Академический Документы
Профессиональный Документы
Культура Документы
Applied Energy
journal homepage: www.elsevier.com/locate/apenergy
h i g h l i g h t s
Off-grid Mini-grids can be implemented in different ways. It depends on the AC load prole.
Not always the AC coupled is the best option.
There are different PV inverters that can be used in the implementation.
New PV inverter concept, multiport inverter, is being deployed in off-grid Mini-grids.
In medium and high penetration the control strategy of all elements of the Mini-grid system is a key point.
a r t i c l e
i n f o
Article history:
Received 6 November 2014
Received in revised form 4 June 2015
Accepted 25 July 2015
Keywords:
PV Hybrid
Off-grid
Mini-grids
Multiport inverter
MPPT
Charge controller
a b s t r a c t
The target of this manuscript is to make a review about the Off-grid Photovoltaic Diesel Hybrid Systems
(Off-grid Mini Grids) where only AC loads are connected. It will take into consideration the different types
(performed through of the DC coupled, AC coupled or hybrid DCAC coupled congurations), solutions
(PV/Diesel and PV/Diesel/Energy Storage) related with the diesel hybridization of those systems and their
main elements (power converters). So, it will encompasses an analysis about the current state of the technique of converters implemented in those systems, including the stand-alone inverters, bidirectional,
multiport and even the grid-connected inverters implemented in the AC coupled systems. In addition,
the standardization in this topic will be analyzed too.
2015 Elsevier Ltd. All rights reserved.
Contents
1.
2.
3.
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .196
Power converters implemented in the PV Hybrid Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .196
2.1.
Battery charging systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
2.2.
PV inverters implemented in PV Hybrid systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
2.2.1.
Stand-alone inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
2.2.2.
Grid-interactive inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
2.2.3.
Bidirectional inverter (BDI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
2.2.4.
Multiport input/multi output inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
2.2.5.
Grid-connected inverters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
PV diesel hybrid solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
3.1.
Integration of the photovoltaic into genset systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
3.1.1.
Low penetration (<20%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
3.1.2.
Medium penetration (2065%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
3.1.3.
Continuous genset operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
196
3.1.4.
Intermittent genset operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Power management in PV hybrid systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
3.2.1.
Grid forming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
3.2.2.
Supervisoy control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
3.2.3.
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Case studies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .209
4.1.
Small-scale PV Hybrid System, less than 100 kW scale systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
4.2.
Medium-scale PV Hybrid System, more 100 kW scale systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
4.3.
Large-scale PV Hybrid Systems, more than 1000 kW scale systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
4.3.1.
Case Study 1: 4.2 MW PV/Diesel/Battery Micro Grid System implemented in a remote site in Tanjung Labian, Malaysia, 2012. 210
4.3.2.
Case Study 2: 3.3 MW, PV/Diesel/Battery Micro Grid System implemented in a remote site at Kemar Villages, Gelik, Perak,
Malaysia, November 2012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
4.3.3.
Case Study 3: 4.93 MW, PV/Diesel/Battery Micro Grid System implemented in a remote site at Banggi Island, Kudat, Sabah,
Malaysia, March 2014 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
4.3.4.
Case Study 4: 2.84 MW PV/Diesel/Battery Micro Grid System implemented in a remote site at Sswee Island, Kalangala,
Lake Victoria, Uganda, September 2014 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
International standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .213
5.1.
Standards related with PV modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
5.2.
Standards for battery charge controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
5.3.
Standards for inverters (stand-alone, bidirectional, interactive and grid-connected) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
5.4.
Standards for batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
5.5.
Standards related to consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Conclusions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214
3.2.
4.
5.
6.
1. Introduction
At present, a huge of inhabitants worldwide including still lack
access to utility electricity, most living in small remote villages or
isolated islands far away from power grid [1,2].
A utility grid extension to these off-grid locations is impractical
and uneconomical due to such conditions as dispersed population
or rugged terrain [3]. As a result, the electrical demand of such
places is normally powered by diesel generators [46] or even with
no power supply.
The signicant rise of diesel price and subsequent environmental pollution concerns [7], however, have drawn extensive public
attention to the need of renewable energy applications such as
solar photovoltaics (PV) power.
