1
800
SEG
2.0
11.0
1.5
40
1.2
4.5
77.0
11.7
1000
SEG
2.0
11.0
1.5
40
1.2
4.5
81.0
13.7
1200
SEG
2.0
11.0
1.5
40
1.2
4.5
85.0
15.7
1400
SEG
2.0
11.0
1.5
40
1.2
4.5
89.0
17.9
1600
SEG
2.0
11.0
1.5
40
1.2
4.5
92.0
19.8
1800
SEG
2.0
11.0
1.5
40
1.2
4.5
95.0
21.8
2000
SEG
2.0
11.0
1.5
40
1.2
4.5
98.0
23.8
11
Construction : Copper Conductor / XLPE Insulation / Aluminum Sheath / PVC (or PE) Outer Jacket
Conductor
Nominal
Area Shape
[mm]
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Conductor Insulation Insulation
[mm]
Shield
Shield
[mm]
[mm]
Thickness
of
Sheath
[mm]
Thickness
of
Jacket
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
200
C.C
1.0
13.0
1.5
1.6
3.5
69.0
5.2
250
C.C
1.0
13.0
1.5
1.6
3.5
72.0
6.6
325
C.C
1.0
13.0
1.5
1.7
3.5
75.0
7.5
400
C.C
1.0
13.0
1.5
1.8
3.5
78.0
8.5
500
C.C
1.0
13.0
1.5
1.8
3.5
81.0
9.6
600
C.C
1.0
13.0
1.5
1.9
3.5
84.0
10.9
800
SEG
2.0
13.0
1.5
2.0
3.5
92.0
14.0
1000
SEG
2.0
13.0
1.5
2.1
3.5
97.0
16.4
1200
SEG
2.0
13.0
1.5
2.2
3.5
102.0
18.7
1400
SEG
2.0
13.0
1.5
2.2
3.5
106.0
21.0
1600
SEG
2.0
13.0
1.5
2.3
3.5
110.0
23.3
1800
SEG
2.0
13.0
1.5
2.3
3.5
112.0
25.2
2000
SEG
2.0
13.0
1.5
2.4
3.5
116.0
27.7
Approx.
Approx.
Thickness Thickness Thickness No.
of
of
of
of
Nominal
Conductor Insulation Insulation Wire
Area Shape
[mm]
Shield
Shield
[mm]
[mm]
[mm]
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
200
C.C
1.0
13.0
1.5
40
1.2
3.5
60.0
4.8
250
C.C
1.0
13.0
1.5
40
1.2
3.5
62.0
5.3
325
C.C
1.0
13.0
1.5
40
1.2
3.5
64.0
6.2
400
C.C
1.0
13.0
1.5
40
1.2
4.0
67.0
7.2
500
C.C
1.0
13.0
1.5
40
1.2
4.0
70.0
8.3
600
C.C
1.0
13.0
1.5
40
1.2
4.0
73.0
9.4
800
SEG
2.0
13.0
1.5
40
1.2
4.5
81.0
12.1
1000
SEG
2.0
13.0
1.5
40
1.2
4.5
86.0
14.2
1200
SEG
2.0
13.0
1.5
40
1.2
4.5
90.0
16.3
1400
SEG
2.0
13.0
1.5
40
1.2
4.5
94.0
18.4
1600
SEG
2.0
13.0
1.5
40
1.2
4.5
97.0
20.4
1800
SEG
2.0
13.0
1.5
40
1.2
4.5
100.0
22.4
2000
SEG
2.0
13.0
1.5
40
1.2
4.5
103.0
24.4
12
Dia. Thickness
of
of
Jacket
Wire
[mm]
[mm]
Construction : Copper Conductor / XLPE Insulation / Aluminum Sheath / PVC (or PE) Outer Jacket
Conductor
Nominal
Area Shape
[mm]
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Conductor Insulation Insulation
[mm]
Shield
Shield
[mm]
[mm]
Thickness
of
Sheath
[mm]
Thickness
of
Jacket
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
400
C.C
1.5
15.0
1.2
1.8
4.0
83
9.3
500
C.C
1.5
15.0
1.2
1.9
4.0
86
10.8
630
C.C
1.5
15.0
1.2
2.0
4.0
92
12.7
800
SEG
2.0
15.0
1.2
2.1
4.0
97
15.4
1000
SEG
2.0
15.0
1.2
2.2
4.0
102
17.9
1200
SEG
2.0
15.0
1.2
2.3
4.0
108
20.2
2000
SEG
2.0
15.0
1.2
2.5
4.0
122
29.6
Construction : Copper Conductor / XLPE Insulation / Copper Wire Shield / Lead Sheath /
PVC (or PE) Outer Jacket
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Nominal
Conductor Insulation Insulation
Area Shape
[mm]
Shield
Shield
[mm]
[mm]
[mm]
Conductor
400
C.C
1.5
15.0
1.2
2.0x67ea
2.5
4.0
81
15.5
500
C.C
1.5
15.0
1.2
2.0x70ea
2.6
4.0
84
17.4
630
C.C
1.5
15.0
1.2
1.9x67ea
2.7
4.0
88
19.3
800
SEG
2.0
15.0
1.2
1.8x70ea
2.9
4.0
94
22.8
1000
SEG
2.0
15.0
1.2
1.8x65ea
3.0
4.0
98
25.6
1200
SEG
2.0
15.0
1.2
1.7x67ea
3.1
4.0
102
28.1
1.4x70ea
3.5
4.0
115
39.1
2000
SEG
2.0
15.0
1.2
13
Construction : Copper Conductor / XLPE Insulation / Aluminum Sheath / PVC (or PE) Outer Jacket
Conductor
Nominal
Area Shape
[mm]
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Conductor Insulation Insulation
[mm]
Shield
Shield
[mm]
[mm]
Thickness
of
Sheath
[mm]
Thickness
of
Jacket
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
400
C.C
1.5
16
1.2
1.9
4.0
88
9.8
500
C.C
1.5
16
1.2
2.0
4.0
92
11.2
630
C.C
1.5
16
1.2
2.1
4.0
96
13.1
800
SEG
2.0
16
1.2
2.2
4.0
102
15.7
1000
SEG
2.0
16
1.2
2.3
4.0
109
18.4
1200
SEG
2.0
16
1.2
2.3
4.0
113
20.4
2000
SEG
2.0
16
1.2
2.6
4.0
126
29.9
