38AKS028-044
38AH024-034
With 40RM016-034
Commercial Air-Cooled
Split Systems
50 Hz
63 to 127 kW (18 to 35.8 Nominal Tons)

These dependable split systems


match Carriers indoor-air handlers
with outdoor condensing units for a
wide selection of commercial cooling
solutions.

Features/Benefits

38AKS,38AH

Building owners will appreciate the


high unit EERs (Energy Efficiency
Ratios) offered by the 38AKS and
38AH units. These units provide
greater efficiency than similar units in
the marketplace, which translates into
year-round operating savings. Latest
safety standards for 38AKS and 38AH
units are assured through UL and UL,
Canada approvals.

Constructed for long life


The 38AKS and 38AH units are
designed and built to last. Cabinets are
constructed of pre-painted galvanized
steel, delivering unparalleled protection
against the environment. Inside and
outside surfaces are protected to
ensure long life, good looks and reliable performance. The copper tubealuminum fin outdoor coil construction provides long term reliability and
improved heat transfer. Where conditions require them, copper fin coils are
available. For corrosive or coastal
environments an epoxy barrier is available to provide superior coil durability.

Reliability

40RM016-034

Copyright 2004 Carrier Corporation

The 38AKS and 38AH condensing


units offer the building owner components and operating controls designed
for performance dependability. These
condensing units feature the time
proven highly reliable 06D and 06E
compressors. Unloading capability for

Form 38A-C11PD

superior part load performance is a


standard feature of these compressors.
The compressor mounting system
has vibration isolation to provide quiet
operation and reduce component
stress.
Each compressor is equipped with a
crankcase heater to eliminate the occurrence of liquid slugging at start-up.
The compressors also include an oil
level sight glass for maintenance ease.
The following safety features are
included in each unit:
Anti short cycling control
Low oil pressure safety
Low refrigerant pressure safety
High refrigerant pressure safety
Calibrated circuit breakers

38AH series
38AH condensing units feature 2 compressors and 2 refrigeration circuits.
These units can be matched with a
single air handler or two separate air
handlers.
Standard units are designed for
constant volume control. A variable air
volume (VAV) control is available as a
factory-installed option. The VAV units
feature electrically controlled compressor unloading to precisely match unit
capacity to building loads. The VAV
equipped unit has a simple control
interface for connection to a VAV
discharge air control system.

Ease of installation and service


These units are equipped with hinged
control box access panels, control
interface terminal boards, liquid line
shut off valves and compressor service
valves.

Innovative Carrier 40RM


air-handling units ideal
matches for 38AKS and
38AH condensing units
The 40RM Series has excellent fan
performance, efficient directexpansion (DX) coils, a unique
combination of indoor air quality

features, and easy installation. Its versatility and state-of-the-art features


help to ensure that your split system
provides economical performance
now and in the future.

Indoor-air quality (IAQ)


features
The unique combination of IAQ features in the 40RM Series air handlers
helps to make sure that only clean,
fresh, conditioned air is delivered to
the occupied space.
Direct-expansion (DX) cooling coils
prevent the build-up of humidity in the
room, even during part-load conditions. The 40RM016-034 sizes feature
dual-circuit coils.
Standard 2-in. (50.3 mm) disposable
filters remove dust and airborne particles from the occupied space.
The pitched PVC drain pan can be
adjusted for a right-hand or left-hand
connection to provide positive
drainage and to prevent standing
condensate.
The 40RM accessory economizer
can provide ventilation air to improve
indoor-air quality. When used with
CO2 sensors, the economizer admits
fresh outdoor air to replace stale, recirculated indoor air.

Economy
The 40RM Series packaged air handlers have low initial costs, and they
continue to save money by providing
reduced installation expense and
energy-efficient performance.
Quick installation is ensured by the
multipoise design. Units can be installed in either the horizontal or
vertical configuration without modifications. All units have drain-pan connections on both sides, and pans can be
pitched for right-hand or left-hand
operation with a simple adjustment.
Fan motors and contactors are
prewired and thermostatic expansion
valves (TXVs) are factory-installed on
all 40RM models.

High efficiency, precision-balanced


fans minimize air turbulence, surging,
and unbalanced operation, cutting
operating expenses.
The economizer accessory precisely
controls the blend of outdoor air and
room air to achieve comfort levels.
When the outside air enthalpy is
suitable, outside air dampers can fully
open to provide free cooling.

Rugged dependability
40RM units are made to last. The
die-formed galvanized steel panels
ensure structural integrity under all
operating conditions. Galvanized steel
fan housings are securely mounted to
a die-formed galvanized steel deck.
Mechanically bonded coil fins provide
improved heat transfer. Rugged pillowblock bearings are securely fastened to
the solid steel fan shaft with split collets
and clamp locking devices.

Coil flexibility
Model 40RM direct-expansion coils
have galvanized steel casings; inlet and
outlet connections are on the same
end. The coils are designed for use
with Refrigerant 22 and have 3/8-in.
diameter copper tubes mechanically
bonded to aluminum sine-wave fins.
The coils include matched, factoryinstalled TXVs with matching distributor nozzles. Accessory hot water and
steam coils and electric heaters are
also available.

Easier installation and service


The multipoise design and component
layout help you to get the unit installed
and running quickly. The DX coils have
factory-installed TXVs with matching
distributor nozzles. Units can be converted from horizontal to vertical operation by simply repositioning the unit.
Drain pan connections are duplicated
on both sides of the unit. The filters,
motor drive, TXVs, and coil connections are all easily accessed by removing a single side panel.

Table of contents
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
Model Number Nomenclature 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . 4
Model Number Nomenclature 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . 5
Model Number Nomenclature 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . 6
Capacity Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Physical Data 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8,9
Physical Data 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10,11
Physical Data 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12,13
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-16
Dimensions 38AKS028, 034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Dimensions 38AKS044 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Dimensions 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensions 40RM016-024 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions 40RM028, 034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22,23
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24-50
38AKS Unit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24,25
38AKS/40RM Combination Ratings . . . . . . . . . . . . . . . . . . . . . . . . .26-31
38AH Unit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32-35
38AH/40RM Combination Ratings . . . . . . . . . . . . . . . . . . . . . . . . . .36-43
40RM Unit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44-50
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51-54
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55-58
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59-61
Typical Control Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . .62-65
Application Data 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66,67
Application Data 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68-70
Application Data 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71-73
Guide Specifications 38AKS Units. . . . . . . . . . . . . . . . . . . . . . . . . . .74-76
Guide Specifications 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . . . .77-79
Guide Specifications 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . .80-82

Model number nomenclature 38AKS units


38AKS
38AKS Commercial Air-Cooled
Condensing Units (Semi-Hermetic)

Nominal Capacity kW* (Tons)


028 82.8 (23.4)
034 94.5 (26.5)
044 127.0 (35.8)
Not Used

Condenser Coil Fin Material


Aluminum (Standard)
C Copper (Optional)
K Pre-Coated Aluminum (Optional)
E E-Coated Al Fin/Cu Tubes (Optional)
F E-Coated Cu Fin/Cu Tubes (Optional)

028

Not Used
Packaging
1 Std. Domestic Packaging
3 Export Packaging - Top
and Bottom Skid

Revision Number
0 Original

Voltage Designation
3 346-3-50
8 230-3-50
9 400-3-50

LEGEND
Al Aluminum
Cu Copper
*Gross capacity based on 36 C air temperature entering condenser and 8 C saturated suction temperature.
Gross capacity based on 95 F air temperature entering condenser and 45 F saturated suction temperature.

Quality Assurance
Certified to ISO 9001:2000

Model number nomenclature 38AH units


38AH
38AH Commercial Air-Cooled
Condensing Unit
Nominal Capacity kW (Tons)
024 63 (18)
028 73 (21)
034 87 (25)
Not Used
Condenser Coil Fin Material
Aluminum (Standard)
C Copper (Optional)
K Pre-Coated Aluminum (Optional)
E E-Coated Al Fin/Cu Tubes (Optional)
F E-Coated Cu Fin/Cu Tubes (Optional)
Voltage Designation
3 346-3-50
8 230-3-50
9 400-3-50

024

A
Compressors
A Standard Compressors One Suction
Pressure-Actuated Unloader on Lead
Compressor
C Variable Air Volume (VAV) Option
Includes 2 Electric Unloaders on Lead
Compressor and Control Box
Modifications
Fan Motors and Labels
A Standard Condenser Fan Motors
and Labels
Packaging
1 Standard Domestic Packaging
Bottom Skid
3 Export Packaging Top and Bottom
Skid
Revision Number
1 Current Revision

LEGEND
Al Aluminum
Cu Copper

Quality Assurance
Certified to ISO 9001:2000

Model number nomenclature 40RM units


40RM

016

GC

40RM Commercial Packaged


Air Handler
Cooling Coil
Direct Expansion
Nominal Capacity kW (Tons)
016 52 (15)
024 70 (20)
028 87 (25)
034 105 (30)
Not Used
Expansion Device
B Thermostatic Expansion Valve
H High Capacity 4-Row Coil
Voltage Designation (V-Ph-Hz)
8 230-3-50
9 400-3-50
Revision Number
0 Original Model
*YC and WD option codes for all 034 size units designate standard motor and high-static drive.

