Air-Cooled

Series R
Helical-rotary Chiller
Model RTAD 85-100-115-125-145-150165-180
250 to 650 kW (50 Hz)
Built For the Industrial and
Commercial Markets

RLC-PRC015-E4

Introduction
The Trane Model RTAD Air Cooled
Helical Rotary Screw Chiller: the
search for Reliability, and Lower
Sound Levels for today's
environment.
The Model RTAD chiller utilizes the
proven design of the Trane helical
rotary screw compressor; which
embraces all of the design features
that have made the Trane helical
rotary screw compressor liquid
chillers such a success since 1987.
The RTAD offers high reliability
coupled with a competitive physical
footprint and acoustical performance
due to its advanced design, low
speed/direct drive compressor and
proven Series R performance.
The advantages of the Model RTAD
are:
Low sound levels.
Designed specifically for operation
with environment safe HFC-134a.
A wide capacity range
High Ambient units for operation
up to 46C with 915 rpm fans
The Series R Model RTAD helical
rotary screw chiller is an industrial
grade design built for the
commercial market. It is ideal for
schools, hospitals, retailers, and
office buildings.

American Standard Inc. 2003

RLC-PRC015-E4

Contents

RLC-PRC015-E4

Introduction

Features and Benefits

Application Considerations

Selection Procedure

11

General Data

12

Performance Data

20

Controls

48

Job Site Data

52

Electrical Data

53

Dimensional Data

56

Mechanical Specifications

58

Features and Benefits

The Series R Helical Rotary


Screw Compressor
Unequaled Reliability. The next
generation Trane helical rotary
screw compressor is designed,
built and tested to the same
demanding and rugged standards
as the Trane scroll compressors,
the centrifugal compressors, and
the previous generation helical
rotary screw compressors used in
both air and water cooled chillers
for more than 13 years.
Years of research and testing. The
Trane helical rotary screw
compressor has amassed
thousands of hours of testing, much
of it at severe operating conditions
beyond normal commercial air
conditioning applications.
Proven track record. The Trane
Company is the world's largest
manufacturer of large helical rotary
compressors used for refrigeration.
Over 90,000 compressors
worldwide have proven that the
Trane helical rotary screw
compressor has a reliability rate of
greater than 99.5 percent in the first
year of operation - unequalled in
the industry.
Resistance to liquid slugging. The
robust design of the Series R

Figure 1 - Cutaway of a compressor

compressor can ingest amounts of


liquid refrigerant that would
severely damage reciprocating
compressor valves, piston rods and
cylinders.
Fewer moving parts. The helical
rotary screw compressor has only
two rotating parts: the male rotor
and the female rotor. Unlike
reciprocating compressors, the
Trane helical rotary screw
compressor has no pistons,
connecting rods, suction and
discharge valves or mechanical oil
pump. In fact, a typical
reciprocating compressor has
15 times as many critical parts as
the Series R compressor. Fewer
moving parts lead to increased
reliability and longer life.
Direct-drive, low speed, semihermetic compressor for high
efficiency and high reliability.
Field serviceable compressor for
easy maintenance.
Suction gas-cooled motor. The
motor operates at lower
temperatures for longer motor life.
Five minute start-to-start/two
minute stop-to-start anti-recycle
timer allows for closer water loop
temperature control.

Improved Operating
Capabilities
Larger Capacity Range
The Series R Model RTAD include
seven sizes available in standard or
high efficiency versions covering a
total capacity range from 250 to
480kW where the previous largest
RTAB 212 had a capacity of 360kW.
The efficient RTAC air-cooled helicalrotary chillers are available for larger
capacity up to 1500kW.
High Ambient Operation Capability
The High Ambient Series R Model
RTAD have been designed for
operation at 46C at full load, some
units can also operate at 49C at full
load using 915 rpm ZephyrWing fans.
The former RTAB were using 1410
rpm fans were generating higher
sound levels requiring on site
additional and costly sound
treatments, the RTAD will then be the
ideal solution for applications having
sound restrictions.
Improved Acoustical Performance
The sound levels of the Series R
Model RTAB have been steadily
improved since its introduction with
the different options to reduce the
sound level. With the advent of the
Model RTAD, sound levels are
reduced significantly with the new
compressor specifically designed to
minimize sound generation.
Superior Efficiency levels - the bar
has been raised
The High Efficiency Trane Model RTAD
has COP levels better than the
previous RTAB and also better COP
levels than conventional reciprocating
chillers operating with blends of
refrigerant.
The modern technology of the RTAD
with the efficient direct-drive
compressor, the electronic expansion
valve and the UCM-CLD
Microprocessor Adaptive Control has
permitted Trane to achieve these
efficiency levels.
Precise Rotor Tip Clearances. Higher
energy efficiency in a helical rotary
screw compressor is obtained by
reducing the rotor tip clearances.

RLC-PRC015-E4

Features and Benefits


This next generation compressor is
no exception. With today's
advanced manufacturing
technology, clearances can be
controlled to even tighter
tolerances. This reduces the leakage
between high and low pressure
cavities during compression,
allowing for more efficient
compressor operation.
Capacity Control and Load
Matching. The combination
patented unloading system on Trane
helical rotary screw compressor
utilizes the variable unloading valve
for the majority of the unloading
function. This allows the
compressor to modulate infinitely
to exactly match building load and
to maintain chilled water supply
temperatures within 0.3C of
setpoint. Reciprocating and screw
chillers that rely on stepped
capacity control must run at a
capacity equal to or greater than the
load and typically can only maintain
water temperature to around 1C.
Much of this excess capacity is lost
because overcooling goes toward
building latent heat removal,
causing the building to be dried
beyond normal comfort
requirements. When the load
becomes very low, the compressor
also uses a step unloader valve
which is a single unloading step to
achieve the minimum unloading
point of the compressor. The result
of this design is optimized part-load
performance far superior to single
reciprocating compressors and
step-only screw compressors.

Simple Installation
Factory Testing Means Trouble-Free
Start-Up. All air-cooled Series R
chillers are given a complete
functional test at the factory. This
computer-based test program
completely checks the sensors,
wiring, electrical components,
microprocessor function,
communication capability,
expansion valve performance and
fans. In addition, each compressor
is run tested to verify capacity and
efficiency. Where applicable, each

RLC-PRC015-E4

unit is factory preset to the


customer's design conditions, an
example would be leaving liquid
temperature set point. The end
result of this test program is that
the chiller arrives at the job site fully
tested and ready for operation.
Factory-Installed and -Tested
Controls/Options Speed Installation.
All Series R chiller options,
including main power supply
disconnect, low ambient control,
ambient temperature sensor, low
ambient lockout, communication
interface and ice making controls
are factory installed and tested.

Superior Control with the


UCM-CLD Adaptive
Control Microprocessor
Module
System Options - Ice Storage
Trane air-cooled chillers are well
suited for ice production. The unique
ability to operate at decreased
ambient temperature while producing
ice lends to roughly the same work
seen by the compressor. An aircooled machine typically switches to
ice production at night. Two things
happen under this assumption. First,
the leaving brine temperature from
the evaporator is lowered to around 5.5 to -5C. Second, the ambient
temperature has typically dropped
about 8.3 to 11C from the peak
daytime ambient. This effectively
places a lift on the compressors that
is similar to daytime running
conditions. The chiller can operate in
lower ambient at night and
successfully produce ice to
supplement the next day's cooling
demands.
The Model RTAD produces ice by
supplying ice storage tanks with a
constant supply of glycol solution. Aircooled chillers selected for these lower
leaving fluid temperatures are also
selected for efficient production of
chilled fluid at nominal comfort cooling
conditions. The ability of Trane chillers
to serve "double duty" in ice
production and comfort cooling greatly
reduces the capital cost of ice storage
systems.

When cooling is required, ice chilled


glycol is pumped from the ice storage
tanks directly to the cooling coils. No
expensive heat exchanger is required.
The glycol loop is a sealed system,
eliminating expensive annual chemical
treatment costs. The air-cooled chiller is
also available for comfort cooling duty
at nominal cooling conditions and
efficiencies. The modular concept of
glycol ice storage systems and the
proven simplicity of Trane Tracer
controls allow the successful blend of
reliability and energy saving
performance in any ice storage
application.
The ice storage system is operated in
six different modes: each optimized
for the utility cost of the hour.
1. Provide comfort cooling with chiller
2. Provide comfort cooling with ice
3. Provide comfort cooling with ice
and chiller
4. Freeze ice storage
5. Freeze ice storage when comfort
cooling is required
6. Off
Tracer optimization software controls
operation of the required equipment
and accessories to easily transition
from one mode of operation to
another. For example:
Even with ice storage systems there
are numerous hours when ice is
neither produced nor consumed, but
saved. In this mode the chiller is the
sole source of cooling. For example,
to cool the building after all ice is
produced but before high electrical
demand charges take effect, Tracer
sets the air-cooled chiller leaving fluid
set point to its most efficient setting
and starts the chiller, chiller pump,
and load pump.
When electrical demand is high, the
ice pump is started and the chiller is
either demand limited or shut down
completely. Tracer controls have the
intelligence to optimally balance the
contribution of ice and chiller in
meeting the cooling load.
The capacity of the chiller plant is
extended by operating the chiller and
ice in tandem. Tracer rations the ice,
augmenting chiller capacity while
reducing cooling costs. When ice is
produced, Tracer will lower the aircooled chiller leaving fluid set point
5

Features and Benefits


and start the chiller, ice and chiller
pumps, and other accessories. Any
incidental loads that persists while
producing ice can be addressed by
starting the load pump and drawing
spent cooling fluid from the ice
storage tanks.
For specific information on ice
storage applications, contact your
local Trane sales office.

RLC-PRC015-E4

Features and Benefits


Options
High Efficiency/Performance Option
This option provides oversized heat
exchangers with two purposes. One,
it allows the unit to be more energy
efficient. Two, the unit will have
enhanced operation in high ambient
conditions.
Low Temperature Brine
The hardware and software on the
unit are factory set to handle low
temperature brine applications,
typically below 5C.
Ice Making
The unit controls are factory set to
handle ice making for thermal
storage applications.
Communication interface module
Provides the following possibilities:
1. Tracer/Summit Communication
Interface Permits bi-directional
communication to the Trane
Integrated Comfort system.
2. Chilled Water Temperature Reset
This option provides the control
logic and field installed sensors to
reset leaving chilled water
temperature. The setpoint can be
reset based off of either ambient
temperature or return evaporator
water temperature.
3. External Chilled Water Setpoint
Allows the external setting
independent of the front panel set
point by mean of a 2-10VDC input
or a 4-20mA input.
4. External Current Limit Setpoint
Allows the external setting
independent of the front panel set
point by mean of a 2-10VDC input
or a 4-20mA input.
Coil Protection
Rectangle punching type panels that
protect the condenser coils on the
two-third upper part only. The
compressors and the evaporator are
accessible.
Service Valves
Provides a service valve on the
discharge line of each circuit to
facilitate compressor servicing.

RLC-PRC015-E4

High Ambient Option


The high ambient option consists of
special control logic to permit high
ambient (46 C) operation.
Low Ambient Option
The low ambient option consists of
special control logic and fans to
permit low ambient (down to
-18 C) operation.

Under/Over-voltage protection
Controls the variation of the power
supply voltage. If the value exceeds
the minimum or maximum voltage,
the unit is shut down.
IP20 protection
Provides a protection against direct
contacts inside the control panel. The
current -carrying parts are shrouded
in order to prevent accidental contact.

Power Disconnect Switch


A disconnect switch plus compressor
protection fuses with a through-thedoor handle is provided to disconnect
main power.
Night Noise Set Back
At night, on a contact closure all the
fans run at low speed bringing the
overall sound level further down. Not
available on high ambient units.
Neoprene Isolators
Isolators provide isolation between
chiller and structure to help eliminate
vibration transmission. Neoprene
isolators are more effective and
recommended over spring isolators.
Low Noise Version
The unit is equipped with low speed
fans and compressors sound
attenuating enclosure. All the sound
emissive parts like refrigerant lines
and panels subject to vibration are
acoustically treated with sound
absorbent material.
Ground Fault Detection
Sensing ground current for an
improved chiller protection.
Pressure Gauges
A set of two pressure gauges per
refrigerant circuit, one for low
pressure and one for high pressure.
Counter Flanges
One set of mating flanges on which
the customer will weld the pipe-work.
(supplied with bolts and gaskets)
Flow Switch
For field installation on the chilled
water outlet connection.

Application Considerations
Certain application constraints
should be considered when sizing,
selecting and installing Trane aircooled Series R chillers. Unit and
system reliability is often dependent
upon properly and completely
complying with these
considerations. When the application
varies from the guidelines presented,
it should be reviewed with your local
Trane sales engineer.
Unit Sizing
Unit capacities are listed in the
performance data section.
Intentionally over-sizing a unit to
assure adequate capacity is not
recommended. Erratic system
operation and excessive compressor
cycling are often a direct result of an
over-sized chiller. In addition, an
oversized unit is usually more
expensive to purchase, install, and
operate. If over-sizing is desired,
consider using two units.
Water Treatment
Dirt, scale, products of corrosion and
other foreign material will adversely
affect heat transfer between the
water and system components.
Foreign matter in the chilled water
system can also increase pressure
drop and, consequently, reduce
water flow. Proper water treatment
must be determined locally,
depending on the type of system and
local water characteristics. Neither
salt nor brackish water is
recommended for use in Trane aircooled Series R chillers. Use of either
will lead to a shortened life to an
indeterminable degree. The Trane
Company encourages the
employment of a reputable water
treatment specialist, familiar with
local water conditions, to assist in
this determination and in the
establishment of a proper water
treatment program.
Effect Of Altitude on Capacity
Air-cooled Series R chiller capacities
given in the performance data tables
are for use at sea level. At elevations
substantially above sea level, the
decreased air density will reduce
condenser capacity and, therefore,
8

unit capacity and efficiency. The


adjustment factors can be applied
directly to the catalog performance
data to determine the unit's adjusted
performance.
Ambient Limitations
Trane air-cooled Series R chillers are
designed for year-round operation
over a range of ambient
temperatures. The air-cooled Model
RTAD chiller will operate in ambient
temperatures of 7 to 40 C. Selecting
the high ambient option will allow
the chiller to operate in ambient
temperatures above 40 C and
selecting the low ambient option will
increase the operational capability of
the water chiller to ambient
temperatures as low as -18 C. For
operation outside of these ranges,
contact the local Trane sales office.
Water Flow Limits
The minimum water flow rates are
given in this catalog. Evaporator flow
rates below the tabulated values will
result in laminar flow causing freezeup problems, scaling, stratification
and poor control. The maximum

evaporator water flow rate is also


given in the general data section.
Flow rates exceeding those listed
may result in excessive tube erosion.
The evaporator can withstand up to
50 percent water flow reduction as
long as this flow is equal or above
the minimum flow rate requirement.
The microprocessor and capacity
control algorithms are designed to
take a minimum of 10% change in
water flow rate per minute.
Flow Rates out of Range
Many process cooling jobs require
flow rates that cannot be met with
the minimum and maximum
published values within the Model
RTAD evaporator. A simple piping
change can alleviate this problem.
For example: A plastic injection
molding process requires 5.1 l/s of
10C water and returns that water at
15.6C. The selected chiller can
operate at these temperatures, but
has a minimum flow rate of 7.6 l/s.
The following system can satisfy the
process.

Figure 2 - Evaporator flow rate out of range

1. Load
2. 15.6C - 5 L/s
3. Chilled water pump - 7.5 L/s
4. 13.7C - 7.6 L/s

5. 10C - 7.6 L/s


6. 10C - 5 L/s
7. Chilled water pump - 5 L/s
8. 10C - 2.5 L/s

RLC-PRC015-E4

Application Considerations
Leaving Water Temperature Range.
Trane air-cooled Series R chillers
have three distinct leaving water
categories: standard, low
temperature, and ice making. The
standard leaving solution
temperature range is 4.4 to 15.6 C.
Low temperature machines produce
leaving liquid temperatures less than
4.4 C. Since liquid supply
temperature setpoints less than
4 .4 C result in suction temperatures
at or below the freezing point of
water, a glycol solution is required
for all low temperature machines. Ice
making machines have a leaving
liquid temperature range of -6.7 to
15.6 C. Ice making controls include
dual set point controls and safeties
for ice making and standard cooling
capabilities. Consult your local Trane
sales engineer for applications or
selections involving low temperature
or ice making machines. The
maximum water temperature that
can be circulated through an
evaporator when the unit is not
operating is 42 C .

Leaving Water Temperature out of


Range
Similar to the flow rates above,
many process cooling jobs require
temperature ranges that cannot be
met with the minimum and
maximum published values for the
Model RTAD evaporator. A simple
piping change can alleviate this
problem. For example: A laboratory
load requires 7.6 l/s of water entering
the process at 29.4C and returning
at 35C. The accuracy required is
better than cooling tower can give.
The selected chiller has adequate
capacity, but a maximum leaving
chilled water temperature of 15C.
In the example shown, both the
chiller and process flow rates are
equal. This is not necessary. For
example, if the chiller had a higher
flow rate, there would simply be
more water bypassing and mixing
with warm water.
Supply Water Temperature Drop
The performance data for the Trane
air-cooled Series R chiller is based on

Figure 3 - If temperatures are out of range for equipment

1. Load
2. 35C - 7.6 L/s
3. 35C - 2.2 L/s
4. Chilled water pump
5. 21C - 7.6 L/s

RLC-PRC015-E4

6. 15.6C - 7.6 L/s


7. 15.6C - 2.2 L/s
8. 15C - 5.4 L/s
9. Chilled water pump
10. 35C - 5.4 L/s

a chilled water temperature drop of


6C. Chilled water temperature drops
from 3.3 to 10 C may be used as
long as minimum and maximum
water temperature and minimum
and maximum flow rates are not
violated. Temperature drops outside
this range are beyond the optimum
range for control and may adversely
affect the microcomputer's ability to
maintain an acceptable supply water
temperature range. Furthermore,
temperature drops of less than 3.3 C
may result in inadequate refrigerant
superheat. Sufficient superheat is
always a primary concern in any
direct expansion refrigerant system
and is especially important in a
package chiller where the evaporator
is closely coupled to the compressor.
When temperature drops are less
than 3.3 C, an evaporator runaround
loop may be required.
Ice Storage Provides Reduced
Electrical Demand
An ice storage system uses a
standard chiller to make ice at night
when utilities charge less for
electricity. The ice supplements or
even replaces mechanical cooling
during the day when utility rates are
at their highest. This reduced need
for cooling results in big utility cost
savings.
Another advantage of ice storage is
standby cooling capacity. If the
chiller is unable to operate, one or
two days of ice may still be available
to provide cooling. In that time the
chiller can be repaired before
building occupants feel any loss of
comfort.
The Trane Model RTAD chiller is
uniquely suited to low temperature
applications like ice storage because
of the ambient relief experienced at
night. This allows the Model RTAD
chiller to produce ice efficiently, with
less stress on the machine.
Simple and smart control strategies
are another advantage the Model
RTAD chiller offers for ice storage
applications. Trane Tracer building
management systems can actually
anticipate how much ice needs to be
made at night and operate the
system accordingly. The controls are
9

Application Considerations
integrated right into the chiller. Two
wires and preprogrammed software
dramatically reduce field installation
cost and complex programming.
Short Water Loops
The proper location of the
temperature control sensor is in the
supply (outlet) water connection or
pipe. This location allows the
building to act as a buffer and
assures a slowly changing return
water temperature. If there is not a
sufficient volume of water in the
system to provide an adequate
buffer, temperature control can be
lost, resulting in erratic system
operation and excessive compressor
cycling. A short water loop has the
same effect as attempting to control
from the building return water.
Typically, a two-minute water loop is
sufficient to prevent a short water
loop. Therefore, as a guideline,
ensure the volume of water in the
evaporator loop equals or exceeds
two times the evaporator flow rate.
For a rapidly changing load profile,
the amount of volume should be
increased. To prevent the effect of a
short water loop, the following items
should be given careful
consideration: A storage tank or
larger header pipe to increase the
volume of water in the system and,
therefore, reduce the rate of change
of the return water temperature.
Applications Types
Comfort cooling.
Industrial process cooling.
Ice/thermal storage.
Low temperature process cooling.

10

RLC-PRC015-E4

Selection Procedure
The chiller capacity tables cover the
most frequently encountered leaving
liquid temperatures. The tables
reflect a 6C temperature drop
through the evaporator. For other
temperature drops, apply the
appropriate Performance Data
Adjustment Factors. For chilled brine
selections, refer to Figures F-2 and 3
for Ethylene and Propylene Glycol
Adjustment Factors.
Selection Procedure SI units
To select a Trane air-cooled RTAD
chiller, the following information is
required:
1 Design load in kW of refrigeration
2 Design chilled water temperature
drop
3 Design leaving chilled water
temperature
4 Design ambient temperature
Evaporator flow rates can be
determined by using the following
formula:

5 The final unit selection is:


QTY (1) RTAD 115 (Table P-3)
Cooling Capacity = 395.9 kW
Entering/Leaving Chilled Water
Temperatures = 12/7C
Ambient 35C
Chilled Water Flow Rate = 18.91 l/s
Evaporator Water Pressure Drop =
80 kPa
Compressor Power Input =
139.8 kW
Unit COP = 2.64 kW/kW
Contact the local Trane sales
engineer for a proper selection at the
given operating conditions.

Selection Procedure English units


1 ton = 3.5168 kW
Evaporator flow rate in GPM = 24 x
tons / delta T (F)
Delta T (F) = delta T (C) x 1.8
1 GPM = 0.06309 l/s
1 ft WG = 3 kPa
EER = COP / 0.293

l/s = kW (Capacity) x 0.239 /


Temperature Drop (Degrees C)
To determine the evaporator
pressure drop we use the flow rate
(l/s) and the evaporator water
pressure drop Figure 4
For selection of chilled brine units or
applications where the altitude is
significantly greater than sea level or
the temperature drop is different
than 6C, the performance
adjustment factors from Table P85
should be applied at this point.
For example:
Corrected Capacity = Capacity
(unadjusted) x Glycol Capacity
Adjustment Factor
Corrected Flow Rate = Flow Rate
(unadjusted) x Glycol Flow Rate
Adjustment Factor

RLC-PRC015-E4

11

General Data
SI Units
Table G-1 - General Data RTAD Standard
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

165
2
100/85

180
2
100/100

(l)
(l/s)
(l/s)

EG120
106
4.1
17.3

EG140
270
6.0
20.8

EG170
222
7.3
24.8

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG250
415
11.6
38.0

EG250
415
11.6
38.0

2
2743
1626
192
3/3

2
3658
1626
192
2/2

2
3658
1626
192
3/3

2
3658
1626
192
3/3

2
4572
1626
192
3/3

2
4572
1626
192
3/3

2
5486
1626
192
3/3

2
5486
1626
192
3/3

(m/s)
(kW)

3/3
762
23.4
915
36.5
2.05

3/3
762
28.5
915
36.5
2.05

3/3
762
27.0
915
36.5
2.05

3/3
762
27.0
915
36.5
2.05

5/4
762
37.0
915
36.5
2.05

5/5
762
39.0
915
36.5
2.05

6/5
762
44.9
915
36.5
2.05

6/6
762
46.8
915
36.5
2.05

(C)
(C)

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
24/24
5/5
2760
2660

2
17
30/32
6/6
3205
2940

2
17
35/36
8/8
3655
3440

2
17
36/37
9/9
3670
3470

2
17
43/45
9/9
4260
4060

2
17
43/45
9/9
4520
4060

2
17
53/56
11/9.5
5440
5030

2
17
53/57
11/11
5525
5115

(mm)
(mm)
(Fins/ft)

(mm)
(m3/s)

(kg)
(l)
(kg)
(kg)

Table G-2 - General Data RTAD High Efficiency


Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

12

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

(l)
(l/s)
(l/s)

EG140
270
6.0
20.8

EG170
222
7.3
24.8

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG250
415
11.6
38.0

EG250
415
11.6
38.0

2
3658
1626
192
3/3

2
3658
1626
192
3/3

2
4572
1626
192
3/3

2
4572
1626
192
3/3

2
5486
1626
192
3/3

2
5486
1626
192
3/3

(m/s)
(kW)

3/3
762
27.0
915
36.5
2.05

4/4
762
31.2
915
36.5
2.05

4/4
762
35.0
915
36.5
2.05

5/5
762
39.0
915
36.5
2.05

6/5
762
44.8
915
36.5
2.05

6/6
762
46.8
915
36.5
2.05

(C)
(C)

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
32/34
5/5
3240
2975

2
17
35/36
6/6
3370
3145

2
17
42/45
9/9
3905
3700

2
17
42/45
9/9
4000
3800

2
17
53/56
9.5/9.5
5390
4980

2
17
53/56
9.5/9.5
5445
5035

(mm)
(mm)
(Fins/ft)

(mm)
(m3/s)

(kg)
(l)
(kg)
(kg)

RLC-PRC015-E4

General Data
Table G-3 - General Data RTAD High Efficiency Low Noise
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

165
2
100/85

180
2
100/100

(l)
(l/s)
(l/s)

EG120
106
4.1
17.3

EG140
270
6.0
20.8

EG170
222
7.3
24.8

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG250
415
11.6
38.0

EG250
415
11.6
38.0

2
2743
1626
192
3/3

2
3658
1626
192
2/2

2
3658
1626
192
3/3

2
3658
1626
192
3/3

2
4572
1626
192
3/3

2
4572
1626
192
3/3

2
5486
1626
192
3/3

2
5486
1626
192
3/3

(m/s)
(kW)

3/3
762
18.1
730
29.1
1.30

3/3
762
22.4
730
29.1
1.30

3/3
762
21.0
730
29.1
1.30

3/3
762
21.0
730
29.1
1.30

5/4
762
28.7
730
29.1
1.30

5/5
762
30.1
730
29.1
1.30

6/5
762
34.7
730
29.1
1.30

6/6
762
36.2
730
29.1
1.30

(C)
(C)

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
24/24
5/5
2760
2660

2
17
30/32
6/6
3205
2940

2
17
35/36
8/8
3655
3440

2
17
36/37
9/9
3670
3470

2
17
43/45
9/9
4360
4160

2
17
43/45
9/9
4620
4420

2
17
53/56
11/9.5
5540
5130

2
17
53/57
11/11
5625
5215

(mm)
(mm)
(Fins/ft)

(mm)
(m3/s)

(kg)
(l)
(kg)
(kg)

Table G-4 - General Data RTAD High Efficiency Low Noise


Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

RLC-PRC015-E4

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

(l)
(l/s)
(l/s)

EG140
270
6.0
20.8

EG170
222
7.3
24.8

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG250
415
11.6
38.0

EG250
415
11.6
38.0

2
3658
1626
192
3/3

2
3658
1626
192
3/3

2
4572
1626
192
3/3

2
4572
1626
192
3/3

2
5486
1626
192
3/3

2
5486
1626
192
3/3

(m/s)
(kW)

3/3
762
21.0
690
27.5
1.30

4/4
762
24.1
690
27.5
1.30

4/4
762
27.2
690
27.5
1.30

5/5
762
30.1
690
27.5
1.30

6/5
762
34.7
690
27.5
1.30

6/6
762
36.1
690
27.5
1.30

(C)
(C)

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
32/34
5/5
3340
3075

2
17
35/36
6/6
3470
3245

2
17
42/45
9/9
4005
3800

2
17
42/45
9/9
4100
3900

2
17
53/56
9.5/9.5
5490
5080

2
17
53/56
9.5/9.5
5545
5135

(mm)
(mm)
(Fins/ft)

(mm)
(m3/s)

(kg)
(l)
(kg)
(kg)

13

General Data
Table G-5 - General Data RTAD Standard Low Noise with Night Noise Set Back option
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

165
2
100/85

180
2
100/100

(l)
(l/s)
(l/s)

EG120
106
4.1
17.3

EG140
270
6.0
20.8

EG170
222
7.3
24.8

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG250
415
11.6
38.0

EG250
415
11.6
38.0

2
2743
1626
192
3/3

2
3658
1626
192
2/2

2
3658
1626
192
3/3

2
3658
1626
192
3/3

2
4572
1626
192
3/3

2
4572
1626
192
3/3

2
5486
1626
192
3/3

2
5486
1626
192
3/3

(m/s)
(kW)

2/2
762
13.4
550
21.9
1.05

3/3
762
20.5
550
21.9
1.05

3/3
762
19.3
550
21.9
1.05

3/3
762
19.3
550
21.9
1.05

4/4
762
25.0
550
21.9
1.05

4/4
762
25.0
550
21.9
1.05

5/5
762
30.7
550
21.9
1.05

5/5
762
30.7
550
21.9
1.05

(C)
(C)

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
24/24
5/5
2760
2650

2
17
30/32
6/6
3200
2935

2
17
35/36
8/8
3660
3435

2
17
36/37
9/9
3670
3670

2
17
43/45
9/9
4360
4160

2
17
43/45
9/9
4620
4420

2
17
53/56
11/9.5
5540
5130

2
17
53/57
11/11
5625
5215

(mm)
(mm)
(Fins/ft)

(mm)
(m3/s)

(kg)
(l)
(kg)
(kg)

Table G-6 - General Data RTAD High Efficiency Low Noise with Night Noise Set Back option
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

14

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

(l)
(l/s)
(l/s)

EG140
270
6.0
20.8

EG170
222
7.3
24.8

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG250
415
11.6
38.0

EG250
415
11.6
38.0

2
3658
1626
192
3/3

2
3658
1626
192
3/3

2
4572
1626
192
3/3

2
4572
1626
192
3/3

2
5486
1626
192
3/3

2
5486
1626
192
3/3

(m/s)
(kW)

3/3
762
19.2
550
21.9
1.05

3/3
762
19.2
550
21.9
1.05

4/4
762
24.9
550
21.9
1.05

4/4
762
25.0
550
21.9
1.05

5/5
762
30.6
550
21.9
1.05

5/5
762
30.6
550
21.9
1.05

(C)
(C)

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
32/34
5/5
3340
3075

2
17
35/36
6/6
3470
3245

2
17
42/45
9/9
4005
3800

2
17
42/45
9/9
4100
3900

2
17
53/56
9.5/9.5
5490
5080

2
17
53/56
9.5/9.5
5545
5135

(mm)
(mm)
(Fins/ft)

(mm)
(m3/s)

(kg)
(l)
(kg)
(kg)

RLC-PRC015-E4

General Data
Table G-7 - General Data RTAD Standard High External Static Pressure
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

165
2
100/85

180
2
100/100

(l)
(l/s)
(l/s)

EG120
106
4.1
17.3

EG140
270
6.0
20.8

EG170
222
7.3
24.8

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG250
415
11.6
38.0

EG250
415
11.6
38.0

2
2743
1626
192
3/3

2
3658
1626
192
2/2

2
3658
1626
192
3/3

2
3658
1626
192
3/3

2
4572
1626
192
3/3

2
4572
1626
192
3/3

2
5486
1626
192
3/3

2
5486
1626
192
3/3

(m/s)
(kW)

3/3
762
23.7
935
37.3
1.05

3/3
762
29.5
935
37.3
2.05

3/3
762
27.6
935
37.3
3.05

3/3
762
27.6
935
37.3
4.05

5/4
762
37.6
935
37.3
5.05

5/5
762
39.5
935
37.3
6.05

6/5
762
45.5
935
37.3
7.05

6/6
762
47.4
935
37.3
8.05

(C)
(C)

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

R134a

R134a

R134a

R134a

R134a

R134a

R134a

R134a

2
17
24/24
5/5
2760
2660

2
17
30/32
6/6
3205
2940

2
17
35/36
8/8
3655
3440

2
17
36/37
9/9
3670
3470

2
17
43/45
9/9
4260
4060

2
17
43/45
9/9
4520
4060

2
17
53/56
11/9.5
5440
5030

2
17
53/57
11/11
5525
5115

(mm)
(mm)
(Fins/ft)

(mm)
(m3/s)

(kg)
(l)
(kg)
(kg)

Table G-8 - General Data RTAD High Efficiency High External Static Pressure
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

(l)
(l/s)
(l/s)

EG140
270
6.0
20.8

EG170
222
7.3
24.8

EG200
204
8.8
30.7

EG200
204
8.8
30.7

EG250
415
11.6
38.0

EG250
415
11.6
38.0

2
3658
1626
192
3/3

2
3658
1626
192
3/3

2
4572
1626
192
3/3

2
4572
1626
192
3/3

2
5486
1626
192
3/3

2
5486
1626
192
3/3

(m/s)
(kW)

3/3
762
27.6
935
37.3
1.05

4/4
762
31.5
935
37.3
2.05

4/4
762
35.6
935
37.3
3.05

5/5
762
39.4
935
37.3
4.05

6/5
762
45.4
935
37.3
5.05

6/6
762
47.3
935
37.3
6.05

(C)
(C)

0
-18

0
-18

0
-18

0
-18

0
-18

0
-18

R134a

R134a

R134a

R134a

R134a

R134a

2
17
32/34
5/5
3240
2975

2
17
35/36
6/6
3370
3145

2
17
42/45
9/9
3905
3700

2
17
42/45
9/9
4000
3800

2
17
53/56
9.5/9.5
5390
4980

2
17
53/56
9.5/9.5
5445
5035

(mm)
(mm)
(Fins/ft)

(mm)
(m3/s)

(kg)
(l)
(kg)
(kg)

Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2
2. Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
3. Percent minimum load is for total machine at 10C (50F) ambient and 7C (44F) leaving chilled water temp. Not each individual circuit.
4. Operating weight: with aluminum fins

RLC-PRC015-E4

15

General Data
English Units
Table G-9- General Data RTAD Standard
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evpaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

165
2
100/85

180
2
100/100

(Gallon)
(GPM)
(GPM)

EG120
28.0
65.2
274.6

EG140
71.3
95.1
329.9

EG170
58.7
115.0
393.1

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG250
109.6
184.0
603.0

EG250
109.6
184.0
603.0

2
108
64
192
3/3

2
144
64
192
2/2

2
144
64
192
3/3

2
144
64
192
3/3

2
180
64
192
3/3

2
180
64
192
3/3

2
216
64
192
3/3

2
216
64
192
3/3

(Ft/s)
(kW)

3/3
30
49556
915
119.8
2.05

3/3
30
60460
915
119.8
2.05

3/3
30
57194
915
119.8
2.05

3/3
30
57248
915
119.8
2.05

5/4
30
78439
915
119.8
2.05

5/5
30
82716
915
119.8
2.05

6/5
30
95103
915
119.8
2.05

6/6
30
99250
915
119.8
2.05

(F)
(F)

32
0

32
0

32
0

32
0

32
0

32
0

32
0

32
0

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
52.9/52.9
1.32/1.32
6085
5864

2
17
66.1/70.5
1.59/1.59
7066
6481

2
17
77.2/79.4
2.11/2.11
8058
7584

2
17
79.4/81.6
2.38/2.38
8091
7650

2
17
94.8/99.2
2.38/2.38
9392
8951

2
17
94.8/99.2
2.38/2.38
9965
8951

2
17
116.8/123.5
2.91/2.51
11993
11089

2
17
116.8/125.7
2.91/2.91
12180
11276

(inch)
(inch)
(Fins/ft)

(inch)
(CFM)

(Lbs.)
(Gallon)
(Lbs.)
(Lbs.)

Table G-10 - General Data RTAD High Efficiency


Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evpaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

16

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

(Gallon)
(GPM)
(GPM)

EG140
71.3
95.1
329.9

EG170
58.7
115.0
393.1

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG250
109.6
184.0
603.0

EG250
109.6
184.0
603.0

2
144
64
192
3/3

2
144
64
192
3/3

2
180
64
192
3/3

2
180
64
192
3/3

2
216
64
192
3/3

2
216
64
192
3/3

(Ft/s)
(kW)

3/3
30
57108
915
119.8
2.05

4/4
30
66046
915
119.8
2.05

4/4
30
74100
915
119.8
2.05

5/5
30
82628
915
119.8
2.05

6/5
30
95008
915
119.8
2.05

6/6
30
99132
915
119.8
2.05

(F)
(F)

32
0

32
0

32
0

32
0

32
0

32
0

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
70.5/75.0
1.32/1.32
7143
6559

2
17
77.2/79.4
1.59/1.59
7429
6933

2
17
92.6/99.2
2.38/2.38
8609
8157

2
17
92.6/99.2
2.38/2.38
8818
8377

2
17
116.8/123.5
2.51/2.51
11883
10979

2
17
116.8/123.5
2.51/2.51
12004
11100

(inch)
(inch)
(Fins/ft)

(inch)
(CFM)

(Lbs.)
(Gallon)
(Lbs.)
(Lbs.)

RLC-PRC015-E4

General Data
Table G-11 - General Data RTAD High Efficiency Low Noise
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evpaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

165
2
100/85

180
2
100/100

(Gallon)
(GPM)
(GPM)

EG120
28.0
65.2
274.6

EG140
71.3
95.1
329.9

EG170
58.7
115.0
393.1

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG250
109.6
184.0
603.0

EG250
109.6
184.0
603.0

2
108
64
192
3/3

2
144
64
192
2/2

2
144
64
192
3/3

2
144
64
192
3/3

2
180
64
192
3/3

2
180
64
192
3/3

2
216
64
192
3/3

2
216
64
192
3/3

(Ft/s)
(kW)

3/3
30
38246
730
95.6
1.3

3/3
30
47434
730
95.6
1.3

3/3
30
44514
730
95.6
1.3

3/3
30
44568
730
95.6
1.3

5/4
30
60751
730
95.6
1.3

5/5
30
63878
730
95.6
1.3

6/5
30
73628
730
95.6
1.3

6/6
30
76644
730
95.6
1.3

(F)
(F)

32
0

32
0

32
0

32
0

32
0

32
0

32
0

32
0

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
52.9/52.9
1.32/1.32
6085
5864

2
17
66.1/70.5
1.59/1.59
7066
6481

2
17
77.2/79.4
2.11/2.11
8058
7584

2
17
79.4/81.6
2.38/2.38
8091
7650

2
17
94.8/99.2
2.38/2.38
9612
9171

2
17
94.8/99.2
2.38/2.38
10185
9744

2
17
116.8/123.5
2.91/2.51
12213
11310

2
17
116.8/125.7
2.91/2.91
12401
11497

(inch)
(inch)
(Fins/ft)

(inch)
(CFM)

(Lbs.)
(Gallon)
(Lbs.)
(Lbs.)

Table G-12 - General Data RTAD High Efficiency Low Noise


Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evpaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

RLC-PRC015-E4

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

(Gallon)
(GPM)
(GPM)

EG140
71.3
95.1
329.9

EG170
58.7
115.0
393.1

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG250
109.6
184.0
603.0

EG250
109.6
184.0
603.0

2
144
64
192
3/3

2
144
64
192
3/3

2
180
64
192
3/3

2
180
64
192
3/3

2
216
64
192
3/3

2
216
64
192
3/3

(Ft/s)
(kW)

3/3
30
44426
690
90.3
1.3

4/4
30
50964
690
90.3
1.3

4/4
30
57562
690
90.3
1.3

5/5
30
63784
690
90.3
1.3

6/5
30
73521
690
90.3
1.3

6/6
30
76510
690
90.3
1.3

(F)
(F)

32
0

32
0

32
0

32
0

32
0

32
0

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
70.5/75.0
1.32/1.32
7363
6779

2
17
77.2/79.4
1.59/1.59
7650
7154

2
17
92.6/99.2
2.38/2.38
8829
8377

2
17
92.6/99.2
2.38/2.38
9039
8598

2
17
116.8/123.5
2.51/2.51
12103
11199

2
17
116.8/123.5
2.51/2.51
12224
11321

(inch)
(inch)
(Fins/ft)

(inch)
(CFM)

(Lbs.)
(Gallon)
(Lbs.)
(Lbs.)

