The power electronics components of a photovoltaic (PV) system, such as grid-direct inverters, have maximum
and minimum voltage inputs; therefore, you need to adjust the module voltage values to meet your specific
needs on each project. This ensures the proper operation of your system. But before jumping into any voltage
correction calculations, its important to understand the fundamental voltage and current outputs from PV
modules and how they vary with changes in temperature and sunlight intensity (irradiance).
PV modules are rated with two different voltage values open circuit voltage and maximum power voltage.
Open circuit voltage occurs whenever there isnt any load connected to the PV modules, and current is not
flowing. Maximum power voltage is the amount of voltage produced by the module that corresponds to the
maximum amount of power for that module. The yellow line on Fig. 1below, a typical current versus voltage
curve, shows you that the open circuit voltage (Voc) value occurs at the bottom right side of the curve. At this
point, the voltage is at its maximum, and current flow is zero. The maximum power voltage (Vmp) is directly
below the knee of the curve shown. Voc is always a greater value than Vmp for PV modules. Module
manufacturers will commonly show the power versus voltage on the same graph, as seen with the blue line.
07-03-15 3:02 PM
2 of 7
http://ecmweb.com/print/green-building/highs-and-lows-photovoltaic-sys...
Fig. 1. A typical current verus voltage curve for PV modules shows how each factor relates to the other at a
defined temperature and irrdiance level. The module's power versus voltage is also represented on this graph.
If you draw a straight line down from the knee of the IV curve, you intersect with the Vmp value. If you also draw
a straight line to the left of the knee, you intersect with the maximum power current value (Imp). The product of
those two values (Vmp Imp) results in the maximum power value in watts. The final point shown on the upper
left corner of Fig. 1 is the short circuit current (Isc). That is the scenario where the positive and negative
terminals from the PV module are in direct contact. While this situation may not damage the module, current is
flowing within the module(s), and care must be taken when interrupting the current flow. Improper
disconnection can result in pulling a DC arc that can be difficult to extinguish.
All PV modules will list all five values on their spec sheets and, as a listing requirement, on a label attached to
each module. The values reported are always at standard test conditions (STC). For module voltage and current
values, the two critical STC values are for temperature [25C (77F)] and irradiance [1,000 W/m2].
The temperature value is for the PV module itself, which will be a function of the ambient temperature. You can
use some tools noted in this article to estimate module temperature based on ambient temperature values. The
irradiance value can be related to a bright sunny day at sea level. Both of these values will vary over the course of
a day. Therefore, its your job to realize how these changes in environmental conditions affect the voltage and
current.
The amount of current produced by a PV module is directly proportional to how bright the sun is. Higher levels
of irradiance will cause more electrons to flow off the PV cells to the load attached. The amount of voltage
produced by the PV module is affected by the irradiance value, but not as much as most people initially think. In
fact, Fig. 2 below shows a graph of a typical modules IV curve in response to irradiance. The PV modules
voltage changes very little with varying levels of irradiance. Crystalline PV modules will produce approximately
07-03-15 3:02 PM
3 of 7
http://ecmweb.com/print/green-building/highs-and-lows-photovoltaic-sys...
90% of their rated voltage at irradiance levels of approximately 200 W/m2. As the irradiance value continues to
increase, so does the voltage but at a much slower rate. Therefore, for the purposes of this article and your
design methodologies in general it is safe to assume that if there is ambient light, the PV module has the
ability to produce its full rated voltage.
Fig. 2. A PV module's current versus voltage curve varies with the irradiance or intensity of sunlight. As the
graph shows, current dramatically changes as irradiance varies, but voltage remains relatively constant.
A PV modules voltage output is actually a variable value that is primarily affected by temperature. The
relationship between module voltage and temperature is actually an inverse one. As the modules temperature
increases, the voltage value decreases and vice versa. You can see this correlation in Fig. 3 below. The variable
output voltage is an important factor for both cold temperatures and hot temperatures, and both must be
considered during system design. When temperatures are cold, the PV module will increase in voltage. When it
is hot, the modules voltage will drop. Both are simple and unavoidable facts in PV design. So as long as you
account for both properly, you wont have any issues in the performance of your array at least not due to the
voltages.
07-03-15 3:02 PM
4 of 7
http://ecmweb.com/print/green-building/highs-and-lows-photovoltaic-sys...
Fig. 3. As temperature changes, a module's current versus voltage curve will also change, primarily in terms
of voltage.
PV module manufacturers will report the amount of change their modules experience in the form of
temperature coefficients (TCs), most often in terms of a percentage per degree Celsius (e.g., TC Voc =
-0.35%/C). This means that for every degree change in temperature, the modules Voc will change in the
opposite direction by 0.35%. For example, if the PV module got colder by 1C, the PV voltage would increase by
0.35%. This specific value happens to be common for crystalline PV modules.
