Control
Performance
Energy savings
Better building
management
TABLE OF CONTENTS
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
Power
Building
Function
Humidity
Control
Application
Outputs /
Inputs
Controller
Relay Pack
Typical
Application
Line
Voltage
Commercial or
Hospitality
Yes
2 or 4 pipe,
Up to 3
speed fan
1H/1C with
Reheat
SER8350A0Axx
SC3500E5045
Page: 38, 42
1H/1C with 4
inputs
and reheat
SER8350A0Axx
SC3504E5045
Page: 40, 44
1H/1C with 4
inputs reheat
and occ.
output
SER8350A0Axx
SC3514E5045
Page: 44
1H/1C with
pulsed reheat
SER8300A0Axx
SC3400E5045
Page: 42
1H/1C with
pulsed reheat
and 4 inputs
SER8300A0Axx
SC3404E5045
Page: 38
1H/1C with
Reheat
SER8350A0Axx
SC3500E5045
Page: 36, 50
1H/1C with 4
inputs
and reheat
SER8350A0Axx
SC3504E5045
Page: 40, 48
1H/1C with 4
inputs reheat
and occ.
output
SER8350A0Axx
SC3514E5045
Page: 44
1H/1C with
pulsed reheat
SER8300A0Axx
SC3400E5045
Page: 42
1H/1C with
pulsed reheat
and 4 inputs
SER8300A0Axx
SC3404E5045
Page: 38
3 fan outputs
SER8300A0Axx
SC3300E5000
Page: 46
No
Yes
No
2 Pipe, Up to
3 speed fan
2 or 4 pipe,
Up to 3
speed fan
2 Pipe, Up to
3 speed fan
Slave fan
control only
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
Part Number
Description
Humidity
PIR Cover
SER8300A0Axx
No
No
Stand-alone
SER8300A0Bxx
No
No
BACnet
SER8300A0Pxx
No
No
SER8300A5Axx
No
Yes
Stand-alone
SER8300A5Bxx
No
Yes
BACnet
SER8300A5Pxx
Yes
Yes
SER8350A0Axx
Yes
No
Stand-alone
SER8350A0Bxx
Yes
No
BACnet
SER8350A0Pxx
Yes
No
SER8350A5Axx
Yes
Yes
Stand-alone
SER8350A5Bxx
Yes
Yes
BACnet
SER8350A5Pxx
Yes
Yes
Communication
Part Number
Description
SC3500E5045
SC3504E5045
Transformer relay pack five relay fan outputs, and four outputs
SC3514E5045
Transformer relay pack five relay outputs, smart VDC OCC output, and four inputs
SC3400E5045
Transformer relay pack four relay outputs and smart VDC output
SC3404E5045
Transformer relay pack four relay outputs, smart VDC output, and four inputs
SC3300E5045
Power
Part Number
Description
SED-DOR-P-5045
SED-WIN-P-5045
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
Occupancy sensing
Open
communications
Energy savings
Advance control of
your building with
truly open, integrated
communications.
Open protocol options
include Zigbee Pro
wireless and BACnet.
Easy to install
Temperature and
humidity sensing
Deliver efficient,
measureable control.
If you can measure it,
you can control itproviding more precise
occupant comfort and
productivity.
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
Unparalelled design
and customization
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
Heating Coil
FAN
2-Position
Cooling
Valve
2-Position
Heating
Valve
SED-DOR-P-5045
SER8300
SC3500E
Password
BI1
BI2
RUI1
RBI2
AutoMode
C or F
RH disp
Pulsed Heating
Pipe No
Seq. Operat
Fan Menu
Deh. lockout
Dehumidify
Deh. hyster
Deh. max cool
Standby time
Unocc. time
Standby heat
Standby cool
Unocc heat SP
Unocc cool SP
Max heating
Max cooling
Prop. band
T. Occup. time
Min. deadband
calibr. temp.
calibr. humid.
