GENERATOR AUXILIARIES (PRIMARY WATER SYSTEM )

PART-II ABC OF THERMAL POWER PLANT


We are breifly discussing the important auxiliary system of Generator . In part-i
we discussed about the seal oil system of generator. Now i will describe briefly
about primary water system used in power house of 500 MW above rating sets.

The treated water used for cooling the stator winding, phase connectors and
bushings is referred to as primary water in order to distinguish it from the
secondary coolant (raw water, or condensate). The primary water is circulated in
a closed system and dissipates the absorbed heat to the secondary cooling water
The pump is supplied with hot primary water from the primary water tank, and delivers the
water to the generator via the coolers.
Primary water system comes as a skid only pipelines and cabling connections are to be made
after erection. Skid erection gives front for piping erection and this job can be done
independently . However the total piping job including impulse
piping of instruments to be done by SS material. Stator purity is challenge to erection and
commissioning engineer therefore system should be leakproof . O2
measured in the stator water in p.p.b. ( parts per billion).
The skid contains 2x100% pumps , 2x100% coolers , filters , primary water tanks ,necessary
valves and insrtumentations. A typical PID is given below.
Flow path I of primary water is used for cooling the stator winding.
This flow path routes the water to the manifold at the exciter end and from there to the stator
bars via insulating hoses. Each stator bar is connected to the manifold by a separate hose.
The cooling water flows through hollow conductors towards the turbine end of the generator.
After exiting the stator bars, the water flows through insulating hoses to a water manifold
from where it is rerouted to the primary water tank.
The other flow path is for cooling the phase connector and bushings.
The bushings and phase connectors are made of thick-walled copper tubes carrying the
cooling water. The 6 bushings and the phase connectors, which are arranged in circular
fashion around the stator-end winding, are interconnected in such a manner that 3 parallel
flow paths are established. The cooling water is admitted from outside the generator through
3 bushings and exits through the other 3 bushings.
The secondary water flow through the primary water cooler is automatically controlled to
ensure that the generator temperature is maintained at a constant level under different load
conditions.