Quality Assurance
Certified to ISO 9001:2000

Factory-Installed Options
GC Unpainted, Standard Motor, and
Standard Drive
HC Unpainted, Standard Motor, and
Medium-Static Drive (Not available
to sizes 016-028)
TC Unpainted, Alternate Motor, and
Medium-Static Drive (sizes 016-028)
YC Unpainted, Alternate Motor, and
High-Static Drive*
ED Painted, Standard Motor, and
Standard Drive
FD Painted, Standard Motor, and
Medium-Static Drive
(Not available for sizes 016-028)
RD Painted, Alternate Motor, and
Medium-Static Drive
(sizes 016-028)
WD Painted, Alternate Motor, and
High-Static Drive*

Packaging
3 Export Packaging

Capacity summary
CONDENSING
UNIT

AIRHANDLING
UNIT 40RM

028
38AKS
034
044
024

38AH

028

034

024
028
034
028
034
034
016
024
028
024
028
034
028
034

AIR-HANDLING
UNIT AIRFLOW
L/s
Cfm
3800
8,000
4700
10,000
5650
12,000
4700
10,000
5650
12,000
5650
12,000
2800
6,000
3800
8,000
4700
10,000
3800
8,000
4700
10,000
5650
12,000
4700
10,000
5650
12,000

SYSTEM GROSS CAPACITY


(Standard 3-Row Coil)
kW*
Btuh
75.6
256,000
80.4
273,000
84.6
288,000
88.2
298,000
93.1
316,000
113.8
385,000
57.3
195,000
62.5
214,000
66.3
227,000
68.9
236,000
73.5
251,000
77.6
265,000
82.6
283,000
87.7
300,000

LEGEND
db Dry Bulb
wb Wet Bulb
SST Saturated Suction Temperature
*System gross capacities are rated according to indoor unit airflow,
35 C air temperature entering condenser, and 20 C wb air temperature entering evaporator.

SYSTEM GROSS CAPACITY


(High-Capacity 4-Row Coil)
kW*
Btuh
83.8
285,800
84.3
287,700
88.7
302,800
89.9
306,800
94.8
323,500
111.8
381,600
60.2
205,300
64.7
220,600
68.6
234,000
72.1
246,100
76.7
261,600
80.5
274,500
86.0
293,600
90.9
310,000

CONDENSING UNIT
ONLY GROSS CAPACITY
kW**
Btuh
82.8

281,000

94.5

320,000

127.0

429,000

63.0

216,000

73.0

250,000

87.0

297,000

System gross capacities are rated according to indoor unit airflow,


95 F air temperature entering condenser, and 67 F wb air temperature entering evaporator.
**Condensing unit gross capacity based on 36 C air temperature entering condenser and 8 C SST.
Condensing unit gross capacity based on 95 F air temperature entering condenser and 45 F SST.

ESTIMATED SOUND POWER LEVELS


50 Hz UNITS
ESTIMATED RADIATED SOUND POWER LEVELS, dB 38AH024-034 AND 38AKS028-034
UNIT
38AH024
38AH028
38AH034
38AKS028
38AKS034
38AKS044

63
97.7
97.7
98.5
97.7
98.5
101.5

125
93.6
93.6
94.2
93.3
94.1
97.3

OCTAVE BAND CENTER FREQUENCY, Hz


250
500
1000
2000
91.0
88.5
87.6
85.7
91.1
88.6
87.9
85.6
91.9
89.5
88.7
86.1
91.0
88.7
88.4
84.5
91.8
89.5
89.2
85.3
94.4
92.1
91.3
87.5

NOTES:
1. Estimated sound power levels, dB re 1 Picowatt
This data is based upon a limited amount of actual testing with the
estimated sound power data being generated from this data in
accordance with ARI (Air Conditioning and Refrigeration Institute,
U.S.A. Standard) standard 370 for large outdoor refrigerating and
air conditioning equipment.

4000
78.8
78.5
76.0
77.8
78.6
81.5

8000
74.4
74.5
74.9
74.0
74.8
78.1

dB(A)
92.5
92.6
93.2
92.4
93.2
95.6

2. Since this data is estimated, the sound power levels should not be
guaranteed or certified as being the actual sound power levels.
The acoustic center of the unit is located at the geometric center of
the unit.

ESTIMATED SOUND POWER LEVELS (Lw) 40RM016-034


UNIT
40RM016
40RM024
40RM028
40RM034

Cfm
6,000
8,000
10,000
12,000

dB(A)
92.7
96.4
96.2
98.5

63
98.9
102.6
102.5
104.7

OCTAVE BAND CENTER FREQUENCY, Hz


125
250
500
94.9
90.9
91.9
98.6
94.6
95.6
98.5
94.5
95.5
100.7
96.7
97.7

1000
85.9
89.6
89.5
91.7

2000
83.9
87.6
87.5
89.7

4000
79.9
83.6
83.5
85.7

NOTE: Since this data is calculated, these sound power levels may be different than the actual sound power levels.
The acoustic center of the unit is located at the geometric center of the unit.

Physical data 38AKS units


38AKS028-044 UNITS SI
UNIT 38AKS
NOMINAL CAPACITY (kW)*
OPERATING WEIGHTS (kg)
With Aluminum-Fin Coils (Standard)
With Copper-Fin Coils (Optional)
REFRIGERANT
Operating Charge, Typical (kg)
COMPRESSOR
Qty...Model
No. Cylinders (ea)
Speed (r/s)
Oil Charge (L)
Capacity Steps
Unloader Settings (kPag)
No. 1 Load
Unload
No. 2 Load
Unload
Crankcase Heater Watts
CONDENSER FANS
Qty...r/s
Diameter (mm)
Nominal kW
Nominal Airflow (L/s total)
Watts (Total)
CONDENSER COIL
Rows...Fins/m
Face Area (sq m)
Storage Capacity (kg)**
CONTROLS
Pressurestat (kPag)
High-Pressure Switch
Cutout
Cut-in
Low-Pressure Switch
Cutout
Cut-in
Oil Pressure Switch
Cutout
Cut-in
FAN CYCLING CONTROLS
Operating Pressure (kPag)
No. 2 Fan, Close
Open
PRESSURE RELIEF
Location
Temperature (C)
PIPING CONNECTIONS (in. ODM)
Suction
Liquid
Hot Gas Stub

028
82.8

034
94.5

748
818

818
1106
911
1246
R-22
13.8
19.7
29.5
Reciprocating, Semi-Hermetic
1...06E9265
1...06E9275
1...06E9299
6
6
6
24.2
9
9
9.5
100%, 66%, 33%
524
400
538
414
180
Propeller Type Direct Drive
2...16
3...16
762
0.75
7400
11,180
1490
1750
1520
Enhanced Copper Tubes, Lanced Aluminum Fins
2...748
3...670
3...670
3.6
3.6
5.4
17
26
38

2940 50
2200 40
185 20
300 35
43
62
1760 70
1100 70
Fusible Plug
Liquid and Suction Line
100
15 / 8

21 / 8
7/
8
5/
8

*Based on operation at 8 C saturated suction temperature and 36 C outdoor ambient temperature.


Typical operating charge with 7.6 m of interconnecting piping.
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at 51.7 C.

044
127.0

21 / 8

38AKS028-044 UNITS ENGLISH


UNIT 38AKS
NOMINAL CAPACITY (tons)*
OPERATING WEIGHTS (lb)
With Aluminum-Fin Coils (Standard)
With Copper-Fin Coils (Optional)
REFRIGERANT
Operating Charge, Typical (lb)
COMPRESSOR
Qty...Model
No. Cylinders (ea)
Speed (rpm)
Oil Charge (pt)
Capacity Steps
Unloader Setting (psig)
No. 1 Load
Unload
No. 2 Load
Unload
Crankcase Heater Watts
CONDENSER FANS
Qty...Speed (Rpm)
Diameter (in.)
Nominal Hp
Nominal Airflow (cfm total)
Watts (Total)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
Storage Capacity (lb)**
CONTROLS
Pressurestat (psig)
High-Pressure Switch
Cutout
Cut-in
Low-Pressure Switch
Cutout
Cut-in
Oil Pressure Switch
Cutout
Cut-in
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close
Open
PRESSURE RELIEF
Location
Temperature (F)
PIPING CONNECTIONS (in. ODM)
Suction
Liquid
Hot Gas Stub

028
23.4

034
26.5

044
35.8

1650
1804

1803
2437
2009
2745
R-22
30.5
43.5
65.0
Reciprocating, Semi-Hermetic
1...06E9265
1...06E9275
1...06E9299
6
6
6
1450
20.0
20.0
19.0
100%, 66%, 33%
76
58
78
60
180
Propeller Type Direct Drive
2...950
3...950
30
1.0
15,700
23,700
1490
1750
1520
Enhanced Copper Tubes, Lanced Aluminum Fins
2...19
3...17
3...17
39.2
39.2
58.4
37.7
56.6
84.4

426 7
320 20
27 3
44 5
6.2
9.0
255 10
160 10
Fusible Plug
Liquid and Suction Line
210
15 / 8

21 / 8
7/8
5/
8

21 / 8

*Based on operation at 45 F saturated suction temperature and 95 F outdoor ambient.


Typical operating charge with 25 ft of interconnecting piping.
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at 125 F.

