OPERATION & MAINTENANCE

INSTRUCTIONS MANUAL

F I

3 0 3 M E

smar
www.smar.com

Specifications and information are subject to change without notice.


Up-to-date address information is available on our website.

web: www.smar.com/contactus.asp

Introduction

INTRODUCTION
The FI303 is from the first generation of Profibus PA devices. It is a converter mainly intended for
interface of a Profibus PA system to control valve or other actuators. The FI303 produces a 4-20 mA
output proportional to input received over the Profibus PA network. The digital technology used in
the FI303 enables an easy interface between the field and the control room and several interesting
features that reduce considerably the installation, operation and maintenance costs.
The FI303 is part of Smar's complete 303 line of Profibus PA devices.
Profibus PA, is not only a replacement for 4-20 mA or intelligent/smart transmitter protocols, it
contains much more.
The digital technology used in the FI303 enables the choice of several types of transfer functions, an
easy interface between the field and the control room and several interesting features that
considerably reduce the installation, operation and maintenance costs.
Some of the advantages of bi-directional digital communications are known from existing smart
transmitter protocols: Higher accuracy, multi-variable access, remote configuration and diagnostics,
and multi-dropping of several devices on a single pair of wires.
The system controls variable sampling, algorithm execution and communication so as to optimize
the usage of the network, not loosing time. Thus, high closed loop performance is achieved.
Using Profibus technology, with its capability to interconnect several devices, very large control
schemes can be constructed. In order too be user friendly the function block concept was
introduced.
The FI303, like the rest of the 303 family, has some Function Blocks built in, like Analog Output and
Transducer and Display Blocks.

The need for implementation of Fieldbus in small as well as large systems was considered
when developing the entire 303 line of Profibus-PA devices. They have common features
and can configured locally using a magnetic tool, eliminating the need for a configuration
tool or console in many basic applications.
Get the best result of the FI303 by carefully reading these instructions.

NOTE
In case of using Simatic PDM as the configuration and parameterization tool, Smar
recommends that the user does not apply the option "Download to Device". This function
can improperly configure the field device. Smar recommends that user make the use of the
option "Download to PG / PC" and then selecting the Device Menu, use the menus of the
transducer, function and display blocks acting specifically, according to each menu and
method for reading and writing.

III

FI303 - Operation and Maintenance Instruction Manual


NOTE
This Manual is compatible with version 3.XX, where 3 denote software version and XX software release. The
indication 3.XX means that this manual is compatible with any release of software version 3.

Waiver of responsibility
The contents of this manual abides by the hardware and software used on the current equipment
version. Eventually there may occur divergencies between this manual and the equipment. The
information from this document are periodically reviewed and the necessary or identified corrections
will be included in the following editions. Suggestions for their improvement are welcome.

Warning
For more objectivity and clarity, this manual does not contain all the detailed information on the
product and, in addition, it does not cover every possible mounting, operation or maintenance
cases.
Before installing and utilizing the equipment, check if the model of the acquired equipment complies
with the technical requirements for the application. This checking is the users responsibility.
If the user needs more information, or on the event of specific problems not specified or treated in
this manual, the information should be sought from Smar. Furthermore, the user recognizes that the
contents of this manual by no means modify past or present agreements, confirmation or judicial
relationship, in whole or in part.
All of Smars obligation result from the purchasing agreement signed between the parties, which
includes the complete and sole valid warranty term. Contractual clauses related to the warranty are
not limited nor extended by virtue of the technical information contained in this manual.
Only qualified personnel are allowed to participate in the activities of mounting, electrical connection,
startup and maintenance of the equipment. Qualified personnel are understood to be the persons
familiar with the mounting, electrical connection, startup and operation of the equipment or other
similar apparatus that are technically fit for their work. Smar provides specific training to instruct and
qualify such professionals. However, each country must comply with the local safety procedures,
legal provisions and regulations for the mounting and operation of electrical installations, as well as
with the laws and regulations on classified areas, such as intrinsic safety, explosion proof, increased
safety and instrumented safety systems, among others.
The user is responsible for the incorrect or inadequate handling of equipments run with pneumatic
or hydraulic pressure or, still, subject to corrosive, aggressive or combustible products, since their
utilization may cause severe bodily harm and/or material damages.
The field equipment referred to in this manual, when acquired for classified or hazardous areas, has
its certification void when having its parts replaced or interchanged without functional and approval
tests by Smar or any of Smar authorized dealers, which are the competent companies for certifying
that the equipment in its entirety meets the applicable standards and regulations. The same is true
when converting the equipment of a communication protocol to another. In this case, it is necessary
sending the equipment to Smar or any of its authorized dealer. Moreover, the certificates are
different and the user is responsible for their correct use.
Always respect the instructions provided in the Manual. Smar is not responsible for any losses
and/or damages resulting from the inadequate use of its equipments. It is the users responsibility to
know and apply the safety practices in his country.

IV

Table Of Contents

TABLE OF CONTENTS
SECTION 1 - INSTALLATION ..................................................................................................................... 1.1
GENERAL ............................................................................................................................................................................... 1.1
MOUNTING ............................................................................................................................................................................ 1.1
TOPOLOGY AND NETWORK CONFIGURATION ................................................................................................................. 1.4
INTRINSIC SAFETY BARRIER .............................................................................................................................................. 1.5
JUMPER CONFIGURATION .................................................................................................................................................. 1.5
POWER SUPPLY ................................................................................................................................................................... 1.5
INSTALLATION IN HAZARDOUS AREAS ............................................................................................................................. 1.6
EXPLOSION/FLAME PROOF ................................................................................................................................................. 1.6
INTRINSICALLY SAFE ........................................................................................................................................................... 1.6

SECTION 2 - IOPERATION .......................................................................................................................... 2.1


FUNCTIONAL DESCRIPTION - ELECTRONICS REFER TO THE BLOCK DIAGRAM ......................................................... 2.1

SECTION 3 - CONFIGURATION .................................................................................................................. 3.1


HOW TO CONFIGURE A TRANSDUCER BLOCK................................................................................................................. 3.1
TERMINAL NUMBER ............................................................................................................................................................. 3.2
FUNCTIONAL DIAGRAM OF THE PROFIBUS PA TO CURRENT TRANSDUCER BLOCK ................................................. 3.2
PROFIBUS TO CURRENT CONVERTER TRANSDUCER BLOCK - PARAMETERS DESCRIPTION .................................. 3.2
PROFIBUS TO CURRENT CONVERTER TRANSDUCER BLOCK - PARAMETERS TABLE ............................................... 3.4
CYCLIC CONFIGURATION .................................................................................................................................................... 3.5
HOW TO CONFIGURE THE ANALOG OUTPUT BLOCK .................................................................................................... 3.11
CURRENT TRIM ................................................................................................................................................................... 3.17
VIA LOCAL ADJUSTMENT .................................................................................................................................................. 3.20
TRANSDUCER DISPLAY CONFIGURATION ................................................................................................................... 3.21
DISPLAY TRANSDUCER BLOCK ........................................................................................................................................ 3.22
DEFINITION OF PARAMETERS AND VALUES................................................................................................................... 3.23
LOCAL ADJUST TREE QUICK GUIDE ............................................................................................................................. 3.28
PROGRAMMING USING LOCAL ADJUSTMENT ................................................................................................................ 3.29
J1 JUMPER CONNECTIONS ............................................................................................................................................... 3.30
W1 JUMPER CONNECTIONS.............................................................................................................................................. 3.30
CYCLICAL DIAGNOSIS........................................................................................................................................................ 3.33

SECTION 4 - MAINTENANCE PROCEDURES............................................................................................4.1


GENERAL ............................................................................................................................................................................... 4.1
DISASSEMBLY PROCEDURE ............................................................................................................................................... 4.2
REASSEMBLY PROCEDURE ................................................................................................................................................ 4.3
INTERCHANGEABILITY......................................................................................................................................................... 4.3
ACCESSORIES AND RELATED PRODUCTS ....................................................................................................................... 4.3
SPARE PARTS LIST .............................................................................................................................................................. 4.4

SECTION 5 - TECHNICAL CHARACTERISTICS ........................................................................................5.1


ORDERING CODE ................................................................................................................................................................. 5.2

APPENDIX A - CERTIFICATIONS INFORMATION .................................................................................... A.1


MANUFACTURING LOCATION APPROVED ........................................................................................................................ A.1
EUROPEAN DIRECTIVE INFORMATION .............................................................................................................................. A.1
HAZARDOUS LOCATIONS GENERAL INFORMATION ........................................................................................................ A.1
HAZARDOUS LOCATIONS APPROVALS ............................................................................................................................. A.2
IDENTIFICATION PLATE AND CONTROL DRAWING .......................................................................................................... A.5

APPENDIX B SRF SERVICE REQUEST FORM ................................................................................... B.1


RETURNING MATERIALS ..................................................................................................................................................... B.2

FI303 - Operation and Maintenance Instruction Manual

VI

Installation Flowchart

Installation Flowchart
Start

Was the converter


configured on the bench
to match the application?

Yes

Install the converter on the field


following the instructions below.

Install the converter preferably


on wether-protected areas.

No
Configure the engineering unit.

Check the area classification


and its practices.
Configure the terminal(s)
and output scale(s) .
(Section 3 - Calibration)
Install the converter (mechanically
and electrically) according to the
application after checking the best
position for the LCD
(Section 4 - Maintenance).

Configure the LCD reading.


(Section 3 - Configuration)

Simulate the values in the Fieldbus


input according to output scale
and verify the signals of the
4 a 20 mA output current.

Yes
Is the indication correct?

Power-up the converter properly.


FI303 needs a external power supply
for supply the 4 - 20 mA equipment .

No
See section 4 - Maintenance

OK

VII

FI303 - Operation and Maintenance Instruction Manual

VIII

Section 1
INSTALLATION
General
NOTE
The installation carried out in hazardous areas should follow the recommendations of the IEC60079-14
standard.

The overall accuracy of measurement and control depends on several variables. Although the
converter has an outstanding performance, proper installation is essential, in order to maximize its
performance.
Among all factors, which may affect converter accuracy, environmental conditions are the most
difficult to control. There are, however, ways of reducing the effects of temperature, humidity and
vibration.
Locating the converter in areas protected from extreme environmental changes can minimize
temperature fluctuation effects.
In warm environments, the converter should be installed to avoid, as much as possible, direct exposure to the sun. Installation close to lines and vessels subjected to high temperatures should also be
avoided.
Use of sunshades or heat shields to protect the converter from external heat sources should be
considered, if necessary.
Humidity is fatal to electronic circuits. In areas subjected to high relative humidity, the O-rings for the
electronics cover must be correctly placed. Removal of the electronics cover in the field should be
reduced to the minimum necessary, since each time it is removed the circuits are exposed to the
humidity. The electronic circuit is protected by a humidity proof coating, but frequent exposures to
humidity may affect the protection provided. It is also important to keep the covers tightened in
place. Every time they are removed, the threads are exposed to corrosion, since painting cannot
protect these parts. Code-approved sealing methods on conduit entering the converter should be
employed.

Mounting
Using the bracket, the mounting may be done in several positions, as shown on Figure 1.3 Dimensional Drawing and Mounting Positions.
For better visibility, the digital indicator may be rotated in steps of 90 (See the section Maintenance
Procedures).
Output Wiring
The output is in fact a current link. An external power source is therefore necessary. The FI303
controls the current in the loop. (See Figure 1.4 - Output Connections). The three channels have a
common ground for the external power supply.
The output load is limited by the voltage of the external power supply. Please refer to the load graph
to determine the maximum load.
On loss of power the output will be uncertain. If power is maintained, but communication is lost, the
output may be pre-configured to freeze or go to a safe value.
Electric Wiring
Access the wiring block by removing the Electrical Connection Cover. This cover can be locked
closed by the cover locking screw (See Figure 1.1 - Cover Locking). To release the cover, rotate the
locking screw clockwise.

