ZN551 Control Module

Technical Instructions

What is the ZN551 control module? ........................................................................... 2


Module driver and control program ................................................................ 2
Specifications ............................................................................................... 2
Inputs ........................................................................................................... 3
Room sensors................................................................................................ 3
Digital outputs............................................................................................... 3
Analog outputs.............................................................................................. 3
To mount the ZN551.................................................................................................. 4
Wiring for power ........................................................................................................ 4
To wire for power............................................................................................ 4
To address the ZN551................................................................................................ 5
Wiring for communications ........................................................................................ 5
Wiring specifications ..................................................................................... 5
To wire the ZN551 for communications .......................................................... 5
Wiring inputs and outputs .......................................................................................... 6
Wiring specifications ..................................................................................... 6
To wire inputs and outputs ............................................................................. 7
Downloading memory ................................................................................................ 9
To download memory in WebCTRL .................................................................. 9
To assign inputs or outputs to points........................................................................... 9
Input values.................................................................................................10
Output values ..............................................................................................10
Resolution values ........................................................................................11
Offset/Polarity values..................................................................................11
Using flow sensors................................................................................................... 12
To connect the duct tubes to the flow sensors ...............................................12
To wire the flow sensor to the control module................................................12
To set up the Airflow Control microblock .......................................................12
To set up the module driver ...................................................................................... 13
Driver ..........................................................................................................13
Device.........................................................................................................14
Notification Class #1 ...................................................................................14
Common Alarms..........................................................................................15
Custom Translation Tables...........................................................................15
To communicate through the local access port .......................................................... 16
To set up a Local Access connection in WebCTRL ..........................................16
Troubleshooting ...................................................................................................... 16
Formatting the control module .....................................................................17
LED's..........................................................................................................17
Manufacture date........................................................................................18
Compliance ............................................................................................................ 18

Automated Logic Corporation 1150 Roberts Blvd. Kennesaw, GA 30144 770/429-3000 Fax 770/429-3001
www.automatedlogic.com 2005 Automated Logic Corporation. All rights reserved throughout the world. Automated
Logic Corporation, the Automated Logic logo, WebCTRL, EIKON, BACview, SuperVision, and InterOp are registered
trademarks, and Alert is a trademark of Automated Logic Corporation. BACnet is a registered trademark of ASHRAE.
All other brand and product names are trademarked by their respective companies.

What is the ZN551 control module?


The ZN551 control module is used for zone control.

Module driver and


control program

Module driver

DRV_ZN

Maximum number of control


programs

Maximum number of
BACnet objects*

200

* Depends on available memory

Specifications

Power

24 Vac 10%, 5060 Hz, 15 VA


26 Vdc (25 V min, 30 V max)

CMnet port

For communication with the control module network using


ARC156 or MS/TP (9600 bps76.8 kbps)

Rnet port

For RS room sensors. The Rnet port supports up to four


RS sensors and one RS Pro or RS Plus sensor for
averaging or high/low select control.
NOTE The ZN551 does not support BACview.

LStat port

For LogiStat and LogiStat Plus room sensors. The LogiStat


port uses two universal inputs.
NOTE The ZN551 does not support the LogiStat Pro. Use
an RS Pro on the Rnet port instead.

Local access port

For system start-up and troubleshooting

Inputs

5 inputs configurable for thermistor or dry contact. Inputs


1 and 2 are also configurable for 05 Vdc. Inputs 4 and 5
are used when a LogiStat sensor is connected, but are
available if an RS room sensor is connected.

Input resolution

10 bit A/D

Digital outputs

5 digital outputs, relay contacts rated at 1 A max. @ 24


Vac/Vdc. Configured normally open.

Analog output

1 analog output, 010 Vdc (5 mA max)

Output resolution

8 bit D/A

Memory

512 kB non-volatile battery-backed RAM, 1 MB Flash


memory, 16-bit memory bus

Battery

10-year Lithium CR2032 battery provides a minimum of


10,000 hours of data retention during power outages

Protection

Incoming power and network connections are protected


by non-replaceable internal solid-state polyswitches that
reset themselves when the condition that causes a fault
returns to normal. The power, network, analog inputs,
analog outputs, and relay output connections are also
protected against voltage transient and surge events.

ZN551 Control Module Rev. 3/17/2005

2005 Automated Logic Corporation

Inputs

Status indicators

LED's indicate status of communications, running, errors,


power, and digital outputs

Environmental operating
range

0 to 130F (-17.8 to 54.4C), 1090% relative humidity,


non-condensing

Physical

Rugged GE C2950 Cycoloy plastic

Overall dimensions

Width:
Height:

Mounting dimensions

5 9/16" (14.1 cm) between mounting slot centerlines

Weight

0.6 lbs (0.27 kg)

BACnet support

Conforms to the Advanced Application Controller (B-AAC)


Standard Device Profile as defined in ANSI/ASHRAE
Standard 135-2004 (BACnet) Annex L

Listed by

UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart BClass A, CE EN50082-1997

5 1/16 in. (12.9 cm)


5 11/16 in. (14.4 cm)

The ZN551 has 5 inputs that accept the following signal types:
These
inputs...

Support this
signal type...

All

Thermistor

Precon type 2 (10 kOhm at 77F). Input voltages will be


from 0.33 Vdc to 2.52 Vdc for thermistors.

All

Dry contact

A 3.3 Vdc wetting voltage detects contact position,


resulting in a 0.3 mA maximum sense current when the
contacts are closed.

IN-1, IN-2

05 Vdc

The output impedance of a 05 Vdc source must not


exceed 100 Ohms. The input impedance of the ZN551
is approximately 30 kOhm.

IN-4, IN-5

LogiStat

IN-4See Thermistor.

Description

IN-5Setpoint adjust. Input voltages should be from


1.43.4 Vdc.

NOTE A LogiStat sensor connected to the ZN551 uses IN-4 and IN-5. An RS
room sensor connected to the Rnet port does not use these inputs.

Room sensors

You can wire an RS Standard, RS Plus or RS Pro to the ZN551's Rnet port.
Or you can wire a LogiStat or LogiStat Plus to the ZN551's LStat port. See the
RS Room Sensors Technical Instructions (http://info.automatedlogic.com) or
the LogiStat Sensors Technical Instructions (http://info.automatedlogic.com).
NOTE The ZN551 does not support the LogiStat Pro.

Digital outputs

The ZN551 has 5 digital outputs. You can connect each output to a
maximum of 24 Vac/Vdc. Each output is a dry contact rated at 1 A, 24 V
maximum and is normally open.

Analog outputs

The ZN551 has 1 analog output that supports voltage devices from 0-10 Vdc.
The controlled device must have a minimum of 2000 Ohms resistance

ZN551 Control Module Rev. 3/17/2005

2005 Automated Logic Corporation

measured from its input to ground and must share the same ground as the
control module.

To mount the ZN551


Screw the ZN551 into an enclosed panel using the mounting slots provided
on the cover plate. Leave about 2 in. (5 cm) on each side of the control
module for wiring.
Mounting slot

Mounting slot

Wiring for power


CAUTIONS

The ZN551 is a Class 2 device (less than 30 Vac, 100 VA). Take
appropriate isolation measures when mounting it in a control panel
where non-Class 2 devices (120 Vac or greater) are present.

Do not power pilot relays from the same transformer that powers the
ZN551.

NOTE You can power several control modules from the same transformer if
you maintain the same polarity.

To wire for power

Remove power from the 24 Vac transformer.

Pull the screw terminal connector from the control module's power
terminals labeled Gnd and 24 Vac.

Connect the transformer wires to the screw terminal connector.

Apply power to the transformer.

Measure the voltage at the ZN551s power input terminals to verify that
the voltage is within the operating range of 21.626.4 Vac.

Insert the screw terminal connector into the ZN551's power terminals.

Verify that the Power LED is on and the Run LED is blinking.

ZN551 Control Module Rev. 3/17/2005

2005 Automated Logic Corporation

To address the ZN551


You can address the ZN551 before or after you wire the control module for
power.
1

If the ZN551 has been wired for power, pull the screw terminal connector
from the control module's power terminals labeled Gnd and 24 Vac. The
control module reads the address each time you apply power to it.

Using the rotary switches, set the control module's address to match the
Address in the control module's Device Properties dialog box in
SiteBuilder. Set the Tens (10's) switch to the tens digit of the address,
and set the Ones (1's) switch to the ones digit.
EXAMPLE If the control modules address is 35, point the arrow on the
Tens (10's) switch to 3 and the arrow on the Ones (1's) switch to 5.

10's

1's

Wiring for communications


The ZN551 communicates using BACnet on the following types of network
segments:

ARC156 communicating at 156 kbps

MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps

NOTE ARC156 is a unique implementation of the industry standard


ARCNET. For a summary of differences between ARCNET and ARC156, see
the ARC156 Wiring Technical Instructions (http://info.automatedlogic.com).

Wiring specifications

For...

Use...

Maximum Length

ARC156

22 AWG, low-capacitance, twisted,


stranded, shielded copper wire*

2000 feet (610 meters)

MS/TP

A dedicated 22 AWG to 18 AWG


twisted pair wire (EIA-485)

3000 feet (914.4 meters) for 9600


bps, 19.2 kbps, or 38.4 kbps
2000 feet (610 meters) for 76.8 kbps

* See the ARC156 Wiring Technical Instructions (http://info.automatedlogic.com).

To wire the ZN551 for


communications

Pull the screw terminal connector from the control module's power
terminals labeled Gnd and 24 Vac.

Check the communications wiring for shorts and grounds.

Connect the communications wiring to the control modules screw


terminals labeled Net +, Net -, and Shield.
NOTE Use the same polarity throughout the network segment.

ZN551 Control Module Rev. 3/17/2005

2005 Automated Logic Corporation

Set the communication type and baud rate.

For...

Set Communications
Selection jumper to...

ARC156

ARC156

N/A. Baud rate will be 156 kbps


regardless of the DIP switch settings.

MS/TP

MSTP

The appropriate baud rate. See the MSTP


Baud diagram on the control module.

Set DIP switches 1 and 2 to...

NOTE Use the same baud rate for all control modules on the network
segment.
5

Insert the power screw terminal connector into the ZN551's power
terminals.

Verify communication with the network by viewing a module status


report in WebCTRL.

Wiring inputs and outputs


Wire the ZN551's inputs and outputs as follows.

Wiring specifications

Input wiring
Input

Maximum length

Minimum gauge

Shielding

05 Vdc

1000 feet
(305 meters)

26 AWG

Shielded

Thermistor
Dry contact

1000 feet
(305 meters)

22 AWG

Shielded

RS room sensors

500 feet
(152 meters)

22 AWG,
4 conductor1

Shielded or
unshielded

LogiStat

100 feet
(30 meters)

22 AWG2

Unshielded

1
2

See the RS Room Sensors Technical Instructions (http://info.automatedlogic.com).


See the LogiStat Sensors Technical Instructions (http://info.automatedlogic.com).

Output wiring
To size output wiring, consider the following:

Total loop distance from the power supply to the control module, and
then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires,
this is twice the cable length.

Acceptable voltage drop in the wire from the control module to the
controlled device

Resistance (Ohms) of the chosen wire gauge

Maximum current (Amps) the controlled device requires to operate

ZN551 Control Module Rev. 3/17/2005

2005 Automated Logic Corporation

To wire inputs and


outputs

Verify that the ZN551's power and communications connections work


properly.

Pull the screw terminal connector from the control module's power
terminals labeled Gnd and 24 Vac.

Connect the input wiring to the screw terminals on the ZN551.


NOTE Connect the shield wire to the GND terminal with the ground
wire.

Any input
thermistor

Gnd
Any input

Relay,
dry contact

Gnd

+V
DC
power
supply

+V
Out
Gnd

Gnd

Gnd
4

0-5Vdc

To wire a room sensor to the ZN551, wire the ZN551's terminals to the
room sensor's terminals.

For an RS room sensor, wire each terminal on the ZN551's Rnet port
to the terminal of the same name on the RS room sensor.
NOTE If wiring an RS room sensor with shielded wire, connect the
shield wire to the GND terminal with the ground wire.

For a LogiStat room sensor, use the following table.


Wire this terminal
on the LStat port...

To this terminal on
the LogiStat sensor

Gnd
IN-4
IN-5
LED

Gnd
Temp
SW
LS5v

Set the appropriate jumpers on the ZN551.


To use...

For...

IN-1 or IN-2

Thermistor
Dry contact
05 Vdc

Set jumpers IN-1 or IN-2 to the type of signal the


input will receive.

IN-4 or IN-5

Thermistor
Dry contact

Verify the LStat/IN-4 jumper is on.

IN-4 and IN-5

LogiStat

1. Remove the jumper from LStat/IN-4.


2. Set the LStat/Rnet jumper to LStat.

Rnet Port

RS sensor

Set the LStat/Rnet jumper to Rnet.

ZN551 Control Module Rev. 3/17/2005

2005 Automated Logic Corporation

LStat
Rnet
LStat
IN-4

IN-1
IN-2

Thermistor/dry contact
0-5Vdc
Thermistor/dry contact
0-5Vdc

Connect the digital output wiring to the screw terminals on the ZN551
and to the controlled device.

Any DO

Motor

Any DO

Bus 24 Vac or
24 Vdc
7

Connect the analog output wiring to the screw terminals on the ZN551
and to the controlled device.

Gnd
Any AO +

Gnd
Any AO +

Motor 0-10 V

Valve 0-10 V

NOTE Current from the analog outputs can drive a 20 mA device. To use
an analog output for this purpose, you may need to add a 1/2 watt
resistor in series with the device to achieve the required total resistance
of 500 Ohms. For example, to drive a device that has 100 Ohms of
resistance, wire a 400 Ohm resistor in series with the 20 mA device to
achieve 500 Ohms resistance.
8

Insert the power screw terminal connector into the ZN551's power
terminals.

ZN551 Control Module Rev. 3/17/2005

2005 Automated Logic Corporation

Downloading memory
Download memory to a control module to do either of the following:

Send control programs, the module driver, editable properties, and


schedules to a control module for the first time. The first download takes
longer than subsequent downloads.

Send changes such as a change to a control program, an upgrade to the


module driver, or a change to the control module's address.

The ZN551 can store one DRV_ZN module driver and one control program.
CAUTIONS

The control module automatically halts before and restarts after a


memory download, causing the shutdown and restart of any equipment
controlled by the module.

Downloading memory overwrites all control programs in the control


module causing it to lose stored data.

You download memory from WebCTRL. If your network is complete, you can
download from any network browser. If not complete, connect a laptop with a
local copy of the system database to the ZN551's local access port. See steps
13 of To communicate through the local access port (page 16).

To download memory
in WebCTRL

On WebCTRL's CFG tree, click Download.

Select the Memory checkbox.


NOTE A memory download includes a Parameters and Schedules
download.

On the Network tree on the right, select the control module you want to
download to.

Click Add to add the control module to the Download Items list.

Click Download Selected Items.

If the download fails, the control module appears in the Failures box. Since
this indicates a system problem, do not clear the failure. Locate and resolve
the problem, then retry the download. To retry, select the control module in
the Failures box, then repeat steps 4 and 5 above.

