Fan Selections and Their Energy Impacts, Part 1 of 2

1 of 8

http://hpac.com/print/iaq-ventilation/fan-selections-and-their-energy-imp...

print | close

Fan Selections and Their Energy Impacts, Part 1 of 2

By KHALIL KAIROUZ, PhD, PE, Carollo Engineers Inc., Costa Mesa, Calif., and DALE PRICE, M&P Air
Components Inc., Lake Arrowhead, Calif.
Tue, 2016-08-23 09:47

Evaluating fans and fan systems and their impact on operating costs
Fans and fan systems can be significant consumers of energy in commercial applications and the greatest
consumer in industrial ones. Concerned about underperformance, designers tend to compensate for
uncertainties by adding capacity to fans. Oversizing fan systems creates problems that can increase costs and
decrease reliability. This article explains how to evaluate fans and fan systems and their impact on operating
costs. It does so by examining the criteria most commonly used in fan selection:
Air-stream characteristics.
Capacity.
Pressure.
Power.
Efficiency.
Fan and system curves.

Air-Stream Characteristics

Fan manufacturers published ratings for airflow, pressure, and power are based on laboratory conditions using
standard cubic feet per minute (scfm) for airflow and 0.075 lb per cubic foot for fan-inlet-air-stream density
(corresponding to dry air at 70F and atmospheric pressure of 29.92 in. Hg). Normally, they can be used for fan
selection and evaluation when the difference between standard density and actual site density at a fan inlet is
less than 5 percent. This occurs when:
Fan-inlet temperature is within 30F of the standard +70F dry air.
Fan-inlet pressure is within 12 in. wg of the standard atmospheric pressure of 29.92 in. Hg.
Fan-inlet-air-stream moisture content is less than 0.02 lb of water per pound of dry air or the dew point
is less than 80F.
Installation is between 1,000 ft below and 1,000 ft above sea level (asl).
In cases in which at least one of the above parameters is not met, inlet-air-stream density should be corrected to
actual conditions (actual cubic feet per minute [acfm]). This is done by multiplying the standard density,
airflow, pressure, and power by each parameters density factor. The density factors will be equal to the actual
inlet density divided by the standard inlet density of 0.075 lb per cubic foot. The density factor (F) for each
parameter is estimated as follows:
Density-factor temperature, degrees Fahrenheit:
F(t) = 530 (460 + Tinlet)

25/08/2016 1:35

Fan Selections and Their Energy Impacts, Part 1 of 2

2 of 8

http://hpac.com/print/iaq-ventilation/fan-selections-and-their-energy-imp...

Density-factor pressure, inches water gauge:


F(p) = 407 (407 + Pinlet)
Density-factor moisture, pounds of water per pound of dry air:
F(m) = (1 + w) (1 + 1.607w)
where:
w = humidity ratio, pounds of water per pound of dry air
Density-factor elevation, feet above sea level:
F(e) = [1 (6.73 106) z]5.258
where:
z = elevation, feet
Overall density-correction factor, then, is given by:
F = F(t) F(p) F(m) F(e)
Example 1: Density-factor calculation. For a fan capable of handling 176F air at an inlet static pressure of
15 in. wg, a humidity ratio of 0.04 lb of water per pound of dry air, and a site elevation of 3,000 ft asl, we will
calculate the required density factor and actual air density:
Inlet temperature, 176F:
F(t) = 530 (460 + 176) = 0.83
Inlet static pressure, 15 in. wg:
F(p) = (407 + 15) 407 = 0.96
Inlet moisture, 0.04 lb water per pound dry air:
F(m) = (1 + 0.04) [1 + (1.607 0.04)] = 0.98
Elevation, 3,000 ft asl:
F(e) = [1 (6.73 106) 3,000]5.258 = 0.90
Density factor:
F = 0.83 0.96 0.98 0.90 = 0.70
The actual air-stream density at the fan inlet is the product of the density factor and the standard air density
(0.075 lb per cubic foot) and is calculated as:
(actual) = 0.70 0.075 lb per cu ft = 0.0525 lb per cu ft
Example 2: Fan performance. If a fan were selected from a manufacturers standard catalogued ratings for
a volumetric-flow rate of 30,000 acfm, a static pressure of 15 in. wg, 1,910 rpm, and 86 hp, but installed at the
25/08/2016 1:35

Fan Selections and Their Energy Impacts, Part 1 of 2

3 of 8

http://hpac.com/print/iaq-ventilation/fan-selections-and-their-energy-imp...

above conditions, the operating performance would be:


Actual volumetric capacity: 30,000 acfm.
Actual mass-flow capacity: 1,575 lb per minute (30,000 0.0525).
Actual static-pressure delivery: 10.5 in. wg (15 in. wg 0.70).
Actual fan-shaft power consumption: 60.2 hp (86 hp 0.70).
Actual inlet-air-stream density: 0.0525 lb per cubic foot (0.70 0.075).
Key point: With proper definition of inlet-air-stream conditions for density, temperature, pressure, moisture,
and elevation, corrections between a fan manufacturers published ratings and actual operating conditions can
be made to ensure proper fan selection and performance.

