Switchgear room defect list

Switchgear area
name:
AWR booster pump
house sub-station

Defect description

AWR sub-station

SWR sub-station

Sewage plant substation

All access doors should be replaced by fire


doors, the wooden doors are starting to rot
and the single door frame is rusting. (MMD
O/P)
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency. (Civil
Maintenance)
No flash suit signs on the doors. (EMD)
Fire extinguisher last inspected in August
2015 (Fire station)
The entire switchgear room needs to be
cleaned. (EMD)
There is no secondary exit available as a
steel bar has been welded across the double
doors in order to keep out burglars. This
poses significant danger to the operator,
should a breaker explode while inside the
Sub-Station the operator will have only one
way out. The 2 person rule must absolutely
be applied here when operating is being
done. (risk & assurance)
Fire extinguisher last inspected in August
2015 (Fire station)
2 lights inside the sub-station are defective.
(EMD)
There is no secondary exit available as
grating has been welded around the entire
Sub-Station in an attempt to keep out
burglars. This again poses significant danger
to the operator, should a breaker explode
while inside the Sub-Station the operator will
have only one way out. The 2 person rule
must absolutely be applied here when
operating is being done. (risk & assurance)
A sign needs to be placed on top of the door
naming the sub-station.
No flash suit signs or 11 Point plan on the
doors.
Door was found open and does not use an
A master to lock and unlock but a normal 2
or 3 lever lock & key. This key is in the
possession of the chemical services
supervisor.
The 380V incomer is not labeled, it should
indicate from where it is getting supplied
from.

Notificatio
n number

Access building
Switchgear room
(control room 2)

Security fence
switchgear room
(control room 1)

Station Diesel Gen


Sub-Station

Sub- Station South


(next to CW pump
house south)

Water treatment
plant Sub-Station no:
1 South

Door locking system should be changed to


allow self-locking and a quick release system
to exit the switchgear room in an emergency.
The sign placed on top of the door naming
the switchgear room should be changed
from Control room 2 to Access building
switchgear room
1 out of the 2 lights is o/c.
Special key is needed to open the switchgear
room and not an A master.
The sign placed on top of the door naming
the switchgear room should be changed
from Control room 1 to Security fence
switchgear room
Isolation procedure to be displayed on
panels.
Special key is needed to open the switchgear
room and not an A master.
2 blue (precip/induction) portable earths
found inside the switchgear room, MPCB 2 &
MPCB 7. Clamp indicate that these earths
are rated at 20kA/sec. this is not possible for
such thin earth leads. When last where they
tested?
Door locking system should be changed to
allow self-locking and a quick release system
to exit the switchgear room in an emergency
on all three doors.
1 light o/c at each Diesel Gen
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
The double doors was unlocked, the sliding
pin locking mechanism was locked in such a
way that the door could no close. (Please
Check EOD)
A large plate above the double door is
coming loos and could fall at any moment.
The old 380V CW Unit board 3A & 3B is still
standing inside the sub-station without
decommission stickers attached. Same
should be removed after confirming that
they are fully de-commissioned and
declassified.
Double door handle damaged.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
1 light o/c.

Water treatment
plant Sub-Station no:
2 South

Water treatment
plant UPS room South

Fire and first aid


switchgear room (at
the medical centre)

Workshop sub-station
no: 1 ( top floor at the
stores)
Workshop sub-station
no: 2

Welders & Platters


Workshop board.

Coal Staith 1 SubStation

Coal Staith 2 SubStation

Both the single & Double door locking


systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
1 light o/c.
A sign needs to be placed on top of the door
naming the room.
The 2 UPS chargers are not labeled.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency on the
double door.
A master door lock system with self-locking
but needs an A master key to exit, a quick
release system is needed to exit the
switchgear room in an emergency.
1 light o/c.
Circuit labeling on the board is problematic.
A sign needs to be placed on top of the door
naming the sub-station.
No flash suit signs or 11 Point plan on the
doors.
The sign on top of the door naming the substation should be changed from just
Workshop Sub-Station to Workshop SubStation no: 2.
The flash suit signs and 11 Point plan on the
door should be replaced.
There is no access control to this board as it
is standing in the middle of the welders &
platters workshop without any fencing or
walls around it, allowing anyone to operate
on this board and to approach it without the
correct flash suit. A fence should be built
around this board or it should be moved into
the Workshop sub-station no: 2 +/- 50
meters from where it is standing currently.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
The flash suit signs and 11 Point plan on the
door should be replaced with the newer
signs.
The Sub-Station floor is dirty. (EMD O/P)
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
The flash suit signs and 11 Point plan on the

