1MRS757058 D
Contents
1. Description.....................................................................3
2. Standard configurations.................................................3
3. Protection functions........................................................6
4. Application.....................................................................8
6. Control.........................................................................12
7. Measurement...............................................................12
8. Disturbance recorder....................................................13
9. Event log......................................................................13
25. Tools...........................................................................49
27. References..................................................................53
13. Self-supervision...........................................................13
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
Copyright 2012 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
ABB
1. Description
The voltage protection and control IED, REU615
is available in two standard configurations,
denoted A and B. Configuration A is preadapted
for voltage and frequency-based protection
schemes in utility and industrial power systems
and distribution systems including networks with
distributed power generation. The B configuration
is designed for automatic voltage regulation of
power transformers equipped with an on-load tapchanger. Both configurations also feature
additional CB control, measuring and supervising
functions. REU615 is a member of ABBs Relion
product family and part of its 615 protection and
control product series. The 615 series IEDs are
characterized by their compactness and
withdrawableunit design.
Re-engineered from the ground up, the 615 series
has been designed to unleash the full potential of
the IEC 61850 standard for communication and
interoperability between substation automation
devices. Once the standard configuration IED has
1MRS757058 D
Issued: 2011-05-09
Revision: D
been given the application-specific settings, it can
directly be put into service.
The 615 series IEDs support a range of
communication protocols including IEC 61850
with GOOSE messaging, IEC 60870-5-103,
Modbus and DNP3.
2. Standard configurations
REU615 is available in two standard
configurations. The standard signal configuration
can be altered by means of the graphical signal
matrix or the graphical application functionality of
the Protection and Control IED Manager PCM600.
Further, the application configuration functionality
of PCM600 supports the creation of multi-layer
logic functions using various logical elements,
including timers and flip-flops. By combining
protection functions with logic function blocks,
the IED configuration can be adapted to userspecific application requirements.
ABB
Std.conf.
Voltage and frequency based protection and measurement functions, synchrocheck and load shedding
1MRS757058 D
2)
2)
2)
Three-phase thermal overload protection for power transformers, two time constants
o3)
o3)
o3)
o5)
o5)
o5)
o5)
o5)
Protection1)
ABB
1MRS757058 D
o5)
5)
5)
5)
5)
5)
5)
5)
5)
5)
5)
5)
5)
5)
5)
5)
Disturbance recorder
Control
Circuit-breaker control
Condition Monitoring
Measurement
ABB
1MRS757058 D
RTD/mA measurement
Frequency measurement
The instances of a protection function represent the number of identical function blocks available in a standard configuration. By setting the
application specific parameters of an instance, a protection function stage can be established.
U 0 selectable by parameter, U 0 measured as default.
3)
4)
5)
Light only.
Multi-purpose protection is used for, for example, RTD/mA based protection.
Available in IED and SMT but not connected to anything in logic.
3. Protection functions
Standard configuration A
Standard configuration A is intended for busbar
voltage supervision, load shedding
(disconnection) and restoration (reconnection)
applications. It is also used for overfrequency and
underfrequency protection of power generators
and for other AC equipment, e.g. capacitor
banks, requiring three-phase overvoltage
protection, three-phase undervoltage protection,
residual overvoltage protection, positive phase
sequence undervoltage protection, negative
phase sequence overvoltage protection and
frequency supervision.
The integrated load shedding and restoration
functionality offers five instances for
disconnection and reconnection of less-important
loads in network overload situations. The five
instances enable the connected feeders to be
more thoroughly prioritized and grouped thus
facilitating the securing of critical applications.
If the restoration process is coordinated by an
automation system or process control system, the
IEDs load shedding and restoration function can
send a signal to the system when the
prerequisites for network restoration are fulfilled.
Enhanced with optional hardware and software,
standard configuration A also features three light
detection channels for arc fault detection in the
metering cubicle or busbar compartment of metalenclosed switchgear. The arc-fault detection
sensor interface is available on the optional
communication module.
1MRS757058 D
GUID-5E258DF3-B410-4FEE-9925-A8FC9C3617CE V2 EN
Figure 1.
ABB
1MRS757058 D
GUID-DCA293F5-58D2-4CE8-9602-842A6498F9ED V2 EN
Figure 2.
4. Application
Standard configuration A
The A configuration of REU615 is intended to be
used in medium voltage switchgear, supplied with
a dedicated voltage measurement cubicle. The A
configuration of REU615 provides busbar
overvoltage and undervoltage supervision,
network residual overvoltage supervision and
frequency supervision. REU615 offers the
functionality needed to provide load shedding or
generation rejection to enhance network stability.