Capacity

Fan capacity can be stated in terms of either volumetric-flow rate or mass-flow rate.
Volumetric-flow rate:
Is the normal basis for fan ratings.
Normally is stated in cubic feet per minute.
Represents the actual volumetric-flow capacity of a fan at a given speed and static pressure.
Is constant for any air-stream density.
Mass-flow rate:
Normally is stated in pounds per minute.
Represents the mass-flow capacity of a fan at a given speed, static pressure, and inlet density.
Is calculated by multiplying volumetric-flow rate by actual air-stream density at a fans inlet.
Varies with changes in air-stream density.
Figure 1 is a simplified illustration of a centrifugal-fan wheel and a substance conveyed by the fan. If each scoop
of the fan wheel has a volumetric capacity of 5 cu ft and the speed is a constant 1,000 rpm, the volumetric
capacity is 30,000 cfm (5 cu ft per scoop 6 scoops 1,000 rpm). The mass-flow rate is:

25/08/2016 1:35

Fan Selections and Their Energy Impacts, Part 1 of 2

4 of 8

http://hpac.com/print/iaq-ventilation/fan-selections-and-their-energy-imp...

5 cu ft per scoop 6 scoops 1,000 rpm density (pounds per cubic foot) of substance conveyed
Assuming the substance is air at standard conditions and standard density of 0.075 lb per cubic foot, the mass
delivery is 2,250 lb per minute (30,000 cfm 0.075 lb per cu ft).
Assuming the substance is air at the non-standard conditions in examples 1 and 2 with a density of 0.0525 lb
per cubic foot, the mass delivery is 1,575 lb per minute (30,000 cfm 0.0525 lb per cu ft).
If the fan system must maintain a minimum mass-flow rate of 2,250 lb per minute, then the required actual
volumetric-flow rate is 42,857 cfm (2,250 lb per min 0.0525 lb per cu ft) and the fan should be selected on the
volumetric basis of 42,857 acfm.
Key point: At constant speed, a fan will deliver a constant volumetric-flow rate and a variable mass-flow rate,
with the mass-flow rate varying directly with the density factor, or the ratio of actual density to standard
density.

Pressure

In air-moving applications, the most common pressure is static pressure. Still, for the proper selection and
operation of fans, one must have a basic understanding of all pressures:
Total pressure (TP).
Velocity pressure (VP).
Static pressure (SP).
Fan static pressure (FSP).
Fan velocity pressure (FVP).
Fan total pressure (FTP).
Figure 2 shows total-, static-, and velocity-pressure components for a short section of ductwork. Total pressure
is parallel to and measured in the direction of flow. Velocity pressure is parallel to the direction of flow and can
25/08/2016 1:35

Fan Selections and Their Energy Impacts, Part 1 of 2

5 of 8

http://hpac.com/print/iaq-ventilation/fan-selections-and-their-energy-imp...

be measured only indirectly as the difference between total pressure and static pressure. Static pressure is
exerted equally in all directions and measured perpendicularly to the direction of flow.

Total pressure. Total pressure is the algebraic sum of kinetic energy (velocity pressure) and potential energy
(static pressure) at any point in a system. Thus, total pressure represents the total energy at the point of
measurement of fluid flow:
TP = VP + SP
Total pressure can be positive or negative, depending on the measurement location.
Velocity pressure. Velocity pressure is kinetic energy in the direction of flow that causes a fluid at rest to
flow:
VP = TP SP
VP = (V 1,097)2 (actual)
therefore:
VP = (V 4,005)2 F
Velocity pressure is mutually convertible with static pressure. It always is positive, regardless of its
measurement location.
Static pressure. Static pressure is potential energy exerted in all directions by a fluid:
SP = TP VP
Static pressure is mutually convertible with velocity pressure. It can be positive or negative, depending on the
measurement location.

25/08/2016 1:35

Fan Selections and Their Energy Impacts, Part 1 of 2

6 of 8

http://hpac.com/print/iaq-ventilation/fan-selections-and-their-energy-imp...

