OPERATION MANUAL FOR PUMP STARTER PANEL

1. PANEL COMPOSITION

NO.2
COMPRESSOR

NO.1
COMPRESSOR

NAME PLATE
NO.

DESCRIPTION

NP

PUMP STARTER PANEL (LCP-435-001)

NP1

NO.1 CHILLED WATER PANEL (PA-95001)

NP2

NO.2 CHILLED WATER PANEL (PA-95002)

NP3

POWER

NP4

RUN

NP5

OVERLOAD

NP6

HEATER

NP7

PUMP START

NP8

PUMP STOP

NP9

HEATER OFF-ON

NP10

LOCAL REMOTE

NP11

AMMETER

NP12

HOUR METER

2. OPERATION DESCRIPTION
2.1 LOCAL MODE
a. Before operating Pump Starter Panel in local mode, select the position OFF on the selector switch
(NP9) Space Heater and check the panel status as below:
(Refer to the Table 1)
<Table 1>

NAME
PLATE NO.

DESCRIPTION

NP3
NP5
NP6

POWER
OVERLOAD
HEATER

LAMP STATUS LAMP COLOR


ON
OFF
OFF

WHITE
RED
ORANGE

b. Select the position "LOCAL" (local mode) on the selector switch (NP10) of the control mode for pump.
c. Press the PUMP START push button (NP7) which enables to start the chilled water pump, check if the
corresponding lamp (NP4) is on.
(Refer to the Table 2)
<Table 2>

NAME
PLATE NO.

DESCRIPTION

NP4

RUN

LAMP STATUS LAMP COLOR


ON

GREEN

e. During the operation, if a problem exists like overloading, the pump will stop automatically and the
corresponding alarm lamp will be turned on as below:
(Refer to the Table 3)
<Table 3>

NAME
PLATE NO.

DESCRIPTION

NP5

OVERLOAD

LAMP STATUS LAMP COLOR


ON

RED

f. If you want to manually stop the chilled water pump, press the PUMP STOP push button (NP8), check
the corresponding lamp (NP4) is off:
(Refer to the Table 4)
<Table 4>

NAME
PLATE NO.

DESCRIPTION

NP4

RUN

if

LAMP STATUS LAMP COLOR


OFF

GREEN

g. When the operation stops, select the position ON on the selector switch (NP9) Heater and check the
panel status as below:
(Refer to the Table 5)
<Table 5>

NAME
PLATE NO.

DESCRIPTION

NP6

HEATER

LAMP STATUS LAMP COLOR


ON

ORANGE

2.2 REMOTE MODE


a. Before operating Pump Starter Panel in remote mode, select the position OFF on the selector switch
(NP9) Heater and check the panel status as below:
(Refer to the table 1)
<Table 1>

NAME
PLATE NO.

DESCRIPTION

LAMP STATUS LAMP COLOR

NP3
NP5
NP6

POWER
OVERLOAD
HEATER

ON
OFF
OFF

WHITE
RED
ORANGE

b. Select the position "REMOTE" on the selector switch (NP10) of the control mode for pump.
c. After receiving the pump START order from the HVAC PANEL, the pump will start to run automatically,
check if the corresponding lamp (NP5) status is ON:
(Refer to the Table 2)
<Table 2>

NAME
PLATE NO.

DESCRIPTION

NP4

RUN

LAMP STATUS LAMP COLOR


ON

GREEN

e. During the operation, if a problem exists like overloading, the pump will stop and the corresponding alarm
lamp will be turned on as below:
(Refer to the Table 3)
<Table 3>

NAME
PLATE NO.

DESCRIPTION

NP5

OVERLOAD

LAMP STATUS LAMP COLOR


ON

RED

f. Once the HVAC Panel sends the STOP order the pump will stop running, check if the corresponding lamp
(NP4) is off:
(Refer to the Table 4)
<Table 4>

NAME
PLATE NO.

DESCRIPTION

NP4

RUN

LAMP STATUS LAMP COLOR


OFF

GREEN

g. When the operation stops, select the position ON on the selector switch (NP9) Heater and check the
panel status as below:
(Refer to the Table 5)
<Table 5>

NAME
PLATE NO.

DESCRIPTION

NP6

HEATER

LAMP STATUS LAMP COLOR


ON

ORANGE