In generator and motor applications REU615
provides supplementary protection by detecting
any deviation from the permitted frequency and
voltage values. An integrated synchro-check
function ensures a synchronized connection of
the equipment into the network. In distribution
ABB
1MRS757058 D
GUID-CA7B4D3E-1269-450F-A061-5A404FF52455 V2 EN
Figure 3.
ABB
Busbar protection and supervision using REU615 with the standard configuration A. The arc protection
schemes of REU615 and REF615 are employed for busbar protection for the voltage measurement bay
and related parts of the busbar. Apart from the busbar protection and supervision the REU615 IED is
utilized for centralized load shedding (disconnection) and restoration (reconnection) of one of the
outgoing feeders. The synchro-check and energizing check functions incorporated in REU615 are
employed for ensuring a safe connection of the outgoing feeder, including distributed generation, to the
network.
1MRS757058 D
GUID-A90B4035-68B9-4264-83C5-DD791DDEDAB0 V2 EN
Figure 4.
Tap changer control and power transformer thermal overload protection using REU615 with the
standard configuration B. The tap changer position information is received as a mA-signal from the tap
changer operation mechanism. The position value is sent to the transformer differential protection
function of the RET615 IED using GOOSE messaging. Further, the analog GOOSE messaging enables
the tap changer control of the two parallel running power transformers. The RTD inputs complement the
thermal overload protection by measuring the oil and ambient temperature of the power transformer.
10
ABB
1MRS757058 D
Version
3.5 or later
System 800xA
GUID-66EB52A0-21A1-4D1F-A1EF-61060B371384 V3 EN
Figure 5.
ABB
Utility power distribution network example using 615 series IEDs, Grid Automation controller COM600
and MicroSCADA Pro
11
1MRS757058 D
GUID-6984D893-45D5-427A-BABF-F1E1015C18E2 V3 EN
Figure 6.
Industrial power system example using 615 series IEDs, Grid Automation controller COM600 and
System 800xA
6. Control
The IED offers control of one circuit breaker with
dedicated push-buttons for circuit breaker
opening and closing. Further, the optional large
graphical LCD of the IEDs HMI includes a singleline diagram (SLD) with position indication for the
relevant circuit breaker. Interlocking schemes
required by the application are configured using
the signal matrix or the application configuration
feature of PCM600.
Standard configuration A incorporates a synchrocheck function to ensure that the voltage, phase
angle and frequency on either side of an open
circuit breaker satisfy the conditions for safe
interconnection of two networks. Standard
configuration B includes functionality for
controlling the voltage on the load side of the
power transformer. Based on the measured
values the IED sends control commands to the
tap changer thus enabling automatic voltage
regulation.
7. Measurement
The offered measurement functions depend on
the chosen standard configuration. Standard
configuration A offers phase voltage, residual
12
ABB
ABB
1MRS757058 D
13
1MRS757058 D
The phase-current input 1 A or 5 A, the residualcurrent input 1 A or 5 A, and the rated voltage of
the residual voltage input are selected in the IED
software. In addition, the binary input thresholds
18176 V DC are selected by adjusting the IEDs
parameter settings.
All binary inputs and outputs contacts are freely
configurable with the signal matrix or application
configuration functionality of PCM600.
1)
2)
3)
14
Analog inputs
Binary inputs/outputs
CT
VT
RTD inputs
mA inputs
BI
BO
12
10
B1)
62)
22)
8 (14)3)
10 (13)3)
The optional I/O module and the optional RTD/mA modules are mutually exclusive
Optional
With optional binary I/O module ( )
ABB
1MRS757058 D
1MRS757058 D
connections are supported. Termination and pullup/down resistors can be configured with jumpers
on the communication card so external resistors
are not needed.
Ethernet-based:
SNTP (Simple Network Time Protocol)
Client A
Client B
Network
Network
RED615
REF615
RET615
REU615
REM615
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V3 EN
Figure 7.
