Академический Документы
Профессиональный Документы
Культура Документы
CTJV
OCT 2007
Mott MacDonald
1 Atlantic Quay
Broomielaw
Glasgow
G2 8JB
UK
Tel: 44 (0)141 222 4500
Fax: 44 (0)141 221 8083
Mott MacDonald
CTJV
Mott MacDonald
CTJV
List of Contents
Page
1-1
2-1
2.1
Introduction
2-1
2.2
2-1
2.3
2-2
2-2
2-2
3-1
3.1
Introduction
3-1
3.2
3-1
3-1
3-4
3-6
3-8
3-9
3-11
3-12
3-12
3-13
3-25
3-26
A1
A2
A20
A-3: Interface with Kahramaa - Schedule for 87L and 87T protection
A25
A29
A33
B1
Table 1-1: Main protection functions set and relay used for the protection
Table 3-1: Fault levels at 132 kV main switchboard of the Kahramaa substation
Table 3-2: Current matrix for various ratings of transformer
Table 3-3: Fault current matrix for over current relay setting
Table 3-4: Permissible time delay for over current relay co-ordination
Table 3-5: Guideline for relay setting for under voltage protection
Table 3-6: Guideline for relay setting for over-voltage protection
Table 3-7: Setting group for REM 543 relay for thermal over load protection
Table 3-8: Time constant heating; Data assumed if not available
Table 3-9: Setting of 87L protection for 33 kV feeders from SB-27101 A/B
Table 3-10: Setting group for REF 542+ relay for 87T protection
Table 3-11: Setting of 87M protection for MV BOG compressors
Table 3-12: Direct on line starters with MCCB and INSUM-2, load up to 45kW
Table 3-13: Direct on line starters with MCCB and INSUM-2, load more than 45kW
Mott MacDonald
CTJV
1-1
3-1
3-2
3-3
3-4
3-6
3-8
3-9
3-10
3-14
3-21
3-24
3-27
3-28
ii
Mott MacDonald
CTJV
Mott MacDonald
CTJV
Introduction
This report describes the relay co-ordination studies performed by Mott MacDonald on behalf of
Chiyoda Technip Joint Venture (CTJV) for the QGX-CLP (Qatar Gas II Common Lean LNG
Project) development project.
The electrical distribution system of the CLP network comprises of the substation SS-2701, SS-2702
and SS-2703. The substation SS-2701 is having option of power supply either from QGX system or
from the SS-2702. The substation SS-2702 (Lean LNG storage tank substation-2) is connected to the
Kahramaa substation through two 132 kV underground cables and the substation SS-2703 is supplied
from SS-2701. For the CLP system study the substation SS-2701 is considered to be supplied from the
substation SS-2702.
In this report, integrated relay setting of various protection functions and co-ordination of various
relays are presented. Main protection functions for which the relay settings are carried out are shown
in Table 1-1.
S.No.
ANSI Number
Protection Name
Transformer differential
7UT612, REF542+
87-L
Line differential
87-M
Motor differential
REM 543
49
Motor Thermal
REM 543
27
Under voltage
59
Over voltage
46
Unbalance current
REM 543
47
REM 543
66
REM 543
37
Under power
REM 543
Over current / EF
10
50, 50N
11
81U
Under frequency
REF 542+
Table 1-1: Main protection functions set and relay used for the protection
1-1
Mott MacDonald
CTJV
2.1
Introduction
This section describes the electrical distribution system for the QGX-CLP development project, the
modelling methodology adopted and the data used in performing the electrical system studies.
Included within this section is a description of the following:
Software package
The ETAP representation of the QGX-CLP electrical network is presented in electrical system studies
report1 already submitted.
2.2
Fault level and relay co-ordination studies are carried out using version 5.0.3 of ETAP PowerStation,
developed by Operation Technology, Incorporated. This package uses standard models of the main
components in the power system in combination with numerical techniques to solve the various
electrical and mechanical equations describing the system. The system model and parameters are
entered into the model using the ETAP network schematic capture facility.
The main components represented in the ETAP model are as follows:
Synchronous machines: A standard two-axis equivalent circuit model is used to represent
synchronous machines. This model includes sub-transient, transient and synchronous reactances and
their associated time constants and allows full dynamic modelling of transient events. Stator and rotor
saturation are accounted for, as are the alternator and prime mover inertia.
Asynchronous (induction) machines: These elements are modelled based on their per-phase
equivalent circuit parameters. The equivalent circuit data is manipulated to create a two axis transient
model that also includes the motor and driven load inertia and the load torque-slip curve. The
dynamic simulation therefore takes account of the motor and load dynamics. The model also accounts
for the momentary and decaying current contribution that asynchronous machines will make into a
system short circuit.
Transformers: These are modelled as equivalent pi impedance network. The zero sequence
impedance, and winding connections are included in the model. This is used to assemble the correct
zero sequence network representation when calculating earth fault currents.
Cables: Cables (and transmission lines) are modelled by a circuit of fixed positive sequence
impedance and shunt susceptance. A pi impedance network is used to represent the circuit with half of
the total circuit capacitance connected as a shunt element at each end of the circuit.
Electrical system studies for QGX-CLP development protect; Load flow, short circuit and motor starting studies Rev A;
Mar 2007, report submitted by Mott MacDonald Ltd.
2-1
Mott MacDonald
CTJV
Controllers: The prime mover turbines and voltage regulator/exciter system associated with
synchronous machines are included as transfer function block diagrams and associated gains and time
constants.
Relays:
Over current relay specific to manufacturer and model are available with all setting
ranges and typical ANSI and IEC curves for inverse, very inverse and other characteristics. By
selecting one particular setting of current and time delay the same can be projected on TCC (on loglog scale) to view the possible operation time for various currents.
2.3
The ETAP single line representation of the QGX electrical system is based on CTJV General Single
Line Diagram for the Electrical System2. The system model3 used for system study is used for the
relay co-ordination.
2.3.1
System Earthing
The QGX electrical system earth fault levels are generally limited by neutral earthing resistors that are
organised as follows:
132 kV
- Solidly earthed
33 kV
11 kV
6.6 kV
0.415 kV
2.3.2
System Operation
Various transformer configurations were considered in the studies for calculation of the minimum and
the maximum fault current calculation. The following definitions are used throughout the report when
referring to transformer connections:
Dual transformers each switchboard section is fed in isolation by its associated transformers.
This is the normal operating configuration for the system.
Single transformers two or more switchboard sections are fed via a single transformer. This is to
consider a case where there is a single transformer outage and its load is taken up by another unit.
For a switchboard fed by three or more transformers, it is not expected that one unit would be
rated to supply the whole load.
CTJV, QATARGAS II DEVELOPMENT PROJECT General Single Line Diagram, Dwg. N: QGX/20/91/EL/DR/SD/001
Rev C2
3
Electrical system study for QGX-CLP development project Mar-2007 (Study report for load flow, short circuit, motor
starting) submitted by Mott MacDonald Ltd.
2-2
Mott MacDonald
CTJV
3.1
Introduction
Methodology used for relay setting and co-ordination of relays are presented in the various sub-section
below. Based on that relay setting schedules and TCC of the over current relays are prepared.
3.2
The relay setting and co-ordination studies are carried out for various relays and protection functions
presented in the Table 1-1. Before carrying out the relay setting, a fault current matrix for various
voltage levels is prepared.
The current matrix gives important information for the minimum and maximum fault currents seen by
each relay at various locations in the system, based on which proper discriminated, sensitive and coordinated protection can be achieved.
In order to achieve the uniform relay setting for the feeders having similar rating of transformers and
loads guidelines are prepared for setting of the various protection functions.
3.2.1
Current matrix is calculated for faults at voltage levels. The following tables present the current
matrices.
The minimum and maximum three-phase fault levels at 132 kV main switchboard of the Kahramaa
substation4 are presented below:
S.No.