Standalone renewable energy systems (RESs) have a reputation
for being inexhaustible, environmentally benign, reliable, efcient,
and with cost-effective characteristics and are hence seen to be the
most likely viable energy supply solutions to such areas. Besides,
renewable energy holds the key to future prosperity and a healthy
global environment and is considered a promising means of solving the problems of environmental pollution [810].
Therefore, the last decade has witnessed a dramatic expansion
in the use of renewable energies as substitutes of fossil-based
energy, a noted by-product being the potential to reduce atmospheric degradation [11].
A potential solution for addressing these problems can be the
use of the photovoltaic hybrid systems. A photovoltaic hybrid system is a system that is formed by combining two energy sources,
at least, including the photovoltaic energy. They can be off-grid or
grid-connected. Regarding off-grid, the PV Hybrid systems can be
divided into: micro (less than 5 kW), small (530 kW), medium
(30100 kW), large (100 kW1 MW) and very large (greater than
1 MW) systems [1214].
Micro PV hybrid systems are related to residential solutions.
Small PV hybrid systems are suitable for supplying the power
needs of a small rural village where the energy consumption is
quite limited; for instance a village with no, or very few, productive
or commercial activities. Medium-size hybrid systems are suitable
to supply the power needs of a village where productive and commercial activities use energy during the daytime.
197
Leonics
Morningstar
Outback
Schneider
SMA
Steca
Studer
Victron
SCM-480200
TS-MPPT-60
Flexmax 60
XW MPPT 80 600
1
1
1
1
480
48
1260
2448
200
60
60
80
<550
<150
<150
<500
2
1
1
1060
1248
1248
60
80
85
<200
<150
<150
Simple technology
Better efciency
Technique similar to
inverters used for
connecting to grid but
with simpler circuits and
no protection from or
synchronisation with
grid
Elevated efciency
No regulation of
outgoing voltage
(varies with charge
and incoming
voltage)
198
generator into AC power for supplying to load and feed the excess
energy back to utility grid line. When utility power is not available,
the inverter can operate as backup power source to supply power
from PV panels and battery, Fig. 3.
In a grid-interactive system, that inverter is a much smarter,
more agile device and capable of doing three things as opposed
to the one-trick grid-tied inverter [29]: like a grid-tied inverter, a
grid-interactive type can convert solar-generated DC power to AC
power; it can also function as a battery charger and store energy
in a battery system designed for residential and commercial applications and it can convert battery-produced DC during an outage
into useable AC power and charge those batteries during the day
from the PV generator or a genset. It can even turn a generator
on as needed. Having battery-back up taking care of power needs
in the evening means the generators run time and fuel consumption can be greatly reduced during an outage.
Model
Phase
Range of power
(kW)
Battery
voltage (V)
Ingeteam
Ingecon Hybrid
AC Link
Apolo S
Apolo STP
Apolo M
Apolo MTP
FX and VFX
Sunny Island
Compact and
Xtender
Conext XW
Multiplus
HIS1
HTDI
60250
330820
1
3
1
3
1
1
1
330
15100
520
152400
23
58
0.57
48
48
120240
120480
1248
48
1248
7
1
1
3
7
0.85
1.28
1501800
48
1248
2448
672
Leonics
Outback
SMA
Studer
Schneider
Victron
Zigor
Table 4
Three-phase off-grid PV Hybrid system options for a AC coupled conguration.
Three-phase
system
String
inverter
Option
Option
Option
Option
X
X
1
2
3
4
Central
inverter
Bidirectional
single-phase
Bidirectional
three-phase
X
X
X
X
X
X
[30]. In addition, it has Intelligent Battery Management for charging and discharging the batteries.
The BDI (Bidirectional Inverter) can be integrated in the AC coupled topology, Fig. 4 [31,32].
Currently, the BDI (Bidirectional Inverter) is marketed as a single compact enclosure for ranges between 0.8 kW up to 1800 kW.
And where even the lithium batteries are approved for almost all
models.
