Air System Sizing Summary for 00-Gr. Flr.

-ODC-A&B
Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ...................... 00-Gr. Flr.-ODC-A&B
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area ............................................................ 6509.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 18.5
Total coil load ..................................................... 222.5
Sensible coil load ................................................ 170.5
Coil CFM at Jul 1400 ........................................... 6133
Max block CFM at Oct 1500 ................................ 6133
Sum of peak zone CFM ....................................... 6455
Sensible heat ratio .............................................. 0.766
ft/Ton ................................................................. 351.0
BTU/(hr-ft) ........................................................... 34.2
Water flow @ 10.0 F rise ................................... 44.53

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1400


OA DB / WB .................................................. 105.6 / 77.9
Entering DB / WB ........................................... 82.2 / 65.9
Leaving DB / WB ........................................... 54.8 / 53.3
Coil ADP .................................................................. 51.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 3.1

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Oct 1500 ............................... 6133 CFM
Standard CFM ..................................................... 5747 CFM
Actual max CFM/ft ............................................... 0.94 CFM/ft

Fan motor BHP ........................................................ 5.04 BHP


Fan motor kW .......................................................... 4.00 kW
Fan static ................................................................. 3.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 1249 CFM
CFM/ft ................................................................. 0.19 CFM/ft

Hourly Analysis Program v4.70

CFM/person ........................................................... 13.94 CFM/person

Page 1 of 42

Space Design Load Summary for 00-Gr. Flr.-ODC-A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

N EXPOSURE
WALL
WINDOW 1
S EXPOSURE
WALL
WINDOW 1

Hourly Analysis Program v4.70

03/05/2016
10:10AM

COMPONENT LOADS FOR SPACE '' 00-Gr.Flr.-ODC A&B '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Oct 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 102.0 F / 76.0 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
750 ft
8867
750 ft
945 ft
1152
945 ft
1510
0 ft
0
0 ft
0
750 ft
17608
750 ft
10123
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
1936 ft
14051
1936 ft
0
0 ft
0
0 ft
0
3255 W
6114
0
0
0W
0
0
0
8960 W
27661
0
0
112
20125
22960
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
95578
22960
11633
0

ENVELOPE LOADS FOR SPACE '' 00-Gr.Flr.-ODC A&B '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

313
308

0.107
0.900

0.230

333
7225

1133

500
4154

632
442

0.107
0.900

0.230

819
10383

7733

1010
5969

Page 2 of 42

Air System Sizing Summary for 00-Gr.FAS-BMS-ODC-A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ............ 00-Gr.FAS-BMS-ODC-A&B
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 183.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 0.6
Total coil load ........................................................ 7.8
Sensible coil load ................................................... 7.4
Coil CFM at Jun 1900 ........................................... 420
Max block CFM at Jul 1900 .................................. 420
Sum of peak zone CFM ........................................ 443
Sensible heat ratio .............................................. 0.958
ft/Ton ................................................................. 283.3
BTU/(hr-ft) ........................................................... 42.4
Water flow @ 10.0 F rise ..................................... 1.55

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................. Jun 1900


OA DB / WB .................................................. 100.2 / 76.9
Entering DB / WB ........................................... 73.9 / 61.9
Leaving DB / WB ........................................... 56.5 / 55.3
Coil ADP .................................................................. 54.6
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1900 ................................. 420 CFM
Standard CFM ...................................................... 394 CFM
Actual max CFM/ft ............................................... 2.30 CFM/ft

Fan motor BHP ........................................................ 0.35 BHP


Fan motor kW .......................................................... 0.27 kW
Fan static ................................................................. 3.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 3 of 42

Space Design Load Summary for 00-Gr.FAS-BMS-ODC-A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 00-Gr.FAS-BMS-ODC-A&B '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1900
HEATING DATA AT DES HTG
COOLING OA DB / WB 101.2 F / 76.9 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
0 ft
0
0 ft
0
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
357 ft
2658
357 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
92 W
219
0
0
Task Lighting
0W
0
0
0
Electric Equipment
1000 W
3187
0
0
People
2
490
410
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
6553
410
0
0

TABLE 1.1.B.

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 00-Gr.FAS-BMS-ODC-A&B '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

Page 4 of 42

Air System Sizing Summary for 00-Gr.Flr.BATTERY ROOM


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ............ 00-Gr.Flr.BATTERY ROOM
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 310.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 3.5
Total coil load ....................................................... 41.9
Sensible coil load .................................................. 41.7
Coil CFM at May 1400 ......................................... 2137
Max block CFM at Jul 1700 ................................. 2137
Sum of peak zone CFM ....................................... 2249
Sensible heat ratio .............................................. 0.996
ft/Ton ................................................................... 88.8
BTU/(hr-ft) ......................................................... 135.2
Water flow @ 10.0 F rise ..................................... 8.39

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................ May 1400


OA DB / WB .................................................. 102.6 / 76.7
Entering DB / WB ........................................... 73.3 / 60.1
Leaving DB / WB ........................................... 54.0 / 52.8
Coil ADP .................................................................. 51.9
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 56.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1700 ................................ 2137 CFM
Standard CFM ..................................................... 2002 CFM
Actual max CFM/ft ............................................... 6.89 CFM/ft

Fan motor BHP ........................................................ 1.17 BHP


Fan motor kW .......................................................... 0.93 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 5 of 42

Space Design Load Summary for 00-Gr.Flr.BATTERY ROOM


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 00-Gr.Flr.BATTERY ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 104.6 F / 77.7 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
132 ft
293
132 ft
211
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
357 ft
2651
357 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
155 W
370
0
0
Task Lighting
0W
0
0
0
Electric Equipment
10000 W
34120
0
0
People
1
188
205
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
37623
205
211
0

TABLE 1.1.B.