17

General Data
Table G13 - General Data RTAD Standard Low Noise with Night Noise Set Back
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evpaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

165
2
100/85

180
2
100/100

(Gallon)
(GPM)
(GPM)

EG120
28.0
65.2
274.6

EG140
71.3
95.1
329.9

EG170
58.7
115.0
393.1

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG250
109.6
184.0
603.0

EG250
109.6
184.0
603.0

2
108
64
192
37318

2
144
64
192
37289

2
144
64
192
37318

2
144
64
192
37318

2
180
64
192
37318

2
180
64
192
37318

2
216
64
192
37318

2
216
64
192
37318

(Ft/s)
(kW)

2/2
30
28479
550
72.0
1.05

3/3
30
43376
550
72.0
1.05

3/3
30
40791
550
72.0
1.05

3/3
30
40842
550
72.0
1.05

4/4
30
52929
550
72.0
1.05

4/4
30
52962
550
72.0
1.05

5/5
30
64956
550
72.0
1.05

5/5
30
65000
550
72.0
1.05

(F)
(F)

32
0

32
0

32
0

32
0

32
0

32
0

32
0

32
0

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
52.9/52.9
1.32/1.32
6085
5842

2
17
66.1/70.5
1.59/1.59
7055
6470

2
17
77.2/79.4
2.11/2.11
8069
7573

2
17
79.4/81.6
2.38/2.38
8091
8091

2
17
94.8/99.2
2.38/2.38
9612
9171

2
17
94.8/99.2
2.38/2.38
10185
9744

2
17
116.8/123.5
2.91/2.51
12213
11310

2
17
116.8/125.7
2.91/2.91
12401
11497

(inch)
(inch)
(Fins/ft)

(inch)
(CFM)

(Lbs.)
(Gallon)
(Lbs.)
(Lbs.)

Table G14 - General Data RTAD High Efficiency Low Noise with Night Noise Set Back
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evpaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

18

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

(Gallon)
(GPM)
(GPM)

EG140
71.3
95.1
329.9

EG170
58.7
115.0
393.1

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG250
109.6
184.0
603.0

EG250
109.6
184.0
603.0

2
144
64
192
37318

2
144
64
192
37318

2
180
64
192
37318

2
180
64
192
37318

2
216
64
192
37318

2
216
64
192
37318

(Ft/s)
(kW)

3/3
30
40710
550
72.0
1.05

3/3
30
40746
550
72.0
1.05

4/4
30
52846
550
72.0
1.05

4/4
30
52904
550
72.0
1.05

5/5
30
64872
550
72.0
1.05

5/5
30
64906
550
72.0
1.05

(F)
(F)

32
0

32
0

32
0

32
0

32
0

32
0

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

HFC 134a

2
17
70.5/75.0
1.32/1.32
7363
6779

2
17
77.2/79.4
1.59/1.59
7650
7154

2
17
92.6/99.2
2.38/2.38
8829
8377

2
17
92.6/99.2
2.38/2.38
9039
8598

2
17
116.8/123.5
2.51/2.51
12103
11199

2
17
116.8/123.5
2.51/2.51
12224
11321

(inch)
(inch)
(Fins/ft)

(inch)
(CFM)

(Lbs.)
(Gallon)
(Lbs.)
(Lbs.)

RLC-PRC015-E4

General Data
Table G15 - General Data RTAD Standard High External Static Pressure
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evpaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

165
2
100/85

180
2
100/100

(Gallon)
(GPM)
(GPM)

EG120
28.0
65.2
274.6

EG140
71.3
95.1
329.9

EG170
58.7
115.0
393.1

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG250
109.6
184.0
603.0

EG250
109.6
184.0
603.0

2
108
64
192
37683

2
144
64
192
37654

2
144
64
192
37683

2
144
64
192
37683

2
180
64
192
37683

2
180
64
192
37683

2
216
64
192
37683

2
216
64
192
37683

(Ft/s)
(kW)

3/3
30
50118
935
122.4
1.05

3/3
30
62540
935
122.4
2.05

3/3
30
58514
935
122.4
3.05

3/3
30
58578
935
122.4
4.05

5/4
30
79569
935
122.4
5.05

5/5
30
83640
935
122.4
6.05

6/5
30
96363
935
122.4
7.05

6/6
30
100368
935
122.4
8.05

(F)
(F)

32
0

32
0

32
0

32
0

32
0

32
0

32
0

32
0

R134a

R134a

R134a

R134a

R134a

R134a

R134a

R134a

2
17
52.9/52.9
1.32/1.32
6085
5864

2
17
66.1/70.5
1.59/1.59
7066
6481

2
17
77.2/79.4
2.11/2.11
8058
7584

2
17
79.4/81.6
2.38/2.38
8091
7650

2
17
94.8/99.2
2.38/2.38
9392
8951

2
17
94.8/99.2
2.38/2.38
9965
8951

2
17
116.8/123.5
2.91/2.51
11993
11089

2
17
116.8/125.7
2.91/2.91
12180
11276

(inch)
(inch)
(Fins/ft)

(inch)
(CFM)

(Lbs.)
(Gallon)
(Lbs.)
(Lbs.)

Table G16 - General Data RTAD High Efficiency High External Static Pressure
Size
Compressor Quantity
Nominal Size (1)
Evaporator
Evpaporator Model
Water Storage
Minimum Flow
Maximum Flow
Condenser
Qty of Coils
Coil Length
Coil Height
Fin series
Number of Rows
Condenser Fans
Quantity (1)
Diameter
Total Air Flow
Nominal RPM
Tip Speed
Motor kW
Min Starting/Oper Ambient(2)
Standard Unit
Low Ambient Unit
General Unit
Refrigerant
No. Of independent
Refrigerant Circuits
% Min. Load (3)
Refrigerant Charge (1)
Oil Charge (1)
Operating Weight
Shipping Weight

(Tons)

85
2
40/40

100
2
50/50

115
2
60/60

125
2
70/70

145
2
85/70

150
2
85/85

(Gallon)
(GPM)
(GPM)

EG140
71.3
95.1
329.9

EG170
58.7
115.0
393.1

EG200
53.9
139.2
486.4

EG200
53.9
139.2
486.4

EG250
109.6
184.0
603.0

EG250
109.6
184.0
603.0

2
144
64
192
37683

2
144
64
192
37683

2
180
64
192
37683

2
180
64
192
37683

2
216
64
192
37683

2
216
64
192
37683

(Ft/s)
(kW)

3/3
30
58412
935
122.4
1.05

4/4
30
66796
935
122.4
2.05

4/4
30
75432
935
122.4
3.05

5/5
30
83562
935
122.4
4.05

6/5
30
96257
935
122.4
5.05

6/6
30
100248
935
122.4
6.05

(F)
(F)

32
0

32
0

32
0

32
0

32
0

32
0

R134a

R134a

R134a

R134a

R134a

R134a

2
17
70.5/75.0
1.32/1.32
7143
6559

2
17
77.2/79.4
1.59/1.59
7429
6933

2
17
92.6/99.2
2.38/2.38
8609
8157

2
17
92.6/99.2
2.38/2.38
8818
8377

2
17
116.8/123.5
2.51/2.51
11883
10979

2
17
116.8/123.5
2.51/2.51
12004
11100

(inch)
(inch)
(Fins/ft)

(inch)
(CFM)

(Lbs.)
(Gallon)
(Lbs.)
(Lbs.)

Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2
2. Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
3. Percent minimum load is for total machine at 10C (50F) ambient and 7C (44F) leaving chilled water temp. Not each individual circuit.

RLC-PRC015-E4

19

Performance Data
SI Units
Table P1 - RTAD 085 Standard Efficiency
LWT
C
5
7
9
11
13

25
C.C. kW
294.3
313.6
333.7
354.4
375.5

P.I. kW
74.8
77.6
80.6
83.8
87.1

30
COP
kW/kW
3.44
3.55
3.65
3.75
3.84

C.C. kW
277.4
295.7
314.7
334.4
354.4

P.I. kW
80.8
83.8
86.9
90.1
93.5

Entering Condenser Air Temperature (C)


35
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
3.03
259.5
87.6
2.64
241.2
3.13
277.1
90.7
2.74
257.7
3.23
295.0
93.9
2.83
274.6
3.32
313.6
97.2
2.91
292.2
3.41
332.6
100.7
2.99
310.1

40
P.I. kW
95.2
98.4
101.7
105.1
108.6

46
COP
kW/kW
2.28
2.37
2.45
2.53
2.61

C.C. kW
218.7
230.7
234.2
238.0
241.6

P.I. kW
105.4
106.7
103.1
99.5
96.4

COP
kW/kW
1.89
1.97
2.07
2.17
2.27

Table P2 - RTAD 100 Standard Efficiency


LWT
C
5
7
9
11
13

25
C.C. kW
354.1
377.3
400.8
425.1
450.1

P.I. kW
92.6
96.4
100.3
104.4
108.7

30
COP
kW/kW
3.44
3.53
3.62
3.70
3.78

C.C. kW
333.3
355.1
377.6
400.8
424.4

P.I. kW
98.9
102.8
106.8
111.1
115.5

Entering Condenser Air Temperature (C)


35
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
3.05
311.9
106.2
2.68
289.7
3.14
332.6
110.1
2.76
309.1
3.22
353.7
114.3
2.84
329.1
3.30
375.5
118.6
2.92
349.8
3.38
398.0
123.1
2.99
367.1

40
P.I. kW
114.3
118.4
122.6
127.1
129.5

46
COP
kW/kW
2.33
2.41
2.48
2.55
2.63

C.C. kW
255.3
257.7
263.0
266.2
269.7

P.I. kW
120.8
116.2
112.7
108.7
105.2

COP
kW/kW
1.95
2.04
2.14
2.25
2.34

Table P3 - RTAD 115 Standard Efficiency


LWT
C
5
7
9
11
13

25
C.C. kW
422.3
449.3
477.1
505.3
533.7

P.I. kW
114.7
119.2
123.9
128.7
133.9

30
COP
kW/kW
3.37
3.47
3.55
3.63
3.70

C.C. kW
397.7
423.0
449.0
475.7
502.8

P.I. kW
124.3
128.9
133.8
138.8
144.1

Entering Condenser Air Temperature (C)


35
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.95
372.0
135.0
2.56
345.6
3.04
395.9
139.8
2.64
367.8
3.12
420.5
144.8
2.71
390.6
3.19
445.1
150.1
2.78
414.2
3.26
470.8
155.6
2.84
425.1

40
P.I. kW
146.9
151.9
157.2
162.6
160.2

46
COP
kW/kW
2.20
2.27
2.34
2.40
2.50

C.C. kW
285.5
289.4
292.5
296.1
301.3

P.I. kW
146.3
142.4
138.3
134.3
130.9

COP
kW/kW
1.83
1.90
1.97
2.05
2.14

Table P4 - RTAD 125 Standard Efficiency


LWT
C
5
7
9
11
13

25
C.C. kW
485.6
515.1
545.0
575.6
606.5

P.I. kW
145.7
151.7
157.8
164.3
171.0

Entering Condenser Air Temperature (C)


35
COP
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW
3.11
456.0
158.0
2.71
425.8
171.6
2.34
394.9
3.18
483.8
164.2
2.77
451.8
177.9
2.40
401.5
3.24
511.9
170.6
2.83
478.5
184.6
2.46
406.8
3.30
540.8
177.2
2.89
505.3
191.4
2.51
413.8
3.35
569.9
184.1
2.94
521.8
191.0
2.60
419.1
30

40
P.I. kW
186.5
181.2
174.8
169.2
164.0

46
COP
kW/kW
2.01
2.10
2.20
2.31
2.41

C.C. kW
276.7
280.2
284.1
286.9
291.8

P.I. kW
153.6
149.9
146.3
142.2
138.5

COP
kW/kW
1.69
1.75
1.82
1.89
1.97

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

20

RLC-PRC015-E4

Performance Data
SI Units
Table P5 - RTAD 145 Standard Efficiency
LWT
C
5
7
9
11
13

25
C.C. kW
550.6
586.5
623.4
661.0
699.7

P.I. kW
146.9
152.8
158.9
165.2
171.8

30
COP
kW/kW
3.39
3.48
3.57
3.66
3.74

C.C. kW
520.0
554.1
588.9
624.8
661.4

P.I. kW
158.7
164.7
171.0
177.5
184.2

Entering Condenser Air Temperature (C)


35
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.99
488.7
171.8
2.61
456.4
3.08
520.7
178.0
2.70
486.6
3.16
553.8
184.5
2.78
517.6
3.24
587.5
191.1
2.85
532.3
3.32
622.0
198.0
2.92
538.0

40
P.I. kW
186.4
192.8
199.4
197.0
189.5

46
COP
kW/kW
2.27
2.34
2.42
2.51
2.63

C.C. kW
354.4
359.3
365.0
370.9
375.5

P.I. kW
172.6
167.8
163.1
159.6
155.4

COP
kW/kW
1.89
1.97
2.05
2.13
2.21

Table P6 - RTAD 150 Standard Efficiency


LWT
C
5
7
9
11
13

25
C.C. kW
589.6
627.3
665.6
705.0
745.0

P.I. kW
162.3
168.9
175.8
182.9
190.4

30
COP
kW/kW
3.28
3.37
3.45
3.52
3.59

C.C. kW
556.9
592.5
628.7
665.9
703.9

P.I. kW
175.0
181.8
188.9
196.2
203.8

Entering Condenser Air Temperature (C)


35
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.90
523.2
189.2
2.54
488.7
2.98
556.9
196.2
2.61
520.0
3.05
591.0
203.4
2.68
552.0
3.12
626.2
210.9
2.75
568.9
3.19
661.7
218.7
2.81
577.3

40
P.I. kW
205.0
212.1
219.5
217.9
210.9

46
COP
kW/kW
2.21
2.27
2.34
2.43
2.54

C.C. kW
385.7
391.0
396.6
401.2
404.0

P.I. kW
192.1
186.8
181.6
177.2
171.9

COP
kW/kW
1.85
1.92
2.00
2.07
2.14

Table P7 - RTAD 165 Standard Efficiency


LWT
C
5
7
9
11
13

25
C.C. kW
641.0
683.2
726.1
770.0
815.4

P.I. kW
178.5
186.0
193.6
201.7
210.0

30
COP
kW/kW
3.25
3.34
3.42
3.49
3.56

C.C. kW
607.9
648.0
688.4
730.3
773.2

P.I. kW
192.3
200.0
207.9
216.2
224.8

Entering Condenser Air Temperature (C)


35
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.88
573.5
207.7
2.54
537.6
2.96
611.1
215.7
2.61
573.5
3.04
649.8
223.8
2.68
609.3
3.11
689.1
232.4
2.75
618.5
3.18
729.6
241.2
2.81
629.0

40
P.I. kW
224.9
233.1
241.6
234.9
228.1

46
COP
kW/kW
2.21
2.28
2.35
2.45
2.56

C.C. kW
420.9
425.8
427.2
430.7
434.9

P.I. kW
209.2
203.3
196.6
191.3
185.9

COP
kW/kW
1.85
1.92
1.99
2.06
2.13

Table P8 - RTAD 180 Standard Efficiency


LWT
C
5
7
9
11
13

25
C.C. kW
687.4
732.4
777.7
824.5
872.3

P.I. kW
195.2
203.5
212.0
220.9
230.2

30
COP
kW/kW
3.18
3.27
3.35
3.42
3.48

C.C. kW
652.6
695.1
738.4
782.3
828.0

P.I. kW
210.1
218.7
227.5
236.7
246.3

Entering Condenser Air Temperature (C)


35
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.83
616.4
226.9
2.50
578.4
2.91
656.4
235.7
2.57
616.4
2.98
697.2
244.9
2.63
654.7
3.05
739.1
254.5
2.69
663.1
3.11
782.0
264.5
2.75
670.2

40
P.I. kW
245.5
254.7
264.2
256.7
247.1

46
COP
kW/kW
2.18
2.25
2.31
2.40
2.51

C.C. kW
452.9
459.9
463.8
469.7
474.0

P.I. kW
227.6
222.2
216.0
211.0
204.8

COP
kW/kW
1.83
1.90
1.97
2.04
2.11

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

21

Performance Data
SI Units
Table P9 - RTAD 085 High Efficiency
LWT
C
5
7
9
11
13

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
COP
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
317.9
72.2
3.84
299.6
77.6
3.40
280.6
83.8
2.98
261.2
90.8
2.58
339.3
75.0
3.96
320.0
80.5
3.52
299.9
86.8
3.09
279.2
93.8
2.68
361.4
77.9
4.08
341.1
83.5
3.63
320.0
89.8
3.19
297.8
96.9
2.78
384.3
81.0
4.20
362.5
86.6
3.74
340.4
93.0
3.29
317.1 100.2
2.88
407.5
84.2
4.30
384.7
89.9
3.84
361.4
96.3
3.39
337.2 103.5
2.97
25

30

46
C.C. kW
237.0
253.5
271.1
289.0
307.3

P.I. kW
100.3
103.4
106.6
109.9
113.3

49
COP
kW/kW
2.15
2.24
2.32
2.41
2.49

C.C. kW
224.3
240.5
257.4
274.6
292.5

COP
P.I. kW kW/kW
105.4
1.94
108.6
2.03
111.8
2.11
115.2
2.19
118.6
2.28

Table P10- RTAD 100 High Efficiency


LWT
C
5
7
9
11
13

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
COP
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
374.8
84.7
3.79
353.4
91.1
3.36
331.6
98.4
2.95
308.7 106.5
2.57
399.8
87.8
3.92
377.3
94.3
3.48
354.1 101.7
3.07
330.2 110.0
2.67
425.8
91.1
4.05
401.9
97.6
3.60
377.6 105.1
3.18
352.3 113.5
2.77
452.5
94.5
4.17
427.6 101.1
3.71
401.9 108.7
3.28
375.5 117.2
2.87
479.9
98.0
4.28
453.6 104.7
3.82
426.5 112.4
3.38
399.1 121.0
2.96
25

30

46
C.C. kW
280.9
300.6
321.4
342.8
356.5

P.I. kW
117.6
121.2
124.9
128.7
128.5

49
COP
kW/kW
2.14
2.24
2.32
2.41
2.51

C.C. kW
266.5
285.9
305.5
326.3
335.4

COP
P.I. kW kW/kW
123.5
1.95
127.2
2.03
131.1
2.12
135.0
2.20
132.6
2.30

Table P11 - RTAD 115 High Efficiency


LWT
C
5
7
9
11
13

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
COP
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
443.4
109.2
3.60
419.1 118.0
3.18
393.8 127.9
2.79
367.8 139.0
2.41
474.0
113.3
3.73
448.3 122.2
3.30
421.6 132.2
2.89
393.8 143.5
2.51
505.6
117.5
3.85
478.2 126.5
3.41
450.1 136.8
3.00
420.9 148.2
2.61
538.3
121.9
3.97
509.5 131.1
3.52
479.2 141.5
3.09
448.6 153.1
2.70
572.1
126.6
4.08
541.1 135.9
3.62
509.5 146.4
3.19
477.1 158.2
2.78
25

30

46
C.C. kW
335.8
359.7
370.6
375.5
380.8

P.I. kW
154.0
158.7
156.6
151.0
146.0

49
COP
kW/kW
2.01
2.09
2.18
2.29
2.39

C.C. kW
319.3
340.7
346.0
352.0
356.5

COP
P.I. kW kW/kW
162.2
1.82
166.1
1.90
161.1
1.99
156.1
2.08
151.3
2.17

Table P12 - RTAD 125 High Efficiency


LWT
C
5
7
9
11
13

25
C.C. kW P.I. kW
519.3
133.2
554.1
138.2
590.3
143.4
627.6
148.8
666.3
154.5

30
COP
kW/kW
3.45
3.56
3.67
3.78
3.88

C.C. kW
490.8
524.2
558.7
594.2
630.8

P.I. kW
144.1
149.2
154.6
160.2
166.0

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
3.04
461.7 156.3
2.66
431.4 169.8
2.31
3.15
493.3 161.6
2.76
461.3 175.3
2.40
3.25
526.0 167.1
2.86
492.6 181.0
2.49
3.35
559.8 172.9
2.95
524.2 186.8
2.58
3.45
594.6 178.8
3.04
557.3 192.9
2.66

46
C.C. kW
387.8
391.7
398.7
405.8
410.7

P.I. kW
184.3
177.6
172.2
167.1
161.7

49
COP
kW/kW
1.93
2.02
2.11
2.21
2.30

C.C. kW
360.4
366.0
372.3
377.3
383.2

COP
P.I. kW kW/k
189.2
1.75
183.2
1.83
177.4
1.92
171.9
2.00
167.1
2.09

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

22

RLC-PRC015-E4

Performance Data
SI Units
Table P13 - RTAD 145 High Efficiency
LWT
C
5
7
9
11
13

25
C.C. kW P.I. kW
553.4
138.2
591.4
143.6
630.4
149.1
670.5
154.9
712.0
161.0

30
COP
kW/kW
3.52
3.64
3.75
3.86
3.96

C.C. kW
524.9
561.2
598.1
636.4
676.1

P.I. kW
149.1
154.6
160.3
166.2
172.3

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
3.13
495.1 161.4
2.75
464.5 175.1
2.40
3.24
529.5 167.0
2.85
496.8 180.8
2.50
3.34
564.7 172.8
2.95
530.2 186.8
2.59
3.44
601.2 178.9
3.05
565.0 193.0
2.68
3.54
638.9 185.1
3.14
600.5 199.3
2.76