Bulk fuel oil SubStation South

Sub- Station East

Bulk fuel oil SubNorth

Overland conveyor
Sub-Station 1

door should be replaced with the newer


signs.
4 out of the 5 light are o/c. (EMD O/P)
The Sub-Station floor is dirty. (EMD O/P)
A sign needs to be placed on top of the door
naming the sub-station.
No flash suit signs or 11 Point plan on the
doors. (EMD)
Secondary exit door needs a special key to
exit and not an A master.
The old wooden doors should be replaced by
fire doors (MMD O/P)
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
The 380V boards should be labeled correctly
i.e. 380V Bulk fuel oil plant board no: 1
South for Unit 1, 380V Bulk fuel oil plant
board no: 2 South for Unit 2 ..
The Sub-Station floor is dirty.
The Sub-Station is very hot inside, suspect
the air-conditioning plant is o/c.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
380V Sub-Station East board 1 to be labeled
as such i.e. the 1 is missing.
Fire extinguisher last inspected in February
2015.
The old wooden doors should be replaced by
fire doors
Both the single & Double door locking
systems should be changed to allow selflocking. The new locking system installed
can be altered to allow for the quick release
needed.
The Sub-Station floor is dirty, but people are
currently working in there for the
refurbishment of Unit 4.
Old A1 electrical diagram available still
displaying the old Eskom logo, which needs
to be replaced with a newer diagram. Frame
& Plexiglas still in a good condition
The secondary exit doors are locked with the
Mines lock on the outside thus not allowing
one to exit through that door.
The secondary exit is also situated in the
same side of the sub-station as the main
entrance, thus not allowing the operator to
flee in the opposite direction should

Water treatment
plant UPS room
North.

Water treatment
plant Sub-Station
North.

Slurry Plant SubStation.

Sub-Station North.

Canteen Sub-Station.

275kV Relay house

400kV Relay house


Sub-Station West

Station room 1

something go wrong.
Entering the sub-station you are immediately
facing the back of the 11kV Board. (11 Point
plan point no: 3 back access). Suggest a new
door to be built in on the south side of the
sub-station and the single door to be bricked
up shut. (risk & assurance or engineering)
4 light o/c.
The Sub-Station floor is dirty.
Door locks with a small Viro lock on a Hasp
Staple locking mechanism, of which only Ptm
has the key.
Fire extinguisher last serviced and inspected
in 2014.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
A sign needs to be placed on top of the door
naming the room.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
Single door still made of wood and needs to
be replaced with a fire door.
1 light o/c.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
The Sub-Station floor is dirty.
A sign needs to be placed on top of the door
naming the sub-station.
Fire extinguisher last serviced on March
2011 and inspected in September 2011.
7 Light o/c.
380V Boards are not labeled as where it is
getting supplied from.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
Fire extinguisher last inspected in February
2015.
The Sub-Station floor is dirty.
Light deficiency due to lights being installed
above the cable racks and cables blocking
any light from coming through.
The room floor is dirty.

Station room 2

Station room 3
Unit 1 DC switchgear
room.

Unit 1 MV Switchgear
room.

Unit 1 LV Switchgear
room.
Unit 2 DC switchgear
room.

Unit 2 MV Switchgear
room.

Unit 2 LV Switchgear
room.

Unit 3 DC switchgear
room.

The single door lock is damaged and the


double door does not lock.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
The room floor is dirty.
The single emergency exit door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
The double door needs to be adjusted to
allow the door to lock.
3 light o/c in the battery room.
New non self-locking A master locks
installed on the doors where found unlocked
on both doors.
Both the single & double door locking
systems should be changed to allow selflocking. The new locking system installed
can be altered to allow for the quick release
needed.