According to Table 3, can be seen that about the battery voltage
there are two types of BDI: with low voltage (12, 24 and 48) and
with high voltage (330, 820). In addition, it can be distinguished
between single-phase (up to 20 kW) or three-phase (up to
1800 kW). Although there are much more models for
199
Fig. 5. Block circuit diagram for a three-phase multi-cluster Off-grid system. Source: SMA.
200
Fig. 6. The schematic block diagram of the multiport input/multi output inverter.
However, in both cases, they consist of multiple power processing stages that contribute to lowering the efciency of the overall
system.
Finally an alternative to inverter topologies previously presented that simplies and reduces the cost of those inverters while
increasing their reliability can be a single-stage multi-input high
Model
System power
(kW h)
Battery nominal
voltage (V)
ABB
REACT-3.6-TL
REACT-4.6-TL
2
2
Bosch
BPT-S 5 Hybrid
4.4
6.6
8.8
11
13.2
96
144
192
240
288
GoodWe
GW5048D-ES
GW3648D-ES
0.5
0.5
4060
4060
Kostal
PIKO BA System
2.8
228
PowerRouter
3.6
48
SMA
150
150
201
in these inverters are Li-ion, except Kostal product where only OPzV
battery type can be connected. Anyway, by using single-phase
equipment can create three-phase off-grid system as well as
increasing the system power by connecting inverters in parallel.
Fig. 8 shows an example of topology for those inverters.
In general, they are applicable for both on-grid and off-grid PV
systems and can control the ow of energy hybrid with its working
situation able to be switched automatically or manually.
During the daytime, the PV plant generates electricity that can
be provided to the loads, fed into the grids or charged the battery.
The power stored can be released when the loads require it during
the night. In the Table 5 is shown a list of some battery hybrid integrated inverters. According Table 5, the battery nominal voltage
varies between 40 up to 288 Volts.
Instead, medium size hybrid inverters are always three-phase
inverters where the power rating is from 120 to 300 kW for each
inverter and 50200 kW for MPPT charge controller. In addition,
they can parallel operation of inverters for total inverter power
up to 1200 kW and up to 2000 kW of PV. They are design for operate in micro grid operation with utility line or operate as
stand-alone PVDG Hybrid, Fig. 9. Then, then can provide backup
power to load when utility grid line is not available and supply
load and charge battery from PV panels at the same time [38].
2.2.5. Grid-connected inverters
These inverters have a technology well known, [3941] and
they only can be implemented in the PV Hybrid systems along with
a bidirectional inverter in an AC coupling conguration. Then, they
always are running as current source. The stand-alone operation is
not possible for those inverters.
The AC bus is made by the bidirectional inverter or by the genset, [4244].
202
Fig. 10. World crude oil prices. Source: Bloomberg, Thomson Reuters.
203
204
Controllable characteristic
Control possibilities
PV generator
Power
Communication line
Frequency
Batteries
Depth of discharge
Number of cycles per day
Charge/discharge power
Communication line
Frequency
Energy management
Genset
Communication line
Start/stop signal
Frequency
Consumption
Communication line
Frequency User
For a PV penetration between 40% and 65% additional components are required, such as short and long-term energy storage.
Two possible dispatch strategies of genset operation can be possible: continuous and intermittent operation [5961].
3.1.3. Continuous genset operation
Any PV Hybrid system under continuous operation in medium
penetration has the following elements: PV generator, genset(s),
PV grid-connected inverter, wattmeter and control system. The
control is required for protecting the diesel generator(s) from
low loading and limiting generator cycling. It must be taken into
account that it is not recommendable that a genset is operated at
load below than 0.15 of its nominal power. This value may also
be recommended to secure the electrical stability of the grid
formed by the generator of the gensets. As a consequence for systems without storage, PV power has to be dumped in the case that
the effective load (loadPV power) is pushed to this boundary. This
affects again the fuel savings. A reduction of these losses however
can be achieved by splitting the total DGS (Diesel Generators)
capacity into several units with at best unequal sizes, together with
the appropriate scheduling. By this, the required minimal load can
be reduced to that for the smallest of the diesel units.
