UT35A/UT32A
Digital Indicating Controllers
Users Manual
IM 05P01D31-01EN
IM 05P01D31-01EN
4th Edition
Product Registration
Thank you for purchasing YOKOGAWA products.
YOKOGAWA provides registered users with a variety of information and services.
Please allow us to serve you best by completing the product registration form accessible
from our homepage.
http://www.yokogawa.com/ns/reg/
Introduction
Thank you for purchasing the UT35A/UT32A digital indicating controller (hereinafter
referred to as UT35A/UT32A).
This manual describes how to use UT35A/UT32A functions other than UT35A/UT32As
communication function and ladder sequence function. Please read through this users
manual carefully before using the product.
Note that the manuals for the UT35A/UT32A comprise the following seven documents:
Printed manual
Manual Name
Manual Number
Description
IM 05P01D31-11EN
IM 05P01D31-15EN
Electronic manuals
Manual Name
Manual Number
Description
IM 05P01D31-11EN
IM 05P01D31-15EN
UT35A/UT32A
Users Manual
IM 05P01D31-01EN
IM 05P07A01-01EN
UTAdvanced Series
Communication Interface (Open
Network)
Users Manual
IM 05P07A01-02EN
IM 05P05A01-01EN
IM 05P05A01-02EN
UTAdvanced Series
Communication Interface
(RS-485, Ethernet)
Users Manual
Target Readers
Notice
The contents of this manual are subject to change without notice as a result of
continuing improvements to the instruments performance and functions.
Every effort has been made to ensure accuracy in the preparation of this manual.
Should any errors or omissions come to your attention, however, please inform
Yokogawa Electrics sales office or sales representative.
Under no circumstances may the contents of this manual, in part or in whole, be
transcribed or copied without our permission.
Trademarks
Our product names or brand names mentioned in this manual are the trademarks or
registered trademarks of Yokogawa Electric Corporation (hereinafter referred to as
YOKOGAWA).
Microsoft, MS-DOS, Windows, Windows XP, Windows Vista, and Windows 7 are
either registered trademarks or trademarks of Microsoft Corporation in the United
States and/or other countries.
Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of
Adobe Systems Incorporated.
Ethernet is a registered trademark of XEROX Corporation in the United States.
Modbus is a registered trademark of Schneider Electric.
PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.
DeviceNet is a registered trademark of Open DeviceNet Vender Association, Inc.
CC-Link is a registered trademark of CC-Link Partner Association (CLPA.)
We do not use the TM or mark to indicate these trademarks or registered
trademarks in this users manual.
All other product names mentioned in this users manual are trademarks or registered
trademarks of their respective companies.
Safety Precautions
CAUTION
This instrument is an EMC class A product. In a domestic environment, this product
may cause radio interference in which case the user needs to take adequate
measures.
ii
IM 05P01D31-01EN
AC/DC
The equipment wholly protected by double insulation or reinforced insulation.
Functional grounding terminal (Do not use this terminal as a protective grounding terminal.)
In order to protect the system controlled by this product and the product itself, and
to ensure safe operation, observe the safety precautions described in this users
manual. Use of the instrument in a manner not prescribed herein may compromise the
products functions and the protection features inherent in the device. We assume no
liability for safety, or responsibility for the products quality, performance or functionality
should users fail to observe these instructions when operating the product.
Installation of protection and/or safety circuits with respect to a lightning protector;
protective equipment for the system controlled by the product and the product itself;
foolproof or failsafe design of a process or line using the system controlled by the
product or the product itself; and/or the design and installation of other protective and
safety circuits are to be appropriately implemented as the customer deems necessary.
Be sure to use the spare parts approved by YOKOGAWA when replacing parts or consumables.
This product is not designed or manufactured to be used in critical applications that
directly affect or threaten human lives. Such applications include nuclear power
equipment, devices using radioactivity, railway facilities, aviation equipment, air
navigation facilities, aviation facilities, and medical equipment. If so used, it is the
users responsibility to include in the system additional equipment and devices that
ensure personnel safety.
Modification of the product is strictly prohibited.
This product is intended to be handled by skilled/trained personnel for electric devices.
This product is UL Recognized Component. In order to comply with UL standards,
end-products are necessary to be designed by those who have knowledge of the
requirements.
WARNING
Power Supply
Ensure that the instruments supply voltage matches the voltage of the power
supply before turning ON the power.
Do Not Use in an Explosive Atmosphere
Do not operate the instrument in locations with combustible or explosive gases
or steam. Operation in such environments constitutes an extreme safety hazard.
Use of the instrument in environments with high concentrations of corrosive gas
(H2S, SOX, etc.) for extended periods of time may cause a failure.
Do Not Remove Internal Unit
The internal unit should not be removed by anyone other than YOKOGAWAs
service personnel. There are dangerous high voltage parts inside. Additionally,
do not replace the fuse by yourself.
Damage to the Protective Construction
Operation of the instrument in a manner not specified in this users manual may
damage its protective construction.
IM 05P01D31-01EN
iii
The instrument comprises many plastic components. To clean it, wipe it with a soft,
dry cloth. Do not use organic solvents such as benzene or thinner for cleaning, as
discoloration or deformation may result.
Keep electrically charged objects away from the signal terminals. Not doing so may
cause the instrument to fail.
Do not apply volatile chemicals to the display area, operation keys, etc. Do not leave
the instrument in contact with rubber or PVC products for extended periods. Doing so
may result in failure.
If the equipment emits smoke or abnormal smells or makes unusual noises, turn OFF
the instruments power immediately and unplug the device. In such an event, contact
your sales representative.
This is an explanation of how to dispose of this product based on Waste Electrical and
Electronic Equipment (WEEE), Directive 2002/96/EC. This directive is only valid in the
EU.
Marking
This product complies with the WEEE Directive (2002/96/EC) marking requirement.
This marking indicates that you must not discard this electrical/electronic product in
domestic household waste.
Product Category
With reference to the equipment types in the WEEE directive Annex 1, this product is
classified as a Monitoring and Control instrumentation product.
Do not dispose in domestic household waste. When disposing products in the EU,
contact your local Yokogawa Europe B.V. office.
iv
IM 05P01D31-01EN
Unpack the box and check the contents before using the product. If the product is
different from that which you have ordered, if any parts or accessories are missing, or if
the product appears to be damaged, contact your sales representative.
UT35A/UT32A Main Unit
The UT35A/UT32A main units have nameplates affixed to the side of the case.
Check the model and suffix codes inscribed on the nameplate to confirm that the product
received is that which was ordered.
No. (Instrument number)
When contacting your sales representative, inform them of this number, too.
Note
The last digit of the display code (-x0) has been changed into the case color code.
IM 05P01D31-01EN
Optional
suffix
code
Suffix code
UT35A
Type 1:
Basic
control
-0
-1
-2
Type 2:
Functions
0
1
2
Type 3:
Open networks
0
1
2
3
4
5
Case color
Fixed code
-1
-2
-3
-4
0
1
vi
-00
/LP
/HA
/DC
/CT
[Style:S3]
Description
Digital Indicating Controller (provided with retransmission output or 15 V DC
loop power supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC)
Standard type
Position proportional type
Heating/cooling type
None
2 additional DIs, 2 additional DOs
5 additional DIs, 5 additional DOs
None
RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)
Ethernet communication (with serial gateway function)
CC-Link communication (with Modbus master funciton)
PROFIBUS-DP communication (with Modbus master function)
DeviceNet communication (with Modbus master function)
English
German
French
Spanish
White (Light gray)
Black (Light charcoal gray)
Always "-00"
24 V DC loop power supply (*2)
Heater break alarm (*3)
Power supply 24 V AC/DC
Coating (*4)
English, German, French, and Spanish can be displayed as the guide display.
The /LP option can be specified in the combination of Type 2 code (any of "0" or "1") and
Type 3 code (any of "0" or "1".)
The /HA option can be specified when the Type 1 code is "-0" or "-2."
When the /CT option is specified, the UT35A does not conform to the safety standards (UL
and CSA) and CE marking.
IM 05P01D31-01EN
Optional
suffix
code
Suffix code
UT32A
Type 1:
Basic
control
-0
-1
-2
Type 2:
Functions
Type 3:
Open networks
0
1
2
0
Case color
Fixed code
Description
Digital Indicating Controller (provided with retransmission output or 15 V DC
loop power supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC)
Standard type
Position proportional type
Heating/cooling type
None
RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire)
2 additional DIs and 2 additional DOs
None
-1
-2
-3
-4
0
1
IM 05P01D31-01EN
[Style:S3]
-00
/LP
/HA
/DC
/CT
English
German
French
Spanish
White (Light gray)
Black (Light charcoal gray)
Always "-00"
24 V DC loop power supply (*2)
Heater break alarm (*3)
Power supply 24 V AC/DC
Coating (*4)
English, German, French, and Spanish can be displayed as the guide display.
The /LP option can be specified in the combination of Type 1 code (any of "-0" or "-1")
and Type 2 code (any of "0" or "1.") Additionally, when the Type 2 code is "1", the RS-485
communication is 2-wire system.
The /HA option can be specified when the Type 1 code is "-0" or "-2."
When the /CT option is specified, the UT32A does not conform to the safety standards (UL
and CSA) and CE marking.
vii
Optional
suffix
code
Suffix code
UT35A
Fixed code
-NNN
-1
-2
-3
-4
Case color
0
1
viii
-A
-R
-U
-T
-P
A
R
U
N
/RT
/HA
/X1
/Y1
/W1
/CH3
/CC3
/PD3
/DN3
/ET3
/L4
/X4
/Y4
/W4
/DC
/CT
[Style:S3]
Description
Digital Indicating Controller (provided with 2 DIs, and 3 DOs) (Power
supply: 100-240 V AC)
Always "-NNN
English
German
French
Spanish
White (Light gray)
Black (Light charcoal gray)
Analog output (current/voltage pulse)
Relay output (c-contact)
Universal output (current/voltage pulse/relay)
Triac output
Position proportional output
Analog output (current/voltage pulse)
Relay output (a-contact)
Universal output (current/voltage pulse/relay)
None
Retransmission output or 15 V DC power supply
Heater break alarm
5 additional DIs
5 additional DOs
2 additional DIs and 2 additional DOs
RS485 communication (Max. 38.4 kbps, 2-wire/4-wire)
CC-Link communication (with Modbus master function)
PROFIBUS-DP communication (with Modbus master function)
DeviceNet communication (with Modbus master function)
Ethernet communication (with serial gateway function)
24 V DC loop power supply
5 additional DIs
5 additional DOs
2 additional DIs and 2 additional DOs
Power supply 24 V AC/DC
Coating
English, German, French, and Spanish can be displayed as the guide display.
For heating/cooling output, both Output 1 and Output 2 should be specified. Not available
when Output 2 is N. For position proportional output, specify -P for Output 1 and N for
Output 2.
When the code for Output 1 is "-R" or "-U" and Output 2 is "R" or "U", Output 1 is changed
from the contact point c to the contact point a. When the code for Output 1 is specified to
"-T", only "A" or "N" is available for Output 2.
The /RT option can be specified only when the code for Output 2 is R or N.
The /HA option can be specified in the combination of Output 1 and Output 2 codes except for
-PN.
Only one option is available for each terminal area of E1, E2 and E4.
The /L4 option for E4 terminal area can be specified only when the E3 terminal area option is
not specified or specified /CH3.
When the /CT option is specified, the UT35A does not conform to the safety standards (UL
and CSA) and CE marking.
IM 05P01D31-01EN
Optional
suffix
code
Suffix code
UT32A
Fixed code
-NNN
-1
-2
-3
-4
Case color
0
1
-A
-R
-U
-T
-P
A
R
U
N
Power supply
Additional treatment (*8)
*1:
*2:
*3:
*4:
*5:
*6:
*7:
*8:
/RT
/HA
/L1
/CH1
/LCH1
/X1
/Y1
/W1
/DC
/CT
[Style:S3]
Description
Digital Indicating Controller (provided with 2 DIs, and 3 DOs) (Power supply:
100-240 V AC)
Always "-NNN
English
German
French
Spanish
White (Light gray)
Black (Light charcoal gray)
Analog output (current/voltage pulse)
Relay output (c-contact)
Universal output (current/voltage pulse/relay)
Triac output
Position proportional output
Analog output (current/voltage pulse)
Relay output (a-contact)
Universal output (current/voltage pulse/relay)
None
Retransmission output or 15 V DC power supply
Heater break alarm
24 V DC loop power supply
RS485 communication (Max. 38.4 kbps, 2-wire/4-wire)
24 V DC loop power supply and RS485 communication (Max. 38.4 kbps, 2-wire)
5 additional DIs
5 additional DOs
2 additional DIs and 2 additional DOs
Power supply 24 V AC/DC
Coating
English, German, French, and Spanish can be displayed as the guide display.
For heating/cooling output, both Output 1 and Output 2 should be specified. Not available
when Output 2 is N. For position proportional output, specify -P for Output 1 and N for
Output 2.
When the code for Output 1 is "-R" or "-U" and Output 2 is "R" or "U", Output 1 is changed
from the contact point c to the contact point a. When the code for Output 1 is specified to
"-T", only "A" or "N" is available for Output 2.
The /RT option can be specified only when the code for Output 2 is R or N.
The /HA option can be specified in the combination of Output 1 and Output 2 codes except for
-PN.
Only one option is available for E1 terminal area.
The /L1 or /LCH1 option can be specified only when the code for Output 2 is N.
When the /CT option is specified, the UT32A does not conform to the safety standards (UL
and CSA) and CE marking.
Coating Treatment
(1) HumiSeal coating treatment
Apply HumiSeal coating to the printed circuit board assembly.
Do not apply HumiSeal coating to the following parts: connector, gold-plated contact
area, relay part, RJC device, and in the vicinity of the push switch/LED lamp.
(2) Apply terminal coating to the gold-plated contact area on the printed circuit board.
Notes
There are two treatments as described above, but we do not guarantee their
effectiveness.
We do not supply any test data on these treatments.
Do not apply any treatment to the screw terminal area on the back side of the
instrument.
IM 05P01D31-01EN
ix
Accessories
The product is provided with the following accessories according to the model and suffix
codes. Check that none of them are missing or damaged.
1
No.
Product Name
Quantity
Remark
Brackets
Unit label
Tag label
Operation Guide
Suffix code
-00
Description
Parameter Setting Software
Terminal cover
For UT35A, Model: UTAP001
For UT32A, Model: UTAP002
For UT35A
For UT32A
Brackets
Part number L4502TP (2 pieces for fixing the upper and lower parts)
Users Manual (A4 size)
* Users Manual can be downloaded from a website.
Users Manual (CD-ROM), Model: UTAP003
* Contains all manuals.
IM 05P01D31-01EN
WARNING
Calls attention to actions or conditions that could cause serious or fatal injury to the user,
and indicates precautions that should be taken to prevent such occurrences.
CAUTION
Calls attention to actions or conditions that could cause injury to the user or damage to
the instrument or property and indicates precautions that should be taken to prevent such
occurrences.
Note
IM 05P01D31-01EN
xi
For the ladder sequence and communication functions, see the respective manuals. This
users manual is organized into Chapters 1 to 19 as shown below. This manual mainly
uses the illustrations of the UT35A for describing the operations and functions. The basic
operations are the same for the UT32A, so please read them in the same way.
Chapter
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
xii
IM 05P01D31-01EN
Contents
2
Introduction.............................................................................................................................i
Target Readers.......................................................................................................................i
Notice .................................................................................................................................i
Trademarks........................................................................................................................... ii
Safety Precautions................................................................................................................ ii
Handling Precautions for the Main Unit................................................................................ iv
Waste Electrical and Electronic Equipment (WEEE), Directive 2002/96/EC........................ iv
Checking the Contents of the Package.................................................................................v
Model and Suffix Codes of UT35A (for Standard model)..................................................... vi
Model and Suffix Codes of UT32A (for Standard model).................................................... vii
Model and Suffix Codes of UT35A (for Detailed model)..................................................... viii
Model and Suffix Codes of UT32A (for Detailed model)....................................................... ix
Symbols Used in This Manual.............................................................................................. xi
How to Use This Manual..................................................................................................... xii
6.2
IM 05P01D31-01EN
5
6
7
8
9
10
11
12
13
14
15
16
17
19
App
18
xiii
Index
Contents
6.3
6.4
6.5
6.6
6.7
6.8
6.9
7.1.5
8.2
8.3
8.4
8.5
8.6
8.7
8.8
xiv
Contents
9.3
9.4
9.5
9.6
12.2
IM 05P01D31-01EN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
App
Index
Contents
13.2
13.3
13.4
16.2
16.3
16.4
Troubleshooting............................................................................................................... 16-1
16.1.1 Troubleshooting Flowchart................................................................................. 16-1
16.1.2 Errors at Power On............................................................................................ 16-2
16.1.3 Errors during Operation..................................................................................... 16-4
Maintenance.................................................................................................................. 16-15
16.2.1 Cleaning........................................................................................................... 16-15
16.2.2 Packaging when Shipping the Product for Repair........................................... 16-15
16.2.3 Replacing Parts............................................................................................... 16-15
Periodic Maintenance . ................................................................................................. 16-16
Disposal......................................................................................................................... 16-17
xvi
Contents
17.5
17.4.3 Control Output (Relay, Triac, Current, and Voltage Pulse) Wiring..................... 17-8
17.4.4 Valve Position Output and Feedback Input Wiring.......................................... 17-10
17.4.5 Contact Input Wiring.........................................................................................17-11
17.4.6 Contact Output Wiring..................................................................................... 17-13
17.4.7 Retransmission Output Wiring ........................................................................ 17-15
17.4.8 15 V DC Loop Power Supply Wiring................................................................ 17-15
17.4.9 24 V DC Loop Power Supply Wiring................................................................ 17-15
17.4.10 Heater Break Alarm Wiring.............................................................................. 17-16
17.4.11 RS-485 Communication Interface Wiring........................................................ 17-17
17.4.12 Coordinated Operation Wiring......................................................................... 17-19
17.4.13 Peer-to peer Communication Wiring................................................................ 17-21
17.4.14 Ethernet Communication Interface Wiring....................................................... 17-23
17.4.15 PROFIBUS-DP Communication Interface Wiring............................................ 17-25
17.4.16 DeviceNet Communication Interface Wiring.................................................... 17-27
17.4.17 CC-Link Communication Interface Wiring........................................................ 17-29
17.4.18 Power Supply Wiring....................................................................................... 17-31
Attaching and Detaching Terminal Cover...................................................................... 17-32
Chapter 18 Parameters
18.1
18.2
Chapter 19 Specifications
19.1
Revision Information
IM 05P01D31-01EN
xvii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
App
Index
Blank Page
1.1
Buy and
Unpacking
Installation
and Wiring
Setup
Operation
IM 05P01D31-01EN
1-1
Introduction to Functions
The Quick setting function is a function to easily set the basic function of the controller.
1.2
Input/Output Function
PV Input (equipped as standard)
PV input is a universal input to arbitrarily set the type and range for the thermocouple (TC),
resistance-temperature detector (RTD), and DC voltage/current.
Chapter 7 Input (PV) Functions
TC
mV
V
mA
Current
Voltage pulse
RTD
Relay contact / Triac
2-wire
transmitter
Motor-operated valve
Control output (OUT) is a universal output to arbitrarily set the type for the current,
voltage pulse, and relay/triac. Heating/cooling control and Position proportional control
are possible by specifying the suffix code for the control.
Position proportional control is used exclusively for the motor-operated valve.
Heating/cooling control is for two output type of heat and cool.
Chapter 10 Output (Control and Retransmission) Functions
TC
mV
V
mA
Current
Voltage pulse
RTD
Relay contact / Triac
2-wire
transmitter
Motor-operated valve
Retransmission Output
Retransmission output outputs a PV input value (PV), target setpoint (SP), control output
value (OUT) and the like as an analog signal to, for example, the recorder.
Chapter 10 Output (Control and Retransmission) Functions
External device such as recorder etc.
UT35A/UT32A
Current
1-2
IM 05P01D31-01EN
Contact Input
Contact Output
Up to 13 contact outputs can be incorporated. Contact output can output events such as
alarms.
PID control and sequence control can be performed simultaneously using the ladder
sequence function.
For details, see the table of Model and Suffix Codes.
Chapter 11 Alarm Functions
UT35A/UT32A
2-wire transmitter
IM 05P01D31-01EN
1-3
Introduction to Functions
1.3
Control Functions
PID Control
PID control is a general control using the PID control-related parameters.
8.2.1 PID Control
Recorder
UT35A/UT32A
Alarms
Retransmission
output
TC
4-20 mA DC
Electric
furnace
SCR
Thyristor
Heating/cooling Control
Heating/cooling control is available only for Heating/cooling type.
In Heating/cooling control, the controller outputs the result of control computation after
splitting it into heating-purpose and cooling-purpose signals.
8.2.3 Heating/cooling Control
UT35A/UT32A
Cooling (relay signal)
Cooling
water
Heating
(4-20 mA DC signal)
Heating unit
PV
SCR
Thyristor
TC
1-4
IM 05P01D31-01EN
Introduction to Functions
Position proportional control is available only for Position proportional type. It is used
exclusively for the motor-operated valve.
10.14 Adjusting Motor-operated Valve Position (Position Proportional Output)
UT35A/UT32A
H (direct) or L (reverse)
contact signal
Control motor
Position signal
TC
Air
Motor-operated valve
Furnace
Gas
Burner
Hysteresis
Hysteresis
ON
OFF
Main SP
Initial value: Reverse
IM 05P01D31-01EN
Sub-SP
Initial value: Direct
(offset from main SP)
PV
1-5
1.4
Abnormal
Guide Display
The guide is displayed on PV display when setting parameters. This guide can be turned
on/off with the Fn key.
The scrolling guide is displayed
when setting parameters.
1-6
IM 05P01D31-01EN
1.5
Introduction to Functions
To use the ladder sequence function, it is necessary to create a ladder program using
LL50A Parameter Setting Software and download it to a controller.
Ladder sequence function: LL50A Parameter Setting Software Users Manual
Ladder program
IM 05P01D31-01EN
1-7
1.6
Communication Functions
The UT35A/UT32A can use RS-485 communication, Ethernet communication,
PROFIBUS-DP communication, DeviceNet communication, and CC-Link communication
by specifying the suffix code and optional suffix code for each communication.
UTAdvanced Series Communication Interface (RS-485, Ethernet) Users Manual
UTAdvanced Series Communication Interface (Open Network) Users Manual
RS-485/
RS-232C
converter
Host computer
Hub
LAN
connnection
Ethernet
Modbus/TCP
1-8
IM 05P01D31-01EN
PROFIBUS-DP Communication
PLC
PROFIBUS-DP Master
PROFIBUS-DP communication
PROFIBUS-DP Slave / Modbus Master
Modbus/RTU communication
Max. 1200 m, number of connected slaves: 31
Modbus Slave
Modbus Slave
Modbus Slave
Modbus Slave
DeviceNet Communication
The UT35A can be used as the slave devices for DeviceNet communication. Read-out of
PV, operation or alarm status, and SP setting can be done by accessing the remote I/O
on the master unit of DeviceNet.
PLC
DeviceNet Master
DeviceNet communication
DeviceNet Slave / Modbus Master
Modbus/RTU communication
Max. 1200 m, number of connected slaves: 31
Modbus Slave
IM 05P01D31-01EN
Modbus Slave
Modbus Slave
Modbus Slave
1-9
Introduction to Functions
The UT35A can be used as the slave devices for PROFIBUS-DP communication. Readout of PV, operation or alarm status, and SP setting can be done by accessing the
remote I/O on the master unit of PROFIBUS-DP.
CC-Link Communication
The UT35A can be used as the slave devices for CC-Link communication. Read-out of
PV, operation or alarm status, and SP setting can be done by accessing the remote I/O
on the master unit of CC-Link.
PLC
CC-Link Master
CC-Link communication
CC-Link Slave / Modbus Master
Modbus/RTU communication
Max. 1200 m, number of connected slaves: 31
Modbus Slave
Modbus Slave
Modbus Slave
Modbus Slave
Peer-to-peer Communication
In Peer-to-peer communication, controllers send and receive process data each other
and share data. However, ladder program creation using LL50A Parameter Setting
Software is necessary.
Ladder program: LL50A Parameter Setting Software Users Manual
Controller No. 1 to 4 can transmit and receive data. Controller No. 5 to 32 can only receive data.
15
32
Max. 32 controllers
Coordinated Operation
A system of coordinated operation is configured with a master controller and a number of
slave controllers. The slave controllers are set to operate in the same way as the master
controller. Therefore you do not have to create a communication program.
Master
Master: UP or UT controller
Slave: UT controller only
Slave
1-10
Slave
Slave
Slave
IM 05P01D31-01EN
Light-loader Communication
Light-loader function: LL50A Parameter Setting Software Users Manual
To USB terminal
Dedicated cable
To USB terminal
Dedicated cable
CAUTION
When using the maintenance port, do not supply power to the controller. Otherwise, the
controller does not work normally.
If power is supplied to the controller while the cable is connected, or the cable is
connected to the controller already turned on, unplug the cable and turn on the controller
again. The controller returns to the normal condition.
IM 05P01D31-01EN
1-11
Introduction to Functions
Use the LL50A to set parameters and create ladder programs. Attach the adapter to the
front of the controller to communicate.
1.7
Engineering Units
Input range (scale): the PV range low limit is set to 0%, and the high limit is set to 100%
for conversion.
Input range (scale) span: the PV range span is set to 100% for conversion.
In this manual, the parameter setting range is described as the input range and input
range span. This means that engineering units are required to be set. Set a temperature
for temperature input.
The following describes a conversion example.
When the PV input range is 100 to 600C, 0% of the PV range is equivalent to 100C,
50% of the PV range is equivalent to 350C, and 100% of the PV range is equivalent to
600C.
100% of the PV range span is equivalent to 500C.
20% of the PV range span is equivalent to 100C.
Minimum value of PV input range
100C
350C
0% of PV input range
The above applies to the scale for voltage and current input.
1-12
IM 05P01D31-01EN
2.1
Installation
and Wiring
Power ON
Use
Quick setting
function?
NO
YES
Section 8.2
Input setup
Section 7.1
Position
proportional
type?
NO
Other setup
IM 05P01D31-01EN
YES
YES
Position
proportional
type?
NO
Output setup
PID tuning
Operation
2-1
Blank Page
3.1
IM 05P01D31-01EN
3-1
(1) PV display
(2) Group display
UT32A
(1) PV display
(3) Symbol display
(4) Data display
(5) Bar-graph display
(6) Event indicator
(7) Key navigation indicator
3-2
IM 05P01D31-01EN
Name
PV display
(white or red)
(2)
Group display
(green)
(3)
Symbol display
(orange)
(4)
(5)
Bar-graph display
(orange)
(6)
Event indicator
(orange)
(7)
Key navigation
indicator
(green)
(8)
Parameter display
level indicator
(green)
EASY
Lit
Unlit
Unlit
PRO
Unlit
Unlit
Lit
Status indicator
(green and red)
Display
REM
STOP
MAN
IM 05P01D31-01EN
Description
Lit when in remote mode (REM).
Lit when in stop mode (STOP).
Lit when in manual mode (MAN).
Blinks during auto-tuning.
(10)
(11)
Ladder operation
indicator (green)
3-3
3
Part Names
(1)
Description
Displays PV.
Displays an error code if an error occurs.
Displays the scrolling guide in the Menu Display and
Parameter Setting Display when the guide display ON/
OFF is set to ON.
Displays a group number (1 to 4, or R) and terminal area
(E1 to E4).
1 to 4 represent SP numbers in the Operation Display.
R and E1 to E4 are displayed in the Parameter Setting
Display.
3.2
UT32A
3-4
IM 05P01D31-01EN
(1)
(2)
UT35A: PARAMETER
key
UT32A: PARA key
(3)
SET/ENTER key
Up/Down/ Left/Right
arrow keys
(4)
Light-loader interface
(5)
A/M key
(6)
Description
Used to switch the Operation Displays.
Press the key in the Operation Display to switch the
provided Operation Displays.
Press the key in the Menu Display or Parameter Setting
Display to return to the Operation Display.
Hold down the key for 3 seconds to move to the Operation
Parameter Setting Display.
Hold down the key and the Left arrow key simultaneously
for 3 seconds to move to the Setup Parameter Setting
Display.
Press the key in the Parameter Setting Display to return
to the Menu Display. Press the key once to cancel the
parameter setting (setpoint is blinking).
SET/ENTER key
Press the key in the Menu Display to move to the
Parameter Setting Display of the Menu. Press the key in
the Parameter Setting Display to transfer to the parameter
setting mode (setpoint is blinking), and the parameter can
be changed. Press the key during parameter setting mode
to register the setpoint.
Up/Down/Left/Right arrow keys
Press the Left/Right arrow keys in the Menu Display to
switch the Displays.
Press the Up/Down/Left/Right arrow keys in the Parameter
Setting Display to switch the Displays.
Press the Up/Down arrow keys during parameter setting
mode (setpoint is blinking) to change a setpoint.
Press the Left/Right arrow keys during parameter setting
mode (setpoint is blinking) to move between digits
according to the parameter.
It is the communication interface to the adapter cable
when setting and storing parameters via PC. The LL50A
Parameter Setting Software (sold separately) is required.
Used to switch between AUTO and MAN modes.
The setting is switched between AUTO and MAN each
time the key is pressed. The user can assign a function
key.
The UT35A has F1, F2, and Fn keys.
The UT32A has only the Fn key. The user can assign a
function to the key. The function is set by the parameter.
3-5
3
Part Names
IM 05P01D31-01EN
Name
Maintenance port
Upper surface
Upper surface
UT32A
UT35A
CAUTION
When using the maintenance port, do not supply power to the controller. Otherwise, the
controller does not work normally.
If power is supplied to the controller while the cable is connected, or the cable is
connected to the controller already turned on, unplug the cable and turn on the controller
again. The controller returns to the normal condition.
3-6
IM 05P01D31-01EN
3.3
Part Names
c (lower-case)
IM 05P01D31-01EN
3-7
X
None
3-8
Space
IM 05P01D31-01EN
3.4
Setting Details
Parameter
symbol
A1 to A4
Name
Alarm-1 to -4
setpoint
Display
level
EASY
Setting range
Menu symbol
(1) Parameter symbol: Symbol displayed on Symbol display on the front panel.
(2) Name: Parameter name
(3) Display level: Indicates the parameter display level.
(4) Setting range: Parameter setting range
(5) Menu symbol: Indicates the menu to which the parameter belongs.
: Operation parameter
: Setup parameter
Parameter Display Level
Display level
EASY
STD
PRO
Description
Note
For more intelligible display operation of parameters and the references, see Chapter 18,
"Parameter Map."
IM 05P01D31-01EN
3-9
Part Names
(Display Example)
Blank Page
4.1
Power ON
Operation Display
OUT Display
Same as *1.
END Display
SP Menu Display
SP Display
END Display
END Display
END Display
IM 05P01D31-01EN
END Display
END Display
END Display
4-1
4
Basic Operation
The following shows the transition of Operation Display, Operation Parameter Setting
Display, and Setup Parameter Setting Display.
The Operation Parameter Setting Display has the parameters for setting the functions
necessary for the operation.
The Setup Parameter Setting Display has the parameters for setting the basic functions
of the controller.
Description
The Menu Display is segmented by the function and optional terminal position.
The scrolling guide for the menu is displayed on PV display. The guide display
can be turned on/off with the Fn key.
Menu Display of Operation Parameter
Menu Display
OPE.M is displayed.
Menu symbol is displayed.
Group number or Terminal area is displayed.
SET.M is displayed.
Menu symbol is displayed.
Group number or Terminal area is displayed.
Setpoint is displayed.
Parameter symbol is displayed.
Group number or Terminal area is displayed.
4-2
IM 05P01D31-01EN
+
Hold down the keys
for 3 seconds.
IM 05P01D31-01EN
4-3
Basic Operation
END is displayed.
4.2
Operation
1. Hold down the PARAMETER key for 3 seconds in the Operation Display to call up
the [MODE] Menu Display.
2. Press the Right arrow key to display the [SP] Menu Display.
3. Press the SET/ENTER key to display the [SP] Parameter Setting Display.
4. Press the Down arrow key to display the [A1] Parameter Setting Display.
4-4
IM 05P01D31-01EN
4
Basic Operation
(Change the setpoint using the Up/Down arrow keys to increase and decrease
the value and the Left/Right arrow keys to move between digits.)
7. Press the SET/ENTER key to register the setpoint (the setpoint stops blinking).
8. Press the PARAMETER key once to return to the Menu Display. Press the
DISPLAY key once to return to the Operation Display.
IM 05P01D31-01EN
4-5
3. Press the Left arrow key to move one digit to the left.
(Press the Right arrow key to move one digit to the right.)
4-6
IM 05P01D31-01EN
4
1.
2.
3.
4.
5.
IM 05P01D31-01EN
Basic Operation
4-7
Blank Page
5.1
Description
The Quick setting function is a function to easily set the basic function of the controller.
The Quick setting function starts when the power is turned on after wiring.
The following lists the items to set using the Quick setting function.
(1) Control type (PID control, Heating/cooling control, etc.)
(2) Input function (PV input, range, scale (at voltage/current input), etc.)
(3) Output function (control output type and cycle time)
IM 05P01D31-01EN
5-1
NO
Select YES.
Press the SET/ENTER key.
The Quick setting function is started.
The parameter CNT (control type)
is displayed first.
Setting Method
(1) Press the Up or Down arrow key to
display a parameter to set.
(2) Press the SET/ENTER key.
(The setpoint blinks).
(3) Press the UP or Down arrow key to
change a setpoit.
(4) Press the SET/ENTER key to
register the setpoint.
(The setpoint stops blinkng.)
Select NO.
Press the SET/ENTER key.
Operation Display
PV is displayed.
SP is displayed.
5-2
IM 05P01D31-01EN
5
Quick Setting Function
CNT
Name
Control type
Display
level
EASY
Setting range
Menu symbol
IM 05P01D31-01EN
5-3
Name
Display
level
IN
PV input type
EASY
UNIT
PV input unit
EASY
RH
Maximum value of
PV input range
EASY
RL
Minimum value of
PV input range
EASY
Setting range
Menu symbol
OFF: Disable
K1: -270.0 to 1370.0 C / -450.0 to 2500.0 F
K2: -270.0 to 1000.0 C / -450.0 to 2300.0 F
K3: -200.0 to 500.0 C / -200.0 to 1000.0 F
J: -200.0 to 1200.0 C / -300.0 to 2300.0 F
T1: -270.0 to 400.0 C / -450.0 to 750.0 F
T2: 0.0 to 400.0 C / -200.0 to 750.0 F
B: 0.0 to 1800.0 C / 32 to 3300 F
S: 0.0 to 1700.0 C / 32 to 3100 F
R: 0.0 to 1700.0 C / 32 to 3100 F
N: -200.0 to 1300.0 C / -300.0 to 2400.0 F
E: -270.0 to 1000.0 C / -450.0 to 1800.0 F
L: -200.0 to 900.0 C / -300.0 to 1600.0 F
U1: -200.0 to 400.0 C / -300.0 to 750.0 F
U2: 0.0 to 400.0 C / -200.0 to 1000.0 F
W: 0.0 to 2300.0 C / 32 to 4200 F
PL2: 0.0 to 1390.0 C / 32.0 to 2500.0 F
P2040: 0.0 to 1900.0 C / 32 to 3400 F
WRE: 0.0 to 2000.0 C / 32 to 3600 F
JPT1: -200.0 to 500.0 C / -300.0 to 1000.0 F
JPT2: -150.0 to 150.0 C / -200.0 to 300.0 F
PT1: -200.0 to 850.0 C / -300.0 to 1560.0 F
PT2: -200.0 to 500.0 C / -300.0 to 1000.0 F
PT3: -150.00 to 150.00 C / -200.0 to 300.0 F
0.4-2V: 0.400 to 2.000 V
1-5V: 1.000 to 5.000 V
PV
4-20: 4.00 to 20.00 mA
0-2V: 0.000 to 2.000 V
0-10V: 0.00 to 10.00 V
0-20 : 0.00 to 20.00 mA
-1020: -10.00 to 20.00 mV
0-100: 0.0 to 100.0 mV
-: No unit
C: Degree Celsius
-: No unit
- -: No unit
- - -: No unit
F: Degree Fahrenheit
Depends on the input type.
- For temperature input Set the temperature range that
is actually controlled. (RL<RH)
- For voltage / current input Set the range of a voltage /
current signal that is applied.
The scale across which the
voltage / current signal is actually
controlled should be set using
the maximum value of input
scale (SH) and minimum value
of input scale (SL). (Input is
always 0% when RL=RH.)
5-4
IM 05P01D31-01EN
SH
SL
Name
PV input scale
decimal point
position
Maximum value of
PV input scale
Minimum value of
PV input scale
Display
level
EASY
EASY
EASY
Setting range
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Menu symbol
PV
Output Function
Parameter
symbol
OT
CT
CTc
Name
Display
level
EASY
EASY
Setting range
Menu symbol
0.5 to 1000.0 s
EASY
IM 05P01D31-01EN
5-5
5.2
CAUTION
The parameters related to the range or scale are initialized if the PV input type is
changed.
Setting Details
Parameter
symbol
IN
QSM
5-6
Name
PV input type
Quick setting mode
Display
level
Setting range
Menu symbol
EASY
OFF: Disable
PV
EASY
OFF: Disable
ON: Enable
SYS
IM 05P01D31-01EN
6.1
6.1.1
Standard Type
SP Display (SP can be changed.)
6
Monitoring and Control of Regular Operations
SELECT Displays 1 to 5
(Displayed only when SELECT Display is registered.
(The figure on the left is the example of
the parameter A1 (alarm-1 setpoint).)
IM 05P01D31-01EN
6-1
SELECT Displays 1 to 5
(Displayed only when SELECT Display is registered.)
(The figure on the left is the example of
the parameter A1 (alarm-1 setpoint).)
6-2
IM 05P01D31-01EN
SELECT Displays 1 to 5
(Displayed only when SELECT Display is registered.)
(The figure on the left is the example of
the parameter A1 (alarm-1 setpoint).)
IM 05P01D31-01EN
6-3
RMS=PROG
SELECT Displays 1 to 5
(Displayed only when SELECT Display is registered.)
(The figure on the left is the example of the parameter A1 (alarm-1
setpoint)).
6-4
IM 05P01D31-01EN
6
Display and operation description
PV display: Displays measured input value (PV).
Setpoint display: Displays and changes target setpoint (SP).
Symbol
Target setpoint
SP Display
Symbol
Remote setpoint
IM 05P01D31-01EN
6-5
Operation Display
Symbol
Control output
Control output
OUT Display
(Valve Position
Display)
Symbol
Preset output
Symbol
Preset output
6-6
IM 05P01D31-01EN
Heating-side
control output
Symbol of
heating side
When the control output value is less than 100%, one digit is displayed
to the right of the decimal point. When the control output value is equal
to or more than 100%, no digits are displayed to the right of the decimal
point.
The display is switched to the Heating/cooling OUT Display if the
operation mode is switched to MAN when other Operation Display is
shown.
An interruption is displayed while auto-tuning is performed.
Heating/cooling
OUT Display
Heating-side
preset output
Symbol of STOP
Cooling-side preset output
Cooling-side symbol
Target setpoint (SP) number
Heating-side or cooling-side preset output value is displayed in STOP
mode.
Preset output values cannot be changed by OUT change operation.
PV display: Displays measured input value (PV).
Setpoint display: Displays PID number currently being used.
PID Number
Display
Symbol
PID number
IM 05P01D31-01EN
6-7
Analog Input
Display
Symbol
PV input
Position
Proportional
Computation
Output Display
Symbol
Target setpoint (SP) number
Internal
computed value
Can be changed in MAN mode. The valve opens or closes so that the
valves feedback input value reaches the setpoint.
PV display: Displays measured input value (PV).
Setpoint display: Displays measured heater current.
Symbol
Target setpoint (SP) number
SELECT Display
Symbol
Alarm setpoint
6-8
IM 05P01D31-01EN
6.2
2.
3.
Press the Left arrow key to move one digit to the left.
(Press the Right arrow key to move one digit to the right.)
4.
5.
IM 05P01D31-01EN
6-9
1.
seconds (to [MODE] Menu Display) > Right arrow key (to [SP]
Menu Display ) > SET/ENTER key (The setting parameter is
displayed.)
Press the Right arrow key until the [SP] Menu Display appears.
In the Setting Display for the target setpoint parameter,
pressing the Left or Right arrow keys changes the group. (The
group number is displayed on Group display.)
Setting Details
Parameter
symbol
Name
Display
level
SP
Target setpoint
EASY
SPGR.
Number of SP
groups
STD
Setting range
Menu symbol
SP
1 to 4
CTL
Note1: If the SP limiter is set, the setting can be made within the range of the SP limiter.
Description
The controller has four target setpoints (SP).
SP limiter: 9.1 Setting SP Limiter
SELECT parameter: 13.1.5 Registering SELECT Parameter Display (Up to 10 Displays)
6-10
IM 05P01D31-01EN
6.3
Setting Display
Operation Mode Setting Display Operation Display > PARAMETER or PARA key for 3 seconds
Parameter
symbol
Name
Display
level
AT
AUTO-tuning
switch
EASY
AT.BS
SP bias in autotuning
PRO
Setting range
Menu symbol
OFF: Disable
1: Perform auto-tuning. Tuning
result is stored in the PID of
group 1.
2: Perform auto-tuning. Tuning
result is stored in the PID of
group 2.
3: Perform auto-tuning. Tuning
MODE
result is stored in the PID of
group 3.
4: Perform auto-tuning. Tuning
result is stored in the PID of
group 4.
R: Tuning result is stored in the PID
for reference deviation.
-100.0 to 100.0% of PV input range
TUNE
span (EUS)
CAUTION
Set the operation mode to AUTO and RUN to perform auto-tuning.
Lamp Status
Status
During auto-tuning
IM 05P01D31-01EN
STOP lamp
MAN lamp
Unlit
Blinking
6-11
Setting Details
CAUTION
Do not perform auto-tuning for the following processes.
Tune PID manually.
Processes with fast response such as flow rate control and pressure control.
Processes which do not allow the output to be turned on and off even
temporarily.
Processes which prohibit output changes at control valves (or other actuators).
Processes in which product quality can be adversely affected if PV values
fluctuate beyond their allowable ranges.
Auto-tuning in progress
MAN lamp blinkng
SP
Temperature
ON
Control
output
OFF
ON/OFF control
AT = Started
Time
There is a hysteresis of 0.25% of the input range above and below SP.
Control
output
ON
OFF
ON/OFF control
AT = Started
6-12
SP bias in auto-tuning
(negative setpoint)
Time
There is a hysteresis of 0.25% of the input range above and below SP.
IM 05P01D31-01EN
AT setpoint
Tuning point
Local
1 to 4, R
Remote
1 to 4, R
Remote setpoint
Storage location
When the setpoint of AT is R, the AT result is stored in the PID group for reference
deviation.
When performing auto-tuning in AT setpoint "R", set the parameter ZON to other than 0
and 3, and set the parameter RDV to other than 0.
Auto-tuning cannot be performed when the control type (CNT) is as follows.
ON/OFF control (1 point of hysteresis)
ON/OFF control (2 points of hysteresis)
Two-position two-level control
Sample PI control
In addition, auto-tuning cannot be performed in the following cases (no error indication).
Input error occurs. (Input burnout, ADC error, etc.)
The operation mode is STOP.
The operation mode is MAN.
Output limiter setpoint at auto-tuning: AT.OLAT.OH
Start and Stop of Auto-tuning
Start and stop of auto-tuning can be set by parameter setting, communication, or contact
input.
Auto-tuning is stopped in the following cases.
Switch to MAN
Switch to STOP
The parameter AT is set to OFF.
Power failure
Auto-tuning is not finished even after the time-out detection time is elapsed.
The time-out detection time is about 24 hours.
When the auto-tuning error occurs, the error code is shown in the Operation Display.
Press any key to erase it.
Auto-tuning time output limiter: 8.8 Adjusting Auto-tuning Operation
IM 05P01D31-01EN
6-13
6
Monitoring and Control of Regular Operations
6.4
Setting Display
Parameter Setting Display Operation Display > PARAMETER or PARA key for 3
seconds (to [MODE] Menu Display) > Right arrow key (to [PID]
Menu Display ) > SET/ENTER key (The setting parameter
is displayed.) > Down arrow key (The setting parameter is
displayed.)
In the Setting Display for the PID parameters, Displays can
be arbitrarily switched using the Up, Down, Left or Right arrow
key. Pressing the Left or Right arrow key changes the group.
(The group number is displayed on Group display.)
Setting Details
Parameter
symbol
Name
Proportional band
Heating-side
proportional band
(in Heating/cooling
control)
Integral time
Heating-side
integral time (in
Heating/cooling
control)
Derivative time
Heating-side
derivative time (in
Heating/cooling
control)
Cooling-side
proportional band
Pc
Ic
Dc
PIDN
PIDG.
Cooling-side
integral time
Cooling-side
derivative time
PID number
selection
Number of PID
groups
Display
level
Setting range
EASY
0.0 to 999.9%
When 0.0% is set, it operates as
0.1%.
Heating-side ON/OFF control
applies when 0.0% in Heating/
cooling control
EASY
OFF: Disable
1 to 6000 s
EASY
OFF: Disable
1 to 6000 s
EASY
EASY
EASY
Menu symbol
PID
0.0 to 999.9%
Cooling-side ON/OFF control
applies when 0.0% in Heating/
cooling control
OFF: Disable
1 to 6000 s
OFF: Disable
1 to 6000 s
EASY
1 to 4
SP
STD
1 to 4
CTL
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
6-14
IM 05P01D31-01EN
SP
1 to 4
SP
1 to 4
SP
1 to 4
SP
1 to 4
IM 05P01D31-01EN
6-15
0%
Deviation
P = 100%
P = 50%
P = 0%
(ON/OFF)
SP
SP
Output (%)
Output (%)
100%
SP
Output (%)
(Example of
reverse action)
Deviation
Proportional band
Total span
Output = 100 e
P
Deviation
P: Proportional band
e: Deviation
Temperature
Offset
Time
6-16
IM 05P01D31-01EN
e+
1
T1
e : Deviation
TI : Integral time
edt
Output =
Deviation
P = 100%
Small integral time
Output (%)
(On-time ratio)
Output change due to P action
Integral
time
Time
Temperature
SP
Time
Use the manual reset (MR) to cancel an offset when the integral action is disabled.
Manual reset: 10.8 Canceling Offset of PV and SP (Manual Reset)
IM 05P01D31-01EN
6-17
e + TD d e
dt
e : Deviation
TD: Derivative time
Deviation
P = 100%
Output (%)
(On-time ratio)
Large
derivative time
Small
derivative time
Derivative
time
Time
Temperature
SP
Time
6-18
IM 05P01D31-01EN
Reference Values for Manual Tuning of Temperature, Pressure, and Flow Rate
Flow rate
Temperature
(electric
furnace)
IM 05P01D31-01EN
100 to 300%
200%
5 to 30 s
15 s
OFF
OFF
100 to 240%
150%
8 to 30 s
20 s
OFF
OFF
1 to 20%
5%
180 to 600 s
240 s
1/4 to 1/6 of I
60 s
Pressure
Setting range
(reference)
6-19
6.5
Setting Display
Parameter Setting Display Operation Display > PARAMETER or PARA key for 3
seconds (to [MODE] Menu Display) > Right arrow key (to
[SP] Menu Display) > SET/ENTER key (The setting parameter
is displayed.) > Down arrow key (The setting parameter is
displayed.)
In the setting Display for the alarm parameters, Displays can
be arbitrarily switched using the Up, Down, Left or Right arrow
key. Pressing the Left or Right arrow key changes the group.
(The group number is displayed on Group display.)
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
A1 to A4
Alarm-1 to -4
setpoint
EASY
ALNO.
Number of alarms
PRO
1 to 4
CTL
Note:1 When the alarm setpoint parameter is displayed, the group number is shown on Group
display.
Note2: The initial value of the parameter ALNO. is 4. Four alarm setpoint parameters are displayed
for each SP group.
Description
Each alarm type has four alarm setpoints.
Specifying the SP number (SPNO) determines the alarm setpoint to be used.
Alarm-related parameter
Number of settings
Alarm type
4 (number of settings)
4 (number of settings)
Alarm hysteresis
4 (number of settings)
4 (number of settings)
Alarm setpoint
6-20
IM 05P01D31-01EN
6.6
Setting Display
Parameter Setting Display Operation Display > PARAMETER or PARA key for 3 seconds
Parameter
symbol
Name
SP number
selection
Number of SP
groups
SPNO.
SPGR.
Display
level
EASY
STD
Setting range
Menu symbol
MODE
1 to 4
CTL
Description
The SP number (SPNO) selection can be used when the parameter ZON (zone PID
selection) is set to SP group number selection.
SP Group Number Selection
The PID group which is set in the PID number selection (PIDN) of each SP group is
used.
SP number (SPNO)
SP
1 to 4
SP
1 to 4
SP
1 to 4
SP
1 to 4
IM 05P01D31-01EN
6-21
Setting Details
6.7
6.7.1
Description
AUTO/MAN switching can be performed by any of the following:
(1) A/M key
(2) Contact input (status or edge)
(3) Communication
(4) User function key
AUTO
MAN
When the contact input (status) is ON, operation cannot be performed by keystroke or
communication.
When the contact input is OFF, and the setting is switched by keystroke or
communication, the last switching operation is performed.
Switch by contact input: 12.1 Setting Contact Input Function
Switch by user function key: 13.2 Assigning Function to User Function Key and A/M key
Switch
AUTOMAN
MANAUTO
Output action
Holds the control output value from AUTO mode.
The control output value can be bump to the manual preset output value by the
setting of parameter MPO.
The output value can be changed in manual mode.
The control output value does not bump (bumpless). Does not work when
Integral time (I) = OFF.
Switch from AUTO to MAN, and MPON: 10.12.2 Setting Output Value When Switched to MAN
Mode (Manual Preset Output)
6-22
IM 05P01D31-01EN
IM 05P01D31-01EN
MAN lamp
Unlit
Lit
6-23
6.7.2
Setting Display
Operation Mode Setting Display Operation Display > PARAMETER or PARA key for
Setting Details
Parameter
symbol
S.R
Name
Display
level
STOP/RUN switch
EASY
Setting range
STOP: Stop mode
RUN: Run mode
Menu symbol
MODE
Description
STOP/RUN switching can be performed by any of the following:
(1) Contact input (status or edge)
(2) Parameter
(3) Communication
(4) User function key
STOP
RUN
When the STOP/RUN switch is set to the contact input (S/R0), switch by keystroke or
via communication is disabled. Disable the setting if the STOP/RUN switch parameter
(S/R) is assigned to the contact input.
When the contact input is OFF, and the setting is switched by parameter, communication,
or keystroke, the last switching operation is performed.
Switch by contact input: 12.1 Setting Contact Input Function
Switch by user function key: 13.2 Assigning Function to User Function Key and A/M key
Switch
RUNSTOP
STOPRUN
Output
Output action
Control output
Preset output
RUN STOP
STOP RUN
Preset output value: 10.12.1 Setting Output Value in STOP Mode (Preset Output)
6-24
IM 05P01D31-01EN
OUT Display
Sub-setting-side OUT Display in Two-position two-level control.
Operation Display in STOP and RUN Modes in Heating/cooling Control
In STOP mode in Heating/cooling control, the display is as follows. The cooling-side
preset output is displayed on the left of the symbol ST and heating-side preset output is
displayed on the right.
The display at operation start differs depending on AUTO or MAN mode.
SP Display is shown in AUTO mode and Heat/cool OUT Display is shown in MAN mode.
SP Display
Heat/cool OUT Display
Symbol C represents the cooling side and H represents the heating side.
Lamp Status
Status
Operation start (RUN)
Operation Stop (STOP)
IM 05P01D31-01EN
STOP lamp
Unlit
Lit
6-25
SP Display
6.7.3
Setting Display
Operation Mode Setting Display Operation Display > PARAMETER or PARA key for 3
Setting Details
Parameter
symbol
R.L
Name
REMOTE/LOCAL
switch
Display
level
EASY
Setting range
LCL: Local mode
REM: Remote mode
Menu symbol
MODE
Description
REMOTE/LOCAL switching can be performed by any of the following:
(1) Contact input (status or edge)
(2) Parameter
(3) Communication
(4) User function key
REMOTE
LOCAL
When the contact input (status) is ON, operation cannot be performed by parameter,
communication, or keystroke.
When the contact input is OFF, and the setting is switched by parameter, communication,
or keystroke, the last switching operation is performed.
The last switching operation is performed for all methods, when the action of contact
input is detected as rising edge.
Switch by contact input: 12.1 Setting Contact Input Function
Switch by user function key: 13.2 Assigning Function to User Function Key and A/M key
The PID group before switching from LOCAL to REMOTE is applied to the PID in remote
operation.
6-26
IM 05P01D31-01EN
SP action
LCLREM
REMLCL
The remote target setpoint bumps to the local target setpoint. Or forces the local
target setpoint to track the remote target setpoint.
Lamp Status
Status
Local (LCL)
Remote (REM)
REM lamp
Unlit
Lit
IM 05P01D31-01EN
6-27
6.8
Operation
Press the Up arrow key to increase
control output.
Press the Down arrow key to decrease
control output.
In Heating/cooling control,
press the Up arrow key to decrease cooling-side control output and to increase heating-side control output;
press the Down arrow key to increase cooling-side control output and to decrease heating-side control output.
Description
In MAN mode, the control output is manipulated by direct key operation. (The value
changed using the Up or Down arrow key is output as is.)
Manipulation of the control output is not possible in STOP mode (the STOP lamp is lit).
Output manipulation differs depending on the ON or OFF setting of the control output
limiter (OH, OL).
10.4 Disabling Output Limiter in MAN mode
OUT Display
Valve position is displayed in Position proportional control.
Sub-setting-side OUT Display in Two-position two-level control.
In Two-position two-level control, main setting-side output can be manipulated
individually. Control output limiter is disabled as well as a case of ON/OFF control.
Heating/cooling OUT Display
The heating/cooling control output is manipulated simultaneously on both the heating
and cooling sides.
In MAN mode, the display is as follows. The symbol C represents the cooling side, and
H the heating side. The value on the right of each symbol is the output value.
When the control output low limit is set to SD while the control output type is 4 to 20
mA, the control output value can be lowered down to 0 mA.
10.6 Reducing 4-20 mA Current Output to 0 mA (Tight Shut Function)
6-28
IM 05P01D31-01EN
6.9
Description
Alarm latch can be released by any of the following.
(1) User function key
(2) Communication
(3) Contact input
For the switching operation by using the above, the last switching operation is performed.
Release by user function key: 13.2 Assigning Function to User Function Key and A/M key
Release by contact input: 12.1 Setting Contact Input Function
Release via communication: UTAdvanced Series Communication Interface Users Manual
IM 05P01D31-01EN
6-29
6
Monitoring and Control of Regular Operations
Releasing the alarm latch function releases all of the latched alarm outputs.
By factory default, the function is not assigned to the user function key and contact input.
Assign and use the function in accordance with the reference sections below.
Blank Page
7.1
7.1.1
Description
The figure below describes the case of PV input.
Example of Temperature Input
The figure below is an example of setting Type K thermocouple and a measurement
range of 0.0 to 800.0 C.
-270.0C
1370.0C
Input type
Set a range to be
controlled.
PV input range
RL = 0.0C
RH = 800.0C
2V
4V
Input type
RL = 1.000
RL = 2.000
RH = 5.000
PV input range
RH = 4.000
PV input scale
SL = 0.0 m/h
Minimum value of PV input scale
5 V (input signal)
Set a range to be
controlled.
SH = 50.0 m/h
Maximum value of PV input scale
When using 1-5 V DC signal as is, set RH = 5.000 V, RL = 1.000 V, SDP=1, and SH =
50.0, and SL=0.0.
IM 05P01D31-01EN
7-1
Name
Display
level
IN
PV input type
EASY
UNIT
PV input unit
EASY
RH
(Physical
quantity)
Maximum value of PV
input range
EASY
RL
(Physical
quantity)
Minimum value of PV
input range
EASY
Setting range
Menu symbol
OFF: Disable
K1: -270.0 to 1370.0 C / -450.0 to 2500.0 F
K2: -270.0 to 1000.0 C / -450.0 to 2300.0 F
K3: -200.0 to 500.0 C / -200.0 to 1000.0 F
J: -200.0 to 1200.0 C / -300.0 to 2300.0 F
T1: -270.0 to 400.0 C / -450.0 to 750.0 F
T2: 0.0 to 400.0 C / -200.0 to 750.0 F
B: 0.0 to 1800.0 C / 32 to 3300 F
S: 0.0 to 1700.0 C / 32 to 3100 F
R: 0.0 to 1700.0 C / 32 to 3100 F
N: -200.0 to 1300.0 C / -300.0 to 2400.0 F
E: -270.0 to 1000.0 C / -450.0 to 1800.0 F
L: -200.0 to 900.0 C / -300.0 to 1600.0 F
U1: -200.0 to 400.0 C / -300.0 to 750.0 F
U2: 0.0 to 400.0 C / -200.0 to 1000.0 F
W: 0.0 to 2300.0 C / 32 to 4200 F
PV
(Note1)
PL2: 0.0 to 1390.0 C / 32.0 to 2500.0 F
P2040: 0.0 to 1900.0 C / 32 to 3400 F
WRE: 0.0 to 2000.0 C / 32 to 3600 F
JPT1: -200.0 to 500.0 C / -300.0 to 1000.0 F
JPT2: -150.0 to 150.0 C / -200.0 to 300.0 F
PT1: -200.0 to 850.0 C / -300.0 to 1560.0 F
PT2: -200.0 to 500.0 C / -300.0 to 1000.0 F
PT3: -150.00 to 150.00 C / -200.0 to 300.0 F
0.4-2V: 0.400 to 2.000 V
1-5V: 1.000 to 5.000 V
4-20: 4.00 to 20.00 mA
0-2V: 0.000 to 2.000 V
0-10V: 0.00 to 10.00 V
0-20 : 0.00 to 20.00 mA
-1020: -10.00 to 20.00 mV
0-100: 0.0 to 100.0 mV
-: No unit
C: Degree Celsius
-: No unit
PV
- -: No unit
- - -: No unit
F: Degree Fahrenheit
Depends on the input type.
- For temperature input Set the temperature range
that is actually controlled.
(RL<RH)
- For voltage / current input Set the range of a voltage
/ current signal that is
applied.
PV
The scale across which the
voltage / current signal is
actually controlled should
be set using the maximum
value of input scale (SH)
and minimum value of
input scale (SL). (Input
is always 0% when RL =
RH.)
Same as RH
PV
7-2
IM 05P01D31-01EN
Name
Display
level
Setting range
Menu symbol
SDP
(Scaling)
EASY
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
SH
(Scaling)
Maximum value of PV
input scale
EASY
PV
SL
(Scaling)
Minimum value of PV
input scale
EASY
PV
PV
IN, UNIT, RH, and RL described above are the parameters to be used for processing
before the input ladder calculation program.
The following parameters are used for processing after the input ladder calculation
program.
P.UNI
P.DP
Control PV input
decimal point position
P.RH
P.RL
7.1.2
Name
Display
level
STD
Maximum value of
control PV input range
Minimum value of
control PV input range
Setting range
-: No unit
C: Degree Celsius
-: No unit
- -: No unit
- - -: No unit
F: Degree Fahrenheit
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Menu symbol
MPV
Description
The input value when input burnout occurs can be determined.
The input value is 105.0% of the input range when the upscale is set, and -5.0% of the
input range when the downscale is set.
Burnout detection is activated for TC, RTD, and standard signal (0.42 V or 15 V).
For standard signal, burnout is determined to have occurred if it is 0.1 V or less for the
range of 0.42 V and 15V, or if it is 0.4 mA or less for the range of 420 mA.
When input burnout occurs, the error preset output (EPO) is output as control output.
Input error preset output: 10.12.3 Setting Output Value When Error Occurs (Input Error Preset
Output)
Setting Details
Parameter
symbol
BSL
IM 05P01D31-01EN
Name
Display
level
STD
Setting range
OFF: Disable
UP: Upscale
DOWN: Downscale
Menu symbol
PV
7-3
Parameter
symbol
7.1.3
Description
Reference Junction Compensation (RJC)
When TC input is selected, presence/absence of input reference junction compensation
can be set.
Usually input values are compensated with the RJC function provided for the controller.
However, if it is necessary to rigorously compensate the values with a device other than
the function of the controller, for example with a zero-compensator, the RJC function of
the controller can be turned off.
External Reference Junction Compensation (ERJC)
For TC input, a temperature compensation value for external device can be set.
The external RJC can be used only when RJC = OFF.