Auto Fan Funct
Cooling cph
Heating cph
Cooling Valve
Heat Valve
Fan Control
Configuration settings
0 is factory set, range is: 0-9999
Door
None
None
None
ON
As per user. Default value = F
OFF
OFF
4.0
2 = Cooling / Heating 4 pipes
2
ON
As per user. Default value = 50%. Range = 30% to 95%
As per user. Default value = 5%. Range = 2% to 20%
As per user. Default value = 100%. Range = 20% to 100%
0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
69 F is factory set, range is: 40 to 90 F ( 4.5 to 32.0 C )
78 F is factory set, range is: 54 to 100 F ( 12.0 to 37.5 C )
As per user. Default value = 62 F ( 17 C ). Range = 40 to 90 F ( 4.5 to 32.0 C )
As per user. Default value = 80 F ( 27 C ). Range = 54 to 100 F ( 12 to 37.5 C )
As per user. Default value = 90 F ( 32 C ). Range = 40 to 90 F ( 4.5 to 32.0 C )
As per user. Default value = 54 F ( 12 C ). Range = 54 to 100 F ( 12 to 37.5 C )
3 F is factory set, range is: 2 to 10 F ( 0.6 to 5.6 C )
As per user. Default value 2 hours. Range = 0 to 24 hours
As per user. Default value 2.0 F ( 1.0 C ).
0 F or C
0 F or C
AS or AS AD
As per user. 4 to 8 CPH
As per user. 4 to 8 CPH
NC
NC
ON
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
Configuration
parameter
name
SER8300
Controller
SC3500E
Relay Pack
Tx/Rx
Tx-Rx
7 VDC
7 VDC
COM
COM
BI1
SCOM
BI2
White - Neutral
Options
BACnet and Wireless communication models
available (see Appendix B for network wiring).
SC3500E
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
10
SER8350A0AXX - SC3404E5045: COOLING AND ELECTRIC HEAT: 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN,
DEHUMIDIFICATION, 2-POSITION VALVES
Cooling Coil
Electric Heat
FA N
SER8300
SC3404E
Configuration
parameter
name
Configuration settings
Password
BI1
BI2
RUI1
RBI2
AutoMode
C or F
RH disp
Pulsed Heating
Pipe No
Seq. Operat
Fan Menu
Deh. lockout
Dehumidify
Deh. hyster
Deh. max cool
Standby time
Unocc. time
Standby heat
Standby cool
Unocc heat SP
Unocc cool SP
Max heating
Max cooling
Prop. band
T. Occup. time
Min. deadband
calibr. temp.
calibr. humid.
Auto Fan Funct
Cooling cph
Heating cph
Cooling Valve
Heat Valve
Fan Control
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
SSR
11
SER8350
Controller
SC3404E
Relay Pack
Tx/Rx
Tx-Rx
7 VDC
7 VDC
COM
COM
BI1
RUI 1
SCOM
SCOM
BI2
RBI 2
SS
RS
Heat SSR
Heat +
Options
BACnet and Wireless communication models
available (see Appendix B for network wiring).
White - Neutral
1 Tx / Rx
2 7 Vdc
3 Com
4 RUI 1
SC3404E5045
008-0565
5 SCom
6 RBI 2
7 SS
FAN
LOW
8 RS
9 Heat-
Power
Supply
1/2 HP FAN
MED
Max
10 Heat+
5A
Max
WHITE
BLACK
RED
BLUE
FAN
HIGH
BROWN
COOL
YELLOW
STATUS
Use copper conductors
75oC min. only.
Made in Canada
SC3404E
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
12
SED-WIN-P-5045
Heating/Cooling Coil
FAN
Supply Sensor
C/O Sensor
Changeover
Sensor:
10KOhm
typetype
2 2.
Changeover
Sensor:
10K Ohm
Supply Sensor: 10KOhm type 2
Switch:
VWA5000W5045W.
Refer Window
to Schneider
Electric
Catalog for valves and actuators.