Then, the control system establishes communication with the
power meter, PV inverters and load control managing
demand-based PV feed-in into the diesel-powered grid. This control system helps to the system in the following items: minimum
diesel load (it guarantees that the diesel generator does not operate under a minimum load level, in order to ensure a longer engine
life); reverse power protection (it avoids a power ow from the
inverter to the genset, for example, in the event of a total load disconnection); stability against irradiance variations (stability
against irradiance variation it is guaranteed by the spinning
reserve of the genset, previously sized for the maximum possible
load) and load control (it allows switching loads on when the genset load level is low and there is a PV generation surplus) [62].
Advantages for this solution are: reduction of diesel consumption, lower cost of energy, unlimited resource and resource
availability.
3.1.4. Intermittent genset operation
In this type of operation, the on/off control of genset is imposed.
Two different systems can be distinguished: without energy storage and with energy storage. In both cases are necessary two types
of controllers: a diesel manager and a system controller.
In systems where there is no energy storage, the photovoltaic
inverters inject current to the diesel grid, being detected by the
genset as a load reduction. The controller monitors the genset
units, obtaining which ones are operating as well as their load
level. This information is used to determine the maximum power
that the solar inverters can supply in order to guarantee the system
stability, i.e. in a cloud-shading event.
205
206
Table 7
Grid forming, supervisory control and communication in PV Hybrid Systems.
Grid forming
Supervisory control
Communication
CAN/CANopen
IEEE P1547-3 guide line
IEC 61850-7-420
UESP developed by CIA
207
208
runs in short intervals, keeping the SOC at the same level. The battery is re-charged from renewable sources. Charging the battery to
its full capacity is applied periodically if there is not enough renewable sources available for longer periods.
Another supervisory can be the power converter control without storage, where the following controls can be distinguished:
PV supply load and use excess energy to charger battery, power
limit control/Back feed control, dummy load dispatching and
deferrable load dispatching.
And the last supervisory control is the power converter supervisory control with storage in where three different types of control
can be distinguished: transient support, PV and genset-base battery charging and PV battery charging only.
In the transient support the reserve power is provided by a
storage unit, capable of delivering very quickly a high level of power.
In the PV and genset-base battery charging the gensets are
operated at their optimal efciency level to cover the load and
charging the battery with the surplus power. Typically, the diesel
gensets are running when the load level is high in order to reduce
the amount of energy to be stored in the battery. When the load
level is low, the load can be directly fed by the battery and the gensets
can be switched off in order to avoid inefcient low loading operation.
In the PV battery charging only the batteries are charged by PV
only. The gensets are not able to charge the batteries. The main role
of the battery is to shift solar power use to optimal periods of the day.
The Peak shaving strategy consists on operating the genset at
full power. Battery power is only used to meet buffer instantaneous uctuations around the netload. Battery power is used as a
Table 8
Dispatch strategy for the different elements of any PV Hybrid System.
Element
Action
Dispatch strategy
Diesel
Diesel starts
At specic battery level that is determined by the state of charge (SOC) or battery terminal voltage
At specic site load power which is measured as a percentage of the diesel generator or inverter rated capacity
At specic renewable output power as a percentage of the peak power of the PV generator
After a specic time period
At xed, at the full power rating
Diesel meeting the entire load and charging the battery if required
Diesel meeting the base load with battery supplying the transient load
At specic battery level that is determined by the SOC or battery terminal voltage
At specic site load power which is measured as a percentage of the diesel generator or inverter rated capacity
At specic renewable output power as a percentage of the peak power of the PV generator
At specic power transferred to battery
At specic diesel operating power level
After a specic time period
Diesel generator
operation
Diesel stops
Inverter
Inverter operation
Battery
charger
Battery charger
starts
Battery charger
power level
Battery charger
stops
(1) At the beginning of the diesel operating. (2) At specic battery level during the running of the diesel generator. (3) At specic
diesel operating power level. (4) At specic PV output power
(1) Fixed at the full power rating of the charger. (2) Varying to meet the maximum battery charging rate
At specic battery level
At specic diesel operating power level
At specic PV output power
Spectrum
GSM
GPRS
3G
WIMAX
PLC
ZigBee
9001800 MHz
9001800 MHz
1.921.98 GHz
2.53.5 GHz
130 MHz
2.4915 MHz
110
110
110
1050
13
0.30.50
frequency and grid voltage for the control of the AC bus (AC grid)
[111116].
