Академический Документы
Профессиональный Документы
Культура Документы
User Manual
Document no. 1471
Issue 01
Published 15 February 2002
ISSUE HISTORY
Issue
Date
15/02/2002
Version
Details
GCU2
User Manual
This document is copyright by Ziton, and all rights are reserved. It may not be photocopied,
translated, or reduced to a machine readable form, in whole or in part, without the prior written consent
of Ziton Ltd. It may not be distributed with changes or omissions, which have not been authorized by
Ziton Ltd.
Although Ziton has reviewed and checked this documentation, and believes it to be accurate, Ziton
gives no warranty or representation, either expressed or implied, with respect to accuracy,
completeness, or errors.
For further information, please contact Customer Support at one of the following Ziton Centres.
Ziton Ltd
8 Newmarket Court
Chippenham Drive, Kingston
Milton Keynes MK10 0AQ
United Kingdom
Telephone:
Fax:
Email:
Telephone:
Fax:
Email:
GCU2
User Manual
Table of Contents
Introduction & System Overview
1.1
1.1.1
1.1.2
1.1.2.1
1.1.2.2
1.1.2.3
1.1.2.4
1.1.2.5
1.1.2.6
1.1.2.7
1.1.2.8
1.1.3
1.1.3.1
1.1.3.2
1.1.3.3
1.1.3.4
1.1.3.5
1.1.3.6
1.1.3.7
1.1.4
1.1.5
1.2
1.2.1
1.2.2
1.2.3
1.2.4
1.2.5
Introduction ..........................................................................................................1
Ziton ZP Gas Control Products.............................................................................1
Installation Criteria ...............................................................................................1
System Power Supplies .......................................................................................1
Operating Environment ........................................................................................1
Power Transients .................................................................................................2
Physical Mounting ................................................................................................2
Wiring...................................................................................................................2
Screw Terminals ..................................................................................................2
Static Sensitive Components................................................................................2
System Documentation ........................................................................................2
Limitations............................................................................................................3
Sensing Equipment Limitations ............................................................................3
Power Faults ........................................................................................................3
Bells and Sirens Faults.........................................................................................3
Equipment Compatibility.......................................................................................3
Gas System Design .............................................................................................3
Response Time ....................................................................................................3
Maintenance Faults..............................................................................................3
Engineering..........................................................................................................4
Manual structure ..................................................................................................4
System overview ..................................................................................................5
Control of gaseous fire extinguishing systems......................................................5
Gas control panel .................................................................................................6
Gas Status Unit ....................................................................................................7
Gas Repeater Units..............................................................................................8
Gas Door Monitor Board ......................................................................................8
Operation
2.1
2.1.1
2.1.2
2.1.3
2.1.3.1
2.1.3.2
2.1.3.3
2.1.4
2.1.4.1
2.1.4.2
2.1.5
2.1.5.1
2.1.5.2
2.1.5.3
2.1.5.4
2.1.5.5
2.2.
2.2.1
2.2.2
2.3
2.3.1
2.3.2
2.4
2.4.1
2.4.2
2.4.3
2.5
Installation
3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.1.6
3.2
3.3
3.3.1
Commissioning
4.1
4.2
4.3
4.4
4.4.1
4.4.2
4.4.3
4.4.4
4.4.5
4.4.6
4.4.7
4.4.8
Scope...................................................................................................................1
Commissioning pre-requisites ..............................................................................2
Addressing ...........................................................................................................3
Checks.................................................................................................................5
Check Gas Control Unit........................................................................................5
Check bells/sounders ...........................................................................................5
Check detonator wiring.........................................................................................6
Check Pressure Switches (Optional fitting)...........................................................6
Check Remote Functions .....................................................................................6
Check Door Lock Monitor (Optional fitting) ...........................................................6
Check Gas Release Breakglass Units..................................................................6
Check ZP Fire Panel ............................................................................................6
4.5
4.6
4.6.1
4.6.2
4.6.3
4.6.4
4.7
4.7.1
4.8
4.9
Maintenance
5.1
5.1.1
5.1.2
5.2
5.3
5.4
5.5
5.5.1
5.5.2
5.5.2.1
5.5.2.2
5.5.2.3
5.5.3
5.6
5.7
5.7.1
5.7.2
5.7.3
5.7.4
5.8
5.8.1
5.8.1.1
5.8.1.2
5.8.1.3
5.8.1.4
5.8.1.5
5.8.1.6
5.8.2
5.9
5.10
Typical Application
6.1
6.2
6.3
6.4
6.5
6.6
6.6.1
6.7
Scope...................................................................................................................1
A Single Gas Area................................................................................................3
Multiple Gas Areas with Individual Gas Supplies..................................................5
Multiple Gas Areas with Common Gas Supply .....................................................7
Single Gas Area with Door Monitor Unit ...............................................................9
Single Gas Area with Multiple Doors and Gas Status Units................................11
Rewiring of Status for reverse Auto/Manual Control ...........................................13
Remote Monitoring using a Gas Repeater Unit ..................................................15
Appendix A
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
PS1464.1
PS1465.1
PS1466.1
PS1467.1
PS1468.1
PS1469.1
PS1470.1
501-126900-0-02
501-127000-0-01
501-127100-0-01
501-138700-0-01
501-138800-0-01
GCU2
UD1471.1
Issue 1
15/02/2002
GCU2
Introduction and System Overview
1.1 Introduction
1.1.1 Ziton ZP Gas Control Products.
A list of part numbers for the Ziton products relating to the construction of a Gas Control
System follows. This list includes all standard as well as optional products.
NB: It is important to note that the Ziton ZP Gas Control System works as a integral part of
the Ziton ZP Fire Control System. It is also understood that the engineer in charge of the
design and installation of the Gas Control System is fully conversant with the operation and
functioning the Ziton ZP Fire Control Systems.
Part No.
Reference No.
Description
Usage
80001
ZP5-GCU2
standard
80002
ZP5-GCU2
standard
80101
ZP5-GCU2S
optional
80201
ZP5-GCU2R
optional
07700
ZP5-GMD1
optional
GCU2
UD1471.1 Iss 1 (15/02/2002)
Page 1 - 1
GCU2
Introduction and System Overview
1.1.2.5 Wiring
It is imperative that wiring falls within the limitations given in the wiring guide, in respect of
line resistance, line capacitance and crosstalk from interfering signals.
Page 1 - 2
GCU2
UD1471.1 Iss 1 (15/02/2002)
GCU2
Introduction and System Overview
1.1.3 Limitations
Certain limitations must be borne in mind when protecting life or property.
GCU2
UD1471.1 Iss 1 (15/02/2002)
Page 1 - 3
GCU2
Introduction and System Overview
1.1.4 Engineering
This manual is written assuming the reader is fully familiar with the Ziton ZP Fire Control
System and the following standards.
NFPA 12
NFPA 12A
NFPA 12B
BS7273
PART1
BS5839
PART 1
Great care must be taken to ensure the correct engineering of the system. The instructions
stipulated in Parts 2 - 6 of this manual must be thoroughly understood and carefully followed.
Inappropriate application can give rise to system failure.
Part 2
Operation
Part 3
Installation
Part 4
Commissioning
Part 5
Maintenance
Part 6
Typical
Applications
Page 1 - 4
GCU2
UD1471.1 Iss 1 (15/02/2002)
GCU2
Introduction and System Overview
GCU2
UD1471.1 Iss 1 (15/02/2002)
Page 1 - 5
GCU2
Introduction and System Overview
Page 1 - 6
GCU2
UD1471.1 Iss 1 (15/02/2002)
GCU2
Introduction and System Overview
GCU2
UD1471.1 Iss 1 (15/02/2002)
Page 1 - 7
GCU2
Introduction and System Overview
Page 1 - 8
GCU2
UD1471.1 Iss 1 (15/02/2002)
GCU2
Operation
UD1471.2
Issue 1
15/02/2002
GCU2
Operation
Fire LEDs
Fault LEDs
Lock-off/Reset LEDs
Power-on LED
Lock-off/Reset keyswitch
Automatic Mode LEDs
Automatic/Manual keyswitch
Manual Mode LEDs
Silence pushbutton
Hold off gas release button
Hold off gas release indicator
Gas Discharge LEDs
Gas discharge pending indicator
Break-glass Unit Protective Flap
Break-glass Pane
GCU2
UD1471.2 Iss 1 (15/02/2002)
Page 2 - 1
GCU2
Operation
b.
c.
d.
b.
Close doors and openings leading into the gas protected area to minimise gas
leakage if required.
c.
Lift the flap on the breakglass unit and break the glass panel. Leave the area of the
Gas Control Unit if inside the protected area.
a.
b.
Any plant/ventilation etc connected to the Gas Control Unit will shut down, and
doors and openings will automatically close.
c.
The gas will be discharged. This discharge might be instantaneous or occur after a
time delay depending on set-up.
d.
The two red "Gas Discharge" LEDs will illuminate on the Gas Control Unit.
e.
This event will be displayed on the ZP Fire Detection Panel in the format "GAS
DROP!" with the zone number and line address of the Gas Control Unit.
f.
If a printer is connected to the ZP Fire Detection Panel then the message "GAS
RELEASE" will be printed with details of the Gas Control Unit line address, zone
number, event number and date and time.
Page 2 - 2
GCU2
UD1471.2 Iss 1 (15/02/2002)
GCU2
Operation
b.
Investigate the gas protected area and check that the source of smoke or heat has
been adequately extinguished.
c.
Disable the Gas Control Unit by turning the "LOCK-OFF/RESET" key switch
clockwise so that the two red LEDs illuminate.
d.
e.