46
C.C. kW
426.5
444.8
447.6
453.2
459.5

P.I. kW
193.4
193.6
186.0
179.5
174.1

49
COP
kW/kW
2.02
2.10
2.19
2.30
2.39

C.C. kW
406.8
415.2
419.5
424.4
430.0

COP
P.I. kW kW/kW
203.4
1.84
198.8
1.92
191.9
2.00
185.5
2.09
179.8
2.18

Table P14- RTAD 150 High Efficiency


LWT
C
5
7
9
11
13

25
C.C. kW P.I. kW
594.6
153.2
634.6
159.3
675.4
165.6
717.3
172.3
760.5
179.2

30
COP
kW/kW
3.42
3.52
3.62
3.72
3.81

C.C. kW
563.6
601.6
640.6
680.7
721.8

P.I. kW
164.9
171.1
177.7
184.4
191.5

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
3.04
531.6 178.1
2.68
498.6 192.9
2.34
3.14
567.8 184.6
2.77
532.7 199.5
2.43
3.23
604.8 191.2
2.86
567.5 206.3
2.51
3.32
642.7 198.1
2.94
603.4 213.3
2.59
3.41
681.8 205.2
3.03
640.3 220.6
2.66

46
C.C. kW
457.8
477.8
483.1
489.4
495.8

P.I. kW
212.9
213.8
206.7
199.7
193.6

49
COP
kW/kW
1.97
2.05
2.13
2.23
2.33

C.C. kW
436.69
447.24
453.56
460.24
466.57

COP
P.I. kW kW/kW
223.7
1.8
219.7
1.87
213.4
1.95
207.2
2.03
200.9
2.12

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

23

Performance Data
SI Units
Table P15 - RTAD 085 Standard Efficiency Low Noise
LWT
C
5
7
9
11
13

25
C.C. kW
286.9
305.2
323.8
342.8
362.2

P.I. kW
79.8
83.0
86.4
90.0
93.7

COP
kW/kW
3.28
3.36
3.44
3.51
3.57

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
269.3
86.4
2.87
251.0
93.8
286.6
89.8
2.94
267.2
97.3
304.1
93.3
3.02
283.7
101.0
322.1
97.0
3.08
300.6
104.8
340.4
100.8
3.14
317.9
108.7

40
COP
kW/kW
2.48
2.55
2.62
2.68
2.74

C.C. kW
232.4
247.5
263.0
268.3
271.8

P.I. kW
102.0
105.6
109.4
106.4
102.0

COP
kW/kW
2.13
2.19
2.26
2.36
2.49

Table P16- RTAD 100 Standard Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
343.5
365.0
386.8
409.3
432.1

P.I. kW
97.3
101.4
105.7
110.3
115.0

COP
kW/kW
3.28
3.35
3.42
3.48
3.53

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
322.4
104.2
2.89
300.3
112.0
342.5
108.5
2.96
319.3
116.4
362.9
112.9
3.02
338.6
121.0
384.0
117.6
3.07
358.6
125.8
405.4
122.5
3.13
378.7
130.8

40
COP
kW/kW
2.52
2.58
2.64
2.69
2.74

C.C. kW
278.1
295.7
301.0
305.2
310.5

P.I. kW
120.8
125.3
121.7
117.4
113.4

COP
kW/kW
2.17
2.23
2.33
2.45
2.58

Table P17 - RTAD 115 Standard Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
405.0
429.3
453.9
478.5
503.5

P.I. kW
124.0
129.2
134.7
140.4
146.4

COP
kW/kW
3.08
3.14
3.19
3.24
3.28

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
379.4
134.5
2.68
353.4
146.3
402.2
140.0
2.73
374.5
152.0
425.1
145.7
2.78
395.6
158.0
448.3
151.7
2.82
414.5
162.1
471.5
157.9
2.86
420.2
156.5

40
COP
kW/kW
2.30
2.35
2.40
2.45
2.57

C.C. kW
318.9
323.1
328.4
331.9
336.1

P.I. kW
154.0
149.3
144.8
140.6
136.4

COP
kW/kW
1.98
2.07
2.16
2.24
2.34

Table P18 - RTAD 125 Standard Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
459.2
484.5
510.5
536.2
562.2

P.I. kW
160.0
167.0
174.3
182.0
189.9

COP
kW/kW
2.74
2.78
2.81
2.83
2.85

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
429.0
173.6
2.37
391.0
183.1
452.5
180.9
2.41
397.0
177.5
476.8
188.5
2.44
404.0
172.1
491.5
188.7
2.51
408.9
166.2
497.9
181.8
2.63
415.2
161.8

40
COP
kW/kW
2.06
2.15
2.25
2.36
2.46

C.C. kW
311.2
315.4
320.3
323.1
327.3

P.I. kW
160.8
155.9
152.3
147.9
143.9

COP
kW/kW
1.85
1.93
2.01
2.08
2.17

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

24

RLC-PRC015-E4

Performance Data
SI Units
Table P19 - RTAD 145 Standard Efficiency Low Noise
LWT
C
5
7
9
11
13

25
C.C. kW
534.1
566.8
600.2
634.3
669.1

P.I. kW
158.5
165.3
172.3
179.6
187.1

COP
kW/kW
3.15
3.22
3.28
3.33
3.38

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
502.4
171.6
2.76
470.1
186.0
533.4
178.5
2.82
499.3
193.1
565.0
185.8
2.88
526.7
199.3
597.0
193.3
2.93
530.9
191.4
629.4
201.0
2.97
535.8
183.5

40
COP
kW/kW
2.39
2.45
2.51
2.63
2.76

C.C. kW
404.3
408.6
412.8
419.1
425.8

P.I. kW
182.2
175.7
169.8
165.0
161.3

COP
kW/kW
2.10
2.20
2.29
2.39
2.48

Table P20- RTAD 150 Standard Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
570.7
605.1
639.6
674.7
710.2

P.I. kW
175.2
182.8
190.7
198.9
207.4

COP
kW/kW
3.05
3.11
3.16
3.20
3.24

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
537.2
189.3
2.67
502.4
205.0
569.2
197.1
2.72
532.3
213.0
601.9
205.3
2.77
560.8
220.0
634.6
213.7
2.81
567.8
212.9
667.7
222.4
2.85
575.2
205.6

40
COP
kW/kW
2.32
2.37
2.42
2.53
2.65

C.C. kW
436.0
442.3
446.5
453.6
456.7

P.I. kW
202.4
196.4
190.0
184.6
178.9

COP
kW/kW
2.04
2.13
2.21
2.31
2.40

Table P21- RTAD 165 Standard Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
624.4
663.5
702.9
742.6
783.4

P.I. kW
191.5
200.0
208.8
218.1
227.6

COP
kW/kW
3.05
3.11
3.17
3.21
3.26

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
589.6
206.9
2.68
554.1
224.0
626.6
215.7
2.74
588.6
233.1
663.5
224.8
2.79
615.7
237.9
701.1
234.3
2.84
621.3
229.3
739.4
244.2
2.88
633.6
223.8

40
COP
kW/kW
2.34
2.39
2.46
2.57
2.68

C.C. kW
477.1
485.6
489.4
492.6
496.8

P.I. kW
219.1
213.7
206.6
199.4
194.0

COP
kW/kW
2.06
2.15
2.23
2.32
2.40

Table P22 - RTAD 180 Standard Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
668.7
710.2
751.7
793.9
836.8

P.I. kW
209.9
219.4
229.2
239.5
250.3

COP
kW/kW
2.98
3.04
3.09
3.13
3.16

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
632.5
226.6
2.63
594.6
245.2
671.2
236.5
2.68
630.8
255.4
710.2
246.7
2.72
656.1
259.1
750.0
257.4
2.76
663.8
251.2
790.1
268.6
2.80
673.3
242.9

40
COP
kW/kW
2.29
2.34
2.40
2.51
2.62

C.C. kW
511.6
517.9
525.6
530.6
537.6

P.I. kW
239.0
231.9
226.5
220.0
215.0

COP
kW/kW
2.02
2.11
2.19
2.27
2.35

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

25

Performance Data
SI Units
Table P23 - RTAD 085 High Efficiency Low Noise
LWT
C
5
7
9
11
13

25
C.C. kW
305.9
330.5
351.3
372.3
393.8

P.I. kW
75.3
79.0
82.3
85.6
89.1

COP
kW/kW
3.69
3.82
3.91
4.00
4.07

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
288.0
81.2
3.24
269.0
87.9
310.8
85.0
3.36
290.4
91.8
330.2
88.3
3.45
308.7
95.2
350.2
91.8
3.53
327.3
98.7
370.6
95.4
3.60
346.7
102.4

40
COP
kW/kW
2.82
2.93
3.01
3.09
3.16

C.C. kW
249.3
269.3
286.6
304.1
322.4

P.I. kW
95.3
99.3
102.8
106.4
110.2

COP
kW/kW
2.43
2.53
2.60
2.68
2.75

Table P24- RTAD 100 High Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
365.3
388.9
413.1
437.7
463.1

P.I. kW
89.3
92.8
96.4
100.2
104.2

COP
kW/kW
3.68
3.78
3.88
3.97
4.06

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
343.5
96.3
3.24
321.0
104.1
366.0
99.9
3.33
342.1
107.9
388.9
103.7
3.43
363.9
111.8
412.1
107.6
3.51
386.1
115.9
436.3
111.7
3.59
408.6
120.1

40
COP
kW/kW
2.82
2.91
3.00
3.08
3.15

C.C. kW
298.2
317.9
338.2
359.3
380.4

P.I. kW
112.9
116.8
120.8
125.0
129.4

COP
kW/kW
2.43
2.52
2.60
2.67
2.74

Table P25- RTAD 115 High Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
434.2
463.1
492.6
522.8
553.8

P.I. kW
116.3
120.9
125.8
130.9
136.2

COP
kW/kW
3.44
3.54
3.63
3.72
3.80

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
408.9
126.0
3.01
383.2
136.8
436.3
130.8
3.11
408.9
141.8
464.5
135.8
3.19
435.3
147.0
492.9
141.1
3.27
462.0
152.5
522.1
146.6
3.34
489.8
158.2

40
COP
kW/kW
2.62
2.70
2.78
2.85
2.92

C.C. kW
356.5
380.8
405.4
421.9
427.6

P.I. kW
148.8
154.0
159.4
160.2
154.4

COP
kW/kW
2.25
2.33
2.40
2.49
2.61

Table P26 - RTAD 125 High Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
506.7
539.4
572.8
607.2
642.4

P.I. kW
142.8
148.5
154.5
160.8
167.3

COP
kW/kW
3.27
3.36
3.44
3.51
3.58

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
477.5
154.8
2.86
447.2
168.0
508.4
160.7
2.94
476.8
174.2
540.1
166.9
3.02
506.7
180.6
572.8
173.4
3.09
537.2
187.2
606.2
180.0
3.16
568.5
194.1

40
COP
kW/kW
2.49
2.56
2.63
2.70
2.76

C.C. kW
416.7
444.1
448.6
456.7
462.0

P.I. kW
182.6
189.0
182.0
176.6
169.8

COP
kW/kW
2.14
2.21
2.32
2.43
2.55

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

26

RLC-PRC015-E4

Performance Data
SI Units
Table P27 - RTAD 145 High Efficiency Low Noise
LWT
C
5
7
9
11
13

25
C.C. kW
542.9
578.7
615.7
653.3
692.0

P.I. kW
146.8
152.8
159.1
165.6
172.4

COP
kW/kW
3.39
3.48
3.57
3.65
3.73

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
513.3
158.8
2.98
482.8
172.2
547.4
165.0
3.07
514.7
178.6
582.3
171.4
3.16
547.8
185.2
617.8
178.1
3.23
581.6
192.0
654.3
185.1
3.30
616.0
199.2

40
COP
kW/kW
2.61
2.69
2.77
2.84
2.91

C.C. kW
451.1
481.3
507.7
510.9
514.7

P.I. kW
186.9
193.5
197.8
189.8
181.8

COP
kW/kW
2.26
2.33
2.41
2.52
2.65

Table P28- RTAD 150 High Efficiency Low Noise


LWT
C
5
7
9
11
13

25
C.C. kW
581.9
619.9
658.2
697.2
737.0

P.I. kW
162.8
169.7
176.8
184.3
192.0

COP
kW/kW
3.28
3.37
3.44
3.51
3.57

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
550.3
175.8
2.89
517.6
190.3
585.8
182.9
2.97
551.0
197.6
622.0
190.2
3.04
585.1
205.1
658.9
197.8
3.11
619.9
212.9
696.9
205.7
3.17
655.4
221.0

40
COP
kW/kW
2.53
2.60
2.67
2.73
2.79

C.C. kW
483.5
514.7
540.1
548.1
554.8

P.I. kW
206.4
213.9
217.7
211.6
204.1

COP
kW/kW
2.19
2.26
2.33
2.43
2.55

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

27

Performance Data
SI Units
Table P29 - RTAD 085 Standard Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
273.2
289.4
305.5
321.7
338.2

P.I. kW
88.2
92.1
96.2
100.5
105.0

COP
kW/kW
2.97
3.02
3.06
3.09
3.11

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
255.3
95.6
2.57
236.6
103.8
270.0
99.7
2.61
250.3
108.1
285.2
104.0
2.65
253.2
103.8
300.6
108.4
2.68
257.4
100.3
313.6
111.3
2.73
261.6
97.3

40
COP
kW/kW
2.20
2.24
2.36
2.48
2.59

C.C. kW
195.1
198.3
200.8
203.2
206.7

P.I. kW
96.0
93.6
91.3
88.5
85.1

COP
kW/kW
1.96
2.04
2.11
2.21
2.33

Table P30- RTAD 100 Standard Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
334.0
359.3
380.4
401.9
423.7

P.I. kW
98.4
103.7
108.2
112.9
117.8

COP
kW/kW
3.22
3.30
3.35
3.40
3.44

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
312.9
105.6
2.82
291.5
113.7
336.8
111.0
2.90
313.6
119.2
356.5
115.6
2.95
332.3
124.0
376.6
120.5
3.00
350.9
129.0
397.3
125.6
3.04
356.5
125.0

40
COP
kW/kW
2.45
2.52
2.57
2.62
2.74

C.C. kW
269.7
277.8
282.0
285.5
290.1

P.I. kW
122.7
120.2
116.2
111.3
108.2

COP
kW/kW
2.11
2.22
2.33
2.45
2.56

Table P31- RTAD 115 Standard Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
397.7
420.5
443.7
466.9
490.5

P.I. kW
128.0
133.5
139.4
145.5
151.9

COP
kW/kW
2.98
3.03
3.07
3.10
3.12

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
371.6
139.0
2.58
345.3
151.1
393.1
144.8
2.62
365.0
157.2
414.9
150.9
2.66
377.3
157.5
436.3
157.2
2.69
384.0
153.1
458.1
163.8
2.71
388.2
146.9

40
COP
kW/kW
2.21
2.25
2.32
2.43
2.55

C.C. kW
293.2
297.5
300.6
304.1
309.4

P.I. kW
146.2
142.3
138.2
134.2
130.9

COP
kW/kW
1.94
2.02
2.10
2.18
2.27

Table P32 - RTAD 125 Standard Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
447.6
471.5
495.4
519.7
536.2

P.I. kW
166.1
173.6
181.5
189.7
191.6

COP
kW/kW
2.61
2.64
2.66
2.67
2.73

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
417.0
180.2
2.25
359.7
173.1
439.5
188.0
2.28
366.0
167.8
447.9
184.0
2.37
370.9
162.7
453.6
177.2
2.49
376.9
158.4
459.9
170.9
2.61
381.8
154.1

40
COP
kW/kW
2.02
2.12
2.21
2.30
2.40

C.C. kW
284.8
288.3
292.2
296.4
300.3

P.I. kW
153.5
149.8
146.3
142.8
138.5

COP
kW/kW
1.80
1.86
1.93
2.00
2.09

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

28

RLC-PRC015-E4

Performance Data
SI Units
Table P33 - RTAD 145 Standard Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
520.7
551.3
582.3
613.9
645.2

P.I. kW
167.1
174.5
182.2
190.2
198.5

COP
kW/kW
2.99
3.04
3.08
3.12
3.14

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
488.7
180.9
2.60
434.2
182.4
517.6
188.6
2.65
438.8
176.0
544.3
195.2
2.70
443.4
169.9
548.9
187.4
2.83
450.8
165.5
553.8
179.5
2.97
454.6
159.5

40
COP
kW/kW
2.30
2.40
2.51
2.62
2.74

C.C. kW
337.2
341.8
348.4
354.4
357.6

P.I. kW
159.9
155.9
153.3
150.1
145.4

COP
kW/kW
2.02
2.10
2.18
2.26
2.35

Table P34- RTAD 150 Standard Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
550.3
581.2
612.1
642.7
673.7

P.I. kW
191.3
200.0
209.1
218.5
228.3

COP
kW/kW
2.78
2.81
2.84
2.85
2.87

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
515.8
206.9
2.41
456.7
207.0
544.3
215.9
2.45
463.4
200.9
567.5
221.0
2.49
469.4
195.0
574.2
213.5
2.61
476.8
189.9
583.3
207.5
2.72
482.0
184.0

40
COP
kW/kW
2.14
2.23
2.33
2.43
2.53

C.C. kW
359.3
361.4
366.4
370.6
377.3

P.I. kW
182.5
177.5
173.9
169.5
165.9

COP
kW/kW
1.90
1.96
2.03
2.10
2.19

Table P35- RTAD 165 Standard Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
612.1
649.4
686.0
723.2
760.9

P.I. kW
200.2
209.5
219.1
229.1
239.6

COP
kW/kW
2.93
2.98
3.02
3.05
3.07

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
577.0
216.5
2.57
522.1
223.2
611.4
226.1
2.61
529.5
217.0
646.2
236.1
2.65
538.7
211.5
657.8
231.3
2.75
542.2
203.9
668.4
224.8
2.87
547.8
197.6

40
COP
kW/kW
2.26
2.35
2.45
2.56
2.66

C.C. kW
409.6
413.1
415.9
418.8
419.8

P.I. kW
196.5
191.2
186.2
180.7
174.7

COP
kW/kW
2.00
2.07
2.14
2.22
2.29

Table P36 - RTAD 180 Standard Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
651.2
689.5
727.1
765.4
804.1

P.I. kW
222.6
233.3
244.2
255.8
267.8

COP
kW/kW
2.82
2.85
2.88
2.90
2.91

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
613.5
240.7
2.47
555.2
247.6
649.1
251.7
2.50
561.5
240.5
684.6
263.1
2.52
568.9
233.3
695.8
257.8
2.62
576.3
227.6
703.2
248.2
2.74
583.3
222.0

40
COP
kW/kW
2.17
2.26
2.36
2.44
2.54

C.C. kW
439.2
444.8
447.6
454.3
459.5

P.I. kW
218.5
213.7
207.9
203.4
198.7

COP
kW/kW
1.94
2.00
2.07
2.15
2.22

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

29

Performance Data
SI Units
Table P37 - RTAD 085 High Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
307.3
326.6
346.7
367.1
387.8

P.I. kW
77.5
80.7
84.1
87.6
91.3

COP
kW/kW
3.70
3.79
3.87
3.95
4.01

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
288.3
83.6
3.24
269.0
90.4
306.6
86.9
3.33
286.2
93.9
325.6
90.4
3.40
303.8
97.4
344.9
94.0
3.47
322.1
101.1
364.6
97.7
3.54
340.7
105.0

40
COP
kW/kW
2.81
2.89
2.96
3.03
3.09

C.C. kW
248.9
265.1
281.6
298.9
316.1

P.I. kW
98.0
101.6
105.2
109.0
112.9

COP
kW/kW
2.41
2.48
2.55
2.62
2.68

Table P38- RTAD 100 High Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
353.4
375.2
397.0
419.5
442.3

P.I. kW
94.8
98.8
102.9
107.2
111.7

COP
kW/kW
3.53
3.60
3.67
3.73
3.78

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
331.2
102.4
3.08
308.7
110.7
351.6
106.5
3.15
327.7
115.0
372.3
110.8
3.21
347.4
119.5
393.8
115.2
3.27
367.1
124.2
415.2
119.9
3.32
387.1
129.0