N EXPOSURE
WALL

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 00-Gr.Flr.BATTERY ROOM '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)
132

0.107

293

HEATING
TRANS
(BTU/hr)
211

Page 6 of 42

Air System Sizing Summary for 00-Gr.Flr.-ODC C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ....................... 00-Gr.Flr.-ODC C&D
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area ............................................................ 8070.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 26.9
Total coil load ..................................................... 323.2
Sensible coil load ................................................ 248.4
Coil CFM at Jul 1400 ........................................... 9051
Max block CFM at Jul 1700 ................................. 9051
Sum of peak zone CFM ....................................... 9528
Sensible heat ratio .............................................. 0.768
ft/Ton ................................................................. 299.6
BTU/(hr-ft) ........................................................... 40.1
Water flow @ 10.0 F rise ................................... 64.68

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1400


OA DB / WB .................................................. 105.6 / 77.9
Entering DB / WB ........................................... 81.9 / 65.8
Leaving DB / WB ........................................... 54.8 / 53.3
Coil ADP .................................................................. 51.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 47
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 1.6

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1700 ................................ 9051 CFM
Standard CFM ..................................................... 8482 CFM
Actual max CFM/ft ............................................... 1.12 CFM/ft

Fan motor BHP ........................................................ 7.44 BHP


Fan motor kW .......................................................... 5.90 kW
Fan static ................................................................. 3.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 1751 CFM
CFM/ft ................................................................. 0.22 CFM/ft

Hourly Analysis Program v4.70

CFM/person ........................................................... 12.87 CFM/person

Page 7 of 42

Space Design Load Summary for 00-Gr.Flr.-ODC C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

N EXPOSURE
WALL
WINDOW 1
WINDOW 2
S EXPOSURE
WALL
WINDOW 1
SE EXPOSURE
WALL
E EXPOSURE
WALL
WINDOW 1

Hourly Analysis Program v4.70

03/05/2016
10:10AM

COMPONENT LOADS FOR SPACE '' 00-Gr.Flr.-ODC C&D '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 104.6 F / 77.7 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
1316 ft
9263
1316 ft
2146 ft
3514
2146 ft
3430
0 ft
0
0 ft
0
1316 ft
34874
1316 ft
17764
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
1492 ft
11070
1492 ft
0
0 ft
0
0 ft
0
4035 W
7842
0
0
0W
0
0
0
13600 W
42547
0
0
170
31958
34850
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
141068
34850
21194
0

ENVELOPE LOADS FOR SPACE '' 00-Gr.Flr.-ODC C&D '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

444
459
175

0.107
0.900
0.900

0.230
0.230

384
12166
4630

3659
1393

710
6197
2358

977
507

0.107
0.900

0.230

1686
13448

2318

1561
6850

395

0.107

877

631

330
175

0.107
0.900

0.230

568
4630

1892

528
2358

Page 8 of 42

Air System Sizing Summary for 00-Gr.Flr.UPS-WORKSTN


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name .............. 00-Gr.Flr.UPS-WORKSTN
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 254.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 5.0
Total coil load ....................................................... 60.5
Sensible coil load .................................................. 60.5
Coil CFM at Jul 1700 ........................................... 2270
Max block CFM at Jul 1800 ................................. 2270
Sum of peak zone CFM ....................................... 2389
Sensible heat ratio .............................................. 1.000
ft/Ton ................................................................... 50.4
BTU/(hr-ft) ......................................................... 238.3
Water flow @ 10.0 F rise ................................... 12.11

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1700


OA DB / WB .................................................. 104.6 / 77.7
Entering DB / WB ........................................... 83.0 / 48.6
Leaving DB / WB ........................................... 56.6 / 35.7
Coil ADP .................................................................. 53.7
Bypass Factor ........................................................ 0.100
Resulting RH ................................................................ 0
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.3

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1800 ................................ 2270 CFM
Standard CFM ..................................................... 2127 CFM
Actual max CFM/ft ............................................... 8.94 CFM/ft

Fan motor BHP ........................................................ 1.24 BHP


Fan motor kW .......................................................... 0.99 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 9 of 42

Space Design Load Summary for 00-Gr.Flr.UPS-WORKSTN


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 00-Gr.Flr.UPS-WORKSTN '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1800
HEATING DATA AT DES HTG
COOLING OA DB / WB 103.1 F / 77.3 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 82.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
146 ft
225
146 ft
234
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
216 ft
924
216 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
127 W
303
0
0
Task Lighting
0W
0
0
0
Electric Equipment
16000 W
54592
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
56044
0
234
0

TABLE 1.1.B.