1.1

FI303 - Operation and Maintenance Instruction Manual

Figure 1.1 - Cover Locking


Cable access to wiring connections is obtained by one of the two conduit outlets. Conduit threads
should be sealed by means of code-approved sealing methods. The unused outlet connection
should be plugged accordingly.
The wiring block has screws, on which terminal type fork or ring can be fastened, see Figure 1.2 Ground Terminals.

H1 BUS

GROUND
TERMINAL

OUTPUT
GROUND
TERMINAL

OUTPUT
TERMINALS 3
COMUNICATION
TERMINALS

Figure 1.2 - Ground Terminals


For convenience there are three ground terminals: one inside the cover and two externals, located
close to the conduit entries.
The FI303 uses the 31.25 kbit/s voltage mode option for the physical signaling. All other devices on
the same bus must use the same signaling. All devices are connected in parallel along the same
pair of wires.
Various types of Fieldbus devices may be connected on the same bus.
The FI303 is powered via the bus. The limit for such devices is according to the DP/PA coupler
limitations for one bus for non-intrinsically safe requirement. In hazardous area, the number of
devices may be limited by intrinsically safe restrictions, according to the DP/PA coupler and barriers
limitations.

1.2

Installation

Dimensions are in mm (in).

PLUG

ALLOW 150 MM MINIMUM FOR LOCAL


ZERO AND SPAN ADJUSTMENT WITH
MAGNETIC TOOL.

CONDUIT
CONNECTION

COMMUNICATIONS
TERMINAL

PLUG

WALL OR
PANEL MOUNTING

MOUNTING BRACKET

PIPE 2"

FOR WALL MOUNTING


2 EXPANSION ANCHOR - S8
2 HEXAGON SCREW - 3/16X70
FOR PANEL MOUNTING
2 BOLT AND NUTS - 1/4X30
NOT INCLUDED

Figure 1.3 - Dimensional Drawing and Mounting Positions

Figure 1.4 - Output Connections


Avoid routing signal wiring close to power cables or switching equipment.
The FI303 is protected against reverse polarity, and can withstand 35 V DC without damage, but it
will not operate when in reverse polarity.
NOTE
Please refer to the General Installation, Operation and Maintenance Procedures Manual for more details.

1.3

FI303 - Operation and Maintenance Instruction Manual

Topology and Network Configuration


Wiring
Other types of cable may be used, other than for conformance testing. Cables with improved
specifications may enable longer trunk length or superior interface immunity. Conversely, cables
with inferior specifications may be used subject to length limitations for trunk and spurs plus possible
nonconformance to the RFI/EMI susceptibility requirements. For intrinsically safe applications, the
inductance/resistance ratio (L/R) should be less than the limit specified by the local regulatory
agency for the particular implementation.
Bus topology (See Figure 1.5 Bus Topology) and tree topology (See Figure 1.6 Tree Topology)
are supported. Both types have a trunk cable with two terminations. The devices are connected to
the trunk via spurs. The spurs may be integrated in the device giving zero spur length. A spur may
connect more than one device, depending on the length. Active couplers may be used to extend
spur length.
The total cable length, including spurs, between any two devices in the Fieldbus should not exceed
1900m.
The connection of couplers should be kept less than 15 per 250m. In following figures the
DP/PA link depends on the application needs.

Figure 1.5 - Bus Topology

1.4

Installation

Figure 1.6 - Tree Topology

Intrinsic Safety Barrier


When the Profibus converter is in an area requiring intrinsic safety, a barrier must be inserted on the
trunk. If the DP/PA coupler is already intrinsically safe, there is this necessary. Use of DF47-17
(Smar intrinsic safety barrier) is recommended.

Jumper Configuration
In order to work properly, the jumpers J1 and W1 located in the FI303 main board must be correctly
configured (See Table 1.1 - Description of the Jumpers).
J1

This jumper enables the simulation mode parameter in the AO block.

W1

This jumper enables the local adjustment programming tree.

Table 1.1 - Description of the Jumpers

Power Supply
The FI303 receives power from the bus via the signal wiring. The power supply may come from a
separate unit or from another device such as a controller or DCS.
The voltage should be between 9 to 32 Vdc for non-intrinsic safe applications.
A special requirement applies to the power supply used in an intrinsically safe bus and depends on
the type of barrier used.
Use of PS302 is recommended as power supply.

1.5

FI303 - Operation and Maintenance Instruction Manual

Installation in Hazardous Areas


WARNING
Explosions could result in death or serious injury, besides financial damage. Installation of this
converter in explosive areas must be carried out in accordance with the local standards and the
protection type adopted .Before continuing the installation make sure the certificate parameters are
In accordance with the classified area where the equipment will be installed.
The instrument modification or parts replacement supplied by other than authorized representative
of Smar is prohibited and will void the certification.
The converters are marked with options of the protection type. The certification is valid only when
the protection type is indicated by the user. Once a particular type of protection is selected, any
other type of protection can not be used.
The electronic housing and the sensor installed in hazardous areas must have a minimum of 6 fully
engaged threads. Lock the housing using the locking screw (Figure 1.1).
The cover must be tighten with at least 8 turns to avoid the penetration of humidity or corrosive
gases. The cover must be tighten until it touches the housing. Then, tighten more 1/3 turn (120) to
guarantee the sealing. Lock the covers using the locking screw (Figure 1.1).
Consult the Appendix A for further information about certification.

Explosion/Flame Proof
WARNING
In Explosion-Proof installations the cable entries must be connected or closed using metal cable
gland and metal blanking plug, both with at least IP66 and Ex-d certification.
The standard plugs provided by Smar are certified according to CEPEL certificate. If the plug
needs to be replaced, a certified plug must be used.
The electrical connection with NPT thread must use waterproofing sealant. A non-hardening
silicone sealant is recommended.
For NEMKO ATEX certificate please to follow the installation guidelines in hazardous locations
below: Group II Category 2G, Ex d, Group IIC, Temperature Class T6, EPL Gb U = 28VDC
Ambient Temperature: -20 to 60C for T6
Environmental Protection: IP66/687 or IP66W/687W
The electrical connection available are - 14NPT and M20x1,5.
Cable entries must be connected or closed using metal cable gland and metal blanking plug,
both with at least IP66 and Ex-d certification or any appropriate ATEX approved metal cable
gland and metal blanking plug. Do not remove the transmitter covers when power is ON.

Intrinsically Safe
WARNING
In hazardous zones with intrinsically safe or non-incendive requirements, the circuit entity
parameters and applicable installation procedures must be observed.
To protect the application the transmitter must be connected to a barrier. Match the parameters
between barrier and the equipment (Consider the cable parameters). Associated apparatus
ground bus shall be insulated from panels and mounting enclosures. Shield is optional. If used, be
sure to insulate the end not grounded. Cable capacitance and inductance plus Ci and Li must be
smaller than Co and Lo of the associated Apparatus.
It is not recommended to remove the transmitter cover when the power is ON.

1.6

Section 2
OPERATION
Functional Description - Electronics Refer to the block diagram

Figure 2.1 - FI303 Block Diagram


The function of each block is described below:
D/A

Receives the signal from the CPU and converts it to an analog voltage, used by the current
control.
Current Control
Controls the current of the channel according the data received from the CPU.
Signal Isolator
Its function is to isolate the data signal between the output and the CPU.

(CPU) Central Processing Unit, RAM and PROM


The CPU is the intelligent portion of the converter, being responsible for the management and
operation of block execution, self-diagnostics and communication. The program is stored in PROM.
For temporary storage of data there is a RAM. The data in the RAM is lost if the power is switched
off, however the device also has a nonvolatile EEPROM where data that must be retained is stored.
Examples of such data are calibration, configuration and identification data.
Communication Controller
It monitors line activity, modulates and demodulates communication signals and inserts and deletes
start and end delimiters.
Power Supply
Takes power of the loop-line to power the converter circuitry.
Power Isolation
Just like the signals to and from the output section, the power to the output section must be isolated.
Display Controller
Receives data from the CPU and drives the Liquid Crystal Display.
2.1

FI303 - Operation and Maintenance Instruction Manual


Local Adjustment
Two switches that are magnetically activated. They can be activated by the magnetic tool without
mechanical or electrical contact.

Figure 2.2 - LCD Indicator

2.2

Section 3
CONFIGURATION
One of the many advantages of using Fieldbus technologies is that device configuration is
independent of the configuration software. The FI303 may be configured by a third party terminal or
operator console as Smars configurators ProfibusView or AssetView for FDT.
The FI303 contains three output transducer blocks, one physical block, one display transducer
block, three analog output function blocks.
Function Blocks are not covered in this manual. For further explanation and details of function
blocks, see the Function Blocks Instruction Manual.
The transducer block isolates the function block of the specific I/O hardware, like sensors and
actuators, for example. Transducer block controls access to I/O through manufacturer specific
implementation. This allows the transducer block to execute the algorithm, as frequently as
necessary to obtain good data from sensors without burdening the function blocks that use the data.
It also insulates the function blocks from the manufacturer specific characteristics of certain
hardware.
By accessing the hardware, the transducer block can get data from I/O or passing control data to it.
The connection between Transducer block and Input/Output Function blocks is called channel.
Normally, transducer blocks perform functions, such as linearization, characterization, temperature
compensation, control and exchange data to/from hardware.
In order to assure correct values in the offline configuration, when using download function of
Simatic PDM, please make sure you have done the upload firstly.
Offline Configuration
1. First run Download to PG/PC option to assure valid values.
2. Run after the Menu Device option to configure the required parameters using the related menus.
NOTE
It is not advisable to use the Download to Device option. This function can misconfigure the equipment.

How to Configure a Transducer Block


The transducer block has an algorithm, a set of contained parameters and a channel connecting it to
a function block.
The algorithm describes the behavior of the transducer as a data transfer function between the I/O
hardware and other function block. The set of contained parameters, it means, you are not able to
link them to other blocks, defines the user interface to the transducer block. They can be divided into
Standard and Manufacturer Specific.
The standard parameters will be present for such class of device, as pressure, temperature,
actuator, etc., whatever is the manufacturer. Oppositely, the manufacturers specific ones are
defined only by its manufacturer. As common manufacturer specific parameters, we have calibration
settings, material information, linearization curve, etc.
When deforming a standard routine as a calibration, user is conducted step by step by a method.
The method is generally defined as guide line to help the user to make common tasks. The
Configuration Tool identifies each method associated to the parameters and enables the interface
to it., linearization curve, etc.
When you perform a standard routine as a calibration, you are conducted step by step by a method.
The method is generally defined as guide line to help the user to make common tasks. The
Configuration Tool identifies each method associated to the parameters and enables the interface
to it.

3.1

Configuration

Terminal Number
It is the parameter, which makes reference to a channel value, which in its turn, is sent via internally
from the specified transducer output to function block.
It starts at channel one (1) for transducer number one until channel three (3) for transducer number
three.
The channel number of the AO block is related to the transducers terminal number. Channel
number 1, 2, 3 corresponds bi-univocally to the terminal block with the same number. Therefore, all
user has to do is choosing combinations: (1.1), (2.2), (3.3) for (CHANNEL, BLOCK) respectively.