40
COP
kW/kW
2.66
2.73
2.79
2.84
2.89

C.C. kW
285.5
303.4
315.0
320.0
325.6

P.I. kW
120.0
124.5
125.0
120.7
116.8

COP
kW/kW
2.28
2.34
2.42
2.54
2.67

Table P39 RTAD 115 High Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
430.0
458.1
487.0
516.2
546.0

P.I. kW
119.3
124.2
129.3
134.6
140.2

COP
kW/kW
3.41
3.49
3.57
3.65
3.71

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
404.7
129.2
2.97
378.7
140.4
431.1
134.3
3.05
403.6
145.7
458.1
139.7
3.13
429.0
151.2
485.9
145.3
3.20
455.0
157.0
513.7
151.1
3.26
481.0
163.0

40
COP
kW/kW
2.57
2.65
2.72
2.78
2.84

C.C. kW
352.0
375.2
385.7
392.4
395.9

P.I. kW
152.7
158.2
156.4
151.8
145.8

COP
kW/kW
2.21
2.27
2.37
2.48
2.60

Table P40 - RTAD 125 High Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
493.3
523.5
554.5
585.8
617.8

P.I. kW
152.2
158.7
165.5
172.5
179.9

COP
kW/kW
3.10
3.16
3.22
3.27
3.31

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
463.4
165.1
2.70
432.8
179.2
491.9
171.8
2.76
459.5
186.2
521.1
178.8
2.81
475.7
186.3
550.6
186.1
2.86
482.0
179.9
580.5
193.7
2.90
489.1
173.8

40
COP
kW/kW
2.33
2.38
2.47
2.58
2.71

C.C. kW
366.7
372.7
378.3
384.3
387.8

P.I. kW
172.2
166.9
162.3
157.8
152.9

COP
kW/kW
2.05
2.15
2.24
2.34
2.43

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

30

RLC-PRC015-E4

Performance Data
SI Units
Table P41 - RTAD 085 High Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
535.1
569.9
605.1
640.6
677.2

P.I. kW
152.5
159.0
165.7
172.7
180.0

COP
kW/kW
3.32
3.40
3.47
3.54
3.60

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
505.3
165.1
2.91
474.3
179.1
538.0
171.8
2.99
504.9
186.0
571.0
178.7
3.05
536.2
193.1
604.8
185.9
3.11
560.5
196.4
639.2
193.4
3.17
566.4
189.4

40
COP
kW/kW
2.53
2.60
2.66
2.74
2.87

C.C. kW
427.2
430.0
434.6
440.2
446.5

P.I. kW
186.2
178.9
172.7
167.5
162.4

COP
kW/kW
2.20
2.30
2.40
2.50
2.62

Table P42- RTAD 100 High Efficiency Low Noise Night Noise Set Back
LWT
C
5
7
9
11
13

25
C.C. kW
570.7
606.5
642.0
678.6
715.5

P.I. kW
171.1
178.6
186.4
194.6
203.1

COP
kW/kW
3.18
3.24
3.30
3.34
3.38

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
538.3
185.0
2.78
504.6
200.4
571.7
192.8
2.84
535.8
208.4
605.5
200.8
2.89
567.5
216.7
639.6
209.2
2.94
592.8
221.0
674.4
217.9
2.98
601.2
214.5

40
COP
kW/kW
2.42
2.47
2.52
2.59
2.70

C.C. kW
456.0
461.3
467.6
473.3
480.3

P.I. kW
208.8
202.0
196.1
190.2
184.5

COP
kW/kW
2.10
2.19
2.29
2.39
2.49

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

31

Performance Data
SI Units
Table P43 - RTAD 085 Standard High External Static Pressure
LWT
C
5
7
9
11
13

25
C.C. kW
286.6
304.8
323.5
342.8
362.2

P.I. kW
79.5
82.7
86.1
89.7
93.4

COP
kW/kW
2.98
3.07
3.15
3.23
3.30

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
269.0
86.3
2.62
250.3
93.9
286.2
89.7
2.70
266.5
97.4
303.8
93.2
2.77
283.0
101.1
321.7
96.9
2.84
299.9
104.9
340.0
100.7
2.91
317.1
108.9

40
COP
kW/kW
2.28
2.35
2.42
2.48
2.54

C.C. kW
231.4
246.5
260.9
264.8
269.0

P.I. kW
102.3
106.0
109.1
105.3
101.6

COP
kW/kW
1.96
2.02
2.09
2.18
2.29

Table P44- RTAD 100 Standard High External Static Pressure


LWT
C
5
7
9
11
13

25
C.C. kW
341.1
362.2
383.6
405.4
427.9

P.I. kW
98.2
102.4
106.8
111.4
116.3

COP
kW/kW
2.98
3.05
3.12
3.18
3.23

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
318.9
105.5
2.62
296.4
113.8
338.6
109.9
2.69
314.7
118.4
359.0
114.5
2.75
333.7
123.1
379.4
119.3
2.81
353.0
128.1
400.5
124.3
2.86
361.8
126.3

40
COP
kW/kW
2.29
2.35
2.40
2.45
2.55

C.C. kW
273.2
279.9
284.1
289.4
293.2

P.I. kW
123.1
120.8
116.8
113.1
109.2

COP
kW/kW
1.97
2.05
2.15
2.25
2.35

Table P45 RTAD 115 Standard High External Static Pressure


LWT
C
5
7
9
11
13

25
C.C. kW
401.9
425.8
449.7
474.0
498.2

P.I. kW
125.3
130.7
136.3
142.2
148.4

COP
kW/kW
2.84
2.90
2.95
3.00
3.03

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
375.5
136.5
2.46
348.1
149.0
397.7
142.2
2.52
368.5
155.0
419.8
148.1
2.56
389.2
161.2
442.3
154.3
2.60
394.9
156.1
464.8
160.7
2.64
401.2
151.0

40
COP
kW/kW
2.11
2.16
2.20
2.30
2.41

C.C. kW
300.3
305.2
308.4
312.6
316.4

P.I. kW
148.4
144.2
140.4
136.5
132.2

COP
kW/kW
1.83
1.91
1.98
2.06
2.14

Table P46 - RTAD 125 Standard High External Static Pressure


LWT
C
5
7
9
11
13

25
C.C. kW
454.6
479.6
504.6
529.5
554.5

P.I. kW
162.2
169.4
177.0
184.9
193.2

COP
kW/kW
2.55
2.59
2.62
2.64
2.66

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
423.0
176.7
2.20
372.3
177.4
445.8
184.3
2.23
379.0
172.6
465.5
189.2
2.27
384.7
166.9
472.2
183.1
2.38
389.9
161.9
477.5
175.6
2.50
393.4
156.0

40
COP
kW/kW
1.93
2.01
2.11
2.20
2.29

C.C. kW
291.8
295.7
299.9
303.4
307.3

P.I. kW
155.6
151.3
148.0
144.1
140.0

COP
kW/kW
1.71
1.77
1.83
1.90
1.98

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

32

RLC-PRC015-E4

Performance Data
SI Units
Table P47 - RTAD 145 Standard High External Static Pressure
LWT
C
5
7
9
11
13

25
C.C. kW
532.7
565.4
598.8
632.9
667.3

P.I. kW
158.7
165.5
172.6
179.9
187.5

COP
kW/kW
2.91
2.98
3.05
3.11
3.16

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
500.3
172.3
2.55
467.3
187.3
531.3
179.3
2.62
496.1
194.6
562.6
186.6
2.68
523.2
200.9
594.2
194.3
2.73
527.4
193.0
626.2
202.2
2.78
532.3
185.0

40
COP
kW/kW
2.22
2.28
2.33
2.44
2.56

C.C. kW
397.0
400.1
405.8
411.7
418.1

P.I. kW
181.5
174.7
169.6
164.7
161.1

COP
kW/kW
1.94
2.02
2.10
2.19
2.27

Table P48- RTAD 150 Standard High External Static Pressure


LWT
C
5
7
9
11
13

25
C.C. kW
571.0
605.1
639.9
675.4
710.9

P.I. kW
174.5
182.0
189.9
198.0
206.5

COP
kW/kW
2.84
2.90
2.96
3.01
3.05

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
536.5
189.0
2.49
501.0
205.3
568.5
196.9
2.55
530.9
213.4
601.2
205.0
2.60
556.9
219.1
633.9
213.4
2.65
566.1
213.2
667.3
222.2
2.69
573.5
205.9

40
COP
kW/kW
2.17
2.22
2.28
2.37
2.48

C.C. kW
429.7
434.6
440.2
447.2
451.8

P.I. kW
200.7
194.2
188.7
183.2
178.6

COP
kW/kW
1.90
1.98
2.05
2.14
2.21

Table P49 RTAD 165 Standard High External Static Pressure


LWT
C
5
7
9
11
13

25
C.C. kW
619.5
658.9
698.3
738.4
778.8

P.I. kW
184.2
192.4
200.8
209.7
218.9

COP
kW/kW
2.90
2.97
3.04
3.09
3.14

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
585.1
199.5
2.56
548.9
216.5
621.6
208.0
2.63
583.0
225.4
658.6
216.8
2.68
617.4
234.5
696.2
226.0
2.73
626.2
228.1
734.1
235.6
2.78
636.4
221.6

40
COP
kW/kW
2.24
2.30
2.35
2.44
2.55

C.C. kW
479.2
487.3
492.2
496.5
499.3

P.I. kW
216.5
211.1
204.5
197.8
191.5

COP
kW/kW
1.96
2.04
2.12
2.20
2.27

Table P50 - RTAD 180 Standard High External Static Pressure


LWT
C
5
7
9
11
13

25
C.C. kW
665.2
707.1
748.9
791.5
834.4

P.I. kW
201.0
210.0
219.3
229.1
239.4

COP
kW/kW
2.86
2.92
2.98
3.04
3.08

Entering Condenser Air Temperature (C)


30
35
COP
C.C. kW
P.I. kW
kW/kW
C.C. kW
P.I. kW
628.7
217.5
2.52
590.7
235.9
667.7
226.9
2.59
626.9
245.7
706.7
236.6
2.64
663.5
255.9
746.8
246.9
2.69
671.9
248.7
787.2
257.6
2.73
681.8
241.3

40
COP
kW/kW
2.21
2.27
2.31
2.40
2.51

C.C. kW
515.1
520.0
527.4
535.5
540.8

P.I. kW
235.1
227.3
221.6
216.7
210.8

COP
kW/kW
1.94
2.02
2.09
2.16
2.24

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

33

Performance Data
SI Units
Table P51 - RTAD 085 High Efficiency
LWT
C
5
7
9
11
13

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
COP
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
308.7
76.5
3.32
289.7
82.7
2.93
269.7
89.6
2.55
249.3
97.4
2.20
328.8
79.6
3.42
308.4
85.9
3.02
287.3
93.0
2.64
265.8 100.9
2.28
349.1
82.9
3.52
327.7
89.3
3.11
305.5
96.5
2.72
282.7 104.5
2.35
369.9
86.3
3.61
347.4
92.8
3.19
323.8 100.1
2.79
299.9 108.2
2.42
391.3
89.9
3.69
367.4
96.4
3.27
342.8 103.9
2.86
317.5 112.1
2.49
25

30

46
C.C. kW
237.0
253.5
271.1
289.0
307.3

P.I. kW
100.3
103.4
106.6
109.9
113.3

49
COP
kW/kW
2.15
2.24
2.32
2.41
2.49

C.C. kW
224.3
240.5
257.4
274.6
292.5

COP
P.I. kW kW/kW
105.4
1.94
108.6
2.03
111.8
2.11
115.2
2.19
118.6
2.28

Table P52- RTAD 100 High Efficiency


LWT
C
5
7
9
11
13

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
COP
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
365.0
89.1
3.29
343.2
96.2
2.91
320.3 104.3
2.55
296.8 113.3
2.21
388.9
92.6
3.40
365.3
99.8
3.01
341.4 108.0
2.64
316.4 117.2
2.29
413.1
96.2
3.50
388.5 103.6
3.11
362.9 111.9
2.73
336.8 121.3
2.37
438.1
99.9
3.60
411.7
107.5
3.19
385.0 116.0
2.81
357.6 125.5
2.44
463.4
103.9
3.69
436.0 111.6
3.28
407.9 120.2
2.89
379.0 129.9
2.51
25

30

46
C.C. kW
280.9
300.6
321.4
342.8
364.6

P.I. kW
117.6
121.2
124.9
128.7
132.7

49
COP
kW/kW
2.14
2.24
2.32
2.41
2.50

C.C. kW
266.5
285.9
305.5
326.3
335.4

COP
P.I. kW kW/kW
123.5
1.95
127.2
2.03
131.1
2.12
135.0
2.20
132.6
2.30

Table P53 - RTAD 115 High Efficiency


LWT
C
5
7
9
11
13

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
COP
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
432.1
117.1
3.11
406.5 127.2
2.74
380.1 138.5
2.38
352.7 151.1
2.05
460.6
121.8
3.21
433.5 132.1
2.83
405.4 143.7
2.46
376.2 156.6
2.12
490.1
126.7
3.31
461.0 137.2
2.91
431.1 149.1
2.54
397.3 160.3
2.20
520.4
131.9
3.39
489.4 142.6
2.99
457.8 154.7
2.61
402.6 155.1
2.29
551.0
137.3
3.47
518.3 148.3
3.06
484.5 160.5
2.67
407.5 148.8
2.40
25

30

46
C.C. kW
335.8
359.7
384.7
410.3
431.1

P.I. kW
154.0
158.7
163.6
168.7
170.9

49
COP
kW/kW
2.01
2.09
2.18
2.26
2.34

C.C. kW
319.3
340.7
346.0
352.0
356.5

COP
P.I. kW kW/kW
162.2
1.82
166.1
1.90
161.1
1.99
156.1
2.08
151.3
2.17

Table P54 - RTAD 125 High Efficiency


LWT
C
5
7
9
11
13

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
COP
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
506.3
142.3
2.99
476.4 154.6
2.63
446.2 168.3
2.29
414.5 183.3
1.98
539.0
148.0
3.08
507.7 160.5
2.71
475.4 174.4
2.37
437.4 187.2
2.05
572.8
153.9
3.17
539.4 166.7
2.79
505.3 180.8
2.44
444.4 181.4
2.14
607.6
160.1
3.25
572.1 173.1
2.87
535.8 187.5
2.51
449.3 174.4
2.24
642.7
166.6
3.33
605.5 179.8
2.94
567.1 194.4
2.58
455.7 168.6
2.34
25

30

46
C.C. kW
394.5
422.3
451.1
458.1
466.2

P.I. kW
187.8
193.5
199.4
193.2
187.3

49
COP
kW/kW
1.93
2.01
2.09
2.19
2.29

C.C. kW
360.4
366.0
372.3
377.3
383.2

COP
P.I. kW kW/kW
189.2
1.75
183.2
1.83
177.4
1.92
171.9
2.00
167.1
2.09

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

34

RLC-PRC015-E4

Performance Data
SI Units
Table P55 - RTAD 145 High Efficiency
LWT
C
5
7
9
11
13

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
COP
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
541.5
146.9
3.07
511.6 159.2
2.71
480.6 173.1
2.38
447.9 188.4
2.07
577.7
152.9
3.17
545.7 165.5
2.80
512.3 179.5
2.46
478.2 195.1
2.14
614.3
159.2
3.26
580.1 172.0
2.89
545.0 186.2
2.54
499.3 196.9
2.22
651.9
165.7
3.34
616.0 178.7
2.97
578.7 193.2
2.61
502.4 188.7
2.32
690.5
172.5
3.42
652.2 185.7
3.04
612.8 200.4
2.68
506.0 180.5
2.42
25

30

C.C. kW
426.5
444.8
447.6
453.2
459.5

P.I. kW
193.4
193.6
186.0
179.5
174.1

46
COP
kW/kW
2.02
2.10
2.19
2.30
2.39

P.I. kW
212.9
213.8
206.7
199.7
193.6

46
COP
kW/kW
1.97
2.05
2.13
2.23
2.33

C.C. kW
347.0
352.3
357.9
364.3
369.2

P.I. kW
174.1
169.4
164.8
161.1
157.1

49
COP
kW/kW
1.81
1.88
1.96
2.03
2.11

P.I. kW
192.9
188.6
183.5
178.2
174.1

49
COP
kW/kW
1.77
1.84
1.92
1.99
2.06

Table P56 - RTAD 150 High Efficiency


LWT
C
5
7
9
11
13

Entering Condenser Air Temperature (C)


35
40
COP
COP
COP
COP
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW C.C. kW P.I. kW kW/kW
581.6
162.3
2.99
549.6 175.6
2.65
515.8 190.6
2.32
481.3 207.2
2.02
619.5
169.1
3.08
585.1 182.7
2.73
549.2 197.8
2.40
512.6 214.7
2.09
657.8
176.2
3.16
621.3 190.0
2.80
583.3 205.4
2.47
533.0 215.9
2.16
697.2
183.6
3.23
658.2 197.6
2.87
618.1 213.2
2.53
540.8 209.7
2.25
737.0
191.3
3.30
695.8 205.5
2.94
653.6 221.3
2.59
547.1 201.9
2.35
25

30

C.C. kW
457.8
477.8
483.1
489.4
495.8

C.C. kW
377.27
384.3
390.28
392.74
398.36

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

35

Performance Data
SI Units
Table P57 - RTAD 085 High Efficiency High Ambient
30
LWT
C
5
7
9
11
13

C.C. kW
299.6
320.0
341.1
362.5
384.7

P.I. kW
77.6
80.5
83.5
86.6
89.9

35
COP
kW/kW
3.40
3.52
3.63
3.74
3.84

C.C. kW
280.6
299.9
320.0
340.4
361.4

P.I. kW
83.8
86.8
89.8
93.0
96.3

Entering Condenser Air Temperature (C)


40
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.98
261.2
90.8
2.58
237.0
3.09
279.2
93.8
2.68
253.5
3.19
297.8
96.9
2.78
271.1
3.29
317.1
100.2
2.88
289.0
3.39
337.2
103.5
2.97
307.3

46
P.I. kW
100.3
103.4
106.6
109.9
113.3

49
COP
kW/kW
2.15
2.24
2.32
2.41
2.49

C.C. kW
224.3
240.5
257.4
274.6
292.5

P.I. kW
105.4
108.6
111.8
115.2
118.6

COP
kW/kW
1.94
2.03
2.11
2.19
2.28

Table P58 - RTAD 100 High Efficiency High Ambient


30
LWT
C
5
7
9
11
13

C.C. kW
353.4
377.3
401.9
427.6
453.6

P.I. kW
91.1
94.3
97.6
101.1
104.7

35
COP
kW/kW
3.36
3.48
3.60
3.71
3.82

C.C. kW
331.6
354.1
377.6
401.9
426.5

P.I. kW
98.4
101.7
105.1
108.7
112.4

Entering Condenser Air Temperature (C)


40
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.95
308.7
106.5
2.57
280.9
3.07
330.2
110.0
2.67
300.6
3.18
352.3
113.5
2.77
321.4
3.28
375.5
117.2
2.87
342.8
3.38
399.1
121.0
2.96
364.6

46
P.I. kW
117.6
121.2
124.9
128.7
132.7

49
COP
kW/kW
2.14
2.24
2.32
2.41
2.50

C.C. kW
266.5
285.9
305.5
326.3
335.4

P.I. kW
123.5
127.2
131.1
135.0
132.6

COP
kW/kW
1.95
2.03
2.12
2.20
2.30

Table P59 - RTAD 115 High Efficiency High Ambient


30
LWT
C
5
7
9
11
13

C.C. kW
419.1
448.3
478.2
509.5
541.1

P.I. kW
118.0
122.2
126.5
131.1
135.9

35
COP
kW/kW
3.18
3.30
3.41
3.52
3.62

C.C. kW
393.8
421.6
450.1
479.2
509.5

P.I. kW
127.9
132.2
136.8
141.5
146.4

Entering Condenser Air Temperature (C)


40
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.79
367.8
139.0
2.41
335.8
2.89
393.8
143.5
2.51
359.7
3.00
420.9
148.2
2.61
384.7
3.09
448.6
153.1
2.70
410.3
3.19
477.1
158.2
2.78
431.1