Physical data 38AH units


38AH024-034 UNITS SI
UNIT 38AH
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
With Aluminum-Fin Coil (Standard)
With Copper-Fin Coil (Optional)
REFRIGERANT
Operating Charge, Typical (kg)**
Shipping Charge (kg)
COMPRESSOR
Qty...Model
No. Cylinders
Speed (r/s)
Oil Charge per Circuit (L)
Capacity Steps (%)
(FIOP or Acy)
Standard
VAV FIOP
Unloader Setting (kPa)
Load
Unload
CONDENSER FANS
Qty...Speed (r/s)
Diameter (mm)
Nominal Hp
Nominal Airflow (L/s)
Watts (total)
CONDENSER COIL
Rows...Fins/m
Total Face Area (sq m)
Storage Capacity (kg)
CONTROLS
Pressurestat (kPa)
High Pressure
Cutout
Cut-in
Low Pressure
Cutout
Cut-in
Oil Pressure
Cutout
Cut-in
FAN CYCLING CONTROLS
Temperature (C)
No. 2 Fan, Close
Open
PRESSURE RELIEF
Location
Temperature (C)
CONNECTIONS (in. ODM)
Suction
Liquid
LEGEND
FIOP Factory-Installed Option
VAV Variable Air Volume

10

024

028

Circuit 1

Circuit 2

Circuit 1

034
Circuit 2

Circuit 1

Circuit 2

63

73

87

798.3
872.3

825.6
899.0
R-22

853.0
951.2

9.10
1.36

9.10
1.36

1...06DH824
6
24.3

1...06DA824
6
24.3

100
67*
33

100

524
400
762
1.0
7870
2...748
3.64
17.4

9.10
9.10
1.36
1.36
Reciprocating Semi-Hermetic
1...06DH328
1...06DA328
6
6
24.3
24.3
4.73

11.40
1.36

11.40
1.36

1...06DH328
6
24.3

1...06DA537
6
24.3

100
100
100
67*

67*
33

33
Factory Installed

524

524

400

400
Propeller Type Direct Driven
2...16
762
762
1.0
1.0
7870
7400
3100
Enhanced Copper Tubes, Aluminum Lanced Fin
2...748
3...670
3.64
3.64
17.4
26.0

100

2940 50
2200 140
185 20
300 35
Manual Reset
42
62
21.1 1.6
15.6 1.6
Fusible Plug
Liquid Line, Suction Line, Compressor
100
13/8
5/ 8
*Standard unit single pressure-actuated suction unloader on compressor no. 1.
VAV FIOP double electrically actuated unloaders on compressor
no. 1.
**Typical operating charge with 7.6 m of interconnecting piping.
Storage capacity of condenser coil with coil 80% full of liquid R-22 at
48.8 C.

38AH024-034 UNITS ENGLISH


UNIT 38AH
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
With Aluminum-Fin Coil (Standard)
With Copper-Fin Coil (Optional)
REFRIGERANT
Operating Charge, Typical (lb)**
Shipping Charge (lb)
COMPRESSOR
Qty...Model
No. Cylinders
Speed (rpm)
Oil Charge per Circuit (Pt)
Capacity Steps (%)
(FIOP or Acy)
Standard Unit
VAV FIOP
Unloader Setting (psig)
Load
Unload
CONDENSER FANS
Qty...Speed (rpm)
Diameter (in.)
Nominal Hp
Nominal Airflow (cfm)
Watts (total)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
Storage Capacity (lb)
CONTROLS
Pressurestat (psig)
High Pressure
Cutout
Cut-in
Low Pressure
Cutout
Cut-in
Oil Pressure
Cutout
Cut-in
FAN CYCLING CONTROLS
Temperature (F)
No. 2 Fan, Close
Open
PRESSURE RELIEF
Location
Temperature (F)
CONNECTIONS (in. ODM)
Suction
Liquid
LEGEND
FIOP Factory-Installed Option
VAV Variable Air Volume

024

028

Circuit 1

Circuit 2

Circuit 1

034
Circuit 2

Circuit 1

Circuit 2

18

21

25

1760
1923

1820
1982
R-22

1880
2097

20
3

20
3

1...06DH824
6
1450

1...06DA824
6
1450

100
67*
33

100

76
58
30
1.0
16,700
2...19
39.20
37.7

20
20
3
3
Reciprocating Semi-Hermetic
1...06DH328
1...06DA328
6
6
1450
1450
10

25
3

25
3

1...06DH328
6
1450

1...06DA537
6
1450

100
100
100
67*

67*
33

33
Factory Installed

76

76

58

58
Propeller Type Direct Driven
2...950
30
1.0
16,700
3100
Enhanced Copper Tubes, Aluminum Lanced Fin
2...19
39.20
37.7

100

30
1.0
15,700
3...17
39.20
56.6

426 7
320 20
27 3
44 5
Manual Reset
6.0
8.8
70 3
60 3
Fusible Plug
Liquid Line, Suction Line, Compressor
210
13/8
5/ 8
*Standard unit single pressure-actuated suction unloader on compressor no. 1.
VAV FIOP double electrically actuated unloaders on compressor
no. 1.
**Typical operating charge with 25 ft of interconnecting piping.
Storage capacity of condenser coil with coil 80% full of liquid R-22 at
120 F.

11

Physical data 40RM units


40RM UNITS SI
UNIT 40RM
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
Base Unit with TXV (3 Row/4 Row)
Plenum
FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)*
230-3-50, 400-3-50
Motor Speed (r/s)
230-3-50, 400-3-50
REFRIGERANT
Operating charge (kg)
(approx per circuit)
DIRECT-EXPANSION COIL
Max Working Pressure (kPag)
Face Area (sq m)
No. of Splits
No. of Circuits per Split (3 Row/4 Row)
Split Type...Percentage
Fins/m
STEAM COIL
Max Working Pressure (kPag at 204.4 C)
Total Face Area (sq m)
Rows...Fins/m
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
Water Volume
(L)
(m3)
PIPING CONNECTIONS,
Qty...Size (in.)
DX Coil Suction (ODF)
DX Coil Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
FILTERS
Qty...Size
Access Location
LEGEND
DX Direct Expansion
TXV Thermostatic Expansion Valve

12

016
52

024
70

028
87

034
105

311/323
102

313/331
102

463/470
148

467/482
148

2...381
2831
2124-3539

2...381
3775
2831-4719

2...457
4719
3539-5899

2...457
5663
4247-7079

2.16

3.73

5.59

7.46

23.8

23.8

23.8

23.8

R-22
1.13/1.13
1.64
2
12/16
591

1.59/1.59
2.04/2.04
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
2999
1.85
2.30
2
2
13/18
15/20
Face...50/50
670
591

2.27/2.27
2.77
2
18/24
591

1207
1.24
1...394

1.24
1...394

1.24
2...335

1.24
2...335

1.39
1...394

1.39
1...394

1.39
2...493

1.39
2...493

1034

52.6
0.052
2...11/8

54.1
0.054
2...11/8

2...13/8
2...5/8
1...21/2
1...11/2
1...2
1...2
1...11/4 ODM/1 IDF

2...13/8

Throwaway Factory Supplied


4...406 508 51
4...508 x 610 x 51
4...406 610 51
4...508 x 635 x 51
Right or Left Side
*Refer to Alternate Fan Motor Data table on page 71 for alternate motor
data.
Units are shipped without refrigerant charge.

40RM UNITS ENGLISH


UNIT 40RM
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Base Unit with TXV (3 Row/4 Row)
Plenum
FANS
Qty...Diam. (in.)
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor kW (Standard Motor)*
230-3-50, 400-3-50
Motor Speed (rpm)
230-3-50, 400-3-50
REFRIGERANT
Operating Charge (lb)
(approx per circuit)
DIRECT-EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
No. of Splits
Split Type...Percentage
No. of Circuits per Split (3 Row/4 Row)
Fins/in.
STEAM COIL
Max Working Pressure (psig at 400 F)
Total Face Area (sq ft)
Rows...Fins/in.
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
Water Volume
(gal)
(ft3)
PIPING CONNECTIONS,
Qty...Size (in.)
DX Coil Suction (ODF)
DX Coil Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
FILTERS
Qty...Size (in.)
Access Location
LEGEND
DX Direct Expansion
TXV Thermostatic Expansion Valve

016
15

024
20

028
25

034
30

685/713
225

690/730
225

1020/1050
325

1030/1062
325

2...15
6000
4500-7500

2...15
8000
6000-10,000

2...18
10,000
7500-12,500

2...18
12,000
9000-15,000

2.9

5.0

7.5

10.0

1425
R-22
2.5/2.5
17.67
2
12/16
15

3.5/3.5
4.5/4.5
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
19.88
24.86
2
2
Face...50/50
13/18
15/20
17
15

5.0/5.0
29.83
2
18/24
15

175
13.33
1...10

13.33
1...10

13.33
2...8.5

13.33
2...8.5

15.0
1...10

15.0
1...10

15.0
2...12.5

15.0
2...12.5

150

13.9
1.85
2...11/8

14.3
1.90
2...11/8

2...13/8
2...5/8
1...21/2
1...11/2
1...2
1...2
1
1...1 /4 ODM/1 IDF
Throwaway Factory Supplied
4...16 20 2
4...16 24 2

2...13/8

4...20 24 2
4...20 25 2
Right or Left Side

*Refer to Alternate Fan Motor Data table on page 71 for alternate motor
data.
Units are shipped without refrigerant charge.

13

Options and accessories


38AKS, 38AH factory-installed options

Gage panel package provides a suction and a discharge


pressure gage for the refrigerant circuit.
ModuPanel control box allows systems to operate as
VAV (variable air volume) systems. Includes microprocessor, satellite sequencer, 4 status lights, 5-hour bypass timer,
and locked enclosure.
Hot-gas bypass kit (38AKS only) prevents the indoor
coil from freezing up during low airflow or low return-air
temperature applications by maintaining minimum suction
pressure.
Carriers line of thermostats provide both programmable and non-programmable capability with the new
Debonair line of commercial programmable thermostats,
the Commercial Electronic thermostats provide 7-day
programmable capability for economical applications.
PremierLink controller is a field retrofit split system
control compatible with the Carrier Comfort Network
(CCN) and other building automation systems (BAS). This
control is designed to allow users the access and ability to
change factory-defined settings thus expanding the function of the standard unit.

Enviro-Shield condenser options are available to


match coil protection to site conditions for optimum durability. See table below and refer to the Application Data for
selection guidance. Consult your Carrier representative for
further information.
VAV option (38AH only) provides unit with 2 electric
unloaders and control box modifications necessary to connect to a field-installed VAV controller.

38AKS, 38AH field-installed accessories


Electric unloader package includes hardware and
solenoid valve to convert a pressure-operated unloader to
electric unloading.
Pressure-operated unloading (38AH only) allows
compressor to be unloaded in response to compressor suction pressure.
20 F (29 C) low-ambient temperature kit (Motormaster) controls outdoor-fan motor operation to maintain the correct head pressure at low outdoor ambient
temperatures. Only one low ambient temperature kit is
required per unit.

