Вы находитесь на странице: 1из 5

广泛应用于通讯、工业、租赁

Widely applied in Telecom, Rental, Outdoor


户外工程、矿山、军事等领域
Projects, Mining, etc.

RP Series
GMS44PX6/S
— Generator Set Specification

NO: DT1215012- 02

Super Quiet, Superior Life!

Page - 1 - of 5
GMS44PX6/S

3-Phase, 60Hz@1800RPM
kVA 55
Standby Power
kW 44
kVA 50
Prime Power
kW 40
Voltage V 480/277
480V 60.1
Ampere (A)
208V 138.8
Fuel Tank 8 hours (Standard) 102
Capability (L) 24 hours (Optional) 308
Noise Level at 7 Open Type 91.9
meters (dBA) Silent Type 66.9
Notes:
1) Ambient reference conditions: 1,000 mbar, 27 , 30% relative humidity;
2) Also available in the following voltages: 440/254V-416/240V-220/127V-208-120V;
3) ESP (Standby Power): the maximum power available under varying loads. Only for standby and emergency use. No overload is permissible.
PRP (Prime Power): the maximum power available under varying loads for continuous operation. A 10% overload is permissible for 1 hour
every 12 hours.

Features Benefits
z Tightly structure, excellent design and craft z Function stability credibility, service convenience
z High durability at maximum performance z Low operating cost results in optimal economy
z Excellent cooling system, reliable operation under z Gets the job done wherever you are
harshest conditions z Maximum economy through minimum downtime
z Designed with safety in mind z Operation, and maintenance
z Earth leakage protection
z Quick fix electrical power connections

Performance Specification and Craftwork


Performance Specification Telephone Interference, Electromagnetism
Efficiency of Rated Power 96.3% TIF ≤50
Time needed from start-up to full load
125 seconds THF ≤2%
(inductive)
Time needed from start-up to 50% load Radio interference in compliance with BS800 and VED
8 seconds
(inductive) allowed LEVELS G and N.
1.1 times overload operation time (hour) 1 Craftwork
2.0 time overload operation time (minute) 1 ● Steel base frame with AV mounting
Voltage Regulation, steady state ≤±1% ● standard 8h fuel tank with flexible rubber fuel tube, fuel
level indicator and drainage
Voltage Regulation, transient state 20%-15% ● Overall sprayed powder coating
Voltage Settle Time ≤5 seconds ● Whole set documents, including Installation Manual,
Operation Manual, Spare Parts Catalog, Circuit Diagram
Voltage Fluctuation Ratio 0.5%
±0.5%
Frequency Regulation, steady state Criterion
adjustable
Frequency Regulation, transient state ±5% ● ISO3046, ISO8528, BS4999, BS5514,
● BS5000PT99、AS1359, IEC34
Frequency Settle Time 5 seconds
● UTE5100, VDE0530
Frequency Fluctuation Ratio 0.5% ● ISO9001:2000
Recovery Time 0.5 seconds

Page - 2 - of 5
GMS44PX6/S

Engine Specification Alternator Specification


Brand Powerlink Brand Stamford Leroy Somer
Model PX4108G Model BCI184J LSA43.2S15
No. of Cylinders and Cycle 4L, 4 Stroke Rated Output (kVA) 55
480V 60.1
Induction System NA Rated current (A)
208V 138.8
Governing ≤5% Exciter Brushless
Displacement (L) 5 THF(BS EN60034- 1) <2%
Bore x Stroke (mm) 105 x 125 Bearing number Single
Rated power (kW) 40 Windings 100% Copper
smoke ≤3.5 Connection Type Star Connection
steady idle speed (RPM) ≤800 Insulation Class H
Speed (RPM) 1500 Winding Pitch 2/3
Net weight (kg) ≤410 Amortisseur Winding Full
Starting System Electronic A.V.R. Model SX460 R438
Voltage Regulation (no
± 1.0% ± 0.5%
load- full load)
Under speed Protection Standard
Protection IP23
100% load 9.9 Phase Sequence A(U), B(V), C(W)
Fuel
75% load TIF(NEMA MG 1-22) <50
Consumption
50% load Excitation System Self-excited, PMG optional
(L/h)
25% Ambient Temp. (℃) 40
Governor Type Mechanical Stator Rated Temp. (℃) 125

Page - 3 - of 5
GMS44PX6/S
Control System
PLC-702HC
PLC-702HC key manual start module is a manual engine control module
designed to control the engine via a key switch and push buttons on the front
panel. The module is used to start and stop the engine and indicate fault
conditions, automatically shutting down the engine and giving a true first up
fault condition of an engine failure.
Standard Control Function
● Manual Engine Control Module ● Over speed Protection
● Low Oil Pressure ● Protection hold-off timer
● High Engine Temperature ● Charge Failure warning
● Auxiliary Shutdown

PLC-5220
z Microprocessor control, with high stability and credibility
z Mains supply and generator operation monitoring
z Indicating operation status and fault conditions
z Multiple protections; multiple parameters display, like pressure, temp.
z Manual and automatic work mode selectable
z Real time clock for time and date display, overall runtime display, 99
log entries
z Overall power output display
z Integral speed/frequency detecting, telling status of start, rated
operation, over speed
z Communication with PC via RS485 OR RS232 interface, using
MODBUS protocol.

PLC-1F
Engine Control Generator Protection(ANSI)
● Start preparation (preheating or pre ● Over-/under voltage
lubrication) ● Over-/under frequency
● Start/stop sequences with selectable ● Over current
number of start attempts ● Reverse power
● voltage unbalance
● Fuel solenoid selection (coil type)
● phase sequence error
● Idle speed control
● Local of remote start/stop Clear Text Display
● Stop sequence with cooling down ● 128 x 64 pixel backlight STN
● Running speed detection selectable ● Graphic symbol messaging
O Generator Hz/V ● Clear text alarm messages
O Charger alternator input (W ● Clear text diagnostics for both Generator Monitoring
terminal) hardwired inputs and CANbus ● 3-phase or single phase generator
O Binary input (D+) messages (J1939) monitoring
O Oil pressure ● Log book holding 150 log entries O Voltage /current /frequency /power
● Real time clock for time and date /reactive power

Dimension and Weight

GMS44PX (Open Type) GMS44PX6S (Silent Type)


Length × Width × Height, mm Weight (kg)
Length × Width × Height, mm Weight (kg):
1750×890×1380 900
2400×1155×1625 950

Page - 4 - of 5
GMS44PX6/S

Optional

Engine Alternator Generator Set Fuel System Canopy


● Coolant ● Space heater ● Tools with the ● Low fuel level alarm ● Canopy
heater ● AVR PMG with regulator machine ● Automatic fuel feeding ● Trailer
● Anti-damp and anti-corrosion system ● Container
treatment ● 24 hours fuel tank
● Anti-condensation heater

Lubricating
Exhaust System Cooling System Control Panel Voltages
System
● Oil with the ● Protection board from hotness ● Front heat protection ● Remote control panel ● 440/254V
machine ● Low frequency silencer ● 50℃ radiator ● Automatic paralleling ● 416/240V
● Coolant (-30OC) control panel ● 220/127V
● Automatic Transfer ● 208-120V
Switch (ATS)

Air Switch BGC Paralleling Control ATS Mobile Trailer


System

Local Distributor
Specification may change without prior notice.
For more info., please contact your local distributors.

Page - 5 - of 5