Construction : Copper Conductor / XLPE Insulation / Copper Wire Shield / Lead Sheath /
PVC (or PE) Outer Jacket
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Nominal
Conductor Insulation Insulation
Area Shape
[mm]
Shield
Shield
[mm]
[mm]
[mm]
Conductor
400
C.C
1.5
16
1.2
2.0x67ea
2.5
4.0
82
15.5
500
C.C
1.5
16
1.2
1.9x70ea
2.6
4.0
85
17.2
630
C.C
1.5
16
1.2
1.9x67ea
2.7
4.0
89
19.4
800
SEG
2.0
16
1.2
1.8x67ea
2.9
4.0
95
22.6
1000
SEG
2.0
16
1.2
1.7x70ea
3.0
4.0
99
25.4
1200
SEG
2.0
16
1.2
1.7x65ea
3.1
4.0
103
27.9
1.4x65ea
3.5
4.0
116
38.8
2000
SEG
2.0
16
14
1.2
Construction : Copper Conductor / XLPE Insulation / Aluminum Sheath / PVC (or PE) Outer Jacket
Conductor
Nominal
Area Shape
[mm]
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Conductor Insulation Insulation
[mm]
Shield
Shield
[mm]
[mm]
Thickness
of
Sheath
[mm]
Thickness
of
Jacket
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
600
C.C
1.5
17
1.3
2.9
4.5
103
15.0
1200
SEG
2.0
17
1.3
2.5
4.5
115
21.8
2000
SEG
2.0
17
1.3
2.6
4.5
127
31.2
2500
SEG
2.0
17
1.3
2.8
4.5
135
36.2
Construction : Copper Conductor / XLPE Insulation / Copper Wire Shield / Lead Sheath /
PVC (or PE) Outer Jacket
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Nominal
Conductor Insulation Insulation
Area Shape
[mm]
Shield
Shield
[mm]
[mm]
[mm]
Conductor
600
C.C
1.5
17
1.3
2.9
4.5
95
22.7
1200
SEG
2.0
17
1.3
2.5x65ea
3.3
4.5
109
31.7
2000
SEG
2.0
17
1.3
2.3x68ea
3.6
4.5
122
42.7
2.2x66ea
3.8
4.5
129
48.5
2500
SEG
2.0
17
1.3
15
Construction : Copper Conductor / XLPE Insulation / Aluminum Sheath / PVC (or PE) Outer Jacket
Conductor
Nominal
Area Shape
[mm]
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Conductor Insulation Insulation
[mm]
Shield
Shield
[mm]
[mm]
Thickness
of
Sheath
[mm]
Thickness
of
Jacket
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
600
C.C
1.5
23
1.3
2.4
5.0
117
16.8
1200
SEG
2.0
23
1.3
2.6
5.0
132
24.2
2000
SEG
2.0
23
1.3
2.9
5.0
146
34.1
2500
SEG
2.0
23
1.3
3.0
5.0
153
39.1
Construction : Copper Conductor / XLPE Insulation / Copper Wire Shield / Lead Sheath /
PVC (or PE) Outer Jacket
Approx.
Approx.
Thickness Thickness Thickness No. Thickness Thickness
Overall Approx.
of
of
of
of
of
of
Nominal
Dia.
Weight
Conductor Insulation Insulation Wire Lead Sheath Jacket
Area Shape
[mm] (kg / m)
[mm]
Shield
Shield
[mm]
[mm]
[mm]
[mm]
[mm]
[mm]
Conductor
600
C.C
1.5
23
3.2
5.0
108
25.7
1200
SEG
2.0
23
1.3
2.2x68ea
5.0
121
35.0
2000
SEG
2.0
23
1.3
2.0x65ea
4.0
5.0
134
46.7
1.9x65ea
4.1
5.0
141
52.4
SEG
2.0
23
2.3x66ea
3.6
2500
16
1.3
1.3
Construction : Copper Conductor / XLPE Insulation / Aluminum Sheath / PVC (or PE) Outer Jacket
Conductor
Nominal
Area Shape
[mm]
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Conductor Insulation Insulation
[mm]
Shield
Shield
[mm]
[mm]
Thickness
of
Sheath
[mm]
Thickness
of
Jacket
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
600
C.C
1.5
27
1.3
3.0
6.0
132
19.3
1200
SEG
2.0
27
1.3
2.8
6.0
143
27.4
2000
SEG
2.0
27
1.3
3.0
6.0
157
37.5
2500
SEG
2.0
27
1.3
3.2
6.0
165
43.0
Construction : Copper Conductor / XLPE Insulation / Copper Wire Shield / Lead Sheath /
PVC (or PE) Outer Jacket
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Nominal
Conductor Insulation Insulation
Area Shape
[mm]
Shield
Shield
[mm]
[mm]
[mm]
Conductor
600
C.C
1.5
27
1.3
3.1
6.0
119
31.2
1200
SEG
2.0
27
1.3
2.9x81ea
3.4
6.0
132
41.1
2000
SEG
2.0
27
1.3
2.9x78ea
3.7
6.0
145
53.0
2.9x75ea
3.9
6.0
153
60.2
2500
SEG
2.0
27
1.3
17
Construction : Copper Conductor / XLPE Insulation / Aluminum Sheath / PVC (or PE) Outer Jacket
Conductor
Nominal
Area Shape
[mm]
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Conductor Insulation Insulation
[mm]
Shield
Shield
[mm]
[mm]
Thickness
of
Sheath
[mm]
Thickness
of
Jacket
[mm]
Overall
Dia.