16
ABB
1MRS757058 D
Ethernet
Serial
100BASE-TX RJ-45
100BASE-FX LC
RS-232/RS-485
Fibre-optic ST
IEC 61850
MODBUS RTU/ASCII
MODBUS TCP/IP
DNP3 (serial)
DNP3 TCP/IP
IEC 60870-5-103
= Supported
ABB
17
1MRS757058 D
Value
Width
frame
177 mm
case
164 mm
frame
177 mm (4U)
case
160 mm
Height
Depth
Weight
4.1 kg
2.1 kg
Type 1
Type 2
Uauxnominal
50 ms at Unrated
Uauxvariation
condition
Ripple in the DC auxiliary voltage
Fuse type
T4A/250 V
18
ABB
1MRS757058 D
Value
Rated frequency
50/60 Hz 5 Hz
Current inputs
Rated current, In
1/5 A1)
Thermal withstand
capability:
Continuously
20 A
For 1 s
500 A
Voltage inputs
Half-wave value
1250 A
Input impedance
<20 m
Rated voltage
60...210 V AC
Voltage withstand:
1)
Continuous
240 V AC
For 10 s
360 V AC
<0.05 VA
ABB
Description
Value
Operating range
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
18...176 V DC
Reaction time
3 ms
19
1MRS757058 D
mA inputs
Value
Supported RTD
sensors
100 platinum
250 platinum
100 nickel
120 nickel
250 nickel
10 copper
Supported resistance
range
0...2 k
Maximum lead
resistance (threewire measurement)
25 per lead
Isolation
Response time
<4 s
RTD/resistance
sensing current
Operation accuracy
Resistance
Temperature
2.0% or 1
1C
10 copper: 2C
Supported current
range
020 mA
Current input
impedance
44 0.1%
Operation accuracy
0.5% or 0.01 mA
Value
Rated voltage
250 V AC/DC
5A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
20
ABB
1MRS757058 D
Value
Rated voltage
250 V AC/DC
5A
10 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
ABB
Ethernet interface
Protocol
Cable
Front
TCP/IP protocol
10 MBits/s
21
1MRS757058 D
Fibre type1)
Wave length
Max. distance
LC
MM 62.5/125 or 50/125
m glass fibre core
1300 nm
2 km
<8 dB
ST
MM 62.5/125 or 50/125
m glass fibre core
820-900 nm
1 km
<11 dB
1)
2)
Value
B004, B0051)
Isolation
500V 1 min.
Modulation
Unmodulated
Logic level
TTL Level
Current consumption
2...4 mA
Power consumption
10...20 mW
1)
Table 18. Lens sensor and optical fibre for arc protection
Description
Value
-40...+100C
+140C
100 mm
Value
Front side
IP 54
IP 20
Value
-25...+55C (continuous)
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
Up to 2000 m
-40...+85C
22
ABB
1MRS757058 D
Reference
96 h at +55C
16 h at +85C1)
IEC 60068-2-2
96 h at -25C
16 h at -40C
IEC 60068-2-1
IEC 60068-2-30
5 cycles (3 h + 3 h)
at -25C...+55C
IEC60068-2-14
Storage test
96 h at -40C
96 h at +85C
IEC 60068-2-1
IEC 60068-2-2
1)
ABB
For IEDs with an LC communication interface the maximum operating temperature is +70 o C
23
1MRS757058 D
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
Common mode
2.5 kV
Differential mode
2.5 kV
Reference
IEC 61000-4-18
IEC 60255-22-1, class III
2.5 kV
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
Contact discharge
8 kV
Air discharge
15 kV
IEC 61000-4-6
IEC 60255-22-6, class III
10 V/m (rms)
f=80...2700 MHz
IEC 61000-4-3
IEC 60255-22-3, class III
10 V/m
f=900 MHz
ENV 50204
IEC 60255-22-3, class III
20 V/m (rms)
f=80...1000 MHz
IEEE C37.90.2-2004
All ports
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
4 kV
IEC 61000-4-5
IEC 60255-22-5
Communication
1 kV, line-to-earth
Other ports
4 kV, line-to-earth
2 kV, line-to-line
IEC 61000-4-8
Continuous
1...3 s
300 A/m
1000 A/m
1000 A/m
6.4/16 s
IEC 61000-4-10
2s
100 A/m
1 MHz
400 transients/s
24
IEC 61000-4-9
ABB
1MRS757058 D
Reference
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
IEC 61000-4-16
IEC 60255-22-7, class A
Differential mode
300 V rms
150 V rms
Conducted common mode
disturbances:
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
Emission tests:
IEC 61000-4-16
EN 55011, class A
IEC 60255-25
Conducted
0.15-0.50 MHz
0.5-30 MHz
Radiated
30-230 MHz
230-1000 MHz
Reference
Dielectric tests
>100 M, 500 V DC
<0.1 , 4 A, 60 s
IEC 60255-27
ABB
Description
Reference
Requirement
Class 2
Class 2
Seismic test
IEC 60255-21-3
Class 2
25
1MRS757058 D
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2005)
EN 60255-1 (2009)
Reference
EMC directive
2004/108/EC
Standard
EN 50263 (2000)
EN 60255-26 (2007)
26
ABB
1MRS757058 D
Protection functions
Table 28. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Value
Operation accuracy
PHHPTOC
and
PHIPTOC
Typical
Maximum
16 ms
19 ms
23 ms
11 ms
12 ms
14 ms
22 ms
24 ms
25 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
2)
3)
ABB
Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0
x In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Includes the delay of the signal output contact
Includes the delay of the heavy-duty output contact
27
1MRS757058 D
Function
Value (Range)
Step
Start Value
PHLPTOC
0.05...5.00 x In
0.01
PHHPTOC
0.10...40.00 x In
0.01
PHIPTOC
1.00...40.00 x In
0.01
PHLPTOC
0.05...15.00
0.01
PHHPTOC
0.05...15.00
0.01
PHLPTOC
40...200000 ms
10
PHHPTOC
40...200000 ms
10
PHIPTOC
20...200000 ms
10
PHLPTOC
PHHPTOC
PHIPTOC
Definite time
Time multiplier
1)
Value
Operation accuracy
Start time1)2)
UFault = 1.1 x set Start value
Minimum
Typical
Maximum
22 ms
24 ms
26 ms
Reset time
< 40 ms
Reset ratio
Retardation time
< 35 ms
Suppression of harmonics
1)
2)
3)
28
Start value = 1.0 x Un, Voltage before fault = 0.9 x U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random
phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 1.20 x U n, Start value multiples in range of 1.10 to 2.00
ABB
1MRS757058 D
Function
Value (Range)
Step
Start value
PHPTOV
0.05...1.60 x Un
0.01
Time multiplier
PHPTOV
0.05...15.00
0.01
PHPTOV
40...300000 ms
10
PHPTOV
1)
Value
Operation accuracy
Start time1)2)
UFault = 0.9 x set Start value
Minimum
Typical
Maximum
62 ms
64 ms
66 ms
Reset time
< 40 ms
Reset ratio
Retardation time
< 35 ms
Suppression of harmonics
1)
2)
3)
Start value = 1.0 x Un, Voltage before fault = 1.1 x U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random
phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Minimum Start value = 0.50, Start value multiples in range of 0.90 to 0.20
Function
Value (Range)
Step
Start value
PHPTUV
0.05...1.20 x Un
0.01
Time multiplier
PHPTUV
0.05...15.00
0.01
PHPTUV
60...300000 ms
10
PHPTUV
1)
ABB
29
1MRS757058 D
Value
Operation accuracy
Start time1)2)
Minimum
Typical
Maximum
51 ms
43 ms
53 ms
45 ms
54 ms
46 ms
< 40 ms
Reset ratio
Retardation time
< 35 ms
Suppression of harmonics
1)
2)
Start value = 1.0 x Un, Positive sequence voltage before fault = 1.1 x U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Function
Value (Range)
Step
Start value
PSPTUV
0.010...1.200 x Un
0.001
PSPTUV
40...120000 ms
10
PSPTUV
0.01...1.0 x Un
0.01
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set Start value
UFault = 2.0 set Start value
Minimum
Typical
Maximum
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1)
Negative-sequence voltage before fault = 0.0 U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase
2)
30
ABB
1MRS757058 D
Function
Value (Range)
Step
Start value
NSPTOV
0.010...1.000 x Un
0.001
NSPTOV
40...120000 ms
Value
Operation accuracy
Start time
f>/f<
10 mHz
df/dt
f>/f<
< 80 ms
df/dt
< 120 ms
Reset time
< 150 ms
ABB
Parameter
Values (Range)
Unit
Operation mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
0.900...1.200
xFn
0.800...1.100
Step
Default
Description
1=Freq<
Frequency protection
operation mode
selection
0.001
1.050
Frequency start
value overfrequency
xFn
0.001
0.950
Frequency start
value underfrequency
-0.200...0.200
xFn /s
0.005
0.010
Frequency start
value rate of change
Operate Tm Freq
80...200000
ms
10
200
Operate Tm df/dt
120...200000
ms
10
400
31
1MRS757058 D
Value
Operation accuracy
Table 41. Thermal overload for protection, two time constants (T2PTTR) main settings
Parameter
Function
Value (Range)
Step
Temperature rise
T2PTTR
0.0...200.0oC
0.1
Max temperature
T2PTTR
0.0...200.0oC
0.1
Operate temperature
T2PTTR
80.0...120.0 %
0.1
Weighting factor p
T2PTTR
0.00...1.00
0.01
T2PTTR
6...60000 s
Current reference
T2PTTR
0.05...4.00 x In
0.01
Operation
T2PTTR
Off
On
Value
Operation accuracy
Start time1)2)
UFault = 1.1 x set Start value
Minimum
Typical
Maximum
55 ms
56 ms
58 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1)
Residual voltage before fault = 0.0 x U n , f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on
2)
32
ABB
1MRS757058 D
Function
Value (Range)
Step
Start value
ROVPTOV
0.010...1.000 x Un
0.001
ROVPTOV
40...300000 ms
Value
Operation accuracy
Operate time
Minimum
Typical
Maximum
9 ms
10 ms
12 ms
< 40 ms
Reset time
Reset ratio
Typical 0.96
Function
Value (Range)
Step
ARCSARC
0.50...40.00 x In
0.01
ARCSARC
0.05...8.00 x In
0.01
Operation mode
ARCSARC
2=Light only
3=BI controlled
Value
Operation accuracy
ABB
Parameter
Function
Value (Range)
Step
Start value
MAPGAPC
-10000.0...10000.0
0.1
MAPGAPC
0...200000 ms
100
Operation mode
MAPGAPC
Over
Under
33
1MRS757058 D
Value
Operation accuracy
f<
10 mHz
df/dt
f<
< 80 ms
df/dt
< 120 ms
Reset time
< 150 ms
Function
Value (Range)
Step
LSHDPFRQ
Freq<
Freq< AND df/dt
Freq< OR df/dt
Restore mode
LSHDPFRQ
Disabled
Auto
Manual
LSHDPFRQ
0.800...1.200 x Fn
0.001
LSHDPFRQ
-0.200...-0.005 x Fn
0.005
Operate Tm Freq
LSHDPFRQ
80...200000 ms
10
Operate Tm df/dt
LSHDPFRQ
120...200000 ms
10
LSHDPFRQ
0.800...1.200 x Fn
0.001
LSHDPFRQ
80...200000 ms
10
34
ABB
1MRS757058 D
ABB
Parameter
Values (Range)
35
1MRS757058 D
Control functions
Table 51. Synchrocheck (SECRSYN)
Characteristic
Value
Operation accuracy
Reset time
< 50 ms
Reset ratio
Typical 0.96
36
ABB
1MRS757058 D
ABB
Parameter
Values (Range)
Unit
-1=Off
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live
Difference voltage
0.01...0.50
xUn
Difference
frequency
0.001...0.100
Difference angle
5...90
Synchrocheck
mode
Step
Default
Description
1=Both Dead
Energizing check
mode
0.01
0.05
Maximum voltage
difference limit
xFn
0.001
0.001
Maximum
frequency
difference limit
deg
Maximum angle
difference limit
1=Off
2=Synchronous
3=Asynchronous
2=Synchronous
Synchrocheck
operation mode
Control mode
1=Continuous
2=Command
1=Continuous
Selection of the
synchrocheck
command or
continuous
control mode
0.1...0.8
xUn
0.1
0.2
Voltage low-limit
line for energizing
check
0.2...1.0
xUn
0.1
0.5
Voltage high-limit
line for energizing
check
Close pulse
200...60000
ms
10
200
Breaker-closing
pulse duration
Max energizing V
0.50...1.15
xUn
0.01
1.05
Maximum voltage
for energizing
Phase shift
-180...180
deg
180
Correction of
phase difference
between
measured
U_BUS and
U_LINE
0...60000
ms
10
Minimum time to
accept
synchronizing
37
1MRS757058 D
Table 52. Synchronism and energizing check (SECRSYN) main settings, continued
Parameter
Values (Range)
Unit
Step
Default
Description
Maximum Syn
time
100...6000000
ms
10
2000
Maximum time to
accept
synchronizing
Energizing time
100...60000
ms
10
100
Closing time of CB
40...250
ms
10
60
Closing time of
the breaker
Value