Press the Accept followed by the Reset key on the ZP Fire Detection Panel and the
panel should return to normal.
f.
Notify the maintenance staff or company to have the broken glass pane on the
breakglass unit replaced, the gas cylinders refilled and detonator replaced.
g.
Turn the "LOCK-OFF/RESET" key switch anti-clockwise and the Gas Control Unit
will return to normal.
The two red "Fire" LEDs on the Gas Control Unit illuminate.
b.
c.
The panel buzzer on the ZP Fire Detection Panel will sound, the zone and common
Fire LEDs will flash, and a message will be displayed in the format "FIRE" with the
zone and device number.
d.
e.
GCU2
UD1471.2 Iss 1 (15/02/2002)
Page 2 - 3
GCU2
Operation
Press the "Silence" pushbutton on the Gas Control Unit to silence the fire alarm
sounders connected to it.
b.
Press the "ACCEPT" key on the ZP Fire Detection Panel to silence that panel
buzzer. The zone and common fire LEDs will revert to a steady illumination and
fire alarm sounders connected to the ZP Fire Detection Panel will silence.
c.
Investigate the alarm and remove the source of smoke or heat from the detector
which initiated the alarm.
d.
If the fire is extensive, manual gas discharge can be initiated as in section 2.1.3.1 .
Once the source of smoke or heat has been removed, and any damage rectified,
press the "Reset" key on the ZP Fire Detection Panel. The panels will return to
normal if the initiating source has been adequately handled.
b.
Briefly turn the "LOCK-OFF/RESET" key switch on the Gas Control Unit clockwise
and then anti-clockwise to reset the unit.
c.
b.
Any plant/ventilation etc connected to the Gas Control Unit will be shut down.
c.
d.
e.
Attempt to prevent gas leakage by closing doors and openings leading to the gas
protected area.
Page 2 - 4
GCU2
UD1471.2 Iss 1 (15/02/2002)
GCU2
Operation
When the preset time delay has lapsed the gas will be discharged.
b.
The two red "Gas Discharge" LEDs will illuminate on the Gas Control Unit when
gas has been discharged.
c.
This event will be displayed on the ZP Fire Detection Panel in the format "GAS
DROP!" With the zone number and line address of the Gas Control Unit.
d.
If a printer is connected to the ZP Fire Detection Panel then the message "GAS
RELEASE" will be printed with details of Gas Control Unit line address, zone
number, event number and date and time.
b.
Investigate the gas protected area and check that the source of smoke or heat has
been adequately extinguished.
c.
Once the source of smoke or heat has been removed, press the "ACCEPT"
followed by the "RESET" key and the ZP Fire Detection Panel and the panel
should return to normal if the initiating source has been adequately handled.
d.
Reset the Gas Control Unit by turning the "LOCK-OFF/RESET keyswitch clockwise
once and then anti-clockwise to the vertical position.
e.
f.
g.
Notify the maintenance staff or company to have the gas cylinder re-filled and the
detonator replaced if necessary.
b.
If a printer is connected to the ZP Fire Detection Panel then the message "GC
MANUAL" will be printed as well as the gas unit address, the zone number, the
event number and the date and time.
To select "Automatic" operating mode, turn the "Automatic/Manual" key switch to the vertical
position and the following will occur:
a.
b.
If a printer is connected to the ZP Fire Detection Panel, then the message "GC
AUTO" will be printed as well as the gas unit address, the zone number, the event
number and the date and time.
GCU2
UD1471.2 Iss 1 (15/02/2002)
Page 2 - 5
GCU2
Operation
b.
If a printer is connected to the ZP Fire Detection Panel then the message "GC
DISABLE" will be printed as well as the gas unit address, the zone number, the
event number and the date and time. Remember to enable the Gas Control Unit
once maintenance has been carried out by turning the "Lock-Off/Reset" keyswitch
anti-clockwise to the vertical position so that the two red "Lock-Off/Reset" LEDs
extinguish and the ZP Fire Detection Panel printer prints "GC MANUAL" or "GC
AUTO" depending on the selected mode.
The two yellow "fault" LEDs on the Gas Control Unit will illuminate.
b.
The panel buzzer on the ZP Fire Detection Panel will sound, the common fault LED
will illuminate and a message will be displayed in the format "GC GENFLT" with the
zone number and line address. Note that fault messages "GC OPMODE" and "GC
LOCKOUT" refer to the optional Door Lock Monitor Unit if fitted.
c.
d.
Press the "ACCEPT" key on the ZP Fire Detection Panel to silence the panel
buzzer.
e.
Notify the maintenance staff or company to have the fault investigated and
rectified.
f.
After clearance of the fault, press the "ACCEPT" then the "RESET" key on the ZP
Fire Detection Panel and the panels should return to normal.
Page 2 - 6
GCU2
UD1471.2 Iss 1 (15/02/2002)
GCU2
Operation
a
b
link
setting
L2
ON
L5
OFF
L2
OFF
L5
ON
link function
no delay on callpoint trigger
preset delay on callpoint trigger as set by VR1 on display board
Automatic release must be used with the timer reset link placed on L3 on the main board.
When the hold off button is pressed the delay time as set by VR1 on the main board will be
reset to the full delay time.
GCU2
UD1471.2 Iss 1 (15/02/2002)
Page 2 - 7
GCU2
Operation
KEY
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Fire LEDs
Fault LEDs
Lock-off/Reset LEDs
Power-on LED
Lock-off/Reset keyswitch
Automatic Mode LEDs
Automatic/Manual keyswitch
Manual Mode LEDs
Silence pushbutton
Hold off gas release button
Hold off gas release indicator
Gas Discharge LEDs
Gas discharge pending indicator
Break-glass Unit Protective Flap
Break-glass Pane
Page 2 - 8
GCU2
UD1471.2 Iss 1 (15/02/2002)
GCU2
Operation
2.2.2 Operation
The operation of the Gas System from the Gas Status Unit is exactly the same as the
operation from the Gas Control Unit. This is described in the sections listed below:
It should be noted that if either the Gas Control Unit or the Status Gas Unit is set to Auto by
means of the keyswitch control, the system will be on Automatic as indicated by the front
panel LEDs. Similarly, if either the Gas Control Unit or the Gas Status Unit is set to Lockedoff by means of the keyswitch control, then the system will be locked off as indicated by the
front panel LEDs.
GCU2
UD1471.2 Iss 1 (15/02/2002)
Page 2 - 9
GCU2
Operation
Fire LEDs
Fault LEDs
Lock-off/Reset LEDs
Power-on LED
Automatic Mode LEDs
Manual Mode LEDs
Hold off gas release indicator
Gas Discharge LEDs
Gas discharge pending indicator
Page 2 - 10
GCU2
UD1471.2 Iss 1 (15/02/2002)
GCU2
Operation
2.3.2 Operation
No control of the Gas system is possible from a Gas Repeater Unit. As operation takes place
at the Gas Control Unit or Gas Status Unit, as described in Sections 2.1.2 to 2.1.5, a mimic
of the LED indications is given at the Repeater Unit.
GCU2
UD1471.2 Iss 1 (15/02/2002)
Page 2 - 11
GCU2
Operation
Page 2 - 12
GCU2
UD1471.2 Iss 1 (15/02/2002)
GCU2
Operation
That, apart from "Power on" and "Auto/Manual" LEDs, no other Gas Control Unit
front fascia LEDs are illuminated.
b.
That the Control Panel has not given indication that any fault exists on the Gas
Control Unit.
c.
If a door lock monitor is fitted, check that the buzzer sounds if the unit is switched
to manual whilst the door is locked, or if the unit is switched to automatic when the
door is unlocked.
d.
GCU2
UD1471.2 Iss 1 (15/02/2002)
Page 2 - 13
GCU2
Installation
UD1471.3
Issue 1
15/02/2002
GCU2
Installation
GCU2
UD1471.3 Iss 1 (15/02/2002)
Page 3 - 1
GCU2
Installation
Page 3 - 2
GCU2
UD1471.3 Iss 1 (15/02/2002)
GCU2
Installation
24vDC power
The external 24V DC power connections are now on the add-on board. It will be noticed that
the old power connection terminals on the main board are now pre-wired. This wiring must
not be removed.
ZP Loop wiring
The ZP loop connections are now on the add-on board. Additional terminals have been
provided for the respective loop screens. It will be noticed that the old ZP Loop terminals on
the main board are now pre-wired. This wiring must not be removed.
Note that screens must be properly connected at the fire panel.
Earth connection
The add-on board includes a separate earth terminal which did not exist on the original Gas
Control Unit.
The Gas Control Unit must be connected to a secure earth. If this was not previously done a
new connection will be necessary. Good wiring practice should be followed and the earth
connection should be kept as short as possible.
When mounting the Main Control Board, ensure that the earth wiring lug included in the
wiring loom is correctly fastened. Refer to Main Control Board mounting diagram for
mounting instructions.
NB:
GCU2
UD1471.3 Iss 1 (15/02/2002)
Page 3 - 3
GCU2
Installation
Mounting Instructions
The Gas Control Unit main board is now supplied with two screws and two spring washers
for mounting into the Gas Control Unit box. To ensure the effectiveness of the surge
suppression board, the earth lug from the wiring loom must be earthed as shown below.
To mount the Gas Unit Main Board, align the main board chassis mounting slots with the
lower studs of the Gas Unit box. Insert the main board into the Gas Unit box so that the
main board chassis rests on the studs. Insert the mounting screws, spring washers and
the free earth lug of the wiring loom as shown below. Tighten screws.
Do not disassemble the circuit boards from the chassis.