The single emergency exit door locking


systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
A floor or frame pin should be fitted to the
double door to allow the door to lock.
2 light are o/c in the battery room and there
is water on the floor.
Both the single & double door locking
systems should be changed to allow selflocking. The new locking system installed
can be altered to allow for the quick release
needed.
2 Lights o/c.
The double door between Unit 2 LV and Unit
3 battery room does not lock and needs
repair.
9 light o/c.
Switchgear room floor is dirty.
9 lights are o/c.
Electrical cables are hanging out of one light
fitting
The quick release locking mechanism needs
repairs
The quick release locking mechanism for the
battery room door also needs repairs

Unit 3 MV Switchgear
room.

Unit 3 LV Switchgear
room.

Unit 4 DC switchgear
room.
Unit 4 MV Switchgear
room.

Unit 4 LV Switchgear
room.

Unit 5 DC switchgear
room.

Unit 5 MV Switchgear
room.

Unit 5 LV Switchgear
room.

Unit 6 DC switchgear
room.

1 light is o/c in the battery room.


New non self-locking A master locks
installed on the doors where found unlocked
on both doors.
Both the single & double door locking
systems should be changed to allow selflocking. The new locking system installed
can be altered to allow for the quick release
needed.
6 Light are o/c.
7 lights are o/c.
The south door quick release and self-locking
mechanism needs repair
Switchgear room floor is dirty.

Both the single & double door locking


systems should be changed to allow selflocking. The new locking system installed
can be altered to allow for the quick release
needed.
The double door between Unit 4 LV
switchgear room and Unit 5 battery room
needs a floor or frame pin to enable it to
lock.
One of the 2 smaller doors above the door
between Unit 4 LV switchgear room & Unit 5
battery room is missing.
1 Light o/c
Switchgear room floor is dirty.
The double door locking mechanism is
installed incorrectly; the quick release
handle should be in the inside of the room.
Both the single & double door locking
systems should be changed to allow selflocking. The new locking system installed
can be altered to allow for the quick release
needed.
4 lights o/c.
The double door between Unit 5 LV and Unit
6 battery room is damaged and needs repair
to enable it to lock.
Unable to open the south door from inside
and the quick release and self-locking
mechanism needs to be repaired on the
north door.
Switchgear room floor is dirty.
13 lights are o/c.
The single emergency exit door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.

Unit 6 MV Switchgear
room.

Unit 6 LV Switchgear
room.

Unit 6 Precip SubStation A

Unit 6 Precip SubStation B

Incline conveyor SubStation 3.

Unit 5 Precip SubStation A

9 lights o/c inside the DC switchgear room.


And 11 out of the 19 light in the battery
room is o/c.
Both the single & double door locking
systems should be changed to allow selflocking. The new locking system installed
can be altered to allow for the quick release
needed.
Switchgear room floor is dirty.
16 lights are o/c.
The split Unit air-conditioning system is off.
Is it still the same?
30 out of the 42 light in the switchgear room
is o/c.
The split Unit air-conditioning system is off.
Is it still the same?
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency. A
cover should be made and placed over the
lock to prevent dust from clogging key slot.
1 Light is o/c.
The Sub-Station floor is dirty.
Newer flash suit signs and 11 Point plan to
be placed on the doors.
New door locks installed and none of them
opens with an A master from the outside or
the inside.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency. A
cover should be made and placed over the
lock to prevent dust from clogging key slot.
1 Light is o/c.
No flash suit signs or 11 Point plan on the
doors.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
Should a conventional door lock be used a
cover should be made to prevent dust from
clogging key slot.
The Sub-Station is dirty.
No flash suit signs with the pictures are
displayed on the door.
A sign needs to be placed on top of the door
naming the sub-station.
New door locks installed and the single door

Unit 5 Precip SubStation B

Unit 4 Precip SubStation A

Unit 4 Precip SubStation B

does not open with an A master from the


outside.
The double door requires an A master key
to exit.
No key slot or quick release on the inside of
the single door lock.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency. A
cover should be made and placed over the
lock to prevent dust from clogging key slot.
The Sub-Station floor is dirty.
Hasp & Staple locking mechanism must be
removed.
The air-conditioning unit is not cooling down
the sub-station sufficiently.
3 Lights are o/c.
No flash suit signs or 11 Point plan on the
doors.
New door locks installed and the single door
does not open with an A master from the
outside. Both the single & double door
requires an A master key to exit.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency. A
cover should be made and placed over the
lock to prevent dust from clogging key slot.
The Sub-Station floor is dirty.
The air-conditioning unit is not cooling down
the sub-station sufficiently.
1 Light is o/c.
No flash suit signs or 11 Point plan on the
doors.
No door lock available.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency. A
cover should be made and placed over the
lock to prevent dust from clogging key slot.
No flash suit signs or 11 Point plan on the
doors.
A sign needs to be placed on top of the door
naming the sub-station.
No door lock available.
Both the single & Double door locking
systems should be changed to allow self-


Incline conveyor SubStation 2.

