Академический Документы
Профессиональный Документы
Культура Документы
PROJECT
Date
Capacity
Design
Item
Design Class
Class 1
Class 2
Class 3
Once through
Cooling water
system
Design cooling
duty
Cooling water
design flow,
hydraulics
CW pumps
sparing
Chlorination
system
Capacity based on
2ppm continuous
dozing. 5ppm
intermittent shock
dosing capability with
extra capacity from
storage tank.
Capacity based on
2ppm continuous
dozing.
5ppm intermittent
shock dosing capability
with extra capacity
from storage tank.
2 x 100% system
1 x 100% system
2 x 130% system
(allowance for sea
water fouling)
Chilling system
Chiller duty
Chiller sparing
Expandability
Design Class
Page 1 of
Design
Item
PROJECT
Date
Class 1
Class 2
Class 3
Future expansion
provision of once
through cooling
water system
No future expansion
provision in the layout
header extension / tiein
Future expansion
provision of once
through chilling
system
No future expansion
provision in the layout
header extension /
tie-in
Design Class
Class 1
Class 2
Class 3
CW pump drive
(not applicable
when power
system is highly
reliable)
Steam drive on at
least one pump based
on critical cooling
demand.
Steam drives on N
pumps
Motor drives on spare
pumps
Page 2 of
PROJECT
Date
Energy Efficiency
Design
Item
Design Class
Class 1
Class 2
Class 3
Syphonic recovery
Use spare pump during
start up.
Process chilling up
to 7C (45F)
Compression
refrigeration chillers
Process chilling
<7C (45F)
Not considered.
Compression
refrigeration chillers
Air cooled
Compression
refrigeration chillers
Water cooled
CW outfall design
Chiller energy
source
Page 3 of