Page 3 - 4
GCU2
UD1471.3 Iss 1 (15/02/2002)
GCU2
Installation
GCU2
UD1471.3 Iss 1 (15/02/2002)
Page 3 - 5
GCU2
Installation
Page 3 - 6
GCU2
UD1471.3 Iss 1 (15/02/2002)
GCU2
Installation
Diagram 3 :
OUTPUT
MODE
ZONE 1
ZONE 2
Diagram 3 :
OUTPUT
MODE
1001
2001
DIAGRAM 3
INPUT
OUTPUT
MODE
1001
1002
1003
2001
2002
2003
One would follow the same format and apply the same rules for any protected area.
GCU2
UD1471.3 Iss 1 (15/02/2002)
Page 3 - 7
GCU2
Installation
Page 3 - 8
GCU2
UD1471.3 Iss 1 (15/02/2002)
GCU2
Installation
GCU2
UD1471.3 Iss 1 (15/02/2002)
Page 3 - 9
GCU2
Installation
Page 3 - 10
GCU2
UD1471.3 Iss 1 (15/02/2002)
GCU2
Installation
GCU2
UD1471.3 Iss 1 (15/02/2002)
Page 3 - 11
GCU2
Installation
The Gas Status Units and Gas Repeater Units are mounted the same way.
Page 3 - 12
GCU2
UD1471.3 Iss 1 (15/02/2002)
GCU2
Installation
GCU2
UD1471.3 Iss 1 (15/02/2002)
Page 3 - 13
GCU2
Installation
Page 3 - 14
GCU2
UD1471.3 Iss 1 (15/02/2002)
GCU2
Commissioning
UD1471.4
Issue 1
15/02/2002
GCU2
Commissioning
4.1 Scope
This section covers the programming of ZP5 Mk2 and ZP3 Fire Panels using the ZP5-GCU2
Gas Control Unit.
For programming the Gas Control Unit of ZP5 Mk1 Fire Panels refer to the applicable
Commissioning Manual.
Commissioning a Gas Control Unit requires the performing of a number of logical steps.
These must be done in the sequence given to successfully complete the task.
IMPORTANT: Once the gas control unit is connected, the wiring must not be
meggered: to do so will cause irreparable damage to the circuit.
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 1
GCU2
Commissioning
Page 4 - 2
GCU2
UD1471.4 Iss 1 (15/02/2002)
GCU2
Commissioning
4.3 Addressing
The Gas Control Unit uses two addresses on the address line. These are selectable via the
two sets of address settings switches on the main board of the Gas Control Unit illustrated
below in figure 3.1. Any two addresses may be used but it is recommended that the two
addresses are spaced at least twenty address numbers apart as security against short-term
random noise interference.
The gas relay address is identified by the ZP5 and ZP3 Control Panel as a gas unit. The
coincidence connection relay address is identified by the ZP5 Control Panel as a line relay.
The switches are used to set the ZP device address. The switches are numbered 1 to 7, and
may be coded to represent all addresses from 1 to 127. Switch positions and codes are
shown in figure 3.2
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 3
GCU2
Commissioning
A switch represents a particular number only when it is in the ON position. In the OFF
position, it represents 0.
To arrive at the address number of a device, ADD the representative numbers of all the
switches which are in the ON position.
An example is given in figure 3.3
Page 4 - 4
GCU2
UD1471.4 Iss 1 (15/02/2002)
GCU2
Commissioning
4.4 Checks
4.4.1 Check Gas Control Unit
a.
Ensure that all field wiring is tested and correct and is connected, except the
detonator and power.
b.
Check that the display PCB is connected via ribbon cable connector.
c.
d.
e.
f.
L3 on the main board must be in for the more time function to operate on the
double knock automatic detonation.
Check that the Fire Alarm sounders (if connected to the Gas Control Unit) are fitted
with polarizing diodes.
b.
Check that the last Fire Alarm sounder in the circuit (if connected to the Gas
Control Unit) is fitted with a 2200 ohm end of line resistor.
NOTE:
If the Fire Alarm sounder is not connected to the Gas Control Unit (ie it is
connected to the ZP Fire Panel) then connect a 2200 ohm resistor across terminals
TB1.4 & TB1.5 on the Gas Control Unit.
c.
Check that the Gas Discharge sounders are fitted with polarizing diodes.
d.
Check that the last Gas Discharge sounder in the circuit is fitted with a 2200 ohm
end of line resistor.
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 5
GCU2
Commissioning
b.
Check that a 2200 ohm end of line resistor is fitted at the point of detonator
connection.
c.
For the purpose of commissioning, connect a 24V dc lamp or use the multi-meter
to monitor the voltage across the end of line resistor at the point of detonator
connection.
If the gas cylinder pressure and gas discharge (via pressure switch) are being
monitored, then connect a 3900 ohm end of line resistor in series with the low
cylinder pressure monitor at the cylinder. (see Installation Part 3 for wiring details).
b.
If gas discharge and gas pressure are not being monitored (with link L1 not
removed), then fit a 3900 ohm resistor across terminals TB1.15 and TB1.16.
Check that they are connected according to the respective wiring schematic
2)
Check that the end of line links are inserted on the last Status / Repeater unit
and are removed from the GCU2 and other Status/Repeater units in the
chain.
If a Door Lock Monitor board is fitted check that it is wired according to the Door
Lock Monitor wiring schematic. (see datasheet PS1467.1) .
Check that glass panes on the Gas Release Breakglass Units are intact.
Page 4 - 6
GCU2
UD1471.4 Iss 1 (15/02/2002)
GCU2
Commissioning
Step 2:
Apply power to the ZP Fire Panel to which the Gas Control Unit is connected.
Step 3:
After a short period the panel will then revert to normal running mode and display date and
time. If any faults are displayed, remove power, rectify the fault and repeat steps 2 and 3.
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 7
GCU2
Commissioning
The prefix for the Gas Relay address is determined by the line number connected to
ADD A (+) & (-) terminals of the surge suppression board. The prefix for the
coincidence connection relay address is determined by the line number connected to
ADD B (+) & (-) terminals of the surge suppression board
Two address lines used with the gas control unit activated from one zone on each
line.
Two address lines used with the gas control unit activated by groups of individual
sensors on each line.
One address line used with the gas control unit activated by groups of individual
sensors on the same line.
One address lines used with the gas control unit activated by zones defined for
sensors on the same line.
It should be noted that the double knock facility is mechanically provided by relays
connected to the two addresses used by the Gas Control Unit: all software programming to
these addresses used by the Gas Control Unit is for single knock activation.
Page 4 - 8
GCU2
UD1471.4 Iss 1 (15/02/2002)
GCU2
Commissioning
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 9
GCU2
Commissioning
Page 4 - 10
GCU2
UD1471.4 Iss 1 (15/02/2002)
GCU2
Commissioning
(Refer to Section 3)
Step 2: Use the I/O mapping routine to map
devices 1001,1002 & 1004 to operate the Gas Relay (1005)
devices 2021,2022 & 2025 to operate the Coincidence connection
Relay (2026)
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 11
GCU2
Commissioning
Programme both the GCU2 Gas Relay (1005) and the GCU2 Coincidence connection Relay
(2026) to single-knock/non-silencing operation Mode.
(Refer to ZP5 Mk2 and ZP3 Commissioning Manual.
Step 3: Verify the programming by triggering a sensor in each line and checking that the
Gas Control Unit functions correctly.
WARNING:
Page 4 - 12
GCU2
UD1471.4 Iss 1 (15/02/2002)
GCU2
Commissioning
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 13
GCU2
Commissioning
Programme both the GCU2 Gas Relay (1025) and the GCU2 coincidence connection relay
(1046) to single-knock/non-silencing operation Mode.
(Refer to ZP5 Mk2 and ZP3 Commissioning Manuals).
Step 3: Verify the programming by triggering two sensors, and one mapped to each output,
and checking that the Gas Control Unit functions correctly.
WARNING
Page 4 - 14
GCU2
UD1471.4 Iss 1 (15/02/2002)
GCU2
Commissioning
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 15
GCU2
Commissioning
Page 4 - 16
GCU2
UD1471.4 Iss 1 (15/02/2002)
GCU2
Commissioning
4.7 Tests
Verify Programming
a.
Verify that the zones are correctly programmed by taking a printout with the use of
menu report facilities on the ZP5 Mk2 and ZP3 Panel.
b.
Verify that the relay mapping and operating parameters are correct by taking a
printout using the menu maintenance report facility on the ZP5 Panel.
c.
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 17
GCU2
Commissioning
Page 4 - 18
GCU2
UD1471.4 Iss 1 (15/02/2002)
GCU2
Commissioning
4.9 Specification
Model
Activation Method
Communication
Capacity
Primary Supply
ZP5-GCU2
Software Link
ZP Polling System
One Extinguishing Area
Operating Voltage
Current - Quiescent
Current - Fault
Controls
Auto/Manual Control
Lock-off/Reset
Fire Sounder Silence
Gas Sounder Silence
Manual Gas Release
Gas Discharged
System in Auto
System in Manual
System Locked
Fire
Fault
Power ON
Function
Indications
Monitoring
22-29Vdc
80mA
100mA (Excl ext. devices)
150mA (excl ext. devices)
Status
Field Wiring
Compatible with ZP5-GCU2S Gas Control Status Unit and ZP5-GCU2R Gas Control
Repeater Units (maximum number of 10 units can be connected)
Outputs
Gas discharge
5A 24Vdc intermitt.