[mm]
Approx.
Weight
(kg / m)
600
C.C
1.5
29
1.5
2.6
6.0
132
19.9
1200
SEG
2.0
29
1.5
2.9
6.0
146
27.6
2000
SEG
2.0
27
1.5
3.0
6.0
157
37.5
2500
SEG
2.0
27
1.5
3.2
6.0
165
43.8
Construction : Copper Conductor / XLPE Insulation / Copper Wire Shield / Lead Sheath /
PVC (or PE) Outer Jacket
Approx.
Approx.
Thickness Thickness
Thickness Thickness Thickness No.
Overall Approx.
of
of
of
of
of
of
Nominal
Dia. Weight
Conductor Insulation Insulation Wire Lead Sheath Jacket
Area Shape
[mm] (kg / m)
[mm]
[mm]
[mm]
Shield
Shield
[mm]
[mm]
[mm]
[mm]
Conductor
600
C.C
1.5
29
3.1
6.0
122
31.4
1200
SEG
2.0
29
1.5
2.5x77ea
6.0
135
41.3
2000
SEG
2.0
27
1.5
2.5x74ea
3.7
6.0
145
51.6
2.5x71ea
3.9
6.0
153
58.8
SEG
2.0
27
2.5x82ea
3.5
2500
18
1.5
1.5
Construction : Copper Conductor with Insulated Wires / XLPE Insulation / Copper Wire Shield /
Lead Sheath / PVC (or PE) Outer Jacket
Approx.
Approx.
Thickness Thickness Thickness
of
of
of
Nominal
Conductor Insulation Insulation
Area Shape
[mm]
Shield
Shield
[mm]
[mm]
[mm]
Conductor
2000
SEG
2.0
27
1.5
2.54x84ea
4.0
6.0
152
55
2500
SEG
2.0
27
1.5
2.54x79ea
4.0
6.0
160
61
Construction : Copper Conductor with Insulated Wires / XLPE Insulation / Copper Wire Shield /
Al-laminated Tape /PE(or HFPE) Outer Jacket
Approx.
Approx.
Thickness Thickness
Thickness Thickness Thickness No.
Overall Approx.
of
of
of
of
of
of
Nominal
Dia. Weight
Conductor Insulation Insulation Wire Al-laminated Jacket
Area Shape
[mm] (kg / m)
Tape
[mm]
[mm]
Shield
Shield
[mm]
[mm]
[mm]
[mm]
[mm]
Conductor
2000
SEG
2.0
30
2.0
2.16x82ea
0.35
6.0
151
35
2500
SEG
2.0
30
2.0
2.16x82ea
0.35
6.0
156
40
19
Manufacturing
Manufacturing Process
Flow Chart of Manufacturing Process
Wire
Drawing
Wire
Stranding
Conductor
Assembling
Segmental
Conductor Binder
Taping
SemiConductive Tape
Taping
Wire
Shield
Manufacturing
SemiConductive Tape
Leads Alloy
Sheath
Wiring
Machine
Copper Wire
Jacket
Extrusion
Aluminum-Foil
PE or PVC
Leads Screw
Extrusion
Jacket
Extrusion
Test &
Delivery
20
Inner Semi-Conductive PE
Insulation XLPE
Outer Semi-Conductive PE
Corrugated
Aluminum Sheath
Lead Alloy
Aluminum
Press
Aluminum
Flooding Compound
PE or PVC
Jacket
Extrusion
Flooding Compound
PE or PVC
Manufacturing
VCV Line
Metering Capstan
Conductor Preheater
Extruder
(3 Layer Triple Common Extrusion)
N2 Gas
Heating Zone
N2 Gas Tank
Take-up
Conductor
Accumulator
Cooling
Zone
Tensioning
Caterpillar
N2 Gas Heat
Exchanger
Turn Wheel
Pay-off
End Seal
Reversing Wheel
Water
Water Tank
Manufacturing
21
Manufacturing
CDCC System
22
Manufacturing
Manufacturing
Advantage of CDCC
Water Content
Sample
Dry
Steam
Wt(%)
0.018
0.29
Microvoids
The exteremly small amount of residual water in dry cured
insulation minimize micorovoids. The example of comparison of
voids in insulation during curing process is shown in Table 2.