N EXPOSURE
WALL

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 00-Gr.Flr.UPS-WORKSTN '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)
146

0.107

225

HEATING
TRANS
(BTU/hr)
234

Page 10 of 42

Air System Sizing Summary for 00-Gr.Flr-Hub Room-A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name .............. 00-Gr.Flr-Hub Room-A&B
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 201.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 2.0
Total coil load ....................................................... 24.1
Sensible coil load .................................................. 24.1
Coil CFM at Jan 2000 .......................................... 1379
Max block CFM at Jan 2300 ................................ 1379
Sum of peak zone CFM ....................................... 1451
Sensible heat ratio .............................................. 1.000
ft/Ton ................................................................. 100.3
BTU/(hr-ft) ......................................................... 119.7
Water flow @ 10.0 F rise ..................................... 4.81

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................. Jan 2000


OA DB / WB ................................................... 89.2 / 70.0
Entering DB / WB ........................................... 72.6 / 43.9
Leaving DB / WB ........................................... 55.4 / 35.1
Coil ADP .................................................................. 53.5
Bypass Factor ........................................................ 0.100
Resulting RH ................................................................ 0
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jan 2300 ............................... 1379 CFM
Standard CFM ..................................................... 1292 CFM
Actual max CFM/ft ............................................... 6.86 CFM/ft

Fan motor BHP ........................................................ 0.76 BHP


Fan motor kW .......................................................... 0.60 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 11 of 42

Space Design Load Summary for 00-Gr.Flr-Hub Room-A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 00-Gr.Flr.Hub Room-A&B '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jan 2300
HEATING DATA AT DES HTG
COOLING OA DB / WB 85.2 F / 68.8 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
0 ft
0
0 ft
0
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
968 ft
774
968 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
101 W
240
0
0
Task Lighting
0W
0
0
0
Electric Equipment
6000 W
20472
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
21486
0
0
0

TABLE 1.1.B.

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 00-Gr.Flr.Hub Room-A&B '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

Page 12 of 42

Air System Sizing Summary for 00-Gr.Flr-Hub Room-C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name .............. 00-Gr.Flr-Hub Room-C&D
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 183.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 2.0
Total coil load ....................................................... 23.9
Sensible coil load .................................................. 23.5
Coil CFM at Jan 1700 .......................................... 1398
Max block CFM at Jan 1700 ................................ 1398
Sum of peak zone CFM ....................................... 1471
Sensible heat ratio .............................................. 0.986
ft/Ton ................................................................... 92.0
BTU/(hr-ft) ......................................................... 130.4
Water flow @ 10.0 F rise ..................................... 4.77

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................. Jan 1700


OA DB / WB ................................................... 94.4 / 71.4
Entering DB / WB ........................................... 74.3 / 62.5
Leaving DB / WB ........................................... 57.7 / 56.6
Coil ADP .................................................................. 55.9
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.2

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jan 1700 ............................... 1398 CFM
Standard CFM ..................................................... 1310 CFM
Actual max CFM/ft ............................................... 7.64 CFM/ft

Fan motor BHP ........................................................ 0.77 BHP


Fan motor kW .......................................................... 0.61 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 13 of 42

Space Design Load Summary for 00-Gr.Flr-Hub Room-C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 00-Gr.Flr-Hub Room-C&D '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jan 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 94.4 F / 71.4 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
0 ft
0
0 ft
0
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
897 ft
718
897 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
92 W
219
0
0
Task Lighting
0W
0
0
0
Electric Equipment
6000 W
20472
0
0
People
2
376
410
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
21784
410
0
0

TABLE 1.1.B.

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 00-Gr.Flr-Hub Room-C&D '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

Page 14 of 42

Air System Sizing Summary for 01'st Flr.-BATTERY ROOM


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ............ 01'st Flr.-BATTERY ROOM
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 310.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 3.5
Total coil load ....................................................... 41.6
Sensible coil load .................................................. 41.6
Coil CFM at May 1400 ......................................... 2126
Max block CFM at Jul 1800 ................................. 2126
Sum of peak zone CFM ....................................... 2238
Sensible heat ratio .............................................. 1.000
ft/Ton ................................................................... 89.5
BTU/(hr-ft) ......................................................... 134.1
Water flow @ 10.0 F rise ..................................... 8.32

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................ May 1400


OA DB / WB .................................................. 102.6 / 76.7
Entering DB / WB ........................................... 73.3 / 44.2
Leaving DB / WB ........................................... 54.0 / 34.3
Coil ADP .................................................................. 51.8
Bypass Factor ........................................................ 0.100
Resulting RH ................................................................ 0
Design supply temp. ................................................ 56.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1800 ................................ 2126 CFM
Standard CFM ..................................................... 1992 CFM
Actual max CFM/ft ............................................... 6.86 CFM/ft

Fan motor BHP ........................................................ 1.16 BHP


Fan motor kW .......................................................... 0.92 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 15 of 42

Space Design Load Summary for 01'st Flr.-BATTERY ROOM


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 01'st Flr.-BATTERY ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1800
HEATING DATA AT DES HTG
COOLING OA DB / WB 103.1 F / 77.3 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
132 ft
292
132 ft
211
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
357 ft
2654
357 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
155 W
370
0
0
Task Lighting
0W
0
0
0
Electric Equipment
10000 W
34120
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
37436
0
211
0

TABLE 1.1.B.