UT35A/UT32A
Furnace
Terminal block
Compensating lead wire
TC
Terminal block
Furnace
Normal wiring
UT35A/UT32A
TC
Example:
Setting parameters
RJC = OFF,
ERJC = 25.0C
Setting Details
Parameter
symbol
RJC
ERJC
7-4
Name
PV input reference
junction compensation
PV input external RJC
setpoint
Display
level
Setting range
Menu symbol
PRO
PV
PRO
-10.0 to 60.0C
PV
IM 05P01D31-01EN
7.1.4
PV input bias
Compensation
value
Estimated material
temperature
PV Input Filter
If input noise or variations cause the low-order display digits to fluctuate so that the
displayed value is difficult to read, a digital filter can be inserted to smooth operation.
This filter provides a first-order lag calculation, which can remove more noise the larger
the time constant becomes. However, an excessively large time constant will distort the
waveform.
PV input filter is used for normal operation.
Actual input
Input
IM 05P01D31-01EN
7-5
Temperature sensed
by thermocouple
Display
level
Setting range
BS
PV input bias
EASY
-100.0 to 100.0% of PV
input range span (EUS)
FL
PV input filter
EASY
OFF, 1 to 120 s
Parameter
symbol
7.1.5
Name
Name
Display
level
Setting range
Menu symbol
PVS
Menu symbol
A.BS
STD
A.FL
STD
OFF, 1 to 120 s
PV
Description
Ratio bias computing performs ratio computation and bias addition for remote setpoints.
SP = Remote input x Remote input ratio (RT) + Remote input bias (RBS)
Setting Details
Parameter
symbol
Name
Display
level
Setting range
RT
STD
0.001 to 9.999
RBS
STD
100.0 to 100.0% of PV
input range span (EUS)
Menu symbol
SPS
7-6
IM 05P01D31-01EN
8.1
8.1.1
Description
These control functions provide the basic control function having one control computation
unit.
Single-loop control can be used for Standard type or Heating/cooling type controller.
Heating/cooling control can be used for Heating/cooling type controller.
Position proportional control can be used for Position proportional type controller.
Two-position two-level control can be used for Heating/cooling type controller.
PID control, Heating/cooling control, and Two-position two-level control: 8.2 Setting Control
Type (CNT)
For the functions and parameters which are not described in Function block diagram, see
the following.
IM 05P01D31-01EN
8-1
Control Functions
Equipped as standard
PV input
PV
DI1
Com.
Input type
IN
Input unit
UNIT
Input range/scale
RH, RL
A.BS
A.FL
SDP
Equipped as standard.
Contact inputs
DI2
SH, SL
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameters Setting Software Users Manual.
PV input bias
BS
PV input filter
FL
SPNO
RT
RBS
LOCAL
R/L
PV display
SP limiter
SPH, SPL
SP ramp rate
UPR, DNR
SP display
Control computation
CNT
ALG
SP
Target setpoints 1 to 4
TMU
8-2
IM 05P01D31-01EN
Output limiter
EPO
IM 05P01D31-01EN
Normal
OH, OL
MPON
Manual operation
Output limiter
OH, OL
OLMT
MAN
AUTO
A/M
Preset output
PO
STOP
RUN
STOP (ON)/RUN (OFF) switch
S/R
OT
Equipped as standard
Equipped as standard
Alarm
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software Users Manual.
LPS
Relay
OUT
RET
AL1
Alarm 2
(PV low limit)
Alarm 1
(PV high limit)
OUT
Alarm 3
(PV high limit)
24 V loop
power supply
AL2
HAL1
HAL2
Heater break
alarm 1
Heater break
alarm 2
AL3
Current
Legend
Terminal
Parameter
Function
Analog signal
Contact signal
8-3
Control Functions
Equipped as standard
PV input
PV
DI1
Com.
Input type
IN
Input unit
UNIT
Input range/scale
RH, RL
A.BS
A.FL
SDP
Equipped as standard.
Contact inputs
DI2
SH, SL
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameters Setting Software Users Manual.
PV input bias
BS
PV input filter
FL
SPNO
RT
RBS
LOCAL
R/L
PV display
SP limiter
SPH, SPL
SP ramp rate
UPR, DNR
SP display
Control computation
CNT
ALG
SP
Target setpoints 1 to 4
TMU
8-4
IM 05P01D31-01EN
MPON
MAN
AUTO
A/M
Heating/cooling computation
EPO
Normal
When sensor
burnout occurs
STOP
OH, OL
Normal
RUN
RUN
EPO
S/R
OT
O1RS
Alarm
RTS
Equipped as standard
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software Users Manual.
24 V loop
power supply
LPS
OUT
Relay
OUT
OUT2
RET/OUT2
AL1
Current or
voltage pulse
(Current when retransmission output)
Alarm 3
(PV high limit)
Cooling-side
output
AL2
AL3
Relay
Legend
HAL1
HAL2
Heater break
alarm 1
Heater break
alarm 2
Terminal
Parameter
Function
Analog signal
Contact signal
8-5
Current or
voltage pulse
(Current when retransmission output)
Cooling-side
output
Alarm 2
( PV low limit)
Heating-side Heating-side
output
output
Alarm 1
(PV high limit)
Control Functions
Equipped as standard
PV input
PV
DI1
Com.
Input type
IN
Input unit
UNIT
Input range/scale
RH, RL
A.BS
A.FL
SDP
Equipped as standard.
Contact inputs
DI2
SH, SL
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software Users Manual.
PV input bias
BS
PV input filter
FL
SPNO
RT
RBS
LOCAL
R/L
PV display
SP limiter
SPH, SPL
SP ramp rate
UPR, DNR
SP display
Control computation
CNT
ALG
SP
Target setpoints 1 to 4
TMU
8-6
IM 05P01D31-01EN
Output limiter
IM 05P01D31-01EN
OH, OL
EPO
Normal
AUTO
A/M
Preset output
PO
STOP
RUN
STOP (ON)/RUN (OFF) switch
S/R
Equipped as standard
Equipped as standard
Equipped as standard
Alarm
RTS
O1RS
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software Users Manual.
FBIN
H relay
key)
(
VALV
LPS
Relay output
Feedback input
Direct/reverse signal
Motor-operated valve
RET
Current
Current
Legend
AL1
AL2
AL3
Terminal
Parameter
Function
Analog signal
Contact signal
8-7
OUT
Alarm 3
(PV high limit)
L relay
key)
Alarm 1
(PV high limit)
HYS
DB
Alarm 2
(PV low limit)
Signal comparison
24 V loop
power supply
Control Functions
Equipped as standard
PV input
Equipped as standard.
Contact inputs
PV
DI1
Com.
Input type
IN
Input unit
UNIT
Input range/scale
RH, RL
A.BS
A.FL
SDP
DI2
SH, SL
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software Users Manual.
PV input bias
BS
PV input filter
FL
Target setpoints 1 to 4
LOCAL
R/L
PV display
SP limiter
SPH, SPL
SP ramp rate
UPR, DNR
TMU
SP display
CNT
ALG
Sub-target setpoints
PV display
SUB
SP display
SPNO
SP
8-8
EPO
IM 05P01D31-01EN
Normal
Normal
EPO
Manual operation
AUTO
MAN
AUTO
A/M
Preset output
MAN
A/M
PO
Sub-preset output
STOP
RUN
RUN
SU.PO
STOP
S/R
OT
Alarm
RTS
O1RS
Equipped as standard
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software Users Manual.
LPS
OUT
Relay
OUT
OUT2
Relay
RET/OUT2
AL1
Current or
voltage pulse
(Current when retransmission output)
Legend
Alarm 2
(PV low limit)
Sub-setting
control output
AL2
HAL1
HAL2
Heater break
alarm 1
Heater break
alarm 2
AL3
Terminal
Parameter
Function
Analog signal
Contact signal
8-9
Current or
voltage pulse
(Current when retransmission output)
Alarm 1
(PV high limit)
Main setting
control output
Alarm 3
(PV high limit)
24 V loop
power supply
Control Functions
8.2
Heating/cooling
type
Position
proportional type
N/A
N/A
N/A
N/A
Heating/cooling control
N/A
N/A
PID control
ON/OFF control
(1 point of hysteresis)
ON/OFF control
(2 points of hysteresis)
The following table shows combination of control type (CNT) and output type.
Output type
Current
output
Time
proportional
output
ON/OFF
output
Position
proportional
output
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Heating/cooling control
N/A
Control type
PID control
ON/OFF control
(1 point of hysteresis)
ON/OFF control
(2 points of hysteresis)
8-10
IM 05P01D31-01EN
8.2.1
PID Control
Description
PID control is a general control using control-related parameters PID.
When PID control is selected, PID should be obtained by auto-tuning after setting SP or
PID should be set manually.
Setting Details
Parameter
symbol
CNT
Name
Control type
Cooling-side
proportional band
Pc
Ic
Dc
MR
PIDN
PIDG.
Cooling-side
integral time
Cooling-side
derivative time
Manual reset
PID number
selection
Number of PID
groups
EASY
EASY
Setting range
Menu symbol
EASY
OFF: Disable
1 to 6000 s
EASY
OFF: Disable
1 to 6000 s
PID
EASY
0.0 to 999.9%
Cooling-side ON/OFF control applies
when 0.0% in Heating/cooling control.
OFF: Disable
1 to 6000 s
OFF: Disable
1 to 6000 s
-5.0 to 105.0%
EASY
1 to 4
SP
STD
1 to 4
CTL
EASY
EASY
EASY
8
Control Functions
Proportional band
Heating-side
proportional band
(in Heating/cooling
control)
Integral time
Heating-side
integral time (in
Heating/cooling
control)
Derivative time
Heating-side
derivative time (in
Heating/cooling
control)
Display
level
Note 1: The PID number (1 to 4, or R) is displayed on Group display while the parameter P, I, D, Pc,
Ic, Dc, or MR is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
8-11
8.2.2
Description
ON/OFF control compares the SP and PV and outputs an on or off signal according to
the positive or negative deviation (PV SP). Hysteresis can be set in the vicinity of the
on/off output operating point.
If the SP and PV become close and the polarity of the deviation reverses frequently,
the on/off output will cycle repeatedly. The life of the output relay will therefore be
dramatically shortened.
In such a case, set a wider hysteresis so that the relays frequent on/off output (chattering)
will not occur.
When the control type (CNT) is set to ONOF, one point of hysteresis can be set to the
operating point.
When the control type (CNT) is set to ONOF2, two points of hysteresis (deviation
positive hysteresis and deviation negative hysteresis) can be set to the operating point.
1 point of hysteresis
Hysteresis
ON
Control
output
OFF
SP
PV
PV
Hysteresis
SP
Control
output
ON
Temperature
ON
ON
OFF
OFF
2 points of hysteresis
HY.LO HY.UP
ON
Control
output
OFF
SP
PV
PV
HY.UP
SP
Control
output
ON
OFF
8-12
Temperature
ON
ON
OFF
HY.LO
IM 05P01D31-01EN
CNT
HYS
HY.LO
PIDN
PIDG.
Control type
Hysteresis
(in ON/OFF
control, Position
proportional
control, or Twoposition two-level
control)
Heating-side
ON/OFF control
hysteresis (in
Heating/cooling
control)
Upper-side
hysteresis (in ON/
OFF control)
Lower-side
hysteresis (in ON/
OFF control)
PID number
selection
Number of PID
groups
Display
level
Setting range
Menu symbol
EASY
EASY
EASY
EASY
EASY
STD
8
PID
Control Functions
HY.UP
Name
1 to 4
SP
CTL
Note1: The PID number (1 to 4, or R) is displayed on Group display while the parameter HYS,
HY.UP or HY.LO is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
8-13
8.2.3
Heating/cooling Control
Description
Heating/cooling control can be used only for Heating/cooling type.
In Heating/cooling control, the controller outputs the result of computation after splitting it
into heating-purpose and cooling-purpose signals. PID control or ON/OFF control can be
selected for each of the heating side and the cooling side.
Set the heating-side proportional band to 0 to perform ON/OFF control on the heating
side. Set the cooling-side proportional band to 0 to perform ON/OFF control on the
cooling side.
PV
SP
Control computation
COM
0 to 100%
Heating/cooling computation
0 to 50%
50 to 100%
Heating-side output limiter
DB
50% ) 2
2
DB
P
COUT = ( 50% OUT
)2
2
Pc
HOUT = ( OUT
8-14
IM 05P01D31-01EN
100%
Heating-side
control output
high limit
(OH)
Cooling-side
control output
high limit
(OHc)
Dead
band
(DB)
Dead
band
(DB)
0%
0%
0%
50%
50%
100%
100%
Cooling-side
control output
high limit
(OHc)
100%
Heating-side
control output
high limit
(OH)
Dead
band
(DB)
Dead
band
(DB)
0%
0%
0%
50%
100%
0%
Control computation output
(OUT)
50%
100%
CAUTION
Set the ratio of the heating-side proportional band (P) to the cooling-side
proportional band (Pc) to within 1 to 5.
Setting the heating-side or cooling-side integral time (I or Ic) to OFF results in
the integral time of both sides being set to OFF.
IM 05P01D31-01EN
8-15
Control Functions
0%
100%
Control computation output
(OUT)
DB
HYS
+
)
2
2
Other than this case, maintain current state.
DB
COUT = ( 50% OUT
)2
HOUT = OUT > ( 50% +
100%
Cooling-side
control output
high limit
(OHc)
Dead
band
(DB)
Dead band
(DB)
0%
0%
0%
50%
0%
100%
Control computation output
(OUT)
50%
100%
Hysteresis (HYS)
100%
Dead band
(DB)
Cooling-side
control output
high limit
(OHc)
Dead band
(DB)
0%
0%
0%
50%
100%
0%
50%
100%
8-16
IM 05P01D31-01EN
HOUT = ( OUT
DB
50% ) 2
2
DB
HYSc
)
2
2
HYSc
DB
+
)
2
2
Other than these cases, maintain current state.
OUT > ( 50% +
100%
Heating-side
control output
high limit
(OH)
Dead band
(DB)
Dead band
(DB)
0%
0%
0%
50%
Hysteresis (HYSc)
0%
100%
Control computation output
(OUT)
50%
100%
100%
Dead band
(DB)
100%
Heating-side
control output
high limit
(OH)
Dead band
(DB)
0%
0%
0%
IM 05P01D31-01EN
50%
100%
0%
Control computation output
Hysteresis (HYSc)
(OUT)
50%
100%
8-17
Control Functions
ON
Neutral (OFF)
50%
ON
Cooling-side
output
Output (%)
100
Heating-side
output
Cooling-side
output
Heating-side
output
0
0
8-18
50
0
100(%)
50
100(%)
IM 05P01D31-01EN
CNT
HYS
DB
PIDN
PIDG.
Control type
Hysteresis
(in ON/OFF
control, Position
proportional
control, or Twoposition two-level
control)
Heating-side
ON/OFF control
hysteresis (in
Heating/cooling
control)
Cooling-side
ON/OFF control
hysteresis
Output dead band
(in Heating/cooling
control or Position
proportional
control)
PID number
selection
Number of PID
groups
Display
level
Setting range
Menu symbol
EASY
EASY
8
Control Functions
HYSc
Name
PID
EASY
0.0 to 100.0%
EASY
EASY
1 to 4
SP
STD
1 to 4
CTL
Note1: The PID number (1 to 4, or R) is displayed on Group display while the parameter HYS,
HYSc, or DB is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
8-19
8.2.4
Description
Two-position two-level control outputs the ON signal and OFF signal for the target
setpoint (SP) of the main setting and the sub-target setpoint (SP + SUB) of the subsetting.
The sub-setting is set as a deviation from the main setting.
Hysteresis can be set in the vicinity of the on/off output operating point
Two-position two-level control: 8.1.1 Single-loop Control, Heating/cooling Control, Position
Proportional Control, and Two-position Two-level Control
Hysteresis (HYS)
Hysteresis (SU.HY)
ON
OFF
Main SP (SP)
Sub-SP (SP+SUB)
PV
Hysteresis (HYS)
Hysteresis (SU.HY)
ON
OFF
Main SP (SP)
Sub-SP (SP+SUB)
PV
Hysteresis (HYS)
Hysteresis (SU.HY)
ON
OFF
Main SP (SP)
Sub-SP (SP+SUB)
PV
Hysteresis (HYS)
Hysteresis (SU.HY)
ON
OFF
Main SP (SP)
8-20
Sub-SP (SP+SUB)
PV
IM 05P01D31-01EN
Name
Display
level
CNT
Control type
EASY
SP
Target setpoint
EASY
SUB
SU.HY
DR
SU.DR
PIDN
PIDG.
EASY
Menu symbol
8
EASY
Control Functions
HYS
Sub-target setpoint
(in Two-position
two-level control)
Hysteresis
(in ON/OFF
control, Position
proportional
control, or Twoposition two-level
control)
Heating-side
ON/OFF control
hysteresis (in
Heating/cooling
control)
Sub-hysteresis (in
Two-position twolevel control)
Direct/reverse
action switch
Sub-direct/reverse
action switch (in
Two-position twolevel control)
PID number
selection
Number of PID
groups
Setting range
PID
EASY
STD
STD
EASY
1 to 4
SP
STD
1 to 4
CTL
Note1: The PID number (1 to 4, R) is displayed on Group display while the parameter SP, SUB,
HYS, SU.HY, DR, or SU.DR is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
8-21
8.2.5
Description
This control type performs control in which integral action (I action) is excluded from PID
action.
Set the integral time (I or Ic) to OFF.
It is useful when stable control in which a setpoint is not exceeded is desired for integral
processes in which constant flows are delivered.
The following shows the PID control computation formula.
OUT = 100 e + Td
P
d
dt
PV + MR
where OUT: control output, e: deviation (PV-SP), P: proportional band, Td: derivative time,
PV: PVn-PVn-1 (n-1: value before one control period), and MR: manual reset
PD control
Current
output
Time
proportional
output
ON/OFF
output
Position
proportional
output
N/A
Setting Details
Parameter
symbol
Name
Display
level
Proportional band
EASY
Derivative time
EASY
MR
Manual reset
EASY
PIDG.
Number of PID
groups
STD
Setting range
Menu symbol
0.0 to 999.9%
When 0.0% is set, it operates as 0.1%.
OFF: Disable
PID
1 to 6000 s
-5.0 to 105.0%
1 to 4
CTL
Note1: The PID number (1 to 4, or R) is displayed on Group display while the parameter P, D, or MR
is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
8-22
IM 05P01D31-01EN
8.3
Description
There are two PID control modes: standard PID control mode and fixed-point control
mode.
Select a PID control computation formula shown in the following table according to the
control mode or operation mode.
Operation mode
AUTO+Local
Standard PID control
PV derivative type
(output bump at SP change)
mode
Fixed-point control
PV derivative type
mode
(output bumpless at SP change)
AUTO+Remote
Deviation derivative type
PV derivative type
(output bump at SP change)
OUT = 100 e + 1
Ti
P
e dt + Td
Control Functions
d PV
dt
where OUT: control output, e: deviation (PV-SP), P: proportional band, Ti: integral time,
Td: derivative time, and PV: PVn-PVn-1 (n-1: value before one control period)
SP
PV
OUT
SP
PV
IM 05P01D31-01EN
OUT
8-23
OUT = 100 e + 1
Ti
P
e dt + Td
d e
dt
where OUT: control output, e: deviation (PV-SP), P: proportional band, Ti: integral time,
and Td: derivative time
SP
PV
OUT
Setting Details
Parameter
symbol
ALG
8-24
Name
PID control mode
Display
level
PRO
Setting range
0: Standard PID control mode
1: Fixed-point control mode.
Menu symbol
CTL
IM 05P01D31-01EN
8.4
8.4.1
Switching PID
Switching PID According to Target Setpoint Number (SPNO)
Description
The SP group number selection selects a group of target setpoint (SP) and PID
parameters by switching the SP number (SPNO).
The PID number selection (PIDN) can be set for each SP group.
SP number (SPNO)
SP
SP of group 1
SP of group 2
SP of group 3
SP of group 4
When ZON=3 (SP group number selection 2): In coordinated operation, slaves operate
with the setpoint in the PID number selection (PIDN) within the SP group.
Setting Details
Parameter
symbol
ZON
PIDN
PID
PIDG.
Name
Zone PID
selection
PID number
selection
PID number
(display only)
Number of PID
groups
Display
level
STD
EASY
Setting range
0: SP group number selection 1
1: Zone PID selection (selection
by PV)
2: Zone PID selection (selection
by target SP)
3: SP group number selection 2
4: Zone PID selection (selection
by SP)
1 to 4 (Depends on the setup
parameter PIDG. setting.)
Menu symbol
CTL
SP
EASY
1 to 4
MODE
STD
1 to 4
CTL
Note1: The initial values for PIDN of the four groups are same as SP number selection (SPNO.). Set
a PID number to use as necessary.
Note3: A currently-used PID number is displayed for the parameter PID.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
8-25
Control Functions
When ZON=0 (SP group number selection 1): In coordinated operation, slaves operate
with the same PID number as that of the master.
The setpoint in the PID number selection (PIDN) within the SP group is ignored.
8.4.2
Description
The PID switching according to PV is a function that switches between the groups of PID
parameters according to the PV.
The maximum number of PID groups to be switched is 8. (Set RP1 to RP3.)
This function is useful for reactors in which the chemical reaction gain changes
depending on the temperature.
The figure below shows an example of dividing the PV input range from the maximum
value to the minimum value into four zones by reference points 1 to 3. (Set RP1 to RP3.)
If the PV is currently positioned at this point,
control is based on the PID of group 4.
PID of group 3
Reference point 2
PID of group 2
Reference point 1
PID of group 1
The PV input range can be divided into the number of zones that is set in the reference
point.
Hysteresis at the time of zone switch can be set.
Setpoint PD: 8.4.6 Setting Hysteresis at Time of Zone Switch
8-26
IM 05P01D31-01EN
Name
Display
level
ZON
Zone PID
selection
STD
RP1 to RP3
Reference point
1 to 3
STD
PIDG.
PID
Number of PID
groups
PID number
(display only)
STD
EASY
Setting range
0: SP group number selection 1
1: Zone PID selection (selection
by PV)
2: Zone PID selection (selection
by target SP)
3: SP group number selection 2
4: Zone PID selection (selection
by SP)
0.0 to 100.0% of PV input range
(EU)
(RP1 RP2 RP3)
Menu symbol
CTL
ZONE
1 to 4
CTL
MODE
IM 05P01D31-01EN
8-27
Control Functions
Note
8.4.3
Description
The zone PID selection by SP switches between the groups of PID parameters according
to the SP.
The maximum number of PID groups to be switched is 4. (Set RP1 to RP3)
The figure below shows the example of switching the group of PID parameters according
to the SP. It shows an example of dividing the PV input range from the maximum value to
the minimum value into four zones by reference points 1 to 3. (Set RP1 to RP3.)
SP
Maximum value of
PV input range
(PID of group 5)
(PID of group 4)
Reference point 3
SP
(PID of group 3)
Reference point 2
(PID of group 2)
Reference point 1
(PID of group1)
Minimum value of
PV input range
PID No. to be selected
Time
PID of group 1
PID of group 3
PID of group 2
PID of grop 2
PID of group 4
PID of group 3
The PV input range can be divided into the number of zones that is set in the reference
point.
Reference deviation can be set at the same time.
Reference deviation: 8.4.5 Switching PID according to Deviation (Reference Deviation)
8-28
IM 05P01D31-01EN
Name
Display
level
Setting range
Menu symbol
Zone PID
selection
STD
RP1 to RP3
Reference point 1
to 3
STD
ZONE
PIDG.
Number of PID
groups
STD
1 to 4
CTL
PID
PID number
(display only)
MODE
EASY
CTL
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
8-29
Control Functions
ZON
8.4.4
Description
The zone PID selection by target SP switches between the groups of PID parameters
according to the target SP.
The figure below shows the example of switching the group of PID parameters according
to the target SP. It shows an example of dividing the PV input range from the maximum
value to the minimum value into four zones by reference points 1 to 3. (Set RP1 to RP3.)
SP
Maximum value of
PV input range
800C
(PID of group 4)
Reference point 3
Target SP
(PID of group 3)
350C
Reference point 2
(PID of group 2)
250C
Reference point 1
Current SP
100C
(PID of group 1)
Minimum value of
PV input range
Time
PID of group 3
Target SP is
changed from
100C to 350C
PID of group 2
Target SP is
changed from
350C to 250C
PID of group 5
Target SP is
changed from
250C to 800C
The PV input range can be divided into the number of zones that is set in the reference
point.
Reference deviation can be set at the same time.
Reference deviation: 8.4.5 Switching PID according to Deviation (Reference Deviation)
8-30
IM 05P01D31-01EN
Name
Display
level
ZON
Zone PID
selection
STD
RP1 to RP3
Reference point 1
to 3
STD
PIDG.
PID
Number of PID
groups
PID number
(display number)
STD
EASY
Setting range
0: SP group number selection 1
1: Zone PID selection (selection
by PV)
2: Zone PID selection (selection
by target SP)
3: SP group number selection 2
4: Zone PID selection (selection
by SP)
0.0 to 100.0% of PV input range
(EU)
(RP1 RP2 RP3)
Menu symbol
CTL
ZONE
1 to 4
CTL
MODE
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
8-31
Control Functions
Note
8.4.5
Description
The zone PID selection by deviation switches between the groups of PID parameters
according to the amount of deviation.
This function is called reference deviation.
In the fixed point control, if the actual amount of deviation exceeds the setpoint of the
reference deviation, the controller automatically changes to the PID parameter group
(PID of group R) set for the zone. If the actual amount of deviation becomes smaller than
the setpoint of reference deviation, the controller changes to the PID parameter group
appropriate for the zone.
For example, if the deviation is large, PV can be reached more rapidly to SP by
increasing the proportional gain (i.e., narrowing the proportional band). Switching PID
according to deviation is effective when ZON is set to 1, 2, 4. The zone PID selection by
reference deviation has priority over other zone PID selections.
Maximum value of
PV input range
PV
Reference point 2
Reference deviation (RDV)
Reference deviation (RDV)
SP
Reference point 1
Minimum value of
PV input range
PID No. to be selected PID of group R
PID of group 2
Setting Details
Parameter
symbol
Name
Display
level
ZON
Zone PID
selection
STD
RDV
Reference
deviation
STD
PID
PID number
(display only)
EASY
Setting range
0: SP group number selection 1
1: Zone PID selection (selection
by PV)
2: Zone PID selection (selection
by target SP)
3: SP group number selection 2
4: Zone PID selection (selection
by SP)
OFF: Disable
0.0 + 1 digit to 100.0% of PV input
range span (EUS)
1 to 4, R: PID group for reference
deviation
Menu symbol
CTL
ZONE
MODE
8-32
IM 05P01D31-01EN
8.4.6
Description
When the zone PID selection is selected, hysteresis at time of each zone switch can be
set.
The following shows the operation example of hysteresis at time of zone switch.
PV
Reference point 1
Hysteresis
PID of group 2
PID of group 1
PID of group 2
Setting Details
Parameter
symbol
RHY
8.4.7
Name
Zone PID switching
hysteresis
Display
level
STD
Setting range
0.0 to 10.0% of PV input
range span (EUS)
Menu symbol
ZONE
Description
PID can be switching by contact input.
Setting Details
Contact input assignment: 12.1 Setting Contact Input Function
IM 05P01D31-01EN
8-33
Control Functions
PID of group 1
8.5
Description
The Super function monitors the deviation for evidence that there is a danger of
overshoot, and on sensing such danger automatically changes the setpoint temporarily
to a somewhat lower value (sub-SP).
Once the danger of overshoot appears diminished, the function returns the effective SP
gradually to the true SP. Fuzzy ratiocination techniques are employed in the algorithms
used to change the SP to the lower temporary value, and to return it gradually to the true
SP.
Operation Diagram
PV
Sub-SP
Original SP
PV
Time
Start of
fuzzy inference
8-34
SP
PID
computation
Process
PV
Sub-SP
Target
SP
Manipulated variable
Sub-SP
setting
IM 05P01D31-01EN
Temperature
Temperature
Time
SUPER is not used
Time
SUPER is used
Temperature
8
Control Functions
Temperature
Sub-SP
Time
SUPER is not used
Time
SUPER is used
Setting Details
Parameter
symbol
SC
Name
Super function
Display
level
EASY
Setting range
Menu symbol
OFF: Disable
1: Overshoot suppressing function
(normal mode)
2: Hunting suppressing function
(stable mode)
TUNE
3: Hunting suppressing function
(response mode)
4: Overshoot suppressing function
(strong suppressing mode)
The setting SC=4 is effective compared with SC=1. However, the hunting may occur until
the PV reaches SP. Use it as usage.
Do not use the Super function for the Sample PI control.
IM 05P01D31-01EN
8-35
8.6
Description
The Super2 function suppresses the hunting effect of the controller without re-tuning the
PID parameters.
Hunting means the PV becomes unstable and oscillates around SP.
PV
SP
PV
SUPER2 = ON
Hunting
In hunting condition, the Super2 function selects the output from process model as PV
signal.
The process model removes a factor of dead time from the actual process.
The real process is under the open-loop condition.
After hunting is suppressed, the Super2 function selects real PV signal, and carry out
the standard feedback control.
+
SP
PID control
CPV
OUT
Process
PV
Process
model
PV
8-36
IM 05P01D31-01EN
SP
PV
SUPER2 = ON
Hunting
Temperature change
PV
PID parameters are set at this condition.
SUPER2 = ON
8
Hunting
Parameter
symbol
SC
Name
Super function
Display
level
EASY
Setting range
Menu symbol
OFF: Disable
1: Overshoot suppressing function
(normal mode)
2: Hunting suppressing function
(stable mode)
TUNE
3: Hunting suppressing function
(response mode)
4: Overshoot suppressing function
(strong suppressing mode).
Set SC=2 when there are a lot of disturbances, and much hunting occurs.
Set SC=3 when SP is changed frequently. Hunting suppressing effect is smaller than that
of SC=2, however, responsiveness is good.
The Super function does not work in direct action.
IM 05P01D31-01EN
8-37
Control Functions
Setting Details
8.7
Description
Where there is a large deviation at the start of the control operation, for example, integral
outputs are accumulated and the PV exceeds the SP, thereby causing the output to
overshoot. To avoid this, the controller provides an anti-reset wind-up function for
suppressing an extreme integral output by stopping PID computations. Same applies to
the case of undershoot.
PID computations stop
100
OH
OH: Output high limit
Output (%)
0
Time
SP
PV
Deviation band (AR):
the ratio of (PVSP) to proportional band
PV
Time
The parameter AR sets the point (by deviation band (%)) to restart the PID computation
that is suspended by the controllers anti-reset windup function. PID computation restarts
when the deviation band has decreased to the AR setpoint. When the parameter AR is
set to AUTO, the controller automatically determines the point at which to restart the PID
computation.