Fan total pressure vs. total pressure. While total pressure is the sum of velocity pressure and static
pressure, fan total pressure is the increase in total pressure through or across a fan and represents the total
work delivered by the fan. As defined in Air Movement and Control Association (AMCA) International
standards, fan total pressure normally is not used for fan-rating purposes (this is by custom, not because of any
deficiency in the rating technique). However, an understanding of fan total pressure is important for proper
selection and field measurement of fans and fan systems. Fan total pressure is expressed as:
FTP = TPfan outlet TPfan inlet
FTP = (SPoutlet + VPoutlet) (SPinlet + VPinlet)
When fan-inlet velocity pressure and fan-outlet velocity pressure are the same, the pressures cancel each other,
and the fan-total-pressure calculation is simplified to:
FTP = SPoutlet SPinlet
In this case, fan total pressure simply is the difference between fan-inlet static pressure and fan-outlet static
pressure. When a fan is specified on the basis of summing inlet and outlet static pressures (static-pressure rise
across the fan), the fan rating is on the fan-total-pressure basis.
Fan velocity pressure. AMCA International defines fan velocity pressure as velocity pressure based on the
average velocity at a fans discharge. The average velocity at a fans discharge typically is calculated as fan outlet
velocity divided by fan outlet area (square feet). For standard air, this is:
FVP = (fan outlet velocity 4,005)2
Fan static pressure vs. static pressure. Fan static pressure as defined by AMCA International is the basis
for most published fan ratings today. While static pressure is the difference between total pressure and velocity
pressure, fan static pressure is defined as fan total pressure minus fan velocity pressure:
FSP = FTP FVP
FSP = (TPfan outlet TPfan inlet) VPfan outlet
FSP = (SPoutlet + VPoutlet) (SPinlet + VPinlet) VPoutlet
Because the outlet velocity pressures are identical and cancel each other:
FSP = SPoutlet SPinlet VPinlet
or, more commonly:
FSP = SPoutlet TPinlet
However, it is not uncommon to find the static pressure used by system designers for fan selection calculated
simply as:
SPoutlet SPinlet
Often in these cases, the fan is oversized by the inlet-velocity-pressure energy component, resulting in excessive
energy consumption.
When static pressure used for fan sizing is calculated in this manner, a fan cannot perform exactly on the fan
curve because of the velocity pressure at the fan inlet normally not accounted for by the fan manufacturer.
25/08/2016 1:35

Fan Selections and Their Energy Impacts, Part 1 of 2

7 of 8

http://hpac.com/print/iaq-ventilation/fan-selections-and-their-energy-imp...

Figures 3 and 4 present examples of how to calculate fan pressure for various fan configurations.

Key point: For optimum energy utilization


and fan performance, follow the fan-staticpressure calculations issued by AMCA
International.
Example 3: Fan pressureactual and
equivalent. Actual fan pressure normally is
defined as the pressure a fan delivers at
actual operating conditions, while equivalent
fan pressure normally is defined as the
pressure a fan delivers at standard conditions
(0.075-lb-per-cubic-foot air-stream density).
Because fan manufacturers catalogue ratings
are based on standard conditions, it is
important to make sure a fan is selected to achieve its design pressure at actual operating conditions.
Referring to examples 1 and 2, a fan with a catalogued fan static pressure of 15 in. wg will produce a fan static
pressure of only 10.5 in. wg at actual operating conditions. If 15-in.-wg fan static pressure is required at actual
operating conditions, a fan must be selected for a catalogued fan static pressure of 21.4 in. wg (15 0.7).
Normally, the designer would note a requirement of 15 in. wg at standard conditions and 21.4 in. wg at actual
operating conditions.
So far, we have discussed air-stream characteristics, capacity, and pressure. Next month, in Part 2 of this
two-part article, we will discuss fan power, fan efficiency, and fan-system curves.
Khalil Kairouz, PhD, PE, is an associate vice president for Carollo Engineers Inc., a consulting firm
specializing in water and wastewater treatment. He has bachelors and masters degrees in mechanical
engineering from the University of Louisiana at Lafayette and a doctorate from Claremont Graduate
University. He has taught in the mechanical-engineering departments of Loyola Marymount University and
California State University. Dale Price is president of M&P Air Components Inc., a company specializing in
ventilation and air-distribution equipment. He has a bachelors degree is mechanical engineering and is an
active member of an American Industrial Hygiene Association task force on fan efficiency. He has taught

25/08/2016 1:35

Fan Selections and Their Energy Impacts, Part 1 of 2

8 of 8

http://hpac.com/print/iaq-ventilation/fan-selections-and-their-energy-imp...

numerous training sessions on fan systems and their effects to employees of state and federal agencies and
private industries.
Did you find this article useful? Send comments and suggestions to Executive Editor Scott Arnold at