To assign inputs or outputs to points


To use an input or output, you must assign it to its corresponding point in
the control program.
1

In WebCTRL's GEO tree, select the equipment controlled by the ZN551.

From the menu

ZN551 Control Module Rev. 3/17/2005

, select Point Checkout.

2005 Automated Logic Corporation

In the Num field for each point, type the number of the control module's
corresponding input or output. For example, if you use DO1 on the
ZN551 for the point Fan S/S, type 1 in the Num field for Fan S/S.
NOTE Exp (expander number) is 0 for the ZN551.

Enter the appropriate values for each input and output in the remaining
columns. See Input values, Output values, Resolution values and
Offset/Polarity values below.
NOTE You can also enter these values in EIKON for WebCTRL.

Input values

If you have not performed the initial memory download to the ZN551, you
must download now so you can verify inputs and outputs.

To verify each input's operation, force each sensor to a known value, then
compare it to the Value shown on the control program's Point Checkout
tool in WebCTRL.

To verify each output's operation, lock each output to a known condition


on the control program's Point Checkout tool in WebCTRL, then verify
that the equipment operates correctly.

Input

I/O Type

Sensor/Actuator Type

Min/Max

05 Vdc

05 Volt

Linear Full Range

Engineering values
associated with 0 Vdc (Min)
and 5 Vdc (Max)1

Thermistor

Thermistor

Select your Thermistor


type or set up and select
a Non-Linear, Custom
Table2

N/A

Analog (BAI)

Digital (Binary) (BBI)


Dry Contact

Output values

Dry Contact

N/A

N/A

The sensor reads a value and sends a corresponding signal (Volt, mA, or psi) to the
ZN551's physical input. The Analog Input microblock uses the Min and Max values to
linearly translate the signal into the engineering value used in subsequent control logic.
For example, set Min to 0 and Max to 10 for a 420 mA sensor that measures velocity
from 0.0 to 10.0 inches/second so that when the input reads 4 mA, the microblock
outputs a value of 0. Similarly, when the input reads 8 mA, the microblock outputs a
value of 2.5.

To set up a custom translation table, see the module driver's Custom Translation Tables
properties page in WebCTRL.

Output

I/O Type

Sensor/Actuator Type

Min/Max

010 Vdc

Electrical
010 Volt

Linear Full Range

Engineering values
associated with 0 Vdc (Min)
and 10 Vdc (Max)1

210 Vdc

Electrical
010 Volt

Linear w/Offset,
210 Volts

Engineering values
associated with 2 Vdc (Min)
and 10 Vdc (Max)1

Analog (BAO)

ZN551 Control Module Rev. 3/17/2005

10

2005 Automated Logic Corporation

Output

I/O Type

Sensor/Actuator Type

Min/Max

N/A

N/A

Digital (Binary) (BBO)


Relay
1

Resolution values

Relay/Triac
Output

The Analog Output microblock uses the Min and Max values to linearly translate its
EIKON for WebCTRL wire value into a physical output signal (Volt, mA, or psi) sent from
the ZN551 to an actuator. For example, set Min to 0 and Max to 100 for an Analog
Output microblock that receives a 0 to 100% open signal from a PID microblock and
that controls a 010 Vdc actuator so that when the PID signal is 100%, the ZN551
output is 10 Vdc. Similarly, when the PID signal is 50%, the ZN551 output is 5 Vdc.

Resolution is not particular to a type of input or output, but the module


driver handles analog and digital (binary) inputs and outputs differently. To
set these values appropriately, you should understand how the module driver
uses them.
Resolution

Notes

Analog Input (BAI)

The driver truncates the microblock's present value according


to the resolution.
EXAMPLE If the calculated present value is 13.789 and you
set the Resolution to 0.1, the control program uses 13.7 for
any calculations downstream from the microblock.

Analog Output (BAO)

The driver truncates the wire input value to the microblock


before performing any scaling calculations.
EXAMPLE If the wire input value is 13.789 and you set the
Resolution to 0.1, the microblock uses 13.7 for any scaling
calculations.