SC3504E
Configuration
parameter
name
Configuration settings
Password
BI1
BI2
RUI1
RBI2
AutoMode
C or F
RH disp
Pulsed Heating
Pipe No
Seq. Operat
Fan Menu
Deh. lockout
Dehumidify
Deh. hyster
Deh. max cool
Standby time
Unocc. time
Standby heat
Standby cool
Unocc heat SP
Unocc cool SP
Max heating
Max cooling
Prop. band
T. Occup. time
Min. deadband
calibr. temp.
calibr. humid.
Auto Fan Funct
Cooling cph
Heating cph
Cooling Valve
Heat Valve
Fan Control
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
SER8300
Occupied Mode:
Setpoints will revert to those defined by occupied
cooling and heating.
Stand-by Mode (only available when PIR
motion detector cover is used):
Setpoints will revert to those defined by stand-by
cooling and heating.
Unoccupied Mode:
Setpoints will revert to those defined by unoccupied
heating and cooling.
Occupied Override Mode:
The system will revert to occupied mode for the
duration determined by the ToccTime parameter.
SER8300
Controller
SC3504E
Relay Pack
Tx/Rx
Tx-Rx
7 VDC
7 VDC
COM
COM
BI1
RUI 1
SCOM
SCOM
BI2
RBI 2
SS
RS
Options
BACnet and Wireless communication models
available (see Appendix B for network wiring).
SC3504E
L
V
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
13
14
Electric Heater
FAN
Configuration
parameter
name
Password
BI1
BI2
RUI1
RBI2
AutoMode
C or F
RH disp
Pulsed Heating
Pipe No
Seq. Operat
Fan Menu
Deh. lockout
Dehumidify
Deh. hyster
Deh. max cool
Standby time
Unocc. time
Standby heat
Standby cool
Unocc heat SP
Unocc cool SP
Max heating
Max cooling
Prop. band
T. Occup. time
Min. deadband
calibr. temp.
calibr. humid.
Auto Fan Funct
Cooling cph
Heating cph
Cooling Valve
Heat Valve
Fan Control
SC3400E
Configuration settings
0 is factory set, range is: 0-9999
None
None
None
None
ON
As per user. Default value = F
ON
ON
2.0
2 = Cooling with electric reheat
2
ON
As per user. Default value = 50%. Range = 30% to 95%
As per user. Default value = 5%. Range = 2% to 20%
As per user. Default value = 100%. Range = 20% to 100%
0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
69 F is factory set, range is: 40 to 90 F ( 4.5 to 32.0 C )
78 F is factory set, range is: 54 to 100 F ( 12.0 to 37.5 C )
As per user. Default value = 62 F ( 17 C ). Range = 40 to 90 F ( 4.5 to 32.0 C )
As per user. Default value = 80 F ( 27 C ). Range = 54 to 100 F ( 12 to 37.5 C )
As per user. Default value = 90 F ( 32 C ). Range = 40 to 90 F ( 4.5 to 32.0 C )
As per user. Default value = 54 F ( 12 C ). Range = 54 to 100 F ( 12 to 37.5 C )
3 F is factory set, range is: 2 to 10 F ( 0.6 to 5.6 C )
As per user. Default value 2 hours. Range = 0 to 24 hours
As per user. Default value 2.0 F ( 1.0 C ).
0 F or C
0 F or C
AS or AS AD
As per user. 4 to 8 CPH
As per user. 4 to 8 CPH
NC
NC
ON
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
SER8300
15
SER8350
Controller
Tx-Rx
Tx/Rx
7 VDC
7 VDC
COM
COM
BI1
Heat SSR
SCOM
Heat +
BI2
SC3400E
Relay Pack
SC3400E
L
V
Options
BACnet and Wireless communication models
available (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
16
FAN
Fresh Air
C/O Sensor
Return Air
Configuration
parameter
name
Configuration settings
Password
BI1
BI2
RUI1
RBI2
AutoMode
C or F
RH disp
Pulsed Heating
Pipe No
Seq. Operat
Fan Menu
Deh. lockout
Dehumidify
Deh. hyster
Deh. max cool
Standby time
Unocc. time
Standby heat
Standby cool
Unocc heat SP
Unocc cool SP
Max heating
Max cooling
Prop. band
T. Occup. time
Min. deadband
calibr. temp.
calibr. humid.