CONDENSER COIL OPTIONS


COPPER-TUBE COILS
WITH ENVIRO-SHIELD
OPTION*
Al Fins (Standard Coils)
Cu Fins
Al Fins, E-Coating
Cu Fins, E-Coating
Al Fins, Pre-coated
Al
Cu
Enviro-Shield
E-Coated
Pre-Coated

14

Standard

Mild
Coastal

ENVIRONMENT
Moderate
Severe
Coastal
Coastal

Industrial

Combined
Industrial/Coastal

X
X
X
X

LEGEND
Aluminum
Copper
Family of Coil Protection Options
Epoxy coating Applied to Entire Coil Assembly
Epoxy coating Applied to Fin Stock Material

*See Selection Guide: Environmental Corrosion Protection Catalog


No. 811-287 for more information.

40RM factory-installed options


Prepainted steel units are available from the factory for
applications that require painted units. Units are constructed of pre-painted steel panels in American Sterling
Gray color.
High-capacity 4-row coils are available to provide
increased latent/sensible capacities and efficiencies.
Alternate fan motors and drives are available to provide the widest possible range of performance.

40RM field-installed accessories


Discharge plenum directs the air discharge directly into
the occupied space; integral horizontal and vertical louvers
enable redirection of airflow. Accessory is available
unpainted or painted.
Two-row hot water coils have 5/8-in. (15.875 mm)
diameter copper tubes mechanically bonded to aluminum
plate fins. Coils have non-ferrous headers.
One-row steam coil has 1-in. (25.44 mm) OD copper
tube and aluminum fins. The Inner Distributing Tube (IDT)
design provides uniform temperatures across the coil face.
The steam coil has a broad operating pressure range; up to
20 psig at 260 F (138 kpag at 126 C). The IDT steam coils
are especially suited to applications where sub-freezing air
enters the unit.
Electric resistance heat coils have an open-wire design
and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard.
Economizer (enthalpy controlled) provides ventilation
air and free cooling if outside ambient temperature and
humidity are suitable. It can also be used with CO2 sensors
to help meet indoor air quality requirements.

Return-air grille provides a protective barrier over the


return-air opening and gives a finished appearance to units
installed in the occupied space. Accessory is available
unpainted or painted.
Subbase provides a stable, raised platform and room for
condensate drain connection for floor-mounted units.
Accessory is available unpainted or painted.
Overhead suspension package includes necessary
brackets to support units in horizontal ceiling installations.
CO2 sensors can be used in conjunction with the economizer accessory to help meet indoor air quality requirements. The sensor signals the economizer to open when
the CO2 level in the space exceeds the set point. A Carrier
Comfort System programmable thermostat can also be
used to override the sensor if the outside air temperature is
too high or too low.
Condensate drain trap includes an overflow shutoff
switch that can be wired to turn off the unit if the trap
becomes plugged. The kit also includes a wire harness that
can be connected to an alarm if desired. The transparent
trap is designed for easy service and maintenance.
UV-C germicidal lamps kill mold and fungus, which may
grow on evaporator coil and condensate pan surfaces. The
use of UV-C germicidal lamps eliminates the foul odors
that result from this growth of mold and fungus. It also provides a self-cleaning function for the evaporator coil and
drain pan.

15

Options and accessories (cont)


40RM WITH DISCHARGE PLENUM,
RETURN GRILLE, AND SUBBASE

40RM WITH HOT WATER OR STEAM COIL


HOT WATER OR
STEAM COIL

DISCHARGE
PLENUM

RETURN-AIR
GRILLE

SUBBASE
FAN
COIL
UNIT

40RM WITH ECONOMIZER


AND UV-C GERMICIDAL LAMPS

ECONOMIZER

UV-C GERMICIDAL LAMPS

16

FAN COIL
UNIT

40RM WITH CONDENSATE DRAIN TRAP

Dimensions 38AKS028,034

NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space
above unit.
3. The approximate operating weight of the unit is:
UNIT
38AKS
028
028C
034
034C

WEIGHT
(lb)
1650
1804
1803
2009

WEIGHT
(kg)
748
818
818
911

NOTE: A C in model number indicates unit has optional


factory-installed copper-fin coil.
4. Dimensions in [ ] are millimeters.

APPROXIMATE OPERATING WEIGHT*


AT SUPPORT POINTS LB (KG)*
UNIT
38AKS
028
034

418
626
242
364
(189.6) (284.0) (109.8) (165.1)
459
673
272
399
(208.2) (305.3) (123.4) (181.0)

TOTAL
1650
(748.4)
1803
(817.8)

*Standard copper tube aluminum-fin coil.

17

Dimensions 38AKS044

NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space
above unit.
3. The approximate operating weight of the unit is:
UNIT
38AKS
044
044C

WEIGHT
(lb)
2437
2745

WEIGHT
(kg)
1106
1246

NOTE: A C in model number indicates unit has


optional factory-installed copper-fin coil.

APPROXIMATE OPERATING WEIGHT*


AT LIFTING HOLES LB (KG)*
UNIT
38AKS

TOTAL

044

720
(327)

900
(409)

455
(207)

362
(165)

2437
(1106)

*Standard copper tube aluminum-fin coil.

18

Dimensions 38AH024-034

NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all
sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space above unit.
3. C in the package number indicates copper coils.
4. Dimensions in [ ] are in millimeters.
5. The approximate operating weight of the unit is shown below.
6. Certified dimensional drawing is available on request.
CORNER WEIGHT lb [kg]
UNIT
38AH

024
024C
028
028C
034
034C

631.6
[286.5]
666.5
[302.3]
658.7
[298.8]
693.0
[314.3]
667.0
[302.5]
718.3
[325.8]

577.6
[262.0]
609.5
[276.5]
602.4
[273.3]
633.8
[287.5]
610.0
[276.7]
656.8
[297.9]

263.1
[119.3]
309.0
[140.2]
267.0
[121.1]
313.0
[142.0]
288.0
[130.7]
344.8
[156.4]

287.7
[130.5]
337.9
[153.3]
291.9
[132.4]
342.2
[155.2]
315.0
[142.9]
377.0
[171.0]

CENTER OF
GRAVITY
A Dim.
in.
[mm]
40.00
[1016]
43.00
[1092]
39.25
[997]
42.25
[1073]
41.00
[1041]
44.00
[1117]

B Dim.
in.
[mm]

32.75
[832]

TOTAL
UNIT WT
lb [kg]
1760
[798.3]
1923
[872.3]
1820
[825.6]
1982
[899.0]
1880
[853.0]
2097
[951.2]

19

Dimensions 40RM016-024

TXV Thermostatic Expansion Valve


NOTES:
1. Dimensions in [ ] are in millimeters.
2.

Direction of airflow.

3. Recommended clearance:
Rear: 76 mm (3 in.)
Front: 762 mm (2 ft, 6 in.)
Right side: 762 mm (2 ft, 6 in.)
Left side: 762 mm (2 ft, 6 in.)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.

UNIT 40RM
3-Row
Coil
4-Row
Coil

20

016
024
016
024

UNIT WEIGHT
lb (kg)
685 (311)
690 (313)
713 (323)
730 (331)

Dimensions 40RM028,034

CONTROL BOX

CONTROL BOX

TXV Thermostatic Expansion Valve


NOTES:
1. Dimensions in [ ] are in millimeters.
2.

Direction of airflow.

3. Recommended clearance:
Rear: 76 mm (3 in.)
Front: 762 mm (2 ft, 6 in.)
Right side: 762 mm (2 ft, 6 in.)
Left side: 762 mm (2 ft, 6 in.)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.

UNIT 40RM
3-Row
Coil
4-Row
Coil

028
034
028
034

UNIT WEIGHT
lb (kg)
1020 (463)
1030 (467)
1050 (470)
1062 (482)

21

Selection procedure
38AH024-034/40RM SI
NOTE: This book contains combination ratings for
38AH024-034 units and matching 40RM air handlers. If
the 38AH units are matched with 39 Series air handlers,
use the Carrier AHU (Air-Handling Unit) selection program
software package for combination ratings. If Totaline
P702 water coolers are used, determine the performance
by cross-plotting the condensing unit performance found
in this book against the P702 performance in the P702
product data book. If the 38AH condensing units are
matched with 2 independent 40RM units, cross-plot for
performance ratings or contact Carrier Application Engineering for assistance.
I Determine cooling load, evaporator-air temperature and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . . . . . . . . 60 kW
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . . . . . . . 48 kW
Temperature Air Entering
Condenser (Edb) . . . . . . . . . . . . . . . . . . . 36 C
Temperature Air Entering
Evaporator (db/wb) . . . . . . 26.7 C db, 20 C wb
Evaporator Air Quantity. . . . . . . . . . . . . 3800 L/s
External Static Pressure . . . . . . . . . . . . .150 Pa
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . 18 m (Linear)
II Select condensing unit air-handler combination.
For this example, select a 38AH024 matched with
a 40RM024. This 38AH024/40RM024 condensing unit-air handler combination provides 62.5 kW
of total cooling capacity and 49.2 kW of sensible
capacity at the given conditions. If other temperatures or airflow values are required, interpolate the
values from the combination ratings.

22

III Determine sizes of liquid and suction lines.