Digital Inputs and


Outputs

Offset/Polarity values

N/A

Offset/Polarity is not particular to a type of input or output, but the module


driver handles analog and digital (binary) inputs and outputs differently. To
set these values appropriately, you should understand how the module driver
uses them.
Offset/Polarity

Notes

Analog Input (BAI)

Offset value (positive or negative) adds a fine adjustment to a


sensor reading after all scaling for calibration.
EXAMPLE If a sensor reads 74.9F when the actual
measured value is 73.6F, enter an Offset of 1.3 to
calibrate the sensor to the measured value.

Analog Output (BAO)

ZN551 Control Module Rev. 3/17/2005

You can use the Offset value (positive or negative) to


calibrate an output, but you generally do not need to. If used,
the driver adds the offset value to the wire input value before
performing any scaling calculations to determine the ZN551's
output.

11

2005 Automated Logic Corporation

Offset/Polarity

Notes

Digital (Binary) Input


(BBI)

Polarity determines the microblock's present value when no


signal is received from the equipment.
When no signal is received from the equipment, if Polarity is
set to:
normalpresent value is off
reversedpresent value is on

Digital (Binary) Output


(BBO)

Polarity determines the ZN551's output based on the control


program's signal to the microblock.
When the control program's signal to the microblock is on, if
Polarity is set to:
normaloutput is on
reversedoutput is off
NOTE Regardless of Polarity, the output will be off if the
ZN551 loses power.

Using flow sensors


In a single duct system, the ZN551 controls airflow in the zone using a USF
flow sensor and an actuator connected to two digital outputs.
In a dual duct system, the ZN551 controls airflow in the zone using a UDF
flow sensor and two actuators, with each actuator connected to two digital
outputs.

To connect the duct


tubes to the flow sensors

USF
1

Connect the ducts total pressure tube to the USF's High connector.

Connect the ducts static pressure tube to the USF's Low connector.

UDF
Follow the procedure for a USF, but connect one duct's tubes to the UDF's
Flow #1 connectors and the other duct's tubes to the UDF's Flow #2
connectors.

To wire the flow sensor


to the control module

To set up the Airflow


Control microblock

Use the cable included with the flow sensor (ALC part #235012) or a 20 AWG,
4-conductor cable, maximum length 4 feet (1.22 meters).
1

Turn off the control module's power.

Connect the ends of the cable to the 4-pin connector on the flow sensor
and to the 4-pin connector on the control module.

The ZN551's control program must include one Airflow Control microblock
for a single duct system or two of the microblocks for a dual duct system.
You must set up the Airflow Control microblock for each flow sensor.

ZN551 Control Module Rev. 3/17/2005

12

2005 Automated Logic Corporation

For a single duct system


1

In WebCTRL, on the control program's Logic page, select the U-Line


Airflow Control microblock.

On the Details tab in the Flow Sensor field under Hardware


Configuration, select External flow sensor.

In the Input Number field, type 1.

In the I/O Type field, select Flow Input.

At the bottom of the Details tab, click the plus sign (+) to the left of Flow
Input (AI) Configuration.

In the Sensor Type field under Calibration, select No Translation.

For a dual duct system


1

In WebCTRL, on the control program's Logic page, select the Airflow


Control microblock for Flow #1.

On the Details tab in the Flow Sensor field under Hardware


Configuration, select External flow sensor.

In the Input Number field, type 1.

In the I/O Type field, select Flow Input.

At the bottom of the Details tab, click the plus sign (+) to the left of Flow
Input (AI) Configuration.

In the Sensor Type field under Calibration, select No Translation.

On the Logic page, select the airflow control microblock for Flow #2.

Repeat steps 2 through 6 for Flow #2, typing 2 in step 3.

NOTE When performing test and balance, follow the steps under Test and
Balance on the Airflow Control microblock's Properties page Details tab in
WebCTRL.