Fault level
X/R ratio
The minimum
10.2
12.05
The maximum
15.47
6.48
Table 3-1: Fault levels at 132 kV main switchboard of the Kahramaa substation
Email from Vincent Sauvergrain to Manoj Gupta, dated 31/08/2007, subject: QGX-CLP-MMD electrical studies-Company
and KM comments
3-1
S.No
1
2
3
4
5
6
Transformer
Tag
Name
TR-27101 A/B
TR-27601
TR-27204 A/B
TR-27201 A/B
TR-27301 A/B
DTR-27302 A/B
Primary
Voltage
Secondary
Voltage
KV
132
33
33
33
6.9
6.9
kV
33
11
6.9
6.9
0.44
0.44
Mott MacDonald
CTJV
Transformer
Rating
Min
Max
MVA
MVA
80
100
25
25
20
25
12
15
1.6
1.6
1
1
3-2
Mott MacDonald
CTJV
Fault location
Fault current
observation
0.415 kV
SB-27302A
SB-27302A
Bus section
6.6 kV incomer
0.415 kV
SB-27301A
SB-27301A
Bus section
6.6 kV incomer
28.12
28.12
1.83
30.22
30.22
1.98
6.6 kV
SB-27201 A
SB-27201A
6.6 kV incomer
Bus section
33 kV TR-27201
33 kV incomer
132 kV CLP
10.08
10.08
10.08
2.06
2.06
0.52
16
11
11
2.34
1.51
0.4
6.6 kV
SB-27205A
6.6 kV incomer
Bus section
33 kV TR-27204
33 kV incomer
132 kV CLP
11.81
11.81
11.81
2.41
2.41
0.62
17
11.73
11.73
2.89
1.68
0.45
33 kV TR-27603
Bus section
33 kV incomer
132 kV CLP
9.02
9.02
9.02
2.31
13.92
13.92
9.46
2.52
132 kV CLP
9.5
13.92
132 kV CLP
(LG fault current)
10.05
15.17
SB-27205A
33 kV
TR-27603
132 kV
TR-27101A
Table 3-3: Fault current matrix for over current relay setting
For the minimum three-phase fault current calculation, the minimum fault level at Kahramaa S/S and
no motor contribution are considered. For the maximum fault current calculation, the maximum fault
level at Kahramaa S/S and motor contributions are considered. All faults currents are as per
IEC 60909 symmetrical breaking currents. Earth fault current is restricted to the value as indicated in
the Section 2.3.1 due to the resistance grounded system.
3-3
3.2.2
Mott MacDonald
CTJV
Guidelines for relay settings for 51, 50, 51N and 51G protection function
The Circuit protection Time Interval (CTI)5 for the over current relay settings is presented
below
S.No.
Components
0.1
0
0.12
Total CTI
0.22
Table 3-4: Permissible time delay for over current relay co-ordination
Hence it is practical to have CTI for the electronics relays as low as 0.22 s. CTI provides the
necessary time delay between the operations of the two relays and ensure co-ordinated
operation.
A sample circuit is shown below with a transformer and load. Relay locations are presented
by A, B and C. Fault is presented on the primary side and secondary side of the transformer
by Fp and Fs respectively.
C
Fp
B
.
A
Fs
Figure 3-1: Sample circuit diagram for relay setting guideline
3-4
Mott MacDonald
CTJV
The characteristic of the relays at A, B and C for over current protection is normal
inverse. Exception can be made for the relay at A, if associated with a motor protection,
then it may be definite time or extremely inverse.
Relay at B and C must not operate for the maximum full load current of the transformer.
The pickup is set between 115-150% of the full load current depending on the coordination with the down-stream and up-stream relays.
Relay at C must not operate for inrush current of the transformer, to ensure this the
pickup setting of the instantaneous element must be more than the inrush current as
indicated in the Table 3-1
For the fault Fs, the instantaneous elements of the relay at A should give protection,
backup by the over-current element of the B and C. The instantaneous element of the
relay at B will not be co-ordinated as the same is used for blocking of ATS (Automatic
transfer system)6 in event of fault at the secondary side of the transformer. Pickup values
for the instantaneous element at B are considered as follows
o
In no case the minimum CTI should be violated for the maximum fault current seen by
the relays
Because earth fault current is limited by the NGR, definite time characteristics are
adopted to co-ordinate all 51N and 51G protection functions.
Characterise of the fuse are as per the ABB fuse manual7. The fuse characteristics as
given on page 13 of the manual are modelled in ETAP.
The TCCs for the over current protection is presented in the Appendix B.
6
7
3-5
3.2.3
Mott MacDonald
CTJV
For the under voltage protection the following settings are considered
S.No.
1
2
For Motor
0.7
500 ms
For Transformer
0.7
70 ms
Table 3-5: Guideline for relay setting for under voltage protection
Under voltage relay at transformer secondary is used for ATS operation as shown in
figure below. During the operation of 50, 50N or 27 immediate transfers of the loads
to the other main bus (S1-R) should not occur otherwise that bus (S1-R) will also see
the fault. For this reason operation time of the 27 and ATS should be time delayed to
allow the operation of 51, 51N at each outgoing feeder to disconnect the faulty
feeders from the bus (S1-L), if the fault is at the outgoing feeders. Hence the
additional time delay is used for this purpose. Time delay of 2s is provided by the
27X of the ATS.
For faults at transformer secondary side the ATS operation is blocked by the
instantaneous over-current relays 50 and 50N as well as 27
For the low voltage at the secondary of the transformer by opening the primary
CB motor under voltage operates first followed by under voltage relay on the
transformer secondary with the time delay of 70 ms that activates the transfer
logic of ATS. The ATS operates after a delay of 2s by opening the primary CB of
the affected transformer, then opening secondary CB of the transformer and
closing the bus coupler. In this way the bus S1-L is transferred to the bus S1-R.
3-6
Mott MacDonald
CTJV
P1-L
P1-R
C
"#
$
!
"#
%
'(
S1-L
S1-R
A
Fs
"#&
&
Figure 3-1A: ATS operation Interaction with over-current and under voltage relays
3-7
3.2.4
Mott MacDonald
CTJV
For the over voltage protection the following settings are considered
S.No.
1
2
For Motor
1.15
5000
Motor starting results reveals that the maximum post transient over voltages after the motor
start are as high as 1.1 pu for less than 100 ms. Considering the result of the motor starting the
low set U> of the 59 function is set to 1.15 pu with a time delay of 5s.
3-8
3.2.5
Mott MacDonald
CTJV
For the thermal over load protection (49) of the MV motors, REM 543 (ABB) is used. For the
LV motors the setting of the thermal protection is presented in Appendix A1.
3.2.5.1 49 protection function for ABB REM 543 relay
S.No.
Setting Parameter
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Ist = 0.1-10.00 In
Tst = 0.1 - 120.0 s
NC-st = 1-3
Device Type = 0-6
Trip Temp. = 80-120 %
Alarm Temp. = 40-100%
Reset Temp. = 40-100%
Am Temp.= -50-100 Deg C
TC-cooling = 1.0-10.0
TC-Heating = 1-999 min
ST-CS = 0.0-999.0 min
LT-CSS = 0.0-999.0 min
p = 0.0 - 1.0
S-TR =50-350 Deg C
Tmax S = 0.0-350 Deg C
ST-CR = 0.0-999.0 min
LT-CR = 0.0-999.0 min
p = 0.0 - 1.0
R-TR =50-350 Deg C
Tmax R = 0.0-350 Deg C
Trip Delay = 0-86400 s
Sample
Data
3.5
12
3
3
120
90
60
50
3
45
14.00
69
0.5
90
155
4
69
0.25
100
200
3600
Remarks
Starting current
Starting time
Number of starts allowed from cold
Surface cooling
Trip temperature
Alarm temperature
Reset temperature
Ambient Temp.