Nowadays, the modern grid-tie inverters come with a lot of
functionality compared to inverters of the past. Key features
including grid frequency dependent are related with the active
power reduction, Grid frequency dependent power reduction
(GFPR) or with the reactive power characteristics, including power
factor or Q, Grid Voltage dependent Power reduction (GVPR) and
Reactive Power as a function of Voltage (Q = f(V)), [117].
That is to say, the main control strategy in microgrids can be
linked to the communication by means of the frequency and AC
voltage bus. Then power sharing without extra cabling can be done
if the components determine their instantaneous active and reactive power set value. The supervisory control just provides parameter settings for each component.
Such approach results in some advantages such as: more simple
expansion of the system, increased redundancy, as the system does
not rely on a vulnerable bus system, for optimization a simple bus
system is sufcient and a simplied supervisory control.
For instance, the frequency can be modied as a function of the
battery status or consumer on the AC bus can switch on/off according to the information carried out by the frequency [118].
209
Fig. 17. Case study of small-scale PV Hybrid System total power 75 kW is the system installed at school in Peninsular Malaysia, in Malaysia.
210
hybrid system consists of PV module 20 kWp, Bidirectional inverter 25 kW, Lead Acid Battery 1500 Ah 240 Vdc, and Diesel
Generator 30 kW. The system diagram is exhibited as follow in
Figs. 1719.
4.2. Medium-scale PV Hybrid System, more 100 kW scale systems
Case study of Medium-Scale PV Hybrid system total power
370 kW is the system installed at technical college in Cambodia,
Kampong Chheuteal (see Figs. 20 and 21). The PVDG system consisted of PV 120 kWp, Bidirectional inverter 75 kW, Lead Acid battery 1500 Ah, and Diesel Generator 100 kW. System operate since
September 2014 with the aim to reduce usage of diesel fuel from
100% to only 30%.
4.3. Large-scale PV Hybrid Systems, more than 1000 kW scale systems
Fig. 18. Implementation of the case study of Fig. 17.
Fig. 20. Case study of Medium-Scale PV Hybrid system installed in Cambodia at Kampong Chertial College by NSTDA, Thailand working for the IT Project under H.R.H.
Princess Maha Chakri Sirindhorns Initiatives.
211
Fig. 21. Daily graph of the implementation of the Cambodia system according to Fig. 20 installed in Cambodia at Kampong Chertial College by NSTDA, Thailand working for
the IT Project under H.R.H. Princess Maha Chakri Sirindhorns Initiatives.
212
Fig. 23. Diagram of the installation implemented in Tanjung Labian (Malaysia), by Leonics.
Fig. 24. Equipment for the installation implemented in Tanjung Labian (Malaysia), by Leonics.
Table 10
Standards related with PV modules.
61464) and safety (IEC 61730). The IEC 60904-1 provides procedures for the measurement of currentvoltage characteristics of
photovoltaic devices in natural or simulated sunlight.
Standard
Title
IEC 61215
IEC 61464
IEC 61730
Standard
Title
IEC 61683
IEC 62891
IEC 60904-1
213
Table 11
Standards related with efciency in PV power converters.
214
Table 12
Standards about batteries.
Standard
Title
IEC 60896-11
IEC 61427
IEC 62485-2
IEEE 1361
Table 13
Standards related with consumptions.
Standard
Title
IEC 60969
IEC 61347-1-4
References
[1] The energy access situation in developing countries: a review focusing on the
least developed countries and sub-saharan Africa. New York and Geneva:
World Health Organization (WHO) and United Nations Development
Programme (UNDP); 2009.
[2] IEA. World energy outlook. 2nd ed. International Energy Agency Publications;
2006.
[3] Hansen U. Technological options for power generation. Energy J
1998;19(2):6387.
[4] Sopian K et al. Optimal operational strategy for hybrid renewable energy
system using genetic algorithms. WSEAS Trans Math 2008;7(4):13040.