There are two additional points to make on TC values. One, there are two TCs for every PV module one for the
Voc and one for the Vmp. The amount of change experienced by each is different and needs to be calculated
differently. Secondly, PV module manufacturers rate their modules at 25C. This means that when applying
temperature coefficients, you need to figure out how many degrees Celsius the PV module is operating from the
STC value of 25C.
PV modules will wake-up every morning with very little sunlight. Because the PV array is sitting outside, the
temperatures of the modules will be the exact same value as the night air. Because the sun isnt actually hitting
the array immediately, the modules will not immediately produce any current, which means they will
immediately go to open circuit voltage. If the temperature of the module is less than the STC value of 25C, the
modules Voc value will actually be greater than the value listed on the modules listing label. For our discussion,
we will consider the temperature of the module to be equal to ambient temperature at daybreak. You will
estimate the new module voltage to verify too many PV modules arent placed in series and exceed the power
electronics maximum input value.
Once the sun comes up a bit and is able to reach the array, there will be enough irradiance to allow current to
flow, which will result in the modules voltage dropping from Voc to a value close to the Vmp point. Where the
voltage value lands exactly is a function of the temperature of the PV module. As the day wears on and the
module is exposed to the sun for a longer period of time the temperature of the module will continue to rise.
How hot the PV module finally gets depends on how hot the ambient temperature is and how close the module is
to anything that may trap heat, such as a rooftop. So to estimate the temperature of the PV modules in the
07-03-15 3:02 PM
5 of 7
http://ecmweb.com/print/green-building/highs-and-lows-photovoltaic-sys...
07-03-15 3:02 PM
6 of 7
http://ecmweb.com/print/green-building/highs-and-lows-photovoltaic-sys...
Using the values supplied in our example above, you can solve for Vadj as follows:
Vadj = 44.4V {100% + [(-3C - 25C) -.33%/C]}
= 44.4V {100% + [(-28C) -.33%/C]}
= 44.4V {100% + 9.24%}
= 44.4V {109.24%}
= 48.5V
What this tells us is we really need to apply a Voc value of 48.5V (not 44.4V) when determining how many
modules we can place in series on a specific inverter or other pieces of power electronics. The reason this is an
NEC issue is because placing too much voltage on equipment could potentially damage it or cause injury to
people.
The other calculation we need to make is for the Vmp value at high temperatures. This is not addressed in the
NEC, so you will have to use the calculation method to determine the answer (i.e., there isnt a Table you can
reference like there is for cold temperatures). In this calculation, the formula is exactly the same; you just have
to apply different values for each of the variables.
The first variable to consider is the temperature of the module. As mentioned earlier, the modules temperature
is a function of the ambient temperature plus the method used to mount the PV array. In this case, the array is
placed 5 in. from the roof surface, so we will estimate the PV module temperature to be 35C above the ambient:
Tmod = 37C +35C = 72C
Vadj = Vmp {100% + [(Tmod - 25C) TC Vmp]}
where,
Vadj is the temperature adjusted voltage
Vmp is the modules rated maximum power voltage
Tmod is the temperature of the PV module
25C is the STC condition we must adjust from
TC Vmp = Temperature correction factor in %/C
Again, using the values supplied in our example above, you can solve for Vadj as follows:
Vadj = 35.4V {100% + [(72C - 25C) -.45%/C]}
= 35.4V {100% + [(47C) -.45%/C]}
= 35.4V {100% + -21.15%}
= 35.4V {78.85%}
= 27.9V
This results in a PV module that will only produce 27.9V in the middle of the summer. Therefore, you need to
make sure that you have enough modules wired in series so that the sum of the modules adjusted voltages are
always above the minimum required by the power electronics while staying below the maximum values during
cold temperature periods.
If youre working with an inverter that can accept up to 500V maximum but needs 200V minimum, you can
calculate the acceptable number of modules in a series string as follows:
500V 48.5V = 10.3 modules
Thus, you could place a maximum of 10 modules in series and remain below the maximum in all temperatures
expected at your site.
On the low end, 200V 27.9V = 7.2 modules
07-03-15 3:02 PM
7 of 7
http://ecmweb.com/print/green-building/highs-and-lows-photovoltaic-sys...
Thus, you would need at least eight modules in a series string to remain above the minimum requirement at
your site.
As you can see, these calculations are an important part of the PV design process. In fact, many power electronic
manufacturers, especially grid-direct inverter manufacturers, supply on-line calculators to help you work
through these calculations. However, you shouldnt totally rely on their calculators, as they are not official parts
of their website. Prior to using these calculators you must always click a button acknowledging that the
information they present may not be fully accurate. Theyre not a bad tool to double check your calculations
though.
Mayfield is a principal with Renewable Energy Associates, Corvallis, Ore. He can be reached at
ryan@renewableassociates.com.
Source URL: http://ecmweb.com/green-building/highs-and-lows-photovoltaic-system-calculations