* TC-Heating
Time constant
Short TC - Stator
Long TC - Stator
Wt. factor
Stator Temp. rise at FL
Stator Max. Temp
Short TC - Rotor
Long TC - Rotor
Wt. factor
Rotor Temp. rise at FL
Rotor Max. Temp
60 min
Table 3-7: Setting group for REM 543 relay for thermal over load protection
Explanations of the above setting parameters are presented below
Device type8 is set for motor rating > 500 kW and surface cooling
Relay technical data sheet: ABB ProtectIT Machine Terminals REM 543 and REM 545, document number:
1MRS751173-MBG
3-9
Mott MacDonald
CTJV
Trip Temp. is set to 120% with Trip Delay of 60 min (3600s). It means that from
motor temperature in the range of 100-120%, warning alarm will be generated until
time delay of 60 min, for temperature more than 120%, tripping will occur
instantaneously.
TC-cooling is set at 3 times the heating time constant. For motors less than 1300 kW
it is taken as 6.0
TC heating is set according to individual motor data. Following values are used
when the data is not available
S.No.
Motor rating
30
1300 kW to 2000 kW
35
2100 kW to 3000 kW
40
45
Settings from ST-CS to TMAX R are taken as default setting for wide range of motor
ratings, except for S-TR and R-TR. The value of S-TR and R-TR for motors above
2000 kW is 90 and 100 respectively and for motors between 1000 kW to 2000 kW is
70 and 80 respectively.
3-10
3.2.6
Mott MacDonald
CTJV
For current unbalance protection (for ABB REM 543) the following settings are considered
Pick up Is = 0.05
K is calculated for individual motor in such a manner that the tripping time of the
relay is below the thermal damage curve. For motors above 2500 kW the thermal
damage limit is taken as 15s and below that it is 10s.
Operation time = Not applicable as the operation mode is not definite time
Start delay = 1 s
For ABB make REM 5439 relay inverse time characteristic is used for this function.
Negative Phase Sequence Protection ABB document no. 1MRS752310-MUM, Issued 10/1998, Version
E/24.11.2003
3-11
3.2.7
Mott MacDonald
CTJV
For protection function 66 (for ABB make, REM 543) the following settings are considered
The protection function is also used to derided the 51LR protection function using the
NOC3High (I>>)10 of the over- current protection. Output of the 66 protection function (using
MotStart) is applied as input to NOC3High to double the setting of the NOC3High during the
motor start-up duration. Once the motor reaches to its normal speed the NOC3High is
returned to the actual setting (which set at 0.75 * Motor starting current). In this way 51LR is
achieved during the motor start-up and the motor normal running condition. During the motor
start-up the 51LR function is provided by the MotStart (66 protection function) and during the
motor normal running condition the 51LR function is provided using the NOC3High of the
over-current protection.
3.2.8
For protection function 37 (for ABB make, REM 543) the following settings are considered
Minimal load = 5%, Minimal current = 5%
Op. time = 300 s (5 min)
10
Email from Toshiaki Saito to Manoj Gupta; dated 28/09/2006; subject: QGX : 51LR protection of REM543
(SL19020); attachment: Motstart_ver_0.10.pdf
3-12
3.2.9
Mott MacDonald
CTJV
The differential protection as indicated in Table 1-1 is used for cables, transformers and
motors protections. The differential protection is a unit protection and setting of this function
required detailed analysis. The following sections present the calculation of the differential
protection for various equipments using different relays.
3-13
33 kV feeder To
Mott MacDonald
CTJV
TR-27204 A/B
TR-27601 to TR-27605
TR-27201 A/B
438
438
263
600
600
400
400
400
400
1.06
1.06
1.16
0.67
0.67
1.00
Minimum Differential
Allowed wrt to Ic (x In)
0.1
0.1
0.1
0.2
0.2
0.2
Table 3-9: Setting of 87L protection for 33 kV feeders from SB-27101 A/B
Same setting is used for both sending end and receiving end of the 33 kV feeder cables
Ic: Relay bias current
3-14
Mott MacDonald
CTJV
2.500
2.000
1.500
1.000
B2 = 2.5
0.500
0.000
0.00000
0.50000
1.00000
1.50000
2.00000
2.50000
3.00000
Mott MacDonald
CTJV
800/1
REL 561
800/1
7SD53
7SD53
800/1
REL 561
Pickup for differential current (I-Diff>) should be more than 2.5 time the charging
current
Charging current compensation is not required as the charging current is only 20A
For dual slope characteristic relay, set the first slope to 50%, second slope to 100%,
and intersection of slope 1 and slope 2 to 350% of I-bias.
Same setting of the differential protection should be adopted for both the ends of
cable if CT ratios at both the ends are same.
3-16
Mott MacDonald
CTJV
Setting of I-Diff>
I-Diff> = (2.5 * Charging current + 5% CT ratio error) / CT ratio
= (2.5 * 20 + 0.05 * 800) / 800
= 0.1125
Adopted setting for I-Diff> = 0.12
Inrush Restraint = On
Cross block = No
Maximum Inrush Peak = 9.0 (Based on 11 * Transformer full load RMS current)
3-17
Mott MacDonald
CTJV
Calculations of relay setting parameters for REL 561 are presented below
Operation = On
Asymdelay (Asymmetrical time delay in data communication between the two ends)
Asymdelay = 0.0 (Refer relay manual for this setting)
Complete relay setting schedule for the 87L protection is listed in Appendix A3, for the
132 kV feeders C30 and C40.
3-18
Mott MacDonald
CTJV
TR-27101 A/B
80 MVA
Z = 12.5%
87 T
87N
7UT612
400/1
2000/1
33 kV
Figure 3-4: Representation of 87T protection for TR-27101 A/B
Calculations of the relay setting parameters are presented below
The relay should have minimum restrain for magnetising current (assumed to be 2% of full
load current) , CT errors (considered to be 5%) at full loads and should consider the effects of
transformer tap operations
Using the formula shown below minimum restraint current = 0.07
Minimum restraint current (Is) = (5% of Isecondary / CT ratio) + (5% of Iprimary / CT ratio)
Isecondary = X * FLC (FLC: Full load current)
Iprimary = X * FLC
X = 1.15 (15% allowable overload is considered)
Adding the differential current at full load due to CT ratio mismatch, the minimum
differential current = 0.07 + 0.11 = 0.18
Considering the safety margin, CT saturation and transformer tap operation set Id> to 0.25 In
3-19
Mott MacDonald
CTJV
Add on Stabilization
Setting of the Add on Stabilization is based on the inrush current magnitude.
Inrush current for TR-27101A/B = 7 * Full load current
= 7 * 350 = 2450 A
The inrush current seen at CT secondary = 2450 / 600 = 4.08
Adopted setting for Add on Stabilization = 75% of 4.08In = 3.0 In
Setting of Id>> is calculated based on the formula given in the manual of 7UT612 on page 37
Id>> = (Transformer Full load current / CT primary) / Z (pu)
= (350/ 600) / 0.125 = 4.7 In
Adopted setting for Id>> = 4.7
Calculation of setting parameters for 87N protection (Setting group of Restricted Earth
Fault (64) are use for 7UT612)
Secondary side Neutral CT ratio = 400/1
Line CT ratio = 2000/1
Slope = 0
Because earth fault current is limited to 400A hence chances of CT saturation and error due to
through fault current is remote. Complete relay setting schedule for the 87T protection for the
transformer TR-27101 A/B is presented in the Appendix A3.