Auto Fan Funct
Cooling cph
Heating cph
Cooling Valve
Heat Valve
Fan Control
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
SER8300
17
SER8300
Controller
Tx-Rx
7 VDC
Unoccupied Mode:
Setpoints will revert to those defined by unoccupied
heating and cooling. The fresh air damper will
close.
Occupied Override Mode:
The system will revert to occupied mode for the
duration determined by the ToccTime parameter.
SC3514E
Relay Pack
Tx/Rx
To Fan Coil Unit
(High Voltage Side)
7 VDC
COM
COM
BI1
RUI 1
SCOM
SCOM
BI2
RBI 2
SS
OCC
RS
Fresh Air
Damper
Relay
SC3514E
L
V
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
Options
18
SER8300A0AXX -SC3500E5045 -SC3300E5045: HEATING/COOLING: 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN,
2-POSITION VALVES WITH SLAVE RELAY PACK
Cooling Coil Heating Coil
FAN
FAN
SC3300E
1 Tx / Rx
2 7 Vdc
3 Com
Power
Supply
SC3300E5045
008-0563
FAN
LOW
9 Heat-
5A
Max
WHITE
BLACK
RED
1/2 HP FAN
MED
Max
10 Heat+
BLUE
FAN
HIGH
BROWN
COOL
YELLOW
STATUS
Use copper conductors
75oC min. only.
2-Position
Cooling
Valve
2-Position
Heating
Valve
Made in Canada
1 Tx / Rx
2 7 Vdc
3 Com
Power
Supply
SC3500E5045
008-0566
FAN
LOW
1/2 HP FAN
MED
Max
5A
Max
WHITE
BLACK
RED
BLUE
FAN
HIGH
COOL
BROWN
YELLOW
ORANGE
HEAT
ORANGE
90-277 Vac
10A Max
Amb. Temp. 50oC
STATUS
Use copper conductors
75oC min. only.
Made in Canada
SC3500E
Configuration
Configuration settings
parameter name
PswrdSet
0 is factory set, range is: 0-1000
BI1
None
BI2
None
RUI1
None
RBI2
None
MenuScro
ON
AutoMode
ON
C or F
As per user. Default value = F
%RH disp
OFF
Lockout
As per user. Default value = 0 No lock
PulsedHt
OFF
Pipe No
4.0
SeqOpera
2 = Cooling / Heating 4 pipes
Fan Menu
2
DHumiLCK
ON
%RH set
As per user. Default value = 50%. Range = 30% to 95%
DehuHyst
As per user. Default value = 5%. Range = 2% to 20%
DehuCool
As per user. Default value = 100%. Range = 20% to 100%
St-By TM
0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
Unocc TM
0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
St-By HT
69 F is factory set, range is: 40 to 90 F ( 4.5 to 32.0 C )
St-By CL
78 F is factory set, range is: 54 to 100 F ( 12.0 to 37.5 C )
Unocc HT
As per user. Default value = 62 F ( 17 C ). Range = 40 to 90 F ( 4.5 to 32.0 C )
Unocc CL
As per user. Default value = 80 F ( 27 C ). Range = 54 to 100 F ( 12 to 37.5 C )
heat max
As per user. Default value = 90 F ( 32 C ). Range = 40 to 90 F ( 4.5 to 32.0 C )
cool min
As per user. Default value = 54 F ( 12 C ). Range = 54 to 100 F ( 12 to 37.5 C )
Pband
3 F is factory set, range is: 2 to 10 F ( 0.6 to 5.6 C )
Set Type
Permanent
SptFunc
Dual Stp or AttchStp
TOccTime
As per user. Default value 2 hours. Range = 0 to 24 hours
deadband
As per user. Default value 2.0 F ( 1.0 C ).