Operation accuracy1)
1)
2)
38
ABB
1MRS757058 D
Table 54. On-load tap changer control with voltage regulator (OLATCC) main settings
ABB
Parameter
Function
Value (Range)
Step
OLATCC
0.000...2.000 x Un
0.001
OLATCC
1000...300000 ms
100
OLATCC
1000...300000 ms
100
OLATCC
0.0...25.0 %
0.1
OLATCC
0.0...25.0 %
0.1
OLATCC
-89...89 deg
Stability factor
OLATCC
0.0...70.0 %
0.1
OLATCC
Auto master
Auto follower
NRP
MCC
Operation mode
OLATCC
Manual
Auto single
Auto parallel
Input control
Delay characteristics
OLATCC
Inverse time
Definite time
OLATCC
500...10000 ms
100
OLATCC
1.20...18.00 % Un
0.01
OLATCC
1=Custom disabled
2=OC
3=UV
4=OC, UV
5=EXT
6=OC, EXT
7=UV, EXT
8=OC, UV, EXT
OLATCC
0.10...5.00 x In
0.01
OLATCC
0.10...1.20 x Un
0.01
OLATCC
0.80...2.40 x In
0.01
OLATCC
0.10...5.00 x In
0.01
OLATCC
-36...36
OLATCC
-36...36
LDC limit
OLATCC
0.00...2.00 x Un
0.01
LDC enable
OLATCC
False
True
OLATTC
6...20 s
39
1MRS757058 D
Measurement functions
Table 55. Three-phase current measurement (CMMXU)
Characteristic
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
40
ABB
1MRS757058 D
Value
Operation accuracy
Suppression of harmonics
mA inputs
Value
Supported RTD
sensors
100 platinum
250 platinum
100 nickel
120 nickel
250 nickel
10 copper
Supported resistance
range
0...2 k
Maximum lead
resistance (threewire measurement)
25 per lead
Isolation
Response time
<4 s
RTD/resistance
sensing current
Operation accuracy
Resistance
Temperature
2.0% or 1
1C
10 copper: 2C
Supported current
range
020 mA
Current input
impedance
44 0.1%
Operation accuracy
0.5% or 0.01 mA
ABB
Characteristic
Value
Operation accuracy
10 mHz
(in measurement range 35 - 75 Hz)
41
1MRS757058 D
Supervision functions
Table 62. Current circuit supervision (CCRDIF)
Characteristic
Value
Operate time1)
< 30 ms
1)
Values (Range)
Unit
Description
Start value
0.05...0.20
x In
1.00...5.00
x In
Value
Operate time1)
NPS function
< 33 ms
voltage Lev
UFault = 5.0 x set Neg Seq
< 18 ms
voltage Lev
Delta function
< 30 ms
< 24 ms
change rate
change rate
1)
Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
42
ABB
1MRS757058 D
IECA070904 V3 EN
Figure 8.
IECA070901 V3 EN
Small display
Figure 9.
Large display
20
8 or more
1)
ABB
43
1MRS757058 D
Character size1)
10
20
8 or more
1)
Mounting methods:
Flush mounting
Semi-flush mounting
Semi-flush mounting in a 25 tilt
Rack mounting
Wall mounting
Mounting to a 19" equipment frame
Mounting with a RTXP 18 test switch to a
19" rack
190
6
18
164
177
177
230
177
160
160
25
107
1 53
48
IECA070900 V4 EN
Figure 10.
44
98
103
IECA070902 V4 EN
IECA070903 V4 EN
Flush mounting
Figure 11.
133
Figure 12.
Semi-flush mounting
Semi-flush with a 25
tilt
ABB
1MRS757058 D
Description
IED
615 series IED (including case)
615 series IED (including case) with test switch, wired and in
stalled in a 19 equipment panel
H
-
615 series IED (including case) with test switch, wired and in stalled in a mounting bracket for CombiFlex rack mounting (RGHT
19 4U variant C)
2
Standard
Main application
IEC
K
L
GUID-AD8D5903-41C6-4187-A02A-1F5C3407E335 V2 EN
The standard configuration determines the I/O hardware and available options.
The example below shows standard configuration B with chosen options.
#
4-8
HBU BCCAH
NBA1ABN1XE
Description
Standard configurations, analog and binary I/O options
Standard configuration descriptions in short:
A = Voltage and frequency based protection and measurement functions,
synchro-check, load shedding and CB control
B = Automatic voltage regulator, CB control and with the optional I/O module
control of one network object
Std. conf.