Functional Diagram of the Profibus PA to Current Transducer Block

Figure 3.1 - Functional Diagram of the Profibus PA to Current Transducer Block

PROFIBUS to Current Converter Transducer Block - Parameters Description


PARAMETERS
FINAL_VALUE
FINAL_VALUE_SCALE
CAL_POINT_HI
CAL_POINT_LO

CAL_MIN_SPAN
CONVERTER_SER_NUM
CONVERTER_MAN
CONVERTER_MAINT_DATE
FEEDBACK_VALUE
TERMINAL_NUMBER
TAB_ACTUAL_NUMBER
3.2

DESCRIPTION
The actual value variable for the final control element in units of OUT_SCALE. Status
BAD will indicate a hardware problem.
This is the output conversion of the linearisated value using the high and low scale. The
engineering unit is mA (1211).
This parameter contains the highest calibrated value. This parameter indicates where
the converter should be when the setpoint is 100%. The engineering unit used by this
calibration is mA.
This parameter contains the lowest calibrated value. This parameter indicates where
the converter should be when the setpoint is 0%. The engineering unit used by
calibration is mA.
This parameter contains the minimum calibration span value allowed. This minimum
span information is necessary to ensure that when calibration is done, the two
calibrated points (high and low) are not too close together. The engineering unit used
by calibration is mA.
This parameter contains the converter serial number.
Name of converter-manufacturer
The date of last maintenance.
The actual final value of the final control element in units of OUT_SCALE.
The terminal number, which references a channel value, which is sent via internal,
manufacturer-specific from AO function block to the specified transducer. It starts at
one (1) for transducer number one until three (3) for transducer number three.
Contains the actual numbers of entries in the table. It shall be calculated after the
transmission of the table is finished.

FI303 - Operation e Maintenance Instruction Manual


PARAMETERS
TAB_ENTRY
TAB_MAX_NUMBER
TAB_MIN_NUMBER

TAB_OP_CODE

TAB_STATUS

TAB_X_Y_VALUE

LIN_TYPE

FEEDBACK_CAL
CAL_CONTROL

ACTUATOR_ACTION

SP_RATE_INC
SP_RATE_DEC
SP_HI_LIM
SP_LO_LIM

DESCRIPTION
The index parameter identifies which element of the table is in the X_VALUE and
Y_VALUE parameter currently
TAB_MAX_NUMBER is the maximum size (number of X_VALUE and Y_VALUE
values) of the table in the device.
For device internal reasons (e.g. for calculation), sometimes it is necessary to use a
certain number of table values in minimum. This number is provided in the
TAB_MIN_NUMBER parameter.
The modification of a table in a device influences the measurement or actuation
algorithms of the device. Therefore an indication of a starting and an end point is
necessary. The TAP_OP_CODE controls the transaction of the table.
0: not initialised
1: new operation characteristic, first value (TAB_INDEX=1), old curve cleared
2: reserved
3: last value, end of transmission, check table, swaps the old curve with the new
curve, actualise ACTUAL_NUMBER.
4: delete point of table with actual index (optional), sort records with increasing
Charact-Input-Value, assign new indexes, decrement CHARACT_NUMBER.
5: insert point (Charact-Input-Value relevant) (optional), sort records with increasing
Charact-Input-Value, assign new indexes. Increment CHARACT_NUMBER.
6: replace point of table with actual index (optional).
It is possible to read a table or parts of the table without start an stop an interaction
(TAB_OP_CODE 1 and 3). The start is indicated by set TAB_ENTRY to 1.
It is common to provide a plausibility check in the device. The result of this check is
indicated in the TAB_STATUS parameter.
0: not initialised
1: good (new table is valid)
2: not monotonous increasing (old table is valid)
3: not monotonous decreasing (old table is valid)
4: not enough values transmitted (old table is valid)
5: too many values transmitted (old table is valid)
6: gradient of edge too high (old table is valid)
7: Values not excepted (old values are valid)
8: 127 reserved
> 128 manufacturer specific
The X_Y_VALUE parameter contains one value couple of the table
Type of linearisation.
0 = no linearisation (mandatory)
1 = linearisation table (optional)
240 = Manufacturer specific
249 = Manufacturer specific
250 = Not used
251 = None
252 = Unknown
253 = Special
This parameter should be set with the actual output current during the calibration
procedure.
This parameter controls when the calibration procedure ends. It is necessary since the
user should enter the "analog current" value that he sees at the multi-meter. The device
waits for a flag that tells it when to change from TRIM mode to normal one.
Fail-Safe position for power-loss of the actuator resp. the valve:
0 = not initialized
1 = opening (100%)
2 = closing (0%)
3 = none / remains in actual position
Ramp rate at which upward setpoint changes are acted on in Auto mode, in FV units
per second. If the ramp rate is set to zero or minus infinite then the setpoint will be used
immediately.
Ramp rate at which downward setpoint changes are acted on in Auto mode, in FV units
per second. If the ramp rate is set to zero or plus infinite then the setpoint will be used
immediately.
The setpoint high limit is the highest setpoint operator entry that can be used for the
transducer block.
The setpoint low limit is the lowhest setpoint operator entry that can be used for the
3.3

Configuration
PARAMETERS

BACKUP_RESTORE

XD_ERROR

DESCRIPTION
transducer block.
This parameter allows to save and to restore data according to factory and user
calibration procedures. It has the following options:
1, "Factory Cal Restore",
2, "Last Cal Restore",
3, "Default Data Restore",
4, "Shut-Down Data Restore",
11, "Factory Cal Backup",
12, "Last Cal Backup",
14, "Shut-Down Data Backup",
0, "None".
Indicates the condition of calibration process according to:
{16, "Default value set"},
{22, "Applied process out of range"},
{26, "Invalid configuration for request"},
{27, "Excess correction"},
{28, "Calibration failed"}
The electronic main board serial number.
This parameter is used to indicate EEPROM saving process.
{0, False}
{1, True}
This array of Unsigned 8 bytes contains information about which kind of materials and
mechanical parts have been used for the device. This is part of the Ordering Code
information necessary to buy a spare unit.

XD_ERROR

MAIN_BOARD_SN
EEPROM_FLAG
ORDERING_CODE

Table 3.1 - Parameters Description

PROFIBUS to Current Converter Transducer Block - Parameters Table


Relative
Index

Parameter Name

Object
Type

Data Type

Store

Size

Access

Parameter
usage/Type
of Transport

Initial/Default
Value

Mandatory/
Optional
Class

Standard Parameters

13

Additional Parameters for Transducer Block

3.4

VIEW

FINAL_VALUE

DS-33

R/w

C/a

FINAL_VALUE_SCALE

Array

Float

R/w

C/a

4 and 20 mA

10

CAL_POINT_HI

Float

R/w

C/a

20

11

CAL_POINT_LO

Float

R/w

C/a

12

CAL_MIN_SPAN

Float

C/a

13

CONVERTER_SER_NUM

Unsigned32

R/w

C/a

14

CONVERTER_MAN

Octet String

16

R/w

C/a

""

15

CONVERTER_MAINT_DATE

Octet String

16

R/w

C/a

""

16

FEEDBACK_VALUE

DS-33

R/w

C/a

Unsigned8

R/w

C/a

17

TERMINAL_NUMBER

18

TAB_ACTUAL_NUMBER

See explanation about table handling

19

TAB_ENTRY

See explanation about table handling

20

TAB_MAX_NUMBER

See explanation about table handling

21

TAB_MIN_NUMBER

See explanation about table handling

22

TAB_OP_CODE

See explanation about table handling

23

TAB_STATUS

See explanation about table handling

24

TAB_X_Y_VALUE

See explanation about table handling

25

LIN_TYPE

See explanation about table handling

FI303 - Operation e Maintenance Instruction Manual


Relative
Index

Parameter Name

Object
Type

Data Type

Store

Size

Access

26

FEEDBACK_CAL

Float

R/w

Parameter
usage/Type
of Transport
C/a

CAL_CONTROL

Unsigned8

R/w

C/a

27
28-38

Mandatory/
Optional
Class
M

Initial/Default
Value

NOT USED

39

ACTUATOR_ACTION

Unsigned8

R/w

C/a

40

SP_RATE_INC

float

R/w

C/a

41

SP_RATE_DEC

float

R/w

C/a

42

SP_HI_LIM

float

R/w

C/a

43

SP_LO_LIM

float

R/w

C/a

44

BACKUP_RESTORE

Unsigned8

R/w

C/a

45

XD_ERROR

Unsigned8

C/a

0x10

46

MAIN_BOARD_SN

Unsigned32

R/w

C/a

47

EEPROM_FLAG

Unsigned8

R/w

C/a

Array of
Char

R/w

C/a

48

VIEW

ORDERING_CODE

Table 3.2 - Parameters Table


See FUNCTION BLOCKS PROFIBUS PA manual for more parameters information, by visiting our
web page on the Internet: http://www.smar.com.

CYCLIC CONFIGURATION
The profibus network master executes the equipment initialization process through the gsd file,
which has details for hardware and software revision, equipment bus timing and information on the
cyclic data exchange.
The FI303 has 3 function blocks with analog output (AOs) that the class 1 master uses to execute
the cyclic services. Users must choose what configuration best suits their application. If the AO
Block Mode is in AUTO, it will receive the value and the status of the class 1 master setpoint. In
addition, the user may alter this value via a class 2 master if the setpoint status is equal to 0x80
(good), and the following configurations can be chosen:
SP;

SP/CKECKBACK;

SP/READBACK/POSD;

SP/READBACK/POSD/CKECKBACK.

If the AO block is in RCAS, the equipment only receives the setpoint value and status through a
class 1 master, and the status will always be equal to 0xc4 (IA). The following configurations may
be chosen:
SP;

SP/CKECKBACK;

SP/READBACK/POSD;

SP/READBACK/POSD/ CKECKBACK;

RCASIN/RCASOUT;

RCASIN/RCASOUT/ CKECKBACK;

SP/READBACK/RCASIN/RCASOUT/POSD/CHECKBACK.

The example below shows the necessary steps to integrate the FI303 to a PA system. These steps
are applicable to all the equipments on Smar 303 line:

Copy the FI303 gsd file into the search directory of the PROFIBUS configurator, usually called
GSD;

3.5

Configuration

Copy the FI303 bitmap file on the search directory of the PROFIBUS configurator, usually called
BMP;

After choosing the master, define the communication rate. Do not forget that the couplers may
have the following fixed communication rates 45,45 kbits/s (Siemens) or 93,75 kbits/s (P+F) and
variable comm rates up to 12 Mbit/s as instance: SK2 and SK3 from P+F, link IM157 from
Siemns and Smars controllers with embedded couplers (DF95 or DF97);

Add the FI303 and specify its bus address;

Choose the configuration via parameterization with the gsd file, according to the application, as
seen previously. Notice that this choice must match the AO blocks operating mode. Under these
conditions mind the status value of the setpoint value, which should be 0x80 (Good) when in
Auto mode, and 0xc4(IA) when in Rcas. Three AO blocks may be operated in the following cyclic
order: AO_1, AO_2 e AO_3. If only 2 AOs are to be applied, there should be: configuration for
the AO_1, configuration for the AO_2 and EMPTY MODULE.

The watchdog condition may be activated, prompting the equipment to enter a fail-safe mode when
detecting a communication loss between the slave and the master equipment. As FI303 will be on a
final element, it is recommended that a fail-safe value be configured.
Using ProfibusView, AssetView FDT from Smar or Simatic PDM from Siemens, for instance, user
may configure parameters of the Transducer block. See Figure 3.2 - Function and Transducer
Blocks.

Figure 3.2 - Function and Transducer Blocks ProfibusView.

3.6

FI303 - Operation e Maintenance Instruction Manual

Figure 3.3 - Function and Transducer Blocks Simatic PDM.


Use this main menu in order to:
- change the device address;
- make the up/download of parameters;
- configure the Transducer Block, Analog Output Block and Display Block;
- calibrate the converter;
- make the reset by software, to protect the device against writing and to simulate the value from
transducer block to analog output block;
- save and restore data calibration.
Select main menu make the configuration of Transducer Block:

3.7

Configuration

Figure 3.4 Transducer Block ProfibusView.

Figure 3.5 Transducer Block - Simatic PDM.