\ PV SP \
Deviation band (= Setpoint of AR) =
Proportional band
100 (%)
Setting Details
Parameter
symbol
AR
8-38
Name
Anti-reset windup
Display
level
STD
Setting range
AUTO, 50.0 to 200.0%
Menu symbol
TUNE
IM 05P01D31-01EN
8.8
Description
Auto-tuning Type
Normal of auto-tuning type requires a rapidly rising PID constant. This type is useful for
processes that allow some overshooting.
On the other hand, stable of auto-tuning type requires a slowly rising PID constant.
Auto-tuning Output Limiter
When executing auto-tuning, the control output high and low limits can be set.
When the control output low limit > AT.OL, or AT.OH < control output high limit, autotuning is limited by the control output low or high limit.
In Heating/cooling control, AT.OH and AT.OL do not work.
Note
Setting Details
Parameter
symbol
AT.TY
AT.OH
AT.OL
IM 05P01D31-01EN
Name
Auto-tuning type
Output high limit in
auto-tuning
Output low limit in
auto-tuning
Display
level
STD
PRO
PRO
Setting range
Menu symbol
0: Normal
1: Stability
-5.0 to 105.0% (Disabled in
Heating/cooling control)
TUNE
8-39
Control Functions
In time proportional output, the output is turned on and off irrespective of the upper/lower limit.
Blank Page
9.1
Setting SP Limiter
Description
The SP high and low limits can be set to restrict the SP to the range between those limits
whether in REM (remote) or LCL (local) mode. They works to the SP of all SP groups.
(%)
100.0
Actual SP
High limit of SP
SPL
0.0
0.0
Setting range
SPH
100.0(%)
Setting Details
Parameter
symbol
IM 05P01D31-01EN
Name
Display
level
SPH
SP high limit
STD
SPL
SP low limit
STD
Setting range
0.0 to 100.0% of PV input range
(EU), (SPL<SPH)
Menu symbol
MPV
9-1
9.2
Description
SP ramp-rate setting function forces SP to change at a fixed rate when SP is changed in
order to prevent abrupt changes in SP.
Velocity (rate-of-change) can be set for both the SP ramp-up rate (UPR) and SP rampdown rate (DNR). Set the ramprate time unit (TMU) per hour or minute.
The SP ramp-rate setting function works when:
(1) SP is changed.
(2) SP is changed by switching SP number (SPNO).
(3) Power is turned on or has recovered from a failure (PV tracking=ON); or
(4) Operation mode is switched from MAN to AUTO (PV tracking=ON).
SP ramp-rate setting action starts from PV when the PV tracking function is used.
(2) When SP No. (SPNO) is switched
SP of group 2
Old SP
Specified ramp rate
New SP
SP change
Time
PV input range
SP
PV
Time
SP of group 1/SP of group 2 switch
Time
Power-on or
Switch from MAN to AUTO
SP
Increases
according
to UPR
SP of group 3
(PID of group 3)
Decreases
according
to DNR
SP of group 2
(PID of group 2)
SP of group 1
(PID of group 1)
SP of group 1
(PID of group 1)
Increases
according
to UPR
Time
Switch
from SP of group 1
to SP of group 3
9-2
Switch
from SP of group 3
to SP of group 1
Switch
from SP of group 1
to SP of group 2
IM 05P01D31-01EN
SP of group 2
SP of group 2= 640C
Temperature
difference of 140C
70C/min
UPR = 140/2 = 70 (C/min)
SP of group 1 = 500C
Temperature rise time of 2 min.
UPR =
140C
2 min
= 70 (C/min)
Setting Details
Parameter
symbol
Display
level
UPR
SP ramp-up rate
EASY
DNR
SP ramp-down rate
EASY
TMU
SP ramp-rate time
unit
EASY
Setting range
Menu symbol
9
Auxiliary Control Functions
IM 05P01D31-01EN
Name
9-3
9.3
Description
PV tracking function is used to prevent abrupt PV changes.
With PV tracking, SP is first aligned with PV and then changed to its original SP at the
SP ramp rate.
SP ramp-rate setting function: 9.2 Changing SP at a Fixed Rate (SP Ramp-Rate Setting
Function)
PV tracking disabled
SP
PV
PV
MAN
AUTO
Mode switch
MAN
Time
AUTO
Time
Mode switch
Setting Details
Parameter
symbol
PVT
9-4
Name
PV tracking selection
Display
level
STD
Setting range
OFF, ON
Menu symbol
SPS
IM 05P01D31-01EN
9.4
Description
SP tracking function is the function to force the local setpoint (SP) to track the remote
setpoint (RSP) when the operation mode is switched from REM (remote) to LCL (local)
mode.
The function is effective to prevent abrupt PV changes.
SP tracking enabled
SP tracking disabled
SP
SP
RSP
PV
PV
RSP
9
Time
REM LCL mode switch
Setting Details
Parameter
symbol
SPT
Name
SP tracking selection
Display
level
STD
Setting range
OFF, ON
Menu symbol
SPS
IM 05P01D31-01EN
9-5
Time
REM LCL mode switch
9.5
Description
For details, see Chapter 15, Power Failure Recovery Processing.
Setting Details
Parameter
symbol
R.MD
Name
Restart Mode
Display
level
STD
Setting range
Menu symbol
9-6
IM 05P01D31-01EN
9.6
Description
The time between power on and the instant where controller starts control computation
can be set.
Operation start time = Operating time of controller initialization after power on.
Setting Details
Parameter
symbol
R.TM
Name
Restart Timer
Display
level
STD
Setting range
0 to 10 s
Menu symbol
SYS
9
Auxiliary Control Functions
IM 05P01D31-01EN
9-7
Blank Page
In time proportional output, the control computation result is output in the form of an
on/off signal pulse width proportional to the time. The pulse width is calculated as follows
with the cycle time (control output cycle) at 100%.
Control output pulse width = Control output (%) x Cycle time
The output type is selected as either the relay/triac output or the voltage pulse output.
PV
UT35A/UT32A 100
ON
OFF
ON/OFF signal
pulse output
Heater
SSR
10
ON
OFF
0
0.0
50.0
100.0
Displayed output value (%)
Current Output
In current output, the control computation result is output as a current signal. (Example of
4 to 20 mA)
PV
Heater
Furnace
20 mA
UT35A/UT32A
Control output
Control output
TC
4 mA
0.0
Thyristor unit
ON/OFF Output
ON/OFF control compares the SP and PV and outputs an on or off signal according to
the positive or negative deviation (PV SP).
IM 05P01D31-01EN
10-1
Tank
On-time ratio
TC
PV
Control motor
Position signal
TC
Air
Motor-operated valve
Furnace
Gas
Burner
Control
output
Valve position
signal
Comparator
Direct action
Reverse
action
Slide-wire resistor
Motor-operated
valve
Heating/cooling Output
10-2
IM 05P01D31-01EN
Two-position Two-level Control is equipped only with Heating/cooling type (Suffix code:
Type 1 = -2).
Two-position two-level control output: 8.1.1 Single-loop Control, Heating/cooling Control,
Position Proportional Control, and Two-position Two-level Control
Two-position two-level control: 8.2.4 Two-position Two-level Control
Setting Details
Parameter
symbol
OT
Name
Output type
selection
Display
level
EASY
Setting range
Menu symbol
OUT
10
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay/triac)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage
pulse)
08: RET/OUT2 terminals (current)
CAUTION
No output is generated even if the terminal which is not provided is selected.
Confirm that the terminal to be selected is provided.
For each output terminal number, see 17.4, Wiring.
Set a control type, and an input type before setting an output type.
Control type: 8.2 Setting Control Type (CNT)
Input type: 7.1.1 Setting Input Type, Unit, Range, Scale, and Decimal Point Position
Symbol
00
IM 05P01D31-01EN
10-3
Symbol
Symbol
10-4
IM 05P01D31-01EN
ON
On time
On time
OFF
OFF
Cycle time
Cycle time
ON
ON
OFF
5 sec
10
20 sec
OFF
Setting Details
Parameter
symbol
CT
CTc
IM 05P01D31-01EN
Name
Control output cycle
time
Heating-side control
output cycle time
(in Heating/cooling
control)
Cooling-side control
output cycle time
Display
level
EASY
Setting range
0.5 to 1000.0 s
Menu symbol
OUT
EASY
10-5
OFF
10 sec
Actual output
variable range
Output low limit
Setting range
5.0
Low limit
High limit
105.0 (%)
Setting Details
Parameter
symbol
OH
OL
OHc
OLc
Name
Control output high
limit
Heating-side control
output high limit
(in Heating/cooling
control)
Control output low limit
Heating-side control
output low limit (in
Heating/cooling
control)
Cooling-side control
output high limit
Cooling-side control
output low limit
Display
level
Setting range
EASY
EASY
EASY
EASY
Menu symbol
PIDN
EASY
1 to 4
SP
PIDG.
STD
1 to 4
CTL
Note1: The PID number (1 to 4, R) is displayed on Group display while each parameter is displayed.
Note2: When the setting is low limit high limit, the controller operates as low limit = high limit -1 digit.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
10-6
IM 05P01D31-01EN
Name
Output limiter switch
Display
level
PRO
Setting range
OFF: Disable output limiter in
MAN mode
ON: Enable output limiter in
MAN mode
Menu symbol
TUNE
10
Output (Control and Retransmission) Functions
IM 05P01D31-01EN
10-7
Output
Actual output
change
100%
50 sec
0
Time (sec)
In Heating/cooling control, the output velocity limiter can be set to the control computation
result before split into heating-and cooling-side outputs.
In ON/OFF control or Two-position two-level control, the setting is invalid even if the
output velocity limiter is set.
Setting Details
Parameter
symbol
OPR
10-8
Name
Output velocity limiter
Display
level
STD
Setting range
OFF: Disable
0.1 to 100.0%/s
Menu symbol
TUNE
IM 05P01D31-01EN
10
5.0%
4.0 mA
3.2 mA
100.0%
0.0 mA
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
OL
PIDN
EASY
1 to 4
SP
PIDG.
STD
1 to 4
CTL
EASY
Note1: The PID number (1 to 4, R) is displayed on Group display while each parameter is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
10-9
OFF
SP
PV
Hysteresis
SP
ON
Temperature
ON
ON
OFF
Output
OFF
OFF
SP
PV
Upper-side hysteresis
SP
ON
Output
OFF
10-10
Temperature
ON
ON
OFF
Lower-side hysteresis
IM 05P01D31-01EN
HYS
HY.UP
HY.LO
Name
Hysteresis (in ON/OFF
control, Position
proportional control, or
Two-position two-level
control)
Heating-side ON/OFF
control hysteresis
(in Heating/cooling
control)
Upper-side hysteresis
(in ON/OFF control)
Lower-side hysteresis
(in ON/OFF control)
Display
level
EASY
EASY
EASY
Setting range
In ON/OFF control or Twoposition two-level control:
0.0 to 100.0% of PV input
range span (EUS)
In Heating/cooling control
or Position proportional
control: 0.0 to 100.0%
Menu symbol
PID
PIDN
EASY
1 to 4
SP
PIDG.
STD
1 to 4
CTL
Note1: The PID number (1 to 4, R) is displayed on Group display while each parameter is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
10
Output (Control and Retransmission) Functions
IM 05P01D31-01EN
10-11
Name
Display
level
Setting range
Menu symbol
MR
Manual reset
EASY
-5.0 to 105.0%
PID
PIDN
EASY
1 to 4
SP
PIDG.
STD
1 to 4
CTL
Note1: The PID number (1 to 4, or R) is displayed on Group display while each parameter is
displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
10-12
IM 05P01D31-01EN
ON
Neutral (OFF)
50%
ON
10
Output (%)
100
Cooling-side
output
Output (%)
100
Heating-side
output
Cooling-side
output
Heating-side
output
0
0
50
0
100(%)
IM 05P01D31-01EN
50
100(%)
10-13
The following shows the case when both the heating side and cooling side are PID
control.
10.9 Setting Hysteresis and Dead Band for Heating/cooling Control Output
Setting Details
Parameter
symbol
HYS
HYSc
DB
Name
Hysteresis (in ON/OFF
control, Position
proportional control, or
Two-position two-level
control)
Heating-side ON/OFF
control hysteresis
(in Heating/cooling
control)
Cooling-side ON/OFF
control hysteresis
Output dead band (in
Heating/cooling control
or Position proportional
control)
Display
level
EASY
Setting range
In ON/OFF control or Twoposition two-level control:
0.0 to 100.0% of PV input
range span (EUS)
In Heating/cooling control
or Position proportional
control: 0.0 to 100.0%
EASY
0.0 to 100.0%
EASY
In Heating/cooling control:
-100.0 to 50.0%
In Position proportional
control: 1.0 to 10.0%
Menu symbol
PID
PIDN
EASY
1 to 4
SP
PIDG.
STD
1 to 4
CTL
Note1: The PID number (1 to 4, or R) is displayed on Group display while each parameter is
displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
10-14
IM 05P01D31-01EN
Position proportional
output relay hysteresis
Direct output (ON)
Neutral (OFF)
10
Reverse
output (ON)
0
(Control computation output value Position signal)
Setting Details
Parameter
symbol
HYS
DB
Name
Hysteresis (in ON/OFF
control, Position
proportional control, or
Two-position two-level
control)
Heating-side ON/OFF
control hysteresis
(in Heating/cooling
control)
Output dead band (in
Heating/cooling control
or Position proportional
control)
Display
level
EASY
Setting range
In ON/OFF control or Twoposition two-level control:
0.0 to 100.0% of PV input
range span (EUS)
In Heating/cooling control
or Position proportional
control: 0.0 to 100.0%
EASY
In Heating/cooling control:
-100.0 to 50.0%
In Position proportional
control: 1.0 to 10.0%
Menu symbol
PID
PIDN
EASY
1 to 4
SP
PIDG.
STD
1 to 4
CTL
Note1: The PID number (1 to 4, R) is displayed on Group display while each parameter is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
10-15
Dead band
Maximum value of
PV input range
200.0C
PV scale
50.0C
150.0C
Retransmission scale
Output range
4 mA
20 mA (output signal)
To Recorder
Setting Details
Parameter
symbol
RTS
10-16
Name
Retransmission
out type of
RET
Display
level
EASY
Setting range
Menu symbol
OFF: Disable
PV1: PV
SP1: SP
OUT1: OUT (Valve opening: 0 to
100 % in Position proportional control)
LPS: 15 V DC loop power supply
OUT
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1: Position proportional output
(internal computed value)
PV: PV terminals analog input
IM 05P01D31-01EN
RTL
O1RS
O1RH
Maximum
value of
retransmission
output scale of
RET
Minimum
value of
retransmission
output scale of
RET
Retransmission
output type of
OUT current
output
Maximum
value of
retransmission
output scale of
OUT current
output
Minimum
value of
retransmission
output scale of
OUT current
output
Display
level
STD
STD
Setting range
When RTS = PV1, SP1, TSP1, PV
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1, SP1, or TSP1,
decimal point position is same as
that of PV input.
When RTS=PV, decimal point position
is same as that of PV input scale.
STD
Same as RTS
STD
STD
Menu symbol
OUT
10
IM 05P01D31-01EN
RET/OUT2 terminal
OUT terminal
10-17
O1RL
Name
Description
Preset output becomes the output when the operation mode is switched from RUN to
STOP.
The preset output is not limited by the output high and low limits.
The preset output is prepared for each PID parameter group, and works according to the
selected PID parameter group.
Control output
100%
Control output obtained by
computation based on
deviation between SP and PV.
The preset output (fixed) applies
according to the preset output.
50%
Preset output
0%
RUN state
STOP state
Time
10-18
IM 05P01D31-01EN
Name
Preset output
Heating-side preset
output (in Heating/
cooling control)
Cooling-side preset
output
Display
level
EASY
EASY
Setting range
Menu symbol
PID
SU.PO
EASY
PIDN
EASY
1 to 4
SP
PIDG.
STD
1 to 4
CTL
Note1: The PID number (1 to 4, R) is displayed on Group display while each parameter is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
IM 05P01D31-01EN
10-19
For ON/OFF output (ON/OFF output or ON/OFF output in Two-position two-level control
or Heating/cooling control), 0.0% is output when the setting value is 0.0% or less and
100.0% is output when 0.1% or more.
10
10.12.2
Setting Output Value When Switched to MAN Mode (Manual Preset Output)
Description
When the operation mode is switched from AUTO to MAN, each of the following can be
selected.
The control output takes over the control output as is.
The control output bumps to the manual preset output.
When the manual preset output is output, the manual operation is possible after the
bump.
Manual preset output is limited by the output high and low limits. (when Output limiter
switch (OLMT) = ON)
Control output
100%
Output bump
Output bumpless
0%
AUTO state
MAN state
Time
When the operation mode is switched from MAN to AUTO, transferred without bump from
the manual output to the control output.
Output limiter: 10.3 Setting Limiter to Control Output
Output limiter switch: 10.4 Disabling Output Limiter in MAN mode
Setting Details
Parameter
symbol
10-20
Name
Display
level
Setting range
Menu symbol
MPON
STD
MPO1 to
MPO5
STD
-5.0 to 105.0%
IM 05P01D31-01EN
10.12.3
Setting Output Value When Error Occurs (Input Error Preset Output)
Description
The 0% control output, 100% control output, or input preset output can be selected and
output as input error preset output in the following conditions.
The input burnout occurs during operation in AUTO mode and RUN mode.
The ADC error occurs during operation in AUTO mode and RUN mode.
However, the manual output becomes the output when the input burnout occurs in MAN
mode and RUN mode.
Setting Details
Parameter
symbol
EPO
Name
Input error preset
output
Display
level
STD
Setting range
0: Preset output
1: 0% output
2: 100% output
Menu symbol
SYS
10
Output (Control and Retransmission) Functions
IM 05P01D31-01EN
10-21
Name
OUT current output
range
RET current output
range
Display
level
STD
STD
Setting range
4-20: 4 to 20 mA,
0-20: 0 to 20 mA,
20-4: 20 to 4 mA,
20-0: 20 to 0 mA
Menu symbol
OUT
10-22
OU.A
OUT terminal
RET.A
RET/OUT2 terminal
IM 05P01D31-01EN
NO
YES
Move to
the estimating type
if a feedback
input burnout
occurs.
NO
10
YES
V.MOD = 0
V.MOD = 2
Control with
feedback input
V.MOD = 1
Control by
valve position estimating type.
Set TR.T.
Control by
valve position estimating type.
Set TR.T.
Adjust a valve position
automatically.
NO
YES
V.AT
Adjust a valve
position manually.
V.RS, V.L, V.H
End
When controlling by estimating type, set TR.T corresponding to the valve characteristic.
IM 05P01D31-01EN
10-23
10.14.1
Description
Position proportional control monitors the control output signals and the feedback signals
from the control valve and regulates to keep the valve opening and the control output
signal in agreement.
Position proportional control (output) operation mode has feedback type and estimating
type.
Setting Details
Parameter
symbol
V.MOD
10.14.2
Name
Valve adjusting
mode
Display
level
STD
Setting range
Menu symbol
Description
The fully-closed and fully-opened positions of a valve can be set automatically by the
feedback input signal from a valve.
The following describes the procedure of adjusting the valve position automatically.
(1) Verify that the wirings are correct.
(2) Set the operation mode to MAN.
(3) Set the automatic valve position adjustment (V.AT) to ON. (V.AT blinks during the
automatic adjustment.)
(4) When the adjustment is completed, V.AT returns to OFF.
When the adjustment fails, VAT.E appears on PV display.
Setting Details
Parameter
symbol
V.AT
10-24
Name
Automatic
valve position
adjustment
Display
level
EASY
Setting range
OFF: Stop automatic adjustment
ON: Start automatic adjustment
Menu symbol
OUT
IM 05P01D31-01EN
10.14.3
Description
The following procedure describes how to adjust valve position manually.
(1) Verify that the wirings are correct.
(2) Set the operation mode to MAN.
(3) Reset the valve position (Set V.RS=ON).
(4) Display the fully-closed valve position setting (V.L), determine the fully-closed
position while holding down the Down arrow ( ) key, and press the SET/ENTER
key.
(5) Display the fully-opened valve position setting (V.H), determine the fully-opened
position while holding down the Up arrow ( ) key, and press the SET/ENTER key.
Setting Details
Parameter
symbol
Display
level
V.RS
Valve position
setting reset
EASY
V.L
Fully-closed valve
position setting
EASY
V.H
Fully-opened valve
position setting
EASY
Setting range
Menu symbol
10
Output (Control and Retransmission) Functions
IM 05P01D31-01EN
Name
10-25
10.14.4
Description
In the estimating type, a traveling time required to fully open the valve from its fullyclosed position is set and valve positions are estimated according to the time consumed
for valve operation.
The valve position estimating type is used when the feedback input of valve positions
cannot be obtained.
(Wiring for feedback input is not necessary.)
The fully-opened side relay keeps ON-state when the output is 100%, and the fullyclosed side relay keeps ON-state when the output is 0%.
Operating Principles
In the estimating type, the valve position is obtained by calculating the virtual feedback
input based on the valve traveling time.
However, the virtual feedback input starts calculation from 50% at power-on.
Setting Details
Parameter
symbol
TR.T
10.14.5
Name
Valve traveling time
Display
level
STD
Setting range
5 to 300 s
Menu symbol
OUT
Description
Only the wiring for resistor or current is necessary for feedback input. There is no setting.
Wiring: 17.4.5 Valve Position Output and Feedback Input Wiring
10-26
IM 05P01D31-01EN
2-wire transmitter
0.4-2 V DC
100
10
Controller
IM 05P01D31-01EN
10-27
Name
RTS
Retransmission
output type of RET
O1RS
Retransmission
output type of OUT
current output
Display
level
EASY
EASY
Setting range
OFF: Disable
PV1: PV
SP1: SP
OUT1: OUT (Valve opening: 0 to
100 % in Position proportional
control)
LPS: 15 V DC loop power supply
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1: Position proportional output
(internal computed value)
PV: PV terminals analog input
Menu symbol
OUT
10-28
RTS
RET/OUT2 terminal
O1RS
OUT terminal
IM 05P01D31-01EN
Number of settings
4 (number of settings)
4 (number of settings)
4 (number of settings)
Alarm setpoint
11
Alarm Functions
Alarm output can be assigned to the unused control relay output or contact output.
Control relay output: 11.5 Setting Alarm Output to Control Relay Terminal
Contact output: 12.2.1 Setting Function of Contact Output
Alarm conditions
Alarm conditions
Alarm conditions
Alarm conditions
Energized/de-energized
AL1
AL2
AL3
Energized/de-energized
DO11
DO12
Energized/de-energized
DO41
DO42
No function
No function
DO45
Energized/de-energized
OUT1
OUT2
No function
* See Appendix 1 and Appendix 2 for presence/absence of the terminals DO11 to DO12, and DO41 to DO45.
* OUT1 and OUT2 can be used for alarm output when the relay outputs are not used for control otuput.
IM 05P01D31-01EN
11-1
PV high limit
alarm output
ON
OFF
PV high limit
alarm setpoint
Alarm hysteresis
PV
PV low limit
alarm setpoint
Alarm hysteresis
OFF
PV low limit
alarm output
ON
Time
Contact type in the figure above: Energized when an event occurs (factory default).
SP high limit
alarm output
ON
OFF
SP high limit
alarm setpoint
Alarm hysteresis
SP
SP low limit
alarm setpoint
SP low limit
alarm output
Alarm hysteresis
OFF
ON
Time
Contact type in the figure above: Energized when an event occurs (factory default).
11-2
IM 05P01D31-01EN
OFF
ON
OFF
Alarm hysteresis
Target setpoint
(SP)
PV
OFF
ON
OFF
Time
Contact type in the figure above: Energized when an event occurs (factory default).
When a negative setpoint is set for the deviation high limit alarm setpoint, the deviation setpoint will be
lower than the SP.
Moreover, when a positive setpoint is set for the deviation low limit alarm setpoint, the deviation setpoint
will be higher than the SP.
Deviation
high and low limits
alarm output
OFF
Target setpoint
(SP)
ON
OFF
ON
OFF
Alarm hysteresis
PV
Alarm hysteresis
Time
Contact type in the figure above: Energized when an event occurs (factory default).
OFF
ON
OFF
ON
Alarm hysteresis
Target setpoint
(SP)
PV
Alarm hysteresis
Time
Contact type in the figure above: Energized when an event occurs (factory default).
IM 05P01D31-01EN
11-3
Alarm Functions
11
OFF
ON
Alarm hysteresis
OFF
SP changing
SP changing
ON
Time
SP changing
SP changing
Contact type in the figure above: Energized when an event occurs (factory default).
Target SP Deviation High Limit Alarm and Target SP Deviation Low Limit Alarm
Deviation high limit
alarm output
Target SP
(SP)
OFF
ON
OFF
Alarm hysteresis
PV
Alarm hysteresis
OFF
ON
OFF
Time
Contact type in the figure above: Energized when an event occurs (factory default).
* Target SP: a set target setpoint. When the ramp-rate is set, it becomes a final target setpoint.
When a negative setpoint is set for the deviation high limit alarm setpoint, the deviation setpoint will be
lower than the target SP.
Moreover, when a positive setpoint is set for the deviation low limit alarm setpoint, the deviation setpoint
will be higher than the target SP.
11-4
IM 05P01D31-01EN
OFF
Target SP
(SP)
ON
OFF
ON
OFF
Alarm hysteresis
PV
Alarm hysteresis
Time
Contact type in the figure above: Energized when an event occurs (factory default).
OFF
ON
OFF
ON
11
Alarm hysteresis
Deviation within high
and low limits alarm setpoint
PV
Alarm hysteresis
Time
Contact type in the figure above: Energized when an event occurs (factory default).
IM 05P01D31-01EN
11-5
Alarm Functions
Target SP
(SP)
Control Output High Limit Alarm and Control Output Low Limit Alarm
In Heating/cooling control, alarms are heating-side control output high limit alarm and
heating-side control output low limit alarm.
ON
OFF
Alarm hysteresis
Control output (OUT)
Alarm hysteresis
OFF
ON
Time
Contact type in the figure above: Energized when an event occurs (factory default).
ON
Cooling-side
Control output high limit
alarm setpoint
OFF
Alarm hysteresis
Cooling-side control output (COUT)
Cooling-side
Control output low limit
alarm setpoint
Cooling-side
Control output low limit
alarm output
Alarm hysteresis
OFF
ON
Time
Contact type in the figure above: Energized when an event occurs (factory default).
11-6
IM 05P01D31-01EN
Analog Input PV High Limit Alarm and Analog Input PV Low Limit Alarm
These alarms monitor the input value after the analog input computation process (entrance
to the input ladder calculation) is completed.
Analog input
PV high limit
alarm output
ON
Analog input
PV high limit
alarm setpoint
OFF
Alarm hysteresis
Analog input
Analog input
PV low limit
alarm setpoint
Analog input
PV low limit
alarm output
Alarm hysteresis
OFF
ON
11
Time
Alarm Functions
Contact type in the figure above: Energized when an event occurs (factory default).
IM 05P01D31-01EN
11-7
Feedback Input High Limit Alarm and Feedback Input Low Limit Alarm
Feedback input
high limit
alarm output
ON
OFF
Feedback input
high limit
alarm setpoint
Alarm hysteresis
Feedback input
Feedback input
low limit
alarm setpoint
Alarm hysteresis
Feedback input
low limit
alarm output
OFF
ON
Time
Contact type in the figure above: Energized when an event occurs (factory default).
PV Velocity Alarm
PV velocity
alarm output
OFF
ON
OFF
ON
OFF
PV
Exceeds the velocity
VT
VT
VT
VT
VT
VT
Monitors the variation of the measured value for 2 points by the time
interval set in VT.
Time
Velocity alarm
setpoint
Velocity alarm
time setpoint
VT1 to VT8
Velocity alarm
setpoint
Velocity alarm
time setpoint
VT1 to VT8
Contact type in the figure above: Energized when an event occurs (factory default).
The PV velocity alarm function does not work the alarm hysteresis, the stand-by action
and the alarm delay timer functions.
11-8
IM 05P01D31-01EN
FAIL output
When the FAIL condition is caused (faulty MCU or system data error), DO (alarm output)
turned off regardless of contact type.
The FAIL output does not work the alarm latch, the energized/de-energized and the
stand-by action functions.
Stand-by Action
The following shows the behavior of an alarm with the stand-by action at power ON.
C
Treated
as normal
Normal
Abnormal
The alarm output
turns on.
PV low limit alarm setpoint
Power-on
IM 05P01D31-01EN
Time
11-9
11
Alarm Functions
The stand-by action is a function for ignoring the alarm condition and keeps the alarm off
until the alarm condition is removed. Once the alarm condition is removed, the stand-by
action is cancelled.
It is effective in the following cases where;
The power is turned on
SP is changed
SP number is switched (however, except for remote setpoint) (The SP must be
changed.)
The alarm type is changed
Forced stand-by via communication
The alarm latch function is a function for keeping the alarm output (keeping the alarm
output on) after entering the alarm condition (alarm output is turned on) until an order to
release the alarm latch is received.
The alarm latch function has the following four types of action.
Latch 1
Cancels the alarm output when an order to release the alarm latch is received. (Alarm
output OFF.)
However, an order to release the alarm latch is ignored if the order is received during
alarm condition.
Latch 2
Always forces cancelling of the alarm output when an order to release the alarm latch
is received. (Alarm output OFF)
Latch 3
Cancels the alarm output when an order to release the alarm latch is received or when
the alarm condition is removed. (Alarm output OFF.)
Latch 4
Cancels the alarm output when an order to release the alarm latch is received. (Alarm
output OFF.)
However, cancels the alarm output for the duration of the sampling period (control
period) if an order to release the alarm latch is received during alarm condition. (Alarm
output OFF)
PV high limit
alarm setpoint
Alarm hysteresis
PV
PV high limit
alarm indicator
Lit
Unlit
Lit
Unlit
ON
OFF
ON
OFF
ON
OFF
Release order
ON
OFF
Release order
ON
OFF
Release order
ON
OFF
Release order
ON
Release order
ON
OFF
Release order
ON
OFF
Release order
ON
Release order
ON
OFF during the
sampling period
Time
Contact type in the figure above: Energized when an event occurs (factory default).
11-10
IM 05P01D31-01EN
The alarm latch function can be cancelled by the user function key, via communication/
ladder program, or by contact input.
Cancelling the alarm latch function cancels all latched alarm outputs.