N EXPOSURE
WALL

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 01'st Flr.-BATTERY ROOM '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)
132

0.107

292

HEATING
TRANS
(BTU/hr)
211

Page 16 of 42

Air System Sizing Summary for 01'st Flr.-ODC A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ......................... 01'st Flr.-ODC A&B
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area ............................................................ 7058.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 21.7
Total coil load ..................................................... 259.9
Sensible coil load ................................................ 200.4
Coil CFM at Aug 1400 ......................................... 7879
Max block CFM at Nov 1500 ................................ 7879
Sum of peak zone CFM ....................................... 8293
Sensible heat ratio .............................................. 0.771
ft/Ton ................................................................. 325.9
BTU/(hr-ft) ........................................................... 36.8
Water flow @ 10.0 F rise ................................... 52.00

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................ Aug 1400


OA DB / WB .................................................. 105.6 / 77.9
Entering DB / WB ........................................... 80.7 / 65.6
Leaving DB / WB ........................................... 55.5 / 54.2
Coil ADP .................................................................. 52.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 48
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 1.1

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Nov 1500 .............................. 7879 CFM
Standard CFM ..................................................... 7383 CFM
Actual max CFM/ft ............................................... 1.12 CFM/ft

Fan motor BHP ........................................................ 4.32 BHP


Fan motor kW .......................................................... 3.42 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 1449 CFM
CFM/ft ................................................................. 0.21 CFM/ft

Hourly Analysis Program v4.70

CFM/person ........................................................... 13.31 CFM/person

Page 17 of 42

Space Design Load Summary for 01'st Flr.-ODC A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

N EXPOSURE
WALL
WINDOW 1
S EXPOSURE
WALL
WINDOW 1
W EXPOSURE
WALL
WINDOW 1
WINDOW 2

Hourly Analysis Program v4.70

03/05/2016
10:10AM

COMPONENT LOADS FOR SPACE '' 01'st Flr.-ODC A&B '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Nov 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 98.8 F / 74.8 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
883 ft
19477
883 ft
1854 ft
4263
1854 ft
2964
0 ft
0
0 ft
0
883 ft
18190
883 ft
11919
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
1914 ft
13362
1914 ft
0
0 ft
0
0 ft
0
3529 W
9471
0
0
0W
0
0
0
10880 W
33588
0
0
136
24438
27880
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
122790
27880
14883
0

ENVELOPE LOADS FOR SPACE '' 01'st Flr.-ODC A&B '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

586
35

0.107
0.900

0.230

1342
717

112

936
470

590
768

0.107
0.900

0.230

1361
15831

18019

944
10374

678
40
39

0.107
0.900
0.900

0.230
0.230

1560
831
811

681
665

1084
545
531

Page 18 of 42

Air System Sizing Summary for 01'st Flr.-ODC C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ......................... 01'st Flr.-ODC C&D
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area ............................................................ 9016.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 26.8
Total coil load ..................................................... 321.4
Sensible coil load ................................................ 250.5
Coil CFM at Jul 1400 ........................................... 9997
Max block CFM at Jul 1700 ................................. 9997
Sum of peak zone CFM ..................................... 10523
Sensible heat ratio .............................................. 0.779
ft/Ton ................................................................. 336.6
BTU/(hr-ft) ........................................................... 35.6
Water flow @ 10.0 F rise ................................... 64.31

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1400


OA DB / WB .................................................. 105.6 / 77.9
Entering DB / WB ........................................... 81.0 / 65.9
Leaving DB / WB ........................................... 56.2 / 54.9
Coil ADP .................................................................. 53.5
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 48
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 1.7

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1700 ................................ 9997 CFM
Standard CFM ..................................................... 9368 CFM
Actual max CFM/ft ............................................... 1.11 CFM/ft

Fan motor BHP ........................................................ 2.74 BHP


Fan motor kW .......................................................... 2.17 kW
Fan static ................................................................. 1.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 1781 CFM
CFM/ft ................................................................. 0.20 CFM/ft

Hourly Analysis Program v4.70

CFM/person ........................................................... 13.66 CFM/person

Page 19 of 42

Space Design Load Summary for 01'st Flr.-ODC C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

N EXPOSURE
WALL
WINDOW 1
WINDOW 2
S EXPOSURE
WALL
WINDOW 1
E EXPOSURE
WALL
WINDOW 1
WINDOW 2

Hourly Analysis Program v4.70

03/05/2016
10:10AM

COMPONENT LOADS FOR SPACE '' 01'st Flr.-ODC C&D '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 104.6 F / 77.7 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
1571 ft
10136
1571 ft
2372 ft
7527
2372 ft
3791
0 ft
0
0 ft
0
1571 ft
41632
1571 ft
21206
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
1693 ft
12556
1693 ft
0
0 ft
0
0 ft
0
4508 W
12516
0
0
0W
0
0
0
13040 W
40795
0
0
163
30642
33415
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
155804
33415
24997
0

ENVELOPE LOADS FOR SPACE '' 01'st Flr.-ODC C&D '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

738
175
548

0.107
0.900
0.900

0.230
0.230

2344
4630
14524

1393
4369

1180
2358
7398

633
768

0.107
0.900

0.230

2009
20366

3511

1012
10374

1000
39
40

0.107
0.900
0.900

0.230
0.230

3174
1043
1069

426
437

1599
531
545

Page 20 of 42

Air System Sizing Summary for 01'st Flr.UPS-WORKSTN


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ................ 01'st Flr.UPS-WORKSTN
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 254.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 5.0
Total coil load ....................................................... 60.5
Sensible coil load .................................................. 60.5
Coil CFM at Jul 1700 ........................................... 2270
Max block CFM at Jul 1800 ................................. 2270
Sum of peak zone CFM ....................................... 2389
Sensible heat ratio .............................................. 1.000
ft/Ton ................................................................... 50.4
BTU/(hr-ft) ......................................................... 238.3
Water flow @ 10.0 F rise ................................... 12.11