3-20
Mott MacDonald
CTJV
Setting Parameter
VG = 0 - 11
Earthing P: Yes / No
Earthing S: Yes / No
Ip = 10 - 100000 A
Is = 10 - 100000 A
Ith = 0.1 - 0.5 Ir
URL = 0.5 - 5.0 In
SBRT = 0.2 - 2.0
SBRL = 1.00 - 2.00 Ir
Slope = 0.4 - 1.0
Trip Id> = 5.00-40.00
I2 Block= 0.1 - 0.3
I5 Block = 0.1 - 0.3
Sample Data
0
Yes
Yes
350
1400
0.2
0.5
0.25
1
1
5
0.3
0.3
Remarks
Transformer vector group
Rated primary side current
Rated secondary current
Threshold current
Unbiased region limit
Slightly biased threshold
Slightly biased region limit
Third region slope
Upper Id threshold for trip
2nd harmonic threshold
5th harmonic threshold
Table 3-10: Setting group for REF 542+ relay for 87T protection
Id =
Id>
I1 I2
R3
SBRT
It
R2
R1
URL
SBRL
Ib = (I1 + I2) / 2
Mott MacDonald
CTJV
Ith: Threshold current for the unbiased region (R1) is set to 20%, considering the
maximum CT error of +5% and -5% at both ends of the transformer for through fault
condition
For 33/6.9 kV transformers Ith is set to 10%
URL: Unbiased region limit is set to 0.5In corresponding to 50% of the full load
SBRL: Slightly biased region limit is set to 1.0, corresponding to full load
Slope is set to 1 so that wider area is covered under tripping zone and at the same
time higher than the minimum setting to provide the sufficient bias during through
fault condition and CT situation conditions.
For 33/6.9 kV transformers Ith is set to 0.5
Trip Id> is set at 5.0, which is higher than the inrush current
I2 Block and I5 Block for the harmonic current is taken as to be at the default set
value
3-22
Mott MacDonald
CTJV
Turing point 1: Value of Ib/In from where the first slope starts (0.0 1.0 In)
Starting ratio: Slope of the line after the Turning point 1 (10 - 50%)
Turning point 2: Value of Ib/In from where second slope starts (1.0 3.0 In)
Inst. Setting (Id>>): Instantaneous differential element pickup (5.0 30.0 In)
11
Diff6G-Stabilized Three-Phase Differential Protection for Generators ABB document number 1MRS752302-MUM,
version C/18.1.2002
3-23
Mott MacDonald
CTJV
Settings adopted for BOG compressor motor relay are set as under
S.
No.
9500
CT ratio
700/1
10
0.5
50
1.5
5.0
3-24
Mott MacDonald
CTJV
12
Relay REF 542+ manual Protection functions: configuration and settings ABB document number
1VTA10002 Rev03, en
3-25
221661/02/B - OCT 2007
P:\Glasgow\PSB\EEG\3Jobs\221661 QGX\CLP Studies\Report\221661A - QGX-CLP - Relay Coordination-Rev1.doc/CLP
Mott MacDonald
CTJV
13
MCU parameter description Ver. 3.0, ABB document on the INSUM relay
Electrical system study for QGX, Company approved report Relay co-ordination studies Rev G, July 07, report
submitted by Mott MacDonald Ltd. To CTJV
15
Email from Vincent to Manoj Gupta; dated 28/09/2007; subject: RE: QGXE2A4042 / CLP - LDB Relays in Satellite SS2701A, SS-2702A/B/C Settings; Attachment: MM2 Setpoint File Information.pdf
14
3-26
S.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Cub
Size
6E
6E
6E
6E
6E
6E
6E
6E
6E
6E
6E
6E
6E
6E
6E
6E
6E
12E
12E
Motor
kW
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
Mott MacDonald
CTJV
MCCB
I (A)
0.72
0.83
1.1
1.5
2
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
Type
T2H160 MF 1
T2H160 MF 1
T2H160 MF 1.6
T2H160 MF 1.6
T2H160 MF 2
T2H160 MF 3.2
T2H160 MF 4
T2H160 MF 5
T2H160 MF 8.5
T2H160 MF 11
T2H160 MF12.5
T2H160 MA 20
T2H160 MA 32
T2H160 MA 52
T2H160 MA 52
T2H160 MA 52
T2H160 MA 80
T2H160 MA 80
T2H160 MA 100
Magnetic
Tripping
current (A)
13
13
21
21
26
42
52
65
110
145
163
200
288
364
468
520
800
960
1200
I1
MCCB Setting
t1
I2
t2
I3
13
13
13
13
13
13
13
13
13
13
13
10
9
7
9
10
10
12
12
Contactor
INSUM
Interpose
QGX Type
A9
A9
A9
A9
A9
A9
A16
A26
A26
A30
A50
A50
A50
A50
A50
A63
A75
A95
A110
TYPE
MCU2 0.1-3.2 A
MCU2 0.1-3.2 A
MCU2 0.1-3.2 A
MCU2 0.1-3.2 A
MCU2 0.1-3.2 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 63 A
MCU2 0.1-3.2 A
MCU2 0.1-3.2 A
CT
KORC 1A 105/1 S
KORC 1A 105/1 S
Table 3-12: Direct on line starters with MCCB and INSUM-2, load up to 45kW
3-27
Cub
Size
Motor
kW I (A)
I1
MCCB Setting
t1
I2
t2
I3
Contactor
QGX
Type
INSUM
TYPE
Interpose
CT
Tripping
current
(A)
1360
20
12E
55
98
8.5
A145
MCU2 0.1-3.2 A
KORC 1A 105/1 S
21
12E
75
135
1875
7.5
A185
MCU2 0.1-3.2 A
KORC 1A 185/1 S
22
16E
90
158
2000
A210
MCU2 0.1-3.2 A
KORC 1A 185/1 S
23
16E
110
193
2080
6.5
A260
MCU2 0.1-3.2 A
KORC 1A 310/1 S
24
Cub600
132
232
E2N1250In400 PR121/LI
2400
0.8
12
N/A
MCU2 0.1-3.2 A
SUCCESS 400/1 A
25
Cub600
FDR
630
T5H630In630 PR221-LSI
2835
4.5
26
Cub600
FDR
800
S6H800In800 PR212-LSI
6400
S.
No.
Type
MCCB
Mott MacDonald
CTJV
Table 3-13: Direct on line starters with MCCB and INSUM-2, load more than 45kW
3-28
A1
Mott MacDonald
CTJV
Mott MacDonald
CTJV
Note-1: Referring to the Annexure-IV (Transformer Energization Study) of the QGX relay setting
report13.
Note-2: Setting value to be as per "Switch-In Time" for each priority group specified in Annexure-III
(Motor Auto Restart Study) of the QGX relay setting report13.
16
Email from Toshiaki Saito to Manoj Gupta dated 22/06/2007; Subject: Re: QGX : Wrap-up Comment on Relay
Coordination Study (INSUM Setting)
A2
Mott MacDonald
CTJV
INSUM
Device
CT ratio
Setting range
TYPE
Duty
Schedule for LV (0.415 kV) feeders
ST
Setting
MRD
In = 0.10 - 3.20 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
1
6E
0.18
0.72
TYPE -C
MCU2
Remark
0.72
6
5
Nominal current
Startup ratio
Enable
Standard
10
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
0.1 - 3.2A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A3
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
Alarm Only
Measure
1
Alarm level
0.3
Enable
415
80
Alarm level
70
Trip level
0
Trip delay for DOL/RCU
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
Mott MacDonald
CTJV
ST
MRD
In = 0.10 - 3.20 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
2
6E
0.25
0.83
TYPE-C
MCU2
27
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
MRD
49
0.37
1.1
TYPE-C
MCU2
Startup ratio
Enable
Standard
As per Motor Data
10
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
Alarm level
80
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
NR-DOL/RCU Starter Type
In = 0.10 - 3.20 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
6E
Nominal current
0.1 - 3.2A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
0.83
6
5
1.1
6
5
Nominal current
Startup ratio
Enable
Standard
10
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
0.1 - 3.2A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A4
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
Mott MacDonald
CTJV
ST
MRD
In = 0.10 - 3.20 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
4
6E
0.55
1.5
TYPE-C
MCU2
27
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
MRD
49
0.75
TYPE-C
MCU2
Startup ratio
Enable
Standard
As per Motor Data
10
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
Alarm level
80
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
NR-DOL/RCU Starter Type
In = 0.10 - 3.20 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
6E
Nominal current
0.1 - 3.2A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
1.5
6
5
2
6
5
Nominal current
Startup ratio
Enable
Standard
10
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
0.1 - 3.2A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A5
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
Mott MacDonald
CTJV
ST
MRD
49
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
6
6E
1.1
2.8
TYPE-C
MCU2
2.8
6
5
27
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
Enable
Standard
10
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
Alarm level
80
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
Auto reclosing time
0
5
Note-1
As per annexure-III
NR-DOL/RCU Starter Type
MRD
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
6E
1.5
3.5
TYPE-C
MCU2
Startup ratio
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
Nominal current
3.5
6
5
Nominal current
Startup ratio
Enable
Standard
10
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A6
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
Mott MacDonald
CTJV
ST
MRD
49
6E
2.2
TYPE-C
MCU2
2.0-63.0 A
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
Trip Delay
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
5
6
5
Trip Only
400%
5sec
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
Alarm level
80
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
Auto reclosing time
0
5
Note-1
As per annexure-III
NR-DOL/RCU Starter Type
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
9
6E
6.6
TYPE-C
MCU2
Startup ratio
Enable
Standard
10
As per Motor Data
4
cool down time fact.