3.8

FI303 - Operation e Maintenance Instruction Manual

Table handling
It is possible to load and re-load tables into the devices. This table is used for linearisation mostly.
For this procedure the following parameters are necessary:
TAB_INDEX
TAB_X_Y_VALUE
TAB_MIN_NUMBER
TAB_MAX_NUMBER
TAB_OP_CODE
TAB_STATUS
The TAB_X_Y_VALUE parameter contains the value couple of each table entries.
TAB_INDEX parameter identifies which element of the table is current in the TAB_X_ Y_VALUE
parameter (see the following figure).
y_Value
Index

x_Value

1
2
3
4
...
n

x1
x2
x3
x4
...
xn

y_Value

yn
yn-1
y4

y1
y2
y3
y4
...
yn

y3
y2
y1

...

x1

x1

x2

x3

x4

...

x2

x3

x4

xn-1

xn x_Value

xn

x_Value

Tab

y_Value

y1

y2

y3

y4

...

yn

Figure 3.6 - Parameters of a table


TAB_MAX_NUMBER is the maximum size of the table in the device.
TAB_MIN_NUMBER is the minimum size of the table in the device.
Modifing devices table influences the measurement algorithms of the device. Therefore an
indication of a starting and an endpoint is necessary. The TAB_OP_CODE controls the transaction
of the table. The device provides a plausibility check. The result of this check is indicated in the
TAB_STATUS parameter.
The User Table is used to configure the current signal characterization in up to 8 points in
percentage.
The characterization curve is used to give a determined profile to the output. This is useful, for
instance, when the FI303 is controlling a valve with a non-linear characteristic. Characterization
curve, when used, is applied to the input signal before begin converted by the transducer in analog
current.
For instance, the valve characteristic curve may be slightly nonlinear.
3.9

Configuration
This eventual non-linearity may be corrected through the User Table.
User just needs to configure the input values and the correspondent output values in %. Configure a
minimum of two points. These points will define the characterization curve. The maximum number of
points is 8. It is recommended to select the points equally distributed over the desired range or over
a part of the range where more accuracy is required. User needs to set "user defined (table) in the
linearization type field.

Enter the input


and output
values.

Figure 3.7 - User Table Configuration ProfibusView.

3.10

FI303 - Operation e Maintenance Instruction Manual

Figure 3.8 - User Table Configuration - Simatic PDM.

How to configure the Analog Output Block


The AO block provides information to an output transducer block such as value, scaling
conversion,fail-safe mechanism and other features.
The Analog Output Block is a function block used by devices that work as output elements in a
control loop, like valves, actuators, positioners, etc. The AO block receives a signal from another
function block and passes its results to an output transducer block through an internal channel
reference.

3.11

Configuration

Figure 3.9 - Analog Output Block - Basic Settings ProfibusView.

Figure 3.10 - Analog Output Block - Basic Settings - Simatic PDM.


Selecting the Scale/Units, user has the option to configure the scale and unit for the input and output
signals:

3.12

FI303 - Operation e Maintenance Instruction Manual

Figure 3.11 - Analog Output Block - Scale/Units - ProfibusView.

Figure 3.12 - Analog Output Block - Scale/Units - Simatic PDM.

Output engeneering Unit and Scale will be the same for the transducer block. Note that the allowed
unit is mA.
Selecting Advanced Settings page, user can set the fail-safe conditions.
3.13

Configuration

Figure 3.13 - Analog Output Block - Advanced Settings - ProfibusView.

Figure 3.14 - Analog Output Block - Advanced Settings - Simatic PDM.

3.14

FI303 - Operation e Maintenance Instruction Manual

In the screen Config Mode Block the user can adjust the operation of the block.

Figure 3.15 Configuration mode block for AO ProfibusView.

Figure 3.16 Configuration mode block for AO Simatic PDM.

3.15

Configuration
Using Feedback page, the user can monitore and check all values related between the analog block
and the transducer block:

Information
about the
real condition
of transducer
and analog
output block.

Figure 3.17 - Configuration feedback for AO ProfibusView.

Figure 3.18 - Configuration feedback for AO - Simatic PDM.

3.16

FI303 - Operation e Maintenance Instruction Manual

Current Trim
The FI303 provides the capability of making a TRIM in the output channels, if necessary.
TRIM procedure is necessary if the indication of the transducer block output differs from the actual
physical output. The reason may be:

User's current meter differs from the factory standard.


Converter had its original characterization signal shifted by over-load or by long term drift.

User can check the calibration of the transducer output by measuring the actual current in the output
and compare it with the indication of the device (an appropriate meter must be used). If a mismatch
is detected, a TRIM can be done.
TRIM can be done in two points:
LOWER TRIM: Is used to TRIM the output at the lower range.
UPPER TRIM: Is used to TRIM the output at the upper range.
These two points define the linear characteristic of the output. TRIM in one point is independent
from the other.
There are two ways of doing the TRIM: using local adjustment or using a Configuration Tool (For
example, ProfibusView). When doing the TRIM, make sure you are using an appropriate meter (with
the necessary accuracy).

Via ProfibusView, AssetView FDT or Simatic PDM


In the main menu selects the Calibration option:

User can select Lower


or Upper calibration.

Pressing this key, user


starts the lower
calibration method.

Figure 3.19 - Calibration Lower/Upper - Simatic PDM.


After pressing Lower Calibration a warning comes next.
When user press "OK", a new window comes up allowing that allows him to enter the desired value
of the new calibrated point and of the lower current. Write for instance 4.0 mA in new value:

3.17

Configuration
After entering the desired value, the generated current is corrected according to the desired value
and user can make the correction until the right current value is reached. For this purpose, user
needs to inform the generated current:

Pressing OK, we have. When pressing OK the following window comes up:

User can proceed until the generated current is equal to the desired value:

If the calibrated current is correct, press "No" and a new warning appears:

3.18

FI303 - Operation e Maintenance Instruction Manual


After user confirmation, the converter returns to its normal operation.
The upper calibration procedure is similar to the lower:
The user can select
Lower or Upper
calibration.

Pressing this key, the


user starts the upper
calibration method.

Figure 3.20 - Calibration Lower/Upper - Simatic PDM.

When user press "OK", a new window comes up allowing him to enter the desired value of the new
calibrated point and of the upper current. Write for instance 20.0 mA in new value:

After entering the desired value, the generated current is corrected according to this value and user
can make the correction until the right current is reached. For this purpose, the user needs to inform
the generated current:

3.19

Configuration
Pressing OK, it follows:

User can proceed until the generated current is equal to the desired value:

If the calibrated current is correct, press "No" and a new warning appears:

After user confirmation, the converter comes to the normal operation.


NOTE
It is recommended, for every new calibration, saving the existent TRIM data by means of parameter
BACKUP_RESTORE, using option "Last Cal Backup".

Via Local Adjustment


The FI303 has 3 output transducers and it is provided by Smar with default settings. The factory
setting establishes only the transducer #1 as default for local adjustment. In order to configure the
others via local adjustment, user shall configure them in the display transducer via Configuration
Tool, according specific instructions for this transducer block.

3.20

FI303 - Operation e Maintenance Instruction Manual


In order to enter the local adjustment mode, place the magnetic tool in orifice Z until flag MD
lights up in the display. Remove the magnetic tool from Z and place it in orifice S. Remove and
reinsert the magnetic tool in S until the message Loc-Adj is displayed. The message will be
displayed during approximately 5 sec. after the user has removed the magnetic tool from S. By
placing the magnetic tool in Z the user will be able to access the local adjustment/monitoring tree.
Browse to parameter LOWER. After that, in order to start the calibration, the user shall actuate in
the LOWER parameter inserting the magnetic tool in S.
For instance, it is possible to enter 4.0 mA or the lower value. When the magnetic tool is removed
from S, the output will be adjusted to a value close to the desired value. Then user shall browse
the tree up to parameter FEED (FEEDBACK_CAL), and modify this parameter by placing the
magnetic tool in S until reaching the value shown by the multimeter.
User shall write in this parameter the multimeter readout value until 4.0 mA or the desired lower
values are displayed.
Browse up to parameter UPPER. Then, in order to start the calibration, the user shall set the
parameter UPPER by holding the magnetic tool in S.
For instance, it is possible to enter 20.0 mA or the upper value. When the magnetic tool is removed
from S, the output will be adjusted to a value close to the desired value. The user should then
browse the tree up to parameter FEED (FEEDBACK_CAL) and actuate this parameter by placing
the magnetic tool in S until reaching the value shown by the multimeter.
The user should write in this parameter the multimeter readout value until 20.0 mA or the desired
upper values are displayed.
NOTE
TRIM mode exit via local adjustment occurs automatically. Shall the magnetic tool not be used during some
seconds.

LIMIT CONDITIONS FOR CALIBRATION

Lower
Upper

3.99 < NEW_LOWER < 11.5 mA, otherwise XD_ERROR = 22


12.50 < NEW_UPPER < 20.01 mA, otherwise XD_ERROR = 22

NOTE
Codes for XD_ERROR:
16: Default Value Set
22: Out of range
26: Invalid Calibration request
27: Excessive Correction

See Local Adjust Tree Quick Guide, page 3.29 for more information about Via Local Adjustment.

Transducer Display Configuration


Using the ProfibusView, AssetView FDT, the Simatic PDM or any other configuration tool is
possible to configure the Display Transducer block. As described above it is a transducer that
interfaces with LCD hardware.
Transducer Display is treated as a normal block by any configuration tool. It means, this block has
some parameters and those ones can be configured according to customer's needs.
Customer can choose up to six parameters to be shown at LCD display, they can be parameters
just for monitoring purpose or for acting locally in the field devices by using a magnetic tool. The
seventh parameter is used to access the physical device address. The user can change this
address according to his application. To access and configure the Display Block, please, go to the
main menu, and select Device OnLine Configuration:

3.21

Configuration

Figure 3.21 - Display Block - ProfibusView.

Figure 3.22 - Display Block - Simatic PDM.

Display Transducer Block


Local adjustment is completely configured by configuration tool. It means, user can select the best
options to fit his application. From factory, it is configured with the options to set the Upper and
Lower TRIM, for monitoring the input transducer output and check the Tag. Normally, the converter
is much better configured by configuration tool, but the local functionality of the LCD permits an
easy and fast action on certain parameters, since it does not rely on communication and network
wiring connections. Among the possibilities by Local Adjustment, the following options can be
emphasized: Mode block, Outputs monitoring, Tag visualization and Tuning Parameters setting.
3.22

FI303 - Operation e Maintenance Instruction Manual


User interface is described in details on the "General Installation, Operation and Maintenance
Procedures Manual". Please take a detailed look at this manual in the chapter related to
"Programming Using Local Adjustment". The same handling methodology used for this transducer
display can also be used for the 303 Series field devices from Smar. So, since the user has learned
once, he is capable to handle all kind of field devices from SMAR.
All function block and transducers defined according Profibus PA have a description of their features
written by the Device Description Language.
This feature allows third-parties configuration tools, enabled by Device Description Service
technology, interpreting these features and make them accessible to user Function Blocks
and Transducers of 303 Series have been defined rigorously according the Profibus PA
specifications in order to be interoperable to other parties.
In order to enable local adjustment using the magnetic tool, it is necessary a previous setup of
parameters related with this operation via System Configuration.
There are six groups of parameters, which one may be pre-configured by user in order to enable, a
the local adjustment. Use NONE option in the "Select Block Type" parameter to hide unnecessary
itens to be displayed. Doing this, device will not take parameters related (indexed) to its Block as a
valid parameter.