1.5A 24Vdc continuous
0.5A 24Vdc
0.5A 24Vdc
1 SPDT
Changes state at discharge
Max switch power 30W 50VA
Max switch current 1.5A
Max switch power 100Vdc/90Vac
GCU2 Door Lock Monitor Board
Ash Grey
300W x 230H x 100D mm
Surface Mounting
ZP5-GDM
Colour
Size
Mounting Method
IMPORTANT NOTE:
The above current ratings are dependant upon the capacity of the power supply unit.
GCU2
UD1471.4 Iss 1 (15/02/2002)
Page 4- 19
GCU2
Maintenance
UD1471.5
Issue 1
15/02/2002
GCU2
Maintenance
daily checks
weekly checks
quarterly services
The quarterly services (see paragraph 5.5.2) are designed to pre-empt any problems that
may arise and to check that the system is functioning to its installation specifications. The
services should be arranged through a maintenance contract with a servicing company.
The agreement should specify how the service company is to be contacted and how access
to the premises is to be arranged. Repair services should be available within 24 hours. For
premises in continuous use, an engineer should be on call at all times. The servicing
company should have engineers trained in servicing Ziton equipment. The owner of the fire
alarm system is responsible for ensuring that the company contracted is competent to carry
out the work.
The daily checks require no technical knowledge and should be carried out by the panel
operator. Weekly checks can also be carried out by the panel operator.
Weekly checks (see paragraph 5.5.1) can also be carried out by the panel operator.
Quarterly checks should be carried out by trained maintenance personnel. Such personnel
may be direct employees of the company, or may be contracted from the maintenance
company responsible for servicing.
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 1
GCU2
Maintenance
Make sure some small hand tools are available for testing, connecting,
disconnection, etc.
2.
3.
Make sure that the drawings on hand do indicate correct device positions, device
addresses and types with all relevant wiring runs.
4.
It is very important that there is a record available of how the fire system has been
configured. The system specification should describe in detail all aspects of the
gas system such as:
The model of the control panel to which the gas unit is connected.
Physical layout of lines and devices. The type and the address applicable to each
gas control unit should be recorded.
The organisation of devices into logical zones as effects the gas system.
Cause and effect rules programmed into the panel (input/output mappings), which
effect the gas control unit.
This document is the blueprint for how the system should be configured and how it should
behave. The system specification is essential for when the system is extensively tested and
checked during servicing. Without such a specification there is no final arbitration as to what
is the correct behaviour of the system.
It is important to keep the specification valid. Whenever changes are made to the system the
specification should be updated to reflect those changes.
Page 5 - 2
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
A description of each event along with the name of the responsible person on duty
at the time of the event.
Dates and times of all discharges, whatever the cause. The cause of the discharge
should be noted etc.
Dates and times of all alarms, whatever the cause. The cause of the alarm should
be noted. If the cause is not known then this should be stated. The devices
activated and their location should be recorded. Any actions taken should also be
recorded.
Dates, times and types of all defects and faults and the corrective actions taken.
Dates, times and types of all servicing undertaken, whether routine or for corrective
purposes.
Dates and times of all periods of device, zone or system isolation, for whatever
purpose.
Dates of all changes and upgrades to the system along with the names of those
that carried them out. Note that the system specification should also be updated.
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 3
GCU2
Maintenance
Another crucial building block needed for smooth and effective maintenance is a system for
notifying all those affected about the testing of fire alarm systems, and for leaving the system
in its normal operating state afterward.
Occupants of the building and anyone receiving remote alarm signals, such as the fire
department should be informed, in good time, of when the test is to begin and when it is
over. No alarms should be sounded before notification has taken place.
It is essential that all disconnected systems be reconnected at the end of testing.
Page 5 - 4
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
On a weekly basis check any reports sent from the Gas Control Unit to the main
Fire Control Panel. Under normal conditions no abnormal reports should be
detected.
2.
Check the front panel of the Gas Control Unit, and any attached optional
Status/Repeater Units. Apart from the POWER and AUTO/MANUAL LEDs no
other LEDs should be illuminated.
3.
4.
Check that the printer on the main Fire Control Panel indicates the change in
switch position.
5.
6.
Extreme caution must be taken when wiring or unwiring to the Gas Control Unit
when it is live.
1.
Turn the Lock off key to "LOCKOFF". Check that the locked-off LEDs have
illuminated.
2.
Replace the transit pin at the Gas Cylinder and remove the detonator connections
from terminal block TB3 terminals 7 & 8 marked release out on the GCU2 display
board.
3.
Connect a 18 ohm 5 watt resistor across terminals 7 and 8 of terminal block TB3.
Reset the control panel and check that no fault is indicated.
4.
Turn the Lockoff/Reset key to "RESET". Check that the Lock-off LEDs extinguish.
5.
Switch the Auto/Manual key switch and check that the indicating LEDs indicate
appropriately. Leave the switch in AUTO.
6.
7.
8.
Activate one of the inputs mapped to activate the Gas Control Unit (use an Ziton ZSDT2 if requiring to activate a smoke sensor).
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 5
GCU2
Maintenance
9.
Check that the monitored Fire Bell output on terminal block TB1 terminal 4 and 5 is
activated (if measuring with a meter, terminal 1 is +24 Volt with respect to terminal
2)
10.
Check that the red Fire LEDs on the front fascia of the Gas Control Unit illuminate.
11.
Wait for at least 45 seconds and check that no 24 Volt output is detected across
the detonator terminals 7 and 8.
12.
Silence the Fire Bell output by means of the "Silence" pushbutton on the front
fascia of the Gas Control Unit. Check that the bell output responds accordingly.
13.
Activate the second input mapped to activate the Gas Control Unit (use an Ziton ZSDT2 if requiring to activate a smoke sensor).
14.
15.
After waiting 45 seconds check that a 24 Volt output is detected across detonator
terminals 7 and 8.
16.
Also check that the "Gas Discharged" LED on the front fascia of the Gas Control
Unit is illuminated.
17.
Also check that the "Gas Discharged Siren" output on terminal block TB1 terminals
6 and 7 is activated. (Measure 24V at terminal 6 with respect to 7).
18.
Check that the Main Fire Control Panel reports the "Gas Discharge" condition.
19.
Turn the "Lockoff" keyswitch on the front fascia and check that the "Locked off"
LEDs illuminate. Check that the Gas Discharged Siren silences.
20.
Reset the unit by turning the Lockoff/Reset to RESET check that the Lockoff LEDs
go off.
21.
22.
After waiting 10 seconds press the hold off more time button.
23.
Confirm that the delay time after releasing the hold off button is the delay time as
configured. The hold off button will thus reset the delay time to the full delay time.
24.
After cleaning the triggered devices, reset the panel and reset the gas control unit
with the locked off key.
Page 5 - 6
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
Remove link L1 from the Gas Display board of the Status Unit most remote from
the Gas Control Unit. Check that the "FAULT" LEDs illuminate on both the Gas
Status Units and the Gas Control Unit. Check that the Fire Control Panel indicates
a fault.
2.
Replace the link L1 on the Gas Display Board of the Gas Status Unit most remote
from the Gas Control Unit. Check that the "FAULT" LEDs extinguish on both the
Gas Status Units and the Gas Control Unit. Accept and Reset the fault on the Fire
Control Panel. (Repeat the same test removing links L2 and L3).
3.
Activate one of the inputs mapped to activate the Gas Control Unit (use a Ziton ZSDT2 if requiring to activate a smoke sensor).
4.
Check that the red Fire LEDs on the front fascia of the Gas Status Units illumine.
5.
Silence the Fire Bell output on the Gas Control Unit by means of the "Silence"
pushbutton on the front fascia of the Gas Status Unit. Check that the bell output
responds accordingly.
6.
Activate the second input mapped to activate the Gas Control Unit (use a Ziton ZSDT2 if requiring to activate a smoke sensor).
7.
After the delay time check that the "Gas Discharged" LED on the front fascia of the
Gas Status Unit is illuminated, while monitoring the time taken for this operation.
8.
Turn the "Lockoff" keyswitch on the front fascia of the Status Unit and check that
the "Locked off" LEDs on the Gas Control, Status and Repeater Units illuminate.
Check that the Gas Discharged Siren connected to the Gas Control Unit silences.
9.
10.
Reset the unit by turning the Lockoff/Reset key on the Status Unit to RESET.
Check that the Lockoff LEDs go off on the Gas Control, Status and Repeater Units.
11.
Test the hold off operation by completing tests 1 to 6 above. At point 7 after waiting
10s press the more time button. Measure the time between the activation of the
Gas Discharged LEDs and releasing the hold off button. The measured period,
which is the configured delay setup by VR1 (on the main board), should be the
same as the time noted in point 7. Confirm that this is the correct delay time
required.
12.
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 7
GCU2
Maintenance
2.
The Gas Control unit buzzer should sound and after approximately 30 seconds the
ZP3/ZP5 Control Panel will report a fault.
3.
Close the Door Lock Monitoring Switch by locking the door. The buzzer should
silence automatically. Reset the ZP3/ZP5 Contol Panel.
4.
Page 5 - 8
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 9
GCU2
Maintenance
Before starting any fault finding procedures, ensure that the system as a whole is
calibrated correctly. Check the high reference analogue (reading 1) from several
devices covering the length of the line. The reference value should be between 205
and 218.
If there appears to be a problem then disconnect the line and connect a single
sensor to the panel. Check that the reading is within the above parameters.
Caution:
Never use a megger, or any other high voltage instrument, on detection or alarm
lines while there are any devices connected to them. This will cause irreversible
damage to the devices.
Never replace a panel PCB, or any other components while the power is
connected. This could damage them irreversibly.
Never replace a fuse with another that has a amperage rating higher than that
which is specified.
Whenever replacing line devices make sure that the address settings on the
replacement units match those of the units they are replacing.
The fault list describes faults that can be raised by the control panel. The following
information is given for each fault.
Fault name
Fault description
Panel indications
Corrective action
Page 5 - 10
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
Panels are configured to sound a fault buzzer when a fault is raised. The buzzer sounds
approximately every three seconds. A yellow fault LED will also illuminates. After the fault
has been acknowledged by accepting it the buzzer will only sound every 15 seconds. After
correcting the fault the panel can be reset and the panel will return to normal, extinguishing
the fault LED.
Open circuit, short circuit, or missing end of line (EOL) resistors on field wiring.
b)
c)
d)
e)
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 11
GCU2
Maintenance
Corrective action
1.
2.
If this fault has been raised for a number of devices on the same line then there
may be interference on the line. If this does not apply then proceed to the next
point.
3.
Note the GCU2 in need of attention and then show the analogues for the two
addresses applicable to that device on the display by using the maintenance menu
report analogue facility.
4.
Check that slot 5 analog reading is not less than 59 counts or more than 188
counts. Above or below would indicate an open circuit or shorts on the field wiring
respectively.
5.
The gas relay reading should also have an analogue reading in slot 6 of between
39 and 198.
6.
7.
Remove power from the panel and then re-apply it. This will initialise the panel and
the devices. The previously unaccepted device should be accepted.
The display will scroll between two events, one showing the addressable relay
device that has not switched, the other showing the event that has triggered it
(usually a fire event). For example:
FIRE
Event 001
Event 002
The zone in which the relay fault has occurred is indicated by the appropriate red
Zone LED.
Page 5 - 12
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
Possible causes
a)
b)
Corrective action
1.
2.
If the yellow Isolated LED is on, check whether the relay is isolated. If so then
investigate the reasons for this. De-isolate the relay if it is safe to do so.
3.
If no other reason can be found for the fault, replace the faulty GCU2 main board.
4.
TYPE FAULT
Zone 001
Dev 001
Event 001
Probable cause
a)
Device addresses have been swopped within the system after device acceptance.
b)
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 13
GCU2
Maintenance
Corrective action
1.
2. Check the system specification to see which type of device should be at the address in
question. Replace the incorrect device with one of the correct type.
3.
Dev 001
Event 001
Possible causes
a)
b)
Corrective action
1.
2.
Note the device in need of attention and then show the analogues for that device
on the display. Check the first analogue reading. If analogue reading 1 is almost at
zero then the panel cannot communicate with the device.
3.
If the device is missing then install a replacement. If the device is present then
remove it and check the line for pulsing voltage on the device terminals. If there is
no line voltage present then fix the fault in the field wiring or replace the
appropriate line isolator.
4.
Page 5 - 14
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
GC GNFLT
Carbon
Zone 001
dioxide
gas
Dev 5002
storage
Event 012
room
The zone in which the fault has occurred is indicated by the appropriate red Zone
LED.
Possible Causes
a)
There is a fault on the gas control system it will fall into one of the following
categories.
i)
ii)
iii)
iv)
v)
Corrective Action:
1.
2.
Consult the write ups with regard to the faults in the sections below.
3.
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 15
GCU2
Maintenance
A fault message will be displayed on the ZP3/ZP5 Control Panel and the buzzer in
it will sound. The Fault LED on the Control Panel will also illuminate.
Probable Cause:
a)
The Link L1 or L3 on the Gas Control/Status Units display PCB respectively has
not been correctly setup or the monitored circuit has gone open circuit.
Corrective Action:
1.
2.
3.
Insure that Link L1 is removed from the Gas Control Unit and L3 is removed from
the Gas Status Units.
4.
Insert the Link L3 in its appropriate position on the last Gas Status Unit only. This
will cause the EOL resistor to be engaged.
5.
If their are no Gas Status Units on line then L1 must be inserted on the Gas
Control Units display PCB.
6.
7.
Page 5 - 16
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
The Gas Detonator Fault LED on the Gas Control Unit is illuminated.
A fault message will be displayed on the ZP3/ZP5 Control Panel and the buzzer in
it will sound. The Fault LED on the Control Panel will also illuminate.
Probable Cause:
a)
The EOL resistor across the detonator switch has not be inserted or the circuit is
an open circuit.
b)
Corrective Action:
1.
2.
Check the condition of the EOL resistor. If it is missing insert one between
terminals 7 & 8 of TB3 on the GCU2 display board.
3.
Check on the condition of the fuse F1. If it is missing or blown replace it.
4.
5.
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 17
GCU2
Maintenance
The Gas Pressure Low LED on the Gas Control Unit is illuminated.
A fault message will be displayed on the ZP3/ZP5 Control Panel and the buzzer in
it will sound. The Fault LED on the Control Panel will also illuminate.
GC GNFLT Zone 001 Dev 5001 Event 002
Probable Cause:
a)
The EOL resistor across the Gas Pressure Low switch has not be inserted.
b)
Corrective Action:
1.
2.
Check the condition of the EOL resistor. If it is missing insert one between
terminals 15 & 16 of TB1 and the GCU2 main board.
3.
4.
If the condition remains have a proper check done on the pressure in the gas
cylinder.
A fault message will be displayed on the ZP3/ZP5 Control Panel and the buzzer in
it will sound. The Fault LED on the Control Panel will also illuminate.
Page 5 - 18
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
Probable Cause:
a)
The EOL resistor across the Fire Bell has not be inserted or the monitored circuit
wiring is open or short circuited.
Corrective Action:
1.
2.
Check the condition of the EOL resistor. If it is missing insert one between
terminals TB4 & TB5 on the GCU2 main board.
3.
4.
The Gas Bell Fault LED on the Gas Control Unit is illuminated.
A fault message will be displayed on the ZP3/ZP5 Control Panel and the buzzer in
it will sound. The Fault LED on the Control Panel will also illuminate.
Probable Cause:
a)
The EOL resistor across the Gas Discharge Siren has not be inserted.
b)
Corrective Action:
1.
2.
Check the condition of the EOL resistor. If it is missing insert one between
terminals TB6 & TB7 on the GCU2 main board.
3.
4.
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 19
GCU2
Maintenance
A fault message will be displayed on the ZP3/ZP5 Control Panel and the buzzer in
it will sound. The Fault LED on the Control Panel will also illuminate.
Probable Cause:
a)
The Link L1 on the main PCB of the Gas Control Unit is still inserted and there is
no Gas Pressure Verification Switch connected.
b)
The Link L1 on the main PCB of the Gas Control Unit is not inserted and there is a
Gas Pressure Verification Switch connected.
Corrective Action:
1.
2.
Remove the Link L1 from the PCB of the Gas Control Unit (Cause a ) or
alternatively insert the Link L1 (Cause b ).
3.
A fault message will be displayed on the ZP3/ZP5 Control Panel and the buzzer in
it will sound. The Fault LED on the Control Panel will also illuminate.
The display will indicate a fault as GC PWRFLT GC PWRFLT Zone 001 Dev 5001
Event 002
Probable Cause:
a)
b)
Corrective Action:
1.
2.
Check whether the Green Power LED is indicating on the Gas Control Unit. If not it
would indicate a complete loss of 24 Volt power supply. Rectify.
3.
If the Green Power LED is illuminated then check for local power loss on the PCB.
Rectify or replace the board.
4.
Page 5 - 20
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Maintenance
The indicating LEDs which should display on the Gas Status Unit or Gas Repeater
Unit are not illuminating.
Operation of Controls on the Status Unit does not evoke appropriate response on
the Gas Control Unit.
Probable Cause:
1.
The wiring connections to the Status or Repeater Unit are open circuit or incorrect.
2.
The ribbon cable connected from Status Unit Main Control Board to Display board
has come loose.
Corrective Action:
1.
Check terminal wiring and ribbon cable connection. Once corrected, the unit will
respond appropriately.
GCU2
UD1471.5 Iss 1 (15/02/2002)
Page 5 - 21
GCU2
Maintenance
The Door Monitor buzzer sounds when it should not sound or does not sound
when it should sound.
Probable Cause:
1.
2.
Corrective Action:
1.
Read the description of the function in the manual thoroughly and check that the
operation is well understood.
2.
3.
If the fault does not correct, replace the door monitor board.
Page 5 - 22
GCU2
UD1471.5 Iss 1 (15/02/2002)
GCU2
Typical Applications
UD1471.6
Issue 1
15/02/2002
GCU2
Typical Applications
6.1 Scope
Part 6 of the ZP5 Gas Control System manual gives an illustrated guide of some of the
typical applications to which the Gas Control System can be configured.
Figure 1 on the following page gives a pictorial representation of a typical gas system. Other
applications are shown in block diagram format.
GCU2
UD1471.6 Iss 1 (15/02/2002)
Page 6 - 1
GCU2
Typical Applications
Page 6 - 2
GCU2
UD1471.6 Iss 1 (15/02/2002)
GCU2
Typical Applications
Two zones or sensors in the gas area being simultaneously activated into alarm
which will cause the coincidence condition necessary to initiate a gas drop.
2.
The glass pane on the Break Glass callpoint built into the Gas Control Unit is broken.
In this instance a coincidence condition is not necessary as the callpoint is
connected directly to the gas control circuitry.
Note:
The above events are applicable if the gas unit is set to automatic operation. For
manual operation only the callpoint break glass releases the gas.
Figure 2 illustrates typical single gas area protection, using a single gas cylinder.