90
Alarm level
MRD
49
Nominal current
6.6
6
5
Nominal current
Startup ratio
Enable
Standard
10
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A7
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
Mott MacDonald
CTJV
ST
MRD
49
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
10
6E
8.6
TYPE-C
MCU2
8.6
6
5
27
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
Enable
Standard
10
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
Alarm level
80
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
Auto reclosing time
0
5
Note-1
As per annexure-III
NR-DOL/RCU Starter Type
MRD
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
6E
5.5
11.5
TYPE-C
MCU2
Startup ratio
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
11
Nominal current
11.5
6
5
Nominal current
Startup ratio
Enable
Standard
15
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A8
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
Mott MacDonald
CTJV
ST
MRD
49
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
12
6E
7.5
15.2
TYPE-C
MCU2
15.2
6
5
27
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
Enable
Standard
15
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
Alarm level
80
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
Auto reclosing time
0
5
Note-1
As per annexure-III
NR-DOL/RCU Starter Type
MRD
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
6E
11
22
TYPE -C
MCU2
Startup ratio
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
13
Nominal current
22.0
6
5
Nominal current
Startup ratio
Enable
Standard
15
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
0.1 - 3.2A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A9
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
Mott MacDonald
CTJV
ST
MRD
49
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
14
6E
15
28.5
TYPE-C
MCU2
28.5
6
5
27
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
Enable
Standard
15
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
Alarm level
80
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
Auto reclosing time
0
5
Note-1
As per annexure-III
NR-DOL/RCU Starter Type
MRD
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
6E
18.5
36
TYPE-C
MCU2
Startup ratio
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
15
Nominal current
36.0
6
5
Nominal current
Startup ratio
Enable
Standard
15
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A10
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
Mott MacDonald
CTJV
ST
MRD
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
16
6E
22
42
TYPE-C
MCU2
27
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
MRD
49
30
56
TYPE-C
MCU2
Startup ratio
Enable
Standard
As per Motor Data
15
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
Alarm level
80
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
NR-DOL/RCU Starter Type
In = 2.0 - 63.0 A
Ist = 1.0 - 10 In
Tst = 1 - 600s
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
6E
Nominal current
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
17
42.0
6
5
56.0
6
5
Nominal current
Startup ratio
Enable
Standard
15
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
2.0-63.0 A
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A11
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
Mott MacDonald
CTJV
ST
105
1
MRD
In = 10.5 - 105A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
18
12E
37
73.5
TYPE-B
MCU2
KORC 1A
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
0.1 - 3.2 A
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
73.5
5.6
6
Enable
Standard
15
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
105
1
MRD
In = 10.5 - 105A
Ist = 1.0 - 10 In
Tst = 1 - 600s
19
12E
45
84
TYPE-B
MCU2
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
KORC 1A
Trip Delay
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A12
Startup ratio
49
Nominal current
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
84.0
5.9
5
Nominal current
Startup ratio
Enable
Standard
15
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Mott MacDonald
CTJV
ST
105
1
MRD
In = 10.5 - 105A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
20
12E
55
105
TYPE-B
MCU2
KORC 1A
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
0.1 - 3.2 A
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
105.0
5.3
6
Enable
Standard
29
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
185
1
MRD
In = 18.5 - 185A
Ist = 1.0 - 10 In
Tst = 1 - 600s
21
12E
75
129.5
TYPE-B
MCU2
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
KORC 1A
Trip Delay
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A13
Startup ratio
49
Nominal current
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
129.5
6.2
5
Nominal current
Startup ratio
Enable
Standard
13
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Mott MacDonald
CTJV
ST
185
1
MRD
In = 18.5 - 185A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
22
16E
90
166.5
TYPE-B
MCU2
KORC 1A
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
0.1 - 3.2 A
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
ST
166.5
5.7
6
Enable
Standard
15
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
310
1
MRD
In = 31 - 310A
Ist = 1.0 - 10 In
Tst = 1 - 600s
23
16E
110
186
TYPE-B
MCU2
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
KORC 1A
Trip Delay
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
A14
Startup ratio
49
Nominal current
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
186.0
5.7
6
Nominal current
Startup ratio
Enable
Standard
12
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
Alarm level
70
Trip level
Trip delay for DOL/RCU
0
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Mott MacDonald
CTJV
ST
0.1 - 3.2 A
400
1
MRD
In = 40 - 400A
Ist = 1.0 - 10 In
Tst = 1 - 600s
49
24 Cub600
132
240
TYPE-A
MCU2
Success
Function TOL
TOL Type
t6 = 5 - 40s
CDTF = 1 - 100
AL = 50 - 100%
51 LR Stall Protection
Trip Level
Trip Delay
51 G Function EF
Method
RCT Ip = 1,5,50 A
AL = 0.1(0.1)<Ip A
27
(415V
Function 27
Un = 230 - 690 V
AL = 50 - 100%
U< = 50 -100%
t< = 0.2 - 5 s
RVL = 50 - 100 %
MAT = 0.0 - 5.0 s
PDT = 0 - 1200 s
SST = 0 - 1200s
104.4
kW)
240.0
5.8
6
Nominal current
Startup ratio
Enable
Standard
18
As per Motor Data
4
cool down time fact.
90
Alarm level
Trip Only
400%
5sec
Alarm Only
Measure
1
0.3
Alarm level
Enable
415
80
70
0
Trip delay for DOL/RCU
90
Reset Voltage Level
0
Auto reclosing time
5
Note-1
As per annexure-III
Of the QGX Rev G report
supplied
by
the
LDB
17
Email from Vincent to Manoj Gupta; dated 28/09/2007; subject: RE: QGXE2A4042 / CLP - LDB Relays in Satellite SS2701A, SS-2702A/B/C Settings; Attachment: MM2 Setpoint File Information.pdf
A15
A16
Mott MacDonald
CTJV
A17
Mott MacDonald
CTJV
A18
Mott MacDonald
CTJV
A19
Mott MacDonald
CTJV
Mott MacDonald
CTJV
S.No.
Switch
Board
ID
Voltage
(kV)
Panel
Number
Feeder
Name
Device Type /
Manufacturer
CT
ratio
Device
Duty
Setting range
Setting
Remark
2000/1
1
SB27101A
33
A1
B1
Incoming
A/B TR27101 A/B
51
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
50
I>> = 0.05-40
50N
REF 542 +
51N
51G
400/1
A20
0.95
Curve = NI
0.12
Output to ATS
0.02
0.05
0.05 (NI)
Output to ATS
I0>> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
t0>>DT = 0.04 to 300s
0.05
Curve = DT
I0> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
t0>DT = 0.04 to 300s
I0>0.25
Curve = DT
0.42
t0>DT = 0.72
S.No.