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1700


OA DB / WB .................................................. 104.6 / 77.7
Entering DB / WB ........................................... 83.0 / 48.6
Leaving DB / WB ........................................... 56.6 / 35.7
Coil ADP .................................................................. 53.7
Bypass Factor ........................................................ 0.100
Resulting RH ................................................................ 0
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.3

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1800 ................................ 2270 CFM
Standard CFM ..................................................... 2127 CFM
Actual max CFM/ft ............................................... 8.94 CFM/ft

Fan motor BHP ........................................................ 1.24 BHP


Fan motor kW .......................................................... 0.99 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 21 of 42

Space Design Load Summary for 01'st Flr.UPS-WORKSTN


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 01'st Flr.UPS-WORK STN '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1800
HEATING DATA AT DES HTG
COOLING OA DB / WB 103.1 F / 77.3 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 82.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
146 ft
225
146 ft
234
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
216 ft
924
216 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
127 W
303
0
0
Task Lighting
0W
0
0
0
Electric Equipment
16000 W
54592
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
56044
0
234
0

TABLE 1.1.B.

N EXPOSURE
WALL

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 01'st Flr.UPS-WORK STN '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)
146

0.107

225

HEATING
TRANS
(BTU/hr)
234

Page 22 of 42

Air System Sizing Summary for 01'st HUB & MCR-ODC C&D
Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name .......... 01'st HUB & MCR-ODC C&D
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 515.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 8.1
Total coil load ....................................................... 97.0
Sensible coil load .................................................. 96.0
Coil CFM at Jul 1500 ........................................... 4883
Max block CFM at Jul 1900 ................................. 4883
Sum of peak zone CFM ....................................... 5140
Sensible heat ratio .............................................. 0.990
ft/Ton ................................................................... 63.7
BTU/(hr-ft) ......................................................... 188.3
Water flow @ 10.0 F rise ................................... 19.41

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1500


OA DB / WB .................................................. 106.0 / 78.0
Entering DB / WB ........................................... 73.5 / 60.2
Leaving DB / WB ........................................... 54.1 / 52.8
Coil ADP .................................................................. 51.9
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 56.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1900 ................................ 4883 CFM
Standard CFM ..................................................... 4575 CFM
Actual max CFM/ft ............................................... 9.48 CFM/ft

Fan motor BHP ........................................................ 2.67 BHP


Fan motor kW .......................................................... 2.12 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 31 CFM
CFM/ft ................................................................. 0.06 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 23 of 42

Space Design Load Summary for 01'st HUB & MCR-ODC C&D
Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 01st HUB & MCR-ODC C&D '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1900
HEATING DATA AT DES HTG
COOLING OA DB / WB 101.2 F / 76.9 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
0 ft
0
0 ft
0
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
467 ft
3476
467 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
258 W
615
0
0
Task Lighting
0W
0
0
0
Electric Equipment
24000 W
81888
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
85978
0
0
0

TABLE 1.1.B.

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 01st HUB & MCR-ODC C&D '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

Page 24 of 42

Air System Sizing Summary for 01'st HUB & MSR-ODC A&B
Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name .......... 01'st HUB & MSR-ODC A&B
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 933.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 26.5
Total coil load ..................................................... 318.4
Sensible coil load ................................................ 316.7
Coil CFM at Jun 1500 ........................................ 16175
Max block CFM at Jul 1900 ............................... 16175
Sum of peak zone CFM ..................................... 17027
Sensible heat ratio .............................................. 0.994
ft/Ton ................................................................... 35.2
BTU/(hr-ft) ......................................................... 341.3
Water flow @ 10.0 F rise ................................... 63.72

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................. Jun 1500


OA DB / WB .................................................. 105.0 / 78.0
Entering DB / WB ........................................... 73.7 / 60.4
Leaving DB / WB ........................................... 54.4 / 53.1
Coil ADP .................................................................. 52.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 56.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1900 .............................. 16175 CFM
Standard CFM ................................................... 15158 CFM
Actual max CFM/ft ............................................. 17.34 CFM/ft

Fan motor BHP ........................................................ 8.86 BHP


Fan motor kW .......................................................... 7.03 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 56 CFM
CFM/ft ................................................................. 0.06 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 25 of 42

Space Design Load Summary for 01'st HUB & MSR-ODC A&B
Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 01st-HUB & MSR-ODC-A&B '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1900
HEATING DATA AT DES HTG
COOLING OA DB / WB 101.2 F / 76.9 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
0 ft
0
0 ft
0
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
530 ft
3943
530 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
467 W
1114
0
0
Task Lighting
0W
0
0
0
Electric Equipment
82000 W
279783
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
284840
0
0
0

TABLE 1.1.B.

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 01st-HUB & MSR-ODC-A&B '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

Page 26 of 42

Air System Sizing Summary for 02-2'nd Flr-Hub Room-A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ........... 02-2'nd Flr-Hub Room-A&B
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 186.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.9
Total coil load ....................................................... 23.2
Sensible coil load .................................................. 23.2
Coil CFM at Jan 2000 .......................................... 1373
Max block CFM at Jan 2300 ................................ 1373
Sum of peak zone CFM ....................................... 1445
Sensible heat ratio .............................................. 1.000
ft/Ton ................................................................... 96.3
BTU/(hr-ft) ......................................................... 124.6
Water flow @ 10.0 F rise ..................................... 4.64

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................. Jan 2000


OA DB / WB ................................................... 89.2 / 70.0
Entering DB / WB ........................................... 74.4 / 44.7
Leaving DB / WB ........................................... 57.7 / 36.3
Coil ADP .................................................................. 55.8
Bypass Factor ........................................................ 0.100
Resulting RH ................................................................ 0
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.2