GCU2
UD1471.6 Iss 1 (15/02/2002)
Page 6 - 3
GCU2
Typical Applications
Page 6 - 4
GCU2
UD1471.6 Iss 1 (15/02/2002)
GCU2
Typical Applications
Both detectors in the any gas area are triggered causing the necessary
coincidence condition which will cause a gas drop in that area.
2.
If the Break Glass pane built into the Gas Control Unit is triggered in any of the
Gas Areas a gas drop will occur in that specific Gas Area. A coincidence condition
is not necessary here as the Break Glass unit is built directly into the Gas Control
Circuitry.
Note:
The above events are applicable to automatic operation. For manual operation only
the callpoint break glass releases the gas.
The system is illustrated in Figure 3. The system can be extended to include more gas areas
by extending the wiring illustrated.
GCU2
UD1471.6 Iss 1 (15/02/2002)
Page 6 - 5
GCU2
Typical Applications
Page 6 - 6
GCU2
UD1471.6 Iss 1 (15/02/2002)
GCU2
Typical Applications
In any particular Gas Area at least 2 detectors must trigger to cause a coincidence
condition.
2.
The area Gas Control Unit is then triggered from the ZP3/ZP5 Control Panel.
3.
The Gas Control Unit will then trigger a line leading to the Gas Detonator
Distribution Unit.
4.
The Detonator Distribution Unit will then cause the pressure cylinder to activate
and will cause the relevant electro-pneumatic activated valve to open. The
Selection Unit will also cause the appropriate Gas Cylinder Detonator(s) to
activate.
5.
This will cause the appropriate Gas Area to be flooded from the required cylinders.
GCU2
UD1471.6 Iss 1 (15/02/2002)
Page 6 - 7
GCU2
Typical Applications
Page 6 - 8
GCU2
UD1471.6 Iss 1 (15/02/2002)
GCU2
Typical Applications
If the Door is open (ie the room is occupied) and the Gas Control is in Automatic
Discharge Mode a buzzer will sound.
2.
If the Door is closed (ie the room is unoccupied) and the Gas Control Unit is in Manual
Discharge Mode a buzzer will sound.
GCU2
UD1471.6 Iss 1 (15/02/2002)
Page 6 - 9
GCU2
Typical Applications
Page 6 - 10
GCU2
UD1471.6 Iss 1 (15/02/2002)
GCU2
Typical Applications
6.6 Single Gas Area with Multiple Doors and Gas Status Units
This system consists of a Large Gas Area with three access doors (Fig 6). Next to the main
access door is a Gas Control Unit which is attached to a ZP3/ZP5 Control Panel. There is a
Gas Status Unit next to each of the subsidiary access doors. These Gas Status Units are
connected via one another to the Gas Control Unit. The Gas Status Units have identical
controls to that of the Gas Control unit. For further information on Gas Status Units see Part
2 of this manual.
The Gas Status Units allow for remote control of the Gas Control Unit.
A gas release may be caused in the following manner.
1.
Two or more of the Gas Areas detectors may trigger causing a coincidence condition.
This will cause the Control Panel will relay this information to the Gas Control Unit
which will initiate a gas drop.
2.
A manual gas release can be initiated from the Gas Control Unit by triggering the built
in breakglass unit.
3.
A manual gas release may also be initiated remotely from one the Gas Status Unit.
The Gas Status unit then relays the information to the Gas Control Unit which will
trigger a gas drop.
It should be noted that the standard wiring configuration used to connect the Gas Status
Units to the Gas Control Unit causes the following Auto/Manual system response:
1.
2.
The gas system has monitoring for the break glass unit, the more time gas hold off and the
locked off functions. Links L1, L2, & L3 must be placed on the last Status/Repeater
furthermost from the GCU2 in the chain. Links L1, L3 and L4 must be removed from the
GCU2 when it is used in conjunction with Status/Repeater units.
GCU2
UD1471.6 Iss 1 (15/02/2002)
Page 6 - 11
GCU2
Typical Applications
Page 6 - 12
GCU2
UD1471.6 Iss 1 (15/02/2002)
GCU2
Typical Applications
GCU2
UD1471.6 Iss 1 (15/02/2002)
Page 6 - 13
GCU2
Typical Applications
Page 6 - 14
GCU2
UD1471.6 Iss 1 (15/02/2002)
GCU2
Typical Applications
GCU2
UD1471.6 Iss 1 (15/02/2002)
Page 6 - 15
GCU2
Typical Applications
Page 6 - 16
GCU2
UD1471.6 Iss 1 (15/02/2002)
GCU2
Appendix A
UD1471.0
Issue 1
15/02/200
Product Data
PS 1464.1
The Ziton ZP Gas Control Unit is designed to
connect to a ZP fire detection system. Each Gas
Control Unit controls one Halon 1301/1211 or
Carbon Dioxide CO2 gas fire extinguishing system. The ZP fire control panel provides secure "Coincidence Connection" control of the gas
extinguishing system. It is field programmable, with
cross-mapped inputs being selected from various
ZP line devices or zones. Functions such as
automatic gas release delay, selection of delay/nodelay for manual gas release, and output relay
control are fully configurable.
The self-contained unit has key switches for
automatic or manual selection, as well as lock-off
for maintenance. Other controls are manual gas
release, an alarm silence push button, and
indicators for automatic, manual, locked-off, gas
discharged and reset status.
Outputs are provided for gas release valves or
detonators, audible fire alarm sounders, separate
gas release sounders, visual exit signs, door closing
and shutter release. Also provided are facilities for
remote manual gas release, and remote operation
and status functions.
Optional monitoring is provided for low gas
pressure, gas release verification, and locked/
unlocked entry door status of the protected area.
The gas control unit is under the control of its ZP
fire control panel. It communicates with the fire
panel every two seconds. The status of each gas
control unit is displayed at each fire control panel.
A fault signal indicating the type of fault, is raised at
the fire panel for any out-of-normal conditions
which exits at the gas control unit. Monitoring is
provided for many functions, including power
supply, fuses, and operation. Field wiring is
monitored for gas release valves/detonators, fire
sounder, and manual gas release units.
Any number of gas control units may be used on a
ZP fire detection system, with each unit requiring
two system addresses. The unit may be connected
to a single ZP system address line, or it may
optionally be connected to two ZP system address
lines, providing additional security against an
accidental discharge. The casing of all gas control
units must be earthed to building earth.
In addition to being connected to the ZP system
address line, the gas control unit requires a 24Vdc
supply. This can be supplied from the main system
supply, or from a local power supply unit.
ZP5-GCU2
ZP Addressable Gas
Control Unit
Product Data
Wiring Schematic
Specifications
Description
Model
Part No
Activation
Communication
Capacity
Operating Voltage
22 - 29 Volts dc
Current
Quiescent
Alarm
Fault
80mA
150mA (Excl ext dev)
200mA (Excl ext dev)
Controls
Auto/manual control
Lock-off/reset
Fire sounder silence
Gas sounder silence
Manual gas release
Keyswitch
Keyswitch
Push-button
Reset keyswitch
Built-in break glass unit
Status Indications
Gas discharged
System auto
System manual
System locked-off
Fire
Fault
Power on
Function monitoring
Fire sounder
Gas sounder
Gas release valve
or detonator
Manual gas release unit
Status monitoring
Auto/manual
System locked
Door locked/unlocked
Gas discharge - manual
Gas discharge - auto
Output Ratings
Gas release
Sounder
Auxiliary relay
Optional accessories
Remote status units
Remote repeater
Door Monitor
ZP5-GCU2S Pt No 80101
ZP5-GCU2R Pt No 80201
ZP5-GDM1 Pt No 077001
Colour
Size (W x H x D)
Mass
Ash grey
300 x 230 x 100mm
4 Kg
Environmental rating
EN60529
IP 40
IMPORTANT NOTE:
Ziton Ltd
8 Newmarket Court Chippenham Drive Kingston Milton Keynes MK 10 0AQ United Kingdom
Telephone +44 (0) 1908 281981 Fax +44 (0) 1908 282554 email zitonuk@ziton.spx.com
Ziton (Pty) Ltd
Ziton House 555 Voortrekker Road Maitland 7405 PO Box 4965 Cape Town 8000 South Africa
Telephone +27 (0)21 506 6000 Fax +27 (0)21 506 6100 email zitonsa@ziton.spx.com
5 Amps - 24 Volts dc
0,5 Amps - 24 Volts dc
Voltage-free changeover
1,0 Amp (res)/30Vdc
Product Data
PS 1465.1
The Ziton ZP5-GCU2S Gas Status Unit is designed
to connect to a ZP5-GCU2 Gas Control Unit. The
Gas Control unit in turn connects to a Ziton ZP fire
detection system, and controls a Halon 1301/1211
or Carbon Dioxide CO2 gas fire extinguishing
system.
The Gas Status Unit has key switches to enable
remote control of the Gas Control Unit for automatic or manual selection, as well as lock-off for
maintenance. Other controls are manual gas
release, and an alarm silence push button. Indicators mimic those on the Gas Control Unit for
automatic, manual, locked-off, gas discharged and
reset status.
Actual control of the extinguishing system (gas
release valves or detonators, audible fire alarm
sounders, gas release sounders, low pressure
alarms etc), and door lock protection, is handled
from the Gas Control Unit.
There is end of line monitoring for the delay, locked
off and break glass call point function. The end of
line
links
are
to
be
placed
on
the
last
ZP5-GCU2S
ZP GAS CONTROL
STATUS UNIT
Product Data
Wiring Schematic
Specifications
Model
Part No.