Curing Method
Void
1~3m
4~5m
5~10m
10m over
Dry Cure
120
Steam Cure
>2,000
~300
77
AC
Electrical Strength
Both AC and impulse breakdown strength of insulation by
CDCC system have been remarkably improved compared with
that by steam curing process. Fig.2 shows the properties.
Impulse
: SCP-CV
: CDCC
Manufacturing
23
Manufacturing
Quality Assurance & Test Requirements
Extra high voltage cables are the most important cable because they are generally adopted to massive
power transmission system. Therefore the quality of the cable shall be not only tested for finished
cable products but also controlled during the whole manufacturing processes. All the materials and
manufacturing processes are stringently controlled, tested and reported according to quality standards.
Drum test and type test are performed on completed cables. Drum test is done for every length of cables by
measuring conductor resistance, capacitance, power factor, partial discharge, etc.
Electrical quality assurance for D/M length test program is done for sampled cable, generally one out of ten lengths
by measuring impulse breakdown, long-time AC withstand voltage, power factor, partial discharge, etc. Testing
procedure is one of the important process and every necessary test equipments and devices are installed, such
as 3600kV impulse generator, 600kV AC testing transformer, schering bridge, 1200kV dielectric breakdown tester
and shield room.
Test Item
Requirements
Conductor Resistance
Routine Test
AC Voltage Withstand
Insulation Resistance
Capacitance
Power Factor
Partial Discharge
Type Test
(Sequence Test)
BIL/+10 times
U0 is the rated power-frequency voltage between conductor and earth or metallic screen.
Standard : IEC 60840 & IEC 62067
24
Manufacturing
Control Room
Test terminal
Engineering
System Design and Engineering Work
Engineering
25
Engineering
System Design and Engineering Work
Chart 1.
Review on User's
Requirement
Route Survey
Collecting Design
Data
Stady-state
Current Rating
Determining Sheath
Bonding Method
Manufacturing
Capability
Emergency
Current Rating
Selecting Cable
Accessories
Transportation
in one Drum
Short-Circuit
Current Rating
Calculating System
Performance Data
Sheath Bonding
Limits
Cable Pulling
Tension
Determining
Cable Size
Determining
Cable Span
Schematic Line
Diagram
Fixing Cable
System
[V]
Limitied Voltage
Section Length
Bonding Leads
Link Box
With SVL's
[V]
Limited Voltage
Induced Sheath Voltage
2. Cross-Bonding System
This system is generally adopted for single core cable circuit having
two or more joints. In the system, metallic layer of a cable is electrically
separated(insulated) and connected to other cable's metallic layer at
ends of every three section of the circuit, and then it will be connected
to the another cable's layer. In the first section of the circuit, induced
voltage is increased in proportion to cable length, but in the next section,
it is decreased first time and increased again because induced voltages
from two otherphase is mixed together in this section. In same reason,
induced voltage at the end of this three section circuit becomes almost
zero level remaining small amount of residual voltage due to unbalance
of the joint section, etc.
26
Engineering
Sheath
Voltage
Limiters [SVL's]
Minor Section
Bonding & Grounding Cable
Minor Section
Minor Section
Major Section
Cable
Metallic
Sheath
Cable Conductor
Insulated Joint
Normal Joint
Link Plate
Solid Bond
Link Box
Engineering
Installation
TAIHAN has many achievements and excellent techniques related to turnkey-base projects. The turnkey-base
projects include the installation and engineering services as well as the supply of cable system. The quality of the
cable system at the site depends mainly on cable laying work, and jointing and terminating works. TAIHAN has
most qualified engineers and workers who are skillful and experienced in carrying out the installation works. Also
TAIHAN has much experience on various cable laying methods. The followings are generally applied as a cable
laying method.
Special Laying
In case cables are installed in special places where there are bridges or railways, special laying methods are
employed as follows;
1) When a cable crosses a river or canal, cables are attached to the bridge. If there is no suitable bridge in the
neighborhood, an exclusive bridge should be built or a method of submarine laying should be adopted. As long as
the strength and space of the bridge permits, it is best to attach the cables to the bridge. Whether it is better to
build an exclusive bridge or to lay submarine cable depends on the cost and difficulty of construction.
2) In case of crossing a railway, there are two methods; one is digging through the railway bed, and the other is
piercing from the side of the railway by using an excavator, when the cable crosses many tracks like a surface
from railroad or suburban railway, digging the railway bed is usually adopted. Except for the above case, piercing
by using an excavator is adopted.
Engineering
27
Engineering
Installation
Fig 3. Direct Burial
telephone
cable drum
tension
meter
caterpillar
pulling
wire
pulling eye
roller or
caterpillar
power cable for caterpillar
trough, if necessary
caterpillar
cable drum
control
panel
winch
car
Manhole
Duct
cable
pulling
eye
Manhole
pulling wire
tension
meter
telephone
cable drum
control panel
operator
Manhole
cable
caterpillar or roller
power cable for caterpillar
28
Engineering
Manhole
Tunnel
pulling
eye
pulling wire
operator
Accessories
Pre-Molded Joint
[Copper Case with Coffin Box]
4
D1
H
L1
L2
No.
Description
Material
Conductor Sleeve
Copper
Corona Shield
Aluminum
PMJ Unit
4
5
Rated voltage
L1
L2
D1
Silicone Rubber
66kV~69kV
1150
1650
190
420
Outer Case
Copper
110kV~161kV
1350
2300
255
540
Insulating Flange
P.E
220kV~275kV
1800
2500
315
600
Coffin Box
F.R.P
330kV~400kV
2000
2750
360
660
Filling Compound
Polyurethane
500kV
2000
2750
400
680
[FRP Case]
5
No.