Definition of Parameters and Values


Select Block Type
Type of block where the parameter is located. User can choose: Transducer Block, Physical Block,
Analog Output Block or None.
Select/Set Parameter Type/Index
Index related to the parameter to be actuated or viewed (0, 1, 2). For each block there are some
pre-defined indexes. Refer to the Function Blocks Manual to know available indexes to be used.
Set Mnemonic
Mnemonic for parameter identification (it is allowed a maximum of 16 characters into the
alphanumeric field of the display). Choose the mnemonic, preferably with no more than 5 characters
in order to avoid the display rotation.
Set Decimal Step
It is the increment and decrement in decimal units when the parameter is Float or Float Status
value; integer, when the parameter is in whole units.
Set Decimal Point Place.
This is the number of digits after the decimal point (0 to 3 decimal digits).
Set Access Permission
Allows user to read, in the case of the Monitoring option, and to write when "action" option is
selected, then the display will show the increment and decrement arrows.
Set Alpha Numerical
These parameters include two options: value and mnemonic. In option value, it is possible to display
both data in the alphanumeric and in the numeric fields; this way, in case of a data higher than
10000, it will be shown in the alphanumeric field.
Selecting mnemonic, display may show the data in the numeric field and the mnemonic in the
alphanumeric field.
For devices where software version is higher or equal to 1.10, please see the configuration of local
adjustment using the local adjustment, in the Installation, operation and maintenance procedures
manual.
In case you wish to visualize a certain tag, select the relative index equal to "tag". To configure other
parameters just select "LCD-II" up to "LCD-VI" windows:

3.23

Configuration

Figure 3.23 Parameters for Local Adjustment Configuration - ProfibusView.

Figure 3.24 Parameters for Local Adjustment Configuration Simatic PDM.

3.24

FI303 - Operation e Maintenance Instruction Manual

The Local Address Change window allows the user to enable/disable the access to change the
equipment address.

Figure 3.25 Parameters for Local Address Configuration - ProfibusView.

Figure 3.26 Parameters for Local Address Configuration Simatic PDM.


When user is in the local adjustment, he can rotate parameters using the magnet screwdrive.
Normally; primary value (P_VAL) is the standard parameter to be shown. In case of setting another
parameter to be displayed, user shall changue Access Permission to Monitoring. Thus the last
parameter set to Monitoring will be displayed after removing the magnet tool.
3.25

Configuration
Always on the LCD interface will be shown two parameters at the same time, switching between the
configured parameter at the LCD-II and the last monitoring parameter. If user does not want to show
two parameters at the same time, it is only needed to set "none" when configure the LCD-II:

Selecting
None, only
the last chosen
monitoring
parameter will
be shown
at LCD.

Figure 3.27 Parameters for Local Adjustment Configuration - ProfibusView.

Figure 3.28 Parameters for Local Adjustment Configuration - Simatic PDM.

3.26

FI303 - Operation e Maintenance Instruction Manual


The user may select the Mode Block parameter on the display, when an index equal to this mode
should be selected.

With this
option, the
Mode Block
parameter
is shown at
the LCD.

Figure 3.29 - Parameters for Local Adjustment Configuration ProfibusView.

Figure 3.30 - Parameters for Local Adjustment Configuration - Simatic PDM.

3.27

3.28

LOWER

UPPER

LOWER

OUT_1

26

FEED

BLOCK

24

ADDR

LCD6

ADDR

CONF

TRD1
TRD2
TRD3
AO1
AO2

LCD2
LCD3
LCD4
LCD5
LCD6

AO3

PHY

LCD1

PRMT

ITEM

Span Hole

TGGL

1
ADDR

Zero Hole

Magnetic Tool

UPDT

1) Browse until CONF option, select LCD2


2) Browse until BLOCK select the block that will be configured
3) Browse until PRMT and set the relative index of the parameter
4) Browse until ITEM and set the sub index ( if applicable )
5) Browse until UPDT, insert magnetic screw driver in Zero Hole
6) Reenter in Local Adjustment, browse until LCD2, now the
parameter is available to change
7) Repeat above steps for all the parameters to be configured

Browse: Insert magnetic


screw driver in zero hole
and hold
Select: Insert magnetic
screw driver in span hole
and hold

3) HOW TO CONFIGURE A BLOCK PARAMETER

2) HOW TO BROWSE AND


SELECT MENU OPTIONS

CONF: option where it is possible to select the LCD to configure. Six options are available: from LCD1 up to LCD6;
BLOCK: option where the user must select the function block that he desires to configure;
PRMT: number correspondent to the relative index of the desired parameter into the chosen function block;
ITEM: configure this option when a selected parameter has sub items to be configured, for example, the OUT_SCALE parameter is compounded by EU at 100%, EU at 0%,
Unit Index and Decimal Point;
TGGL (Toggle): switches from 1 up to 6 configured parameters on the display. If TGGL is equal to 2, for example, the display wil l switch between LCD1 and LCD2;
UPDT: refreshes the display when one of the LCDs are configured. Finalize display configuration by setting "UPDT", after choosing the configuration for the local adjustment.

10

LCD4

With TOGGLE 6
LCD1
LCD2

Follow Steps:
1) Browse until TGGL
2) Select 2
3) Configure LCD 2 with the desired parameter

FEED

LCD5

UPPER

TIP: DISPLAY SWITCHING BETWEEN 2


VARIABLES

OUT

Follow Steps:
1) Insert magnetic screw driver in zero hole
2) Wait 3 seconds
3) Insert magnetics screw driver in span hole
4) Wait 3 seconds, then MD will appear on display

1) HOW TO ACCESS LOCAL ADJUSTMENT TREE

Local Adjustment Tree - Quick Guide

Configuration

Local Adjust Tree Quick Guide

FI303 - Operation e Maintenance Instruction Manual

Programming Using Local Adjustment


The local adjustment is completely configured by configuration tool. It means, the user can select
the best options to fit his application. From factory, it is configured with the options to set the Upper
and Lower TRIM, for monitoring the input transducer output and check the Tag.
Normally, the converter is much better configured by configuratinon tool, but the local functionality
of the LCD permits an easy and fast action on certain parameters, since it does not rely on
communication and network wiring connections. Among the possibilities by Local Adjustment, the
following options can be emphasized: Mode block, Outputs monitoring, Tag visualization and Tuning
Parameters setting.
The interface between the user is also described very detailed on the "General Installation,
Operation and Maintenance Procedures Manual" Please take a detailed look at this manual in the
chapter related to "Programming Using Local Adjustment". It is significantly the resources on this
transducer display, also all the 303 Series field devices from SMAR has the same methodology to
handle with it. So, since the user has learned once, he is capable to handle all kind of field devices
from SMAR. This Local adjustment configuration is a suggestion only. The user may choose his
preferred configuration via configuration toll, simply configuring the display block).
The converter has two holes marked S and Z under the identification plate, which represent two
internal Reed switches that can be activated by inserting the magnetic tool. (See figure. 3.31).

Figure. 3.31 Local Adjustment Holes


Table 3.4 shows the actions on the Z and S holes on the IF303 when Local Adjustment is enabled.
HOLE
Z
S

ACTION
Inicializes and rotates through the available functions.
Selects the function shown in the display.
Table 3.4 Purpose of the holes on the Housing

3.29

Configuration

J1 Jumper Connections
If J1 (see figure 3.32) is connected to ON, then simulation mode in the AO block is enabled.

W1 Jumper Connections
If W1 is connected to ON, the local adjustment programming tree is enabled and then important
block parameters can be adjusted and communication can be pre-configured via local adjustment.

OFF

ON

OFF

ON

LOC
ADJ

WR

J1

W1

MAIN BOARD

Figure 3.32 - J1 and W1 Jumpers


Example: let's say we want to calibrate the lower and upper current value. From normal display,
enter local adjustment. The display will show:

In order to start the


local adjustment,
place the magnetic
tool in orifice Z and
wait until letters MD
are displayed.

Place the
magnetic tool in
orifice S and wait
during 5
seconds.

Figure 3.33 - Step 1 - FI303

3.30

FI303 - Operation e Maintenance Instruction Manual

Remove the magnetic


tool from orifice S.

Insert the magnetic


tool in orifice S once
more and LOC ADJ
should be displayed.

Figure 3.34 - Step 2 - FI303

This parameter is used to


calibrate the lower current
point. In order to range the
lower value, simply insert
the magnetic tool in orifice
S as soon as lower is
shown on the display. An
arrow pointing upward ()
increment the value and an
arrow pointing downward
() decrement the value.
Apply the 4.00 mA current
in the 1 and 4 terminals.
With the magnetic
screwdriver, adjust the
current value shown on the
display to indicate 4.00 mA.

Place the magnetic tool in


orifice Z. In case this is the
first configuration, the option
shown on the display is the
TAG with its corresponding
mnemonic configured by the
Configuration Tool.
Otherwise, the option shown
on the display will be the
one configured in the prior
operation. By keeping the
tool inserted in this orifice,
the local adjustment menu
will rotate.

Figure 3.35 - Step 3 - FI303

This parameter is used to


calibrate the upper current
point. In order to range the
upper value, simply insert the
magnetic tool in orifice S as
soon as upper is shown on the
display. An arrow pointing
upward () increment the value
and an arrow pointing
downward () decrement the
value. Apply the 20.0 mA
current in the 1 and 4 terminals.
With the magnetic tool, adjust
the current value shown on the
display to indicate 20.00 mA.

In order to decrement
the lower value, place
the magnetic tool in
orifice Z to shift the
arrow to the downward
position and then, by
inserting and keeping
the tool in orifice S, it is
possible to decrement
the lower value.

Figure 3.36 - Step 4 - FI303

3.31

Configuration
To decrease the upper
value, insert the
magnetic tool in orifice
Z to change the arrow
position downward ().
Remove it and insert it
in the orifice S to
decrease the upper
value.

The FEED option allows


the user to correct the
current calibration. To
implement the correction,
read the current
measured on the
Miliamperimeter and use
the screwdriver to adjust
the figure on the display
to this value. This option
corrects the value of a
lower calibration. An
arrow pointed upward
increases the current
value.

Figure 3.37 - Step 5 - FI303

Place the magnetic tool


on orifice S to change
the arrow position
downward and
decrease the calibration
current.

figure 3.38 - Step 6 - FI303

To change the address


value, withdraw the
magnetic tool from orifice
Z when the ADDR is
shown on the display. An
arrow pointing upward ()
increases the address,
and an arrow pointing
downward sets the
desired value.

To decrease the
address value, place
the magnetic tool on
orifice S to change the
arrow position
downward. Insert and
keep the tool to
decrease the address
value

figure 3.39 - Step 7 - FI303


NOTE
This Local adjustment configuration is a suggestion only. The user may choose his preferred configuration via
Configuration Tool, simply configuring the display block (refer to paragraph display Transducer Block).

3.32

FI303 - Operation e Maintenance Instruction Manual

Cyclical Diagnosis
Via cyclic communication is possible to verify diagnostics from the FI303 using the Profibus Master
Class 1 or even via acyclic communication via Master Class 2. The Profibus-PA devices provide up
to 4 standard diagnoses bytes via Physcial Block (See figure 3.40 and 3.41) and when the most
significant bit of the fourth Byte is "1", the diagnose will extend the information in more 6 bytes.
These Diagnosis bytes can also be monitored via cyclic tools.

Figure 3.40 Cyclical Diagnosis

Figure 3.41 Cyclic Diagnosis mapping for 4 bytes of Physical Block.