ZP5-GCU2S
80101
Compatability
Max. No. per GCU
Operating Voltage
Current
Quiescent
Max (Gas Release)
Auto/manual control
Lock-off/reset
Fire sounder silence
28mA
60mA
Keyswitch
Keyswitch
Push-button
Reset button
Ziton Ltd
8 Newmarket Court Chippenham Drive Kingston Milton Keynes MK 10 0AQ United Kingdom
Telephone +44 (0) 1908 281981 Fax +44 (0) 1908 282554 email zitonuk@ziton.spx.com
Ziton (Pty) Ltd
Ziton House 555 Voortrekker Road Maitland 7405 PO Box 4965 Cape Town 8000 South Africa
Telephone +27 (0)21 506 6000 Fax +27 (0)21 506 6100 email zitonsa@ziton.spx.com
IP 40
Product Data
PS 1466.1
The Ziton ZP5-GCU2R Gas Repeater Unit is
designed to connect to a ZP5-GCU2 Gas Control
Unit. The Gas Control unit in turn connects to a
Ziton ZP fire detection system, and controls a Halon
1301/1211 or Carbon Dioxide CO2 gas fire
extinguishing system.
The Gas Repeater Unit has indicators which mimic
those on the Gas Control Unit for auto-matic,
manual, locked-off, gas discharged and reset
status.
Actual control of the extinguishing system (gas
release valves or detonators, audible fire alarm
sounders, gas release sounders, low pressure
alarms etc), and door lock protection, is handled
from the Gas Control Unit.
Up to 10 Gas Status or Repeater Units may be
attached to any one Gas Control Unit. All Gas Unit
casings must be earthed to building earth.
The end of line monitoring is placed on the last
Status/Repeater unit. The locked off input on the
Repeater display board must be looped for the
system to operate with the locked off end of line
ZP5-GCU2R
ZP GAS CONTROL
REPEATER UNIT
Product Data
Wiring Schematic
Specifications
Model
Part No.
Compatability
Max. No. per GCU
Operating Voltage
Current
Quiescent
Max (Gas Release)
ZP5-GCU2R
80201
ZP5-GCU2 Gas Control
10 Status and/or Repeater units
22 - 29 Volts dc
28mA
60mA
Ziton Ltd
8 Newmarket Court Chippenham Drive Kingston Milton Keynes MK 10 0AQ United Kingdom
Telephone +44 (0) 1908 281981 Fax +44 (0) 1908 282554 email zitonuk@ziton.spx.com
Ziton (Pty) Ltd
Ziton House 555 Voortrekker Road Maitland 7405 PO Box 4965 Cape Town 8000 South Africa
Telephone +27 (0)21 506 6000 Fax +27 (0)21 506 6100 email zitonsa@ziton.spx.com
Product Data
PS 1467.1
The Ziton ZP5-GDM1 Gas Door Monitor Unit is
designed to attach to a ZP5-GCU2 Gas Control
Unit. The Gas Control unit in turn connects to a
Ziton ZP fire detection system, and controls a Halon
1301/1211 or Carbon Dioxide CO2 gas fire
extinguishing system.
The door monitor unit gives an alarm when a room
is left in an automatic discharge condition whilst
occupants are in the room, or, if left in a manual
discharge condition when occupants leave the
room. The detection of room occupancy is achieved
by means of a switch connected to the entrance
lock. The Door Monitor unit should be placed within
hearing distance of the door being monitored,
preferably outside the the area being monitored.
OPERATION
During normal room occupancy, the system is set to
MANUAL as a precaution against injury to
personnel due to automatic gas discharge. When
the last occupant locks the room on departure, this
is detected by the door monitor switch and the door
buzzer will sound. A period of 30 seconds is given
to switch the system to AUTOMATIC. If the panel is
not switched to AUTOMATIC inside this period then
a warning is sent to the control panel indicating an
unsafe condition.
The reverse applies on arrival at an unoccupied
room. After unlocking the door, the door monitor
buzzer will sound, and a period of 30 seconds is
given to switch the system to MANUAL. If the panel
is not switched to MANUAL inside this period then a
warning is sent to the control panel indicating an
unsafe condition. The warning buzzer is only
silenced by rectifying the condition.
Gas System
Auto
Manual
Auto
Manual
Door
Locked
Locked
Unlocked
Unlocked
Buzzer
OFF
ON
ON
OFF
ZP5-GDM1
ZP Gas Control Door
Monitor Unit
Product Data
Wiring Schematic
Specifications
Part No. 077001
Description
The Ziton ZP5-GDM1 is an optional Door Monitor Board which piggy-backs on the ZP5 Gas Control Unit Main Control Board ZP5GCM2. It facilitates detection of an unsafe gas condition i.e. when the door is unlocked and the Gas Control Unit is set to automatic,
or when the door is locked and the gas Control Unit is set to manual.
NOTES
1.When a Gas Control Unit is equipped with a Door Monitor Unit it should be situated within hearing distance of the door being
monitored, preferably outside of the area being gas protected.
TERMINAL FUNCTIONS
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
Ziton Ltd
8 Newmarket Court Chippenham Drive Kingston Milton Keynes MK 10 0AQ United Kingdom
Telephone +44 (0) 1908 281981 Fax +44 (0) 1908 282554 email zitonuk@ziton.spx.com
Ziton (Pty) Ltd
Ziton House 555 Voortrekker Road Maitland 7405 PO Box 4965 Cape Town 8000 South Africa
Telephone +27 (0)21 506 6000 Fax +27 (0)21 506 6100 email zitonsa@ziton.spx.com
Product Data
PS 1468.1
The Ziton Gas Control Main Board ZP5-GCM2 is
incorporated inside the housing of the Ziton Gas
Control Unit ZP5-GCU2. The board consists of two
sections, namely a Gas Relay section and Relay
section.
The Gas Relay and Relay sections both have a
dipswitch which allows the addresses of the
individual sections to be set.
Relay controlled outputs are provided for gas
release valves or detonators, audible fire alarm
sounders and separate gas release sounders. Also
provided are facilities for remote manual gas
release, and remote operation and status functions.
Extensive monitoring is provided for many functions, including power supply, fuses, and operation. The Main Control Board has 5 diagnostic
LEDs that help with monitoring for gas release
valves/detonators, fire bell, gas discharge siren,
manual gas release unit and low gas pressure
faults.
The Gas Control Main Board communicates with
ZP5 Control Panel through the ZP Line.
ZP5-GCM2
Gas Control Main
Board
Product Data
DESCRIPTION
The Ziton ZP5 Gas Control Main Board is designed to connect to a ZP5 Gas Control System, and to control a Halon 1301/1211 or
Carbon Dioxide CO2 gas fire extinguishing system. The board interfaces to the fire control panel of a ZP fire detection system and
provides secure "Double Knock" control of the gas extinguishing system.
NOTES
1. Polarising diodes must be fitted to all bells and sirens.
2. Fire Alarm Bell circuits (J3-1 & J3-2) and Discharge Siren (J3-5 & J3-6) utilise 2200 Ohm 1 Watt EOL resistors which must be fitted
after the last unit to be monitored.
3. The detonator circuit (J3-3 & J3-4) is monitored by a 2200 Ohm 1 Watt EOL which must be fitted at the end of the detonator line.
4. Gas Discharge verification and Gas Cylinder pressure low monitoring. An open circuit indicates a drop in the monitored cylinder
pressure. A short circuit verifies gas discharge. A 3900 Ohm EOL resistor is used.
5. Remote manual gas release units (J3-7 & J3-8) are monitored through a 3900 Ohm EOL resistor. Placing a short circuit across these
terminals activates the gas discharge sequence.
Specifications
Model
Part No.
Communication
Operating Voltage
Current
Quiescent
Alarm
Fault
ZP5-GCM2
80301
ZP Polling System
22 - 29 Volts dc
80mA
150mA (Excl external dev)
200mA (Excl external dev)
5 Amps - 24 Volts dc
Terminal functions
F1
Detonator fuse 5 Amp
F2
Gas Siren fuse 2 Amp
F3
Fire bell fuse 2 Amp
J1-1
J1-2
J1-3
J1-4
Address line
Address line
Address line
Address line
J2-1
J2-2
24 V dc (+)
24 V dc (-)
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12
TB1-13
TB1-14
TB1-15
TB1-16
TB1-17
TB1-18
TB1-19
TB1-20
TB1-21
J4
Sounder outputs
Auxiliary relay contact
(Voltage free)
Size (W x H )
Weight
Compatibility
Environmental
IMPORTANT NOTE:
Link operation
L1 (out)
Gas release signal not verified
L1 (in)
Gas release verified via pressure switch
L2
not implemented
L3
Selects the timer reset option for the hold off gas release button
LED indicators
D94
D67
D75
D84
RELAY
G-REL
Address Switch
SW1-2
Gas relay address (2)
SW1-3
Gas relay address (4)
SW1-4
Gas relay address (8)
SW1-5
Gas relay address (16)
SW1-6
Gas relay address (32)
SW1-7
Gas relay address (64)
SW2-1
SW1-2
SW2-3
SW1-4
SW2-5
SW1-6
SW2-7
Double-knock
Double-knock
Double-knock
Double-knock
Double-knock
Double-knock
Double-knock
Timer adjust
VR1
Ziton Ltd
8 Newmarket Court Chippenham Drive Kingston Milton Keynes MK 10 0AQ United Kingdom
Telephone +44 (0) 1908 281981 Fax +44 (0) 1908 282554 email zitonuk@ziton.spx.com
Ziton (Pty) Ltd
Ziton House 555 Voortrekker Road Maitland 7405 PO Box 4965 Cape Town 8000 South Africa
Telephone +27 (0)21 506 6000 Fax +27 (0)21 506 6100 email zitonsa@ziton.spx.com
Product Data
PS 1469.1
The Ziton ZP5-GSM2 Gas Status Main Board, is the
main board used in the ZP5-GCUS2 Gas Status
Unit and the ZP5-GCUR2 Gas Repeater Unit.