46
P.I. kW
154.0
158.7
163.6
168.7
170.9

49
COP
kW/kW
2.01
2.09
2.18
2.26
2.34

C.C. kW
319.3
340.7
346.0
352.0
356.5

P.I. kW
162.2
166.1
161.1
156.1
151.3

COP
kW/kW
1.82
1.90
1.99
2.08
2.17

Table P60 - RTAD 125 High Efficiency High Ambient


30
LWT
C
5
7
9
11
13

C.C. kW
490.8
524.2
558.7
594.2
630.8

P.I. kW
144.1
149.2
154.6
160.2
166.0

35
COP
kW/kW
3.04
3.15
3.25
3.35
3.45

C.C. kW
461.7
493.3
526.0
559.8
594.6

P.I. kW
156.3
161.6
167.1
172.9
178.8

Entering Condenser Air Temperature (C)


40
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.66
431.4
169.8
2.31
394.5
2.76
461.3
175.3
2.40
422.3
2.86
492.6
181.0
2.49
451.1
2.95
524.2
186.8
2.58
458.1
3.04
557.3
192.9
2.66
466.2

46
P.I. kW
187.8
193.5
199.4
193.2
187.3

49
COP
kW/kW
1.93
2.01
2.09
2.19
2.29

C.C. kW
360.4
366.0
372.3
377.3
383.2

P.I. kW
189.2
183.2
177.4
171.9
167.1

COP
kW/kW
1.75
1.83
1.92
2.00
2.09

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

36

RLC-PRC015-E4

Performance Data
SI Units
Table P61 - RTAD 145 High Efficiency High Ambient
Entering Condenser Air Temperature (C)
30
COP
LWT
C
C.C. kW P.I. kW kW/kW C.C. kW
5
524.6
149.1
3.12
495.1
7
561.2
154.6
3.24
529.5
9
598.1
160.3
3.34
564.7
11
636.4
166.2
3.44
601.2
13
676.1
172.3
3.54
638.9

35

40
COP
kW/kW
2.75
2.85
2.95
3.05
3.14

P.I. kW
161.4
167.0
172.8
178.9
185.1

C.C. kW
464.5
496.8
530.2
565.0
600.5

P.I. kW
175.1
180.8
186.8
193.0
199.3

46
COP
kW/kW
2.40
2.50
2.59
2.68
2.76

C.C. kW
426.5
456.4
487.7
517.2
523.5

P.I. kW
193.4
199.3
205.5
210.5
203.4

49
COP
kW/kW
2.02
2.10
2.18
2.27
2.37

C.C. kW
406.8
415.2
419.5
424.4
430.0

P.I. kW
203.4
198.8
191.9
185.5
179.8

COP
kW/kW
1.84
1.92
2.00
2.09
2.18

Table P62 - RTAD 150 High Efficiency High Ambient


30
LWT
C
5
7
9
11
13

C.C. kW
563.6
601.6
640.6
680.7
721.8

P.I. kW
164.9
171.1
177.7
184.4
191.5

35
COP
kW/kW
3.04
3.14
3.23
3.32
3.41

C.C. kW
531.6
567.8
604.8
642.7
681.8

P.I. kW
178.1
184.6
191.2
198.1
205.2

Entering Condenser Air Temperature (C)


40
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.68
498.6
192.9
2.34
457.8
2.77
532.7
199.5
2.43
489.1
2.86
567.5
206.3
2.51
521.4
2.94
603.4
213.3
2.59
552.4
3.03
640.3
220.6
2.66
560.8

46
P.I. kW
212.9
219.6
226.6
232.4
225.9

49
COP
kW/kW
1.97
2.05
2.12
2.19
2.29

C.C. kW
436.7
447.2
453.6
460.2
466.6

P.I. kW
223.7
219.7
213.4
207.2
200.9

COP
kW/kW
1.80
1.87
1.95
2.03
2.12

Table P63 - RTAD 165 Standard Efficiency High Ambient


30
LWT
C
5
7
9
11
13

C.C. kW
604.1
644.5
684.9
726.8
769.7

P.I. kW
185.1
192.5
200.1
208.0
216.2

35
COP
kW/kW
2.97
3.05
3.13
3.21
3.28

C.C. kW
570.3
608.3
646.6
686.0
726.4

P.I. kW
199.9
207.5
215.3
223.5
232.0

Entering Condenser Air Temperature (C)


40
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.61
535.1
216.4
2.28
488.7
2.69
570.7
224.3
2.35
496.8
2.77
606.9
232.3
2.42
502.8
2.84
644.1
240.7
2.49
511.2
2.90
682.1
249.5
2.55
516.5

46
P.I. kW
237.2
231.7
224.4
218.7
211.9

49
COP
kW/kW
1.92
1.99
2.08
2.16
2.25

C.C. kW
402.6
406.1
407.9
411.0
414.9

P.I. kW
214.1
207.6
201.0
195.7
190.4

COP
kW/kW
1.74
1.80
1.86
1.92
1.99

Table P64 - RTAD 180 Standard Efficiency High Ambient


30

Entering Condenser Air Temperature (C)


40
COP
COP
kW/kW C.C. kW P.I. kW kW/kW C.C. kW
2.57
575.9
236.1
2.25
526.7
2.65
613.5
244.9
2.32
534.4
2.72
651.9
254.0
2.38
539.7
2.78
691.3
263.5
2.44
549.2
2.84
731.7
273.4
2.50
553.4

46
COP
COP
LWT
C
C.C. kW P.I. kW kW/kW C.C. kW P.I. kW
P.I. kW kW/kW
5
648.7
202.2
2.91
613.2
218.3
258.5
1.89
7
691.6
210.4
3.00
653.3
226.7
252.4
1.97
9
734.5
218.9
3.07
694.1
235.5
244.3
2.05
11
778.8
227.7
3.14
735.9
244.6
238.5
2.13
13
824.2
236.9
3.21
778.8
254.2
231.3
2.21
Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m K/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40C ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

35

49
C.C. kW
433.5
439.2
443.4
448.6
455.3

P.I. kW
232.7
226.7
220.7
215.6
210.5

COP
kW/kW
1.72
1.78
1.85
1.91
1.98

37

Performance Data
English Units
Table P65 - RTAD 085 High Efficiency High Ambient
LWT
F
41
44
45
46
48

C.C. Ton
85.2
90.0
91.7
93.3
96.6

86
P.I. kW
77.6
80.0
80.8
81.6
83.3

EER
11.6
11.9
12.1
12.2
12.4

C.C. Ton
79.8
84.4
85.9
87.5
90.6

95
P.I. kW
83.8
86.3
87.1
87.9
89.6

Entering Condenser Air Temperature (C)


104
EER
C.C. Ton P.I. kW
EER
C.C. Ton
10.2
74.3
90.8
8.8
68.5
10.5
78.5
93.3
9.1
72.5
10.6
80.0
94.2
9.2
73.9
10.7
81.5
95.0
9.3
75.3
10.9
84.4
96.8
9.5
78.1

113
P.I. kW
98.6
101.2
102.0
102.9
104.7

EER
7.6
7.8
7.9
8.0
8.2

C.C. Ton
64.0
67.8
69.1
70.4
73.0

120
P.I. kW
105.2
107.8
108.7
109.6
111.4

EER
6.7
6.9
7.0
7.1
7.2

113
P.I. kW
115.6
118.6
119.6
120.6
122.7

EER
7.6
7.8
7.9
8.0
8.2

C.C. Ton
76.0
80.5
82.1
83.6
86.8

120
P.I. kW
123.3
126.4
127.4
128.5
130.6

EER
6.7
6.9
7.0
7.1
7.2

113
P.I. kW
151.4
155.3
156.6
157.9
160.6

EER
7.1
7.3
7.4
7.5
7.7

C.C. Ton
91.0
96.5
97.9
98.3
99.2

120
P.I. kW
161.9
165.9
166.4
165.1
162.4

EER
6.2
6.5
6.5
6.6
6.8

113
P.I. kW
184.7
189.4
191.0
192.6
195.8

EER
6.8
7.0
7.1
7.2
7.3

C.C. Ton
103.4
104.4
105.1
105.8
106.4

120
P.I. kW
190.0
184.5
183.4
182.1
178.2

EER
6.0
6.2
6.3
6.4
6.6

Table P66 - RTAD 100 High Efficiency High Ambient


LWT
F
41
44
45
46
48

C.C. Ton
100.5
106.2
108.1
110.0
114.0

86
P.I. kW
91.1
93.8
94.7
95.6
97.5

EER
11.5
11.8
11.9
12.1
12.3

C.C. Ton
94.3
99.6
101.5
103.3
107.0

95
P.I. kW
98.4
101.1
102.1
103.0
104.9

Entering Condenser Air Temperature (C)


104
EER
C.C. Ton P.I. kW
EER
C.C. Ton
10.1
87.8
106.5
8.8
81.2
10.4
92.9
109.4
9.1
86.0
10.5
94.6
110.4
9.2
87.6
10.6
96.4
111.3
9.3
89.2
10.8
99.9
113.3
9.4
92.6

Table P67 - RTAD 115 High Efficiency High Ambient


LWT
F
41
44
45
46
48

C.C. Ton
119.2
126.1
128.4
130.8
135.6

86
P.I. kW
118.0
121.4
122.6
123.8
126.3

EER
10.9
11.2
11.3
11.4
11.6

C.C. Ton
112.0
118.6
120.8
123.0
127.5

95
P.I. kW
127.9
131.5
132.7
134.0
136.5

Entering Condenser Air Temperature (C)


104
EER
C.C. Ton P.I. kW
EER
C.C. Ton
9.5
104.6
139.0
8.2
97.0
9.8
110.8
142.7
8.5
102.8
9.9
112.9
144.0
8.6
104.8
10.0
115.0
145.3
8.7
106.7
10.2
119.2
147.9
8.9
110.7

Table P68 - RTAD 125 High Efficiency High Ambient


LWT
F
41
44
45
46
48

C.C. Ton
139.6
147.5
150.1
152.8
158.3

86
P.I. kW
144.1
148.4
149.8
151.3
154.3

EER
10.4
10.7
10.8
10.9
11.1

C.C. Ton
131.3
138.8
141.3
143.9
149.1

95
P.I. kW
156.3
160.7
162.2
163.7
166.8

Entering Condenser Air Temperature (C)


104
EER
C.C. Ton P.I. kW
EER
C.C. Ton
9.1
122.7
169.8
7.9
113.9
9.4
129.8
174.4
8.2
120.6
9.5
132.2
175.9
8.2
122.9
9.6
134.6
177.5
8.3
125.2
9.7
139.6
180.6
8.5
129.8

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.00010 ft F hr/Btu
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour). Power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 10.8F.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 104F ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

38

RLC-PRC015-E4

Performance Data
English Units
Table P69 - RTAD 145 High Efficiency High Ambient
LWT
F
41
44
45
46
48

C.C. Ton
149.2
157.8
160.7
163.6
169.5

86
P.I. kW
149.1
153.6
155.2
156.8
159.9

EER
10.7
11.0
11.1
11.2
11.4

C.C. Ton
140.8
148.9
151.7
154.4
160.0

95
P.I. kW
161.4
166.0
167.6
169.2
172.5

Entering Condenser Air Temperature (C)


104
EER
C.C. Ton P.I. kW
EER
C.C. Ton
9.4
132.1
175.1
8.2
123.1
9.7
139.7
179.8
8.5
130.3
9.8
142.3
181.5
8.6
132.8
9.9
145.0
183.1
8.6
135.2
10.1
150.3
186.4
8.8
140.2

113
P.I. kW
190.2
195.1
196.8
198.5
201.9

EER
7.1
7.3
7.4
7.5
7.7

C.C. Ton
115.9
118.9
119.2
119.5
119.8

120
P.I. kW
203.0
201.0
199.0
197.0
192.5

EER
6.3
6.5
6.6
6.7
6.8

113
P.I. kW
209.4
215.0
216.9
218.8
222.6

EER
6.9
7.1
7.2
7.3
7.4

C.C. Ton
124.5
127.9
128.3
128.8
129.5

120
P.I. kW
223.3
221.9
220.0
218.1
214.0

EER
6.2
6.4
6.4
6.5
6.7

113
P.I. kW
236.4
232.2
230.1
227.9
224.4

EER
6.5
6.7
6.8
6.9
7.0

C.C. Ton
115.3
116.0
116.6
117.1
117.2

120
P.I. kW
214.6
209.1
207.7
206.3
202.3

EER
6.0
6.1
6.2
6.3
6.4

113
P.I. kW
257.6
251.5
250.7
248.2
244.3

EER
6.4
6.6
6.7
6.8
6.9

C.C. Ton
124.0
125.4
126.1
126.8
127.2

120
P.I. kW
233.2
228.1
226.9
225.6
221.9

EER
5.9
6.1
6.1
6.2
6.3

Table P70 - RTAD 150 High Efficiency High Ambient


LWT
F
41
44
45
46
48

C.C. Ton
160.3
169.3
172.3
175.4
181.6

86
P.I. kW
164.9
170.1
171.9
173.6
177.3

EER
10.4
10.7
10.8
10.8
11.0

C.C. Ton
151.2
159.7
162.6
165.5
171.4

95
P.I. kW
178.1
183.5
185.3
187.1
190.8

Entering Condenser Air Temperature (C)


104
EER
C.C. Ton P.I. kW
EER
C.C. Ton
9.1
141.8
192.9
8.0
132.1
9.4
149.9
198.4
8.2
139.7
9.5
152.6
200.3
8.3
142.2
9.6
155.3
202.1
8.4
144.8
9.7
160.8
205.9
8.5
150.0

Table P71 - RTAD 165 Standard Efficiency High Ambient


LWT
F
41
44
45
46
48

C.C. Ton
171.8
181.4
184.5
187.7
194.2

86
P.I. kW
185.1
191.2
193.3
195.4
199.6

EER
10.1
10.4
10.5
10.5
10.7

C.C. Ton
162.2
171.2
174.2
177.2
183.3

95
P.I. kW
199.9
206.2
208.4
210.5
214.9

Entering Condenser Air Temperature (C)


104
EER
C.C. Ton P.I. kW
EER
C.C. Ton
8.9
152.2
216.4
7.8
138.1
9.1
160.6
222.9
8.0
140.3
9.2
163.4
225.1
8.1
140.6
9.3
166.3
227.4
8.1
141.0
9.4
172.0
231.9
8.3
142.3

Table P72 - RTAD 180 Standard Efficiency High Ambient


LWT
F
41
44
45
46
48

C.C. Ton
184.5
194.6
198.0
201.4
208.2

86
P.I. kW
202.2
209.0
211.3
213.7
218.4

EER
9.9
10.2
10.3
10.3
10.5

C.C. Ton
174.4
183.9
187.0
190.2
196.7

95
P.I. kW
218.3
225.3
227.7
230.1
235.0

Entering Condenser Air Temperature (C)


104
EER
C.C. Ton P.I. kW
EER
C.C. Ton
8.8
163.8
236.1
7.7
148.8
9.0
172.7
243.4
7.9
150.1
9.1
175.7
245.9
7.9
151.2
9.1
178.7
248.4
8.0
151.5
9.3
184.8
253.5
8.1
152.7

Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.00010 ft F hr/Btu
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. P.I. kW = compressor power input only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour). Power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 10.8F.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 104F ambient, the units will have the High-Ambient option
8. Shaded area reflects Adaptive ControlTM Microprocessor control algorithms.

RLC-PRC015-E4

39

Performance Data
SI Units
Table P73 - ARI Part-Load Values RTAD Standard Efficiency
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
275.0
75
206.2
085
50
137.5
25
68.7
100
330.2
75
247.6
100
50
165.1
25
82.5
100
393.4
75
295.1
115
50
196.7
25
98.4
100
449.3
75
337.0
125
50
224.7
25
112.3
100
517.2
75
387.9
145
50
258.6
25
129.3
100
553.1
75
414.8
150
50
276.5
25
138.3
100
606.2
75
454.6
165
50
303.1
25
151.5
100
651.2
75
488.4
180
50
325.6
25
162.8

P.I kW
100.9
67.5
32.4
17.4
120.0
83.7
39.2
21.2
149.6
96.1
46.3
24.0
187.5
121.0
55.7
28.9
192.6
130.6
62.9
30.6
212.4
140.4
68.0
36.8
233.1
156.0
77.4
39.0
254.7
179.2
83.9
47.2

COP (kW/kW)
2.72
3.05
4.24
3.95
2.75
2.96
4.22
3.90
2.63
3.07
4.25
4.10
2.40
2.78
4.03
3.89
2.69
2.97
4.11
4.22
2.60
2.96
4.07
3.76
2.60
2.91
3.92
3.89
2.56
2.72
3.88
3.45

IPLV (kW/kW)

P.I kW
96.9
65.5
31.5
16.8
115.3
82.4
38.5
22.1
145.4
97.8
47.6
25.7
178.2
122.6
57.9
32.2
184.9
129.7
63.6
32.0
204.1
139.8
68.5
38.4

COP (kW/kW)
3.07
3.41
4.73
4.43
3.1
3.2
4.6
4.0
2.88
3.21
4.40
4.08
2.75
3.00
4.23
3.80
2.84
3.04
4.13
4.10
2.76
3.02
4.11
3.66

IPLV (kW/kW)

3.60

3.53

3.63

3.36

3.53

3.47

3.41

3.24

Table P74 - ARI Part-Load Values RTAD High Efficiency


(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
297.8
75
223.4
085
50
148.9
25
74.5
100
352.0
75
264.0
100
50
176.0
25
88.0
100
418.8
75
314.1
115
50
209.4
25
104.7
100
489.8
75
367.3
125
50
244.9
25
122.4
100
524.9
75
393.7
145
50
262.5
25
131.2
100
562.9
75
422.2
150
50
281.5
25
140.7

40

4.02

3.81

3.76

3.55

3.57

3.51

RLC-PRC015-E4

Performance Data
SI Units
Table P75 - ARI Part-Load Values RTAD Standard Efficiency low noise
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
265.5
75
199.1
085
50
132.7
25
66.4
100
317.5
75
238.1
100
50
158.7
25
79.4
100
372.3
75
279.3
115
50
186.2
25
93.1
100
397.0
75
297.7
125
50
198.5
25
99.2
100
496.1
75
372.1
145
50
248.1
25
124.0
100
529.2
75
396.9
150
50
264.6
25
132.3
100
584.0
75
438.0
165
50
292.0
25
146.0
100
625.9
75
469.4
180
50
312.9
25
156.5

P.I kW
104.4
67.1
31.8
16.0
123.4
83.6
38.3
19.8
158.8
96.9
46.3
23.1
185.5
113.6
52.5
27.1
203.1
132.4
62.4
29.3
224.0
141.3
67.6
34.8
244.8
157.3
76.7
37.1
268.1
181.8
83.5
45.0

COP (kW/kW)
2.54
2.97
4.18
4.14
2.6
2.9
4.2
4.0
2.34
2.88
4.02
4.03
2.14
2.62
3.78
3.66
2.44
2.81
3.97
4.23
2.36
2.81
3.92
3.80
2.39
2.79
3.81
3.93
2.33
2.58
3.75
3.47

IPLV (kW/kW)

P.I kW
98.9
64.5
30.6
15.4
117.3
81.2
37.1
20.2
151.0
97.8
47.1
24.2
185.5
123.1
57.4
30.2
190.8
129.5
62.3
30.0
210.8
139.0
67.3
35.8

COP (kW/kW)
2.92
3.35
4.72
4.68
2.9
3.1
4.6
4.2
2.69
3.12
4.31
4.21
2.55
2.89
4.13
3.92
2.68
2.96
4.10
4.26
2.59
2.95
4.06
3.82

IPLV (kW/kW)

3.54

3.45

3.43

3.16

3.39

3.33

3.29

3.11

Table P76 - ARI Part-Load Values RTAD High Efficiency low noise
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
288.3
75
216.2
085
50
144.2
25
72.1
100
340.4
75
255.3
100
50
170.2
25
85.1
100
406.5
75
304.8
115
50
203.2
25
101.6
100
473.6
75
355.2
125
50
236.8
25
118.4
100
510.9
75
383.2
145
50
255.4
25
127.7
100
546.4
75
409.8
150
50
273.2
25
136.6

RLC-PRC015-E4

4.00

3.79

3.68

3.46

3.53

3.47

41

Performance Data
SI Units
Table P77 - ARI Part-Load Values RTAD Standard Efficiency Low Noise Night Noise Set Back
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
248.9
75
186.7
085
50
124.5
25
62.2
100
311.5
75
233.6
100
50
155.8
25
77.9
100
363.2
75
272.4
115
50
181.6
25
90.8
100
366.0
75
274.5
125
50
183.0
25
91.5
100
438.5
75
328.8
145
50
219.2
25
109.6
100
462.7
75
347.0
150
50
231.4
25
115.7
100
530.6
75
397.9
165
50
265.3
25
132.6
100
560.1
75
420.1
180
50
280.1
25
140.0