cal RS
0 F or C
cal RH
0 F or C
Auto Fan
AS or AS AD
Cool cph
As per user. 4 to 8 CPH
Heat cph
As per user. 4 to 8 CPH
CoolNoNc
NC
HeatNoNc
NC
Fan Cont
ON
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
SER8300
19
SER8300
Controller
SC3500E
Relay Pack
Tx-Rx
Tx/Rx
7 VDC
7 VDC
COM
COM
BI1
SC3300E Slave Relay Pack
SCOM
Tx/Rx
BI2
7 VDC
COM
Options
BACnet and Wireless communication models
available (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
White - Neutral
SC3500E
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
20
Heating/Cooling Coil
FAN
Supply Sensor
C/O Sensor
Changeover Sensor: 10K Ohm type 2.
Supply Sensor: 10K Ohm type 2.
Window Switch: Generic Window Switch
Configuration parameter
name
SC3504E
Configuration settings
PswrdSet
BI1
BI2
RUI1
RBI2
MenuScro
AutoMode
C or F
%RH disp
Lockout
PulsedHt
Pipe No
SeqOpera
Fan Menu
DHumiLCK
%RH set
DehuHyst
DehuCool
St-By TM
Unocc TM
St-By HT
St-By CL
Unocc HT
Unocc CL
heat max
cool min
Pband
Set Type
SptFunc
TOccTime
DoorTime
deadband
cal RS
cal RH
0 F or C
Auto Fan
Cool cph
Heat cph
CoolNoNc
HeatNoNc
Fan Cont
AS or AS AD
As per user. 4 to 8 CPH
As per user. 4 to 8 CPH
NC
NC
ON
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
SER8300
Occupied Mode:
Setpoints will revert to those defined by occupied
cooling and heating.
Stand-by Mode (only available when PIR
motion detector cover is used):
Setpoints will revert to those defined by stand-by
cooling and heating.
Unoccupied Mode:
Setpoints will revert to those defined by unoccupied
heating and cooling.
Occupied Override Mode:
The system will revert to occupied mode for the
duration determined by the ToccTime parameter.
SER8300
Controller
SC3504E
Relay Pack
Tx/Rx
Tx-Rx
7 VDC
7 VDC
COM
COM
BI1
SCOM
RUI 1
SCOM
Window Contact
BI2
RBI 2
SS
RS
Options
BACnet and Wireless communication models
available (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2 pipe systems (with
changeover).
SC3504E
L
V
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
21
22
SER8300A0AXX - SC3500E5045: HEATING/COOLING: 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION
VALVES WITH WIRED DOOR SWITCH
Cooling Coil Heating Coil
FA N
2-Position
Cooling
Valve
Door Switch
2-Position
Heating
Valve
Door Switch: Generic wired door switch.
SC3500E
Configuration
parameter
name
Configuration settings
Password
BI1
BI2
RUI1
RBI2
AutoMode
C or F
RH disp
Pulsed Heating
Pipe No
Seq. Operat
Fan Menu
Deh. lockout
Dehumidify
Deh. hyster
Deh. max cool
Standby time
Unocc. time
Standby heat
Standby cool
Unocc heat SP
Unocc cool SP
Max heating
Max cooling
Prop. band
T. Occup. time
Min. deadband
calibr. temp.
calibr. humid.
