Вы находитесь на странице: 1из 4

e tects or

T _I
M utual Incuction etween
f K j . n pedance. The effect of the ground return
ircuit upon the impedance can be de-
termined by either one of two ways:
Parallel Transmission Lines on Current namely, direct measurement
line icosrte, obyassuming an
after the
average value of grould resistivity for
Flow to Ground Faults calculating
The the impedance
latter method is the one by formnula.
which nmust
be used in most cases (see appendix).
JOHN 1. HOLBECK MARTIN J. LANTZ It is not deemed within the scope of this
MEMBER AIEE NONMEMBER AIEE paper to discuss the various theories of
current flow through the ground but to
show hpw assumed conditions are used to
THIS paper is intended to present some such circuits arises when unibalaniced obtain what are considered reasonable
lof the problems encountered in de- faults occur on one line causing induced results.
termining unbalanced fault currents and voltages in the parallel circuit. WVhere The effect of mnutual coupling or the
unusual results that may be expected on the lines are of the same voltage and resultant induction between parallel cir-
systems with parallel lines on a comimon bussed at either or both ends, the cal- cuits is inverselv proportional to the
right of way. Correct results are required culation resolves itself into the use of a spacing between the circuits and di-
so that proper co-ordination and applica- simple equivalent circuit. The problem rectly proportionial to the length of paral-
tion of relays may be accomplished. becomes more complicated when the lines lel.
Fault studies must be made and con- are operated at different voltages which
stantly revised, as a power system obviously cannot be bussed at one end, Mutual Induction
changes and expansions take place. Also, or when a fault calculation is required on
future conditions must be studied so that one end of a pair of parallel lines whose WA/hen two transinission lines parallel
intelligent selection may be made of cir- opposite ends are unbussed, such as a each other close enough for the mutual
cuit breakers and current transformers. split-bus arrangement. In solving a induction to be appreciable, there is
It is the purpose of this paper to discuss problem of the latter type, use is nmade of transformer action between the circuits
1. The use of the a-c network analyzer in the a-c network analyzer which utilizes when unbalanced currents flow. The
solving fault problems by using certain one-to-one ratio transformers to represent mutual induction resulting from the flow
mathematical simplifications which are the mutual induction between lines. of positive-sequence current is small anid
necessary in order to adapt the problem to Usually fault-current calculations are is reduced to a negligible value by the
the analyzer's limitations. within the scope of a d-c calculating transposition of conductors. Transposi-
2. Some rather unusual conditions which board. As a power system becomes more tion, however, has no effect on the zero-
may occur onofasystem
tin bcause
a during fault condi- plicatednfulcand
complicated hmore
ndianonmore than one line oc- ioonectontoc-ro
hs
sequence induction. When paralleling
tion between parallel lines. cupies the same right of way, in some two identical circuits of the positive-
cases operating at different voltages, the sequence network, the resulting imped-
Frequently two or more power tranis- effect of mutual induction between the ance is one half of the impedance of one
mission lines are built on the same right lines becomes important for unbalanced line. This is not true for the zero-se-
of way parallel to each other for partial faults. A d-c board cannot be used for quence network for the reason that the
distances or for the full length. The these more complicated conditions. flow of unbalanced currents will cause a
problem of mutual induction between certain amount of induction or mutual
Paper 43-151, recommended by the AIEE com- Zero-Sequence Currents coupling to exist between the circuits re-
mittee on power transmission and distribution for
presentation at the AIEE national technical meet- tomewhat
sultiig in a valuesg greater thai
ing, Salt Lake City, Utah, September 2-4, 1943. Since the flow of zero-sequence current half the impedance for two identical cir-
Manuscript submitted March 24, 1943; made
available for printing August 2, 1943. 1S not restricted to the physical conductor cuits in parallel. The mutual impedance
JOHN 1. HOLBECK and MARTIN J. LANTZ are with but must return through the ground cir- between the circuits telnds to reduce the
the Bonneville Power Administration, Portland,
ecuit,
the resistivity of the ground itself fault current utnder certain conditiolns
Oreg. Mr. Holbeck is chief in the protection engi-
neering tinit, engineering division. enters into the deterlinatioii of its im- and increase it under other conditions, de-