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jan 2300 ............................... 1373 CFM
Standard CFM ..................................................... 1286 CFM
Actual max CFM/ft ............................................... 7.38 CFM/ft

Fan motor BHP ........................................................ 0.75 BHP


Fan motor kW .......................................................... 0.60 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 27 of 42

Space Design Load Summary for 02-2'nd Flr-Hub Room-A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 02-2'nd Flr-Hub Room-A&B '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jan 2300
HEATING DATA AT DES HTG
COOLING OA DB / WB 85.2 F / 68.8 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
0 ft
0
0 ft
0
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
874 ft
699
874 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
93 W
222
0
0
Task Lighting
0W
0
0
0
Electric Equipment
6000 W
20472
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
21393
0
0
0

TABLE 1.1.B.

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 02-2'nd Flr-Hub Room-A&B '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

Page 28 of 42

Air System Sizing Summary for 02-2'nd Flr-Hub Room-C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ........... 02-2'nd Flr-Hub Room-C&D
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 167.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.9
Total coil load ....................................................... 23.2
Sensible coil load .................................................. 23.2
Coil CFM at Jan 2300 .......................................... 1373
Max block CFM at Jan 2300 ................................ 1373
Sum of peak zone CFM ....................................... 1445
Sensible heat ratio .............................................. 1.000
ft/Ton ................................................................... 86.5
BTU/(hr-ft) ......................................................... 138.8
Water flow @ 10.0 F rise ..................................... 4.64

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................. Jan 2300


OA DB / WB ................................................... 85.2 / 68.8
Entering DB / WB ........................................... 74.3 / 44.7
Leaving DB / WB ........................................... 57.6 / 36.3
Coil ADP .................................................................. 55.8
Bypass Factor ........................................................ 0.100
Resulting RH ................................................................ 0
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.2

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jan 2300 ............................... 1373 CFM
Standard CFM ..................................................... 1286 CFM
Actual max CFM/ft ............................................... 8.22 CFM/ft

Fan motor BHP ........................................................ 0.75 BHP


Fan motor kW .......................................................... 0.60 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 29 of 42

Space Design Load Summary for 02-2'nd Flr-Hub Room-C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 02-2'nd Flr-Hub Room-C&D '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jan 2300
HEATING DATA AT DES HTG
COOLING OA DB / WB 85.2 F / 68.8 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
0 ft
0
0 ft
0
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
901 ft
721
901 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
84 W
199
0
0
Task Lighting
0W
0
0
0
Electric Equipment
6000 W
20472
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
21392
0
0
0

TABLE 1.1.B.

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 02-2'nd Flr-Hub Room-C&D '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

Page 30 of 42

Air System Sizing Summary for 02'nd Flr.-ODC A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ....................... 02'nd Flr.-ODC A&B
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area ............................................................ 9092.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 20.6
Total coil load ..................................................... 247.1
Sensible coil load ................................................ 177.9
Coil CFM at Jul 1500 ........................................... 6087
Max block CFM at Jul 1700 ................................. 6087
Sum of peak zone CFM ....................................... 6407
Sensible heat ratio .............................................. 0.720
ft/Ton ................................................................. 441.6
BTU/(hr-ft) ........................................................... 27.2
Water flow @ 10.0 F rise ................................... 49.44

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1500


OA DB / WB .................................................. 106.0 / 78.0
Entering DB / WB ........................................... 84.4 / 67.8
Leaving DB / WB ........................................... 55.5 / 54.1
Coil ADP .................................................................. 52.3
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.6

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1700 ................................ 6087 CFM
Standard CFM ..................................................... 5704 CFM
Actual max CFM/ft ............................................... 0.67 CFM/ft

Fan motor BHP ........................................................ 3.33 BHP


Fan motor kW .......................................................... 2.64 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 1761 CFM
CFM/ft ................................................................. 0.19 CFM/ft

Hourly Analysis Program v4.70

CFM/person ........................................................... 13.84 CFM/person

Page 31 of 42

Space Design Load Summary for 02'nd Flr.-ODC A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

N EXPOSURE
WALL
S EXPOSURE
WALL
W EXPOSURE
WALL

Hourly Analysis Program v4.70

03/05/2016
10:10AM

COMPONENT LOADS FOR SPACE '' 02'nd Flr.-ODC A&B '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 104.6 F / 77.7 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
3199 ft
7112
3199 ft
5113
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
1245 ft
9232
1245 ft
0
0 ft
0
0 ft
0
4546 W
8835
0
0
0W
0
0
0
12720 W
39794
0
0
159
29890
32595
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
94863
32595
5113
0

ENVELOPE LOADS FOR SPACE '' 02'nd Flr.-ODC A&B '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

1078

0.107

2396

1723

1359

0.107

3017

2172

762

0.107

1698

1218

Page 32 of 42

Air System Sizing Summary for 02'nd Flr.-ODC C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ....................... 02'nd Flr.-ODC C&D
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area ............................................................ 9501.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 24.2
Total coil load ..................................................... 290.2
Sensible coil load ................................................ 209.9
Coil CFM at Jul 1500 ........................................... 7364
Max block CFM at Jul 1700 ................................. 7364
Sum of peak zone CFM ....................................... 7752
Sensible heat ratio .............................................. 0.723
ft/Ton ................................................................. 392.9
BTU/(hr-ft) ........................................................... 30.5
Water flow @ 10.0 F rise ................................... 58.07

