Objective
Determine or estimate the root cause of a fault based on
the voltage and current waveforms captured by power
quality monitors.
Approach: Perform waveform characterization and identify
unique features.
Underground cable faults: cable, joint or splice, and termination
failures
Animal contacts
Tree contacts
Lightning induced
Page - 2
Page - 3
Page - 5
Duration 32 samples
Magnitude >> 5 p.u.
Duration 64 samples
Magnitude >> 2-3 p.u.
Duration 32 samples
Magnitude < 1 p.u.
Duration 64 samples
Magnitude 1 p.u.
Page - 6
Page - 8
Page - 9
Short duration impulses/ high frequency oscillations occur once each half cycle
Impulses occur at same instant as faulted phase current zero crossing
For all cable faults, oscillation frequency is from 0.9 to 4.0 kHz
Cable faults in joints with tracking, oscillation frequency is from 1.3 to 1.9 kHz
Oscillations or impulses may appear at different instants of event
Impulses can continue throughout duration of even or appear near middle or
end of event
Oscillation of 1.9 kHz in the Voltage Waveform during a Cable Fault in Joint with Tracking
Page - 10
Page - 11
Page - 12
arc
(t ) =
r =1
a V sin( r t )
r a
Method proposed by
Radojevic et al.
Looking from the PQ
monitoring site
VF =R.I F +L.
dI F
+Varc .sign(I F )
dt
Page - 14
Implementation
[VF ] = [I F
dI F
dt
sign(I F )] L
V
arc
a1 = I F
dIF
dt
a3 = sign(I )
a2 =
A = [a1a2a3 ]
x = [R L Varc]T
b =V
Ax = b
Page - 15
Implementation
dI F
[VF ] = [I F
sign(I F )] L
dt
V
arc
Residual/ Neutral current (In) is used instead of fault current for term IF
In = Ia + Ib + Ic
I 0 = I1 = I 2 =
Vf
In
=
3 z1 + z 2 + z0
z +z +z
2z + z
zs = 1 2 0 = 1 0
3
3
Vf
In
= zs
Page - 16
Validation of Algorithm:
Arc Voltage Waveshapes (actual data)
Station B - Downstream
Station A - Upstream
Page - 17
18
Page - 18
Vb
Vc
Ia
Ib
Ic
Vo ltag e (V )
10000
5000
0
-5000
-10000
Cur re nt (A)
10000
5000
0
-5000
0.00
Harmonics
0.05
0.10
Time (s)
0.15
PQView
Page - 19
Page - 20
Lightning
28
Animal
Contact
66
Tree
Contact
143
Page - 21
90.00
80.00
65.73
% of Events
70.00
60.00
50.00
42.42
40.00
30.00
24.24
20.00
24.48
21.21
12.12
10.00
5.59
4.20
3.57
10.71
0.50
0.00
Animal Contact
Spring
Tree Contact
Summer
Fall
Lightning
Winter
% of Events
88.03
75.00
64.37
35.66
12.12
Animal Contact
Tree Contact
Daytime
26.61
Lightning
Night time
Page - 24
Event
Insertionanglearound
peak15 of(90)
OffpeakInsertion
angle
Total
cases
AnimalContact
43(70.5%)
18(29.5%)
61
TreeContact
66(73.33%)
24(26.67%)
90
LightningInduced
16(84.21%)
3(15.79%)
19
Page - 25
Event
Singlephasefaults
Multiphasefaults
Totalcases
AnimalContact
53(86.88%)
8(13.12%)
61
TreeContact
66(73.33%)
24(26.67%)
90
LightningInduced
8(42.10%)
11(57.90%)
19
Page - 26
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
Animal Contact
Cable Failure
Lightning
Tree contact
0.1
0
200
400
600
800
1000
1200
1400
1600
1800
2000
Concluding Remarks
A fault cannot be completely described by a single
characteristics.
Combining common and unique characteristics are
necessary to determine the root cause of the fault.
Page - 28