To set up the module driver


After you download the module driver and control program to the ZN551, you
may want to change the module driver's properties to suit your application.
1

On WebCTRL's NET tree, click the plus sign (+) to the left of your ZN551.
NOTE Driver properties are on the Driver Properties page and on its
children in the tree.

Driver

Click the page you want to view, then change properties as needed.

On this page, you can change the following properties:

Module clock synchronization and failure. See table below.


Network Input microblock communication properties.

ZN551 Control Module Rev. 3/17/2005

13

2005 Automated Logic Corporation

Module Clock
Date and time control program uses when module's realtime clock is invalid.

Clock Fail Date and Time

TIP Use an occupied date and time (such as a Tuesday


at 10 a.m.) so the equipment does not operate in
unoccupied mode if the module loses power during
occupancy.
Time Synch Sensitivity
(seconds)

Device

On this page, you can change the following properties:

Notification Class #1

On a Time Synch signal, update the module clock only if


the module time differs from the signal time by more
than this value.

BACnet device object properties for the ZN551


ZN551 network communication

Configuration

NOTE The three APDU fields refer to all networks over


which the ZN551 communicates.

Max Masters and Max Info


Frames

Apply only if the ZN551's parent network is an MS/TP


network.

WebCTRL alarms use Notification Class #1. A BACnet alarm's Notification


Class defines:

Alarm priority for Alarm, Fault, and Return to Normal states


Options for BACnet alarm acknowledgement
Where alarms should be sent (recipients)

NOTE You may need to set up additional Notification Classes if your system
will handle Life Safety alarms or if you need to send certain types of alarms
only to an alarm manager other than WebCTRL.

NOTE BACnet defines the following Network message


priorities for Alarms and Events.

Priorities

Priority range

Network message priority

0063

Life Safety

64127

Critical Equipment

128191

Urgent

192255

Normal

Priority of Off-Normal

BACnet priority for Alarms.

Priority of Fault

BACnet priority for Fault messages.

Priority of Normal

BACnet priority for Return-to-normal messages.

ZN551 Control Module Rev. 3/17/2005

14

2005 Automated Logic Corporation

Ack Required for Off-Normal,


Fault, and Normal

Requires a control module acknowledgement for each


message type. Normally not required.
TIP To require operator acknowledgement for an Alarm
or Return-to-normal message (stored in the WebCTRL
database) change the acknowledgement settings on
WebCTRL's Alarm > Enable/Disable tab for an alarm
source or an alarm category.

Recipient List

Common Alarms

Recipients

The first row in this list is the WebCTRL Server. Do not


delete this row. Click Add if you want other BACnet
devices to receive alarms.

Recipient Description

Name that appears in the Recipients table.

Recipient Type

Use Address (static binding) only for third-party BACnet


device recipients that do not support dynamic binding.

Recipient Device Object


Identifier

Type the Device Instance from SiteBuilder (or from the


network administrator for third-party devices) in the #
field.

Process Identifier

Change for third-party devices that use a BACnet Process


Identifier other than 1. WebCTRL processes alarms for
any 32-bit Process Identifier.

Issue Confirmed
Notifications

Select to have a device continue sending an alarm


message until it receives delivery confirmation from the
recipient.

On these pages, you can change the following control module alarm
properties:

BACnet alarm object properties


Enable/disable
Delays

NOTE To set up alarm actions for control module generated alarms, see
Setting up alarm actions in WebCTRL Help.
Module Generated Alarm
Short message shown on WebCTRL's Alarm page or in an
alarm action when this type of alarm is generated.

Description
Events

Custom Translation
Tables

Alarm Category and Alarm


Template

See Customizing alarms in WebCTRL Help.

Enable

Clear these checkboxes to disable Alarm or Return to


normal messages of this type from this control module.

Notification Class

Do not change this field.