Release by user function key: 13.2 Assigning Function to User Function Key and A/M key
Release by contact input: 12.1.1 Setting Contact Input Function
Release via communication: UTAdvanced Series Communication Interface Users Manual
PV high limit
alarm setpoint
Alarm hysteresis
Alarm hysteresis
PV low limit
alarm setpoint
PV
Lit
Unlit
Unlit
Lit
ON
Unlit
Unlit
Lit
OFF
ON
ON
Release order
ON
Release order
OFF
Release order
Unlit
OFF
Release order
ON
OFF
Release order
Time
Contact type in the figure above: Energized when an event occurs (factory default).
The contact output and display lamp (EV) are usually output and displayed according
to the setpoint of the alarm type. However, the alarm conditions (operations) of the
normal action, and latch action can be assigned to the contact output and display lamp
(EV), regardless of the setpoint of the alarm type. (Two operations can be assigned
simultaneously.)
Display lamp action: 13.1 Setting Display Functions
Contact output action: 12.2.1 Setting Function of Contact Output
IM 05P01D31-01EN
11-11
11
Alarm Functions
Release order
PV low limit alarm output
of latch 2 action
Lit
Display
level
Name
Setting range
AL1 to AL4
Alarm-1 to -4 type
EASY
VT1 to VT4
EASY
00.01 to 99.59
(minute.second)
Menu symbol
ALRM
Note1: The initial values of the parmeters AL1 to AL4 and VT1 to VT4 are "4". The number of alarms
can be changed using the parameter ALNO.
The following shows the example of setting PV high limit (01), With stand-by action (1),
De-energized (1), and Latch 1 action (1).
Symbol
Name
Disable
Alarm type
Stand-by action
Energized/de-energized
Latch
Latch action
(Note 1)
Alarm
type
- (Note 2)
- (Note 2)
- (Note 2)
00
PV high limit
0/1/2/3/4
0/1
0/1
01
PV low limit
0/1/2/3/4
0/1
0/1
02
SP high limit
0/1/2/3/4
0/1
0/1
03
SP low limit
0/1/2/3/4
0/1
0/1
04
0/1/2/3/4
0/1
0/1
05
0/1/2/3/4
0/1
0/1
06
0/1/2/3/4
0/1
0/1
07
0/1/2/3/4
0/1
0/1
08
0/1/2/3/4
0/1
0/1
09
0/1/2/3/4
0/1
0/1
10
0/1/2/3/4
0/1
0/1
11
0/1/2/3/4
0/1
0/1
12
0/1/2/3/4
0/1
0/1
13
0/1/2/3/4
0/1
0/1
14
0/1/2/3/4
0/1
0/1
15
0/1/2/3/4
0/1
0/1
16
0/1/2/3/4
0/1
0/1
17
0/1/2/3/4
0/1
0/1
18
0/1/2/3/4
0/1
0/1
19
0/1/2/3/4
0/1
0/1
20
0/1/2/3/4
0/1
0/1
27
0/1/2/3/4
0/1
0/1
28
PV velocity
0/1/2/3/4
0/1
- (Note 2)
29
Fault diagnosis
0/1/2/3/4
0/1
- (Note 2)
30
- (Note 2)
- (Note 2)
- (Note 2)
31
FAIL
11-12
IM 05P01D31-01EN
Name
Number of alarm
groups
Display
level
PRO
Setting range
1 to 4
Menu symbol
CTL
11
Alarm Functions
IM 05P01D31-01EN
11-13
ON
OFF
Hysteresis
PV
Closed (ON)
Closed (ON)
Open
Open
Alarm-1 setpoint:
100C (example)
Alarm-1 setpoint:
100C (example)
PV
PV
Alarm ON
OFF
ON
OFF
Alarm ON
ON
OFF
OFF
Time
Time
Setting Details
11-14
Parameter
symbol
Name
HY1 to HY4
Alarm-1 to -4
hysteresis
Display
level
EASY
Setting range
Sets the hysteresis setpoint as a
display value.
-19999 to 30000 (set it within the
input range)
The decimal point position
depends on the input type.
Menu symbol
ALRM
IM 05P01D31-01EN
PV high limit
alarm setpoint
Alarm hysteresis
PV
PV high limit
alarm state
(without
delay timer)
Unlit
Elapsed time
Lit
11
Elapsed time
PV high limit
alarm output
OFF
ON
Time
Contact type in the figure above: Energized when an event occurs (factory default).
The alarm Off-delay timer is a function for turning off the alarm when the alarm condition
is removed (normal condition), and the timer starts and the set time elapses.
The timer is reset if the alarm condition occurs again while the timer is running. The
alarm is not cancelled.
Setting Details
Parameter
symbol
DYN1 to
DYN4
DYF1 to
DYF4
IM 05P01D31-01EN
Name
Alarm-1 to -4 On-delay
timer
Alarm-1 to -4 Off-delay
timer
Display
level
STD
PRO
Setting range
Menu symbol
11-15
Alarm Functions
Name
Display
level
OR.S
STD
OR.D
PRO
OR2.S
OR2.D
OUT2 relay
function selection
OUT2 relay contact
type
Setting range
Same as the setpoint for the
contact output function.
See 12.2.1, Setting Function of
Contact Output.
0: Closes the contact when an
event occurs
1: Opens the contact when an
event occurs.
STD
Same as OR.S.
PRO
Same as OR.D
Menu symbol
ALM
11-16
OR.S, OR.D
OUT terminal
OR2.S, OR2.D
OUT2 terminal
IM 05P01D31-01EN
Name
Alarm mode
Display
level
STD
Setting range
0: Always active
1: Not active in STOP mode
2: Not active in STOP or MAN
mode
Menu symbol
ALRM
11
Alarm Functions
IM 05P01D31-01EN
11-17
Cycle time
ON
ON
OFF
Turn off the power
supply for heater
after the cycle time in
progress elapses.
130 ms
Control
output
75%
0%
RUNSTOP
However, preset output = 0% in STOP.
Time
11-18
IM 05P01D31-01EN
Temperature input
CT1
Control output
CTL-6-S-H
(Current sensor)
Alarm Functions
SSR
11
TC
Single-phase heater
Electric furnace
CT1
CT2
Control output
CTL-6-S-H
(Current sensor)
TC
R
S
T
SSR
Three-phase heater
Electric furnace
IM 05P01D31-01EN
11-19
The heater break alarm function can be used only for ON/OFF output (relay output), for
time proportional output (relay output, voltage pulse output) or for current output.
Heater current value is detected every 200 ms.
Setting Details
Parameter
symbol
HB1.S,
HB2.S
Name
CT1.T,
CT2.T
HDN1,
HDN2
HDF1,
HDF2
HB1.D,
HB2.D
HB1, HB2
Display
level
Setting range
EASY
0: Heater current
measurement
1: Heater break alarm
(Heating-side)
2: Cooling-side heater break
alarm
EASY
EASY
1 to 3300
STD
PRO
PRO
Menu symbol
HBA
Note1: In cases where the current transformer manufactured by U.R.D Co., Ltd. are used, set the
following value for the CT coil winding number ratio.
CTL-6-S-H: 800
CTL-12L-30: 3000
11-20
IM 05P01D31-01EN
Operation
Remark
ON
AUTO
OFF
MAN
Operation
Remark
REMOTE
OFF
LOCAL
Operation
Remark
ON
STOP
OFF
RUN
Operation
Remark
OFFON
Switch to AUTO
ONOFF
IM 05P01D31-01EN
Operation
Remark
OFFON
Switch to MAN
ONOFF
12-1
12
Contact Input/Output Functions
ON
Operation
Remark
OFFON
Switch to REMOTE
ONOFF
Operation
Remark
OFFON
Switch to LOCAL
ONOFF
Operation
Remark
OFFON
Starts auto-tuning
ONOFF
Stops auto-tuning
Operation
Remark
OFFON
ONOFF
Releasing the latch function releases all latched contact (alarm) outputs.
Operation
Remark
OFFON
ONOFF
12-2
Operation
Remark
OFFON
Interrupt-displays the message Pressing the DISPLAY key erases the message.
ONOFF
IM 05P01D31-01EN
Operation
Remark
ON
Red color
OFF
White color
Contact status
SP.B2
SP.B1
SP.B0
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
Contact status
SP.B2
SP.B1
SP.B0
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
*1: 1 when the contact input is turned on and 0 when turned off.
*2: Contact input is turned off when the bit of SP number is not assigned to the contact input.
Setting Details
Parameter
symbol
SP.BC
IM 05P01D31-01EN
Name
Bit changing method of
SP number
Display
level
STD
Setting range
0: Status switch 1
1: Status switch 2
Menu symbol
DI.NU
12-3
12
Contact Input/Output Functions
*1: 1 when the contact input is turned on and 0 when turned off.
*2: SP number can be switched by keystroke or via communication when all contact inputs of SP.B0
to SP.B2 are turned off.
*3: SP number cannot be switched by keystroke or via communication when any contact input of
SP.B0 to SP.B2 is turned on.
*4: The contact input is turned off when the bit of SP number is not assigned to the contact input.
*5: The immediately preceding SP number is held when all contact inputs are turned off.
Contact status
PN.B2
PN.B1
PN.B0
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
*1: 1 when the contact input is turned on and 0 when turned off.
*2: PID number can be switched by keystroke or via communication when all contact inputs of
PN.B0 to PN.B3 are turned off.
*3: PID number cannot be switched by keystroke or via communication when any contact input of
PN.B0 to PN.B3 is turned on.
*4: The contact input is turned off when the bit of PID number is not assigned to the contact input.
Contact status
PN.B2
PN.B1
PN.B0
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
*1: 1 when the contact input is turned on and 0 when turned off.
*2: Contact input is turned off when the bit of PID number is not assigned to the contact input.
Setting Details
Parameter
symbol
PN.BC
12-4
Name
Bit changing method of
PID number
Display
level
PRO
Setting range
0: Status switch 1
1: Status switch 2
Menu symbol
DI.NU
IM 05P01D31-01EN
Manual preset
output number
MP.B2
MP.B1
MP.B0
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
*1: 1 when the contact input is turned on and 0 when turned off.
*2: Manual preset output number can be switched by keystroke via communication when all contact
inputs of MP.B0 to MP.B2 are turned off.
*3: Manual preset output number cannot be switched by keystroke or via communication when any
contact input of MP.B0 to MP.B2 is turned on.
*4: The contact input is turned off when the bit of manual preset output number is not assigned to
the contact input.
MP.B1
MP.B0
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
12
Setting Details
Parameter
symbol
MP.BC
IM 05P01D31-01EN
Name
Bit changing method of
manual preset output
number
Display
level
PRO
Setting range
0: Status switch 1
1: Status switch 2
Menu symbol
DI.NU
12-5
Manual preset
output number
Operation
Description
ON
Status
OFF
OFF
Rising edge
ON
Rising edge
OFF
OFF
Detection time:
Control period + 50 ms
Falling edge
ON
Falling edge
OFF
OFF
Detection time:
Control period + 50 ms
12-6
IM 05P01D31-01EN
AUTO/MAN switch
Display
level
R/L
REMOTE/LOCAL switch
STD
STOP/RUN switch
STD
AUTO
Switch to AUTO
STD
MAN
Switch to MAN
STD
Switch to REMOTE
STD
Switch to LOCAL
STD
AT
STD
LAT
Latch release
STD
LCD
STD
PVRW
PV red/white switch
STD
MG1
PRO
MG2
PRO
MG3
PRO
MG4
PRO
SP.B0
Bit-0 of SP number
EASY
SP.B1
Bit-1 of SP number
EASY
SP.B2
Bit-2 of SP number
EASY
PN.B0
STD
PN.B1
STD
PN.B2
STD
MP.B1
MP.B2
Menu symbol
DI.SL
12
Contact Input/Output Functions
REM
LCL
Setting range
STD
S/R
MP.B0
IM 05P01D31-01EN
Name
DI.NU
STD
STD
STD
12-7
Setpoint
DI1
5025
DI2
5026
Additional DI
(For Standard model)
When Type 2 code is 1
DI symbol
Setpoint
DI symbol
Setpoint
DI11
5041
DI11
5041
DI12
5042
DI12
5042
DI13
5043
DI14
5044
DI15
5045
Setpoint
DI1
5025
DI2
5026
Additional DI
(For Standard model)
When Type 2 code is 2
DI symbol
Setpoint
DI11
5041
DI12
5042
Additional DI
(For Detailed model)
When Option code is /X1
DI symbol
12-8
Setpoint
Setpoint
DI11
5041
DI41
5089
DI12
5042
DI42
5090
DI13
5043
DI43
5091
DI14
5044
DI44
5092
DI15
5045
DI45
5093
IM 05P01D31-01EN
Name
Display
level
DI1.D
PRO
DI2.D
PRO
Setting range
Menu symbol
Name
Display
level
DI1.D
PRO
DI2.D
PRO
DI3.D
PRO
DI4.D
PRO
DI5.D
PRO
Setting range
Menu symbol
12
IM 05P01D31-01EN
12-9
Note1: When each parameter is displayed, the terminal area (E1 to E4) is displayed on Group
display according to the suffix code and optional suffix code. n denotes the position of the
terminal area. (n = 1 to 4)
Name
Display
level
AL1.S
STD
AL2.S
STD
AL3.S
STD
Setting range
Menu symbol
ALM
Name
Display
level
DO1.S
STD
DO2.S
STD
DO3.S
STD
DO4.S
STD
DO5.S
STD
Setting range
Menu symbol
DO
Note1: When each parameter is displayed, the terminal area (E1 to E4) is displayed on Group
display according to the suffix code and optional suffix code. n denotes the position of the
terminal area. (n = 1 to 4)
Name
OUT relay function
selection
OUT2 relay function
selection
Display
level
STD
STD
Setting range
Menu symbol
ALM
12-10
IM 05P01D31-01EN
Function
Alarm status
Alarm output
status
4321
4353
Alarm 1
4322
4354
Alarm 2
4323
4355
Alarm 3
4325
4357
Alarm 4
Alarm status: The internal alarm status is turned on when an alarm occurs and
turned off in normal condition
Alarm output status: Contact output status when an alarm occurs (ON in alarm
condition and OFF in normal condition)
Function
4385
4417
4449
4481
Alarm 1
4386
4418
4450
4482
Alarm 2
4387
4419
4451
4483
Alarm 3
4389
4421
4453
4485
Alarm 4
Alarm output latch 1, 2, 3, and 4 status: ON in the latch status of the contact output
when an alarm occurs and OFF in the latch release status of the contact output in
normal condition
IM 05P01D31-01EN
12-11
12
Function
4705
PARAMETER key
4706
DISPLAY key
4707
4708
4709
SET/ENTER key
4710
Up arrow key
4711
Left key
4712
F2 key
4713
F1 key
4714
A/M key
4715
Fn key
ON
Contact status
Key is pressed
OFF
Function
ON
Contact status
4193
AUTO/MAN
4194
Remote/Local
4195
STOP/RUN
4201
4207
During auto-tuning
4209
4210
4213
Valve is open
4214
Valve is closed
4256
FAIL output
OFF
MAN
AUTO
Remote
Local
STOP
RUN
Tracking ON
Tracking OFF
During AT
During adjustment
During operation by
feedback input
Open
Closed
Normal status
FAIL status
12-12
Function
ON
Contact status
OFF
4529
Alarm occurs
Normal
4530
Alarm occurs
Normal
4769
With interruption
Without interruption
4770
With interruption
Without interruption
4771
With interruption
Without interruption
4773
With interruption
Without interruption
IM 05P01D31-01EN
Function
4065
4073
4070
4081
4082
Feedback resistance/current
burnout
Automatic valve position
adjustment error
4097
4101
PV input over-scale
4102
PV input under-scale
4111
ON
Contact status
Error occurs
OFF
Normal
4002
4003
4005
4006
4017
4018
4019
4021
4022
4009
Faulty FRAM
ON
Contact status
Error occurs
OFF
12
Normal
IM 05P01D31-01EN
Function
12-13
Name
Display
level
AL1.D
PRO
AL2.D
PRO
AL3.D
PRO
Setting range
0: When the event of assigned
function occurs, the contact
output is closed.
1: When the event of assigned
function occurs, the contact
output is opened.
Menu symbol
ALM
Name
Display
level
DO1.D
PRO
DO2.D
PRO
DO3.D
PRO
DO4.D
PRO
DO5.D
PRO
Setting range
0: When the event of assigned
function occurs, the contact
output is closed.
1: When the event of assigned
function occurs, the contact
output is opened.
Menu symbol
DO
Note1: When each parameter is displayed, the terminal area (E1 to E4) is displayed on Group
display according to the suffix code and optional suffix code. n denotes the position of the
terminal area. (n = 1 to 4)
Name
Display
level
OR.D
PRO
OR2.D
PRO
Setting range
Menu symbol
12-14
IM 05P01D31-01EN
Link to Alarm
The PV display color changes by linking to the alarm 1 or alarm 2.
The following is an example of operation linking to alarm 1.
Set the alarm-1 type to PV high limit alarm and alarm-1 setpoint to 80C.
When the active color PV display switch is set to2, PV display color changes from white
to red if PV exceeds the alarm-1 setpoint.
The red-to-white switching action can be set.
C
Alarm-1 hysteresis
Alarm-1 setpoint
A1 = 80C
75C
13
PV
PV color: red
PV color: white
Time
Change by Deviation
The PV display color changes by deviation (PV SP).
Set the PV color change high limit to 10C and the PV color change low limit to 5C
as deviation band for the current target setpoint 50C. PV display color changes from
white to red if PV is out of the deviation.
The red-to-white switching action can be set. There is no hysteresis.
C
60C
Target setpoint
SP = 50C
45C
IM 05P01D31-01EN
PV color: white
PV color: red
PV color: red
PV color: white
Time
13-1
PV color: white
Link to PV
The PV display color changes by linking to PV.
Set the PV color change high limit to 70C and the PV color change low limit to 20C.
PV display color changes from white to red if PV is out of the range.
The red-to-white switching action can be set. There is no hysteresis.
C
PV color: white
PV color: red
Time
PV color: white
PV color: red
SP color: orange
(SP color cannot be changed.)
Link to DI
The PV display color changes by linking to DI (ON/OFF).
The following is an example for changing the display color by a state of DI1.
Set the parameter PCMD=10, and PVRW=5025.
PV display color is red when DI1=ON, and is white when DI1=OFF.
PVRW: PV red/white switch (Menu: DI.SL)
13-2
IM 05P01D31-01EN
PCMD
Name
Active color PV
display switch
Display
level
EASY
PCH
PV color change
high limit
EASY
PCL
PV color change
low limit
EASY
Setting range
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF:
white, Alarm ON: red)
3: Link to alarm 1 (Alarm OFF:
red, Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm
OFF: white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm
OFF: red, Alarm ON: white)
6: PV limit (Within range: white,
Out of range: red)
7: PV limit (Within range: red, Out
of range: white)
8: SP deviation (Within deviation:
white, Out of deviation: red)
9: SP deviation (Within deviation:
red, Out of deviation: white)
10: Link to DI (ON: red, OFF:
white)
Menu symbol
DISP
13
Display, Key, and Security Functions
IM 05P01D31-01EN
13-3
Status display
Setting Details
Parameter
symbol
PV.D
SP.D
STS.D
13-4
Name
PV display area ON/
OFF
Setpoint display area
ON/OFF
Status display area
ON/OFF
Display
level
Setting range
Menu symbol
PRO
PRO
OFF: Nondisplay
ON: Display
DISP
PRO
IM 05P01D31-01EN
SELECT Display
SP Display
OUT Display
Setting Details
Parameter
symbol
SELECT Display-1 to
-5 registration
Display
level
STD
Setting range
Menu symbol
For D register numbers, see sections 8.4.2 and 8.4.5 in the UTAdvanced Series Communication
Interface Users Manual.
D Resistor
Number
2301 to 2500
Operation Mode
Parameters
Description
Operation Mode
2501 to 2700
2701 to 2800
SP-related settings
2801 to 2900
2901 to 3000
Operation Parameters
3001 to 3500
PID settings
3501 to 3600
4701 to 4800
IM 05P01D31-01EN
Category
P Parameters
P parameters
Reference in
Communication
Interface
User's Manual
Section 8.4.2
Section 8.4.3
Section 8.4.5
13-5
13
Display, Key, and Security Functions
CS1 to CS5
Name
Name
Display
level
Setting range
Setting range: 4001 to 6304
OFF: Disable
4321: Link to alarm 1 (Lit when the alarm occurs)
4322: Link to alarm 2 (Lit when the alarm occurs)
4323: Link to alarm 3 (Lit when the alarm occurs)
4325: Link to alarm 4 (Lit when the alarm occurs)
Menu
symbol
EV1 to
EV4
EV1 to EV4
display
condition
registration
PRO
DISP
13-6
IM 05P01D31-01EN
System error
4065 to 4128
Input error
4129 to 4192
Free area
4193 to 4256
Operation mode
4257 to 4320
Free area
4321 to 4384
Alarm
4385 to 4528
Alarm latch
4529 to 4576
4577 to 4640
4641 to 4704
Free area
4705 to 4768
Key
4769 to 4832
Display
4833 to 5024
Free area
5025 to 5152
Input relay
5153 to 5280
Output relay
5281 to 5408
5409 to 5472
Special relay
5473 to 5536
Free area
5537 to 5792
Internal relay
5793 to 6048
Free area
6305 to 6432
DI terminals
6433 to 6560
DO terminals
Reference in
Communication Interface
User's Manual
Section 9.3.1
Section 9.3.2
13
Section 9.3.3
IM 05P01D31-01EN
Description
13-7
CS Menu Display
13-8
Registered
SELECT Parameter Display
IM 05P01D31-01EN
Name
Display
level
SELECT parameter-10
to -19 registration
PRO
Setting range
Menu symbol
OFF: No registration
D register number (2301 to
5000)
CSEL
For D register numbers, see sections 8.4.2 and 8.4.5 of UTAdvanced Series Communication
Interface Users Manual.
D Resistor
Number
2301 to 2500
Category
Operation Mode
Parameters
Description
Operation Mode
2501 to 2700
2701 to 2800
SP-related settings
2801 to 2900
2901 to 3000
Operation Parameters
3001 to 3500
PID settings
3501 to 3600
P parameters
Reference in
Communication
Interface
User's Manual
Section 8.4.2
Section 8.4.3
Section 8.4.5
13
Display, Key, and Security Functions
IM 05P01D31-01EN
13-9
0%
PV, SP
0%
100%
More than 100%
Less than 0%
Deviation
When the deviation display band (BDV) is 10%:
0%
Deviation negative side and deviation positive side are displayed by 10% increment of deviation.
Indication is unlit when SP (deviation display band (BDV)) PV SP + (deviation display band (BDV)).
IN = TC Type K -270.0 to 1370.0C
BDV = 82C (5%), SP = 500.0C, PV = 800.0C
Deviation negative side
992.1C or more
910.1 to 992.0C
828.1 to 910.0C
746.1 to 828.0C
664.1 to 746.0C
582.1 to 664.0C
356.0 to 417.9C
254.0 to 355.9C
172.0 to 253.9C
90.0 to 171.9C
8.0 to 89.9C
to 7.9C
All indications are unlit when the deviation is 418 PV 582C.
Valve Opening
0%
13-10
100%
H side
IM 05P01D31-01EN
Name
Display
level
Setting range
Menu symbol
BAR1
Bar-graph display
registration
STD
0: Disable
1:OUT, Heating-side OUT, Internal
value in Position proportional
control
2: Cooling-side OUT
3: PV
4: SP
DISP
5: Deviation
6 to 16: Disable
17: Feedback input (valve opening)
18: PV terminals analog input
BDV
Bar-graph
deviation display
band
STD
Note1: The bar-graph deviation display band (BDV) is enabled when the deviation is set to the
BAR1.
13
Display, Key, and Security Functions
IM 05P01D31-01EN
13-11
The following shows the example of with and without least significant digit
PV display
With least significant digit
1.4999
1.499
1.5000
1.500
1.9999
1.999
2.0000
2.000
3000.0
3000
3000.9
3000
3001.0
3001
Setting Details
Parameter
symbol
MLSD
13-12
Name
Least significant digital
mask of PV display
Display
level
STD
Setting range
Menu symbol
IM 05P01D31-01EN
13
Setting Details
ECO
IM 05P01D31-01EN
Name
Economy mode
Display
level
STD
Setting range
Menu symbol
OFF: Disable
1: Economy mode ON (All
indications except PV display
OFF)
DISP
2: Economy mode ON (All
indications OFF)
3: Brightness 10 % (all indications)
13-13
Parameter
symbol
HOME
13-14
Name
Home Operation
Display setting
Display
level
PRO
Setting range
Menu symbol
SP1: SP Display
OUT1: OUT Display
HCO: Heating/cooling OUT Display
VP: Valve Position Display
MV: Position Proportional
Computation Output Display
PID1: PID Number Display
DISP
HC1: Heater Break Alarm-1
Current Display
HC2: Heater Break Alarm-2
Current Display
PV: PV Analog Input Display
CS1 to CS5: SELECT Display 1 to 5
IM 05P01D31-01EN
13.1.10
Description
Using the message function and turning the contact input on/off, the message registered
beforehand can be displayed on PV display by interrupt.
The message is registered using LL50A Parameter Setting Software.
The messages are limited to 20 alphanumeric characters. A maximum of four messages
can be registered.
If a number of messages occur simultaneously, the priority is as follows:
(high) MG1>MG2>MG3>MG4 (low)
Message registration: LL50A Parameter Setting Software Users Manual
Registration of contact input: 12.1.1 Setting Contact Input Function
Registration symbols: 3.3 List of Display Symbols
Operation Display
13
13.1.11
Description
The guide display language that appears when the parameter or the menu is displayed
can be switched.
Setting Details
Parameter
symbol
LANG
IM 05P01D31-01EN
Name
Guide display
language
Display
level
EASY
Setting range
ENG: English
FRA: French
GER: German
SPA: Spanish
Menu symbol
SYS
13-15
13.1.12
Description
The scroll speed can be changed when the guide for the parameter or menu is displayed.
Setting Details
Parameter
symbol
SPD
13.1.13
Name
Scroll speed
Display
level
PRO
Setting range
(Slow) 1 to 8 (Quick)
Menu symbol
DISP
Description
The guide display that appears when the parameter or the menu is displayed can be
switched.
The guide display can be turned on and off by the Fn key in the Menu Display and
Parameter Setting Display.
Setting Details
Parameter
symbol
GUID
13.1.14
Name
Display
level
STD
Setting range
OFF: Nondisplay
ON: Display
Menu symbol
DISP
Description
The Display will automatically revert to the Operation Display if no keys are pressed for 5
minutes in Menu Display or Parameter Setting Display.
Setting Details
Parameter
symbol
OP.JP
13-16
Name
Automatic return to
Operation Display
Display
level
PRO
Setting range
ON: Automatically returned to
the Operation Display.
OFF: Not automatically
returned to the Operation
Display.
Menu symbol
DISP
IM 05P01D31-01EN
Brightness
White brightness
adjustment of PV
display
Red brightness
adjustment of PV
display
Display
level
EASY
PRO
PRO
B.SP
Brightness adjustment
of Setpoint display
B.BAR
Brightness adjustment
of Bar-graph display
PRO
B.STS
Brightness adjustment
of Status indicator
PRO
D.CYC
PRO
PRO
Setting range
Menu symbol
(Dark) 1 to 5 (Bright)
Adjusts the white brightness
of PV display.
(Dark) -4 to 4 (Bright)
Adjusts the red brightness of
PV display.
(Dark) -4 to 4 (Bright)
Adjusts the brightness of SP
display.
(Dark) -4 to 4 (Bright)
Adjusts the brightness of SP
display.
(Dark) -4 to 4 (Bright)
Adjusts the brightness of
Status indicator.
(Dark) -4 to 4 (Bright)
1: 100 ms
2: 200 ms
3: 500 ms
4: 1 s
5: 2 s
DISP
13
Display, Key, and Security Functions
IM 05P01D31-01EN
Name
13-17
13-18
IM 05P01D31-01EN
Setpoint
OFF
Display
level
Name
F1 to Fn
EASY
A/M
PRO
Function
Unassigned
Setting range
Menu symbol
KEY
Action
F1
Availability (Note 1)
F2
Fn
A/M
A/M
AUTO/MAN switch
R/L1
REM/LCL switch
S/R
STOP/RUN switch
AUTO
Switch to AUTO
MAN
Switch to MAN
Switch to REM
LCL1
Switch to LCL
STOP
Switch to STOP
RUN
Switch to RUN
AT
LTUP
LTDN
BRI
LCD
LAT
PID
IM 05P01D31-01EN
13-19
13
Display, Key, and Security Functions
REM1
13-20
IM 05P01D31-01EN
Name
Password setting
Display
level
EASY
Setting range
0 (No password) to 65535
Menu symbol
SYS
13
Setting Details
Parameter
symbol
LEVL
IM 05P01D31-01EN
Name
Display
level
Parameter display
level
EASY
Setting range
EASY: Easy setting mode
STD: Standard setting mode
PRO: Professional setting mode
Menu symbol
LVL
13-21
Description
Name
Display
level
CTL
PRO
PV
PRO
MPV
PRO
OUT
PRO
HBA
PRO
R485
PRO
ETHR
PRO
PROF
PRO
DNET
PRO
CC-L
PRO
KEY
PRO
DISP
PRO
CSEL
PRO
KLOC
PRO
DI.SL
PRO
DI.NU
PRO
DI.D
PRO
ALM
PRO
DO
PRO
I/O
PRO
SYS
PRO
INIT
PRO
VER
PRO
LVL
PRO
MODE
PRO
CS
PRO
SP
PRO
SPS
PRO
ALRM
PRO
PVS
PRO
PID
PRO
TUNE
PRO
ZONE
PRO
PPAR
PRO
Setting range
Menu symbol
OFF: Display
ON: Nondisplay
MLOC
OFF: Display
ON: Nondisplay
MLOC
Note1: When each parameter is displayed, the terminal area (E1 to E4) is displayed on Group
display according to the suffix code and optional suffix code.
13-22
IM 05P01D31-01EN
Name
DATA
A/M
Display
level
STD
STD
Setting range
OFF: Unlock
ON: Lock
Menu symbol
KLOCK
Setting Details
Parameter
symbol
Display
level
U.SP
SP Display lock
PRO
U.OUT
PRO
U.HCO
PRO
U.VP
PRO
U.MV
Position Proportional
Computation Output Display
lock
PRO
U.PID
PRO
U.HC
PRO
U.PV
PRO
Setting range
OFF: Display
ON: Nondisplay
Menu symbol
13
Display, Key, and Security Functions
IM 05P01D31-01EN
Name
KLOC
13-23
Setting Details
Parameter
symbol
COM.W
Name
Communication write enable/
disable
Display
level
STD
Setting range
OFF: Enable
ON: Disable
Menu symbol
KLOC
13-24
IM 05P01D31-01EN
Display
level
Name
KEY
Key status
PRO
X000
PRO
X100
PRO
X400
PRO
Y000
PRO
Y100
PRO
Y400
PRO
Read only.
