Академический Документы
Профессиональный Документы
Культура Документы
Training Unit
No: EE 018
Training Unit
Earthing and Earth Electrode Resistance
Theoretical Part
No.: EE 018
Edition:
2008
All Rights Reserved
Editor:
CONTENTS
Page
2.1.1
General ..........................................................................................................11
2.1.2
2.1.3
LEARNING OBJECTIVES
1.1
The value of the earth electrode resistance (RE) must, from time to time, be re-measured,
the circuit will only have the required safety protection when RE is below the required
value.
To measure the RE a bridge may be used.
* NOTE: Earthing may also be referred to as grounding.
1.1.1
RE
RH1
RH2
...
RI = RH1 + RE
2. Between E and H2
...
RII = RH2 + RE
3. Between H1 and H2
...
If the values of the first two measurements are added together and the value of the third
measurement is subtracted from this total, then the result will be:
In the network with the earthing as a protective measure, the earthing resistance may
not exceed:
RE max =
65V___________________
operating current of the circuit breaker
1.2
Circuit diagram
1.2.1
The connecting link between E1 and E2 is connected in series with the earthing resistance
RE.
Auxiliary earth H1 is connected at point S, auxiliary earth H2 is connected at point HE. A
transistor power converter in the instrument produces the alternating current. After power
has been applied to the circuit measuring current will flow through auxiliary earth RH, earth
RE and the adjustable resistor R of the compensator. The voltage drop V1 which appears
between earth and auxiliary earth H1 will be opposed by the voltage drop V2 across the
adjustable potentiometer R. When the voltages are equal, zero (0) will be indicated on the
galvanometer. The earth resistance (indicated in Ohms) can be read on the scale of the
adjustable potentiometer.
1.3
Earthing practice
b)
To allow sufficient current to pass to earth so that protective devices will operate.
The current path, on the occurrence of an earth fault, is from the fault to the associated
earth electrode, through the earth to the electrode of the supply transformer and back to
the fault.
If a low earth-loop resistance is required then a metallic earth-return path can be used.
INSULATION RESISTANCE
10
2.1
2.1.1
General
Before putting an installation into operation the soundness of the insulation must be
tested. It is not possible to insulate an installation completely.
For this reason, leakage currents will appear from time to time. However, with a good
insulation not more than 1 mA of current should occur in practice. The insulation
resistance (Rins) will be measured, restricts leakage current.
The following regulations are to be followed when measuring Rins in installations with a
voltage up to 1000 Volts.
2.1.2
a) When possible, the measurement should be made at the rated insulation voltage, and
not less than 500 Volts.
b) When measuring the insulation resistance of a conductor to earth, the negative pole of
the voltage source should be connected, where possible to the conductor being
measured.
c) When not only the insulation resistance of the conductor to earth, but also the
insulation resistance between two conductors are to be tested, all light bulbs, motors
and other power users should be disconnected from the supply; all light sockets will be
connected, all fuses, circuit breakers and switches will be switched on.
d) Each final circuit (circuit directly connected from a fuse to a current consuming device)
must have Rins of not less than 1000 Ohms per volt of the supply voltage.
Example:
100 V network
Rins 100 k
380 V network
Rins 380 k
500 V network
Rins 500 k
11
2.1.3
The device most frequently used is the insulation resistance meter with hand generator.
a)
Insulation resistance tester with hand generator and crossed coil instrument
The measured value is not dependent on the voltage (speed of turning hand
generator).
12
b)
Insulation resistance tester with hand generator and moving coil Instrument
To produce the proper measuring voltage so that the correct M scale reading is obtained
the hand generator must be turned at a given rpm.
For the actual measurement of the insulation resistance, button S1 is pressed and the
hand generator is turned faster and faster until the indicator of the moving coil meter
movement indicates zero on the M scale. When the button S1 is released the insulation
resistance is indicated. (When S1 is pressed the R is bypassed).
c)
Function
A DC voltage delivered from a flash light battery is chopped (mechanically or
electronically) and so transformed into a square alternating voltage.