On the Custom Translation Table pages, you can edit the tables used to
translate raw sensor data to engineering units for inputs associated with
Non-Linear, Custom Table sensor/actuator types.

ZN551 Control Module Rev. 3/17/2005

15

2005 Automated Logic Corporation

To communicate through the local access port


Using a computer and an APT, you can communicate locally with the ZN551
to download memory or to troubleshoot.
PREREQUISITES

A computer with an RS232 port

An APT with cables. See the APT Technical Instructions


(http://info.automatedlogic.com).

Connect the computer to the APT, and then the APT to the control
module.

Connect to the
control modules
Local Access port
Rnet
adapter
cable

9-pin
APT cable
8-pin
APT cable

To set up a Local
Access connection in
WebCTRL

Set the APT's Mode Select switch to 485.

Set the APT's Exec. 4 Relay switch to Network.

On the CFG tree, select Connections.

On the Configure tab, click Add.

From the Type drop-down list, select BACnet Local Access.

Optional: Edit the Description.

Type the computer's Port number where your APT is connected.

Set the Baud rate to 115200.

Click Accept.

On the View tab, click the drop-down arrow next to your device's
network Connection, then select BACnet Local Access.

Click Accept.

10 On the Configure tab, select BACnet Local Access, then click Start.

Troubleshooting
If you have problems mounting, wiring, or addressing the ZN551, contact
ALC Technical Support.

ZN551 Control Module Rev. 3/17/2005

16

2005 Automated Logic Corporation

Formatting the control


module

LED's

If you cannot communicate with a control module after downloading memory


to it, as a last resort, you can manually format the control module to erase its
memory.
1

Pull the screw terminal connector from the control module's power
terminals labeled Gnd and 24 Vac. Make sure the address switches are
not set to 0, 0.

Short the Format jumpers pins.

Insert the power screw terminal connector into the ZN551's power
terminals.

Continue to short the jumper until the Error LED flashes three times in
sync with the Run LED.

Remove the short.

Download memory to the ZN551.

The LED's on the ZN551 show the status of certain functions.


If this LED is on...

Status is...

Power

The ZN551 has power

Rx

The ZN551 is receiving data from the network segment

Tx

The ZN551 is transmitting data over the network segment

DO#

The digital output is active

The Run and Error LED's indicate control module and network status.
If Run LED shows...

And Error LED shows...

Status is..

2 flashes per second

Off

Normal

2 flashes per second

2 flashes,
alternating with Run LED

Five minute auto-restart delay


after system error

2 flashes per second

3 flashes,
then off

Control module has just been


formatted

2 flashes per second

4 flashes,
then pause

Two or more devices on this


network have the same
ARC156 network address

2 flashes per second

On

Exec halted after frequent


system errors or control
programs halted

5 flashes per second

On

Exec start-up aborted, Boot is


running

5 flashes per second

Off

Firmware transfer in
progress, Boot is running

7 flashes per second

7 flashes per second,


alternating with Run LED

Ten second recovery period


after brownout

ZN551 Control Module Rev. 3/17/2005

17

2005 Automated Logic Corporation

Manufacture date

If Run LED shows...

And Error LED shows...

Status is..

14 flashes per second

14 flashes per second,


alternating with Run LED

Brownout

When troubleshooting, you may need to know a control module's


manufacture date.
Obtain the manufacture
date from a...

Notes

Module status report (modstat)

To obtain a modstat in WebCTRL:


1. Select the control module in the NET tree.
2. Press Ctrl+M.
3. Type modstat.
4. Click OK.
The report shows the date under Main board
hardware.

Sticker on the back of the


main control module board

The first three characters on the sticker show the


control module type. The next three characters
show the year, month, and day of manufacture.
(The month digit is in hexadecimal format.)

Compliance
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense.
CAUTION Changes or modifications not expressly approved by the
responsible party for compliance could void the users authority to operate
the equipment.

ZN551 Control Module Rev. 3/17/2005

18

2005 Automated Logic Corporation