each direction can be independently con- equipment so that the thyratron func- rect sequence of excitation to the respec-
trolled by connecting different control tions associated with variable armature tive fields of generator and motor during
potentiometers with interlocks on the excitation of a one-horsepower motor acceleration and deceleration. The re-
reversing contactors. would, instead, provide field excitation versing problem, too, is more complicated
for the generator of a mnotor generator because of the necessity of reversing
Application to Motor-Generator-Set set, and the thyratron circuit for the generator field excitation, but all this
Drives field of the one-horsepower mlotor would has been done.
be adapted to supply variable field ex- Meanwhile, developments are progres-
For those who have immediate need citation to the field of the larger motor. sing toward the use of ignitron-type tubes
for this type of control characteristic for The loop-current control becomes more to provide armature excitation for motors
motors of, say 50- to 400-horsepower complex, particularly since d-c current of higher horsepower ratings than can
ratings, or even 2,000-horsepower, for must be measured directly and its direc- now be supplied with the available hot-
that matter, it is practical to modify this tion of flow ascertained so as to give cor- cathode thyratron tubes.

712 TRANSACTIONS Holbeck,Lctntz-Parallel Transmission Lines ELECTRICAL ENGINEERING

Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on March 10,2010 at 00:00:33 EST from IEEE Xplore. Restrictions apply.
pending upon the relative directions of Zo-Zu STATION"A"
the ground currenit and the induced cur- A. 230K
rent. When -a single-phase-to-ground TOSTA. G ToSTAH
fault occurs on an energized line, the re- ZM-2 ZMI-3 I>
sulting zero-sequence currents flowing KV-i W
I15 - 2-ZM1.3
through all three conductors in the same B.
direction induce a voltage in the coupled 230KV Z°4
L.#f 1ZMM.2ZI3
-3
24Z -ZUM 2-3
ZUI-2 28 Mi.
circuit tending to cause an induced cur- 230 KV -Z Z3ZM23-ZMI3
Z03_M2-_Z,M-3 STATION
15KV
"B"
rent to flow in the opposite direction to
the one causing it. This may add to or D
subtract from the existing zero-sequence ZOI-ZM1-2ZM,3
MM1;
currents flowing in the coupled circuit c.
to the fault through physical circuit ties.
2-3
ZO2-ZM23-ZM12 |2 Mi.434M
Under certain conditions the amount
ZM3 2-2 30KVTOSTE"
of induction may be great enough to re- ZMj3
TO3-ZM2.3-ZMI.3 STA. F
verse the current flow in the coupled cir- ZMA 230 KV
cuit when large fault currents flow. It ZOI-ZMI-2 STATION C" mmD
may even change the direction of flow in D., 115KV-f
nearby transformer neutrals, causing the 2-3 223 STA-.
nearbyransoflwiormverseo
culrrent to flow in reverse of the cneZM2.-3-ZMA
h
conven- -Z03-ZM2.3 -M&,Z34- TO E STJD"
Figure 2. Diagram for indicating the relation.
TO

tional direction. (ZMA-AVE.Zm OFI22 a -a3) ships of mutual induction between the parallel
Figure 1 A. Equivalent zero-sequence im- lines connecting stations A. B, and C.
Devices for Representing Effect of pedance circuit of two parallel lines (same STATION "A"
Mutual Induction voltage) for calculation of ground-fault current
TO 115KV 230KV TO
Figure lB. Use of one-to-one ratio trans- STA. 'G" STA.1H'
Two lines having mutual induction be- formers for representing the mutual induction
tween them may be represented by an between parallel lines on the a-c calculating
equivalent circuit, provided the lines are board J 0.120
bussed at one end. This presupposes -J 0.079
Figure IC. Simplification of the circuits in
Figure 1 B to reduce the number of
age. The equivalent imnpedance is de- transformers required for the setup one-to-one
J 0.031
on the cal- 115KV J 0 567
termined by subtracting the mutual im-
pedance from the zero-sequence imped-
culating board | J 0.097
JJ.I88
ance of each line and adding it as a com- Figure 1 D. Further simplification of Figure l B.
pfeachlinermittding sutis
monimpeance This is only an approximation and is not accu-
2300KV.011 J
T OSTATION B"
mon impedance permitting solution bby aa 0.121
rate for all applications T
reduction of circuits through arithmetical STA. E J 0.094
means. See Figure lA. B A To
STA."F'
This equivalent
This equivalent circuit mlaycircuit
n iay be used tion of several lines on the same right -j 0.028 ~~~~~~~~~230
23
KV
TTINC
on an analyzer, but the solution is limited of way, and their operation at different c Qm STATIONT"C
in its scope to lines of the same voltage voltages. In solving problems of this J Q018 JOQSO TO 1 TO
bussed at one end. A device providing a type, resort must be made to simplifica- STA. E' STA.*D
more general and flexible arrangement is tion of circuits because the usual a-c net- A
used on the network analyzer with alter- work analyzer has few transformers for EQUIVALENT
nating current applied to the analyzer. representing mutual induction. Where a Figure 3. Simplification of the calculating-
A transformer with one-to-one ratio is number of mutual reactances are to be board circuits representing the lines connecting
used, shunting an impedance equal to the considered, as many simplifications as stations A, B, and C for calculating faults ex-
mutual impedance across one set of ter- possible are made to represent the im- ternal to this section of the power system
minals such that a voltage drop propor- pedances between busses, and expansions Reactance values are on a per unit 50-megavolt-
tional to the mutual induction is reflected are made successively byv sections dmpere base
to the coupled circuit, inducing a current throughout the system as a detailed
in the opposite direction to the originating study is made. cuit of the station B transformer bank in
current. This device may be used for Figure 2 shows a section of a possible Figure 3, losing the identity of the sta-
lines of differing voltages and for unbussed system between stations A, B, and C tion B 230-kv bus. Where this cannot
lines. The analyzer setup is the same as with its several parallels. Figure 3 shows be done, a capacitive reactance may be
for the equivalent circuit, and therefore how the section was reduced to an ap- substituted for the negative value of
requires that the mutual imupedance be proximate equivalent circuit requiring inductive reactance on an a-c analyzer.
subtracted from the zero-sequence im- only two instead of six mutual trans- The diagram in Figure .3 could be fulrther
pedance of each line and that one side of formers. Negative values of resistance reduced to save reactor units on the
the transformer be shunted with an im- and reactance may be encountered. The analyzer by using a delta-star transf or-
pedance equal to the mutual impedance. resistance component must be omitted. mation of the lines, but the net result
Either side of the transformer may be The reactance component may be handled still shows a negative value of reactance.
shunted by the mutual impedance. in one of several ways. Wrhere possible, Negative reactance values can sometimes
Modemnsystems may have some rather the negative values of reactance may be be avoided if the mutual transformers
complicated conditions invrolving mutulal combined wvith the positive values such have a ratio equal to the line voltage
impedance resulting from the construc- as wrould be the case with the primary cir- ratio. This simplified network would be

NJOVEMBER 1943, VOLUME 62 Holbecke, Lantz-Parctllel Transmission Lines TRANSACTIONS 713

Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on March 10,2010 at 00:00:33 EST from IEEE Xplore. Restrictions apply.
3 LHNE 2 '-
4
usedduring the study of faults in another current ground relay in position 3 may
____________,_________ o_ section of the system and would require seal its contacts before breaker 2 opens,
AY Ay {DI LINE rD expansion for detailed study. causing an unnecessary trip out of the
CASE A In reducing a network consisting of two unfaulted line. Breaker 2 would probably
3 LINE 2 4 lines bussed at one end and paralleled have cleared before relay 3 closed its
^S>>p by a third line of different voltage, the contacts if the added influence of mutual
I LINE 2 arrangement is as shown in Figure 1B. induction had not increased the current
CASE B ;rb Figure lB is reduced as shown in Fig- in line 2 to speed up the operation of re-
ure 1C by substituting the equivalent lay 3.
operation circuit of Figure IA for the lines that are
bussed. When the values of mutual im- CASE B
CseArepresentstwo 230kv
Case A represents two 230-ky lines operated
linesoperdte pedance are equal or close enough to Case B, Figure 4, represents the same
temporarily at 1 15 kv
average, a single transformer may be pair of lines except that circuit 2 has been
Case B represents the same pair Of lines, substituted as shown in Figure 1D be- raised to 230 kv, and each line is ener-
with line 1 operated at 115 kv and line 2 cause the sum of the induced currents gized by separate generators.
operated at 230 kv, each line energized flow in the mutual branch of the equiva- The fault is again placed at the same
by a separate generator. The location ot the point on line 1, causing breaker 1 to
roundfaul in each case is markd by an v lent circuit.
open. This entirely isolates the two lines
STATION A 3/$/.w4 False Relay Operation Because of except for mutual induction between
230 KV Mutual Induction them which caused the unbalanced cur-
I5 *0 rent to reverse in line 2 and therefore
Cases A and B, Figure 4, are two ex- reverse the normal direction of the current
115 KV amples of how the effects of mutual induc- flow in the transformer neutral. Relay
STATION a tion could cause false relay operation if 4, if current polarized, has both its polar-
n25,
265 it is not considered in the relaying. izing and actuating current reversed so
t
i 22,0 1 < 1585 I CASE A the resultant direction continues to be
1KCAsE A the same until breaker 9 opens. Relay
18l640
T Case A represents two 230-kv
lines 4 may close its contacts before breaker 2
23C KV - A 5230 K operated temporarily at 115 kv. A opens, causing false relay operation of the
STATION E 890 power source is eonnected to each end circuit.
115 KV of the circuit, and the two lines are
900 bussed at both ends. Effect of Mutual Induction on
190
0 7,
-When the fault occurs as shown near Ground Currents
s1 KV I I STATION C the end of the line, a large current flows
through breaker .1 resulting in quick Figures 5-7, inclusive, show diagrams
tripping. At the same time the indue- with data obtained from a system fault
Figure 5A. Direction and magnitudes of the tion-type current-polarized directional study made on the a-c network analyzer
calculated Sround-fault currents in amperes at and pode exampleswoft
grondtre at-2osartsetopre.tAfter and effec
115 k for a fault on the 230-k bus of station groundrelay at2 starts to operate. After provde examples
of the effet of
B with the mutual reactances included for the breaker 1 opens, the direction of current mutual induction between circuits for
calculating-board setup flow in line 2 reverses, and, because of the ground faults. These examples are for
extra induced current from mutual in- the same section of the system as shown
STATION A 3-'5'" duction in the line, the directional over- in Figure 2 except that the line from sta-
230KV tion A to station C is omitted. These
1185- STATION A 3"'-4
g~~~~~~~~~~~~~~3 KV
35 STAT IO0N A -s
10~ ~~3
0 35 230KV
.115VSTATION
~ ~ ~ ~ ~ ~ ~ ~ ~ STTO A s-,,,.
STATION B
135 115 KV
1995
c23Q - 1550 STATION B
65
115FKV 14 5 STAT I45
230V

STATION C8020V
80 - 7t7 2705
705K -
230 KV~
~ ~ ~~~~~-23K
880 STATION C 1480~~~~~~~~~~~0

calculated ground-fault currents in amperes at - 5


115 kv if the mutual reactances of the parallel Figure 6A. Because of mutual induction be-
lines are ignored in the calculating-board setup tween circuits it is possible to have appreciable Figure 6B. The effect of ignoring mutual in-
Comarwthcuret alus hon n igre ground currents flowing in sections isolated duction
5A which include the effects of mutual from the ground fault Note negligible flow oF ground currents be-
induction Note current flow between stations B and A tween stations A and B

714 TRANSACTIONS Hol beck, Lantz-Parcsllel Transmission Lines ELECTRICAL ENGINEERING

Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on March 10,2010 at 00:00:33 EST from IEEE Xplore. Restrictions apply.
STATION ~~~~~~STATIO,N
SAIAr/-Av The effect of mutual induction betweenl
230 KV6o 230KV two lines paralleling each other on the
630i l $05-
| l same right of way through which un-
0 1380 _ - balanced current is flowing in opposite
directions is to increase the flow of ground
- 15 KV - 115 Kv current.
It is possible, because of the effects
STAT ION B
., ~~~~~540
STATION e of mutual induction between lines, to
. 125. the normal direction.
of the
465.> 95 reverse

r5 KV
l <_ 5 e-it 25 l. <;20I v2160 ground current flowing in the grounded
8 1 5KV | * neutral of a transformer bank to a ground
115° {V
40 35 1
115KV
| I

20 fault.
2W30KV 230 KV

Figure 7A. The effect of mutual induction Figure 7B. Mutual induction is ignored in h Appendix. Formulas for Calcu-
increases the aver-all ground current Rowing calculations . lationsof Zero-Sequence Imped-
in parallel lines providing the currents flow in The sum of the ground currents circulating in ances of Short Transmission Link
opposite directions the 11 5-kv line and. the stdtion B 11 5-kY trans- Without Ground Wires
Note the effect on the station A to station B former neutrdl are equdl to only 22 per cent
115-kv line which parallels the 230-kv line of the calculated values of ground currents Zero-Sequence Impedance
for 35 miles. Compare with Figure 7B (shown in Figure 7A) when the mutual induc-
tion is included. In this case faulty relay opera- Zo = R,+0.00477f+j.01397fX
em sh ftohr- tion could result if the effect of mutual induc- logio De
examples show faults on the end of trans- tion is ignored GMR circuit
mission lines with values of ground cur- (1) (Reference 1, page 157)
rent flowing before and after the adjacent Zo = ohms per phase per mile
breaker to the bus has opened for condi- no current circulates in the lines between Zm 0.00477f+j.01397fX
tions with and without the consideration stations A and B. De
of mutual induction. All currents shown The effect of mutual induction in- log1o GMD circuit
are equivalent amperes at 115 kv. creases the over-all ground current flow- (1) (Reference 1, page 158)
Figure 5 shows the effect of mutual ing in parallel lines providing the currents
induction between the 115-ky and 230-kv flow in opposite directions. Figure 7
lines for a single-phase-to-ground fault on shows this effect very clearly on the f= frequency in cycles
the station B 230-kv bus. When mutual station A to station B 115-kv line which De =2,790 feet based on an average ground
calculation consierod(gurrent
induction is considered (Figure 555A), the
calculated value of ground current in the
valu
the
parallels the 230-kv line for 35 miles.
The mutual induction (Figure 7A) in-
resistivity of 100 meter-ohms
(1) (Reference 1, pages 146-8)
creases the ground current in the line and GMR circuit=
to station A. However, when the effect the station B transformer neutral prac- V5GMD sep2 XGMR conductor
of mutual induction is ignored (Figure tically fivefold over the values obtained (1) (Reference 1, page 157)
5B), the calculations show a flow of in Figure 7B, which neglects mutual
only 135 amperes in-the I15-kv line, but induction, for the same 230-kv ground GMIR conductor (1)
obtained from tables
in the opposite direction to that shown in fault. This is an instance that could (Reference 1, page 138)
Figure 5A. In this case the 115-kv line very easily cause false relay operation, GAMD sep =
might be cleared by relay unnecessarily since erroneous results would be obtained Vtthree distances between conductors
for a 230-kv line fault if one were not by neglecting the mutual induction. R,=resistance per mile of one conductor
aware of the effect of mutual induction Proper results could not be obtained on a GjMD circuit =
between paralleling lines of different d-c board since the lines are of different 4/nine distances between conductors
voltages. voltages.
It is possible, as shown in Figure 6, Conversion of ohms to per unit Z
to have appreciable ground currents .- Pe ui . base mvaXohms
flowing in sections isolated from the fault Conclusions
_______=_ Per unit Z
kv2 ~~~~~~~~~~~~~~~~(
because of mutual induction between cir- For mutual impedance between lines of
cuits. The effect shown in Figure 6 A d-c Lcalculating board cannot be different voltages
would be much more pronounced with used to represent the effects of mutual
longer parallels or larger concentrations induction between lines operated at dif- Per unit Z=
of ground currents. Figure 6A shows the ferent voltages. The neglect of these ef- kv1 Xkv2
magnitude and direction of the ground fects may give erroneous answers serious
currents circulating between stations enough to result in false relaying. References
A and B resulting from the effect of With two lines paralleling, each other
s , . .1. SYMMETRICAL COMPONENTS (book), C. -F.
mutual induction when a fault occurs on on the same right of way through which Wagner, R. D. Evans. McGraw-Hill Book Corn-
a radial 230-ky line fed from station C. unbalanced fault current is flowing in the pany, Inc. 1933.
If mutual induction is ignored, results same direction, the effect of mutual in- 2. CALCULATION OF SNORT-CIRCUIT CURRENTS
will be obtained similar to those shown in duction between the lines is to reduce the tinc Review, April 1937, pages 189-96.
Figure 6B. In the latter case practically flow of ground current. -* Megavolt-amperes.

NOVEMBER 1943, VOLUME 62 Hol beck, Lantz-Parallel Transmission Lines TRANSACTIONS 715

Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on March 10,2010 at 00:00:33 EST from IEEE Xplore. Restrictions apply.

Вам также может понравиться