Switch
Board
ID
Voltage
(kV)
Panel
Number
Feeder
Name
Mott MacDonald
CTJV
Device Type
/
Manufacturer
CT
ratio
Device
Duty
51
SB27101A
SB27101A
33
33
A2
B2
A4
B4
TR-27204
A/B
TR-27604
TR-27605
REF 542 +
REF 542 +
Setting range
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
50
I>>> = 0.05-40
t>>> = 0.015 to 300s
27
51N
I0> = 0.05-40
Curve = NI, EI, VI, DT
t0>DT = 0.04 to 300s
51
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
Setting
Remark
0.75
Curve = NI
0.15
9.85
0.015
600/1
600/1
A21
50
I>>> = 0.05-40
t>>> = 0.015 to 300s
27
51N
I0> = 0.05-40
Curve = NI, EI, VI, DT
t0>DT = 0.04 to 300s
50%
4s
CB Open
(Not to trip)
I0>0.15
Curve = DT
t0>DT = 0.12
1.25
Curve = EI
0.2
10.35
0.015
50%
4s
I0>0.15
Curve = DT
t0>DT = 0.12
CB Open
(Not to trip)
S.No.
Switch
Board
ID
Voltage
(kV)
Panel
Number
Feeder
Name
Mott MacDonald
CTJV
Device Type /
Manufacturer
CT
ratio
Device
Duty
51
SB27101A
33
A5
B5
TR-27603
TR-27606
REF 542 +
600/1
SB27101A
33
A6
B7
SB-27104
SB-27105
REF 542 +
600/1
Remark
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
Curve = EI
1.25
0.2
I>>> = 0.05-40
t>>> = 0.015 to 300s
27
51N
I0> = 0.05-40
Curve = NI, EI, VI, DT
I0>0.15
Curve = DT
t0>DT = 0.12
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
Curve = EI
50
I>>> = 0.05-40
t>>> = 0.015 to 300s
27
51N
I0> = 0.05-40
Curve = NI, EI, VI, DT
t0>DT = 0.04 to 300s
A22
Setting
50
51
Setting range
10.35
0.015
50%
4s
1.65
0.05
6.85
0.015
50%
4s
I0>0.15
Curve = DT
t0>DT = 0.12
S.No.
Switch
Board
ID
SB27101A
SB27102
SB27103
Voltage
(kV)
33
33
Panel
Number
A7
B6
RMU
outgoing
feeder
to SB27201
Feeder
Name
SB-27102
SB-27103
RMU
outgoing
feeder
Mott MacDonald
CTJV
Device Type /
Manufacturer
REF 542 +
7SJ600
CT
ratio
Device
Duty
400/1
400/1
Setting range
Setting
51
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
0.75
Curve = NI
0.29
50
I>>> = 0.05-40
t>>> = 0.015 to 300s
6.85
0.15
27
50%
4s
51N
I0> = 0.05-40
Curve = NI, EI, VI, DT
t0>DT = 0.04 to 300s
I0>0.25
Curve = DT
t0>DT = 0.12
51
I> = 0.1-4
Curve = NI, EI, VI, DT
k = 0.05 - 3.2
Curve = NI
0.7
0.2
50
I>>> = 0.1-25
t>>> = 0.0 to 60s
6.9
0.01
27
50%
4s
51N
I0> = 0.05-25
Curve = NI, EI, VI, DT
t0>DT = 0.0 to 60s
A23
Remark
I0>0.25
Curve = DT
t0>DT = 0.12
S.No.
Switch
Board
ID
Voltage
(kV)
Panel
Number
Feeder
Name
Mott MacDonald
CTJV
Device Type /
Manufacturer
CT
ratio
Device
Duty
51
SB27104
SB27105
33
RMU
outgoing
feeder BOG
Compressor
RMU
outgoing
feeder
7SJ600
600/1
A24
Setting range
I> = 0.1-4
Curve = NI, EI, VI, DT
k = 0.05 - 3.2
Setting
Remark
1.6
Curve = EI
0.05
50
I>>> = 0.1-25
t>>> = 0.0 to 60s
6.9
0.01
27
50%
4s
51N
I0> = 0.05-25
Curve = NI, EI, VI, DT
I0>0.15
Curve = DT
t0>DT = 0.12
Mott MacDonald
CTJV
A-3: Interface with Kahramaa - Schedule for 87L and 87T protection
S.No.
Switch
Board
ID
Voltage
(kV)
Panel
Number
From
1A
SS-2702
33
All
outgoing
33 kV
feeders
SS-2702
Device Type /
Manufacturer
CT
ratio
Device
Duty
33
All
outgoing
33 kV
feeders
Setting range
From
1B
Feeder
Name
up
stream
600/1
Solkor-N
B2-B5, B7
87L
Down
stream
600/1
A25
Setting
0.1
20
150
1
0.05
1
1
OFF
ON
0
0.1
20
150
1
0.05
1
1
OFF
ON
0
Remark
Differential current
1st Bias slope
2nd Bias slope
Bias break point
Differential delay
At up-stream relay
At down stream relay
S.No.
Switch
Board
ID
Interface
with KM
132 kV
SSRLS2
Voltage
(kV)
132
Panel
Number
132 kV
KM S/S
Outgoing
feeders
to QGXCLP
Feeder
Name
Mott MacDonald
CTJV
Device Type /
Manufacturer
7SD53
132
87L
800/1
C30
132 kV
KM S/S
Outgoing
feeders
to QGXCLP
Device
Duty
800/1
C30
C40
Interface
with KM
132 kV
SSRLS2
CT
ratio
800/1
REL 561
C40
87L
800/1
Setting range
I-Diff> = 0.1 - 20.00 A
I-Diff>Switch On
TD I-Diff>= 0.0 - 60.0 s
T310 Iphas = 0.0 to 0.5 s
Ic-Com = ON, OFF
IcSTAB/IcN = 2.0 - 4.0
I-Diff>> = 0.8 - 100.0 A
I-Diff>>Switch On
Inrush restraint = ON, OFF
I2/In = 10 - 45%
Cross block = NO, YES
Imax-inrush = 1.1 - 25.0 A
Cross B 2HM
CTFactor = 0.4-1.0
IminSat = 100-1000% In
IminOp = 20-150% In
IdiffLvl1= 20-150% Ib
IdiffLvl2= 30-150% Ib
ILvl1/2Cross = 100-1000% Ib
Evaluate = 2 of 4, 3 of 4
AsymDelay = 0.0 - 5.0 ms
DiffSync = Mater, Slave
CCComp = ON, OFF
A26
Setting
0.12
0.36
0
0
OFF
1.25
5
ON
15
NO
9
0
1
300
20
50
100
350
3 of 4
0
Master
Slave
OFF
Remark
I-Diff> pickup value
I-Diff> under switch on
Time delay for I-Diff
Charging current comp.
Ic stabilization
I-Diff>> pickup value
2nd Harmonic % of In
Max. inrush peak value
CT matching factor
Imin for saturation detection
Idiff pickup
Slope 1
Slope 2
Slope 2 intersection
Tripping condition
Asymmetrical delay
At Kahramma substation
At QGX-CLP SS-2702
Charging current comp.
S.N
o.
SB
ID
SB27101
Voltage
(kV)
33
Panel
Number
A1
B1
Feeder
Name
TR-27101
A/B
Mott MacDonald
CTJV
Device /
Manufactur
er
7UT612
CT
ratio
Up
stream
800/1
Device
Duty
87T
Down
stream
2000/1
Setting range
Diff. Prot.
INC. CHAR.START
INRUSH 2. HARM.
REST.n.HAR.