Unit 3 Precip SubStation A

Unit 3 Precip SubStation B

Unit 2 Precip SubStation A

locking and a quick release system to exit


the switchgear room in an emergency. A
cover should be made and placed over the
lock to prevent dust from clogging key slot.
No flash suit signs or 11 Point plan on the
doors.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
Should a conventional door lock be used a
cover should be made to prevent dust from
clogging key slot.
The Sub-Station is dirty.
Steps up to the sub-station door are
damaged.
New door locks installed and the single door
does not open with an A master. The
double door requires an A master key to
exit.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency. A
cover should be made and placed over the
lock to prevent dust from clogging key slot.
The Sub-Station floor is dirty.
1 Light o/c.
No flash suit signs or 11 Point plan on the
doors.
No working air-conditioning unit in the substation.
New door locks installed and the single door
does not open with an A master. The
double door requires an A master key to
exit.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency. A
cover should be made and placed over the
lock to prevent dust from clogging key slot.
The Sub-Station floor is dirty.
No flash suit signs or 11 Point plan on the
doors.
Water dripping on the sub-station floor,
coming from the air-conditioning unit and
forming a large puddle close to the 380V
Precip board.
Both the single & Double door locking
systems should be changed to allow self-

Unit 2 Precip SubStation B

Incline conveyor SubStation 1.

Unit 1 Precip SubStation A

Unit 1 Precip SubStation B

Unit 3 & 4 Boiler


outage container.

locking and a quick release system to exit


the switchgear room in an emergency.
Should a conventional door lock be used a
cover should be made to prevent dust from
clogging key slot.
The Sub-Station floor is dirty.
1 Light o/c.
A sign needs to be placed on top of the door
naming the sub-station.
Water dripping on the sub-station floor,
coming from the air-conditioning unit and
forming a large puddle close to the 380V
Precip board.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
Should a conventional door lock be used a
cover should be made to prevent dust from
clogging key slot.
The Sub-Station floor is dirty.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
Should a conventional door lock be used a
cover should be made to prevent dust from
clogging key slot.
The Sub-Station is dirty.
1 Light o/c.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
Should a conventional door lock be used a
cover should be made to prevent dust from
clogging key slot.
The Sub-Station floor is dirty.
Both the single & Double door locking
systems should be changed to allow selflocking and a quick release system to exit
the switchgear room in an emergency.
Should a conventional door lock be used a
cover should be made to prevent dust from
clogging key slot.
The Sub-Station floor is dirty.
1 Light o/c.
A master key does not open the single
door lock
The double doors are unlocked
The incoming breakers on the board are

Unit 5 & 6 Boiler


outage container.

Unit 1 & 2 Turbine


outage container.

Unit 3 & 4 Turbine


outage container.

Unit 5 & 6 Turbine


outage container.

labeled incorrectly, showing only the alpha


numeric and not the name of the board from
which they get supplied from.
The container inside is dirty.
The single door is unlocked and the steps for
the double doors have been moved away
from the container.
The air conditioner is not running.
The incoming breakers on the board are
labeled incorrectly, showing only the alpha
numeric and not the name of the board from
which they get supplied from.
The container inside is dirty.
A master key does not open the single
door lock
The double doors are unlocked
The container inside is dark.
A master key does not open the single
door lock
The double doors are unlocked
The incoming breakers on the board are
labeled incorrectly, showing only the alpha
numeric and not the name of the board from
which they get supplied from.
The container inside is dirty.
The air conditioner is not running, keeps
tripping the earth leakage.
Cooling fan is also off, tested same but
running very noisy.
A master key does not open the single
door lock
The double doors are unlocked
The incoming breakers on the board are
labeled incorrectly, showing only the alpha
numeric and not the name of the board from
which they get supplied from.
The container inside is dirty.