Description
Material
Conductor Sleeve
Copper
Corona Shield
Aluminum
PMJ Unit
Silicone Rubber
Outer Case
F.R.P
Earthing Sleeve
Filling Compound
Rated voltage
Copper
110kV~161kV
1400
310
Polyurethane
220kV~275kV
1800
370
Accessories
29
Accessories
Outdoor Termination
[Slip-on Type]
No.
Material
Description
Conductor Sleeve
Copper
Silicone Rubber
Hollow Insulator
Polymeric or Porcelain
Compound
Polybutene Oil
Sealing Unit
Silicone Rubber
Post Insulator
Porcelain
Aluminum
Rated
Voltage
H
[mm]
Creepage Distance
[mm]
[mm]
66kV~69kV
1890
355
Min.5215
110kV~161kV
2650
355
Min.8300
220kV~275kV
4250
600
Min.12600
330kV~400kV
6250
780
Min.23100
500kV
7750
780
Min.24800
[Prefablicated Type]
30
Accessories
No.
Description
Material
Conductor Sleeve
Copper
EPR
Hollow Insulator
Polymeric or Porcelain
Compound
Silicone Oil
Epoxy Support
Epoxy
Post Insulator
Porcelain
Aluminum or Copper
Compression Ring
Stainless Steel
Rated
Voltage
H
[mm]
D
[mm]
Creepage Distance
[mm]
110kV~161kV
2650
355
Min.8300
220kV~275kV
2750
560
Min.8800
Accessories
SF6 Gas Insulated Termination
[Prefablicated Type]
D
Material
Upper Metal
Aluminum
Epoxy Bushing
Epoxy
Conductor Sleeve
Copper
EPR
Compression Ring
Stainless Steel
Copper or Aluminum
No.
Rated
Voltage
[Dry Type]
Dry Type
D
[mm]
H
[mm]
D
[mm]
66kV~88kV
583
110
310
110
110kV~161kV
757
110
470
110
220kV~275kV
960
200
620
140
330kV~400kV
1400
250
960
140
[Slip-on Type]
D
No.
Description
Material
Upper Metal
Aluminum
Epoxy Bushing
Epoxy
Conductor Sleeve
Copper
Silicone Rubber
Compound
Polybutene Oil
Sealing Unit
Silicone Rubber
Copper or Aluminum
Rated
Voltage
H
[mm]
D
[mm]
110kV~161kV
757
110
220kV~275kV
960
140
330kV~500kV
1400
140
Accessories
31
Accessories
COMPOSITE HOLLOW BUSHING
Taihan has been developing and producing composite hollow bushing which consists of FRP tube and
silicone rubber sheds to withstand various environmental conditions. The advantage of composite
bushing over traditional porcelain bushing has been proven and is well known and accepted.
ADVANTAGES
Reduced Risk for transport and assembly (no broken sheds)
Explosion Safety for personnel and installation
Excellent Seismic Performance
High Insulating Performance in highly polluted environment
APPLICATIONS
Cable Terminations
Circuit Breakers
Instrument Transformers
Lightning arrester
[Normal flange]
[Cap flange]
OD
OD
ID
ID
Rated
Voltage
110kV~161kV
220kV~275kV
32
Accessories
Creepage Distance
[mm]
Arcing Distance
[mm]
H
[mm]
ID
[mm]
OD
[mm]
Min.5280
Min.1495
1676
260
378
Min.6720
Min.1879
2060
260
378
Min.8150
Min.2263
2444
260
378
Min.9100
Min.2308
2535
370
505
Accessories
GIS EPOXY INSULATOR
Taihan has been manufacturing several kinds of cast epoxy insulators which are using in GIS systems.
With our extensive knowledge regarding material technology with advanced process engineering
skills, we have been developed and produced GIS insulator upto 800kV grade.
VACUUM CASTING TECHNOLOGY
Void-free Insulation
Excellent adhesion to metallic parts
Net shape casting
PRODUCT
Insulation Spacer
Tri-post Insulator
Earthing Terminal
Insulation Supporter
[420kV 1P Spacer]
[550kV 1P Spacer]
[170kV 3P Spacer]
33
Diagnosis System
Cable Diagnosis System
1. Total Monitoring System (TMS)
As a cable Total Monitoring System, TMS consists of three parts functionally, DTS system which can
monitor distributed temperature of the cable, cable model data which includes thermal resistance
and capacitance, and cable current value acquisition module. Menus of TMS are DCR, DTS, Alarm,
Section, Setup, and History.
DCR menu
How long current can be sustained from now on?
8Hr
DTS menu
Detect cable fault symptom, and find out fault location
as analyzing distributed temperature.
1) Location of Bottle Necks
2) Cable Surface Temperature
3) Cable Conductor Temperature
4) Spatial Peak & Time Interval
Peak
Data Summary Table
Alarm works for exceeding limitation of cable surface temperature, conductor temperature,
conductor temperature 0deviation, temperature differences between joints, peaks, and cable
permitted load. Malfunction of DTS are also sensed based on DTS temperature data.
Section can be set by operator to monitor whole cables separating them into several sections.
These sections are usually divided depending on joints, but its flexible. Information for recent alarm
is shown on the section table.
