Вы находитесь на странице: 1из 1

Marquee at Islamabad Club

Islamabad

Dated: 02-06-2016

SCHEDULE OF KITCHEN HOOD EXHAUST FANS


Description

Unit

LG-KX-01

LG-KX-02

LG-KX-03

LG-KX-04

GF-KX-01

GF-KX-02

GF-KX-03

GF-KX-04

GF-KX-05

GF-KX-06

GF-KX-07

Quantity

No.

Roof

Roof

Roof

Roof

Roof

Roof

Roof

Roof

Roof

Roof

3 Deck Oven Hood

Halwai Burner
Hood

Lower Ground
Tandoor Hood

Dishwasher Hood

Pantry Hood

Ground Floor
Tandoor Hood

Continental Heavy
Burner Hood

Chinese Hood

Pakistani Burners
Hood

BBQ Hood
4800

Location

CFM

1200

4000

1650

Roof
Lower Ground
Kitchen Burner
Hood
2400

1200

1200

3600

Roof
Continental(fryer,
griddle, stove)
Hood
3500

2450

2450

6500

Inch WC

1.5

1.5

1.50

1.00

1.00

1.00

1.5

1.5

RPM

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

960
Kitchen Hood
Exhaust
60

Spaces Served
Supply Air Quantity
External Static Pressure
Fan Blower Revolution
Duty
Max.Sound Level at 1 meter

dB

Backward curve
Backward curve
Backward curve
Backward curve
Backward curve
Backward curve
Backward curve
Backward curve
Backward curve
Backward curve
Backward curve
Backward curve
blower, SWSI
blower, SWSI
blower, SWSI
blower, SWSI
blower, SWSI
blower, SWSI
blower, SWSI
blower, SWSI
blower, SWSI
blower, SWSI
blower, SWSI
blower, SWSI
centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan centrifugal B.D fan
having grease
having grease
having grease
having grease
having grease
having grease
having grease
having grease
having grease
having grease
having grease
having grease
protection/ grease protection/ grease protection/ grease protection/ grease protection/ grease protection/ grease protection/ grease protection/ grease protection/ grease protection/ grease protection/ grease protection/ grease
absorbent material absorbent material absorbent material absorbent material absorbent material absorbent material absorbent material absorbent material absorbent material absorbent material absorbent material absorbent material

Configuration

Construction
Max.Fan Outlet Velocity

FPM

Top Dischage
& side Intake

Top Dischage
& side Intake

Top Dischage
& side Intake

1600

1600

1600

Class-F Insulation Class-F Insulation Class-F Insulation


IP-55 Panel
IP-55 Panel
IP-55 Panel

Motor Protection
Motor Revolution

GF-KX-08

RPM

1450

1450

1450

Top Dischage
& side Intake

Top Dischage
& side Intake

Top Dischage
& side Intake

Top Dischage
& side Intake

Top Dischage
& side Intake

Top Dischage
& side Intake

Top Dischage
& side Intake

Top Dischage
& side Intake

Top Dischage
& side Intake

1600

1600

1600

1600

1600

1600

1600

1600

1600

Class-F Insulation Class-F Insulation Class-F Insulation Class-F Insulation Class-F Insulation Class-F Insulation Class-F Insulation Class-F Insulation Class-F Insulation
IP-55 Panel
IP-55 Panel
IP-55 Panel
IP-55 Panel
IP-55 Panel
IP-55 Panel
IP-55 Panel
IP-55 Panel
IP-55 Panel
1450

1450

1450

1450

1450

1450

1450

1450

1450

Drive

Belt Drive with


Belt Drive with
Belt Drive with
Belt Drive with
Belt Drive with
Belt Drive with
Belt Drive with
Belt Drive with
Belt Drive with
Belt Drive with
Belt Drive with
Belt Drive with
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley Pitch Motor Pulley

Electrical Characteristic

380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50 380~440V /3Ph/ 50
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Drain Connection
for Grease,

Accessories

Remarks

Weather Proof
Canopy
along with Fan

Weather Proof
Canopy
along with Fan

Drain Connection
for Grease,
Weather Proof
Canopy
along with Fan

A. Unit Type:
1. B.D. = Belt Driven
2. D.D. = Direct Driven
A- Motor power input to be provided by the manufacturer / Supplier along with data sheet.
B- Computer selection of each model Fan to be provided by the suppliers for Consultant approval along with fan
dimensions.
C- Fans to be installed at Roof, should have weather proof construction.

SEM Engineers

Weather Proof
Canopy
along with Fan

Weather Proof
Canopy
along with Fan

Weather Proof
Canopy
along with Fan

Weather Proof
Canopy
along with Fan

Drain Connection
for Grease,

Drain Connection
for Grease,

Drain Connection
for Grease,

Drain Connection
for Grease,

Weather Proof
Canopy
along with Fan

Weather Proof
Canopy
along with Fan

Weather Proof
Canopy
along with Fan

Weather Proof
Canopy
along with Fan

Weather Proof
Canopy
along with Fan