Unit_Diag_bit is described in the GSD file Profibus-PA device.
See below a description part of a GSD file for the 4 bytes and more detail:
;----------- Description of device related diagnosis: --------------------;
Unit_Diag_Bit(16)
Unit_Diag_Bit(17)
;
;Byte 01
Unit_Diag_Bit(24)
Unit_Diag_Bit(25)
Unit_Diag_Bit(26)
Unit_Diag_Bit(27)
Unit_Diag_Bit(28)
Unit_Diag_Bit(29)
Unit_Diag_Bit(30)
Unit_Diag_Bit(31)

= "Error appears"
= "Error disappears"
= "Hardware failure electronics"
= "Not used 25"
= "Not used 26"
= "Not used 27"
= "Memory error"
= "Measurement failure"
= "Device not initialized"
= "Device initialization failed"

;Byte 02
Unit_Diag_Bit(32)
Unit_Diag_Bit(33)
Unit_Diag_Bit(34)
Unit_Diag_Bit(35)

= "Not used 32"


= "Not used 33"
= "Configuration invalid"
= "Restart"
3.33

Configuration
Unit_Diag_Bit(36)
Unit_Diag_Bit(37)
Unit_Diag_Bit(38)
Unit_Diag_Bit(39)

= "Coldstart"
= "Maintenance required"
= "Characteristics invalid"
= "Ident_Number violation"

;Byte TRD Block & PHY Block


Unit_Diag_Bit(40) = "Not used 40"
Unit_Diag_Bit(41) = "Not used 41"
Unit_Diag_Bit(42) = "Not used 42"
Unit_Diag_Bit(43) = "Not used 43"
Unit_Diag_Bit(44) = "Not used 44"
Unit_Diag_Bit(45) = "Not used 45"
Unit_Diag_Bit(46) = "Not used 46"
Unit_Diag_Bit(47) = "Not used 47"
;byte 04
Unit_Diag_Bit(48)
Unit_Diag_Bit(49)
Unit_Diag_Bit(50)
Unit_Diag_Bit(51)
Unit_Diag_Bit(52)
Unit_Diag_Bit(53)
Unit_Diag_Bit(54)
Unit_Diag_Bit(55)

= "Not used 48"


= "Not used 49"
= "Not used 50"
= "Not used 51"
= "Not used 52"
= "Not used 53"
= "Not used 54"
= "Extension Available"

; Extended_Diag

3.34

Unit_Diag_Bit(56)
Unit_Diag_Bit(57)
Unit_Diag_Bit(58)
Unit_Diag_Bit(59)
Unit_Diag_Bit(60)
Unit_Diag_Bit(61)
Unit_Diag_Bit(62)
Unit_Diag_Bit(63)

= "Channel 01: current loop is open"


= "Channel 02: current loop is open"
= "Channel 03: current loop is open"
= "TRD Block 1 - Work Range violation"
= "TRD Block 2 - Work Range violation"
= "TRD Block 3 - Work Range violation"
= "Calibration Error - Check XD_ERROR parameter"
= "Device is in Writing Lock"

Unit_Diag_Bit(64)
Unit_Diag_Bit(65)
Unit_Diag_Bit(66)
Unit_Diag_Bit(67)
Unit_Diag_Bit(68)
Unit_Diag_Bit(69)
Unit_Diag_Bit(70)
Unit_Diag_Bit(71)

= "AO Block 1 in Out of Service"


= "AO Block 1 in Fail Safe"
= "Not used 66"
= "Not used 67"
= "Not used 68"
= "Not used 69"
= "Not used 70"
= "Not used 71"

Unit_Diag_Bit(72)
Unit_Diag_Bit(73)
Unit_Diag_Bit(74)
Unit_Diag_Bit(75)
Unit_Diag_Bit(76)
Unit_Diag_Bit(77)
Unit_Diag_Bit(78)
Unit_Diag_Bit(79)

= "AO Block 2 in Out of Service"


= "AO Block 2 in Fail Safe"
= "Not used 74"
= "Not used 75"
= "Not used 76"
= "Not used 77"
= "Not used 78"
= "Not used 79"

Unit_Diag_Bit(80)
Unit_Diag_Bit(81)
Unit_Diag_Bit(82)
Unit_Diag_Bit(83)
Unit_Diag_Bit(84)
Unit_Diag_Bit(85)
Unit_Diag_Bit(86)

= "AO Block 3 in Out of Service"


= "AO Block 3 in Fail Safe"
= "Not used 82"
= "Not used 83
= "Not used 84
= "Not used 85"
= "Not used 86"

FI303 - Operation e Maintenance Instruction Manual


Unit_Diag_Bit(87) = "Not used 87"
Unit_Diag_Bit(88)
Unit_Diag_Bit(89)
Unit_Diag_Bit(90)
Unit_Diag_Bit(91)
Unit_Diag_Bit(92)
Unit_Diag_Bit(93)
Unit_Diag_Bit(94)
Unit_Diag_Bit(95)

= "Not used 88"


= "Not used 89"
= "Not used 90"
= "Not used 91"
= "Not used 92"
= "Not used 93"
= "Not used 94"
= "Not used 95"

Unit_Diag_Bit(96) = "Not used 96"


Unit_Diag_Bit(97) = "Not used 97"
Unit_Diag_Bit(98) = "Not used 98"
Unit_Diag_Bit(99) = "Not used 99"
Unit_Diag_Bit(100) = "Not used 100"
Unit_Diag_Bit(101) = "Not used 101"
Unit_Diag_Bit(102) = "Not used 102"
Unit_Diag_Bit(103) = "Not used 103"
NOTE
If the FIX flag is active on LCD, the FI303 is configured to "Profile Specific". When in "Manufacturer Specific",
the Identifier Number is 0x0899. Once the Identifier_Number_Selector is changed from "Profile Specific" to
"Manufacturer Specific" or vice-versa, you must wait 5 seconds while it is saved and the turn off the FI303 and
then the identifier is updated in the level of communication. If the equipment is in "Profile Specific" and using
the GSD file Identifier Number equals 0x0899, the acyclic communication will work well with tools based on
EDDL, FDT/DTM, but no cyclic communication with the Profibus-DP master will get success.

3.35

Configuration

3.36

Section 4
MAINTENANCE PROCEDURES
General
NOTE
Equipment installed in hazardous atmospheres must be inspected in compliance with the IEC60079-17
standard.

SMAR FI303 PROFIBUS PA to Current Converters are extensively tested and inspected before
delivery to the end user. Nevertheless, during their design and development, consideration was
given to the possibility of repairs by the end user, if necessary.
In general, it is recommended that the end-user do not try to repair printed circuit boards.
Instead, he should have spare circuit boards, which may be ordered from SMAR whenever
necessary.
TROUBLESHOOTING
SYMPTOM

PROBABLE SOURCES OF TROUBLE


Converter PROFIBUS Connections
Check wiring polarity and continuity.

NO QUIESCENT URRENT

Power Supply
Check power supply output. The voltage at the FI303 terminals must be between 9 and 32 VDC.
Electronics Circuit Failure
Check circuit boards for defect by replacing them with spare ones.
Network Connection
Check network connections: devices, power supply, couplers, links and terminators.
Converter Configuration
Check configuration of communication parameters of converter.

NO COMMUNICATION
Network Configuration
Check communication configuration of the network.
Electronics Circuit Failure
Try to replace the converter circuit with spare parts.
Output Terminals Connection
Check wiring polarity and continuity.
Power Supply
Check power supply output. The voltage at the output terminals of FI303 must be between 3 and 45 VDC.
INCORRECT OUTPUTS

Load Resistance
Load resistance must be between 0 and 2000. Note that the maximum value depends on output power
supply voltage.
Calibration
Check calibration of converter.

4.1

FI303 - Operation and Maintenance Manual


If the problem cannot by solved with the diagnostic table above, run the factory init according to
the note below.
NOTE
The Factory Init should be tried as a last option to recover the equipment control when the equipment
presents some problem related to the function blocks or the communication. This operation must only be
carried out by authorized technical personnel and with the process offline, since the equipment will be
configured with standard and factory data.
This procedure resets all the configurations run on the equipment, after which a partial download should
be performed. With exception to the equipment physical address and the gsd identifier number selector
parameter. After doing this, all configurations must be remade according to their applications.
To run the factory Init, use two magnetic screwdrivers. Remove the screw on the equipment that fixes the
identification tag on the carcass top to access the orifices bearing the letters S and Z.
The operations to follow are:
1) Turn off the equipment, insert the magnetic tools in each orifice (S and Z). Leave them in the orifices;
2) Power the equipment;
3) As soon as Factory Init is shown on the display, take off the tools and wait for the "5" symbol on the
right upper corner of the display to unlit, thus indicating the end of the operation.
This operation has factory configuration that eliminates possible problems with the functional blocks or
the transmitter communication.
Caution: this operation must be carried out by an authorized technician, with the process offline, as the
process will be configured with factory standard data.

Disassembly Procedure
Refer to Figure 4.1 - FI303 Exploded View Make sure to disconnect power supply before
disassembling the converter.

12
11
10
9
8
7
15

6
5
14

4
2

16

13

Figure 4.1 - FI303 Exploded View


Electronic Circuit
The main plate (5) and the outlet plate (7) are factory match pairs and must be replaced
together, as one should not be changed separately.
4.2

Maintenance Procedures

To remove the electronic plates (5 and 7) and the display (4), release the lid lock (8) on the
carcass side not bearing the words Field Terminals and unscrew the lid (1).
WARNING
The plates have CMOS components that may be damaged by electrostatic discharges. Follow the right
procedure for handling the CMOS components. The plate should be stored in an electrostatic-proof case.

Loosen both screws (3) that anchors the display and the main circuit board. Gently pull out the
display, and then the main board (5). To remove the output board (7), first unscrew both screws
(6) that anchors it to the housing (9), and gently pull out the board.

Reassembly Procedure
Put output board (7) into housing (9).
Anchor output board with its screws (6).
Place the main plate (5) on the carcass and make sure the pins are connected.
Put display (4) into the housing, observing the four mounting positions. The "" symbol must
point upward.
Anchor the main board and display with their screws (3).
Fit the cover (1) and lock it using the locking screw (8).

Interchangeability
The calibration data on the Inlet plate are stored on the Principal plate EEPROM, reason why
they are said to be match pairs.
ADVERTNCIA
If, for some reason, you separate the input and the main boards, you must do a trim to guarantee
precision of the inputs. With mismatched boards, the factory trim will not be as good as it was.

Accessories and Related Products


ACCESSORIES AND RELATED PRODUCTS
ORDERING CODE

DESCRIPTION

AssetView FDT

Asset Management With FDT

BC1

Fieldbus/RS232 Interface

BT302

Terminator

DF47-17

Intrinsic Safety Barrier

DF73

HSE/PROFIBUS-DP Controller

DF95/DF97

PROFIBUS DP/PA Controller

FDI302

Field Device interface

PBI

USB Profibus Interface

ProfibusView

Profibus PA Device Parameterization Software

PS302/DF52

Power Supply

PSI302/DF53

Power Supply Impedance

SD1

Magnetic Tool for Local Adjustment

4.3

FI303 - Operation and Maintenance Manual

Spare Parts List


SPARE PARTS LIST
DESCRIPTION OF PARTS
Cover Without Window (Includes O-Ring)
Cover With Window for Indicator (Includes ORing)
0-Rings (Note 3)
Aluminum Housing Main Board Screw
316 Stainless Steel Housing Main Board Screw

Aluminum
316 SS
Aluminum
316 SS
Cover, Buna-N
Units with indicator
Units without indicator
Units With Indicator
Units Without Indicator

Digital Indicator
Main and Output Circuit Board Assembly
Input Board Screw

Housing in Aluminum
Housing in 316 Stainless Steel

Cover Locking Screw


Housing, Aluminum (Note 2)

Housing, 316 SS (Note 2)

- 14 NPT
M20 x 1.5
PG 13.5 DIN
- 14 NPT
M20 x 1.5
PG 13.5 DIN

Local Adjustment Protection Cap


Identification Plate Fixing Screw
Terminal Insulator
External Ground Screw
Terminal Holding Screw
Six-Sided Plug 1/2" NPT Internal BR Ex
Six-Sided Plug 1/2" NPT Internal
Six-Sided Plug M20 X 1.5 External BR Ex d
Six-Sided Plug PG13.5 External BR Ex d
Mounting Bracket for 2" Pipe (Note 4)

Housing in Aluminum
Housing in 316 Stainless Steel
Bichromated Carbon Steel
Bichromated 304 Stainless Steel
Bichromated Carbon Steel
Bichromated 304 Stainless Steel
316 Stainless Steel
316 Stainless Steel
Carbon Steel
Stainless Steel 316
Carbon Steel bolts, nuts, washers
and U-clamp in Stainless Steel

POSITION

CODE

1 and 15
1 and 15
1
1
2
3
3
3
3
4
5 and 7
6
6
8
9
9
9
9
9
9
10
11
12
13
14
14
16
16
16
16
16
16
-

204-0102
204-0105
204-0103
204-0106
204-0122
304-0118
304-0117
204-0118
204-0117
214-0108
400-0318
314- 0125
214-0125
204-0120
400-0312
400-0313
400-0314
400-0315
400-0316
400-0317
204-0114
204-0116
314-0123
204-0124
304-0119
204-0119
400-0808
400-0809
400-0583-11
400-0583-12
400-0810
400-0811
214-0801
214-0802

214-0803

CATEGORY
(NOTE 1)

NOTE
1234-

4.4

For category A, it is recommended to keep, in stock, 25 parts installed for each set, and for category B, 50.
It includes terminal holder insulator, bolts (cover lock, grounding and terminal holder insulator) and identification plate without certification.
O-Rings are packaged in packs of 12 units.
Including U-clamp, nuts, bolts and washers. Spare Parts List.