I-Diff>Mon
I>Curr. GUARD
DIFFw.IE1-MEAS
DIFFw.IE2-MEAS
I-DIFF> 0.05 - 2.00 (0.01)
T I-DIFF> = 0.0 - 60.00s
I-DIFF>> = 0.5-35.0 (0.1)
T-IDIFF>> = 0.0 - 60.00s
SLOPE 1= 0.1 - 0.5
BASE Point1 = 0.0 - 2.00
SLOPE 2 = 0.25 - 0.95
BASE Point2 = 0.0 - 10.0
I-REST. STARTUP = 0.0 - 2.0
START-FACTOR = 1.0 - 2.0
T START MAX = 0 - 180s
I-ADD ON STAB = 2.0 - 15.0
T ADD ON STAB = 2- 250
2. HARMONIC = 10- 80%
CROSSB.2.HARM = 2-1000
n. HARMONIC = 10 - 80%
CROSSB.n.HARM = 2-1000
IDIFFmax.n.HM = 0.5 - 20
I-DIFF>MON
T I-DIFF>MON = 1 - 10s
A27
Setting
ON
OFF
ON
5. Harm
ON
0
NO
NO
0.25
0
4.7
0
0.25
0.5
0.5
1
0.1
1
0
3
250
15
20
30
0
1.5
0.25
2
Remark
Id> pickup
Time delay for Id>
Id>> pickup
Time delay for Id>>
Differential relay characteristic
I-RESTRAINT for start detc.
Factor for increasing Char.
Starting time
Pickup for ADD on Stability
Cycles for ADD on stability
2nd Harmonic Content in Id>
Cycles for cross block 2nd harm.
nth Harmonic in Id>
Cylces for cross block nth harm.
Limit Id> max for nth harm. Rest.
Diff current for monitoring
Monitoring time delay
S.No.
Switch
Board
ID
SB27101
Voltage
(kV)
Panel
Number
A1
33
Feeder
Name
Mott MacDonald
CTJV
Device Type /
Manufacturer
TR-27101
A/B
7UT612
33
B1
2000/1
TR-27101
A/B
REF 542 +
87N
87T
VG = 0 - 11
Earthing P: Yes / No
Earthing S: Yes / No
Ip = 10 - 100000 A
Is = 10 - 100000 A
Ith = 0.1 - 0.5 Ir
URL = 0.5 - 5.0
SBRT = 0.2 - 2.0
SBRL = 1.00 - 2.00 Ir
Slope = 0.4 - 1.0
Trip Id> = 5.00-40.00
I2 Block= 0.1 - 0.3
I5 Block = 0.1 - 0.3
Down
stream
2000/1
A28
Setting range
REF Prot = ON, OFF,
BLOCK
I-REF> = 0.05 - 2.0 In
TD-IREF = 0.0 - 60.0 s
Slope = 0.00 - 0.95
Up
stream
800/1
A1
SB27101
Device
Duty
400/1
B1
CT
ratio
Setting
Remark
ON
0.25
0
0.5
Yes
Yes
437
1750
0.2
0.5
0.25
1
1
5
0.3
0.3
Threshold current
Unbiased region limit
Slightly biased threshold
Slightly biased region limit
Third region slope
Upper Id threshold for trip
2nd harmonic threshold
5th harmonic threshold
Mott MacDonald
CTJV
Voltage
Feeder Name
(kV)
Device Type /
Device
CT ratio
Setting range
Manufacturer
Duty
50N
51N
51G
400/1
REF 542 +
1 SB-27204
6.6
I0> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
t0>DT = 0.04 to 300s
U< = 0.1 - 1.2 Un
t< = 40 - 30,000 ms
87
VG = 0 - 11
Earthing P: Yes / No
Earthing S: Yes / No
Ip = 10 - 100000 A
Is = 10 - 100000 A
Ith = 0.1 - 0.5 Ir
URL = 0.5 - 5.0
SBRT = 0.2 - 2.0
SBRL = 1.00 - 2.00 Ir
Slope = 0.4 - 1.0
Trip Id> = 5.00-40.00
I2 Block= 0.1 - 0.3
I5 Block = 0.1 - 0.3
87L
Solkor-N
(33 kV side)
I0>> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
t0>>DT = 0.04 to 300s
600/1
A29
Remark
0.85
NI
0.07
I>> = 0.05-40
t>> = 0.02 to 300s
I0>> = 0.05 - 40
k = 0.05 - 1.5
27
PT
6.6/0.11
Incoming A/B
TR-27204 A/B
20000 kVA
Setting
1.6
0.015
0.05
0.05 (NI)
0.05
DT
0.72
0.25
DT
1.02
0.7
70
No
Yes
437
2092
0.1 Threshold current
0.5 Unbiased region limit
0.2 Slightly biased threshold
1 Slightly biased region limit
0.5 Third region slope
9 Upper Id threshold for trip
0.3 2nd harmonic threshold
0.3 5th harmonic threshold
0.2 Differential current
20 1st Bias slope
150 2nd Bias slope
1 Bias break point
0.05 Differential delay
1 CT raio correction
0 External trip delay
S.
Switch
No
Board ID
.
Voltage
Feeder Name
(kV)
Device Type /
Device
CT ratio
Setting range
Manufacturer
Duty
2500
2 SB-27204
6.6
Bus Coupler
Mott MacDonald
CTJV
REF 542 +
PT
6.6/ 3
/
51
25
0.110/ 3
3 SB-27204
6.6
REF 542 +
150/1
Fuse ABB-CEF
51N
51
4 SB-27204
6.6
TR-27303A/B
1600 kVA
REF 542 +
200/1
6.6
SB-27205A/B
REF 542 +
500/1
0.07
0.05 Delta voltage
10 Delta phase
15 Time delay
0.65
NI
0.2
200A
I0> = 0.05-40
Curve = NI, EI, VI, DT
t0>DT = 0.04 to 300s
DT
0.35
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
NI
0.19
I>>> = 0.05-40
t>>> = 0.015 to 300s
51N
I0> = 0.05-40
Curve = NI, EI, VI, DT
t0>DT = 0.04 to 300s
DT
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
NI
50
I>>> = 0.05-40
t>>> = 0.015 to 300s
51N
I0> = 0.05-40
Curve = NI, EI, VI, DT
t0>DT = 0.04 to 300s
A30
0.12
0.85
50
51
5 SB-27204
0.85
V = 0.02 - 0.4 Un
Phase = 5 - 50 Deg.
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
Remark
NI
TD = 0.2 - 1000s
51
DTR27305A/B
1000 kVA
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
Setting
20
0.015
0.25
0.12
2.35
0.05
11.75
0.015
0.25
DT
0.42
S.
Switch
No
Board ID
.
Voltage
Feeder Name
(kV)
Mott MacDonald
CTJV
Device Type /
Device
CT ratio
Setting range
Manufacturer
Duty
700/1
51N
51G
REF542+
REM 543
SB-27603
1 To
SB27606
11
Incoming
TR-27603
to
TR-27606
25000 kVA
400/1
I0>> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
t0>>DT = 0.04 to 300s
I0> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
t0>DT = 0.04 to 300s
27
87
VG = 0 - 11
Earthing P: Yes / No
Earthing S: Yes / No
Ip = 10 - 100000 A
Is = 10 - 100000 A
Ith = 0.1 - 0.5 Ir
URL = 0.5 - 5.0
SBRT = 0.2 - 2.0
SBRL = 1.00 - 2.00 Ir
Slope = 0.4 - 1.0
Trip Id> = 5.00-40.00
I2 Block= 0.1 - 0.3
I5 Block = 0.1 - 0.3
PT
6.6/0.11
REF542+
87L
Solkor-N
(33 kV side)
I>> = 0.05-40
t>> = 0.02 to 300s
I>>> = 0.05-40
Op. mode I>>>
600/1
Setting
EI
DT
0.15
0.12
0.25
DT
0.72
0.7 From 11 kV, 9500 kW
70 Motor relay
No
Yes
1 CT raio correction
OFF
ON
A31
Used for
51LR
4.75
2
Remark
S.
