Вы находитесь на странице: 1из 4

Isolating switching amplifier

2-channel
IM1-22EX-T

The 2-channel isolating switching amplifier


IM1-22EX-T is equipped with an intrinsically
safe input circuit.
Sensors according to EN 60947-5-6 (NAMUR) can be connected to the device or potential-free contactors.
The output circuits feature two potential-free
and short-circuit protected transistors.

Six front panel switches are available to set


the output mode separately for each channel
(NO/NC mode), as well as to enable/disable
wire-break (WB) and short-circuit (SC) monitoring separately.
When using mechanical contacts, wire-break
and short-circuit monitoring must be switched
off or the contact must be wired with resistors
(II) (see circuit diagram).

ATEX, IECEx, CSA, FM, UL, NEPSI,


-KOSHA, GOST

Installation in zone 2

2 transistor outputs

Adjustable current flow (NO/NC)

Input circuits monitored for wire-break/


short-circuit (ON/OFF switchable)
Complete galvanic isolation

The Pwr LED lights green to indicate operational readiness. The 2-color LEDs 1 and
2 below light yellow to indicate the output
switching status. In the event of an input circuit error, the associated 2-color LED turns
red, provided the input circuit monitoring function is activated. Thereupon the belonging
output transistor is blocked.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Isolating switching amplifier


2-channel
IM1-22EX-T

Dimensions

Type code
Ident no.

IM1-22EX-T
7541232

Flammability class acc. to UL 94

V-0

Nominal voltage
Operating voltage
Frequency
Operating voltage range
Power consumption
Power loss, typical

Universal voltage supply unit


20250 VAC
4070 Hz
20125 VDC
3 W
0.54 W

NAMUR
No-load voltage
Short-circuit current
Input resistance
Cable resistance
Switch-on threshold:
Switch-off threshold:
Wire breakage threshold
Short-circuit threshold

EN 60947-5-6
8.2 VDC
8.2 mA
1 k
50
1.55 mA
1.75 mA
0.1 mA
6 mA

Semicondutor output circuit(s)


Output circuits (digital)
Switching voltage
Switching current per output
Switching frequency
Voltage drop

2 x transistor (potential-free, short-circuit protected)


30 VDC
50 mA
5000 Hz
2.5 V

Galvanic isolation
Test voltage

2.5 kV

Ex approval acc. to conformity certificate


Application area
Protection type
Max. values:
Max.output voltage Uo
Max. output current Io
Max. output power Po
Characteristic
Rated voltage
Internal inductance/capacitance Li/Ci
External inductance/capacitance Lo/Co

TV 04 ATEX 2553
II (1) G, II (1) D
[Ex ia Ga] IIC; [Ex ia Da] IIIC
terminal connection: 1+4 / 2+5
9.6 V
11 mA
26 mW
linear
250 V
Li = 65 H, Ci negligibly small
Ex ia
Lo
[mH]
Co
[F]

Ex approval acc. to conformity certificate


Application area
Protection type
Max. values:
Max.output voltage Uo
Max. output current Io
Max. output power Po
Characteristic
Internal inductance/capacitance Li/Ci
External inductance/capacitance Lo/Co

Approval
MTTF

IIC
10

IIB
10

20

1,1

0,83

0,74

5,2

3,8

3,4

TV 06 ATEX 552968 X
II 3 G
Ex nA [ic Gc] IIC/IIB T4 Gc
terminal connection: 1+4 / 2+5
9.6 V
11 mA
26 mW
linear
Li = 65 H, Ci negligibly small
Ex ic
Lo
[mH]
Co
[F]

IIC

IIB

10

10

1.9

1.4

1.2

11

7.5

6.6

SIL 2 acc. to EXIDA FMEDA


400 years acc. to SN 29500 (Ed. 99) 40 C

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Isolating switching amplifier


2-channel
IM1-22EX-T
Indication
Operational readiness
Switching state
Error indication
Mechanical Data
Protection class
Ambient temperature
Storage temperature
Relative humidity
Dimensions
Weight
Mounting instruction
Housing material
Electrical connection
Terminal cross-section
Tightening torque

green
yellow
red

IP20
-25+70 C
-40+80C
95 %
104 x 18 x 110 mm
146 g
For mounting on DIN rail or mounting panel
polycarbonate/ABS
4 x 3-pole removable terminal blocks, reverse polarity protected, screw connection
1 x 2.5 mm / 2 x 1.5 mm
0.5 Nm
2

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Isolating switching amplifier


2-channel
IM1-22EX-T

Accessories
Type code

Ident no.

Description

IM-CC-3X2BU/2BK

6900475

Cage clamp terminals for IM modules ( Ex-devices with 18

Dimension drawing

mm overall width); includes: 2 pcs. 3-pin blue terminals and 2


pcs. 3-pin black terminals.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com