The board provides ribbon cable connection to the
display board which fits on to the door of the
assembly. Current limiting resistors on the board
limit current to the LEDs on the door.
Terminal blocks allow for separate input and output
connections when the Status or Repeater units are
connected in series.
ZP5-GSM2
ZP Gas Status Main
Board
Product Data
Specifications
Description:
Model:
Part No:
Compatability:
Operating Voltage:
Quiescent Current:
Max Current:
Input Terminals:
Output terminals:
Size:
Mass:
60mA
From GCU2, GCU2S or GCU2R
To next GCU2S or GCU2R
150 x 150 x 30mm
100gm
DESCRIPTION
The Gas Status Unit is designed to connect to a ZP5-GCU2 Gas Control Unit, which in turn
interfaces to the fire control panel of a ZP fire detection system, and controls a Halon 1301/1211 or Carbon Dioxide CO2 gas fire
extinguishing system.
The Ziton ZP5-GSM2 is the Main PCB assembly for the ZP5-GCU2S Gas Status Unit and the ZP5-GCU2R Gas Repeater Unit. The
Status Unit mimics the indications of the Control Unit and provides f a c i l i t y for remote control functions. The repeater unit only
mimics the ZP5-GCU2 Gas Control Unit.
NOTES
1.
Up to 10 Gas Status/Repeater Units can be connected to any one Gas Control Unit.
TERMINAL FUNCTIONS
TB
Input
Call point alarm in from call point alarm out from previous Status/Repeater unit (TB2 No.1) from TB3 CP Terminal on
Gas Control units display board.
Automatic/Manual Control in from auto/manual out from previous Status/Repeater unit (TB2 No.2) from TB3 A/M
terminal on Gas Control units display board.
Lock off control in from lockoff out from lockoff control of previous Status/Repeater unit or from TB3 LOFF terminal on
Gas Control units display board.
Remote silence in from TB1-17 on the gas control unit or from silence output of previous Status/Repeater unit (TB2 No.4)
Locked off LED in from TB1-10 on Gas control unit or from locked off LED on previous Status/Repeater unit. (TB2 No.5)
Auto LED in from TB1-12 on Gas control unit or from Auto LED out on previous Status/Repeater (TB2 No.6)
Manual LED from TB1-11 on Gas control unit or from manual LED out on previous previous Status/Repeater unit (TB2
No.7)
Fire LED in from TB1-14 on Gas Control unit or Fire LED out on previous Status/Repeater unit (TB2 No.8)
Fault LED in from TB1-9 on Gas control unit or from Fault LED out on previous Status/Repeater unit (TB2 No.9)
10
Gas release LED in from TB1-13 on Gas control unit or from gas release out on previous Status/Repeater (TB2 No.10)
11
Delay switch in from TB3 Delay on Gas Control Units display board or from Delay out from previous Status/Repeater
(TB2 No.11)
12
Gas pending in from TB1-8 on gas control unit or from gas pending out on previous gas control unit (TB2 No.12)
Ziton Ltd
8 Newmarket Court Chippenham Drive Kingston Milton Keynes MK 10 0AQ United Kingdom
Telephone +44 (0) 1908 281981 Fax +44 (0) 1908 282554 email zitonuk@ziton.spx.com
Ziton (Pty) Ltd
Ziton House 555 Voortrekker Road Maitland 7405 PO Box 4965 Cape Town 8000 South Africa
Telephone +27 (0)21 506 6000 Fax +27 (0)21 506 6100 email zitonsa@ziton.spx.com
Product Data
PS 1470.1
The Ziton ZP-GSD2 is the display board used in the
ZP5-GCU2S Gas Status Unit and the ZP5-GCU2R
Gas Repeater Unit. The board connects to the ZP5GSM2 main board via a ribbon cable.
( * Silence and more time hold off switches are only
fitted to the Status display board. )
*
*
ZP5-GSD2
ZP Gas
Status/Repeater
Display Board
Product Data
Wiring Schematic
Specifications
Description
Model
Part No
Compatibility
Operating Voltage
Description
When this board is used in the Status Unit it provides controls for the Status Units Gas hold off button, silence button, call point input,
locked off/reset and Auto/Manual controls. These controls are signaled to the Gas Control Unit. The display board also mimics the
LED indicators of the Gas Control Unit.
When the ZP5-GSD2 is used in the Repeater Unit, it is only used to mimic the LED indicators of the Gas Control Unit.
NB. A wire link must also be connected between TB1.7 & TB1.8 (on a repeater) for lockoff end off line function.
Terminal functions for the Status Unit
TB1
Label
Function
Delay
Silence
Auto/Manual
Locked off
Break glass
The Repeater Unit is used only to mimic. It therefore does not have inputs for contacts. The locked off terminal must be looped on the
Repeater.
Link operation
L1, L2 & L3 are placed on the last Status/repeater Unit in the system. These links are used to implement the end of line.
L1
L2
L3
Ziton Ltd
8 Newmarket Court Chippenham Drive Kingston Milton Keynes MK 10 0AQ United Kingdom
Telephone +44 (0) 1908 281981 Fax +44 (0) 1908 282554 email zitonuk@ziton.spx.com
Ziton (Pty) Ltd
Ziton House 555 Voortrekker Road Maitland 7405 PO Box 4965 Cape Town 8000 South Africa
Telephone +27 (0)21 506 6000 Fax +27 (0)21 506 6100 email zitonsa@ziton.spx.com
Wiring Data
Connection Details
ZP5 GCU2 Gas Control Unit to
ZP5 GCU2R Gas Repeater Unit/
ZP5 GCU2S Gas Status Unit
TB1
End of line
ZP5-GCU2S
Gas Status Unit
End of line
2 1
2 3 4 5 6 7 8 9 10 11 12
TB1
2 1
TB2
2 3 4 5 6 7 8 9 10 11 12
OUT
IN
0V 24V
OUT
IN
0V 24V
ZP5-GCU2R
Gas Repeater Unit
2 1
2 3 4 5 6 7 8 9 10 11 12
2 1
2 3 4 5 6 7 8 9 10 11 12
TB2
Intermediate
ZP5-GCU2S
Gas Status Unit
Intermediate
ZP5-GCU2R
Gas Repeater Unit
External
24V
Supply
+
J2
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
TB1
24V 0V
STATUS IN
IN
CP
OUT
LOOP
ZP5-GCU2
Gas Control Unit
Surge protected
24V for gas units
Loop Inputs
Display Board
Attached to Door
of GCU2
- SCRN + - SCRN
LOOP A
LOOP B
Surge Board
Attached to
Main Board
of GCU2
Sensor
Surge protected
24V output
to main board
Discharge
nozzles
Gas Cylinder
ZP Control
Panel
Wiring Data
Wiring Table
Connections in tabular form between Control Unit and Status/Repeater
Unit
Terminal Location
GCU2 Main
Board
Terminal
Label
TB1
J2
Status/Repeater
Unit
Display Board
TB3
Main Board
TB1
10 11 12 13 14 17
0V 24V
0V 24V 12
Ziton Ltd
8 Newmarket Court Chippenham Drive Kingston Milton Keynes MK 10 0AQ United Kingdom
Telephone +44 (0) 1908 281981 Fax +44 (0) 1908 282554 email zitonuk@ziton.com
Ziton (Pty) Ltd
Ziton House 555 Voortrekker Road Maitland 7405 PO Box 4965 Cape Town 8000 South Africa
Telephone +27 (0)21 506 6000 Fax +27 (0)21 506 6100 email zitonsa@ziton.com
10
11
Wiring Data
Sensors
+
_
ZP Control
Panel
+
_
ZP Address Loop 2
3K9
EOL
Gas Cylinder
Pressure Low
Monitor Switch
Normally Closed
Pressure Activated
Discharge Verify
Switch Normally Open
Gas Release
Mechanism
2K2
EOL
Discharge
Nozzles
Gas Cylinder
2K2
EOL
Fire
Bell
2K2
EOL
Gas
Discharge
Siren
Remote
silence
External
24V
Supply
J2
2 3
4 5 6
12 13 14 15 16 17 18 19 20 21 22 23 24
Surge protected
24V for gas units
J3
Gas release
auxiliary
contacts
EARTH 24V 0V
- SCRN + - SCRN
LOOP A
LOOP B
Surge Board
Attached to
Main Board
of GCU2
STATUS IN
DELAY A/M LOFF
IN
CP
OUT
LOOP
-
Display Board
Attached to Door
of GCU2
Surge protected
24V output
to main board
Wiring Data
Sensors
+
_
ZP Control
Panel
+
_
ZP Address Loop 2
3K9
EOL
Gas Cylinder
Pressure Low
Monitor Switch
Normally Closed
Pressure Activated
Discharge Verify
Switch Normally Open
Gas Release
Mechanism
2K2
EOL
Discharge
Nozzles
Gas Cylinder
2K2
EOL
Fire
Bell
2K2
EOL
Gas
Discharge
Siren
Remote
silence
External
24V
Supply
+ _
J2
2 3
4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Surge protected
24V for gas units
TB1
Gas release
auxiliary
contacts
EARTH 24V 0V
- SCRN + - SCRN
LOOP A
LOOP B
Surge Board
Attached to
Main Board
of GCU2
STATUS IN
DELAY A/M LOFF
IN
CP
OUT
LOOP
-
Display Board
Attached to Door
of GCU2
Surge protected
24V output
to main board
Wiring Data
Wiring Data