I/O
Note: When each parameter is displayed, the terminal area (E1 to E4) is displayed on Group display
according to the suffix code and optional suffix code.
Data display
Symbol display
IM 05P01D31-01EN
13
13-25
2nd digit
3rd digit
4th digit
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
PARAMETER (or PARA) key (0: OFF, 1: ON)
DISPLAY (or DISP) key (0: OFF, 1: ON)
RIGHT arrow key (0: OFF, 1: ON)
DOWN arrow key (0: OFF 1: ON)
SET/ENTER key (0: OFF, 1: ON)
UP arrow key (0: OFF, 1: ON)
LEFT arrow key (0: OFF, 1: ON)
F2 key (0: OFF, 1: ON)
F1 key (0: OFF, 1: ON)
A/M key (0: OFF, 1: ON)
Fn key (0: OFF, 1: ON)
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
DI11 status (0: OFF, 1: ON)
DI12 status (0: OFF, 1: ON)
DI13 status (0: OFF, 1: ON)
DI14 status (0: OFF, 1: ON)
DI15 status (0: OFF, 1: ON)
Parameter X000
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
Description
Parameter X100
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
13-26
IM 05P01D31-01EN
2nd digit
3rd digit
4th digit
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
DI41 status (0: OFF, 1: ON)
DI42 status (0: OFF, 1: ON)
DI43 status (0: OFF, 1: ON)
DI44 status (0: OFF, 1: ON)
DI45 status (0: OFF, 1: ON)
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
DO11 status (0: OFF, 1: ON)
DO12 status (0: OFF, 1: ON)
Parameter Y000
Displayed digit
1st digit
2nd digit
3rd digit
13
Display, Key, and Security Functions
4th digit
Description
Parameter Y100
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
IM 05P01D31-01EN
13-27
2nd digit
3rd digit
4th digit
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
DO41 status (0: OFF, 1: ON)
DO42 status (0: OFF, 1: ON)
DO43 status (0: OFF, 1: ON)
DO44 status (0: OFF, 1: ON)
DO45 status (0: OFF, 1: ON)
13-28
Name
Display
level
MCU
MCU version
EASY
DCU
DCU version
EASY
ECU1
ECU-1 version
EASY
ECU3
ECU-3 version
EASY
ECU4
ECU-4 version
EASY
PARA
Parameter version
EASY
H.VER
Product version
EASY
SER1
Serial number 1
EASY
SER2
Serial number 2
EASY
MAC1
MAC address 1
EASY
MAC2
MAC address 2
EASY
MAC3
MAC address 3
EASY
Read only.
VER
IM 05P01D31-01EN
Note
The user setting values (defaults) are not initialized even if the parameter setting values are
initialized to the factory default values.
Setting Details
Parameter
symbol
F.DEF
Name
Display
level
Initialization to factory
default value
PRO
Setting range
-12345: Initialization,
automatically returned to "0"
after initialization.
Menu symbol
INIT
14
Parameter Initialization
IM 05P01D31-01EN
14-1
CAUTION
Before registering the user default value, make sure that the user setting value is set to
the parameter.
14-2
Name
Initialization to user
default value
Display
level
PRO
Setting range
12345: Initialization,
automatically returned to "0"
after initialization.
Menu symbol
INIT
IM 05P01D31-01EN
Chapter 15 Power Failure Recovery Processing / Power Frequency Setting / Other Settings
Does not continue. Alarm with stand-by function will enter stand-by status.
Alarm latch will be initialized.
Setting parameter
Auto-tuning
Cancelled.
Control action
Does not continue. Alarm with stand-by function will enter stand-by status.
Alarm latch will be initialized.
Setting parameter
Auto-tuning
Cancelled.
Differs with setting of the parameter R.MD (restart mode).
MAN (*)
Control action
AUTO (*)
Setting Details
Parameter
symbol
R.MD
IM 05P01D31-01EN
Name
Restart mode
Display
level
STD
Setting range
Menu symbol
15-1
15
Power Failure Recovery Processing / Setting Power Frequency / Other Settings
R.MD setting
CONT
15-2
Name
Power frequency
Display
level
EASY
Setting range
AUTO
60: 60 Hz
50: 50 Hz
Menu symbol
SYS
IM 05P01D31-01EN
16.1 Troubleshooting
16.1.1 Troubleshooting Flowchart
If the Operation Display does not appear after turning on the controllers power, follow
the measures in the procedure below.
If a problem appears complicated, contact our sales representative.
Is the controller
defective?
Yes
Key
operation
failure?
No
Completely
inactive?
Yes
Yes
Display
failure?
*
Yes
Turn off power, and
then turn it on again.
No
No
I/O signal
failure?
No
No
Correct the error(s).
No
Yes
Contact us for repair.
Is the
key locked?
Yes
Correct?
Yes
Communication
failure?
Yes
Yes
Check the
specifications and polarity
of connected devices.
Check the
supply voltage.
Normal?
No
No communication
capability
No
With
communication?
Check the
communication wiring.
Problem solved.
*:
The LCD (a liquid crystal display) is used for a display portion of this product. The LCD has
a characteristic that the display action becomes late at the low temperature. Additionally,
the luminance and contrast degradation are caused due to aged deterioration. However, the
control function is not affected.
16
Troubleshooting, Maintenance, and Inspections
IM 05P01D31-01EN
16-1
The errors shown below may occur in the fault diagnosis when the power is turned on.
PV display
(Operation
Display)
Setpint display
(Operation Display)
Parameter
Status indicator
that displays
(Operation Display)
error details
SYS -----
ERR
PAR 0004
(for user default value error
only)
PAR 0010 (for setup
parameter error only)
PAR 0020 (for operation
Normal
indication
Normal
indication
Normal
indication
Faulty MCU RAM / MCU ROM MCU RAM / MCU ROM are failed.
Setup
parameter
(PA.ER)
PAR 0400
Error description
Setup
parameter
(OP.ER)
Rightmost decimal
point on PV
display blinks.
Setup
parameter
Normal indication
Right most
decimal point on (PA.ER)
Symbol display
blinks.
Setup
LADDER lamp
parameter
Normal indication
blinks.
(LA.ER)
Setup
0.000 00000
parameter
(Decimal point on the left of
(OP.ER)
the Symbol display blinks)
Remedy
Faulty.
Contact us for repair.
Faulty.
Contact us for repair.
Faulty.
Contact us for repair.
Faulty.
Contact us for repair.
Faulty FRAM
16.1 Troubleshooting
16-2
IM 05P01D31-01EN
IM 05P01D31-01EN
PV input
Ladder
calculation
Control
computation
Control
output
Retransmission
output
Alarm
action
Contact
input
Contact
Communi(alarm)
cation
output
Stopped
Stopped
0% or less
OFF
OFF
Undefined
OFF
OFF
Stopped
Undefined
Stopped
Stopped
0% or less
OFF
OFF
Undefined
OFF
OFF
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Undefined
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action (out of
Normal
Normal action
accuracy)
action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action (out of
Normal
Normal action Normal action Normal action
accuracy)
action
Normal action
Normal
action
Normal
action
Normal action
Corrupted
(without
Normal
Normal action
ladder program
ladder
action
program)
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
User profile
error
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
PROFIBUS-DP/
DeviceNet/CC-Link
communication is
disabled
Calibration
value error
Faulty FRAM
Normal action
Normal
action
16-3
16.1 Troubleshooting
Undefined
16
B.OUT
OVER
-OVER
Status indicator
Parameter that
(Operation
displays error details
Display)
Error description
Setup parameter
(AD1.E)
Setup parameter
(AD1.E)
Setup parameter
(AD1.E)
Setup parameter
(PV1.E)
Setup parameter
(PV1.E)
PV input over-scale
PV input under-scale
(PV values out of -5 to 105%)
Normal
indication
(Note)
Normal
indication
Remedy
Faulty
Contact us for repair.
Faulty
Contact us for repair.
Set the parameter RJC to OFF to erase
error indication.
Note: When an error occurs in input shown in Analog input display (Operation display).
Setpoint display shows the same symbol as the PV display.
16.1 Troubleshooting
16-4
IM 05P01D31-01EN
IM 05P01D31-01EN
PV input
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
Depends on the setting action
of the parameter BSL.
Upscale: 105%
Downscale: -5%
Normal
action
When in
AUTO
and RUN
modes:
Error
Normal
preset
action
output
When
in MAN
mode:
MAN
output
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal action
Normal
(without reference
action
junction compensation)
Depends on the
parameter BSL.
Upscale: 105%
Downscale: -5%
Normal action
16-5
16.1 Troubleshooting
PV input over-scale
PV input under-scale
(PV values out of -5 to 105%)
Analog outVoltage
put (control
pulse output
output,
(control
retransmisoutput)
sion output)
When in
AUTO
and RUN
modes:
Error
Normal
preset
action
output
When
in MAN
mode:
MAN
output
RetransAlarm
Control
mission
action
output
output
Ladder Control
calcula- computation
tion
16
LADDER lamp
Normal indication
blinks
Setup
parameter
(LA.ER)
Normal
indication
Remedy
Check wiring of feedback input resistor/current.
Error indication is erased in normal operation.
Check the ladder program.
Change the control period or reduce the
number of steps for the ladder program.
Change the control period or reduce the
number of steps for the ladder program.
Download the ladder program again. If the
error indication is still not erased, there is a
fault. Contact us for repair.
16.1 Troubleshooting
16-6
IM 05P01D31-01EN
IM 05P01D31-01EN
PV input
Ladder
calculation
Control
computation
Control output
Relay outFeedback
put (control
Contact
input (for
CommuContact
output,
(alarm)
Position
nication
input
position
output
proportionproportional type)
al output)
Position
Normal Normal Normal
proportional 105%
action
action
action
output: OFF
Feedback input
Normal action
resistor/current burnout
Normal
action
Normal
action
Normal action
Normal
action
Normal
action
Normal
action
Ladder calculation
overflow
Normal action
Undefined
(calculation
with max.
value)
Normal
action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal action
Does
not work
according to
the control
period.
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal action
Does
not work
according
to the
control
period.
Does
not work
according
to the
control
period.
Normal
action
Does
not work
according
to the
control
period.
Does
not work
according
to the
control
period.
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Does
not work
according
to the
control
period.
Does
not work
Forced end according
to the
at 200%
control
period.
Undefined
(Stopped Normal
at the error action
detection)
Normal action
Normal
action
The
response
from the
main unit
slows.
Normal
action
16.1 Troubleshooting
16-7
16
parameter
indication
communication error
Symbol display
(OP.ER)
blinks)
Setup
AT,E
Normal indication
parameter
Auto-tuning time-out
(PV1.E)
Remedy
Auto-tuning does not end even when 24 hours Check the process. Hold down any key to
have elapsed after the start of tuning.
erase the error indication
Fully-closed valve position is equal to or
larger than the fully-open valve position
after automatic valve position adjustment is
performed.
Framing parity error
Buffer overflow
Inter-character time-out
Checksum error (PC link communication with
checksum)
CRC check error (Modbus/RTU)
LRC check error (Modbus/ASCII)
IM 05P01D31-01EN
VAT,E
Normal indication
Setup
parameter
(AD2.E)
Normal
indication
0.000 00000
(Decimal point
on the left of the
Symbol display
blinks)
Setup
parameter
(OP.ER)
Normal
indication
0.000 00000
(Decimal point
on the left of the
Symbol display
blinks)
Setup
parameter
(OP.ER)
Communication error
(coordinated operation)
Normal
indication
0.000 00000
(Decimal point
on the left of the
Symbol display
blinks)
Setup
parameter
(OP.ER)
Normal
indication
Normal indication
Faulty FRAM
Communication error
(RS-485 communication)
16.1 Troubleshooting
16-8
IM 05P01D31-01EN
PV input
Peer-to-peer communication
Normal action
error
Auto-tuning time-out
Normal action
Normal action
Normal action
Control
Ladder calcucompulation
tation
Normal action
(However, the
Normal
peer-to-peer
communication action
register is not
updated.)
Autotuning
Normal action stopped,
normal
action
Normal
Normal action
action
Normal
Normal action
action
Relay outFeedback
put (control
Contact Cominput (for
Contact
output,
(alarm) municaPosition
input
position
tion
output
proportionproportional type)
al output)
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Autotuning
stopped,
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
105%
Normal action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Faulty FRAM
Normal action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
16-9
16.1 Troubleshooting
PROFIBUSDP/DeviceNet/
CC-Link
communication
is disabled
Normal
action
16
16.1 Troubleshooting
16-10
Status indicator
(Operation
Display)
Parameter
that
displays error details
Error description
Undefined
Undefined
Faulty MCU
MCU is corrupted.
Undefined
Undefined
DCU is corrupted.
Remedy
Faulty
Contact us for repair.
Faulty
Contact us for repair.
Undefined
Relay outFeedback
put (control
input (for
Contact Comoutput,
Contact
Position
(alarm) municaposition
input
proportionoutput
tio
proportional type)
al output)
OFF
Undefined OFF
OFF
Stopped
Undefined
OFF
PV input
OFF
Undefined
OFF
OFF
Stopped
IM 05P01D31-01EN
16.1 Troubleshooting
Symbol display
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
System data error
Calibration value error
User (parameter) default value error
Faulty FRAM
2nd digit
3rd digit
4th digit
IM 05P01D31-01EN
Symbol display
Displayed digit
1st digit
16
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
Non responding hardware in E1-terminal area
16-11
16.1 Troubleshooting
Symbol display
Parameter PA.ER
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
System data error
Calibration value error
User (parameter) default value error
Faulty FRAM
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Parameter LA.ER
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
16-12
Description
IM 05P01D31-01EN
16.1 Troubleshooting
Parameter OP.ER
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
Non responding hardware in E1-terminal area
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
Feedback input resistor/current burnout
Automatic valve position adjustment error
Parameter AD1.E
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
Description
16
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
IM 05P01D31-01EN
Parameter AD2.E
16-13
16.1 Troubleshooting
Parameter PV1.E
Displayed digit
1st digit
2nd digit
3rd digit
4th digit
16-14
bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
PV input over-scale
PV input under-scale
Auto-tuning time-out
Description
IM 05P01D31-01EN
16.2 Maintenance
16.2.1 Cleaning
The front panel and operation keys should be gently wiped with a cloth soaked with water
and squeezed firmly.
CAUTION
In order to prevent LCD from static electricity damage, do not wipe with dry cloth.
(When LCD is electrified, it returns to normal in several minutes.)
Do not use alcohol, benzene, or any other solvents.
CAUTION
Write down the settings of parameters for a repair request.
WARNING
Prior to shipping the instrument, put it into an antistatic bag and repackage it using
the original internal packaging materials and packaging container.
16
Troubleshooting, Maintenance, and Inspections
IM 05P01D31-01EN
16-15
16-16
IM 05P01D31-01EN
16.4 Disposal
When disposing of this instrument, arrange for appropriate disposal as industrial waste
according to the rules of a country, the area, or a local government.
16
Troubleshooting, Maintenance, and Inspections
IM 05P01D31-01EN
16-17
Blank Page
30
Rear of
controller
Note
If the instrument is moved from a location with low temperature and low humidity to a place with
high temperature and high humidity, or if the temperature changes rapidly, condensation will
result. Moreover, in the case of thermocouple inputs, measurement errors will result. To avoid
such a situation, leave the instrument in the new environment under ambient conditions for
more than 1 hour prior to using it.
17
Installation and Wiring
IM 05P01D31-01EN
17-1
150 mm
150 mm
150 mm
150 mm
17-2
IM 05P01D31-01EN
WARNING
Be sure to turn OFF the power supply to the controller before installing it on the
panel to avoid an electric shock.
Panel
Terminal board
Bracket
(bottom mounting hardware)
Appropriate
tightening torque:
0.25 Nm
17
CAUTION
1) Tighten the screws with appropriate tightening torque within 0.25 Nm. Otherwise
it may cause the case deformation or the bracket damage.
2) Make sure that foreign materials do not enter the inside of the instrument
through the case's slit holes.
IM 05P01D31-01EN
17-3
11
(0.43) 65 (2.56)
96 (3.78)
Bracket
Terminal cover
94.6 (3.72)
105.2 (4.14)
96 (3.78)
91.6 (3.61)
20 (0.79)
Unit: mm
(approx. inch)
Bracket
General mounting
117 (4.61) min.
(53) (2.09)
92+0.8
0
(3.62 +0.03
)
0
92+0.8
0
(3.62 +0.03
)
0
UT32A
(25)
(0.98)
Normal tolerance:
(value of JIS B 0401-1998 tolerance class IT18)/2
11
(0.43) 65 (2.56)
48 (1.89)
Unit: mm
(approx. inch)
96 (3.78)
91.6 (3.61)
94.6 (3.72)
105.2 (4.14)
20 (0.79)
Bracket
1 to 10 mm (0.04 to 0.39 inch) (panel thickness)
General mounting
70 min.
(2.76)
([(N-1)1.89+1.77] +0.02
0 )
92 +0.8
0
(3.62 +0.03
)
0
145 min.
(5.71)
(53) (2.09)
92+0.8
0
(3.62 +0.03
)
0
45+0.6
0
17-4
(1.77 +0.02
)
0
(25)
(0.98)
IM 05P01D31-01EN
17.4 Wiring
17.4.1 Important Information on Wiring
WARNING
1) Be sure to turn OFF the power supply to the controller before wiring to avoid an
electric shock. Use a tester or similar device to ensure that no power is being
supplied to a cable to be connected.
2) Wiring work must be carried out by a person with basic electrical knowledge and
practical experience.
Wiring direction
E1-terminal area
E1-terminal area
101
-112
501
-512
401
-412
301
-306
201
-212
101
-112
301
-312
201
-212
101
501
401
301
201
101
301
201
102
502
302
202
102
302
202
103
503
303
203
103
303
203
104
504
304
204
104
304
204
105
505
305
205
105
305
205
106
506
306
206
106
306
206
107
507
407
207
107
307
207
108
508
408
208
108
308
208
109
509
409
110
510
410
Wiring direction
210
109
309
110
310
210
111
511
411
211
111
311
211
112
512
412
212
112
312
212
E3-terminal area
17
CAUTION
When connecting two or more crimp-on terminal lugs to the single terminal
block, bend the crimp-on terminal lugs before tightening the screw.
Note that the wiring of two or more crimp-on terminal lugs to the single highvoltage terminal of the power supply and relay, etc. does not comply with the
safety standard.
IM 05P01D31-01EN
17-5
17.4 Wiring
CAUTION
Do not use an unassigned terminal as the relay terminal.
(A)
(F)
(d)
3.3
(A)
5.5
(F)
4.2
5.5 3.3
Cable Specifications
Purpose
Power supply, relay contact 600 V Grade heat-resistant PVC insulated wires, JIS C 3317(HIV), 0.9
to 2.0 mm2
output
Thermocouple
RTD
Shielded wires
Non shielded wires
RS485 communication
Shielded wires
Ethernet communication
Note
Communication wires of cross-sectional area less than or equal to 0.34 mm2 may not be
secured firmly to the terminals.
Check that the wire is firmly connected to the terminal by folding the conductor of the wire
connected to the climp-on lug.
Recommended length of the stripped wire: 7 mm
Note
If the UT is located at the end of a segment for the PROFIBUS communication wiring,
terminating resistors are separately needed. These are to be prepared by users. (390 : 2 pcs.
220 : 1 pc., or an active terminator.)
17-6
IM 05P01D31-01EN
17.4 Wiring
CAUTION
1) Be careful of polarity when wiring inputs. Reversed polarity can damage the UT.
2) Keep the PV input signal line as far away as possible from the power supply
circuit and ground circuit.
3) For TC input, use shielded compensating lead wires for wiring. For RTD input,
use shielded wires that have low conductor resistance and cause no significant
differences in resistance between the three wires.
4) If there is a risk of external lightning surges, use a lightning arrester etc.
UT35A/UT32A
TC Input
Shield
202
203
RTD
PV
Shield
+
DC voltage
Shield
202
PV
203
202 PV
203
Class D grounding
(grounding resistance
of 100 or less)
Lead wire resistance per wire of
10 or less. Make the resistance
of the three wires equal.
DC Current (mA) Input
DC current
+
Shield
203
204
PV
17
Class D grounding
(grounding resistance of 100 or less)
Class D grounding
(grounding resistance of 100 or less)
201
Class D grounding
(grounding resistance
of 100 or less)
Use
PV input is used for PV input.
IM 05P01D31-01EN
17-7
17.4 Wiring
17.4.3 Control Output (Relay, Triac, Current, and Voltage Pulse) Wiring
CAUTION
1) The use of inductance (L) loads such as auxiliary relays, motors and solenoid
valves causes malfunction or relay failure; always insert a CR filter for use with
alternating current or a diode for use with direct current, as a spark-removal
surge suppression circuit, into the line in parallel with the load.
2) If there is a risk of external lightning surges, use a lightning arrester etc.
3) Relays cannot be used for a small load of 10 mA or less.
4) Since the insulation provided to each relay output terminal is Functional
insulation, provide Reinforced insulation to the external of the device as
necessary. (Refer to the drawing below.)
This product
This product
A safety
voltage circuit
Functional
insulation
A safety
voltage circuit
Functional
insulation
Reinforced insulation
A hazardous
voltage circuit
A safety
voltage circuit
A safety
voltage circuit
A hazardous
voltage circuit
Reinforced insulation
This product
A hazardous
voltage circuit
Functional
insulation
A hazardous
voltage circuit
Reinforced insulation
A hazardous
voltage circuit
A hazardous
voltage circuit
Reinforced insulation
DC Relay Wiring
UT35A/UT32A
Relay
Diode
(Mount it directly
to the relay coil
terminal (socket).)
UTs contact
Relay
(Use one with a relay coil rating
less than the UTs contact rating.)
AC Relay Wiring
UT35A/UT32A
UTs contact
17-8
Relay
(Use one with a relay coil
rating less than the UTs
contact rating.)
CR filter
(Mount it directly
to the relay coil
terminal (socket).)
IM 05P01D31-01EN
17.4 Wiring
Relay Output
(For Standard model) Heating/cooling type
(For Standard model) Standard type output
heating/cooling output
(For Detailed model) Suffix code of Output 1 =
(For Detailed model) Suffix code of Output 1 = -R
R or U
or -U and Suffix code of Output 2 = R or -U
Cooling-side NO2
101
102
Heating-side NO1
102
103
COM
103
NC
101
NO
COM
OUT
OUT/OUT2
Triac Output
(For Detailed model) Suffix code of Output 1 = -T
101
NO
102
COM
103
OUT
+ 207
Shield
OUT
Control valves
(or other
actuators)
+ 511
RET/OUT2
512
Class D grounding
(grounding resistance of
100 or less)
Current:
4 to 20 mA DC or 0 to 20 mA DC
(resistance load: 600 or less)
Voltage pulse:
On-voltage: 12 V DC or more
(load resistance: 600 or more)
Off-voltage: 0.1 V DC or less
Use
When current/voltage pulse output is not used for control output, it can be used for
retransmission output.
When retransmission output terminal is not used for retransmission output, it can be used
for optional control output. The current output range can be changed.
For control output setting, set the control type (CNT), then set the output terminal and
output type in the output type selection (OT).
Control output type: 10.1 Setting Control Output Type
IM 05P01D31-01EN
17-9
17
Installation and Wiring
208
Control valves
Class D grounding
(or other
(grounding resistance of
actuators)
100 or less)
Current:
4 to 20 mA DC or 0 to 20 mA DC
(resistance load: 600 or less)
Voltage pulse:
On-voltage: 12 V DC or more
(load resistance: 600 or more)
Off-voltage: 0.1 V DC or less
17.4 Wiring
CAUTION
1) Use an auxiliary relay for load-switching if the contact rating is exceeded.
2) Keep the relay output wires and the feedback input wires at least 30 cm apart.
3) The output relay has a limited service life. Be sure to connect a CR filter (for AC)
or diode (for DC) to the load.
4) If there is a risk of external lightning surges, use a lightning arrester etc.
5) Relays cannot be used for a small load of 10 mA or less.
When using auxiliary relay: 17.4.3 Control Output (Relay, Current, and Voltage Pulse) Wiring
Relay contact output (UT35A)
HIGH
(direct)
507
HIGH
(direct)
101
LOW
(reverse)
508
LOW
(reverse)
102
COM
509
COM
103
VALV
Shield
Resistance:
100 to 2.5 k
VALV
Shield
Resistance:
100 to 2.5 k
310
311 VALV
312
Class D grounding
(grounding resistance of 100 or less)
Feedback input (current) (UT32A)
Shield +
510
VALV
4 to 20 mA DC
512
Class D grounding
*: Always set the terminal 511 in open state.
17-10
0%
Class D grounding
(grounding resistance of 100 or less)
Shield +
100%
512
0%
510
511
VALV
310
VALV
4 to 20 mA DC
312
Class D grounding
* Always set the terminal 311 in open state.
IM 05P01D31-01EN
17.4 Wiring
CAUTION
1) Use a no-voltage contact (relay contact etc.) for external contacts.
2) Use a no-voltage contact which has ample switching capacity for the terminal's
OFF voltage (approx. 5V) and ON current (approx 1mA).
3) When using a transistor contact, the voltage at both terminals must be 2 V or
less when the contact is ON and the leakage current must be 100 A or less
when it is OFF.
4) If there is a risk of external lightning surges, use a lightning arrester etc.
UT35A/UT32A
Contact Input Equipped as Standard
No-voltage contact
Transistor contact
DI
210 DI2
211 DI1
212 COM
210
211
212
DI2
DI1
+5 V
DI
+5 V
COM
DI
302 DI11
303 DI12
+
+
+
305 DI14
306 DI15
IM 05P01D31-01EN
301
302
303
304
305
306
DI
COM
DI11
DI12
DI13
DI14
DI15
+5 V
17
+5 V
+5 V
+5 V
+5 V
17-11
304 DI13
Transistor contact
17.4 Wiring
(For Detailed model) UT35A optional suffix code: /X4
No-voltage contact
501 COM
Transistor contact
DI
502 DI41
503 DI42
504 DI43
505 DI44
506 DI45
501
502
503
504
505
506
COM
DI41
DI42
DI43
DI44
DI45
DI
+5 V
+5 V
+5 V
+5 V
+5 V
Transistor contact
DI
302 DI11
303 DI12
Contact rating: 12 V DC, 10 mA or more
301
302
303
DI
COM
DI11
DI12
+5 V
+5 V
Transistor contact
DI
502 DI41
503 DI42
Contact rating: 12 V DC, 10 mA or more
501
502
503
COM
DI41
DI42
DI
+5 V
+5 V
17-12
DI1
DI2
IM 05P01D31-01EN
17.4 Wiring
CAUTION
1) Use an auxiliary relay for load-switching if the contact rating is exceeded.
2) Connect a bleeder resistor when a small current is used, so that a current
exceeding 10 mA can be supplied.
3) The output relay has a limited service life. Be sure to connect a CR filter (for AC)
or diode (for DC) to the load.
4) If there is a risk of external lightning surges, use a lightning arrester etc.
5) Since the insulation provided to each relay output terminal is Functional
insulation, provide Reinforced insulation to the external of the device as
necessary. (Refer to the drawing below.)
This product
This product
A safety
voltage circuit
Functional
insulation
A safety
voltage circuit
Functional
insulation
Reinforced insulation
A hazardous
voltage circuit
A safety
voltage circuit
A safety
voltage circuit
A hazardous
voltage circuit
Reinforced insulation
This product
A hazardous
voltage circuit
Functional
insulation
A hazardous
voltage circuit
Reinforced insulation
A hazardous
voltage circuit
A hazardous
voltage circuit
Reinforced insulation
When using auxiliary relay: 17.4.3 Control Output (Relay, Current, and Voltage Pulse) Wiring
UT35A/UT32A
Contact Output Equipped as Standard
Relay contact
AL3 104
ALM
17
COM 105
AL2 106
COM 107
AL1 108
COM 109
Contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
IM 05P01D31-01EN
17-13
17.4 Wiring
Additional Contact Output According to the UT35A/UT32A Suffix Codes
(For Standard model) UT35A Suffix code:
Type 2 = 1
(For Standard model) UT32A suffix code:
Type 2 = 2
(For Detailed model) UT35A/UT32A Optional
suffix code: /W1
DO12 304
DO
DO42 504
DO11 305
DO41 505
COM 306
COM 506
Transistor contact rating: 24 V DC, 50 mA
DO15 301
DO
DO45 501
DO14 302
DO44 502
DO13 303
DO43 503
DO12 304
DO42 504
DO11 305
DO41 505
COM 306
COM 506
DO
The following table shows the initial status for control type.
Control type
Single-loop Control
Heating/cooling Control
Position Proportional Control
Two-position Two-level Control
AL1 terminal
Alarm 1
(PV high limit)
AL2 terminal
Alarm 2
(PV low limit)
AL3 terminal
Alarm 3
(PV high limit)
When UT35A suffix code: Type 2 = 1 or UT32A suffix code: Type 2 = 2, the following
function is assigned to DO11.
DO11: Alarm 4 (PV low limit)
When UT35A suffix code: Type 2 = 2, the following function is assigned to DO41.
DO41: Alarm 4 (PV low limit)
When the optional suffix code: /Y1, the following function is assigned to DO11.
DO11: Alarm 4 (PV low limit)
17-14
IM 05P01D31-01EN
17.4 Wiring
RET
OUT
terminals terminals
205
207
206
208
Receiver
(Recorder etc.)
Receiving resistor:
600 or less
Class D grounding
(grounding resistance
of 100 or less)
Shield
202
203
205
4-20 mA DC
206
PV input
0.4-2 V DC
RET terminals
14.5-18.0 V DC
Class D grounding
(grounding resistance of 100 or less)
2-wire transmitter
Shield
4-20 mA DC
204
203
505
506
PV input
4-20 mA DC
For UT32A
LPS terminals
21.6-28.0 V DC
305
306
LPS terminals
21.6-28.0 V DC
Class D grounding
(grounding resistance of 100 or less)
IM 05P01D31-01EN
17-15
17
17.4 Wiring
17.4.10
HAL1 507
HBA
CT1
Class D grounding
HAL2 508
HBA
511
CT2
COM 509
Shield
512
Class D grounding
(grounding resistance COM
of 100 or less)
Heater break alarm can be used for the UT32A with the optional suffix code /HA.