Section 5
TECHNICAL CHARACTERISTICS
Functional Specifications
Output Signal

Three 4-20 mA current links, external supply, common ground.

Input Signal
Output Load Limitation

Digital only, Fieldbus, 31.25 Kbit/s voltage mode with bus power.
External Output Supply Voltage 3-45 Vdc.
Bus power 9-32 Vdc.
Current consumption quiescent 12 mA.
Output impedance: non-intrinsic safety from 7.8 KHz - 39 KHz should be greater or equal to 3
KOhm.
Intrinsic safety output impedance (assuming an IS barrier in the power supply) from 7.8 KHz - 39
KHz should be greater or equal to 400 Ohm.
Optional 4 digit LCD indicator.

Power Supply

Indication
Hazardous Area Certification

Explosion-proof and intrinsically safe (ATEX (NEMKO and DEKRA EXAM), FM, CEPEL, CSA and
NEPSI).
Designed to comply with European Regulations (ATEX 94/9/EC and LVD 2006/95/EC).

Temperature Limits
Humidity Limits
Turn-on Time
Update Time
Configuration

Operation:
Storage:
Display:

-40
-40
-10
-40

to
to
to
to

85 C
120 C
60 C
85 C

(-40
(-40
( 14
(-40

to
to
to
to

185 F)
250 F)
140 F) operation
185 F) without damage.

0 to 100% RH.
Approximately 10 seconds.
Approximately 0.5 second.
Basic configuration may be done using local adjustment magnetic tool if device is fitted with
display. Complete configuration is possible using remote configurator (Ex.: ProfibusView,
AssetView for FDT or Simatic PDM).
Performance Specifications

Accuracy
Ambient Temperature
Effect
Output Power Supply
Effect
Vibration Effect
Electromagnetic
Interference Effect

0.1%.
For a 10 C variation: 0.05%.
0.005%/V
Complies with SAMA PMC 31.1 standard.
Designed to comply with European Directive EMC 2004/108/EC.
Physical Specifications

Hardware
Electrical Connection
Material of Construction
Mounting
Weight

Physical: according to IEC 61158-2 and conformity with the FISCO model.
1/2-14 NPT, PG 13.5 or M20 x 1.5.
Injected low copper aluminum with polyester painting or 316 Stainless Steel housing, with Buna
N O-rings on covers.
With an optional bracket can be installed on a 2" pipe or fixed on a wall or panel.
Without display and mounting bracket: 0.80 kg.
Add for digital display: 0.13 kg.
Add for mounting bracket: 0.60 kg.

5.1

FI303 - Operation and Maintenance Manual

Ordering Code
MODEL
FI303

TRIPLE CHANNEL PROFIBUS TO CURRENT CONVERTER


COD. Local Indicator
0
1

Without Indicator
With Digital Indicator
COD. Mounting Bracket
0

Without Bracket

Carbon Steel. Accessories: Carbon Steel

316 Stainless Steel. Accessories: AI316

Carbon Steel. Accessories: AI316


COD. Electrical Connections
0

1/2 - 14 NPT

1/2"- 14 NPT X 3/4 NPT (AI316) - with adapter

1/2" - 14 NPT X 3/4 BSP ( AI316) - with adapter

1/2" - 14 NPT X 1/2 BSP (AI316) - with adapter

M20 X 1.5

PG 13.5 DIN
SPECIAL OPTIONS
COD. Housing
H0

Aluminum (IP/TYPE)

H1

316 Stainless Steel (IP/TYPE)

H2

Aluminum for saline atmosphere (IPW/TYPE X)

H3

316 Stainless Steel for saline atmosphere (IPW/TYPE X)


COD. Identification Plate
I1

FM: XP, IS, NI, DI

I4

EXAM (DMT): Ex-ia; NEMKO: Ex-d

I5

CEPEL: Ex-d, Ex-ia

I6

Without Certification

IE

NEPSI: Ex-ia
COD. Painting
P0

Gray Munsell N 6,5 Polyester

P3

Black Polyester

P4

White Epoxi

P5

Yellow Polyester

P8

Without Painting

P9

Safety Blue Epoxy - Electrostatic Painting

PC

Safety Blue Polyester - Electrostatic Painting

PG

Safety Orange Epoxi Paint - Electrostatic Painting


COD. Output Signal
T0

3 output - 4 to 20 mA
COD. Tag Plate
J0

With tag

J1

Blank

J2

According to users notes


COD. Special
ZZ

FI303

* Leave it blank if not applicable

5.2

See Notes

TYPICAL MODEL

Appendix A
CERTIFICATIONS INFORMATION
Manufacturing Location Approved
Smar Equipamentos Industriais Ltda Sertozinho, So Paulo, Brasil.

European Directive Information


Consult www.smar.com for the EC declarations of conformity for all applicable European directives and certificates.
ATEX Directive 94/9/EC - Electrical equipment and protective system intended for use in potential explosive
atmospheres
The EC-Type Examination Certificate had been released by Nemko AS (CE0470) and/or DEKRA EXAM GmbH (CE0158),
according to European Standards.
The certification body for Production Quality Assurance Notification (QAN) and IECEx Quality Assessment Report (QAR) is Nemko
AS (CE0470).
LVD Directive 2006/95/EC - Electrical Equipment designed for use within certain voltage limits
According the LVD directive Annex II, electrical equipment for use in an explosive atmosphere is outside the scope of this directive.
According to IEC standard: IEC 61010-1:2010 - Safety requirements for electrical equipment for measurement, control, and
laboratory use - Part 1: General requirements.
EMC Directive 2004/108/EC - Electromagnetic Compatibility
The equipment is in compliance with the directive and EMC test was performed according to IEC standards: IEC61326-1:2005 and
IEC61326-2-3:2006.
To comply with the EMC directive the installation must follow these special conditions:

Use shielded, twisted-pair cable for powering the instrument and signal wiring.
Keep the shield insulated at the instrument side, connecting the other one to the ground.

Hazardous Locations General Information


Ex Standards:
IEC 60079-0 General Requirements
IEC 60079-1 Flameproof Enclosures d
IEC 60079-11 Intrinsic Safety i
IEC 60079-26 Equipment with equipment protection level (EPL) Ga
IEC 60079-27 Fieldbus intrinsically safe concept (FISCO)
IEC 60529 Classification of degrees of protection provided by enclosures (IP Code)
Customer responsibility:
IEC 60079-10 Classification of Hazardous Areas
IEC 60079-14 Electrical installation design, selection and erection
IEC 60079-17 Electrical Installations, Inspections and Maintenance
Warning:
Explosions could result in death or serious injury, besides financial damage.
Installation of this instrument in an explosive environment must be in accordance with the national standards and according to
the local environmental protection method. Before proceeding with the installation match the certificate parameters according to
the environmental classification.
General Notes:
Maintenance and Repair
The instrument modification or replaced parts supplied by any other supplier than authorized representative of Smar
Equipamentos Industriais Ltda is prohibited and will void the Certification.
A.1

FI303 Operation and Maintenance Instruction Manual


Marking Label
Once a device labeled with multiple approval types is installed, do not reinstall it using any other approval types. Scratch off or
mark unused approval types on the approval label.
For Ex-i protection application
Connect the instrument to a proper intrinsically safe barrier.
Check the intrinsically safe parameters involving the barrier, equipment including the cable and connections.
Associated apparatus ground bus shall be insulated from panels and mounting enclosures.
When using shielded cable, isolate the not grounded cable end.
Cable capacitance and inductance plus Ci and Li must be smaller than Co and Lo of the Associated Apparatus.
For Ex-d protection application
Only use Explosion Proof/Flameproof certified Plugs, Adapters and Cable glands.
As the instrument is non-ignition capable under normal conditions, the statement Seal Not Required could be applied for
Explosion Proof version regarding to electric conduits connection. (CSA Approved)
In an Explosion-Proof/Flame-Proof installation, do not remove the instrument housing covers when powered on.
Electrical Connection
In Explosion-Proof installations the cable entries must be connected through conduit with sealed unit or closed using metal
cable gland or closed using metal blanking plug, all with at least IP66 and Ex-d certification. For enclosure with saline
environment protection (W) and ingress protection (IP) applications, all NPT thread parts must apply a proper water-proof
sealant (a non-hardening silicone group sealant is recommended).
For Ex-d and Ex-i protection application

The transmitter has a double protection. In this case the transmitter shall be fitted with appropriate certified cable entries
Ex-d and the electric circuit supplied by a certified diode safety barrier as specified for the protection Ex-ia.
Environmental Protection
Enclosure Types (Type X): Supplementary letter X meaning special condition defined as default by Smar the following:
Saline Environment approved - salt spray exposed for 200 hours at 35C. (Ref: NEMA 250)
Ingress protection (IP W): Supplementary letter W meaning special condition defined as default by Smar the following: Saline
Environment approved - salt spray exposed for 200 hours at 35C. (Ref: IEC60529)
Ingress protection (IP x8): Second numeral meaning continuous immersion in water under special condition defined as
default by Smar the following: 1 Bar pressure during 24hours. (Ref: IEC60529)

Hazardous Locations Approvals


CSA (Canadian Standards Association)
Class 2258 02 Process Control Equipment For Hazardous Locations (CSA1002882)
Class I, Division 1, Groups B, C and D
Class II, Division 1, Groups E, F and G
Class III, Division 1
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups E, F and G
Class III
CLASS 2258 03 - PROCESS CONTROL EQUIPMENT Intrinsically Safe and Non-Incendive Systems - For Hazardous
Locations (CSA 1002882)
Class I, Division 2, Groups A, B, C and D
Model FI303 Fieldbus Converter; supply 12-42V dc, 4-20mA; Enclosure Type 4/4X; non-incendive with Fieldbus / FNICO Entity
parameters
@ Terminals + and - : Vmax =24V, Imax =570 mA, Pmax = 9.98 W, Ci = 5 nF, Li = 12uH; @ Terminals 1 - 4: Vmax =30V, Imax
=110mA, Ci = 5 nF, Li = 12uH; when connected through CSA Certified Safety Barriers as per SMAR Installation drawing
102A0559; Temp. Code T3C.
Class 2258 04 Process Control Equipment Intrinsically Safe Entity For Hazardous Locations (CSA 1002882)
Class I, Division 1, Groups A, B, C and D
Class II, Division 1, Groups E, F and G
Class III, Division 1
FISCO Field Device