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1500


OA DB / WB .................................................. 106.0 / 78.0
Entering DB / WB ........................................... 82.9 / 66.9
Leaving DB / WB ........................................... 54.8 / 53.4
Coil ADP .................................................................. 51.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 49
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.6

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1700 ................................ 7364 CFM
Standard CFM ..................................................... 6901 CFM
Actual max CFM/ft ............................................... 0.78 CFM/ft

Fan motor BHP ........................................................ 6.05 BHP


Fan motor kW .......................................................... 4.80 kW
Fan static ................................................................. 3.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 1956 CFM
CFM/ft ................................................................. 0.21 CFM/ft

Hourly Analysis Program v4.70

CFM/person ........................................................... 13.29 CFM/person

Page 33 of 42

Space Design Load Summary for 02'nd Flr.-ODC C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

N EXPOSURE
WALL
S EXPOSURE
WALL
E EXPOSURE
WALL

Hourly Analysis Program v4.70

03/05/2016
10:10AM

COMPONENT LOADS FOR SPACE '' 02'nd Flr.-ODC C&D '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 104.6 F / 77.7 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
3076 ft
9760
3076 ft
4916
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
1508 ft
11184
1508 ft
0
0 ft
0
0 ft
0
4751 W
13189
0
0
0W
0
0
0
14720 W
46051
0
0
184
34590
37720
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
114773
37720
4916
0

ENVELOPE LOADS FOR SPACE '' 02'nd Flr.-ODC C&D '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

1112

0.107

3529

1777

1402

0.107

4446

2240

562

0.107

1785

899

Page 34 of 42

Air System Sizing Summary for 03rd Flr.-ODC A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ......................... 03rd Flr.-ODC A&B
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .......................................................... 10222.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 29.3
Total coil load ..................................................... 351.3
Sensible coil load ................................................ 271.3
Coil CFM at Jul 1500 ........................................... 9910
Max block CFM at Jul 1700 ................................. 9910
Sum of peak zone CFM ..................................... 10432
Sensible heat ratio .............................................. 0.772
ft/Ton ................................................................. 349.2
BTU/(hr-ft) ........................................................... 34.4
Water flow @ 10.0 F rise ................................... 70.29

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1500


OA DB / WB .................................................. 106.0 / 78.0
Entering DB / WB ........................................... 81.8 / 65.7
Leaving DB / WB ........................................... 54.8 / 53.4
Coil ADP .................................................................. 51.8
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 45
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 2.1

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1700 ................................ 9910 CFM
Standard CFM ..................................................... 9287 CFM
Actual max CFM/ft ............................................... 0.97 CFM/ft

Fan motor BHP ........................................................ 8.14 BHP


Fan motor kW .......................................................... 6.46 kW
Fan static ................................................................. 3.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 1923 CFM
CFM/ft ................................................................. 0.19 CFM/ft

Hourly Analysis Program v4.70

CFM/person ........................................................... 14.14 CFM/person

Page 35 of 42

Space Design Load Summary for 03rd Flr.-ODC A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

N EXPOSURE
WALL
S EXPOSURE
WALL
W EXPOSURE
WALL
H EXPOSURE
ROOF

Hourly Analysis Program v4.70

03/05/2016
10:10AM

COMPONENT LOADS FOR SPACE '' 03rd Flr.-ODC A&B '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 104.6 F / 77.7 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
3394 ft
10778
3394 ft
5424
10491 ft
42103
10491 ft
11469
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
1601 ft
11877
1601 ft
0
0 ft
0
0 ft
0
5111 W
14190
0
0
0W
0
0
0
13920 W
43548
0
0
170
31958
34850
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
154454
34850
16893
0

ENVELOPE LOADS FOR SPACE '' 03rd Flr.-ODC A&B '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

1273

0.107

4042

2035

1359

0.107

4310

2172

762

0.107

2426

1218

10491

0.073

42103

11469

Page 36 of 42

Air System Sizing Summary for 03rd Flr.-ODC C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ......................... 03rd Flr.-ODC C&D
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .......................................................... 10760.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 29.3
Total coil load ..................................................... 351.4
Sensible coil load ................................................ 272.8
Coil CFM at Jul 1400 ........................................... 9953
Max block CFM at Jul 1700 ................................. 9953
Sum of peak zone CFM ..................................... 10477
Sensible heat ratio .............................................. 0.776
ft/Ton ................................................................. 367.4
BTU/(hr-ft) ........................................................... 32.7
Water flow @ 10.0 F rise ................................... 70.32

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1400


OA DB / WB .................................................. 105.6 / 77.9
Entering DB / WB ........................................... 81.9 / 65.7
Leaving DB / WB ........................................... 54.8 / 53.4
Coil ADP .................................................................. 51.8
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 45
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 2.4

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jul 1700 ................................ 9953 CFM
Standard CFM ..................................................... 9327 CFM
Actual max CFM/ft ............................................... 0.93 CFM/ft

Fan motor BHP ........................................................ 8.18 BHP


Fan motor kW .......................................................... 6.49 kW
Fan static ................................................................. 3.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 1914 CFM
CFM/ft ................................................................. 0.18 CFM/ft

Hourly Analysis Program v4.70

CFM/person ........................................................... 14.77 CFM/person

Page 37 of 42

Space Design Load Summary for 03rd Flr.-ODC C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