P.I kW
111.3
67.0
31.1
14.3
124.0
82.4
37.3
18.7
161.8
96.0
45.8
22.4
174.0
104.6
48.8
25.9
183.5
117.4
56.3
26.6
208.3
125.3
59.9
33.2
227.3
143.4
70.6
33.9
249.4
164.1
75.0
41.1

COP (kW/kW)
2.24
2.79
4.00
4.36
2.5
2.8
4.2
4.2
2.24
2.84
3.97
4.06
2.10
2.63
3.75
3.53
2.39
2.80
3.90
4.13
2.22
2.77
3.86
3.49
2.33
2.78
3.76
3.92
2.25
2.56
3.73
3.41

IPLV (kW/kW)

COP (kW/kW)
2.88
3.38
4.79
4.98
2.7
3.1
4.6
4.5
2.64
3.12
4.33
4.40
2.38
2.79
4.05
4.10
2.59
2.90
4.11
4.44
2.47
2.91
4.04
4.03

IPLV (kW/kW)

3.39

3.46

3.39

3.14

3.35

3.26

3.27

3.08

Table P78 - ARI Part-Load Values RTAD Standard Efficiency Low Noise Night Noise Set Back
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
284.4
75
213.3
085
50
142.2
25
71.1
100
325.9
75
244.4
100
50
163.0
25
81.5
100
401.2
75
300.9
115
50
200.6
25
100.3
100
456.7
75
342.5
125
50
228.4
25
114.2
100
501.0
75
375.8
145
50
250.5
25
125.3
100
532.0
75
399.0
150
50
266.0
25
133.0

42

P.I kW
98.9
63.1
29.7
14.3
120.0
79.8
35.6
18.0
152.0
96.4
46.3
22.8
192.3
122.8
56.4
27.9
193.5
129.4
61.0
28.2
215.7
137.1
65.8
33.0

4.07

3.76

3.71

3.39

3.51

3.46

RLC-PRC015-E4

Performance Data
SI Units
Table P79 - ARI Part-Load Values RTAD Standard Efficiency High External Static Pressure
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
264.4
75
198.3
085
50
132.2
25
66.1
100
312.9
75
234.7
100
50
156.5
25
78.2
100
366.7
75
275.0
115
50
183.4
25
91.7
100
377.3
75
283.0
125
50
188.6
25
94.3
100
492.9
75
369.7
145
50
246.5
25
123.2
100
527.8
75
395.8
150
50
263.9
25
131.9
100
578.7
75
434.0
165
50
289.4
25
144.7
100
622.0
75
466.5
180
50
311.0
25
155.5

P.I kW
113.1
75.8
36.1
20.8
133.9
92.7
42.5
24.6
170.1
105.8
50.4
27.9
187.7
116.8
54.4
31.4
217.4
144.8
69.2
35.6
238.6
155.6
74.5
42.6
252.8
167.7
82.5
44.0
275.5
192.9
89.2
53.1

COP (kW/kW)
2.34
2.62
3.66
3.18
2.34
2.53
3.68
3.19
2.16
2.60
3.64
3.28
2.01
2.42
3.47
3.00
2.27
2.55
3.56
3.46
2.21
2.54
3.54
3.10
2.29
2.59
3.51
3.29
2.26
2.42
3.49
2.93

IPLV (kW/kW)

COP (kW/kW)
2.63
2.91
4.08
3.54
2.63
2.74
3.94
3.19
2.45
2.75
3.80
3.30
2.36
2.57
3.66
3.10
2.45
2.62
3.58
3.35
2.39
2.61
3.59
3.01

IPLV (kW/kW)

3.07

3.03

3.06

2.87

3.03

2.98

3.02

2.87

Table P80 - ARI Part-Load Values RTAD Standard Efficiency High External Static Pressure
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
285.5
75
214.1
085
50
142.8
25
71.4
100
339.3
75
254.5
100
50
169.6
25
84.8
100
402.9
75
302.2
115
50
201.5
25
100.7
100
472.2
75
354.2
125
50
236.1
25
118.1
100
508.4
75
381.3
145
50
254.2
25
127.1
100
545.0
75
408.7
150
50
272.5
25
136.2

RLC-PRC015-E4

P.I kW
108.7
73.7
35.0
20.2
129.1
93.0
43.0
26.6
164.3
110.1
53.1
30.5
200.1
137.7
64.5
38.0
207.6
145.4
70.9
37.9
228.3
156.7
76.0
45.3

3.42

3.24

3.21

3.04

3.07

3.03

43

Performance Data
SI Units
Table P81 - ARI Part-Load Values RTAD High Efficiency High Ambient
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
297.8
75
223.4
085
50
148.9
25
74.5
100
352.0
75
264.0
100
50
176.0
25
88.0
100
418.8
75
314.1
115
50
209.4
25
104.7
100
489.8
75
367.3
125
50
244.9
25
122.4
100
524.9
75
393.7
145
50
262.5
25
131.2
100
562.9
75
422.2
150
50
281.5
25
140.7

P.I kW
96.9
65.5
31.5
16.8
115.3
82.4
38.5
22.1
145.4
97.8
47.6
25.7
178.2
122.6
57.9
32.2
184.9
129.7
63.6
32.0
204.1
139.8
68.5
38.4

COP (kW/kW)
3.07
3.41
4.73
4.43
3.1
3.2
4.6
4.0
2.88
3.21
4.40
4.08
2.75
3.00
4.23
3.80
2.84
3.04
4.13
4.10
2.76
3.02
4.11
3.66

IPLV (kW/kW)

P.I kW
225.0
151.1
75.0
38.0
245.8
173.5
81.3
46.0

COP (kW/kW)
2.68
2.99
4.02
3.97
2.63
2.80
3.98
3.52

IPLV (kW/kW)

4.02

3.81

3.76

3.55

3.57

3.51

Table P82 - ARI Part-Load Values RTAD High Efficiency High Ambient
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
kW cooling
100
603.0
75
452.2
165
50
301.5
25
150.7
100
647.7
75
485.7
180
50
323.8
25
161.9

44

3.49

3.32

RLC-PRC015-E4

Performance Data
English Units
Table P83 - ARI Part-Load Values RTAD High Efficiency High Ambient
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
tons
100
84.1
75
63.1
085
50
42.1
25
21.0
100
99.4
75
74.5
100
50
49.7
25
24.8
100
118.2
75
88.6
115
50
59.1
25
29.5
100
138.3
75
103.7
125
50
69.1
25
34.6
100
148.4
75
111.3
145
50
74.2
25
37.1
100
159.2
75
119.4
150
50
79.6
25
39.8

P.I kW
96.6
65.5
31.5
16.8
114.9
82.2
38.4
22.1
144.9
97.7
47.5
25.8
177.6
122.4
57.8
32.3
184.4
129.6
63.6
32.0
203.5
139.8
68.5
38.5

EER
10.4
11.6
16.0
15.0
10.4
10.9
15.5
13.5
9.8
10.9
14.9
13.8
9.3
10.2
14.4
12.9
9.7
10.3
14.0
13.9
9.4
10.3
13.9
12.4

IPLV

P.I kW
224.3
151.0
75.0
38.1
245.1
173.3
81.3
46.0

EER
9.1
10.2
13.6
13.4
9.0
9.5
13.5
11.9

IPLV

13.6

12.9

12.8

12.0

12.1

11.9

Table P84 - ARI Part-Load Values RTAD High Efficiency High Ambient
(along with ARI 550/590-1998. Info about ARI available on www.ari.org)
Unit
% Load
tons
100
170.5
75
127.9
165
50
85.3
25
42.6
100
183.2
75
137.4
180
50
91.6
25
45.8

RLC-PRC015-E4

11.9

11.3

45

Performance Data

kPa

Figure 4 - Evaporator Water Pressure Drops (SI units)

Water Flow l/s

46

RLC-PRC015-E4

Performance Data
Table P85 - Performance Data Adjustment Factors
Chilled
Water
Temp. drop
C
4.4
5.6
6.7
7.8
8.9
4.4
5.6
6.7
7.8
8.9

Fouling
Factor

0.0176
m K/kW

0.044
m K/kW

Altitude
Sea Level
Cooling
Capacity
1.000
1.000
1.001
1.003
1.004
0.988
0.988
0.990
0.991
0.993

600 m
Evp.
Flow
Rate
1.249
1.000
0.835
0.716
0.628
1.235
0.989
0.825
0.708
0.621

Compr.
kW
Input
1.000
1.000
1.001
1.001
1.001
0.996
0.998
0.998
0.998
0.999

Cooling
Capacity
0.996
0.997
0.997
0.999
1.000
0.984
0.986
0.987
0.988
0.990

1200 m
Evp.
Flow
Rate
1.245
0.996
0.832
0.714
0.626
1.230
0.985
0.822
0.706
0.619

Compr.
kW
Input
1.004
1.004
1.004
1.004
1.005
1.000
1.000
1.000
1.001
1.001

Cooling
Capacity
0.991
0.993
0.993
0.994
0.997
0.980
0.981
0.983
0.984
0.986

1800 m
Evp.
Flow
Rate
1.240
0.992
0.828
0.711
0.623
1.225
0.981
0.819
0.703
0.617

Compr.
kW
Input
1.007
1.007
1.009
1.009
1.009
1.004
1.004
1.005
1.005
1.006

Cooling
Capacity
0.987
0.988
0.988
0.990
0.991
0.975
0.977
0.978
0.980
0.981

Evp.
Flow
Rate
1.234
0.988
0.824
0.708
0.620
1.220
0.976
0.815
0.700
0.614

Compr.
kW
Input
1.014
1.015
1.015
1.015
1.016
1.010
1.011
1.011
1.011
1.012

Table P86 - Ethylene Glycol Pressure Drop Correction Factor


Brine
Temp C
-7
-4
-1
2
4

0
1.00
1.00
1.00
1.00
1.00

10
1.06
1.09
1.12
1.14
1.17

Percent Ethylene Glycol


20
30
1.13
1.24
1.16
1.26
1.19
1.28
1.21
1.30
1.23
1.32

40
1.38
1.39
1.41
1.42
1.44

50
1.54
1.55
1.56
1.57
1.58

Percent Propylene Glycol


20
30
1.23
1.30
1.25
1.31
1.27
1.33
1.29
1.34
1.31
1.36

40
1.39
1.39
1.40
1.40
1.41

50
1.53
1.52
1.52
1.52
1.52

Table P87 - Propylene Glycol Pressure Drop Correction Factor


Brine
Temp C
-7
-4
-1
2
4

0
1.00
1.00
1.00
1.00
1.00

Figure 5 - Ethylene Glycol Performance


Factors

10
1.14
1.17
1.20
1.23
1.26

Figure 6 - Propylene Glycol Performance


Factors

Figure 7 - Ethylene Glycol and Propylene


Glycol Freeze Point
Ethylene Glycol

CapacityAdjustment

Propylene Glycol

Compressor PowerAdjustment

Adjustment Factor

Adjustment Factor

GPMAdjustment

Temperature - Degrees F

GPMAdjustment

CapacityAdjustment
Compressor PowerAdjustment

% Antifreeze by Weight
% Ethylene Glycol by Weight

RLC-PRC015-E4

% Propylene Glycol by Weight

47

Controls
Chiller Unit Controls
Trouble-Free Installation, Start-Up
and Operation
Adaptive Control means the Unit
Control Module (UCM-CLD) directly
senses the control variables that
govern operation of the chiller:
motor current draw, evaporator
temperature, condenser
temperature, etc. When any of the
variables approaches a limit
condition where the unit may be
damaged or shut down on a safety,
the UCM takes corrective action to
avoid shutdown and keep the chiller
operating. It does this through
combined actions of compressor
slide valve modulation, electronic
expansion valve modulation and fan
staging.
Additionally, the UCM optimizes total
unit power consumption during
normal operating conditions. No
other chiller control system in the
marketplace duplicates this
performance.

Safety Controls
A centralized microcomputer offers a
higher level of machine protection.
Since the safety controls are smarter,
they limit compressor operation to
avoid compressor or evaporator
failures, thereby minimizing
nuisance shutdown. During
abnormal operating conditions, the
UCM will continue to optimize chiller
performance by taking the corrective
action necessary to avoid shutdown.
This keeps cooling capacity available
until the problem can be solved.
Whenever possible, the chiller is
allowed to perform its function;
make chilled water. In addition,
microcomputer controls allow for
more types of protection such as
over and under voltage! Overall, the
safety controls help keep the
building running and out of trouble.
The End Of Nuisance Trip-Outs And
Unnecessary Service Calls
Unnecessary service calls and

Figure 8 - Unit control module with Clear Language Display Keypad (UCM-CLD)

unhappy tenants are avoided. The


unit does not nuisance trip or
unnecessarily shut down. Only when
the UCM has exhausted the
corrective actions it can take and the
unit is still violating an operating
limit will the unit shut down.
CONTROLS ON OTHER CHILLERS
TYPICALLY SHUT DOWN THE
CHILLER, QUITE PROBABLY JUST
WHEN IT IS NEEDED THE MOST.
For example:
A typical five-year-old chiller with
dirty coils might trip-out on high
pressure cutout on a 38C day in
August. A hot day is just when
comfort cooling is needed the most.
In contrast, the air-cooled Series R
chiller with an Adaptive Control
microprocessor will stage fans on,
modulate electronic expansion valve,
and modulate slide valve as it
approaches a high pressure cutout.
Thereby KEEPING THE CHILLER ONLINE JUST WHEN YOU NEED IT THE
MOST.

Generic Building
Automation System
Controls
Simple Interface With Other Control
Systems
Microcomputer controls afford
simple interface with other control
systems, such as time clocks,
building automation systems and ice
storage systems. Wiring to the unit
can be as simple as two wires! This
means you can have the flexibility to
meet job requirements while not
having to learn a complicated control
system.
Monitoring And Diagnostics
Since the microcomputer provides
all control functions, it can easily
indicate such parameters as leaving
chilled water temperature and
capacity stage. If a failure does
occur, one of over 90 individual
diagnostic and operating codes will
be used to indicate the problem,
giving more specific information
about the failure. All of the
monitoring and diagnostic
information is displayed directly on a
microcomputer display.

48

RLC-PRC015-E4

Controls
Interface With The Trane Integrated
Comfort System (ICS)
When the air-cooled Series R chiller
is used in conjunction with a Trane
Tracer system, the unit can be
monitored and controlled from a
remote location. The air-cooled
Series R chiller can be controlled to
fit into the overall building
automation strategy by using time of
day scheduling, timed override, duty
cycling, demand limiting, and chiller
sequencing. A building owner can
completely monitor the air-cooled
Series R chiller from the Tracer
system, as all of the monitoring
information indicated on the
microcomputer can be read off the
Tracer system display. In addition, all
the powerful diagnostic information
can be read back at the Tracer
system. Best of all, this powerful
capability comes over a single
twisted pair of wires!
Air-cooled Series R chillers can
interface with many different
external control systems, from
simple stand- alone units to ice
making systems. Each unit requires a
single-source, three-phase power
supply, a 115-volt control power
transformer handles both the
evaporator heat tape and the unit
controls. The control transformer is
directly fed from the 400/3/50 supply
in the control panel. For basic standalone applications, the interface with
outside control is no different than
for other Trane chillers. However, the
RTAD units have many features that
can be used to interface with
building control systems.

Standard Features:
External Auto/Stop
A job site provided contact closure
will turn the unit on and off.
Note: Do not use the chilled water
pump to stop the chiller.
Chilled Water flow Interlock
A job site provided contact closure
from a chilled water pump contactor
or a flow switch is required and will
allow unit operation if a load exists.
This feature will allow the unit to run
in conjunction with the pump
system.
RLC-PRC015-E4

External Interlock
A job site supplied contact opening
wired to this input will turn the unit
off and require a manual reset of the
unit microcomputer. This closure is
typically triggered by a job site
supplied system such as a fire alarm.
Chilled Water Pump Control
Unit controls provide an output to
control chilled water pump(s). One
contact closure to the chiller is all
that is required to initiate the chilled
water system.
Remote Running and Alarm
Indication Contacts
The unit provides three singlepole/double-throw contact closures
to indicate that a failure has
occurred, if any compressors are
running, or if the compressors are
running at maximum capacity. These
contact closures may be used to
trigger job site supplied alarm lights
or alarm bells.

Optional Features:
Communication Interface (CSR
Communication Interface Option)
Capability for communication
withTrane Tracer Building
Automation Systems or Remote
Display
External Chilled Water Set point
Allows the external setting
independent of the front panel
setpoint by a 2-10 VDC input, or a
4-20 mA input.
External Current Limit Set point
Allows the external setting
independent of the front panel
setpoint by a 2-10 VDC input, or a
4-20 mA input.
Ice Making Control
Provides interface with ice making
control systems.
Chilled Water Temperature Reset
Reset can be based on return water
temperature or outdoor air
temperature.

Interface with other control


systems
Stand-Alone Unit
Interface to stand-alone units is very
simple; only a remote auto/stop for
scheduling is required for unit
operation. Signals from the chilled
water pump contactor auxiliary or a
flow switch are wired to the chilled
water flow interlock. Signals from a
time clock or some other remote
device are wired to the external
auto/stop input.
Note: Do not use the chilled water
pump to stop the chiller.
Required Features
External Auto/Stop (Standard)
Chilled Water flow Interlock
(Standard)
Additional Features That May Be
Used
Remote Running and Alarm
Indication Contacts (provided on the
UCM-CLD main module)
External Interlock (Standard)
Chilled Water Temperature Reset
External Trane Devices Required None
Note: All wiring outside the unit is
supplied at the job site.