I/O options
5U + 12 BI + 10 BO
AEAAD
4I (Io 1/5 A) + 3U + 8 BI + 10 BO
BCAAH
4I (Io 1/5 A) + 3U + 14 BI + 13 BO
BCABB*
BCCAH
ABB
45
1MRS757058 D
The communication module hardware determines the available communication proto cols. Choose the hardware from one of the rows below to define the digits # 9-10.
#
Description
9
10
AA
AB
AN
Serial glass fibre (ST), incl. an RS-485 connector and an input for
IRIG-B (cannot be combined with arc protection)
BN
BB
BD
BC
BE
NA
NB
NC
ND
NE
No communication module
NN
HBUBCCAH
BC C1BBN1XE
If serial communication is chosen, please choose a serial communication module including Ethernet (for example BC) if a service
bus for PCM600 or the WebHMI is required.
GUID-A54E91E4-EB6B-45BD-9BC7-DA4EE4295CAF V2 EN
HBUBCCAHBC
#
Description
11
Communication protocols
IEC 61850
(for Ethernet communication modules and IEDs without a com munication module )
Modbus
(for Ethernet/serial or Ethernet + serial communication modules)
IEC 60870-5-103
(for serial or Ethernet + serial communication modules)
DNP3
(for Ethernet/serial or Ethernet + serial communication modules)
C 1BBN1XE
GUID-5B4CE02E-BA34-4AA7-A6E6-8408A3C1763D V2 EN
46
ABB
1MRS757058 D
HBU BCCAHBCC
#
Description
12
Language
13
14
15
English
Front panel
Small LCD
Option 1
Arc protection (only for std conf A, requires a communication
module, cannot be combined with communication modules BN
or BB)
None
Option 2
None
16
17
18
1 B B N 1 XE
Power supply
48...250 V DC, 100...240 V AC
24...60 V DC
Version
Version 4.0
XE
GUID-AC8BE0B1-072C-4907-92D3-3720E344F94E V2 EN
Example code:
HBUBCCAHBCC1BBN1XE
10 11 12 13 14 15 16 17 18
Code
GUID-28A75E3D-BF45-42F0-90D8-B142E3EA28F3 V2 EN
Figure 13.
ABB
47
1MRS757058 D
Order number
1MRS120534-1.5
1MRS120534-3.0
1MRS120534-5.0
Order number
1MRS050696
1MRS050697
1MRS050831
1MRS050694
1MRS050695
Mounting bracket for one IED with test switch RTXP in 4U Combiflex (RHGT 19 variant C)
2RCA022642P0001
2RCA022643P0001
19 rack mounting kit for one IED and one RTXP18 test switch (the test switch is not
included in the delivery)
2RCA021952A0003
19 rack mounting kit for one IED and one RTXP24 test switch (the test switch is not
included in the delivery)
2RCA022561A0003
Replacement kit for a Strmberg SP_J40 series relay (cut-out in the center of the
installation plate)
2RCA027871A0001
Replacement kit for a Strmberg SP_J40 series relay (cut-out on the left or the right of
the installation plate)
2RCA027874A0001
2RCA027880A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (one cut-out)
2RCA027894A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (two cut-outs)
2RCA027897A0001
2RCA027881A0001
2RCA027882A0001
2RCA027885A0001
48
ABB
1MRS757058 D
25. Tools
The IED is delivered as a pre-configured unit. The
default parameter setting values can be changed
from the front-panel user interface, the webbrowser based user interface (WebHMI) or the
PCM600 tool in combination with the IED-specific
connectivity package.
ABB
Version
2.4 SP1 or later
IE 7.0, IE 8.0 or IE 9.0
4.0 or later
49
1MRS757058 D
WebHMI
PCM600 Basic/
Engineering
PCM600 Engineering
Pro
Signal monitoring
Modbus communication
configuration (communication
management)
Application configuration
Event viewing
= Supported
50
ABB
1MRS757058 D
GUID-B89BFFF3-08F0-40D3-8F12-99FB21B3900F V1 EN
Figure 14.
ABB
51
1MRS757058 D
GUID-E5FA44B9-524F-4B19-A002-49D39DF6D6D5 V1 EN
Figure 15.
52
ABB
1MRS757058 D
27. References
The www.abb.com/substationautomation portal
offers you information about the distribution
automation product and service range.
GUID-2ECAAEFE-CEF1-4A31-97F4-B88FCF66DB8E V1 EN
Figure 16.