N EXPOSURE
WALL
S EXPOSURE
WALL
E EXPOSURE
WALL
H EXPOSURE
ROOF

Hourly Analysis Program v4.70

03/05/2016
10:10AM

COMPONENT LOADS FOR SPACE '' 03rd Flr.-ODC C&D '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 104.6 F / 77.7 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
3670 ft
11646
3670 ft
5866
10491 ft
42103
10491 ft
11469
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
2082 ft
15440
2082 ft
0
0 ft
0
0 ft
0
5380 W
14937
0
0
0W
0
0
0
12960 W
40545
0
0
162
30454
33210
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
155125
33210
17335
0

ENVELOPE LOADS FOR SPACE '' 03rd Flr.-ODC C&D '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

1304

0.107

4139

2083

1597

0.107

5065

2552

770

0.107

2443

1230

10491

0.073

42103

11469

Page 38 of 42

Air System Sizing Summary for 03rd.Flr-Hub Room-A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ................ 03rd.Flr-Hub Room-A&B
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 186.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.9
Total coil load ....................................................... 23.2
Sensible coil load .................................................. 23.2
Coil CFM at Jan 2000 .......................................... 1373
Max block CFM at Jan 2300 ................................ 1373
Sum of peak zone CFM ....................................... 1445
Sensible heat ratio .............................................. 1.000
ft/Ton ................................................................... 96.3
BTU/(hr-ft) ......................................................... 124.6
Water flow @ 10.0 F rise ..................................... 4.64

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................. Jan 2000


OA DB / WB ................................................... 89.2 / 70.0
Entering DB / WB ........................................... 74.4 / 44.7
Leaving DB / WB ........................................... 57.7 / 36.3
Coil ADP .................................................................. 55.8
Bypass Factor ........................................................ 0.100
Resulting RH ................................................................ 0
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.2

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jan 2300 ............................... 1373 CFM
Standard CFM ..................................................... 1286 CFM
Actual max CFM/ft ............................................... 7.38 CFM/ft

Fan motor BHP ........................................................ 0.75 BHP


Fan motor kW .......................................................... 0.60 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 39 of 42

Space Design Load Summary for 03rd.Flr-Hub Room-A&B


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 03rd.Flr-Hub Room-A&B '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jan 2300
HEATING DATA AT DES HTG
COOLING OA DB / WB 85.2 F / 68.8 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
0 ft
0
0 ft
0
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
874 ft
699
874 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
93 W
222
0
0
Task Lighting
0W
0
0
0
Electric Equipment
6000 W
20472
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
21393
0
0
0

TABLE 1.1.B.

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 03rd.Flr-Hub Room-A&B '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

Page 40 of 42

Air System Sizing Summary for 03rd.Flr-Hub Room-C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

Air System Information


Air System Name ................ 03rd.Flr-Hub Room-C&D
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 167.0 ft
Location .............................................. Hyderabad, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.9
Total coil load ....................................................... 23.2
Sensible coil load .................................................. 23.2
Coil CFM at Jan 2300 .......................................... 1373
Max block CFM at Jan 2300 ................................ 1373
Sum of peak zone CFM ....................................... 1445
Sensible heat ratio .............................................. 1.000
ft/Ton ................................................................... 86.5
BTU/(hr-ft) ......................................................... 138.8
Water flow @ 10.0 F rise ..................................... 4.64

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................. Jan 2300


OA DB / WB ................................................... 85.2 / 68.8
Entering DB / WB ........................................... 74.3 / 44.7
Leaving DB / WB ........................................... 57.6 / 36.3
Coil ADP .................................................................. 55.8
Bypass Factor ........................................................ 0.100
Resulting RH ................................................................ 0
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.2

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM at Jan 2300 ............................... 1373 CFM
Standard CFM ..................................................... 1286 CFM
Actual max CFM/ft ............................................... 8.22 CFM/ft

Fan motor BHP ........................................................ 0.75 BHP


Fan motor kW .......................................................... 0.60 kW
Fan static ................................................................. 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.70

CFM/person ............................................................. 0.00 CFM/person

Page 41 of 42

Space Design Load Summary for 03rd.Flr-Hub Room-C&D


Project Name: DCS Block C WIPRO @Gopanpally
Prepared by: Jacobs Engineering

03/05/2016
10:10AM

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 03rd.Flr-Hub Room-C&D '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jan 2300
HEATING DATA AT DES HTG
COOLING OA DB / WB 85.2 F / 68.8 F
HEATING OA DB / WB 55.0 F / 48.0 F
OCCUPIED T-STAT 73.4 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft
0
0 ft
Wall Transmission
0 ft
0
0 ft
0
Roof Transmission
0 ft
0
0 ft
0
Window Transmission
0 ft
0
0 ft
0
Skylight Transmission
0 ft
0
0 ft
0
Door Loads
0 ft
0
0 ft
0
Floor Transmission
0 ft
0
0 ft
0
Partitions
901 ft
721
901 ft
0
Ceiling
0 ft
0
0 ft
0
Overhead Lighting
84 W
199
0
0
Task Lighting
0W
0
0
0
Electric Equipment
6000 W
20472
0
0
People
0
0
0
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
>> Total Zone Loads
21392
0
0
0

TABLE 1.1.B.

Hourly Analysis Program v4.70

ENVELOPE LOADS FOR SPACE '' 03rd.Flr-Hub Room-C&D '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(ft) (BTU/(hr-ft-F))
Coeff.
(BTU/hr)
(BTU/hr)

HEATING
TRANS
(BTU/hr)

Page 42 of 42