[5] Bekele Getachew, Tadesse Getnet. Feasibility study of small Hydro/PV/Wind
hybrid system for off-grid rural electrication in Ethiopia. Appl Energy
2012;97:515.
[6] Lau KY et al. Performance analysis of hybrid photovoltaic/diesel energy
system under Malaysian conditions. Energy 2010;35(8):324555.
[7] Elhadidy MA, Shaahid SM. Parametric study of hybrid (wind + solar + diesel)
power generating systems. Renewable Energy 2000;21(2):12939.
[8] Himri Y et al. Techno-economical study of hybrid power system for a remote
village in Algeria. Energy 2008;33(7):112836.
[9] Sharma R, Tiwari GN. Technical performance evaluation of stand-alone
photovoltaic array for outdoor eld conditions of New Delhi. Appl Energy
2012;92:64452.
[10] Chel A, Tiwari GN. A case study of a typical 2.32 kWp stand-alone
photovoltaic (SAPV) in composite climate of New Delhi (India). Appl Energy
2011;88(4):141526.
[11] Shaahid SM, El-Amin I. Techno-economic evaluation of off-grid hybrid
photovoltaicdieselbattery power systems for rural electrication in Saudi
Arabiaa way forward for sustainable development. Renew Sustain Energy
Rev 2009;13(3):62533.
[12] Wuthipong. MW_scale_Stand-alone_PV-DG_Hybrid_systems, Leonics.
[13] Rethinking Energy. IRENA; 2014.
[14] Rural Electrication with PV Hybrid Systems. Overview and
Recommendations for Further Deployment. Report IEA-PVPS T9-13; 2013.
[15] Shaahid SM, Al-Hadhrami LM, Rahman MK. Review of economic assessment
of hybrid photovoltaicdieselbattery power systems for residential loads for
different provinces of Saudi Arabia. Renew Sustain Energy Rev
2014;31:17481.
[16] Hazelton James, Bruce Anna, MacGill Iain. A review of the potential benets
and risks of photovoltaic hybrid mini-grid systems. Renewable Energy
2014;67:2229.
[17] Nema P, Nema RK, Rangnekar S. A current and future state of art development
of hybrid energy system using wind and PV-solar: a review. Renew Sustain
Energy Rev 2009;13(8):2096103.
[18] Chauhan Anurag, Sain RP. A review on Integrated Renewable Energy System
based power generation for stand-alone applications: congurations, storage
options, sizing methodologies and control. Renew Sustain Energy Rev
October 2014;38:99120.
[19] Akikur RK, Saidur R, Ping HW, Ullah KR. Comparative study of stand-alone
and hybrid solar energy systems suitable for off-grid rural electrication: a
review. Renew Sustain Energy Rev November 2013;27:73852.
[20] Nehrir MH, Wang C, Strunz K, Aki H, Ramakumar R, Bing J, et al. A review of
hybrid renewable/alternative energy systems for electric power generation:
congurations, control, and applications. Sustain Energy, IEEE Trans
2011;2(4):392403.
[21] Pantelimon RF, et al. Aspects regarding solar battery charge controllers. In:
Advanced topics in electrical engineering (ATEE), 2013 8th international
symposium on; 2013. p. 16.
[22] Li J, Danzer MA. Optimal charge control strategies for stationary photovoltaic
battery systems. J Power Sources 2014;258:36573.
[23] Salas V et al. Review of the maximum power point tracking algorithms for
stand-alone photovoltaic systems. Rev Article, Sol Energy Mater Sol Cells
2006;90(11):155578.
[24] Bruendlinger R, Bletterie B, Milde M, Oldenkamp H. Maximum power point
tracking performance under partially shaded PV array conditions. In: Proc.
21st EUPVSEC; 2006. p. 215760.
[25] Bruendlinger R, et al. Performance of MPPT charge controllers a state of the
Art Analysis.
[26] Which solar charge controller: PWM or MPPT? Victronenergy; 2014.
[27] Swingler A. Photovoltaic string inverters and shade-tolerant maximum
power point tracking: toward optimal harvest efciency and maximum
ROI. White Paper, Schneider Electric; December 2010.
[28] Tey KS, Mekhilef S, Yang HT, Chuang MK. A differential evolution based MPPT
method for photovoltaic modules under partial shading conditions. Int J
Photoenergy 2014.