Enter the Refrigerant Pipe Sizes table. The sizes
shown are based on an equivalent length of pipe.
This equivalent length is equal to the linear length of
pipe indicated at the top of each sizing column, plus
a 50% allowance for fitting losses. (For a more accurate determination of actual equivalent length in
place of using the estimated 50% value, refer to
Carrier System Design Manual.) For this example,
note in the linear length column that the proper
pipe size is 5/8 in. for the liquid lines and 13/8 in.
for the suction lines.
IV Determine fan rpm and bhp (brake
horsepower).
At the Air Handler Fan Performance table, enter
the 40RM024 section at 3800 L/s and move to the
External Static Pressure (ESP) column. Note that the
conditions require 13.71 r/s at 2.81 kW.
V Determine motor and drive.
Enter the Fan Motor Data tables and find that the
standard motor shaft (kW) for a 40RM024 unit
is rated at 3.73. Since the kW required is 2.81, a
standard motor satisfies the requirement and should
be used.
Next, find the type of drive that satisfies the
13.71 r/s requirement in the Drive Data tables. For a
40RM024 unit, the Standard Drive table shows an
r/s range of 11.9 to 14.6. Since the r/s required is
13.71, the standard drive satisfies the requirement
and should be used. Select the standard motor and
standard drive combination (option code GC or ED).

38AH024-034/40RM English
NOTE: This book contains combination ratings for
38AH024-034 units and matching 40RM air handlers. If
the 38AH units are matched with 39 Series air handlers,
use the Carrier AHU (Air-Handling Unit) selection program
software package for combination ratings. If Totaline
P702 water coolers are used, determine the performance
by cross-plotting the condensing unit performance found
in this book against the P702 performance in the P702
product data book. If the 38AH condensing units are
matched with 2 independent 40RM units, cross-plot for
performance ratings or contact Carrier Application Engineering for assistance.
I Determine cooling load, evaporator-air temperature and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . . 210,000 Btuh
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . .175,000 Btuh
Temperature Air Entering
Condenser (Edb) . . . . . . . . . . . . . . . . . . . .95 F
Temperature Air Entering
Evaporator (db/wb) . . . . . . . . 80 F db, 67 F wb
Evaporator Air Quantity. . . . . . . . . . . . . 8000 cfm
External Static Pressure . . . . . . . . . . . 1.0 in wg
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . .30 ft (Linear)
II Select condensing unit air-handler combination.
For this example, select a 38AH024 matched with a
40RM024. This 38AH024/40RM024 condensing
unit-air handler combination provides 214,500 Btuh
of total cooling capacity and 179,000 Btuh of sensible
capacity at the given conditions. If other temperatures
or airflow values are required, interpolate the values
from the combination ratings.

III Determine sizes of liquid and suction lines.


Enter the Refrigerant Pipe Sizes table. The sizes
shown are based on an equivalent length of pipe.
This equivalent length is equal to the linear length of
pipe indicated at the top of each sizing column, plus
a 50% allowance for fitting losses. (For a more accurate determination of actual equivalent length in
place of using the estimated 50% value, refer to
Carrier System Design Manual.) For this example,
note in the linear length column that the proper
pipe size is 5/8 in. for the liquid lines and 13/8 in.
for the suction lines.
IV Determine fan rpm and bhp (brake
horsepower).
At the Air Handler Fan Performance table, enter
the 40RM024 section at 8000 cfm and move to the
External Static Pressure (ESP) column. Note that the
conditions require 930 rpm at 4.7 bhp.
V Determine motor and drive.
Enter the Fan Motor Data tables and find that the
alternate motor hp for a 40RM024 unit is rated at
7.5 hp. Since the bhp required is 4.7, an alternate
motor satisfies the requirement and should be used.
Next, find the type of drive that satisfies the 930 rpm
requirement in the Drive Data tables. For a
40RM024 unit, the Medium-Static Drive table shows
an rpm range of 814 to 1018. Since the rpm
required is 930, the medium-static drive satisfies the
requirement and should be used. Select the alternate
motor and medium-static drive combination (option
code TC or RD).

23

Performance data
38AKS CONDENSING UNIT RATINGS SI
38AKS028
SST
(C)
6
4
2
0
2
4
6
8
10

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

38AKS044
28
55.3
17.4
41.2
60.4
18.2
42.1
64.4
18.8
42.9
69.9
19.6
43.9
75.6
20.5
45.0
80.2
21.1
45.9
86.4
22.0
47.1
91.2
22.6
48.0
97.9
23.5
49.3

Air Temperature Entering Condenser (C)


32
36
40
44
48
52.4
49.5
46.6
43.8
41.0
18.0
18.6
19.1
19.6
20.0
44.8
48.5
52.1
55.8
59.6
57.3
54.2
51.1
48.1
45.2
18.9
19.5
20.1
20.6
21.1
45.7
49.3
52.9
56.5
60.2
61.1
57.8
54.7
51.5
48.5
19.5
20.3
20.9
21.5
22.0
46.4
50.0
53.6
57.1
60.7
66.4
62.9
59.6
56.3
53.0
20.4
21.2
21.9
22.6
23.1
47.4
50.9
54.5
58.0
61.6
71.9
68.3
64.7
61.2
57.7
21.3
22.2
23.0
23.7
24.3
48.5
52.0
55.4
59.0
62.5
76.3
72.5
68.7
65.0
61.4
22.0
22.9
23.8
24.5
25.2
49.3
52.8
56.2
59.7
63.2
82.3
78.3
74.3
70.3
66.5
23.0
23.9
24.8
25.7
26.5
50.5
53.9
57.3
60.8
64.2
87.0
82.8
78.6
74.5
70.5
23.7
24.7
25.7
26.6
27.4
51.4
54.8
58.2
61.6
65.0
93.5
89.0
84.6
80.3
76.0
24.6
25.7
26.8
27.8
28.7
52.7
56.0
59.4
62.8
66.1

52
38.3
20.4
63.3
42.3
21.5
63.8
45.4
22.4
64.4
49.7
23.7
65.1
54.3
24.9
66.0
57.8
25.9
66.7
62.7
27.2
67.7
66.5
28.2
68.4
71.7
29.5
69.5

38AKS034
SST
(C)
6
4
2
0
2
4
6
8
10

24

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

28
62.4
20.0
42.1
68.7
20.7
42.2
73.3
21.3
42.7
79.5
22.1
43.6
85.9
23.0
44.6
90.9
23.7
45.4
97.8
24.6
46.6
103.0
25.2
47.5
110.0
26.2
48.8

Air Temperature Entering Condenser (C)


32
36
40
44
48
58.9
55.3
51.7
48.1
44.5
20.6
21.2
21.6
21.9
22.2
46.0
50.0
54.1
58.0
62.0
65.0
61.3
57.6
53.7
49.9
21.4
22.2
22.7
23.2
23.5
46.1
50.1
54.1
58.1
62.1
69.7
66.0
62.1
58.2
54.3
22.1
22.9
23.5
24.1
24.5
46.4
50.2
54.1
58.1
62.0
75.8
72.1
68.3
64.3
60.3
23.0
23.9
24.6
25.2
25.8
47.2
50.8
54.5
58.3
62.1
82.1
78.2
74.3
70.3
66.3
24.0
24.9
25.7
26.4
27.1
48.1
51.7
55.2
58.9
62.5
87.0
83.0
79.0
74.9
70.8
24.7
25.7
26.6
27.4
28.1
48.9
52.5
56.0
59.5
63.1
93.6
89.5
85.3
81.0
76.8
25.7
26.8
27.8
28.6
29.4
50.1
53.5
57.0
60.5
64.0
98.8
94.5
90.2
85.8
81.4
26.4
27.6
28.6
29.6
30.5
50.9
54.4
57.8
61.3
64.7
106.0 101.0 96.9
92.3
87.7
27.4
28.7 29.8
30.9
31.9
52.2
55.6
59.0
62.4
65.8

52
40.8
22.2
66.1
46.1
23.7
66.1
50.3
24.8
66.1
56.1
26.2
66.1
62.1
27.6
66.2
66.6
28.7
66.6
72.4
30.1
67.5
76.9
31.2
68.2
83.0
32.7
69.2

SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

6
4
2
0
2
4
6
8
10

kW
SDT
SST
TC

Air Temperature Entering Condenser (C)


28
32
36
40
44
48
52
82.8
78.8
74.8
70.9
67.1
63.3
59.5
27.3
28.1
29.0
29.7
30.4
31.0
31.5
41.4
45.3
49.3
53.3
57.3
61.3
65.3
90.9
86.5
82.3
78.0
73.9
69.8
65.7
28.3
29.3
30.3
31.1
31.9
32.6
33.2
41.3
45.3
49.3
53.3
57.3
61.3
65.3
97.3
92.7
88.2
83.7
79.4
75.0
70.7
29.0
30.1
31.2
32.2
33.0
33.8
34.5
41.4
45.3
49.3
53.3
57.3
61.3
65.3
106.0 101.0 96.5
91.7
87.1
82.4
77.8
30.0
31.2 32.4
33.5
34.5
35.4
36.2
41.8
45.6
49.4
53.4
57.3
61.3
65.3
115.0 110.0 105.0 99.9
95.1
90.2
85.3
31.2
32.5
33.7 34.9
36.0
37.0
37.9
42.5
46.2
50.0
53.7
57.5
61.4
65.4
121.0 116.0 111.0 106.0 101.0 96.1
91.1
32.1
33.5
34.8
36.0
37.2 38.2
39.2
43.2
46.9
50.5
54.2
58.0
61.7
65.5
130.0 125.0 120.0 114.0 109.0 104.0 98.8
33.3
34.8
36.2
37.6
38.8
40.0 41.1
44.2
47.8
51.5
55.1
58.7
62.4
66.1
138.0 132.0 127.0 121.0 116.0 110.0 105.0
34.2
35.8
37.3
38.8
40.1
41.3
42.5
45.0
48.6
52.2
55.8
59.4
63.0
66.7
148.0 142.0 136.0 130.0 124.0 118.0 113.0
35.5
37.2
38.8
40.4
41.8
43.2
44.4
46.1
49.7
53.2
56.8
60.4
64.0
67.6

LEGEND
Out of Range
Compressor Power
Saturated Discharge Temperature at Compressor (C)
Saturated Suction Temperature (C)
Gross Cooling Capacity (kW)