Heater break alarm
HAL1 307
HBA
310
CT1
Class D grounding
HAL2 308
HBA
311
CT2
COM 309
Contact raging: 24 V DC, 50 mA
17-16
Shield
312
Class D grounding
(grounding resistance COM
of 100 or less)
IM 05P01D31-01EN
17.4 Wiring
17.4.11
4-wire Wiring
ML2-
(External)
Terminating resistor
220 1/4 W
PC
2
1
4
3
UT
SDB (+)
RDB (+)
RDB (+)
SDA ()
RDA ()
RDA ()
RDB (+)
SDB (+)
SDB (+)
RDA ()
SDA ()
SDA ()
SG
SG
SG
RS-232C
Straight cable
UT
Class D grounding
(grounding resistance
of 100 or less)
Communication
cable
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
Class D grounding
(grounding resistance
of 100 or less)
(External)
Terminating
resistor
220 1/4 W
(External)
Terminating
resistor
220 1/4 W
PC
4
3
RS-232C
Straight cable
UT
UT
B (+)
RDB (+)
RDB (+)
A ()
RDA ()
RDA ()
SDB (+)
SDB (+)
SDA ()
SDA ()
SG
SG
SG
Communication
cable
17
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
UT35A/UT32A
UT35A
UT32A
Terminal (For Standard model) Suffix code: Type (For Standard model) Suffix code: Type
symbol
3 = 1
2 = 1
above
(For Detailed model) Optional suffix
(For Detailed model) Optional
code: /CH3
suffix code: /CH1
IM 05P01D31-01EN
RDB (+)
410
304
RDA ()
411
305
SDB (+)
407
301
SDA ()
408
302
SG
409
303
17-17
Class D grounding
Class D grounding
(grounding resistance (grounding resistance
of 100 or less)
of 100 or less)
(External)
Terminating
resistor
220 1/4 W
17.4 Wiring
2-wire Wiring
ML2-
PC
(External)
Terminating resistor
220 1/4 W
4
3
RS-232C
Straight cable
UT
UT
B (+)
RSB (+)
RSB (+)
A ()
RSA()
RSA()
SG
SG
SG
Communication
cable
Class D grounding
Class D grounding
(grounding resistance (grounding resistance
of 100 or less)
of 100 or less)
(External)
Terminating
resistor
220 1/4 W
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
UT32A
UT32A
Terminal (For Standard model) Suffix code: Type 2=1,
symbol
and with optional suffix code /LP
above.
(For Detailed model) Optional suffix code:
/LCH1
RSB (+)
301
RSA ()
302
SG
303
Note
17-18
IM 05P01D31-01EN
17.4 Wiring
17.4.12
(External)
Terminating resistor
220 1/4 W
(External)
Terminating resistor
220 1/4 W
UT (Slave)
UT (Slave)
SDB (+)
RDB (+)
RDB (+)
SDA ()
RDA ()
RDA ()
RDB (+)
SDB (+)
SDB (+)
RDA ()
SDA ()
SDA ()
SG
SG
SG
Communication
cable
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
Class D grounding
(grounding resistance
of 100 or less)
(External)
Terminating resistor
220 1/4 W
(External)
Terminating resistor
220 1/4 W
UT (Slave)
UT (Slave)
SDB (+)
RDB (+)
RDB (+)
SDA ()
RDA ()
RDA ()
RDB (+)
SDB (+)
SDB (+)
RDA ()
SDA ()
SDA ()
SG
SG
SG
Communication
cable
(External)
Terminating resistor
220 1/4 W
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
Class D grounding
(grounding resistance
of 100 or less)
17
(External)
Terminating resistor
220 1/4 W
UT (Slave)
SDB (+)
RDB (+)
RDB (+)
SDA ()
RDA ()
RDA ()
RDB (+)
SDB (+)
SDB (+)
RDA ()
SDA ()
SDA ()
SG
SG
SG
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
IM 05P01D31-01EN
UT (Slave)
(External)
Terminating resistor
220 1/4 W
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
17-19
UT (Master)
17.4 Wiring
UT35A/UT32A
Terminal
symbol
above
UT35A
UT32A
(For Standard model) Suffix code: Type (For Standard model) Suffix code: Type
3 = 1
2 = 1
(For Detailed model) Optional suffix
(For Detailed model) Optional suffix
code: /CH3
code: /CH1
RDB (+)
410
304
RDA ()
411
305
SDB (+)
407
301
SDA ()
408
302
SG
409
303
2-wire Wiring
UT (Master)
(External)
Terminating resistor
220 1/4 W
UT (Slave)
UT (Slave)
RSB (+)
RSB (+)
RSB (+)
RSA ()
RSA ()
RSA ()
SG
SG
SG
Communication
cable
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
(External)
Terminating resistor
220 1/4 W
Class D grounding
(grounding resistance
of 100 or less)
UT32A
UT32A
Terminal (For Standard model) Suffix code: Type 2=1,
symbol
and with optional suffix code /LP
above
(For Detailed model) Optional suffix code:
/LCH1
17-20
RSB (+)
301
RSA ()
302
SG
303
IM 05P01D31-01EN
17.4 Wiring
17.4.13
UT
(External)
Terminating resistor
220 1/4 W
UT
SDB (+)
RDB (+)
RDB (+)
SDA ()
RDA ()
RDA ()
SDB (+)
SDB (+)
SDA ()
SDA ()
SG
SG
RDB (+)
RDA ()
SG
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
(External)
Terminating resistor
220 1/4 W
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
UT35A/UT32A
Terminal
symbol
above
UT35A
(For Standad model) Suffix code: Type
3 = 1
(For Detailed model) Optional suffix
code: /CH3
UT32A
(For Standard model) Suffix code: Type
2 = 1
(For Detailed model) Optional suffix
code: /CH1
RDB (+)
410
304
RDA ()
411
305
SDB (+)
407
301
SDA ()
408
302
SG
409
303
17
Installation and Wiring
IM 05P01D31-01EN
17-21
17.4 Wiring
2-wire Wiring
UT
(External)
Terminating resistor
220 1/4 W
UT
UT
RSB (+)
RSB (+)
RSB (+)
RSA ()
RSA ()
RSA ()
SG
SG
SG
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
(External)
Terminating resistor
220 1/4 W
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
UT32A
UT32A
Terminal (For Standard model) Suffix code: Type 2=1,
symbol
and with optional suffix code /LP
above
(For Detailed model) Optional suffix code:
/LCH1
RSB (+)
301
RSA ()
302
SG
303
17-22
IM 05P01D31-01EN
17.4 Wiring
17.4.14
HUB
Straight cable
UT35A
Crossing cable
UT35A
UT35A
Color
Amber
Color
Green
Lit
100M bps
Lit
Linked
Unlit
10M bps
Blink
Active
Unlit
Link failure
CAUTION
Be sure to connect a lightning arrester for Ethernet (100BASE-TX/10BASE-T) in an
environment where a surge voltage may be induced by a lightning discharge.
17
Installation and Wiring
IM 05P01D31-01EN
17-23
17.4 Wiring
RS-485 communication wiring for the serial gateway function is as follows.
2-wire Wiring of 4-wire Terminal
Serial gateway
(External)
Terminating resistor
220 1/4 W
407
408
409
UT
UT
RSB (+)
RDB (+)
RDB (+)
RSA ()
RDA ()
RDA ()
SDB (+)
SDB (+)
SDA ()
SDA ()
SG
SG
SG
Communication
cable
(External)
Terminating resistor
220 1/4 W
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
Class D grounding
(grounding resistance
of 100 or less)
Slave terminals
Terminal
symbol
above
UT35A
UT32A
(For Standard model) Suffix code: Type (For Standard model) Suffix code: Type
3 = 1
2 = 1
(For Detailed model) Optional suffix
(For Detailed model) Optional suffix
code: /CH3
code: /CH1
RDB (+)
410
304
RDA ()
411
305
SDB (+)
407
301
SDA ()
408
302
SG
409
303
2-wire Wiring
Serial gateway
(External)
Terminating resistor
220 1/4 W
407
408
409
UT
UT
RSB (+)
RSB (+)
RSB (+)
RSA ()
RSA ()
RSA ()
SG
SG
SG
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
(External)
Terminating resistor
220 1/4 W
Communication
cable
Class D grounding
(grounding resistance
of 100 or less)
17-24
RSB (+)
301
RSA ()
302
SG
303
IM 05P01D31-01EN
17.4 Wiring
17.4.15
17
IM 05P01D31-01EN
17-25
17.4 Wiring
Number of Pin
Singnal name
Description
VP
RxD/TxD-P
RxD/TxD-N
DGND
Signal ground
SHIELD
Shield ground
RxD/TxD-P
220
Data line
RxD/TxD-N
390
DGND
CHK
RDY
ERR
4
5
LED
CHK (red)
RDY (green)
ERR (red)
Lit
User profile error
Unlit
Normal
Normal.
No electricity, or Communication
Communicating successfully.
failure
Not connected, or communication
Normal
failure (flashing)
17-26
IM 05P01D31-01EN
17.4 Wiring
17.4.16
17
IM 05P01D31-01EN
17-27
17.4 Wiring
Number of Pin
Singnal name
Description
CAN_H
RX/TX + signal
CAN_L
RX/TX - signal
V+
V-
DRAIN
Shield/drain
121
CAN_L
3
(blue) 4
(black) 5
CHK
MNS
LED
CHK (red)
Lit / flashing
User profile error
Unlit
Normal
17-28
IM 05P01D31-01EN
17.4 Wiring
17.4.17
17
IM 05P01D31-01EN
17-29
17.4 Wiring
Number of Pin
Singnal name
Description
FG
Frame ground
SLD
Shield
DG
DB
RX/TX - signal
DA
RX/TX + signal
DB
CHK
L ERR
L RUN
5
LED
CHK (red)
L ERR (red)
Lit
Unlit
Normal
Normal
17-30
IM 05P01D31-01EN
17.4 Wiring
17.4.18
WARNING
1) Wiring work must be carried out by a person with basic electrical knowledge and
practical experience.
2) Be sure to turn OFF the power supply to the controller before wiring to avoid an
electric shock. Use a tester or similar device to ensure that no power is being
supplied to a cable to be connected.
3) As a safety measure, always install a circuit breaker (an IEC 60947-compatible
product, 5 A, 100 V or 220 V AC) in an easily accessible location near the
instrument. Moreover, provide indication that the switch is a device for turning off
the power to the instrument.
4) Install the power cable keeping a distance of more than 1 cm from other signal
wires.
5) The power cable is required to meet the IEC standards concerned or the
requirements of the area in which the instrument is being installed.
6) Wiring should be installed to conform to NEC (National Electrical Code: ANSI/
NFPA-70) or the wiring construction standards in countries or regions where
wiring will be installed.
7) Be sure to use a heat-resistant cable for control output, alarm output, and power
wiring.
CAUTION
1) Provide electricity from a single-phase power supply. If the power is noisy,
install an isolation transformer on the primary side, and use a line filter on the
secondary side. When measures against noise are taken, do not install the
primary and secondary power cables close to each other.
2) If there is a risk of external lightning surges, use a lightning arrester etc.
Primary side
Line filter
17
Circuit
breaker
Insulation transformer
Secondary side
110 N
Controller
power
111 L
G
112
Class D grounding
IM 05P01D31-01EN
17-31
Detaching Method
(1) Slide the terminal cover to the direction of the printed arrow.
17-32
IM 05P01D31-01EN
Chapter 18 Parameters
Display
None
EASY
STD
PRO
Display level
Description
18
Parameters
IM 05P01D31-01EN
18-1
Function
Operation mode (STOP/RUN switch, REMOTE/LOCAL switch, Auto-tuning
switch, SP number selection, etc.)
The parameters in the menu of the following table indicate the parameters to set the
functions necessary for operation. The symbol in parentheses are shown on Group
display.
Menu symbol
18-2
Function
CS
SELECT parameter
SP
SPS
SP-related function
ALRM
Alarm function
PVS
PV-related function
PID
PID setting
TUNE
Super, Super 2, anti-reset windup, output velocity limiter, and manual preset
output
ZONE
Zone control
PPAR
IM 05P01D31-01EN
Functions
Password setting (Displayed only when the password has been sent.)
Menu symbol
Functions
CTL
PV
MPV
OUT
HBA
R485 (E1)
ETHR (E3)
PROF (E3)
DNET (E3)
CC-L (E3)
KEY
DISP
Display functions
CSEL
KLOC
Key lock
MLOC
DI.SL
DI.NU
DI.D
DI.D (E1)
DI.D (E4)
ALM
DO (E1)
DO (E4)
I/O
SYS
Action setting when recovering from a power failure, guide display language,
password setting, etc
INIT
Initialization of parameter
VER
LVL
Note
Some parameters are not displayed according to the setting such as control type, or input and
output.
IM 05P01D31-01EN
18-3
18
Parameters
R485 (E3)
END
CS
SP
S.R
CS10
SP(1)
SP(4)
RT
R.L
CS11
SUB(1)
SUB(4)
RBS
AT
CS12
PIDN(1)
PIDN(4)
UPR
SPNO.
CS13
A1(1)
A1(4)
DNR
PID
CS14
A2(1)
A2(4)
TMU
END
CS15
A3(1)
A3(4)
SPT
CS16
A4(1)
A4(4)
S
PVT S
CS17
A5(1)
END
END
CS18
A6(1)
CS19
A7(1)
END
A8(1)
END
18-4
SPS
S
S
ALRM
PVS
AL1
BS
AL2
FL
AL3
AL4
END
VT1
VT2
VT3
VT4
HY1
HY2
HY3
HY4
DYN1
DYN2
DYN3
DYN4
DYF1
DYF2
DYF3
DYF4
AMD
END
S
S
S
S
P
P
P
P
S
IM 05P01D31-01EN
PID
TUNE
P(1)
P(4)
P(R)
I(1)
D(1)
I(4)
D(4)
I(R)
D(R)
OH(1)
OH(4)
OH(R)
OL(1)
OL(4)
OL(R)
MR(1)
MR(4)
MR(R)
HYS(1)
SU.HY(1)
HYS(4)
SU.HY(4)
HYS(R)
SU.HY(R)
HY.UP(1)
HY.UP(4)
HY.UP(R)
HY.LO(4)
DR(4)
SU.DR(4)
Pc(4)
Ic(4)
Dc(4)
OHc(4)
OLc(4)
HYSc(4)
DB(4)
PO(4)
SU.PO(4)
POc(4)
END
HY.LO(R)
DR(R)
SU.DR(R)
Pc(R)
Ic(R)
Dc(R)
OHc(R)
OLc(R)
HYSc(R)
DB(R)
PO(R)
SU.PO(R)
POc(R)
END
HY.LO(1)
DR(1)
SU.DR(1)
Pc(1)
Ic(1)
Dc(1)
OHc(1)
OLc(1)
HYSc(1)
DB(1)
PO(1)
SU.PO(1)
POc(1)
END
S
S
S
S
S
S
SC
AT.TY
AT.OH
AT.OL
AT.BS
AR
OPR
OLMT
MPON
MPO1
MPO2
MPO3
MPO4
MPO5
END
ZONE
S
P
P
P
S
S
P
S
S
S
S
S
S
PPAR
RP1
P01
RP2
P02
RP3
P03
RHY
P04
RDV
P05
END
P06
ALL
END
MODE
P07
P08
P09
P10
END
ALL
18
Parameters
IM 05P01D31-01EN
18-5
Operation
display
PASS
CTL
Displayed
when
a password
has been set.
CNT
PV
MPV
P.UNI
OT
HB1.S
PSL
PSL
P.DP
CT
HB2.S
BPS
BPS
SPGR.
RH
P.RH
P
ZON
P
PIDG. S
RL
P.RL
SDP
SPH
SH
SPL
V.H
SL
END
TR.T
V.MOD
S
RJC P
ERJC P
A.BS S
A.FL S
ALL
END
CSEL
KLOC
MLOC
P
ALL
F2
Fn
A/M
END
PCMD
PCH
PCL
BAR1
BDV
EV1
EV2
EV3
EV4
PV.D
SP.D
STS.D
SPD
GUID
HOME
ECO
BRI
B.PVW
B.PVR
B.SP
B.BAR
B.STS
D.CYC
OP.JP
MLSD
END
18-6
CS1
CS2
S
S
P
P
P
P
P
P
P
P
S
P
S
P
P
P
P
P
P
P
S
CS3
CS4
CS5
CS10
CS11
CS12
CS13
CS14
CS15
CS16
CS17
CS18
CS19
END
E3
R485
IN
BSL
F1
E1
R485
UNIT
END
DISP
HBA
ALG
ALNO.
KEY
OUT
S
S
S
S
S
P
P
P
P
P
P
P
P
P
P
U.SP
U.OUT
U.HCO
U.VP
U.MV
U.PID
U.HC
U.PV
COM.W
DATA
A/M
END
V.RS
V.L
RTS
S
S
RTH
RTL
O1RS
O1RH
O1RL
OU.A
RET.A
END
S
S
S
S
S
S
S
DI.SL
HB1
PRI
PRI
HB2
STP
STP
CT1.T
DLN
DLN
CT2.T
ADR
ADR
HDN1
S
S
HDF1 P
HDF2 P
HB1.D P
HB2.D P
RP.T
HDN2
END
RP.T
END
END
E1
DI.D
E4
DI.D
DI.NU
DI.D
A/M
SP.B0
DI1.D
DI1.D
DI1.D
R/L
SP.B1
DI2.D
DI2.D
DI2.D
SP.B2
END
DI3.D
DI3.D
DI4.D
DI4.D
DI5.D
DI5.D
END
END
CTL
P
PV
P
MPV
P
OUT
P
HBA
P R485(E1)
(E3)
P R485
ETHR(E3)
P PROF(E3)
P DNET(E3)
S CC-L(E3)
KEY
S
DISP
S
CSEL
KLOC
DI.SL
DI.NU
DI.D
DI.D(E1)
DI.D(E4)
ALM
DO(E1)
DO(E2)
DO(E3)
DO(E4)
I/O
SYS
INIT
VER
LVL
CTc
V.AT
MODE
CS
SP
SPS
ALRM
PVS
PID
TUNE
ZONE
PPAR
END
S
S
S/R
S
AUTO S
MAN S
REM S
LCL S
AT
S
LAT S
LCD S
PVRW S
MG1 P
MG2 P
MG3 P
MG4 P
PN.B0
PN.B1
PN.B2
MP.B0
MP.B1
MP.B2
SP.BC
PN.BC
MP.BC
S
S
S
S
S
S
S
P
P
ALL
ALL
ALL
END
END
IM 05P01D31-01EN
E3
ETHR
E3
PROF
E3
DNET
E3
CC-L
HSR
BR
BR
BR
BPS
ADR
ADR
ADR
PRI
IP1
IP2
BPS
BPS
BPS
FILE
FILE
FILE
SCAN
IP3
END
IP4
SCAN
END
SCAN
END
SM1
SM2
SM3
SM4
DG1
1.IP3
DG2
1.IP4
DG3
2.IP1
DG4
2.IP2
PRT
2.IP3
IPAR
2.IP4
1.IP1
ESW
1.IP2
ALM
AL1.S
AL2.S
AL3.S
OR.S
OR2.S
AL1.D
AL2.D
AL3.D
OR.D
OR2.D
S
S
S
S
S
P
P
P
P
P
E1
DO
DO1.S
DO2.S
DO3.S
DO4.S
DO5.S
DO1.D
DO2.D
DO3.D
DO4.D
DO5.D
END
S
S
S
S
S
P
P
P
P
P
E4
DO
DO1.S
DO2.S
DO3.S
DO4.S
DO5.S
DO1.D
DO2.D
DO3.D
DO4.D
DO5.D
END
S
S
S
S
S
P
P
P
P
P
I/O
KEY
X000
X100(E1)
X400(E4)
SYS
INIT
S
S
EPO S
C.GRN P
VER
LVL
LEVL
R.MD
U.DEF
PA.ER
R.TM
F.DEF
OP.ER
END
AD1.E
ALL
FREQ
Y100(E1)
QSM
LA.ER
Y400(E4)
LANG
MCU
END
PASS
ALL
END
PASS
AD2.E
Y000
SMEC
END
PV1.E
18
DCU
ECU1(E1)
ECU3(E3)
Parameters
END
END
ECU4(E4)
PARA
H.VER
SER1
SER2
MAC1(E3)
MAC2(E3)
MAC3(E3)
END
IM 05P01D31-01EN
18-7
18-8
Name
Display
level
S.R
STOP/RUN switch
EASY
R.L
REMOTE/LOCAL
switch
EASY
AT
Auto-tuning switch
EASY
SPNO.
SP number
selection
EASY
PID
PID number
EASY
Setting range
STOP: Stop mode
RUN: Run mode
Preset output (PO) is generated in
STOP mode.
Default: Not displayed. STOP/RUN
switch is assigned to contact input.
LCL: Local mode
REM: Remote mode
(Displayed only in cases where the
communication is specified.)
OFF: Disable
1 to 4: Perform auto-tuning. Tuning
result is stored in the specified
numbered PID.
R: Tuning result is stored in the
PID for reference deviation.
1 to 4 (Depends on the setup
parameter SPGR. setting.)
The PID group number being
selected is displayed.
1 to 4, R: PID group for reference
deviation
Initial value
RUN
LCL
OFF
IM 05P01D31-01EN
Display
level
EASY
Setting range
Setting range of a registered
parameter.
Initial value
-
A1 to A4
Name
Target setpoint
Sub-target setpoint
(in Two-position
two-level control)
PID number
selection
Alarm-1 to -4
setpoint
Display
level
EASY
EASY
EASY
EASY
Setting range
0.0 to 100.0% of PV input range
(EU) (Setting range: SPL to SPH)
Set the offset from SP.
-100.0 to 100.0% of PV input range
span (EUS)
1 to 4 (Depends on the PIDG.
setting.)
Set a display value of setpoint of
PV alarm, SP alarm, deviation
alarm, output alarm, or velocity
alarm.
-19999 to 30000 (Set a value
within the input range.)
Decimal point position depends on
the input type.
Initial value
SPL
0.0 % of PV
input range
span
Same as SP
number.
Display
level
RT
STD
RBS
STD
UPR
SP ramp-up rate
EASY
DNR
SP ramp-down rate
EASY
TMU
SP ramp-rate time
unit
EASY
SPT
PVT
SP tracking
selection
PV tracking
selection
Setting range
0.001 to 9.999
(Displayed only in cases where the
communication is specified.)
-100.0 to 100.0% of PV input range
span (EUS)
(Displayed only in cases where the
communication is specified.)
Initial value
1.000
0.0 % of PV
input range
span
STD
OFF, ON
ON
STD
OFF, ON
OFF
18
Parameters
IM 05P01D31-01EN
Name
18-9
AL1 to AL4
Name
Alarm-1 to -4
type
PV velocity
VT1 to VT4 alarm time
setpoint 1 to 4
HY1 to HY4
Alarm-1 to -4
hysteresis
DYN1 to
DYN4
DYF1 to
DYF4
Alarm-1 to -4
On-delay timer
Alarm-1 to -4
Off-delay timer
AMD
Alarm mode
Display
level
EASY
Setting range
Initial value
AL1, AL3: PV
high limit (01)
Without Standby action (0)
Energized (0)
Latch action
(0)
AL2, AL4: PV
low limit (02)
Without Standby action (0)
Energized (0)
Latch action
(0)
EASY
EASY
STD
PRO
STD
1.00
0.00
0.00
0
18-10
Name
Display
level
Setting range
Initial value
BS
PV input bias
EASY
0.0 % of PV
-100.0 to 100.0% of PV input range
input range
span (EUS)
span
FL
PV input filter
EASY
OFF, 1 to 120 s
OFF
IM 05P01D31-01EN
OH
OL
Proportional band
Heating-side
proportional band
(in Heating/cooling
control)
Integral time
Heating-side
integral time (in
Heating/cooling
control)
Derivative time
Heating-side
derivative time (in
Heating/cooling
control)
Control output high
limit
Heating-side control
output high limit
(in Heating/cooling
control)
Control output low
limit
Heating-side control
output low limit (in
Heating/cooling
control)
Display
level
5.0%
EASY
OFF: Disable
1 to 6000 s
240 s
EASY
OFF: Disable
1 to 6000 s
60 s
EASY
100.0%
EASY
0.0%
EASY
HYS
Hysteresis
(in ON/OFF
control, Position
proportional control,
or Two-position twolevel control)
Heating-side
ON/OFF control
hysteresis (in
Heating/cooling
control)
EASY
HY.LO
DR
SU.DR
EASY
EASY
EASY
STD
STD
RVS
RVS: Reverse action, DIR: Direct
action
DIR
18-11
18
Parameters
HY.UP
Initial value
EASY
Manual reset
Sub-hysteresis (in
Two-position twolevel control)
Upper-side
hysteresis (in ON/
OFF control)
Lower-side
hysteresis (in ON/
OFF control)
Direct/reverse
action switch
Sub-direct/reverse
action switch (in
Two-position twolevel control)
Setting range
0.0 to 999.9%
When 0.0% is set, it operates as
0.1%.
Heating-side ON/OFF control
applies when 0.0% in Heating/
cooling control
MR
SU.HY
IM 05P01D31-01EN
Name
DB
PO
SU.PO
POc
18-12
Name
Cooling-side
proportional band
Cooling-side
integral time
Cooling-side
derivative time
Cooling-side control
output high limit
Cooling-side control
output low limit
Cooling-side
ON/OFF control
hysteresis
Output dead band
(in Heating/cooling
control or Position
proportional control)
Preset output
Heating-side preset
output (in Heating/
cooling control)
Sub-preset output
(in Two-position
two-level control)
Cooling-side preset
output
Display
level
EASY
EASY
EASY
Setting range
0.0 to 999.9%
(Cooling-side ON/OFF control
applies when 0.0% in Heating/
cooling control)
OFF: Disable
1 to 6000 s
OFF: Disable
1 to 6000 s
Initial value
5.0%
240 s
60 s
EASY
100.0%
EASY
0.0%
EASY
0.0 to 100.0%
0.5%
EASY
EASY
-5.0 to 105.0%
0.0%
EASY
0%, 100%
0%
EASY
-5.0 to 105.0%
0.0%
IM 05P01D31-01EN
SC
Super function
AT.TY
Auto-tuning type
AT.OH
AT.OL
AT.BS
AR
OPR
Display
level
EASY
STD
PRO
PRO
Initial value
OFF: Disable
1: Overshoot suppressing function
(normal mode)
2: Hunting suppressing function
(stable mode)
Enables to answer the wider
characteristic changes
compared with response mode. OFF
3: Hunting suppressing function
(response mode)
Enables quick follow-up and
short converging time of PV for
the changed SP.
4: Overshoot suppressing function
(strong suppressing mode)
0: Normal
0
1: Stability
-5.0 to 105.0% (Disabled in
Heating/cooling control)
100.0%
0.0%
0.0 % of PV
-100.0 to 100.0% of PV input range
input range
span (EUS)
span
STD
STD
Output limiter
switch
PRO
MPON
Manual preset
output number
selection
STD
STD
AUTO
OFF: Disable
OFF
0.1 to 100.0%/s
OFF: Disable output limiter in MAN
mode
ON
ON: Enable output limiter in MAN
mode
OFF: Hold the control output in
AUTO mode (bumpless)
1: Use manual preset output 1
(output bump)
2: Use manual preset output 2
(output bump)
OFF
3: Use manual preset output 3
(output bump)
4: Use manual preset output 4
(output bump)
5: Use manual preset output 5
(output bump)
-5.0 to 105.0%
18
Parameters
Manual preset
output 1 to 5
Setting range
PRO
OLMT
MPO1 to
MPO5
IM 05P01D31-01EN
Name
0.0%
18-13
Name
Display
level
Setting range
Initial value
RP1 to RP3
Reference point 1
to 3
STD
100.0 % of PV
input range
RHY
STD
0.5 % of PV
input range
span
RDV
Reference deviation
STD
OFF: Disable
0.0 + 1 digit to 100.0% of PV input OFF
range span (EUS)
18-14
Name
P01 to P10
parameter
Display
level
STD
Setting range
-19999 to 30000 (Set a decimal
point position using LL50A
Parameter Setting Software.)
Initial value
0
IM 05P01D31-01EN
Name
Display
level
Setting range
PID: PID control
ONOF: ON/OFF control (1 point of
hysteresis)
ONOF2: ON/OFF control (2 points
of hysteresis)
2P2L: Two-position two-level
control
H/C: Heating/cooling control
0: Standard PID control mode
1: Fixed-point control mode
Initial value
Standard type:
PID
Heating/
cooling type:
H/C
CNT
Control type
EASY
ALG
PRO
SPGR.
Number of SP
groups
STD
1 to 4
ALNO.
Number of alarms
PRO
1 to 4
ZON
STD
PIDG.
Number of PID
groups
STD
1 to 4
18
Parameters
IM 05P01D31-01EN
18-15
IN
18-16
Name
PV input type
Display
level
EASY
UNIT
PV input unit
EASY
RH
Maximum
value of PV
input range
EASY
RL
Minimum
value of PV
input range
EASY
Initial
value
Setting range
OFF: Disable
K1: -270.0 to 1370.0 (C) / -450.0 to 2500.0 (F)
K2: -270.0 to 1000.0 (C) / -450.0 to 2300.0 (F)
K3: -200.0 to 500.0 (C) / -200.0 to 1000.0 (F)
J: -200.0 to 1200.0 (C) / -300.0 to 2300.0 (F)
T1: -270.0 to 400.0 (C) / -450.0 to 750.0 (F)
T2: 0.0 to 400.0 (C) / -200.0 to 750.0 (F)
B: 0.0 to 1800.0 (C) / 32 to 3300 (F)
S: 0.0 to 1700.0 (C) / 32 to 3100 (F)
R: 0.0 to 1700.0 (C) / 32 to 3100 (F)
N: -200.0 to 1300.0 (C) / -300.0 to 2400.0 (F)
E: -270.0 to 1000.0 (C) / -450.0 to 1800.0 (F)
L: -200.0 to 900.0 (C) / -300.0 to 1600.0 (F)
U1: -200.0 to 400.0 (C) / -300.0 to 750.0 (F)
U2: 0.0 to 400.0 (C) / -200.0 to 1000.0 (F)
W: 0.0 to 2300.0 (C) / 32 to 4200 (F)
PL2: 0.0 to 1390.0 (C) / 32.0 to 2500.0 (F)
P2040: 0.0 to 1900.0 (C) / 32 to 3400 (F)
WRE: 0.0 to 2000.0 (C) / 32 to 3600 (F)
OFF
JPT1: -200.0 to 500.0 (C) / -300.0 to 1000.0 (F)
JPT2: -150.00 to 150.00 (C) / -200.0 to 300.0 (F)
PT1: -200.0 to 850.0 (C) / -300.0 to 1560.0 (F)
PT2: -200.0 to 500.0 (C) / -300.0 to 1000.0 (F)
PT3: -150.00 to 150.00 (C) / -200.0 to 300.0 (F)
0.4-2V: 0.400 to 2.000 V
1-5V: 1.000 to 5.000 V
4-20: 4.00 to 20.00 mA
0-2V: 0.000 to 2.000 V
0-10V: 0.00 to 10.00 V
0-20: 0.00 to 20.00 mA
-1020: -10.00 to 20.00 mV
0-100: 0.0 to 100.0 mV
Note:
W: W-5% Re/W-26% Re (Hoskins Mfg. Co.),
ASTM E988
WRE: W97Re3-W75Re25
-: No unit
C: Degree Celsius
-: No unit
--: No unit
---: No unit
F: Degree Fahrenheit
Depends on the input type.