History menu supports operators to inquire temperature and alarm history data. Operator can
choose cable surface temperature, conductor temperature, peaks as inquiry objects, and they are
displayed on the chart. Alarm data are listed up at a table. The chart and table can be printed as an
image and a table respectively, and they can be exported as an excel file.
34
Diagnosis System
1) Measurement Method
Impress an AC voltage of commercial cycle to a conductor to detect partial discharge of the insulator
between the conductor and a shielding layer. And measure the starting electric charge and frequency
of the partial discharge.
2) Analyzing Measurements
ICM System
(1) Main Components of PD Devices
Amplifier Unit
Pulse Generator
Spectrum Analyzer
HFCT Sensor
Foil Sensor
Diagnosis System
35
Diagnosis System
Cable Diagnosis System
PD Base System
(1) Main Components of PD Devices
PD Base
Direct Coupler
Calibrator
System Controller
Amplifier Unit
Media Converter
Synchronization Sensor
3) Available Equipment
Equipment
Manufacturer
Purchasing Date
ICM
System
Power Diagnostix
(Germany)
2003/08
PD Base
System
36
Diagnosis System
TECHIMP
(Italy)
2005/07
Diagnosis Performances
KEPCO (345kV Yeongseo -Yeongdeungpo T/L, 154kV Seongdong - Heungin T/L,
154KV Daejeon - Shinheung T/L, etc.)
Commercial Clients (Many sites including Korea LNG Gas)
KEPCO (Many works including 154kV underground T/L in Central P/O of Seoul
Electric Power)
Commercial Clients (Many sites including 230kV Singapore, 154kV Changwon
Specialty Steel, 154kV Honam Thermal Power Plant and
345kV Yangyang Pumping-up Power Plant)
4) Available Equipment
Equipment
Manufacturer
Therma
CAM
QuickView
FLIR System
(Sweden)
Purchasing Date
2004/01
Diagnosis Performances
KEPCO (345kV YeongseoYeongdeungpo T/L, 154kV
Seongdong - Heungin T/L, 154Kv
Daejeon -Shinheung T/L, etc.)
Consigned patrol(Yeongseo,
Seongdong and Daejeon Electric
Power)
Commercial Clients (Many sites
including Korea LNG Gas, Changwon
Specialty Steel, Yangyang Pumpingup Power Plant) <2 times of
measurements a year>
Method of Evaluation
Locking Device of Exits, Installation state of ladder & guard rail, leakage & crack in
electric power culvert, cleaning state of electric power culvert, prevention of disaster
in electric power culvert, snake deformation of cable, prevention of disaster for cable,
state of curvature, disorder of fire shielding plate
* Inspection of power transmission facilities can be performed in on-line or off-line state according to the properties of a facility.
Diagnosis System
37
APPENDIX
Certification
The outstanding quality of TAIHAN EHV XLPE cables are verified by internationally accredited certification institutes.
38
No.
Date
Voltage Grade
Institute
Specification
BIL (kV)
May-86
KEMA
IEC 502
650
May-86
Cable
KERI
KEPCO
750
Aug-86
Cable
KERI
KEPCO
750
Aug-88
Cable
KERI
KEPCO
750
May-95
Cable
Crown Agents
IEC 840
650
May-96
Crown Agents
IEC 840
650
May-97
KERI
KEPCO
750
Sep-97
KERI
KEPCO
750
Jun-98
KEMA
IEC 840
1050
10
Sep-99
KERI
KEPCO
750
11
Aug-00
Taihan
IEC 62067
650
12
Aug-00
KEMA
IEC 60840
650
13
Mar-01
Taihan
650
14
Jun-01
KERI
15
Dec-03
Taihan
16
Mar-04
KERI
17
Jan-05
KEMA
IEC 60840
KEPCO
IEC 62067
IEC 60840
KEPCO
IEC 62067
IEC 62067
18
Feb-05
Cable
CTL(USA)
AEIC CS7-93
650
19
Apr-05
SGS
20
Jul-05
KERI
21
Apr-05
SGS
IEC 62067
KEPCO
IEC 62067
KEPCO
IEC 60840
1050
22
Sep-05
KEMA
IEC 60840
650
23
Oct-05
Cable
Taihan
IEC 60840
650
24
Oct-05
Cable, NJ
KERI
IEC 60840
650
25
Nov-06
Cable
Taihan
IEC 61901
Appendix
1300
650
1300
1425
1300
750
No.
