Вы находитесь на странице: 1из 7

RTU560

ABB Utilities GmbH

Remote Terminal Unit


Connections and Settings
Analog Output 23AA20

Application, characteristics and technical data have


to be taken from the hardware data sheet:
23AA20

1 KGT 150 401

Operation
The 23AA20 board has two galvanic isolated analog
output channels. Each of them can be configured individually to one of the following output current:
V
V
V
V

-5 mA...
-5 mA.....
-10 mA...
-20 mA...

0...+2.5 mA
0...+5 mA
0...+10 mA
0...+20 mA

Unipolar or live zero value output definitions have to


be specified by an RTU560 function parameter.

Processing function
The I/O microcontroller (EAP Ein- Ausgabe-Prozessor / Input- output processor) controls the two digital
to analog converters. It converts the received output
value from CMU (CMU = communication unit) into
the D/A format and force an output conversion. The
output value keeps stable until a new value receives.
The output value is zero after power up, cold start or
warm start of the 23AA20.
Basic subrack only:
If the RTU560 is reset (by CMU reset button or on
command from CS) the 23AA20 board set the output
value negativ. This state is given until the reset button
is released or the CMU software enables the peripheral bus again. A positive output value of e.g. +10 mA
becomes -10 mA.
The last output value keeps set if the ST-LED is ON after normal operation.

Live zero / unipolar output


Defined by the output type parameter of the setpoint
message (SPM) or general output message (GOM).

Doc.No.: 1KGT 150 434 V000 1

The EAP calculates the output value to the live zero


definition:
V 0000 (0 %)

= 4 mA

V 2000 (100 %) = 20 mA
The ouptut channel becomes a live zero channel after
it is parameterized by the CMU. Until that time the output has the default of  20 mA.

Power supply requirements


The 23AA20 board consumes up to 650 mA on
+5 V DC (Vcc) of the subrack power supply 23NG24.
Regard total load in the subrack.
23NG24 supplies max. 5000 mA on 5 V DC.

Settings
The jumper settings for channel 1 or channel 2 are described in table 1 or table 2.

Signalling
The board monitors and checks its functionality as
well as the dialog via the peripheral bus. Detected errors are indicated and/or transmitted by the board:
V by the red LED ST on the front plate
V by diagnostic messages
The ST LED indicates board errors or peripheral
bus errors.
The ST-LED indicates:
V board runs initialization procedure
V board is doing a cold- or warm start
V board has detected a memory error (RAM or
EPROM)
V micro controller faulty
V no dialog via the peripheral bus for at least 2
minutes. The board is not polled by the PBP of
CMU..

ABB Utilities GmbH


Connections and Settings 23AA20

RTU560

ST
opto-

Micro
controller

output
memory

opto-

EPROM

output

age

current range

converter

channel 1

+ 15 V DC
0 V DC
- - 15 V DC

+/U
adjustment

volt- -

output

age

current range

0V

DC / DC
converter

b32

channel 1

ref.

Vcc

z32

adjustment

coupler

DC / DC

0V

+/U

IO11 +
IO10 -

volt-

ref.

output
memory

EAP

Vcc

coupler

RAM

IO21+
z30

IO20 -

b30

channel 2

+ 15 V DC
0 V DC
- - 15 V DC

channel 2

Fig. 1: Logic block diagram

Doc.No.: 1KGT 150 434 V000 1

ABB Utilities GmbH


Connections and Settings 23AA20

RTU560
Channel 1 jumper configuration
Jumper

2.5 mA

5 mA

10 mA

Channel 2 jumper configuration


20 mA

Jumper

X50 X51
X52
X53
X54
X55
X10

2.5 mA

5 mA

10 mA

20 mA

X60 X61
1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

3 2 1

3 2 1

3 2 1

1 2 3

1 2 3

X62 X63

3
2
1

3
2
1

3
2
1

3
2
1

X64 X65

3
2
1

3
2
1

3
2
1

3
2
1

1 2 3

3 2 1

3 2 1

X11

Table 1: channel 1 jumpers

3 2 1

3 2 1

3 2 1

Table 2: channel 2 jumpers

red

321
321

X11
X10

X64 X65
3
2
1

DC / DC DC / DC
converter converter

X62 X63
X60

X50

X51
R 50

123

X52
X53

123

3
2
1

R 60

X61
X54
X55

Fig. 2: Board layout with setting positions

Doc.No.: 1KGT 150 434 V000 1

ABB Utilities GmbH


Connections and Settings 23AA20

23TP21
R0031

R0011

10

10

11

11

12

12

13

13

14

14

15

15

16

16

17

19

18

17

19

18

23ET23
Sub-connector
z32
b32

RTU560
Signal identification
Meaning

Identification
IO11 +

Output channel 1 +

IO10 -

Output channel 1 -

IO21 +

Output channel 2 +

IO20 -

Output channel 2 -

ReRe
mark

d32
z30
b30
d30
z28
b28
d28
z26
b26
d26
z24
b24
d24
z22
A (Faston

6,3)

b22
d22

The pin configuration of 23ET23 subrack corresponds to the direct pin configuration of the board connector

Subrack terminal connection: 23AA20

TP21

ET23

Placement of signal terminal connectors on subracks

Doc.No.: 1KGT 150 434 V000 1

ABB Utilities GmbH


Connections and Settings 23AA20

RTU560
23AA20

23TP21
R 0031
1

D / A output
channel 1

Signalidentific.

Process

IO11 +
IO11 -

Unit 1

2
3
IO21 +
4

D / A output
channel 2

IO20 -

Unit 2

5
6
7
8
9
10
11
12
13
14
15
16
17
b22
d22

18
19

*
*

* Pin assignment 23TP21


Board

23TP21
R0031

23TP21
R0011

17

19

b22

18

17

d22

19

18

Connection diagram 23TP21 subrack

Doc.No.: 1KGT 150 434 V000 1

ABB Utilities GmbH


Connections and Settings 23AA20

RTU560

Doc.No.: 1KGT 150 434 V000 1

ABB Utilities GmbH


Connections and Settings 23AA20

RTU560

ABB Utilities GmbH


68309
Mannheim (Germany)
Telephone +49 (0) 621 381-7592
Telefax
+49 (0) 621 381-7622

Doc.No.: 1KGT 150 434 V000 1

03/2001

Subject to alteration

Вам также может понравиться