- For temperature input Set the temperature range that is actually
controlled. (RL<RH)
- For voltage / current input Set the range of a voltage / current signal
that is applied.
The scale across which the voltage / current
signal is actually controlled should be set
using the maximum value of input scale (SH)
and minimum value of input scale (SL).
(Input is always 0% when RL = RH.)
Depends
on the
input type
Depends
on the
input type
IM 05P01D31-01EN
SH
SL
BSL
RJC
ERJC
Name
Display
level
PV input scale
decimal point
position
Maximum
value of PV
input scale
Minimum value
of PV input
scale
PV input
burnout action
PV input
reference
junction
compensation
PV input
external RJC
setpoint
EASY
EASY
EASY
Initial
value
Setting range
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
Depends
on the
input type
Depends
on the
input type
Depends
on the
input type
STD
OFF: Disable
UP: Upscale
DOWN: Downscale
PRO
ON
PRO
0.0
A.BS
PV analog
input bias
STD
0.0 % of
PV input
range
span
A.FL
PV analog
input filter
STD
OFF, 1 to 120 s
OFF
Display
level
P.UNI
Control PV input
unit
STD
P.DP
Control PV input
decimal point
position
STD
P.RL
Maximum value of
control PV input
range
Minimum value of
control PV input
range
STD
STD
SPH
SP high limit
STD
SPL
SP low limit
STD
Setting range
-: No unit
C: Degree Celsius
-: No unit
--: No unit
---: No unit
F: Degree Fahrenheit
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Initial value
Same as PV
input unit
18
Depends on
the input type
Depends on
the input type
100.0 % of PV
input range
0.0 % of PV
input range
18-17
Parameters
P.RH
IM 05P01D31-01EN
Name
OT
CT
CTc
V.AT
Output type
selection
Display
level
EASY
EASY
Initial value
0.5 to 1000.0 s
30.0 s
30.0 s
OFF: Stop automatic adjustment
ON: Start automatic adjustment
Setting V.RS to ON resets the
valve adjustment settings and
causes the indication V.RS to
blink.
Pressing the SET/ENTER key
with valve position set to the fullyclosed position by Down arrow
key causes the adjusted value to
be stored. When V.L adjustment is
complete, V.L stops blinking.
Pressing the SET/ENTER key
with valve position set to the fullyopened position by Up arrow key
causes the adjusted value to be
stored. When V.H adjustment is
complete, V.H stops blinking.
STD
5 to 300 s
60 s
STD
EASY
Valve position
setting reset
EASY
V.L
Fully-closed valve
position setting
EASY
V.H
Fully-open valve
position setting
EASY
TR.T
Valve adjusting
mode
Setting range
EASY
V.RS
V.MOD
18-18
Name
OFF
OFF
IM 05P01D31-01EN
Name
Display
level
RTS
Retransmission
output type of RET
EASY
RTH
Maximum value
of retransmission
output scale of RET
STD
RTL
O1RS
O1RH
O1RL
OU.A
RET.A
Minimum value
of retransmission
output scale of RET
Retransmission
output type of OUT
current output
Maximum value
of retransmission
output scale of OUT
current output
Minimum value
of retransmission
output scale of OUT
current output
OUT current output
range
RET current output
range
STD
Setting range
Initial value
OFF: Disable
PV1: PV
SP1: SP
OUT1: OUT (Valve opening: 0 to
100 % in Position proportional
control)
LPS: 15 V DC loop power supply PV1
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1: Position proportional output
internal computed value)
PV: PV terminals analog input
When RTS = PV1, SP1, TSP1, PV
100 % of PV
RTL + 1 digit to 30000
input range
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1, SP1, or TSP1,
decimal point position is same
as that of PV input.
When RTS=PV, decimal point
position is same as that of PV
input scale.
0 % of PV
input range
STD
Same as RTS
OFF
STD
STD
STD
STD
18
Parameters
IM 05P01D31-01EN
18-19
Name
Heater break
alarm-1, -2 function
selection
Heater break
alarm-1, -2 current
setpoint
CT1, CT2 coil
CT1.T, CT2.T winding number
ratio
Heater break
HDN1, HDN2 alarm-1, -2 Ondelay timer
Heater break
HDF1, HDF2 alarm-1, -2 Offdelay timer
HB1, HB2
HB1.D,
HB2.D
18-20
Heater break
alarm-1, -2 contact
type
Display
level
Setting range
Initial value
EASY
EASY
OFF
EASY
1 to 3300
800
STD
0.00
0.00 to 99.59 (minute.second)
PRO
PRO
0.00
CLS: When the event occurs, the
contact is closed.
OPN: When the event occurs, the
contact is opened.
CLS
IM 05P01D31-01EN
Name
Display
level
Setting range
Initial value
PSL
Protocol selection
EASY
BPS
Baud rate
EASY
PRI
Parity
EASY
STP
Stop bit
EASY
1: 1 bit, 2: 2 bits
DLN
Data length
EASY
7: 7 bits, 8: 8 bits
ADR
Address
EASY
1 to 99
RP.T
Minimum response
time
PRO
0 to 10 (x10ms)
When each parameter is displayed, the terminal area (E1 or E3) is displayed on Group display.
Parameter: PSL, BPS, STP, DLN, ADR, RP.T
18
Parameters
IM 05P01D31-01EN
18-21
Name
Display
level
HSR
High-speed
response mode
BPS
Baud rate
EASY
PRI
Parity
EASY
IP1 to IP4
IP address 1 to 4
EASY
Default gateway 1
to 4
EASY
EASY
EASY
Setting range
OFF, 1 to 8
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
NONE: None
EVEN: Even
ODD: Odd
0 to 255
Initial value: 192.168.1.1
0 to 255
Initial value: 255.255.255.0
0 to 255
Initial value: 0.0.0.0
Initial value
1
38400
EVEN
See left
See left
See left
PRT
Port number
EASY
502
IPAR
IP access restriction
EASY
OFF
1.IP1 to
1.IP4
2.IP1 to
2.IP4
Permitted IP
address 1-1 to 1-4
Permitted IP
address 2-1 to 2-4
ESW
Ethernet setting
switch
EASY
EASY
EASY
0 to 255
See left
Initial value: 255.255.255.255
0 to 255
See left
Initial value: 255.255.255.255
OFF, ON
Setting this parameter to
ON enables the Ethernet
communication parameter settings. OFF
* The parameter ESW
automatically returns to OFF
after ON is set.
When each parameter is displayed, the terminal area (E3) is displayed on Group display.
Name
Display
level
Setting range
Initial value
BR
Baud rate
EASY
ADR
Address
EASY
0 to 125
BPS
Baud rate
EASY
38400
FILE
Profile number
EASY
0 to 3
PRO
OFF
1M: 1 minute
10M: 10 minutes
30M: 30 minutes
60M: 60 minutes
OFF
SCAN
Automatic rescan
time
AUTO
When each parameter is displayed, the terminal area (E3) is displayed on Group display.
18-22
IM 05P01D31-01EN
Name
Display
level
Setting range
Initial value
125K
EASY
0 to 63
63
38400
BR
Baud rate
EASY
ADR
Address
BPS
Baud rate
EASY
FILE
Profile number
EASY
0 to 3
SCAN
Automatic rescan
time
PRO
OFF
1M: 1 minute
10M: 10 minutes
30M: 30 minutes
60M: 60 minutes
OFF
When each parameter is displayed, the terminal area (E3) is displayed on Group display.
Name
Display
level
BR
Baud rate
EASY
ADR
Address
EASY
BPS
Baud rate
EASY
FILE
Profile number
EASY
SCAN
Automatic rescan
time
PRO
Setting range
Initial value
10M
1 to 64
38400
0
OFF
When each parameter is displayed, the terminal area (E3) is displayed on Group display.
18
Parameters
IM 05P01D31-01EN
18-23
18-24
Name
Display
level
F1 to F2
Fn
EASY
A/M
PRO
EASY
Setting range
OFF: Disable
A/M: AUTO/MAN switch
R/L1: REM/LCL switch
S/R: STOP/RUN switch
AUTO: Switch to AUTO
MAN: Switch to MAN
REM1: Switch to REM
LCL1: Switch to LCL
STOP: Switch to STOP
RUN: Switch to RUN
AT: Auto-tuning
LTUP: LCD brightness UP
LTDN: LCD brightness DOWN
BRI: Adjust LCD brightness
LCD: LCD backlight ON/OFF
switch
LAT: Latch release
PID: PID tuning switch
OFF: Disable
A/M: AUTO/MAN switch
R/L1: REM/LCL switch
S/R: STOP/RUN switch
AUTO: Switch to AUTO
MAN: Switch to MAN
Initial value
OFF
PID
A/M
IM 05P01D31-01EN
Name
Display
level
PCMD
Active color PV
display switch
EASY
PCH
PV color change
high limit
EASY
PCL
PV color change
low limit
EASY
BAR1
Bar-graph display
registration
STD
BDV
Bar-graph deviation
display band
STD
Setting range
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF:
white, Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red,
Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF:
white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF:
red, Alarm ON: white)
6: PV limit (Within range: white,
Out of range: red)
7: PV limit (Within range: red, Out
of range: white)
8: SP deviation (Within deviation:
white, Out of deviation: red)
9: SP deviation (Within deviation:
red, Out of deviation: white)
10: Link to DI (ON: red, OFF:
white)
Set a display value when in PV
limit or SP deviation.
-19999 to 30000 (Set a value
within the input range.)
Decimal point position depends on
the input type.
0: Disable
1:OUT, Heating-side OUT, Internal
value in Position proportional
control
2: Cooling-side OUT
3: PV
4: SP
5: Deviation
6 to 16: Disable
17: Feedback input (valve opening)
18: PV terminals analog input
0.0 to 100.0% of PV input range
span (EUS)
Initial value
0
0
5
(Heating/
cooling type: 1)
10.0 % of PV
input range
span
18
Parameters
IM 05P01D31-01EN
18-25
Name
Display
level
Setting range
Setting range: 4001 to 6304
OFF: Disable
4321: Link to alarm 1 (Lit when the alarm occurs)
4322: Link to alarm 2 (Lit when the alarm occurs)
4323: Link to alarm 3 (Lit when the alarm occurs)
4325: Link to alarm 4 (Lit when the alarm occurs)
4529: Heater break alarm 1 (Lit when the alarm
occurs)
4530: Heater break alarm 2 (Lit when the alarm
occurs)
EV1 to
EV4
EV1 to EV4
display condition
registration
PRO
Initial value
EV1: 4321
EV2: 4322
EV3: 4323
EV4: 4325
18-26
PV display area
ON/OFF
Setpoint display
area ON/OFF
Status display
area ON/OFF
PRO
PRO
ON
OFF: Nondisplay, ON: Display
PRO
SPD
Scroll speed
GUID
Guide display
ON/OFF
STD
HOME
Home Operation
Display setting
PRO
ECO
Economy mode
STD
BRI
Brightness
PRO
EASY
ON
ON
(Slow) 1 to 8 (Quick)
OFF: Nondisplay
ON: Display
SP1: SP Display
OUT1: OUT Display
HCO: Heating/cooling OUT Display
VP: Valve Position Display
MV: Position Proportional Computation
Output Display
PID1: PID Number Display
HC1: Heater Break Alarm-1 Current Display
HC2: Heater Break Alarm-2 Current Display
PV: PV Analog Input Display
CS1 to CS5: SELECT Display 1 to 5
OFF: Disable
1: Economy mode ON (All indications
except PV display OFF)
2: Economy mode ON (All indications
OFF)
3: Brightness 10 % (All indications)
(Dark) 1 to 5 (Bright)
4
ON
SP1
OFF
IM 05P01D31-01EN
Name
White brightness
adjustment of PV
display
Red brightness
adjustment of PV
display
Brightness
adjustment of
Setpoint display
Brightness
adjustment of Bargraph display
Brightness
adjustment of
Status indicator
Display
level
PRO
PRO
PRO
PRO
PRO
D.CYC
Display update
cycle
PRO
OP.JP
Autoreturn to
operation display
PRO
MLSD
Least significant
digital mask of PV
display
STD
Setting range
Adjusts the white brightness of PV
display.
(Dark) -4 to 4 (Bright)
Adjusts the red brightness of PV
display.
(Dark) -4 to 4 (Bright)
Adjusts the brightness of SP
display.
(Dark) -4 to 4 (Bright)
Adjusts the brightness of SP
display.
(Dark) -4 to 4 (Bright)
Adjusts the brightness of Status
indicator.
(Dark) -4 to 4 (Bright)
1: 100 ms
2: 200 ms
3: 500 ms
4: 1 s
5: 2 s
Automatically returned to the
Operation Display when there has
been no keystroke operation for 5
minutes.
OFF, ON
OFF: With least significant digit
ON: Without least significant digit
Initial value
0
ON
OFF
Name
SELECT Display-1
to -5registration
SELECT
parameter-10 to -19
registration
Display
level
Setting range
STD
PRO
Initial value
OFF
OFF
18
Parameters
IM 05P01D31-01EN
18-27
Display
level
Setting range
Initial value
U.SP
SP Display lock
PRO
OFF
U.OUT
PRO
OFF
PRO
OFF
PRO
OFF
U.HCO
U.VP
U.MV
U.PID
U.HC
U.PV
COM.W
DATA
A/M
18-28
Name
Heating/cooling
OUT Display lock
Valve Position
Display lock
Position
Proportional
Computation Output
Display lock
PID Number
Display lock
Heater Break Alarm
Current Value
Display lock
PV Analog Input
Display lock
Communication
write enable/disable
Front panel
parameter data key
lock
Front panel A/M key lock
PRO
OFF: Display
ON: Nondisplay
ON
PRO
ON
PRO
OFF
PRO
ON
STD
STD
OFF: Unlock
ON: Lock
STD
OFF
OFF
IM 05P01D31-01EN
Name
Display
level
PRO
PV
PRO
MPV
PRO
OUT
PRO
HBA
PRO
R485
PRO
ETHR
PRO
PROF
PRO
DNET
PRO
CC-L
PRO
KEY
PRO
DISP
PRO
CSEL
PRO
KLOC
PRO
DI.SL
PRO
DI.NU
PRO
DI.D
PRO
ALM
PRO
DO
PRO
I/O
PRO
SYS
PRO
INIT
PRO
VER
PRO
LVL
PRO
MODE
PRO
CS
PRO
SP
PRO
SPS
PRO
ALRM
PRO
PVS
PRO
PID
PRO
TUNE
PRO
ZONE
PRO
PPAR
PRO
Initial value
OFF: Display
ON: Nondisplay
OFF
OFF: Display
ON: Nondisplay
OFF
18
Parameters
CTL
Setting range
When each parameter is displayed, the terminal area (E1 to E4) is displayed on Group display.
Parameter: R485, ETHR, PROF, DNET, CC-L, DI.D, DO
IM 05P01D31-01EN
18-29
Name
Display
level
A/M
AUTO/MAN switch
STD
5025
R/L
REMOTE/LOCAL
switch
STD
OFF
S/R
STOP/RUN switch
STD
5026
AUTO
Switch to AUTO
STD
OFF
MAN
Switch to MAN
STD
REM
Switch to REMOTE
STD
LCL
Switch to LOCAL
STD
AT
Auto-tuning START/
STOP switch
STD
LAT
Latch release
STD
LCD
STD
PVRW
PV red/white switch
STD
MG1
MG2
MG3
MG4
18-30
Message display
interruption 1
Message display
interruption 2
Message display
interruption 3
Message display
interruption 4
Setting range
Initial value
OFF
Set an I relay number of contact
input.
Set OFF to disable the function.
Standard terminals
DI1: 5025, DI2: 5026
E1-terminal area
DI11: 5041, DI12: 5042,
DI13: 5043, DI14: 5044,
DI15: 5045
OFF
OFF
OFF
OFF
OFF
OFF
PRO
OFF
PRO
OFF
PRO
OFF
PRO
OFF
IM 05P01D31-01EN
Name
Display
level
SP.B0
Bit-0 of SP number
EASY
OFF
SP.B1
Bit-1 of SP number
EASY
OFF
SP.B2
Bit-2 of SP number
EASY
PN.B0
STD
PN.B1
STD
PN.B2
STD
MP.B0
MP.B1
MP.B2
SP.BC
PN.BC
MP.BC
Bit-0 of manual
preset output
number
Bit-1 of manual
preset output
number
Bit-2 of manual
preset output
number
Bit changing
method of SP
number
Bit changing
method of PID
number
Bit changing
method of manual
preset output
number
STD
STD
Setting range
STD
Initial value
OFF
OFF
OFF
OFF
OFF
OFF
OFF
STD
0: Status switch 1
1: Status switch 2
PRO
0: Status switch 1
1: Status switch 2
PRO
0: Status switch 1
1: Status switch 2
Name
Display
level
DI1.D
PRO
DI2.D
PRO
Setting range
Initial value
Name
Display
level
PRO
DI2.D
PRO
DI3.D
PRO
DI4.D
PRO
DI5.D
PRO
Initial value
0
0: The assigned function is
enabled when the contact input 0
is closed.
0
1: The assigned function is
enabled when the contact input 0
is opened.
0
IM 05P01D31-01EN
18
Parameters
DI1.D
Setting range
18-31
Name
AL1 function
selection
AL2 function
selection
AL3 function
selection
OUT relay function
selection
Display
level
STD
STD
STD
STD
OR2.S
STD
AL1.D
PRO
AL2.D
PRO
AL3.D
PRO
OR.D
OR2.D
PRO
PRO
Setting range
Set an I relay number.
Setting range: 4001 to 6000
No function: OFF
Alarm 1: 4353
Alarm 2: 4354
Alarm 3: 4355
Alarm 4: 4357
Initial value
4353
4354
4355
OFF
0
0
0
0
Name
DOn1 function
selection
DOn2 function
selection
DOn3 function
selection
DOn4 function
selection
DOn5 function
selection
Display
level
Setting range
STD
STD
STD
STD
OFF
Same as AL1.S.
Initial value of E1 and E3 teminal
area
All DO settings are OFF.
STD
DO1.D
PRO
DO2.D
PRO
DO3.D
PRO
DO4.D
PRO
DO5.D
PRO
Initial value
OFF
OFF
OFF
OFF
0
0
0
0
0
18-32
IM 05P01D31-01EN
Display
level
Name
KEY
Key status
PRO
X000
PRO
X100
PRO
Y000
PRO
Y100
PRO
Y400
PRO
Read only
Name
Display
level
Setting range
Initial value
R.MD
Restart mode
STD
R.TM
Restart timer
STD
0 to 10 s
EPO
STD
C.GRN
Response as
GREEN Series
PRO
FREQ
Power frequency
EASY
0: Preset output
1: 0% output
2: 100% output
OFF: Works as UT35A/UT32A
in communication of device
information response or
broadcasting.
ON: Works as GREEN Series
in communication of device
information response or
broadcasting.
AUTO, 60: 60 Hz, 50: 50 Hz
OFF: Disable
ON: Enable
ENG: English
FRA: French
GER: German
SPA: Spanish
0
0
OFF
AUTO
QSM
EASY
LANG
Guide display
language
EASY
PASS
Password setting
EASY
SMEC
Sampling period
error counter
PRO
0 when power
is turned on.
ON
Depends on
the Model and
Suffix Codes
18
Parameters
IM 05P01D31-01EN
18-33
Display
level
Name
Initialization to user
default value
Initialization to
factory default value
PRO
PRO
Setting range
Initial value
Display
level
Name
PA.ER
EASY
OP.ER
EASY
AD1.E
EASY
AD2.E
EASY
PV1.E
EASY
LA.ER
EASY
MCU
MCU version
EASY
DCU
DCU version
EASY
ECU1
ECU-1 version
EASY
ECU3
ECU-3 version
EASY
ECU4
ECU-4 version
EASY
PARA
Parameter version
EASY
H.VER
Product version
EASY
SER1
Serial number 1
EASY
SER2
Serial number 2
EASY
MAC1
MAC address 1
EASY
MAC2
MAC address 2
EASY
MAC3
MAC address 3
EASY
Read only
When the following parameters are displayed, the terminal area (E1 to E4) is displayed on Group
display.
Parameter: ECU1, ECU3, ECU4, MAC1, MAC2 and MAC3
18-34
Name
Parameter display
level
Display
level
EASY
Setting range
EASY: Easy setting mode
STD: Standard setting mode
PRO: Professional setting mode
Initial value
STD
IM 05P01D31-01EN
Chapter 19 Specifications
WARNING
This instrument is for Measurement Category I (CAT.I). Do not use it for
measurements in locations falling under Measurement Categories II, III, and IV.
Internal Wiring
II
T
III
I
Entrance IV
Cable
Category
Outlet
Measurement
category
Description
Remarks
CAT.I
II
CAT.II
III
CAT.III
IV
CAT.IV
Appliances, portable
equipments, etc.
19
Specifications
IM 05P01D31-01EN
19-1
Thermocouple
-270.0
to
1370.0C
-450.0
to
2500.0F
-270.0
to
1000.0C
-450.0
to
-270.0
to
500.0C
-200.0
to
-200.0
to
1200.0C
-300.0
to
-270.0
to
400.0C
-450.0
to
0.0
to
400.0C
-200.0
to
750.0F
0.0
to
1800.0C
32
to
3300F
0.0
to
1700.0C
32
to
3100F
0.0
to
1700.0C
32
to
3100F
-200.0
to
1300.0C
-300.0
to
2400.0F
-270.0
to
1000.0C
-450.0
to
1800.0F
-200.0
to
900.0C
-300.0
to
-200.0
to
400.0C
-300.0
to
Accuracy
0.0
to
400.0C
-200.0
to
0.0
to
2300.0C
32
to
Platinel 2
0.0
to
1390.0C
32.0
to
PR20-40
0.0
to
1900.0C
32
to
3400F
W97Re3W75Re25
0.0
to
2000.0C
32
to
3600F
-200.0
to
500.0C
-300.0
to
-150.00
to
150.00C
-200.0
to
300.0F
-200.0
to
850.0C
-300.0
to
1560.0F
-200.0
to
500.0C
-300.0
to
1000.0F
-150.00
to
150.00C
-200.0
to
300.0F
JPt100
RTD
Pt100
4200F
0.400 to 2.000 V
Standard signal
1.000 to 5.000 V
4.00 to 20.00 mA
0.000 to 2.000 V
0.00 to 10.00 V
DC voltage/current
0.00 to 20.00 mA
-10.00 to 20.00 mV
0.0 to 100.0 mV
The accuracy is that in the standard operating conditions: 232C, 5510%RH, and power
frequency at 50/60 Hz.
Note 1: 0.3C 1 digit in the range between 0 and 100C, 0.5C 1 digit in the range between
-100 and 200C.
Note 2: W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988
19-2
IM 05P01D31-01EN
IM 05P01D31-01EN
19-3
19
Specifications
Number of outputs:
Control output: 1
Cooling-side control output of Heating/cooling type (Retransmission output
terminal): 1
Output type: Current output or voltage pulse output
Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 or less
Current output accuracy: 0.1% of span (5% of span for 1 mA or less.)
The accuracy is that in the standard operating conditions: 232C, 5510%RH, and
power frequency at 50/60 Hz.
Voltage pulse output:
Use: Time proportional output
On-voltage: 12 V or more/load resistance of 600 or more
Off-voltage: 0.1 V DC or less
Time resolution: 10 ms or 0.1% of output, whichever is larger
19-4
IM 05P01D31-01EN
19.1.10
19.1.11
IM 05P01D31-01EN
19-5
19
Specifications
19.1.12
19.1.13
19.1.14
19-6
IM 05P01D31-01EN
19.1.15
(Primary terminals: Power (*) and relay output terminals; Secondary terminals: Analog
I/O signal terminals, contact input terminals, communication terminals, and functional
grounding terminals.)
(*): Power terminals for 24V AC/DC models are the secondary terminals.
Insulation resistance
Between power supply terminals and a grounding terminal: 20 M or more at 500 V
DC
Isolation specifications
PV (universal ) input terminals
Control, retransmission (analog) output terminals
(not isolated between the analog output terminals)
Valve position (feedback) input terminals
Control relay (contact point c/contact point a x 2) / Triac output terminals
Alarm-1 relay (contact point a) output terminals
Alarm-2 relay (contact point a) output terminals
Alarm-3 relay (contact point a) output terminals
Internal
circuits
Power
supply
19
Specifications
IM 05P01D31-01EN
19-7
19.1.16
Environmental Conditions
Normal Operating Conditions
Ambient temperature: -10 to 50C (-10 to 40C for side-by-side close mounting)
For the CC-Link option, 0 to 50 C (0 to 40 C for side-by-side close mounting)
Ambient humidity: 20 to 90% RH (no condensation allowed)
Magnetic field: 400 A/m or less
Continuous vibration at 5 to 9 Hz: Half amplitude of 1.5 mm or less, 1oct/min for 90
minutes each in the three axis directions
Continuous vibration at 9 to 150 Hz: 4.9 m/s2 or less, 1oct/min for 90 minutes each in
the three axis directions
Short-period vibration: 14.7 m/s2, 15 seconds or less
Shock: 98 m/s2 or less, 11 ms
Altitude: 2000 m or less above sea level
Warm-up time: 30 minutes or more after the power is turned on
Startup time: Within 10 seconds
*: The LCD (a liquid crystal display) is used for a display portion of this product.
The LCD has a characteristic that the display action becomes late at the low temperature.
However, the control fuction is not affected.
19-8
IM 05P01D31-01EN
Appendix 1
App
Input and Output Table
IM 05P01D31-01EN
App-1
UT35A
Suffix code
-x
-xx
-00
Optional
INPUT
suffix code
PV
/x
OUTPUT
OUT
OUT2
VALV
RET
-0
-1
-2
0
Type 2: Functions
1
2
-xx
Fixed code
-00
/HA
: Equipped
: Relay output only
UT32A
Suffix code
-x
-xx
-00
Optional
INPUT
suffix code
PV
/x
OUTPUT
OUT
OUT2
VALV
RET
-0
-1
-2
0
Type 2: Functions
1
2
x
-xx
-00
/HA
: Equipped
: Relay output only
Description of symbol
App-2
IM 05P01D31-01EN
DI2
DI11
DI
DI12
DI13
DI14
DI15
AL1
AL2
AL3
DO11
DO12
DO
DO41 DO42
DO43
DO44
DO45
HAL1
HAL2
: Equipped
UT32A (Continued)
DI
DI1
DI2
DI11
DI12
AL1
AL2
AL3
DO
DO11
DO12
HAL1
HAL2
App
Input and Output Table
IM 05P01D31-01EN
App-3
App-4
IM 05P01D31-01EN
Appendix 2
App
Input and Output Table
IM 05P01D31-01EN
App-5
UT35A
Optional
Suffix code
-xxx
-xx
-x
INPUT
suffix code
PV
/x
OUTPUT
OUT
(mA/
pulse)
OUT
(relay)
OUT
(triac)
RET
VALV
OUT2
(relay)
RET/
OUT2
-NNN
Display language/
Case color
-xx
-A
-R
Output 1
-U
-T
-P
Output 2
N
Retransmission output
/RT
/HA
/X1
E1 terminal area
/Y1
/W1
/CH3
/CC3
E3 terminal area
/PD3
/DN3
/ET3
/L4
/X4
E4 terminal area
/Y4
/W4
Power supply
/DC
Additional treatment
/CT
: Equipped, : RET terminals are used for the Output 2. Optional suffix code /RT can not be specified.
UT32A
Optional
Suffix code
UT32A
-NNN
Fixed code
-NNN
Display language/
Case color
-xx
-x
INPUT
suffix code
PV
/x
OUTPUT
OUT
(mA/
pulse)
OUT
(relay)
OUT
(triac)
RET
VALV
OUT2
(relay)
RET/
OUT2
-xx
-A
-R
Output 1
-U
-T
-P
A
Output 2
R
U
N
Retransmission output
/RT
/HA
/L1
/CH1
E1 terminal area
/LCH1
/X1
/Y1
/W1
Power supply
/DC
Additional treatment
/CT
: Equipped, : RET terminals are used for the Output 2. Optional suffix code /RT can not be specified.
App-6
IM 05P01D31-01EN
DI2
DO
DI11 DI12 DI13 DI14 DI15 DI41 DI42 DI43 DI44 DI45 AL1
AL2
AL3 DO11 DO12 DO13 DO14 DO15 DO41 DO42 DO43 DO44 DO45 HAL1 HAL2
: Equipped
UT32A (Continued)
DI
DI1
DI2
DI11
DI12
DO
DI13
DI14
DI15
AL1
AL2
AL3
DO11
DO12
DO13
DO14
DO15
HAL1
HAL2
App
: Equipped
IM 05P01D31-01EN
App-7
Blank Page
Revision Information
Title
: UT35A/UT32A Digital Indicating Controller Users Manual
Manual No. : IM 05P01D31-01EN
Jan 2010/1st Edition
Newly published
Jun 2010/2nd Edition
Style change for the case color option, and addition of CC-Link communication.
Sep. 2010/3rd Edition
Addition of the DeviceNet communication and the Detailed code model.
Jan. 2011/4th Edition
Functional improvement, and error correction.
n Written by
Yokogawa Electric Corporation
n Published by Yokogawa Electric Corporation
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, JAPAN
Blank Page
YOKOGAWA EUROPE B. V.
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
Phone : 31-88-4641000 Fax : 31-88-4641111
Branch Sales Offices / Wien (Austria), Zaventem (Belgium),
Ratingen (Germany), Madrid (Spain), Runcorn (United Kingdom), Milano (Italy),
Velizy-Villacoublay (France), Budapest (Hungary), Stockholm (Sweden),
Sola (Norway), Warszawa (Poland), Vila Nova de Gaia (Portugal),
Bucharest (Romania), Dublin (Ireland)
Aug. '10
Printed in Korea