Auto Fan Funct
Cooling cph
Heating cph
Cooling Valve
Heat Valve
Fan Control
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
SER8300
23
SER8300
Controller
SC3500E
Relay Pack
Tx-Rx
Tx/Rx
7 VDC
7 VDC
COM
COM
BI1
SCOM
Door Contact
BI2
White - Neutral
Options
SC3500E
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
24
25
120
6.1 Meters
(20 Feet)
CENTER
15
15
6.1 Meters
(20 Feet)
4.6 Meters
(15 Feet)
45
4.6 Meters
(15 Feet)
CENTER
6.1 Meters
(20 Feet)
Energy savings
50%
40%
30%
50
45
40
35
20%
30
25
20
10%
15
10
5
0
0%
0
10
12
14
16
18
20
22
24
Savings
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
65
60
55
Saving Percentage
75
70
26
Wireless communication
+
-
ref
+
-
ref
+
-
Notes:
- No communication wires needed
ref
Notes:
- Wiring should be daisy chained
- Respect polarity
- If using 2 conductors shielded wires, connect
the shield of each feed together on the back of the
controller. ONLY ground the shield at one location. DO
NOT connect the shield to the ref terminal.
Unoccupied cool
24.5C
76F
Stand-by cool
Occupied heat
Stand-by heat
22C
72F
Deadband
Deadband
22C
72F
Deadband
70F
21C
70F
21C
Stand-by
time
66F
19C
Unoccupied
time
Unoccupied heat
Movement detected
Stand-by timer reset
62F
16.5C
Into Unoccupied
mode
Time
Next movement
detected
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
Occupied cool
27
Model selection
Window Switch
Door Switch
SED-WIN-P-5045
SED-DOR-P-5045
Pull Tab
Hidden Switch
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
28
Specifications
Power requirements:
Operating conditions:
0 C to 50 C ( 32 F to 122 F )
24.38 mm
(0.960)
21.13 mm
(0.832)
Dimensions
8.84 mm
(0.348)
118 mm
(4.646)
121.92 mm
(4.800)
18.16 mm
(0.716)
3.18 mm
18.16 mm
(0.716)
18.16 mm
(0.716)
35.97 mm
(1.416)
39.37 mm
(1.550)
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
(0.125)
29
Product overview
The SER8300 Fan Coil Controller offers a new cost-effective solution for upgrading line-voltage fan coil
unit thermostats. The SER8300 terminal Equipment Fan Coil Unit Controllers are available as BACnet
MSTP or wireless ZigBee Pro networked models.
No previous building automation training is required for the easy installation and commissioning process.
Installation can be completed in approximately fifteen minutes, reducing costs and providing increased
savings.
The SC3000 Series Line Voltage Switching Transformer Relay Pack Controllers has been designed for silent
control of typical high voltage fan coil device loads (90 to 277 VAC multi-voltages capable).
It uses advanced microprocessor-based circuitry with a built-in transformer that eliminates all typical
required peripheral components when automating a Fan Coil unit with traditional building automation
systems.
The SC3000 Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the
control of a single master SER83XX Terminal Equipment Controller.
A single SER83XX Terminal Equipment Controller can control up to 10x SC3000 Series Relay Pack. The
SC3000 Series Relay Packs are line-powered units.
The extremely compact unit locally contains all the relay outputs for fan switching and valve control.
Models are also available for extra monitoring / control inputs of the Fan Coil Units.
H
Electrical
Cabinet
C
FAN
FAN
Star topology
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
30
Operating conditions:
0% to 95% RH non-condensing
Approximate shipping weight:
0.75lb (0.34kg)
33 mm
(1.30)
Dimensions
100 mm (3.94)
70 mm (2.75)
122 mm (4.80)
80 mm (3.15)
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
80 mm (3.15)
31
120 mm (4.722)
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
25 mm
(0.990)
86 mm (3.378)
32
Specifications
Terminal Equipment Controller power requirements
Operating conditions
0 C to 50 C ( 32 F to 122 F )
0% to 95% R.H. non-condensing
Storage conditions
Temperature sensor
0.1 C ( 0.2 F )
4.5 C to 32 C ( 40 F to 90 F )
Binary inputs
Wire gauge
0.34 kg ( 0.75 lb )
Please check with your local government for instruction on disposal of this product.
Schneider Electric - Small Building Systems Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malm, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
AG-SER8300-FCU-A4.EN.10.2013.v1
www.schneider-electric.com/buildings
October 2013 ct
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE
FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND
(2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT
MAY CAUSE UNDESIRED OPERATION.