Академический Документы
Профессиональный Документы
Культура Документы
The codes that govern the power supply to the fire pump, as well as conversations
with the local authority having jurisdiction, determine the best solution for a
buildings fire pump power system design.
Sarah Kuchera, PE, LEED AP, ccrd + WSP, Dallas
03/24/2016
Learning objectives:
Illustrate the basic design of fire pumps and their power systems.
Examine the codes and standards that dictate fire pump power system
design.
Explain best practices by reviewing example designs.
The fire pump plays a critical role in providing for a safe environment, and how
it is powered is an important consideration of the design. A reliable source,
Single-source power
A single power-supply source for a fire pump can be provided from either a
reliable utility supply or from onsite power production. The important
consideration for a single supply service is that the incoming supply power is
not interrupted. Therefore, special consideration should be given to how the
service enters into the fire pump controller and what disconnecting means are
located upstream from the pump.
If a utility power connection is used, there are two methods that can provide
power to the fire pump:
1. The first method is a direct connection from the utility source where a power
feed is brought straight from the utility into the fire pump controller with no
interruptions. This feed is then treated as a service entrance and needs to
meet all of the code-required functions as defined by NEC Article 230
(services).
2. The second method is a tap ahead of the service main disconnecting
means. When using this method, the following items should be considered.
The service feeders shall terminate in a dedicated cabinet or vertical
switchboard section located ahead of and not within the same cabinet
as the disconnecting means.
The service feeder shall be in a location separate from the fire pump so
as to minimize the risk of damage to the fire pump in the event of a fire
at the main service area.
If onsite power production is available to the building, it can be considered as
a service to the fire pump if it is deemed reliable and meets the fire protection
requirements as outlined in NFPA 850: Recommended Practice for Fire
Protection for Electric Generating Plants and High Voltage Direct Current
Converter Stations.
With a single source of power to the pump, if the source that is providing
power to the building fails, then a fire watch or other approved procedure
needs to be put in place to verify that the building and its occupants are not
put into harm's way.
Again, it is important to note that the code does allow for overcurrent
protection on the emergency power feed and it does not require that it be
sized for locked-rotor current.
Wiring methods
It is important for the electrical engineer to design the feeder system delivering
that power to be protected against harm or damage. Keep in mind: If the fire
pump is operating, there is most likely a fire within the building. Thus,
protecting the feeder from harm by the fire is important to ensure the building
does not lose power to the pump that is protecting it and its occupants.
The method of protection is similar to that spelled out in NEC Article 230
(services), which requires a feeder to be routed outside of the building or to
provide an equivalency of protection against harm. This can be accomplished
through concrete encasement or a protected system with a minimum of 2-hour
fire protection. It also is important to segregate the power wiring that serves
the fire pump and its accessories from other loads so a failure in another
feeder would not induce harm to the fire pump feed.
The sizing criteria for the feeder supplying the fire pump are provided by NEC
Article 695 (fire pumps), which indicates that the minimum size is 125% of the
sum of the full-load amps of the fire pump and pressure maintenance pumps
plus 100% of the remaining accessory equipment. Installation, voltage drop,
and other derating factors should be considered when determining the final
selected wire size.
Grounding
Grounding for the fire pump feed is dependent upon what method of
connection is used. If the system is designed with a single source and the
power is essentially being treated as a service, include a grounding electrode
conductor as sized per NEC Table 250.66 and based upon the size of the
incoming ungrounded conductor. If there is a secondary source, like a feed
from a generator, this is treated like a feeder; provide an equipment-grounding
conductor sized per NEC Table 250.122.
The fire pump power feed is a critical item to consider as a part of the overall
design. Consideration for this should be done when determining the systems
that will be used to serve the normal and emergency power supply to the
building. Engaging the local AHJ as well as the building operator in the key
Sarah Kuchera is senior vice president and electrical engineer at ccrd + WSP.
Her duties have included project management, production coordination, and
project engineering on a variety of different projects including hospital, retail,
hospitality, and office buildings.
03/24/2016
The primary supply to the fire pump controller will come directly from a
connection at the utility transformer. This was coordinated with the utility
company; most will allow for this separate connection to be tapped at the
transformer. This meets the requirement for continuity of power as defined by
NEC 695.4(A) (direct connection). The feeder from the switchgear to the fire
pump controller (located in a different area) will be routed below the building
floor slab so that it is considered outside the building per NEC 230.6(1).
The second source for the fire pump will come from the emergency power
system for the building. The building's generator system will be sized to
handle the starting and normal operating load of the fire pump as defined by
NED 695.3(D)(1). A circuit breaker, sized to accommodate normal start-up of
the pump, will be located in the emergency distribution board. The second
feeder will route overhead to the fire pump controller and be encased in a
minimum of 2-in. concrete.
04/25/2016
Fire protection
systems are among the most essential components of any building's
infrastructure. They safeguard both lives and property, so they must be
expertly designed and installed for optimum performance.
A standard fire protection system draws from either a public water supply or
another water source (such as a reservoir or tank) and connects to sprinklers
or standpipes to release water in case of a fire. The fire pumpwhich is often
electrically powered but can also use a diesel engineprovides the sprinklers
with water at high enough pressure to meet the system's needs.
Important factors in electrical fire pump installation
Electrically powered fire pumps must meet many strict codes, such as those
set by FM, IRI, NEC, and NFPA. Understanding the most current requirements
of each code is critical for correct installation and operation.
NFPA 20: Installation of Stationary Pumps for Fire Protection (most recently
updated in 2013) outlines standards for fire pumps that ensure systems will
deliver water reliably during an emergency. NFPA 20 requires that fire pumps
have one or more dependable power sources; a reliable source complies with
these stipulations:
Hasn't had any power outages for more than 4 hours in the last year
Hasn't had any shutdowns not caused by grid-management failure or
natural disasters
Hasn't been supplied by overhead conductors.
Some other requirements for installing an electrical fire pump according to
code include: