Introduction to ED
Prof. Jarmo Partanen, D.Sc Jukka Lassila
Topics of lectures
Introduction to Electricity Distribution, 27.10 (12.30 16), 6426
Methods for electrical, economic and reliability calculations, 28.10 (12.15-16), 6426
Strategic planning of electricity distribution network, 3.11 (12.15-14), 6426
Planning of primary substations and medium voltage networks 4.11 (12.15-16), 6311
Structures and planning of distribution substations and low voltage networks, 18.11 (12.3016), 6311
Short circuit and earth fault protection of distribution networks 21.11 (8.15-12), 6311
Operation of distribution systems 24.11 (12.30-16), 6426
Electricity distribution automation, 1.12 (10.15 -14), 6426
Smart Grids, 2.12 (12.30-16), 6311
Introduction to ED
Local 110 kV networks
Primary substations 110/20 kV (110/10 kV)
Medium voltage networks 20 kV (10 kV)
Distribution substations 20/0,4 kV
Low voltage networks 1.0, 0.4 kV
Industrial networks 20, 10, 6, 3, 0,6, 0,5, 0,4 kV
Electricity distribution network
radially operated
a lot of lines and nodes
low prices of components (compared to transmission level)
a lot of similar design and construction tasks
well analysed cases
principles
Background
400 V
20 kV
110/20 kV
Primary
substation
(10...30 MVA)
20 kV
400 V
Mostly overhead lines (400 V, 20 kV, 110 kV), 3-phase system at all voltage
levels
Feeders, in Finland:
Total 350 000 km of distribution lines:
400 V low voltage (62 %) and 20 kV medium voltage (38 %) lines
MV (20 kV): 30-50 km/feeder
LV (400 V): 116 m/customer
Lappeenranta University of Technology
- 16 000 customers
- 112 km 20 kV
- Peak power 45 MW
- Cabling rate 72 %
- 11 000 customers
- 430 km of 20 kV network
- Peak power 50 MW
- Cabling rate 12 %
MARTINKYL
110/20 kV
110/20 kV
20/0.4 kV distribution
substation (30200 kVA)
KALLBCK
20 kV underground cable
450 000
110/20 kV
LANDBO
Number of customers
400 000
350 000
300 000
250 000
200 000
150 000
1)
2)
10 miles
100 000
20 kV overhead line
50 000
0
110/20 kV
20/0.4 kV
20 kV
Road
500 m = 0.3
miles
20 kV overhead line
7
110/20 kV
NEED FOR..
MARTINKYL
= 20/0.4 kV
distribution
substation
20 kV
20 kV
400 V
400 V
MASSBY
KALLBCK
LANDBO
20 kV
400 V
20 kV medium voltage network
400 V
20/0.4 kV distribution
substation (30200 kVA)
400 V ABC
line
400 V
(3-phase system)
AMR
400 V
Road
150 feet
20 kV
400 V underground cable
Lappeenranta University of (3~)
Technology
10
Elenia
Fortum
E.ON
85 companies
10 biggest, customers:
Fortum Shknjakelu Oy
Helsingin Energia
Vattenfall Siirto Oy
Espoon Shk Oyj
Tampereen Shklaitos
Uudenmaan Shkverkko Oy
Savon Voima Oyj
Jrvi-Suomen Energia Oy
Vantaan Energia Oy
Pohjois-Karjalan Shk Oy
403374
318 695
183 464
119 560
117 976
109 447
99 562
88 213
84 760
80 177
11
1-busbar system
1-busbar system
2-busbar system
double-busbar system
20 kv feeder shells
circuit breaker
disconnectors
CT; load current, protection, zero current coils
protection relays; short circuit, earth fault, recloser,
voltage measurement cell
busbar voltage measurement
earth fault protection, neutral voltage, open delta connection
12
PM1
25 MVA
Teknikum
2 MW
Nybacka
1 MW
Myllynummi
2.0 MW
Koff
4.5 MW
Sorsakorpi
1.5 MW
Nissil
2.5 MW
Alikerava II
PM2
16 MVA
Alikerava I
Varayhteys
uudelle
asemalle
SA1_10
Varayhteys
uudelle
asemalle
SA1_8
Omakytt Koff
SA1_22
SA1_20
Kilta
SA1_18
Jspilnpiha
SA1_16
SA1_21
SA1_19
SA1_17
SA1_15
SA1_13
SA1_11
SA1_9
SA1_7
SA1_5
SA1_3
Sytt
uudelta
asemalta
II
Peltomenkatu
Keskusta
Sompio
Kannisto
Sampola
Savio
Ifi/Stowe
Voimala
SA1_14
Lapila
SA1_12
SA1_4
Sytt
uudelta
asemalta I
SA1_2
13
14
15
Introduction to ED distribution
substations
Disconnector between 20 kv line and transformer
Substation + transformer
pole mounted substations in overhead networks
bad mounted or building substations in cable networks
16
Introduction to ED
low voltage networks
3-phase system, neutral (neutral conductor) earthed
Radial network, rarely backup connections
AMKA-conductors (aerial bundled cable) in rural areas
16120 mm2, 1015 k/km
17
Neutral conductor
MV branch line
Switchgear/
Circuit breaker
Fuses
MV trunk line, e.g. 11 kV
Sectionaliser, recloser
KJ
MV-lines
Trunk line: 3 phases + neutral
Branch line: 1, 2 or 3 phases + neutral
LV
LV (127 V)
a)
b)
23.10.2014
Lappeenranta University of Technology
c)
MV-lines in Canada, 11 kV
1-phase 11 kV line
23.10.2014
Lappeenranta University of Technology
MV-lines in Canada, 11 kV
Fuse
1-phase
transformer
Neutral
conductor
23.10.2014
Lappeenranta University of Technology
MV-lines in Canada, 11 kV
Fuses
3-phase
transformer
23.10.2014
Lappeenranta University of Technology
losses
main 20 kv overhead lines
thermal capacity
main 20 kv and 0,4 kv lines in cable networks
short-circuit current
conductors of 20 kv branch lines near to feeding point (110/20 kv primary
substation)
reliability
medium voltage networks and primary substations
economy
always important
Lappeenranta University of Technology
23