[29] Ozdemir S, Altin N, Sefa I. Single stage three level grid interactive MPPT
inverter for PV systems. Energy Convers Manage 2014;80:56172.
[30] Pierre-Olivier Moix. New trends in hybrid systems with battery inverter.
Studer Innotec.
[31] Nayar CV. Control and interfacing of bi-directional inverters for off-grid
and weak grid photovoltaic power systems. In: Power engineering society
summer meeting, 2000. IEEE, Volume: 2, vol. 2; 2000. p. 128082
[32] Trowler D, Whitaker B. Bi-directional inverter and energy storage
system. Arkansas: Texas Instruments; 2008. p. 129.
[67]
[68]
[69]
[70]
[71]
[72]
[73]
[74]
[75]
[76]
[77]
[78]
[79]
[80]
[81]
[82]
[83]
[84]
[85]
[86]
[87]
[88]
[89]
[90]
[91]
[92]
[93]
[94]
[95]
[96]
215
216
[97] Chua Kein Huat, Lim Yun Seng, Morris Stella. Battery energy storage system
for peak shaving and voltage unbalance mitigation.
[98] Hredzak B, Agelidis VG, Jang M. A model predictive control system for a
hybrid battery-ultracapacitor power source. Power Electron, IEEE Trans
2014;29(3):146979.
[99] Zhu B, Tazvinga H, Xia X. Model predictive control for energy dispatch of a
photovoltaicdieselbattery hybrid power system; 2014.
[100] Engler A, Hardt C, Bechtel N, Rothert M. Next generation of AC coupled hybrid
systems 3 phase parallel operation of grid forming battery inverters. In: 2nd
European PV-Hybrid and Mini-Grid Conference. Kassel; September 2003.
[101] Zahran M, Mahgoub O, Hanafy A. P-controller based photovoltaic battery
diesel (PVBD) hybrid system management and control. In: Energy conversion
engineering conference and exhibit, 2000. (IECEC) 35th Intersociety, Volume:
2, vol. 2; 2000. p. 1513521.
[102] Messinis George, et al. Application of rapid prototyping tools for a
hierarchical microgrid control implementation. In: Power electronics for
distributed generation systems (PEDG), 2014 IEEE 5th international
symposium on. IEEE; 2014.
[103] Camacho Oscar Mauricio Forero, Mihet-Popal Lucian. Fast charging and smart
charging tests for electric vehicles batteries using renewable energy. Oil &
Gas Science and Technology-Revue dIFP Energies nouvelles; 2014.
[104] Karfopoulos E, Tena L, Torres A, Salas Pep, Jorda Joan Gil, Dimeas A, et al. A
multi-agent system providing demand response services from residential
consumers. Electr Power Syst Res 2014.
[105] Thale Sushil, Wandhare Rupesh G, Agarwal Vivek. A novel recongurable
microgrid architecture with renewable energy sources and storage.
[106] Mahmood Anzar, Javaid Nadeem, Razzaq Sohail. A review of wireless
communications for smart grid. Renew Sustain Energy Rev 2015;41:24860.
[107] IEC 61850-7-420. Communication networks and systems for power utility
automation Part 7420: Basic communication structure Distributed
energy resources logical nodes.
[108] Communication between components in Mini-grids. Recommendations for
communication system needs for PV hybrid mini-grid systems. IEA-PVPS
T11-04; 2011.
[109] Mao Meiqin, et al. Application of IEC 61850 in energy management system
for microgrids. In: Power electronics for distributed generation systems
(PEDG), 2014 IEEE 5th international symposium on. IEEE; 2014.
[110] Gopalan Sachit A, Sreeram Victor, Iu Herbert HC. A review of coordination
strategies and protection schemes for microgrids. Renew Sustain Energy Rev
2014;32:2228.
[111] Lautier P, Prevost M, Ethier P, Martel P, Lavoie L. Off-grid diesel power plant
efciency optimization and integration of renewable energy sources. In:
Electrical power conference, 2007. EPC 2007. IEEE Canada. IEEE; 2007,
October. p. 27479.