TRANE Integrated
Comfort System Interface
A single twisted pair of wires tied
directly between the air-cooled
Series R chiller and a Tracer system
provides control, monitoring and
diagnostic capabilities. Control
functions include auto/stop,
adjustment of leaving water
temperature set point, compressor
operation lockout for kW demand
limiting and control of ice making
mode. The Tracer system reads
monitoring information such as
entering and leaving evaporator
water temperatures and outdoor air
temperature. Over 60 individual
diagnostic codes can be read by the
Tracer system. In addition, the Tracer
system can provide sequencing

49

Controls
control for two to six units on the
same chilled water loop. Pump
sequencing control can be provided
from the Tracer system. Tracer ICS is
not available in conjunction with the
remote display or the external set
point capability.
Required Features
Communications Interface (Requires
CSR Communications Interface,
option)
Additional Features That May Be
Used
Chilled Water Temperature Reset
Ice Making Control
External Trane Devices Required
Tracer Summit or Tracer Chiller
Plant Control

Interface With Other


Building Automation
Systems
The air-cooled Series R chillers can
interface with non-Trane building
automation systems via hard wire
connections. Several capabilities
may be utilized:
Required Features
External Auto/Stop (Standard)
Additional Features That May Be
Used
External Interlock (Standard)
External Demand Limit (Set point)
(Requires CSR Communications
Interface, option)
Remote Running and Alarm
Indication Contacts (Standard)
External Chilled Water Set point
(Requires CSR Communications
Interface, option)
Chilled Water flow Interlock
(Standard)

normal daytime cooling. In the ice


making mode, the air-cooled Series R
chiller will operate at full compressor
capacity until the return chilled fluid
temperature entering the evaporator
meets the ice making set point. This
ice making set point is manually
adjusted on the unit's
microcomputer. Two input signals
are required to the air-cooled
Series R chiller for the ice making
option. The first is an auto/stop
signal for scheduling and the second
is required to switch the unit in
between the ice making mode and
normal daytime operation. The
signals are provided by a remote job
site building automation device such
as a time clock or a manual switch. In
addition, the signals may be
provided over the twisted wire pair
from a Tracer system.
Required Features
External Auto/Stop (Standard)
Ice Making Control (Requires CSR
Communications Interface, option)
Additional Features That May Be
Used
Remote Running and Failure
Indication Contacts
Communications Interface (For Tracer
Systems)
Chilled Water Temperature Reset
(Indoor zone reset not available with
ice making option).
External Trane Devices Required None

External Trane Devices Required None

Ice Making Systems


An ice making option may be
ordered with the air-cooled Series R
chiller. The unit will have two
operating modes, ice making and
50

RLC-PRC015-E4

Controls
Remote Display

Figure 9 - Remote display panel

The remote display allows the


operator to monitor chiller operation
from a location within the building.
Over 60 essential chiller operating
parameters can be transmitted
between the unit control module on
the chiller and the remote display via
a bi-directional communications link.
Only one twisted wire pair is
required between the chiller and the
remote display. In addition to
monitoring chiller operation, alarms
and unit diagnostics can be read
from the remote display.
Furthermore, the chilled water
temperature set point can be
adjusted and the chiller can be
turned on or off from the remote
display.
Required Features
Communications Interface
Additional Features That May Be
Used
External Interlock (Standard)
Chilled Water Temperature Reset
Chilled Water flow Interlock
(Standard)
Remote Running and Failure
Indication Contacts
External Trane Devices Required
Remote Display Panel

RLC-PRC015-E4

51

Job Site Data


Table J-1 - Customer Wire Selection 400/3/50

Unit Size

Unit without
Disconnect
Switch

Unit with
Disconnect
Switch

Unit without
Disconnect
Switch

Unit with
Disconnect
Switch

Wire Selection Size


to Main Terminal Block

Wire Selection Size


to Disconnect Switch

Wire Selection Size


to Main Terminal Block

Wire Selection Size


to Disconnect Switch

Maximum
cable size
(mm)

Standard
085
2x300
100
2x300
115
2x300
125
2x300
145
2x300
150
2x300
165
2x300
180
2x300
High Efficiency
085
2x300
100
2x300
115
2x300
125
2x300
145
2x300
150
2x300
High Ambient
085
2x300
100
2x300
115
2x300
125
2x300
145
2x300
150
2x300
165
2x300
180
2x300
Standard Low Noise
085
2x300
100
2x300
115
2x300
125
2x300
145
2x300
150
2x300
165
2x300
180
2x300
High Efficiency Low Noise
085
2x300
100
2x300
115
2x300
125
2x300
145
2x300
150
2x300

52

Disconnect
Switch
Size (A)

Maximum
cable size
(mm)

250
400
400
500
500
630
630
630

150
240
240
240
240
2 x 300
2 x 300
2 x 300

250
400
400
500
500
630

150
240
240
240
240
2 x 300

400
400
400
500
630
630
630
800

240
240
240
240
2 x 300
2 x 300
2 x 300
2 x 300

250
400
400
500
500
630
630
630

150
240
240
240
240
2 x 300
2 x 300
2 x 300

250
400
400
500
500
630

150
240
240
240
240
2 x 300

Maximum
Disconnect
cable size
Switch
Unit Size
(mm)
Size (A)
Standard Low Noise with Night Noise Set Back
085
2x300
250
100
2x300
400
115
2x300
400
125
2x300
500
145
2x300
500
150
2x300
630
165
2x300
630
180
2x300
630
High Efficiency Low Noise with Night Noise Set Back
085
2x300
250
100
2x300
400
115
2x300
400
125
2x300
500
145
2x300
500
150
2x300
630
Standard with High External Static Pressure
085
2x300
250
100
2x300
400
115
2x300
400
125
2x300
500
145
2x300
500
150
2x300
630
165
2x300
630
180
2x300
630
High Efficiency with High External Static Pressure
085
2x300
250
100
2x300
400
115
2x300
400
125
2x300
500
145
2x300
500
150
2x300
630

Maximum
cable size
(mm)
150
240
240
240
240
2 x 300
2 x 300
2 x 300
150
240
240
240
240
2 x 300
150
240
240
240
240
2 x 300
2 x 300
2 x 300
150
240
240
240
240
2 x 300

RLC-PRC015-E4

Electrical Data
Table E-1 - Table E-1 - Unit Wiring 400/3/50
Unit
Nbr of Power
Maximum
size
Connections
Amps (1)
RTAD Standard
085
1
242
100
1
282
115
1
323
125
1
387
145
1
437
150
1
477
165
1
527
180
1
576
High Efficiency
85
1
242
100
1
291
115
1
332
125
1
405
145
1
446
150
1
486
High Ambient
85
1
242
100
1
291
115
1
332
125
1
405
145
1
446
150
1
486
165
1
527
180
1
576
Standard Low Noise
085
1
230
100
1
270
115
1
311
125
1
375
145
1
419
150
1
457
165
1
505
180
1
552
High Efficiency Low Noise
085
1
230
100
1
275
115
1
316
125
1
385
145
1
424
150
1
462
Standard Low Noise with Night Noise Set Back
085
1
226
100
1
270
115
1
312
125
1
376
145
1
417
150
1
453
165
1
503
180
1
548

RLC-PRC015-E4

Unit Wiring
Starting
Amps (2)

Power
Factor (5)

Compressor
Fuse Size (A)

Evaporator
heater (kW)

255
306
359
425
471
502
570
608

0.90
0.88
0.89
0.90
0.90
0.89
0.89
0.89

6 x 125
6 x 160
6 x 200
6 x 250
6 x 250
6 x 250
315 + 250
6 x 315

0.217
0.217
0.217
0.217
0.217
0.217
0.217
0.217

255
315
368
443
480
511

0.90
0.88
0.89
0.90
0.90
0.89

6 x 125
6 x 160
6 x 200
6 x 250
6 x 250
6 x 250

0.217
0.217
0.217
0.217
0.217
0.217

255
315
368
443
480
511
570
608

0.90
0.88
0.89
0.90
0.90
0.89
0.89
0.89

6 x 160
6 x 200
6 x 250
6 x 250
6 x 250
6 x 315
400 + 315
6 x 400

0.217
0.217
0.217
0.217
0.217
0.217
0.217
0.217

243
294
347
413
453
482
548
584

0.90
0.88
0.89
0.90
0.90
0.89
0.89
0.89

6 x 125
6 x 160
6 x 200
6 x 250
6 x 250
6 x 250
315 + 250
6 x 315

0.217
0.217
0.217
0.217
0.217
0.217
0.217
0.217

243
299
352
423
458
487

0.90
0.88
0.89
0.90
0.90
0.89

6 x 125
6 x 160
6 x 200
6 x 250
6 x 250
6 x 250

0.217
0.217
0.217
0.217
0.217
0.217

238
295
348
414
451
478
546
580

0.90
0.88
0.89
0.90
0.90
0.89
0.89
0.89

6 x 125
6 x 160
6 x 200
6 x 250
6 x 250
6 x 250
315 + 250
6 x 315

0.217
0.217
0.217
0.217
0.217
0.217
0.217
0.217

53

Electrical Data
Table E-1 - Table E-1 - Unit Wiring 400/3/50 Cont
Unit Wiring
Starting
Amps (2)

Unit
Nbr of Power
Maximum
size
Connections
Amps (1)
High Efficiency Low Noise with Night Noise Set Back
085
1
231
100
1
270
115
1
317
125
1
381
145
1
381
150
1
381
Standard with High External Static Pressure
085
1
231
100
1
278
115
1
319
125
1
383
145
1
427
150
1
463
165
1
516
180
1
561
High Efficiency with High External Static Pressure
085
1
239
100
1
278
115
1
327
125
1
391
145
1
435
150
1
471

Power
Factor (5)

Compressor
Fuse Size (A)

Evaporator
heater (kW)

244
295
353
419
456
483

0.90
0.88
0.89
0.90
0.90
0.89

6 x 125
6 x 160
6 x 200
6 x 250
6 x 250
6 x 250

0.217
0.217
0.217
0.217
0.217
0.217

244
302
355
421
461
488
559
593

0.90
0.88
0.89
0.90
0.90
0.89
0.89
0.89

6 x 125
6 x 160
6 x 200
6 x 250
6 x 250
6 x 250
315 + 250
6 x 315

0.217
0.217
0.217
0.217
0.217
0.217
0.217
0.217

251
302
363
429
469
496

0.90
0.88
0.89
0.90
0.90
0.89

6 x 125
6 x 160
6 x 200
6 x 250
6 x 250
6 x 250

0.217
0.217
0.217
0.217
0.217
0.217

Table E-2 Motor Data 400/3/50


Compressor (Each)
RLA Amps

Unit
Size
Qty
Ckt 1
Standard
085
2
80
100
2
95
115
2
111
125
2
135
145
2
162
150
2
162
165
2
196
180
2
196
High Efficiency
085
2
80
100
2
95
115
2
111
125
2
135
145
2
162
150
2
162
Standard Low Noise
085
2
80
100
2
95
115
2
111
125
2
135
145
2
162
150
2
162
165
2
196
180
2
196
High Efficiency Low Noise
085
2
80
100
2
95
115
2
111
125
2
135
145
2
162
150
2
162

54

Max Amps (3)

Fans (Each)
Starting Amps (4)

Control

Ckt 2

Ckt 1

Ckt 2

Ckt 1

Ckt 2

Qty

kW

FLA

Fans fuse
size (A)

VA

(400V)
A

80
95
111
135
135
162
162
196

106
125
146
178
214
214
259
259

106
125
146
178
178
214
214
259

144
180
217
259
291
291
354
354

144
180
217
259
259
291
291
354

6
6
6
6
9
10
11
12

2.05
2.05
2.05
2.05
2.05
2.05
2.05
2.05

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3 x 50
3 x 50
3 x 50
3 x 50
3 x 63
3 x 63
3 x 63
3 x 63

1600
1600
1600
1600
1600
1600
1600
1600

4
4
4
4
4
4
4
4

80
95
111
135
135
162

106
125
146
178
214
214

106
125
146
178
178
214

144
180
217
259
291
291

144
180
217
259
259
291

6
8
8
10
11
12

2.05
2.05
2.05
2.05
2.05
2.05

4.5
4.5
4.5
4.5
4.5
4.5

3 x 50
3 x 50
3 x 50
3 x 50
3 x 63
3 x 63

1600
1600
1600
1600
1600
1600

4
4
4
4
4
4

80
95
111
135
135
162
162
196

106
125
146
178
214
214
259
259

106
125
146
178
178
214
214
259

144
180
217
259
291
291
354
354

144
180
217
259
259
291
291
354

6
6
6
6
9
10
11
12

1.30
1.30
1.30
1.30
1.30
1.30
1.30
1.30

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

3 x 50
3 x 50
3 x 50
3 x 50
3 x 63
3 x 63
3 x 63
3 x 63

1600
1600
1600
1600
1600
1600
1600
1600

4
4
4
4
4
4
4
4

80
95
111
135
135
162

106
125
146
178
214
214

106
125
146
178
178
214

144
180
217
259
291
291

144
180
217
259
259
291

6
8
8
10
11
12

1.30
1.30
1.30
1.30
1.30
1.30

2.5
2.5
2.5
2.5
2.5
2.5

3 x 50
3 x 50
3 x 50
3 x 50
3 x 63
3 x 63

1600
1600
1600
1600
1600
1600

4
4
4
4
4
4

RLC-PRC015-E4

Electrical Data
Table E-2 Motor Data 400/3/50 cont
Compressor (Each)
RLA Amps

Max Amps (3)

Unit
Size
Qty
Ckt 1
Ckt 2
Ckt 1
Standard Low Noise with Night Noise Set Back
085
2
80
80
106
100
2
95
95
125
115
2
111
111
146
125
2
135
135
178
145
2
162
135
214
150
2
162
162
214
165
2
196
162
259
180
2
196
196
259
High Efficiency Low Noise with Night Noise Set Back
085
2
80
80
106
100
2
95
95
125
115
2
111
111
146
125
2
135
135
178
145
2
162
135
214
150
2
162
162
214
Standardwith High External Static Pressure
085
2
80
80
106
100
2
95
95
125
115
2
111
111
146
125
2
135
135
178
145
2
162
135
214
150
2
162
162
214
165
2
196
162
259
180
2
196
196
259
High Efficiencywith High External Static Pressure
085
2
80
80
106
100
2
95
95
125
115
2
111
111
146
125
2
135
135
178
145
2
162
135
214
150
2
162
162
214

Fans (Each)
Starting Amps (4)

Control

Ckt 2

Ckt 1

Ckt 2

Qty

kW

FLA

Fans fuse
size (A)

VA

(400V)
A

106
125
146
178
178
214
214
259

144
180
217
259
291
291
354
354

144
180
217
259
259
291
291
354

4
6
6
6
8
8
10
10

1.05
1.05
1.05
1.05
1.05
1.05
1.05
1.05

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

3 x 50
3 x 50
3 x 50
3 x 50
3 x 63
3 x 63
3 x 63
3 x 63

1600
1600
1600
1600
1600
1600
1600
1600

4
4
4
4
4
4
4
4

106
125
146
178
178
214

144
180
217
259
291
291

144
180
217
259
259
291

6
6
8
8
10
10

1.05
1.05
1.05
1.05
1.05
1.05

2.6
2.6
2.6
2.6
2.6
2.6

3 x 50
3 x 50
3 x 50
3 x 50
3 x 63
3 x 63

1600
1600
1600
1600
1600
1600

4
4
4
4
4
4

106
125
146
178
178
214
214
259

144
180
217
259
291
291
354
354

144
180
217
259
259
291
291
354

4
6
6
6
8
8
10
10

2.21
2.21
2.21
2.21
2.21
2.21
2.21
2.21

3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

3 x 50
3 x 50
3 x 50
3 x 50
3 x 63
3 x 63
3 x 63
3 x 63

1600
1600
1600
1600
1600
1600
1600
1600

4
4
4
4
4
4
4
4

106
125
146
178
178
214

144
180
217
259
291
291

144
180
217
259
259
291

6
6
8
8
10
10

2.21
2.21
2.21
2.21
2.21
2.21

3.9
3.9
3.9
3.9
3.9
3.9

3 x 50
3 x 50
3 x 50
3 x 50
3 x 63
3 x 63

1600
1600
1600
1600
1600
1600

4
4
4
4
4
4

Notes:
1. Maximum Compressors FLA + all fans FLA + control Amps
2. Starting Amps of the circuit with the largest compressor circuit including fans plus RLA of the second circuit including fans + control Amps
3. Maximum FLA per compressor.
4. Compressors starting Amps, Star delta start.
5. Compressor Power Factor

RLC-PRC015-E4

55

Dimensional Data

RTAD

Digit 19
X-L-P
STD
Q

85
X-L-P
HE
Q
X-L-P
STD
Q
100
X-L-P
HE
Q
X-L-P
STD
Q
115
X-L-P
HE
Q
X-L-P
STD
Q
125
X-L-P
HE
Q
X-L-P
STD
Q
145
X-L-P
HE
Q
X-L-P
STD
Q
150
X-L-P
HE
Q
X-L-P
STD
Q
165/185
X-L-P
HE
Q

Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu
Al
Cu

12
2760
3090
2670
3000
3340
3780
3340
3780
3205
3485
3205
3485
3470
3910
3380
3820
3655
4095
3655
4095
4005
4555
4005
4555
3670
4110
3670
4110
4100
4555
4015
4565
4260
4670
4360
4770
5390
5900
5490
6000
4520
4930
4620
5030
5445
5955
5545
6055
5440
5950
5540
6050
5525
6035
5625
6235

1+2
5" DN 125 - PN 16

6" DN 150 - PN 16

6" DN 150 - PN 16

6" DN 150 - PN 16

6" DN 150 - PN 16

1 = Evaporator water inlet connection


2 = Evaporator water outlet connection
3 = Starter panel
4 = Control panel
5 = Power supply inlet (155 x 400)
6 = Rigging eyes 45
9 = Minimum clearance for maintenance
10 = Minimum clearance for evaporator tubes removal
11 = Minimum clearance (air entering)
12 = Operating weight (kg)
14 = Power disconnect switch (option)
15 = Isolators (option)
16 = Compressor sound attenuator (option)
17 = Pressure gauges (option)

56

RLC-PRC015-E4

Dimensional Data

RTAD
85 STD
100-115-125 STD
85-100 HE
115-125 HE
145-150 STD
145-150 HE
165-180 STD

Note: for High Efficiency Low noise and High ambient units, use dimensions of the High efficiency units.

RLC-PRC015-E4

57

Mechanical Specifications
General
Units are leak and pressure tested at
35 bar high side, 19 bar low side,
then evacuated and charged.
Packaged units ship with a full
operating charge of oil and
refrigerant.
Unit panels, structural elements and
control boxes are constructed of
galvanized steel and mounted on a
welded structural steel base. Unit
panels and control boxes are
finished with an air-dry paint
RAL 1019.
Evaporator
The evaporator is a tube-in-shell heat
exchanger design with internally
finned copper tubes roller expanded
into the tube sheet. The evaporator is
designed, tested and stamped in
accordance with the appropriate
pressure vessel code approval for a
refrigerant side working pressure of
32 bar. The evaporator is designed
for a water side working pressure of
14 bar. Water connections are
flanged. The evaporator has one
water pass with a series of internal
baffles. Each shell includes a vent, a
drain and fittings for temperature
control sensors and is insulated with
3 /4 -inch Armaflex II or equal
insulation (K=0.26). Heat tape is
provided to protect the evaporator
from freezing at ambient
temperatures down to -18C.
Condenser and Fans
Air-cooled condenser coils have
aluminum fins mechanically bonded
to internally finned seamless copper
tubing. The condenser coil has an
integral subcooling circuit.
Condensers are factory proof and
leak tested at 35 bar. Direct-drive
vertical discharge air foil ZephyrWing
condenser fans are dynamically
balanced. Three-phase condenser
fans motors with permanently
lubricated ball bearing are provided.
Standard units will start and operate
between of 4C (39 F) to the
maximum possible ambient of the
selected unit.

58

Compressor and Lube Oil System


The rotary screw compressor is
semi-hermetic, direct drive, 3000
rpm, with capacity control slide
valve, a load/unload valve, rolling
element bearings, differential
refrigerant pressure oil pump, oil
filter and oil heater. The motor is a
suction gas cooled, hermetically
sealed, two-pole squirrel cage
induction motor. Oil separator
devices are provided separate from
the compressor. Check valves in the
compressor discharge and lube oil
system are provided.
Refrigeration Circuits
Each unit has two refrigerant circuits,
with one rotary screw compressor
per circuit. Each refrigerant circuit
includes a liquid line shutoff valve,
removable core filter drier, charging
port and an electronic expansion
valve. Fully modulating compressors
and electronic expansion valves
provide variable capacity modulation
over the entire operating range.
Unit Controls
All unit controls are housed in a
weather-tight enclosure with hinged
doors to allow for customer
connection of power wiring and
remote interlocks.
All controls, including sensors, are
factory mounted and tested prior to
shipment. All cataloged units comply
to EN 60204 and are EMC
compatible.
Microcomputer controls provide all
control functions including start-up
and shut down, leaving chilled water
temperature control, compressor
and electronic expansion valve
modulation, fan sequencing, antirecycle logic, automatic lead/lag
compressor starting and load
limiting.
The unit control module, utilizing
Adaptive Control microprocessor,
automatically takes action to avoid
unit shutdown due to abnormal
operating conditions associated with
low refrigerant temperature, high
condensing temperature and motor
current overload. Should the
abnormal operating condition
continue until a protective limit is

violated, the unit will be shut down.


Unit protective functions include loss
of chilled water flow, evaporator
freezing, loss of refrigerant, low
refrigerant pressure, high refrigerant
pressure, reverse rotation,
compressor starting and running
over current, phase loss, phase
imbalance, phase reversal, and loss
of oil flow.
A menu driven digital display
indicates over 20 operating data
points including chilled water set
point, current limit Set point, leaving
chilled water temperature,
evaporator and condenser
refrigerant pressures and
temperatures. Over 60 diagnostic
checks are made and displayed when
a problem is detected. The digital
display can be read and advanced on
the unit without opening any control
panel doors.
Standard power connections include
main three phase power and two 115
volt single phase power connections
for control power and heat tape.
Starters
Starters are housed in a weathertight
enclosure with removable cover
plate to allow for customer
connection of power wiring.
Wye Delta closed transition starters
are standard on all RTAD units.

RLC-PRC015-E4

Notes

RLC-PRC015-E4

59

The manufacturer has a policy of continuous


product improvement, and reserves the right
to alter any details of the products at any time
without notice.
This publication is a general guide to install,
use and properly maintain our products. The
information given may be different from the
specification for a particular country or for a
specific order. In this event, please refer to
your nearest office.
For additional information, contact:
Distributor/Installer stamp

Trane
A business of American Standard Companies
www.trane.com
For more information contact your local
district office or e-mail us at comfort@trane.com

Literature Order Number

RLC-PRC015-E4

Date

0903

Supersedes

RLC-PRC015-E4_0801

Stocking Location

Europe

Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice. Only qualified technicians should perform the
installation and servicing of equipment referred to in this publication.