Switch
No
Board ID
.
Voltage
Feeder Name
(kV)
Mott MacDonald
CTJV
Device Type /
Device
CT ratio
Setting range
Manufacturer
Duty
TR-27303A/B
SB-27303
0.415 TR-27301A/B
SB-27301
1600 kVA
2500/1
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
50
I>> = 0.05-40
t>> = 0.02 to 300s
27
1.05
NI
0.09
4 For ATS
0.02 operation
REF 542 +
10/1
51G
51
LDBDTR27302,
27302, 27305,
2
27305,
0.415
27306,
27306,
27307 A/B
1000 kVA
27307 A/B
Remark
Setting
I0> = 0.05-40
Curve = NI, EI, VI, DT
t0>DT = 0.04 to 300s
DT
I> = 0.05-40
Curve = NI, EI, VI, DT
k = 0.05 - 1.5
NI
50
I>> = 0.05-40
t>> = 0.02 to 300s
27
1600/1
0.7
70
0.25
0.52
0.95
0.09
6.2 For ATS
0.02 operation
REF 542 +
10/1
51G
A32
I0> = 0.05-40
Curve = NI, EI, VI, DT
t0>DT = 0.04 to 300s
0.7
70
DT
0.25
0.52
Mott MacDonald
CTJV
Relay
REM
543
Protection
Duty
51(I>)
50 (I>>>)
51N(I0>)
Functional
block
name
NOC3Low
NOC3Inst
NEF1Low
27(U<)
27 (U<<)
UV3LOW
UV3High
59 (U>)
OV3Low
49
Thermal overload
TOL3Dev
46
NPS3Low
66
Start-up supervision
MotStart
37 (I<)
Under current
NUC3St1
51LR
NOC3High
47
PSV3ST1
87M
Motor differential
Diff6G
Function name
A33
SB-27201
SB-27204
Voltage
Feeder Name
(kV)
Device
Type
CT
ratio
PT
ratio
Mott MacDonald
CTJV
Device
Setting range
Duty
Setting
6.6
27-PM7102
LNG Loading
REM 543
pump
589 kW
100/1
59
1.15
5
1
49
Ist = 0.1-10.00 In
Tst = 0.1 - 120.0 s
NC-st = 1-3
Device Type = 0-6
Trip Temp. = 80-120 %
Alarm Temp. = 40-100%
Reset Temp. = 40-100%
Am Temp.= -50-100 Deg C
TC-cooling = 1.0-10.0
TC-Heating = 1-999 min
ST-CS = 0.0-999.0 min
LT-CS = 0.0-999.0 min
p = 0.0 - 1.0
S-TR =50-350 Deg C
Tmax S = 0.0-350 Deg C
ST-CR = 0.0-999.0 min
LT-CR = 0.0-999.0 min
p = 0.0 - 1.0
R-TR =50-350 Deg C
Tmax R = 0.0-350 Deg C
3.6
1
3
3
120
90
60
50
6
30
14
69
0.5
70
155
4
69
0.25
80
200
46
66
Operation Mode = 0 - 2
Ist = 1.0 - 10.0 In
Tst = 0.3 - 250 s
Time limit = 1.0 - 500.0s
Countdwn Rate = 2.0-250 s/h
Stall time = 2.0 - 120.0s
1
3.6
1.1
2
3
37
Op. mode
Op. criteria
I< = 0.1 - 0.99 In
t< = 0.1 - 600.0 s
I< Block
t< blocking
2
0
0.1
300
6.6/0.1
1
51
A34
0.7
0.5
1
2
0.05
5
1
7
3600
1800
Disable
0
1.35
EI
0.74
160 A
65
DT
0.12
2.7
0.5
SB-27603
SB-27606
Voltage
Feeder Name
(kV)
Device
Type
CT
ratio
PT
ratio
Mott MacDonald
CTJV
Device
Setting range
Duty
Setting
11
27-KM7101
Motor 9500
kW
REM 543
0.7
0.5
1
59
1.15
5
1
49
Ist = 0.1-10.00 In
Tst = 0.1 - 120.0 s
NC-st = 1-3
Device Type = 0-6
Trip Temp. = 80-120 %
Alarm Temp. = 40-100%
Reset Temp. = 40-100%
Am Temp.= -50-100 Deg C
TC-cooling = 1.0-10.0
TC-Heating = 1-999 min
ST-CS = 0.0-999.0 min
LT-CS = 0.0-999.0 min
p = 0.0 - 1.0
S-TR =50-350 Deg C
Tmax S = 0.0-350 Deg C
ST-CR = 0.0-999.0 min
LT-CR = 0.0-999.0 min
p = 0.0 - 1.0
R-TR =50-350 Deg C
Tmax R = 0.0-350 Deg C
3.7
10
3
3
120
90
60
50
6
20
14
69
0.5
90
155
4
69
0.25
100
200
46
2
0.05
8
1
7
3600
1800
66
Operation Mode = 0 - 2
Ist = 1.0 - 10.0 In
Tst = 0.3 - 250 s
Time limit = 1.0 - 500.0s
Countdwn Rate = 2.0-250 s/h
Stall time = 2.0 - 120.0s
47
Operation Mode = 0 - 7
U2> = 0.01 - 1.00
t2> = 0.04 - 60.00 s
5
0.05
1
87
Id> = 5 - 50%
TP1 = 0.0 - 1.0 In
Starting ratio = 10 - 50%
TP2 = 1.0 - 3.0 In
Id>> = 5 - 30 In
10.0
0.5
50
1.5
5
51
700/1 11/0.11
1
3.7
11
40
30
2 (EI)
A35
1.55
0.78
2.8
0.5
1
4.75
2
1 (DT)
15
0.12
Mott MacDonald
CTJV
S.No.
Relay location
CT
ratio
Reference
location voltage
Switch Board
number
DTR-27305
150/1
6.6 kV
SB-27204
TR-27303
200/1
6.6 kV
SB-27204
MR-27PM7104A
100/1
6.6 kV
SB-27205
MR-27KM7101C
700/1
11 kV
SB-27603
TR-27204
600/1
33 kV
SB-27101
TR-27201
400/1
33 kV
SB-27101
B1
CTJV
S.No.
Relay location
CT ratio
Reference location
voltage
DTR-27305
150/1
6.6 kV
SB-27204
B2
CTJV
S.No.
Relay location
CT ratio
Reference location
voltage
TR-27303
200/1
6.6 kV
SB-27204
B3
CTJV
S.No.
Relay location
CT ratio
Reference location
voltage
MR-27PM7104A
100/1
6.6 kV
SB-27205
B4
CTJV
S.No.
Relay location
CT ratio
Reference location
voltage
MR-27KM7101C
700/1
11 kV
SB-27603
Settings of relay at the outgoing RMU feeders from switchboard SB-27104/5, is set equal to the relay
settings of the 33kV feeder TR-27601 from the switchboard SB-29103 of the QGX system. The time
margin with the upstream relay will not be available when the SB-27601 and SB-27602 are supplied
either from the QGX system or CLP system; due to the tight relay co-ordination at the 33kV and upstream relays.
B5
CTJV
S.No.
Relay location
CT ratio
Reference location
voltage
TR-27204
600/1
33 kV
SB-27101
B6
CTJV
S.No.
Relay location
CT ratio
Reference location
voltage
TR-27201
400/1
33 kV
SB-27101
Settings of relay at the outgoing RMU feeders from switchboard SB-27102/3, is set equal to the relay
settings of the 33kV feeder TR-27201 from the switchboard SB-29103 of the QGX system. As shown
the above TCC, time margin is provided between the relay RMU-27103 and relay at the incomer feeder
TR-27201 from the switchboard SB-27101 (of the CLP system). The same time margin will not be
available with the upstream relays, when the SB-27201 is supplied from the QGX system due to the tight
relay co-ordination at the 33kV and up-stream relays of the QGX system.
B7