ABB
Product page
53
1MRS757058 D
IEC 61850
IEC 60617
IEC-ANSI
PHLPTOC1
3I> (1)
51P-1 (1)
PHHPTOC1
3I>> (1)
51P-2 (1)
PHIPTOC1
3I>>> (1)
50P/51P (1)
ROVPTOV1
Uo> (1)
59G (1)
ROVPTOV2
Uo> (2)
59G (2)
ROVPTOV3
Uo> (3)
59G (3)
PHPTUV1
3U< (1)
27 (1)
PHPTUV2
3U< (2)
27 (2)
PHPTUV3
3U< (3)
27 (3)
PHPTOV1
3U> (1)
59 (1)
PHPTOV2
3U> (2)
59 (2)
PHPTOV3
3U> (3)
59 (3)
PSPTUV1
U1< (1)
47U+ (1)
PSPTUV2
U1< (2)
47U+ (2)
NSPTOV1
U2> (1)
47O- (1)
NSPTOV2
U2> (2)
47O- (2)
FRPFRQ1
f>/f<,df/dt (1)
81 (1)
FRPFRQ2
f>/f<,df/dt (2)
81 (2)
FRPFRQ3
f>/f<,df/dt (3)
81 (3)
FRPFRQ4
f>/f<,df/dt (4)
81 (4)
FRPFRQ5
f>/f<,df/dt (5)
81 (5)
FRPFRQ6
f>/f<,df/dt (6)
81 (6)
T2PTTR1
3Ith>T
49T
Master trip
TRPPTRC1
94/86 (1)
TRPPTRC2
94/86 (2)
ARCSARC1
ARC (1)
50L/50NL (1)
ARCSARC2
ARC (2)
50L/50NL (2)
ARCSARC3
ARC (3)
50L/50NL (3)
Protection
Frequency protection
Arc protection
54
ABB
1MRS757058 D
IEC 61850
IEC 60617
IEC-ANSI
Multi-purpose protection
MAPGAPC1
MAP (1)
MAP (1)
MAPGAPC2
MAP (2)
MAP (2)
MAPGAPC3
MAP (3)
MAP (3)
MAPGAPC4
MAP (4)
MAP (4)
MAPGAPC5
MAP (5)
MAP (5)
MAPGAPC6
MAP (6)
MAP (6)
LSHDPFRQ1
UFLS/R (1)
81LSH (1)
LSHDPFRQ2
UFLS/R (2)
81LSH (2)
LSHDPFRQ3
UFLS/R (3)
81LSH (3)
LSHDPFRQ4
UFLS/R (4)
81LSH (4)
LSHDPFRQ5
UFLS/R (5)
81LSH (5)
Circuit-breaker control
CBXCBR1
I <-> O CB
I <-> O CB
Disconnector control
DCXSWI1
DCXSWI2
ESXSWI1
I <-> O ESC
I <-> O ESC
DCSXSWI1
I <-> O DC (1)
I <-> O DC (1)
DCSXSWI2
I <-> O DC (2)
I <-> O DC (2)
DCSXSWI3
I <-> O DC (3)
I <-> O DC (3)
ESSXSWI1
I <-> O ES (1)
I <-> O ES (1)
ESSXSWI2
I <-> O ES (2)
I <-> O ES (2)
TPOSSLTC1
TPOSM
84M
OLATCC1
COLTC
90V
SECRSYN1
SYNC
25
TCSSCBR1
TCS (1)
TCM (1)
TCSSCBR2
TCS (2)
TCM (2)
CCRDIF1
MCS 3I
MCS 3I
SEQRFUF1
FUSEF
60
Disturbance recorder
RDRE1
CMMXU1
3I
3I
CSMSQI1
I1, I2, I0
I1, I2, I0
VMMXU1
3U
3U
Control
Condition monitoring
Trip circuit supervision
Measurement
ABB
55
1MRS757058 D
IEC 61850
IEC 60617
IEC-ANSI
RESVMMXU1
Uo
Vn
VSMSQI1
U1, U2, U0
U1, U2, U0
PEMMXU1
P, E
P, E
RTD/mA measurement
XRGGIO130
X130 (RTD)
X130 (RTD)
Frequency measurement
FMMXU1
Product version
History
A/2010-06-11
3.0
First release
B/2010-06-29
3.0
Terminology updated
C/2010-09-07
3.0
Content updated
D/2012-05-11
4.0
56
ABB
57
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
Fax
+358 10 22 41094
www.abb.com/substationautomation
Contact us