38AKS CONDENSING UNIT RATINGS ENGLISH


38AKS044

38AKS028
SST
(F)
20
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Air Temperature Entering Condenser (F)


85
95
100
105
115
120
125
181.0 167.0 161.0 154.0 141.0 134.0 128.0
17.4
18.3
18.6
19.0
19.6
19.8
20.0
108.0 117.0 122.0 126.0 136.0 141.0 145.0
202.0 187.0 180.0 173.0 159.0 152.0 145.0
18.5
19.4
19.8
20.2
20.9
21.2
21.5
110.0 119.0 124.0 128.0 137.0 142.0 146.0
225.0 209.0 201.0 193.0 178.0 171.0 163.0
19.5
20.6
21.0
21.5
22.3
22.7
23.0
112.0 121.0 126.0 130.0 139.0 143.0 148.0
249.0 231.0 223.0 215.0 198.0 190.0 182.0
20.6
21.7
22.3
22.8
23.7
24.2
24.6
115.0 123.0 128.0 132.0 141.0 145.0 150.0
274.0 256.0 246.0 237.0 220.0 211.0 202.0
21.6
23.0
23.6
24.1
25.2
25.7
26.2
117.0 126.0 130.0 135.0 143.0 148.0 152.0
301.0 281.0 271.0 261.0 242.0 233.0 224.0
22.8
24.2
24.9
25.5
26.7
27.3
27.8
120.0 129.0 133.0 137.0 146.0 150.0 154.0
329.0 307.0 297.0 287.0 266.0 256.0 246.0
23.9
25.5
26.2
26.9
28.3
28.9
29.5
123.0 131.0 136.0 140.0 148.0 152.0 157.0

38AKS034
SST
(F)
20
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

85
203.0
20.0
110.0
230.0
21.0
110.0
256.0
22.0
112.0
283.0
23.1
114.0
311.0
24.3
117.0
340.0
25.4
119.0
371.0
26.6
122.0

Air Temperature Entering Condenser (F)


95
100
105
115
120
125
187.0 178.0 170.0 153.0 145.0 136.0
20.8
21.1
21.4
21.8
21.8
21.8
120.0 125.0 130.0 140.0 145.0 150.0
212.0 204.0 195.0 176.0 167.0 158.0
22.0
22.4
22.8
23.4
23.6
23.7
120.0 125.0 130.0 140.0 145.0 150.0
239.0 230.0 221.0 202.0 192.0 182.0
23.2
23.7
24.1
24.9
25.3
25.5
121.0 126.0 130.0 140.0 145.0 150.0
265.0 256.0 247.0 228.0 218.0 208.0
24.4
25.0
25.5
26.5
26.9
27.2
123.0 127.0 132.0 141.0 146.0 150.0
292.0 282.0 273.0 253.0 243.0 233.0
25.7
26.4
27.0
28.1
28.6
29.0
125.0 130.0 134.0 143.0 147.0 152.0
320.0 310.0 300.0 279.0 269.0 259.0
27.0
27.8
28.5
29.7
30.3
30.8
128.0 132.0 136.0 145.0 149.0 154.0
350.0 339.0 328.0 307.0 296.0 285.0
28.4
29.2
30.0
31.4
32.1
32.7
130.0 135.0 139.0 148.0 152.0 156.0

SST
(F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

20
25
30
35
40
45
50

kW
SDT
SST
TC

85
271.0
27.3
109.0
305.0
28.6
109.0
341.0
29.9
109.0
377.0
31.3
111.0
415.0
32.9
113.0
455.0
34.5
115.0
497.0
36.1
117.0

Air Temperature Entering Condenser (F)


95
100
105
115
120
125
252.0 243.0 234.0 216.0 208.0 199.0
28.5
29.0
29.5
30.3
30.7
31.0
119.0 124.0 129.0 139.0 144.0 149.0
284.0 274.0 264.0 245.0 235.0 225.0
30.0
30.7
31.3
32.3
32.8
33.2
119.0 124.0 129.0 139.0 144.0 149.0
319.0 308.0 297.0 275.0 265.0 254.0
31.5
32.3
33.0
34.2
34.8
35.3
119.0 124.0 129.0 139.0 144.0 149.0
355.0 343.0 332.0 309.0 297.0 286.0
33.1
33.9
34.7
36.1
36.8
37.4
120.0 125.0 129.0 139.0 144.0 149.0
391.0 379.0 367.0 343.0 331.0 319.0
34.8
35.7
36.6
38.2
38.9
39.6
122.0 126.0 131.0 140.0 145.0 150.0
429.0 416.0 403.0 377.0 365.0 352.0
36.6
37.6
38.6
40.3
41.1
41.9
124.0 128.0 133.0 142.0 147.0 151.0
468.0 455.0 441.0 413.0 400.0 386.0
38.4
39.5
40.6
42.5
43.5
44.3
126.0 131.0 135.0 144.0 149.0 153.0

LEGEND
Out of Range
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)

25

Performance data (cont)


38AKS/40RM COMBINATION RATINGS STANDARD 3-ROW COIL SI
38AKS028/40RM024 WITH STANDARD 3-ROW COIL
Evaporator Air L/s
Temp (C)
2900
3800
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
22
20
16
22
20
16
22
TC
86.6 81.7 73.9 90.6 84.8 77.6 93.1
20
SHC 44.0 51.5 73.9 48.9 59.2 77.6 53.4
kW
19.70 19.31 18.70 20.01 19.55 18.99 20.20
TC
81.9 77.1 70.0 85.6 80.0 73.6 87.8
28
SHC 42.2 49.6 70.0 47.1 57.1 73.6 51.6
kW
21.44 20.84 19.95 21.90 21.20 20.39 22.18
TC
79.4 74.6 67.8 82.9 77.5 71.3 85.0
32
SHC 41.2 48.6 67.8 46.1 55.9 71.3 50.6
kW
22.57 21.85 20.84 23.09 22.28 21.36 23.41
TC
77.0 72.2 65.8 80.2 74.9 69.2 82.2
36
SHC 40.2 47.6 65.8 45.2 54.8 69.2 49.6
kW
23.66 22.81 21.67 24.23 23.30 22.28 24.59
TC
74.4 69.7 63.7 77.4 72.4 67.0 79.3
40
SHC 39.2 46.6 63.7 44.2 53.6 67.0 48.6
kW
24.82 23.84 22.58 25.45 24.39 23.27 25.84
TC
71.8 67.1 61.4 74.6 69.7 64.6 76.4
44
SHC 38.2 45.5 61.4 43.2 52.4 64.6 47.6
kW
26.02 25.01 23.79 26.63 25.57 24.49 27.01
TC
69.7 64.3 58.1 72.8 67.2 61.8 74.8
48
SHC 37.3 44.4 58.1 42.5 51.3 61.8 47.0
kW
27.31 25.93 24.73 28.10 26.68 25.30 28.61
TC

61.9 56.1

64.8 59.7

52
SHC

43.4 56.1

50.2 59.7

kW

26.99 25.46

27.74 26.40

38AKS028/40RM028 WITH STANDARD 3-ROW COIL


Evaporator Air L/s
Temp (C)
3500
4700
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
22
20
16
22
20
16
22
TC
93.2 89.7 80.1 96.9 90.7 83.9 99.0
20
SHC 49.1 57.0 80.1 55.3 67.5 83.9 61.2
kW
20.21 19.94 19.18 20.50 20.02 19.48 20.67
TC
88.2 83.8 75.7 91.4 85.4 79.4 93.2
28
SHC 47.3 55.3 75.7 53.4 65.2 79.4 59.2
kW
22.22 21.68 20.65 22.62 21.87 21.13 22.85
TC
85.5 80.7 73.3 88.5 82.5 77.0 90.2
32
SHC 46.3 54.4 73.3 52.4 64.0 77.0 58.2
kW
23.48 22.76 21.66 23.92 23.03 22.21 24.18
TC
82.8 77.6 71.0 85.5 79.7 74.6 87.1
36
SHC 45.3 53.6 71.0 51.3 62.8 74.6 57.1
kW
24.70 23.77 22.60 25.18 24.14 23.25 25.46
TC
80.0 74.5 68.6 82.4 76.7 72.2 83.9
40
SHC 44.2 52.7 68.6 50.2 61.5 72.2 56.1
kW
26.00 24.83 23.61 26.50 25.31 24.36 26.81
TC
77.3 71.3 66.1 79.4 73.8 69.7 80.8
44
SHC 43.2 51.8 66.1 49.2 60.3 69.7 55.0
kW
27.19 25.91 24.80 27.66 26.45 25.56 27.95
TC

68.5 63.3

71.7 67.3

48
SHC

51.0 63.3

59.4 67.3

kW

27.02 25.68

27.83 26.71

TC

65.6 61.0

65.0

52
SHC

50.2 61.0

65.0

kW

27.96 26.75

27.81

Edb
Ewb
kW
Ldb
Lwb
SHC
TC

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.