A.2

Certifications Information
Model FI303 Fieldbus Converter; supply 12-42V dc, 4-20mA; Enclosure Type 4/4X; Intrinsically safe with Fieldbus/FISCO Entity
parameters
@ Terminals + and -:
Vmax = 24 V, Imax = 380 mA, Pi = 5.32 W, Ci = 5 nF, Li = 12 uH;
@ Terminals 1 4:
Vmax = 30 V, Imax = 110 mA, Ci = 5nF, Li = 12 uH;
when connected through CSA Certified Safety Barriers as per Smar Installation Drawing 102A0559; Code T3C.
Note: Only models with stainless steel external fittings are Certified as Type 4X.
Special conditions for safe use:
Temperature Class T3C
Maximum Ambient Temperature: 40C (-20 to 40 C)
FM Approvals (Factory Mutual)
Intrinsic Safety (FM 3006959)
IS Class I, Division 1, Groups A, B, C and D
IS Class II, Division 1, Groups E, F and G
IS Class III, Division 1
Explosion Proof (FM 3006959)
XP Class I, Division 1, Groups A, B, C and D
Dust Ignition Proof (FM 3006959)
DIP Class II, Division 1, Groups E, F and G
DIP Class III, Division 1
Non Incendive (FM 3006959)
NI Class I, Division 2, Groups A, B, C and D
Environmental Protection (FM 3006959)
Option: Type 4X/6/6P or Type 4/6/6P
Special conditions for safe use:
Entity Parameters Fieldbus Power Supply Input (report 3015629):
Vmax = 24 Vdc, Imax = 250 mA, Pi = 1.2 W, Ci = 5 nF, Li = 12 uH
Vmax = 16 Vdc, Imax = 250 mA, Pi = 2 W, Ci = 5 nF, Li = 12 uH
4-20 mA Current Loop:
Vmax = 30 Vdc, Imax = 110 mA, Pi = 0,825 W, Ci = 5 nF, Li = 12 uH
Temperature Class T4
Maximum Ambient Temperature: 60C (-20 to 60 C)
NEMKO (Norges Elektriske MaterielKontroll)
Explosion Proof (Nemko 13 ATEX 1570)
Group II, Category 2 G, Ex d, Group IIC, Temperature Class T6, EPL Gb
Ambient Temperature: -20 to 60 C
Environmental Protection (Nemko 13 ATEX 1570)
Options: IP66W/68W
The Essential Health and Safety Requirements are assured by compliance with:
EN 60079-0:2012 General Requirements
EN 60079-1:2007 Flameproof Enclosures d
EXAM (BBG Prf - und Zertifizier GmbH)
Intrinsic Safety (DMT 00 ATEX E 065) - In Progress
Group I, Category M2, Ex ia, Group I, EPL Mb
Group II, Category 2 G, Ex ia, Group IIC, Temperature Class T4/T5/T6, EPL Ga
FISCO Field Device
Supply circuit for the connection to an intrinsically safe fieldbus-circuit:
Ui = 24Vdc, Ii = 380 mA, Pi = 5.32 W, Ci 5 nF, Li = neg
Parameter of the supply circuit complies with FISCO model according to EN 60079-27: 2008.
A.3

FI303 Operation and Maintenance Instruction Manual

Output-signal-circuits; three 4-20 mA current sinks with common ground for external intrinsically safe supply
Effective internal capacitance Ci negligible
Effective internal inductance Ci negligible
Safety-relevant maximum values for certified intrinsically safe 4-20 mA current loop circuits as a function of ambient temperature
and temperature class;
Max. Ambient
temperature Ta
60C
50C
40C

Temperature
Class
T4
T5
T6

Voltage DC
Ui
28 V
28 V
28 V

Current
Ii
93 mA
93 mA
93 mA

Power
Pi
750 mW
750 mW
570 mW

The signal outputs are safely galvanically separated from the fieldbus circuit.
Ambient Temperature: -40C Ta 60C
The Essential Health and Safety Requirements are assured by compliance with:
EN 60079-0:2009 General Requirements
EN 60079-11:2007 Intrinsic Safety i
EN 60079-26:2007 Equipment with equipment protection level (EPL) Ga
EN 60079-27:2008 Fieldbus intrinsically safe concept (FISCO)
CEPEL (Centro de Pesquisa de Energia Eltrica)
Intrinsic Safety (CEPEL 97.0019X)
Ex ia, Group IIC, Temperature Class T4/T5, EPL Ga
FISCO Field Device
Entity Parameters:
Pi = 5.32 W, Ui = 30V, Ii = 380 mA, Ci = 5.0 nF, Li = Neg
Ambient Temperature:
-20 to 65C for T4
-20 to 50C for T5
Explosion Proof (CEPEL 97.0091)
Ex d, Group IIC, Temperature Class T6, EPL Gb
Maximum Ambient Temperature: 40C (-20 to 40 C)
Environmental Protection (CEPEL 97.0019X and CEPEL 97.0091)
Options: IP66/68W or IP66/68
Special conditions for safe use:
The certificate number ends with the letter "X" to indicate that for the version of FIELDBUS to current Converter model FI303
equipped with housing made of aluminum alloy, only can be installed in "Zone 0" if is excluded the risk of occurs impact or friction
between the housing and iron/steel itens.
The Essential Health and Safety Requirements are assured by compliance with:
ABNT NBR IEC 60079-0:2008 General Requirements
ABNT NBR IEC 60079-1:2009 Flameproof Enclosures d
ABNT NBR IEC 60079-11:2009 Intrinsic Safety i
ABNT NBR IEC 60079-26:2008 Equipment with equipment protection level (EPL) Ga
IEC 60079-27:2008 Fieldbus intrinsically safe concept (FISCO)
ABNT NBR IEC 60529:2005 Classification of degrees of protection provided by enclosures (IP Code)
NEPSI (National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation)
Intrinsic Safety (NEPSI GYJ071324)
Ex ia, Group IIC, Temperature Class T4/T5/T6
Supply terminals entity parameters:
Ui = 16 V, Ii = 250 mA, Pi = 2.0 W, Ci = 5 nF, Li = 0
A.4

Certifications Information
Terminals 1-4:
Pi = 0.75 W, Ui = 28 V, Ii = 93 mA, Ci = 0 nF, Li = 0
Ambient Temperature:
T4 40 C for Pi = 2.0W,
Pi = 750 mW
T4 60 C for Pi = 865 mW, Pi = 750 mW
T5 40 C for Pi = 990 mW, Pi = 750 mW
T6 40 C for Pi = 630 mW, Pi = 570 mW

Identification Plate and Control Drawing


CSA (Canadian Standards Association)

FM Approvals (Factory Mutual)

A.5

FI303 Operation and Maintenance Instruction Manual


NEMKO (Norges Elektriske MaterielKontroll) / EXAM (BBG Prf - und Zertifizier GmbH)

CEPEL (Centro de Pesquisa de Energia Eltrica)

NEPSI (National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation)

A.6

Certifications Information
Canadian Standards Association (CSA)

A.7

FI303 Operation and Maintenance Instruction Manual

A.8

MARCIAL
MISSAWA
20 10 08 20 10 08
MARCIAL
MISSAWA
6
16 07 07 16 07 07
MOACIR
CASSIOLATO
5
07 05 03 07 05 03
MOACIR
CASSIOLATO
4
08 02 00 08 02 00
REV. DESIGN
APPROVED

ALT DE
0049/08

AREA

ALT DE
0004/07 28 03 95
ALT DE CUSTOMER:
0043/03
EQUIPMENT:
ALT DE
0015/00

MELONI
+

DRAWING

DESIGN

28

03

95

28

M.MISSAWA SINASTRE

VERIFIED

03

95

FI302/303

CONTROL DRAWING

28

03

FIELDBUS

GROUND BUS

4 to 20mA
I.S.
BARRIER

FIELDBUS
I.S.
BARRIER

OPTIONAL
SHIELDING

APPROVAL CONTROLLED BY C.A.R.

APPROVED

PELUSO

95

DRAWING N.
Voc
Isc
Po

24V
250mA
1,2W

Voc
Isc
Po

CABLE INDUCTANCE +12uh

La
FIELDBUS

CABLE CAPACITANCE +5nF

Ca

GROUPS A,B,C,D,E,F & G

CLASS I,II,III DIV.1

16V
250mA
2W

4-20mA
30V
Voc
110mA
Isc

ENTITY PARAMETERS FOR ASSOCIATED APPARATUS

POWER SUPPLY

POWER SUPPLY

ASSOCIATED APPARATUS

EARTH IN EXCESS OF 250VAC OR 250VDC.

SOURCE OF POTENTIAL IN RELATION TO

NORMAL OR ABNORMAL CONDITIONS, A

BE SUPPLIED FROM, NOR CONTAIN UNDER

UNSPECIFIED, EXCEPT THAT IT MUST NOT

SAFE AREA APPARATUS

NON HAZARDOUS OR DIVISION 2 AREA

TRANSMITTER SPECIFICATION MUST BE IN ACCORDANCE TO


APPROVAL LISTING.

2-

WIRES: TWISTED PAIR, 22AWG OR LARGER.


SHIELD IS OPTIONAL IF USED, BE SURE TO INSULATE THE END NOT
GROUNDED.

56-

4-20mA
Ci=5nF Li=12uH
Vmax
30V
Imax
110mA

FIELDBUS
Ci=5nF Li=12uH
Vmax
24V
Imax
250mA

ENTITY VALUES:

CLASS I,II,III DIV.1, GROUPS A,B,C,D,E,F & G

MODELS FI302 AND FI303 - SERIES

FIELDBUS

APPROVAL.

PREVIOUS MANUFACTURER

BE SUBSTITUTED WITHOUT

COMPONENTS CAN NOT

CABLE CAPACITANCE AND INDUTANCE PLUS Ci AND Li MUST BE


SMALLER THAN Ca AND La OF THE ASSOCIATED APPARATUS.

ASSOCIATED APPARATUS GROUND BUS RESISTANCE TO EARTH MUST BE


SMALLER THAN 1(ONE) OHM, IF NOT ISOLATED.

4-

7-

ASSOCIATED APPARATUS GROUND BUS TO BE INSULATED FROM PANELS


AND MOUNTING ENCLOSURES.

3-

FM

INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE


(ANSI/NFPA 70) AND ANSI/ISA-RP12.6

HAZARDOUS AREA

1-

REQUIREMENTS:

Certifications Information

Factory Mutual (FM)

FM

APPROVED

smar

O.S.

102A0080

REV

SH.01/01

07

A.9

FI303 Operation and Maintenance Instruction Manual

A.10

Appendix B
SRF Service Request Form
Converter from Fieldbus to 4-20mA
GENERAL DATA
Model:
Serial Number:
TAG:

FI302 ( )
FI303 ( )
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________

How many
channels are
used in IF?

1( )

Configuration:

Magnetic Tool ( )

2( )
PC ( )

3( )

Software: _____________

Version: ________________ Other: _____________________

INSTALLATION DATA
Type/Model/Manufacturer of device
connected to the channel 1:

______________________________________________________________________________________

Type/Model/Manufacturer of device
connected to the channel 2:

______________________________________________________________________________________

Type/Model/Manufacturer of device
connected to the channel 3:

______________________________________________________________________________________

PROCESS DATA
Hazardous Area
Classification:

( ) Yes, please specify: ______________________________________________________________________________


( ) No
More details: _______________________________________________________________________________________

Types of Interference
Without interference ( )
presents in the area:
Ambient
Temperature:

Temperature ( )

Vibration ( )

Others: ____________________________________

From __________C up to __________C

OCCURRENCE DESCRIPTION
_____________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________

SERVICE SUGGESTION
Adjustment ( )

Cleaning ( )

Preventive Maintenance ( )

Update / Up-grade ( )

Other: _______________________________________________________________________________________________________________

USER INFORMATION
Company: ___________________________________________________________________________________________________________
Contact: _____________________________________________________________________________________________________________
Title: ________________________________________________________________________________________________________________
Section: _____________________________________________________________________________________________________________
Phone: _________ _________________________

_________ _________________________

E-mail: ________________________________________________________________________

Extension: __________________________
Date: ______/ ______/ _________________

For warranty or non-warranty repair, please contact your representative.


Further information about address and contacts can be found on www.smar.com/contactus.asp.

B.1

FI303 Operation, Maintenance and Instructions Manual

Returning Materials
Should it be necessary to return the converter to Smar, simply contact your local Smar office
informing the defective equipment serial number and dispatch it to our factory.
For easier analysis and faster solution of the problem, the returned material should include the
documentation with a description of the failure observed in the field and the circumstances that
caused it. Other information, such as the installation site, type of measure taken and the process
conditions are also important for a prompt evaluation.