13
This AC is stepped up across a transformer to the desired test voltage and then rectified
by a rectifying circuit, producing a DC voltage. This DC voltage is in turn filtered by a
capacitor. With this high DC voltage the insulation measurement is accomplished.
As an indicating device, a crossed-coil measuring instrument is used.
A direct indicating resistance-measuring instrument may also be used. This is
accomplished by measuring the current with known applied voltage across a resistance.
As an indicator, a normal moving coil instrument is used. The indicator is not dependent
on the condition of the battery. The battery voltage is held constant through the use of a
transistor-regulating circuit.
Measuring the insulation resistance of an installation not in operation
a) Insulation resistance to earth
14
15
16
2.1.4
For this purpose an earth leakage indicator is used. The simplest method is to measure
the three conductor voltage in the power network to earth. This method is only suitable
when the neutral point is not earthed.
Circuit for three-conductor network (mains)
In a system without error the three voltage meters will indicate the same voltage V0 / 3.
Should accidental earthing occur, then the voltage indicated on the voltmeter connected
on the defective conductor will become less, while the voltage on the other two voltmeters
will increase.
17
EE 018
Earthing and Earth Electrode
Resistance
Theoretical Test
18
EE 018
EARTHING AND EARTH ELECTRODE RESISTANCE
TEST 1
QUESTIONS:
1. What is the purpose of an earthing system?
2. What influences the value of the earth electrode resistance?
3. Draw a diagram and write the appropriate equations used to measure earthing
resistance.
4. What type of current is used for measuring the earthing resistance?
5. What is the maximum earthing resistance in a network with earthing as a protective
device?
6. State the current path in a earth measuring bridge when measuring the earthing
resistance.
7. Draw a schematic diagram to be used for measuring the earthing resistance with earth
measuring bridge.
8. Why has the insulation resistance no fixed value?
19
10. State how the insulation resistance may be monitored in a live installation.
20
EE 018
EARTHING AND EARTH ELECTRODE RESISTANCE
TEST 2
QUESTIONS:
1. State the value of Rins per volt of the supply between two lines in order for the
insulation resistance to be considered satisfactory and calculate Rins for:
a) 120 V network
b) 340 V network
c) 460 V network
2. Draw the circuit used to measure the insulation resistance to earth in an installation
not connected to the supply.
3. Draw a diagram in order to measure the Rins using an insulation resistance tester with
hand generator and moving coil instrument.
4. Draw a diagram in order to measure the insulation resistance between conductor and
conductor of an installation not in operation.
5. Draw a diagram to measure the Rins using an insulation meter with a hand generator
and cross-coil instrument.
6. Why is an earth leakage indicator built into an installation?
7. Draw a diagram for monitoring the insulation resistance in an installation in operation
with a two conductor (single phase) network.
21
22
EE 018
EARTHING AND EARTH ELECTRODE RESISTANCE
TEST 1
SOLUTION:
1. To hold the voltage at any desired point in a circuit below a specified value to earth.
2. It is influenced by chemical, biological and weather changes.
3.
65 V
__
23
8. Because of contamination of the surface by dust and condensed water and also
because of the acids and salts in the surrounding atmosphere.
9. Through the use of DC voltage as a measuring voltage all of the capacitive influence
(b) can be eliminated. If the measuring voltage is at least as large as the alternating
voltage during normal operation, then (c) is eliminated.
10. An earth leakage indicator is built in.
The simplest system is to measure the three conductor voltages to earth in the circuit.
24
EE 018
EARTHING AND EARTH ELECTRODE RESISTANCE
TEST 2
SOLUTION:
3.
25
5.
26
27
KEY TO EVALUATION
PER CENT
MARK
88 100
75 87
62 74
50 61
0 49
28