26

16
80.5
80.5
19.22
76.4
76.4
20.75
74.1
74.1
21.78
71.9
71.9
22.76
69.6
69.6
23.82
67.2
67.2
25.04
64.7
64.7
26.04
62.5
62.5
27.15

38AKS028/40RM034 WITH STANDARD 3-ROW COIL


Evaporator Air L/s
Temp (C)
4250
5650
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
22
20
16
22
20
16
22
TC
99.5 92.5 85.7 102.5 95.8 90.0 104.3
24
SHC 54.0 65.4 85.7
61.7 75.3 90.0
68.7
kW
20.71 20.16 19.62 20.94 20.42 19.96 21.09
TC
93.9 86.8 80.8 96.4 90.0 85.0 98.0
28
SHC 51.9 63.0 80.8 59.6 72.7 85.0 66.6
kW
22.94 22.05 21.30 23.25 22.45 21.82 23.45
TC
91.0 83.8 78.2 93.3 86.9 82.3 94.8
32
SHC 50.8 61.8 78.2 58.5 71.4 82.3 65.5
kW
24.29 23.22 22.38 24.64 23.68 23.00 24.86
TC
87.9 80.8 75.6 90.0 83.8 79.6 91.4
36
SHC 49.6 60.5 75.6 57.3 70.0 79.6 64.4
kW
25.61 24.34 23.42 25.98 24.87 24.14 26.22
TC
84.8 77.7 73.0 86.6 80.6 76.9 87.9
40
SHC 48.4 59.2 73.0 56.1 68.6 76.9 63.2
kW
27.00 25.50 24.52 27.38 26.11 25.34 27.64
TC
81.8 74.6 70.2

77.4 74.1

44
SHC 47.3 57.9 70.2

67.2 74.1

kW
28.17 26.62 25.68

27.23 26.52

TC

72.5 67.8

72.2

48
SHC

57.1 67.8

72.2

kW

28.03 26.82

27.96

TC

65.3

52
SHC

65.3

kW

27.88

16
87.1
87.1
19.74
82.6
82.6
21.52
80.1
80.1
22.68
77.7
77.7
23.79
75.2
75.2
24.98
72.6
72.6
26.20
70.7
70.7
27.56

38AKS034/40RM028 WITH STANDARD 3-ROW COIL


Evaporator Air L/s
Temp (C)
3500
4700
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
22
20
16
22
20
16
22
TC
100.5 98.5 86.7 104.9 98.6 90.5 107.4
24
SHC
51.9 59.4 86.7
58.1 71.0 90.5
64.0
kW
22.37 22.22 21.34 22.69 22.23 21.63 22.88
TC
95.4 92.3 82.0 99.2 93.0 85.8 101.5
28
SHC 49.9 57.7 82.0 56.1 68.6 85.8
62.0
kW
24.32 23.96 22.78 24.77 24.05 23.22 25.02
TC
92.8 89.1 79.5 96.4 90.2 83.4 98.6
32
SHC 49.0 55.8 79.5 55.2 67.3 83.4 61.0
kW
25.59 25.09 23.80 26.08 25.24 24.32 26.37
TC
90.2 86.1 77.3 93.6 87.5 81.1 95.6
36
SHC 48.0 56.0 77.3 54.2 66.1 81.1 60.0
kW
26.91 25.25 24.85 27.45 26.57 25.46 27.77
TC
87.5 82.9 74.9 90.7 84.6 78.7 92.5
40
SHC 47.0 55.1 74.9 53.1 64.9 78.7 59.0
kW
28.16 27.41 26.10 26.68 27.68 26.72 28.98
TC
84.7 79.6 72.4 87.7 81.6 76.1 89.4
44
SHC 46.0 54.2 72.4 52.1 63.6 76.1 57.9
kW
29.38 28.32 26.80 29.99 28.72 27.59 30.35
TC
82.8 76.3 68.8 86.0 79.0 73.1 88.0
48
SHC 45.3 53.2 68.8 51.5 62.5 73.1 57.5
kW
30.70 29.30 27.66 31.40 29.87 28.60 31.83
TC
80.1 73.1 66.4 83.0 76.0 70.7 84.9
52
SHC 44.3 52.3 66.4 50.5 61.2 70.7 56.4
kW
31.95 30.27 28.65 32.65 30.98 29.69 33.11

4700
20
87.7
65.8
19.78
82.7
63.5
21.54
80.0
62.2
22.66
77.4
61.0
23.74
74.7
59.8
24.87
71.9
58.5
26.04
69.6
21.9
27.30

5900
20
93.5
75.4
20.24
88.0
72.9
22.20
85.1
71.6
23.42
82.2
70.3
24.59
79.2
69.0
25.82
76.2
67.7
26.96

7050
20
98.7
84.4
20.54
92.7
81.7
22.78
89.5
80.3
24.08
86.3
78.9
25.32
83.0
77.4
26.62
79.8
76.0
27.74

16
93.5
93.5
20.24
88.4
88.4
22.25
85.7
85.7
23.51
83.0
83.0
24.73
80.1
80.1
26.02
77.3
77.3
27.20

5900
20
101.6
78.9
22.45
95.9
76.4
24.38
93.0
75.1
25.62
90.2
73.9
26.91
87.3
72.6
28.12
84.2
71.2
29.28
82.0
70.3
30.53
79.0
68.9
31.70

16
93.8
93.8
21.87
89.1
89.1
23.59
86.6
86.6
24.76
84.3
84.3
25.97
81.9
81.9
27.24
79.3
79.3
28.25
76.8
76.8
29.39
74.3
74.3
30.56

3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCkW x 1000
Ldb C: hlwb = hewb
1.20 x L/s

Ldb C = Edb C

where hewb = enthalpy of air entering evaporator coil (kj/kg).


4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
piping sized to the outdoor unit field connections. (Equivalent length is equal
to the actual length plus a 50% allowance for fitting losses.) For other equivalent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

38AKS/40RM COMBINATION RATINGS STANDARD 3-ROW COIL SI (cont)


38AKS034/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air L/s
Temp (C)
4250
5650
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
22
20
16
22
20
16
22
TC
107.5 100.9 92.9 111.2 104.4 97.3 113.4
24
SHC
57.1 68.9 92.9
64.7 79.0 97.3
71.7
kW
22.89 22.40 21.81 23.16 22.66 22.13 23.33
TC
101.9 95.0 87.8 105.1 98.4 92.1 107.0
28
SHC
55.0 66.4 87.8
62.6 76.4 92.1
69.6
kW
25.07 24.27 23.44 25.44 24.66 23.94 25.66
TC
99.1 92.0 85.1 102.1 95.3 89.5 104.0
32
SHC 53.9 65.2 85.1
61.5 75.1 89.5
68.6
kW
26.44 25.48 24.56 26.85 25.94 25.14 27.10
TC
96.2 89.0 82.7 98.9 92.3 86.9 100.7
36
SHC 52.8 64.0 82.7 60.4 73.8 86.9
67.5
kW
27.87 26.73 25.71 28.31 27.25 26.39 28.59
TC
93.3 86.0 80.0 95.8 89.2 84.2 97.4
40
SHC 51.7 62.7 80.0 59.3 72.4 84.2 66.4
kW
29.10 27.91 26.94 29.51 28.44 27.63 29.78
TC
90.2 82.8 77.3 92.5 86.0 81.5 94.0
44
SHC 50.5 61.4 77.3 58.2 71.0 81.5 65.3
kW
30.52 28.98 27.82 31.00 29.64 28.70 31.31
TC
89.0 80.3 74.1 91.6 84.0 79.0 93.4
48
SHC 50.0 60.3 74.1 57.9 70.1 79.0 65.0
kW
32.05 30.15 28.82 32.61 30.96 29.88 32.99
TC

77.2 71.5

80.8 76.3

52
SHC

59.0 71.5

68.7 76.3

kW

31.25 29.88

32.12 31.04

Edb
Ewb
kW
Ldb
Lwb
SHC
TC

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.

7050
20
107.4
88.3
22.88
101.3
85.5
25.00
98.2
84.2
26.32
95.1
82.8
27.70
92.0
81.4
28.89
88.7
79.9
30.20
87.1
79.2
32.64
83.8
77.7
32.85

16
100.9
100.9
22.40
95.7
95.7
24.36
93.0
93.0
25.62
90.4
90.4
26.95
87.7
87.7
28.19
84.9
84.9
29.41
83.0
83.0
30.74
80.2
80.2
31.98

38AKS044/40RM034 WITH STANDARD 3-ROW COIL


Evaporator Air L/s
Temp (C)
4250
5650
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
22
20
16
22
20
16
22
TC
125.9 118.7 105.4 132.8 123.7 111.1 136.7
24
SHC
64.2 76.3 105.4 72.2 87.5 111.1 79.4
kW
29.60 29.04 28.01 30.14 29.43 28.45 30.44
TC
121.1 114.0 102.1 127.1 118.6 107.5 130.6
28
SHC
62.4 74.3 102.1 70.3 85.2 107.5 77.4
kW
32.30 31.50 30.16 32.98 32.02 30.77 33.36
TC
118.8 112.0 101.3 124.2 116.3 106.3 127.2
32
SHC
61.5 73.5 101.3 69.2 84.2 106.3 76.2
kW
33.92 32.94 31.41 34.68 33.55 32.13 35.12
TC
115.9 108.8 98.4 120.9 113.0 103.5 123.9
36
SHC
60.3 72.1 98.4
68.1 82.8 103.5 75.2
kW
35.55 34.43 32.81 36.35 35.10 33.61 36.81
TC
112.3 104.9 95.0 117.1 109.1 100.1 119.9
40
SHC
59.0 70.5 95.0
66.8 81.1 100.1 73.8
kW
37.31 36.03 34.35 38.13 36.75 35.22 38.61
TC
109.3 101.6 92.2 113.9 105.8 97.3 116.6
44
SHC
57.8 69.2 92.2
65.7 79.6 97.3
72.7
kW
38.86 37.43 35.68 39.71 38.21 36.63 40.21
TC
106.5 97.9 88.3 111.2 102.4 93.9 114.0
48
SHC
56.8 67.6 88.3
64.7 78.2 93.9
71.9
kW
40.58 38.61 36.43 41.64 39.64 37.69 42.28
TC
103.5 94.7 85.7 107.9 99.2 91.2 110.5
52
SHC
55.6 66.3 85.7
63.6 76.7 91.2
70.7
kW
42.27 40.10 37.87 43.34 41.19 39.22 43.99

7050
20
128.1
97.5
29.77
122.6
95.1
32.47
119.9
93.9
34.08
116.7
92.4
35.68
112.7
90.6
37.38
109.4
89.2
38.88
106.3
87.8
40.53
103.0
86.3
42.13

16
115.8
115.8
28.82
112.0
112.0
31.27
110.4
110.4
32.72
107.7
107.7
34.26
104.3
104.3
35.94
101.5
101.5
37.41
98.4
98.4
38.72
95.7
95.7
40.33

3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCkW x 1000
Ldb C: hlwb = hewb
1.20 x L/s

Ldb C = Edb C

where hewb = enthalpy of air entering evaporator coil (kj/kg).