Date
Voltage Grade
26
Oct-05
27
Sep-06
28
Nov-06
29
Jan-07
30
Institute
Specification
BIL (kV)
Cable
Taihan
IEC 60840
IEC 60840
KEMA
IEC 62067
IEC 62067
Taihan
IEC 60840
IEC 60840
Taihan
IEC 60840
IEC 60840
Jan-07
KEMA
IEC 60840
IEC 60840
31
May-07
KEMA
IEC 60840
IEC 60840
32
Dec-07
400kV
KEMA
IEC 62067
IEC 62067
33
Dec-07
KEMA
IEC 62067
IEC 62067
34
Jul-07
Cable, IJ
Taihan
IEC 60840
IEC 60840
35
Oct-07
Cable
KEMA
IEC 60840
IEC 60840
36
Jul-08
KERI
KEPCO
KEPCO
37
Mar-08
Taihan
IEC 60840
IEC 60840
38
May-08
Taihan
IEC 60840
IEC 60840
39
Jun-09
KERI
IEC 60840
IEC 60840
40
Jun-09
KERI
IEC 60840
IEC 60840
41
Jun-09
KERI
IEC 60840
IEC 60840
42
Dec-09
KEMA
IEC 62027
IEC 62027
43
Jul-09
132kV 1000mm
KEMA
IEC 60840
IEC 60840
44
Feb-10
KERI
KEPCO
KEPCO
45
Jan-10
KEMA
IEC 62027
IEC 62027
46
Mar-10
Taihan
IEC 60840
IEC 60840
47
Apr-10
132kV 1200mm
Cable, NJ, GIS & Outdoor Termination, CrossBonding Link Box, Solid Link Box with Arrester,
Solid Bonding Link Box without SVL's
KEMA
IEC 60840
IEC 60840
48
May-10
230kV 3500mm
KEMA
IEC 62067
AEIC CS9-06
49
Dec-10
220kV 1200mm
IEC 62067
AEIC CS9-06
Taihan
IEC 62067
IEC 62067
50
Jul-10
230kV 2000mm
Taihan
IEC 62067
IEC 62067
51
Mar-11
220kV1200mm (AL)
KEMA
IEC 62067
IEC 62067
KEMA
IEC 62067
IEC 62067
Taihan
IEC 62067
IEC 62067
IEC 60840
IEC 60840
400kV 2500mm (Enamel - CU) Cable, IJ, GIS & Outdoor Termination
400kV 2500mm (Enamel - CU) Cable, NJ, GIS & Outdoor Termination
52
Nov-10
500kV 2500mm
53
Jan-11
54
Feb-11
138kV 1200mm
Taihan
55
May-11
132kV 630mm
Taihan
IEC 60840
IEC 60840
56
Jul-11
66kV 1000mm
Taihan
IEC 60840
IEC 60840
Taihan
IEC 60840
IEC 60840
132kV 630mm
Oct-11
57`
Cable
System Certificates
No.
Institute
Date
Specification
SGS-ICS
2001.02
ISO 14001
SGS-ICS
2003.03
ISO 9001
Appendix
39
APPENDIX
Global
Networks
APPENDIX
APPENDIX
Global
Networks
APPENDIX
Global
Networks
Global
Networks
Global
Networks
GlobalNetworks
Networks
Global
Subsidiary Company /
Branch office
Subsidiary
Company
office
Subsidiary
Company/ / Branch
Branch
office
Russia
USA
Russia
Russia
USA
USA
Qatar
Qatar
Qatar
New Zealand
New
Zealand
New
Zealand
Dubai
Representative
Dubai
Branch
Office Office
TEL
TEL :: +971-4-368-8988
+971-4-368-8988
Kuala
119421,Lumpur
Moscow,Branch
LeninskyOffice
prospekt D 111, korpus 1, 2nd floor, 121,122
Russia
Branch
No.
2nd
Floor,Office
Jalan Pandan Prima 1 Dataran Pandan Prima 55100 Kuala Lumpur, Malaysia
TEL
TEL9,:: +7-495-989-5812
+7-495-989-5812
TEL
: +60-3-9018-9113/9115
FAX : +60-3-9200-1136
E-mail
::Moscow,
vkn@taihan.com
E-mail
alexlee@taihan.com,
alexlee.taihan@gmail.com
119421,
Russia. Leninsky
prospect
d. 111, korp. 1, floor 2, office 121-122.
E-mail : iamsj@taihan.com
TEL : +7-495-989-5812
E-mail
: alexlee@taihan.com,
alexlee.taihan@gmail.com
Singapore
Branch Office
Singapore Branch
Branch Office
Office
Singapore
150
Kampong
AmpatOffice
#07-04 KA Centre Singapore 368324,
Singapore
Republic
ofBranch
Singapore
Republic
of Singapore
TELKampong
: +65-6842-5069
FAX : +65-6842-5076
150
Ampat #07-04 KA Centre Singapore
368324,
TEL
: +65-6842-5069
FAX : +65-6842-5076
E-mail
: hcjung@singnet.com.sg
Republic
of
Singapore
E-mail : iamsj@singnet.com.sg
TEL : +65-6842-5069
FAX : +60-3-9200-1136
E-mail
: hcjung@taihan.com
Newzealand
Branch Office
Kuala Lumpur
Lumpur Branch
Branch Office
Office
Kuala
Suite
2, Level
11,Pandan
48 Emily
Place,
AucklandPandan
PO BoxPrima
105895,
No. 2-09,
Jalan
Prima
1 Dataran
55100 Kuala Lumpur, Malaysia
TEL : +60-3-9018-9113/9115
FAX : +60-3-9200-1136
TEL
: +64-9-368-7703
: +64-9
368-7704
E-mail
hcjung@taihan.com
No.E-mail
2-09,
Pandan Prima 1 DataranFAX
Pandan
Prima
55100 Kuala Lumpur, Malaysia
:: Jalan
hcjung@taihan.com
jshuh@taihan.com
TELE-mail:
: +60-3-9018-9113/9115
FAX : +60-3-9200-1136
E-mail : hcjung@taihan.com
No. 2-09, Jalan Pandan Prima 1 Dataran Pandan Prima 55100 Kuala Lumpur, Malaysia
Kuala
Branch1143
Office
Auckland
City, Auckland
TEL : Lumpur
+60-3-9018-9113/9115
FAX : +60-3-9200-1136
40
64
64
Appendix
38 Appendix
Australia
BranchOffice
Office
Australia
Branch
TEL : +61-2-9460-3600
Suite 2, Level 11, 48 Emily place Auckland PO BOX 105895, Auckland City, Auckland 1143
FAX : +64-9-368-7704
E-mail
: okkwon@taihan.com
Suipacha
Suites,
Room
909
Suipacha
1235
Suite
2, Level
11, 48
Emily
Place,
PO Box
105895, Auckland 1143, New Zealand
TEL: +64-9-368-7703
: +54-911-6413-7430
FAX
: 54-911-6413-4694
TEL
FAX
: +64-9-368-7704
EUSA
MAIL
: sikim@taihan.com
E-mail
: Branch
okkwon@taihan.com
Office
Argentina
Branch
Newzealand
BranchOffice
Office
TEL : +64-9-368-7703
South Africa
Malesela Taihan Electric Cable Pty., Ltd. (M-TEC)
Overseas
Subsidiaries
Overseas
Subsidiaries
PO Box 1643,
Vereeniging 1930, Gauteng, South Africa
South
Malesela Taihan Electric
Cable
Pty., Ltd. (M-TEC)
TEL : Africa
+27-16-450-8200
FAX
: +27-16-450-8202
South
Africa Malesela Taihan Electric
Cable
Pty., Ltd. (M-TEC)
: kskil@m-tec.co.za
Website
www.m-tec.co.za
POE-mail
Box 1643,
Vereeniging 1930, Gauteng,
South: Africa
Steel
Road Peacehaven Vereeniging 1930
Gauteng, South Africa
TEL
: +27-16-450-8200
FAX : +27-16-450-8202
TEL ::+27-16-450-8200
FAX Website
: +27-16-450-8202
E-mail
kskil@m-tec.co.za
: www.m-tec.co.za
D.R. Congo
STANDARD TELECOM
E-mail
: junehah@m-tec.co.zaWebsite
: www.m-tec.co.za
No.
158833, Blvd du 30 Juin, Commune de la Gombe, Kinshasa, D.R.Congo
D.R.
STANDARD TELECOM FAX : +243-1511-1100
TELCongo
: Congo
+243-1511-0007
D.R.
STANDARD TELECOM
colee@stelecom.cd
: www.st.cd
No.E-mail
833, :Blvd
du 30 Juin, Commune de Website
la Gombe,
Kinshasa, D.R.Congo
158,
Avenue
de
la Democratie(Ex- Huilerie)
Commune de la Gombe, Kinshasa, D.R.Congo
TEL : +243-1511-0007
FAX : +243-1511-1100
TEL
:
+243-1511-0007FAX
:
+243-1511-1100
E-mail
: colee@stelecom.cd
Website
: www.st.cd
Taihan Sacom Cable Co.,
Ltd (TSC)
Vietnam
E-mail
: colee@stelecom.cdWebsite
: www.st.cd
152/11B Dien Bien Phu St., W.25, Binh Thanh District, HCM City
Taihan Sacom Cable Co., Ltd
(TSC)
Vietnam
TEL : +84-8-3518-0786
: +84-8-3514-0516
Taihan Sacom Cable Co., FAX
Ltd (TSC)
Vietnam
E-mail :Dien
ysshin@taihan.com,
shkim@taihansacom.com
kimjh@tscable.com.vn
WebsiteDistrict,
: www.tsc.vn
152/11B
Bien Phu St., W.25,
Binh Thanh
HCM City Website : www.tsc.vn
7th: +84-8-3518-0786
Floor, 71-73 Dien Bien Phu, phuong
Binh Thanh District, Vietnam
TEL
FAX 15,
: +84-8-3514-0516
TEL ::+84-8-518-0786FAX
+84-8-518-0785
E-mail
frkwak@tscable.com, :shkim@taihansacom.co
Website : www.tsc.vn
E-mail
kimjh@tscable.com.vnWebsite
: www.tsc.vn
USA (Taihan Electric USA.,
Ltd.)
USA : Taihan
LandMark Building, 99 Tulip Avenue, Suite#106, Floral Park, NY 11001, USA
USA (Taihan Electric USA.,
Ltd.)
USA
TEL :Taihan
+1-516-355-5600
FAX
: +1-516-355-5601
Taihan USA (Taihan Electric USA.,
Ltd.)
USA
E-mail : cwlee@taihan.com
sw1012@taihan.com
LandMark
Building,
99 Tulip Avenue, Suite#106, Floral Park, NY 11001, USA
LandMark
Building, 99 Tulip Avenue,FAX
Suite#106,
Floral Park, NY 11001, USA
TEL
: +1-516-355-5600
: +1-516-355-5601
TEL ::+1-516-355-5600FAX
E-mail
sw1012@taihan.com : +1-516-355-5601
Hong :Kong
TGH (Taihan Global Holdings, Ltd.)
E-mail
sw1012@taihan.com
12/F., 3 Lockhart Road, Wanchai, Hong Kong
Hong Kong TGH (Taihan Global Holdings, Ltd.)
Hong Kong TGH (Taihan Global Holdings, Ltd.)
12/F., 3 Lockhart Road, Wanchai, Hong Kong
No.1808, 18F, Tower 2, Admiralty Center,18 Harcourt Road, Admiralty, Hong Kong
Head Office
Dangjin Plant
TPE-0504-1402