4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
piping sized to the outdoor unit field connections. (Equivalent length is equal
to the actual length plus a 50% allowance for fitting losses.) For other equivalent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

27

Performance data (cont)


38AKS/40RM COMBINATION RATINGS STANDARD 3-ROW COIL ENGLISH
38AKS028/40RM024 WITH STANDARD 3-ROW COIL
Evaporator Air Cfm
Temp (F)
6,000
8,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
72
67
62
72
67
62
72
TC
276.7 254.2 231.0 289.4 267.4 245.0 297.0
85 SHC 139.7 174.3 221.2 156.4 201.3 245.0 171.3
kW
21.72 20.72 19.69 22.28 21.30 20.31 22.62
TC
265.3 244.1 222.8 276.9 256.1 236.3 283.6
95 SHC 135.3 170.1 214.1 151.9 196.6 236.3 166.5
kW
23.45 22.43 21.41 24.00 23.00 22.05 24.32
TC
259.0 238.0 217.3 270.4 249.7 230.7 276.7
100 SHC 132.9 167.6 209.2 149.5 193.8 230.7 164.1
kW
24.28 23.18 22.11 24.87 23.79 22.81 25.20
TC
253.0 232.6 212.8 263.8 243.7 226.0 269.7
105 SHC 130.6 165.4 205.4 147.1 191.3 226.0 161.6
kW
25.03 23.85 22.69 25.66 24.49 23.46 26.01
TC
240.9 222.0 204.1 250.7 231.9 216.6 255.6
115 SHC 126.0 161.1 197.7 142.4 186.3 216.6 156.7
kW
26.63 25.34 24.11 27.29 26.01 24.97 27.63
TC

210.5 193.6

219.8 206.1

125 SHC

156.4 188.6

181.2 206.1

kW

26.82 25.59

27.50 26.50

38AKS028/40RM028 WITH STANDARD 3-ROW COIL


Evaporator Air Cfm
Temp (F)
7,500
10,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
72
67
62
72
67
62
72
TC
298.5 274.6 252.4 310.3 286.1 267.8 316.9
85 SHC 157.1 200.0 247.5 177.6 232.2 267.8 197.3
kW
22.69 21.63 20.64 23.21 22.14 21.32 23.51
TC
285.4 262.5 242.8 296.2 273.1 257.5 302.0
95 SHC 152.2 195.1 238.6 172.6 226.9 257.5 192.3
kW
24.41 23.31 22.36 24.93 23.82 23.07 25.21
TC
278.8 255.7 236.9 289.3 266.2 251.7 294.9
100 SHC 149.8 192.4 233.2 170.2 224.0 251.7 190.0
kW
25.31 24.10 23.13 25.85 24.65 23.90 26.14
TC
271.9 249.3 231.7 281.9 259.3 246.2 287.1
105 SHC 147.3 189.8 228.5 167.6 221.2 246.2 187.4
kW
26.13 24.82 23.79 26.72 25.40 24.64 27.02
TC
258.1 236.6 221.4 267.2 245.8 235.3 271.6
115 SHC 142.2 184.7 219.0 162.4 215.6 235.3 182.2
kW
27.80 26.33 25.30 28.41 26.96 26.24 28.72
TC

224.0 210.2

224.3

125 SHC

179.5 208.8

224.3

kW

27.80 26.80

27.82

Edb
Ewb
kW
Ldb
Lwb
SHC
TC

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.

28

62
256.3
256.3
20.81
247.1
247.1
22.57
241.6
241.6
23.37
236.6
236.6
24.08
226.7
226.7
25.65
216.1
216.1
27.23

38AKS028/40RM034 WITH STANDARD 3-ROW COIL


Evaporator Air Cfm
Temp (F)
9,000
12,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
72
67
62
72
67
62
72
TC
317.8 291.3 271.9 328.5 302.8 289.0 334.2
85 SHC 172.3 224.7 268.2 199.4 261.6 289.0 221.4
kW
23.55 22.37 21.51 24.02 22.88 22.27 24.28
TC
302.9 277.5 260.7 312.6 288.1 277.0 317.6
95 SHC 166.7 219.2 258.0 194.0 255.7 277.0 215.9
kW
25.25 24.03 23.22 25.72 24.54 24.01 25.95
TC
295.9 270.3 254.3 305.4 280.8 270.7 310.1
100 SHC 164.0 216.4 252.3 191.5 252.8 270.7 213.4
kW
26.20 24.86 24.03 26.69 25.41 24.89 26.93
TC
288.2 263.1 248.3 297.1 273.2 264.4 301.5
105 SHC 161.1 213.5 246.8 188.7 249.7 264.4 210.5
kW
27.08 25.62 24.76 27.61 26.21 25.70 27.86
TC

248.9 236.5

258.1 251.7

115 SHC

207.9 236.1

243.6 251.7

kW

27.17 26.32

27.80 27.36

TC

224.6

125 SHC

224.5

kW

27.84

62
280.8
280.8
21.90
270.0
270.0
23.67
264.2
264.2
24.55
258.4
258.4
25.35
246.9
246.9
27.03

38AKS034/40RM028 WITH STANDARD 3-ROW COIL


Evaporator Air Cfm
Temp (F)
7,500
10,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
72
67
62
72
67
62
72
TC
322.9 298.4 272.1 336.1 311.1 287.8 344.0
85 SHC 166.0 209.6 265.5 186.7 242.5 287.8 206.3
kW
24.75 23.82 22.82 25.25 24.30 23.42 25.55
TC
310.6 286.4 262.1 323.0 298.4 277.7 330.3
95 SHC 161.5 204.7 256.4 182.1 237.3 277.6 201.8
kW
26.56 25.44 24.31 27.14 26.00 25.03 27.48
TC
304.2 279.9 256.5 316.5 291.8 272.1 323.5
100 SHC 159.1 202.1 251.2 179.8 234.5 272.1 199.5
kW
27.51 26.29 25.12 28.12 26.89 25.90 28.47
TC
297.9 274.0 251.9 309.6 285.5 267.2 316.2
105 SHC 156.8 199.7 247.0 177.4 231.9 267.2 197.1
kW
28.38 27.06 25.83 29.03 27.69 26.68 29.40
TC
284.2 260.6 204.7 295.2 271.5 255.9 301.2
115 SHC 151.8 194.4 236.7 172.3 226.2 255.9 192.1
kW
30.02 28.57 27.34 30.70 29.34 28.28 31.06
TC
271.2 247.3 229.1 281.7 257.8 244.4 287.2
125 SHC 147.0 189.0 226.1 167.6 220.6 244.4 187.4
kW
31.64 29.99 28.73 32.37 30.72 29.79 32.75

10,000
67
276.2
226.0
21.70
264.4
220.6
23.41
258.0
217.6
24.22
251.7
214.8
24.96
239.4
209.2
26.52

12,500
67
295.7
261.4
22.56
282.2
255.5
24.26
275.3
252.5
25.13
268.2
249.4
25.92
254.2
243.3
27.53

15,000
67
312.9
295.1
23.33
297.8
288.5
25.01
290.5
285.3
25.92
282.6
281.8
26.76

62
302.9
302.9
22.88
290.3
290.3
24.64
284.0
284.0
25.58
277.3
277.3
26.45
263.9
263.9
28.20

12,500
67
321.0
272.4
24.68
308.1
266.8
26.45
301.5
263.9
27.38
295.0
261.1
28.22
280.9
254.9
29.82
267.3
249.0
31.37

62
301.3
301.3
23.93
291.0
291.0
25.65
285.4
285.4
26.57
280.3
280.3
27.40
268.6
268.6
29.06
257.2
257.2
30.67

3. Formulas:
SHCBtuh
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCBtuh
Ldb F: hlwb = hewb
4.5 x cfm
Ldb F = Edb F

where hewb = enthalpy of air entering evaporator coil (Btuh/lb).


4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equivalent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

38AKS/40RM COMBINATION RATINGS STANDARD 3-ROW COIL ENGLISH (cont)


38AKS034/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air Cfm
Temp (F)
9,000
12,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
72
67
62
72
67
62
72
TC
344.6 317.4 294.0 256.9 330.1 311.5 363.8
85 SHC 182.5 235.1 288.2 209.0 272.7 311.5 231.3
kW
25.57 24.55 23.65 26.04 25.02 24.32 26.30
TC
331.0 304.2 282.8 342.5 316.2 300.1 348.8
95 SHC 177.3 229.8 278.1 204.1 267.1 300.1 226.3
kW
27.51 26.27 25.27 28.05 26.82 26.08 28.34
TC
324.3 297.3 276.8 335.5 309.2 294.1 341.6
100 SHC 174.8 227.1 272.6 201.7 264.2 294.1 223.9
kW
28.51 27.16 26.14 29.08 27.76 27.00 29.38
TC
317.1 290.6 271.3 327.8 302.1 288.4 333.5
105 SHC 172.0 224.4 267.7 199.1 261.4 288.4 221.2
kW
29.45 27.98 26.91 30.05 28.62 27.85 30.36
TC
302.2 276.0 258.9 312.1 286.9 275.7 317.2
115 SHC 166.4 218.6 256.4 193.8 255.2 275.6 215.7
kW
31.12 29.51 28.46 31.74 30.19 29.49 32.05
TC
288.3 261.8 246.5

272.5 263.3

125 SHC 161.1 213.0 245.1

249.4 263.3

kW
32.83 30.99 29.93

31.73 31.10

38AKS044/40RM034 WITH STANDARD 3-ROW COIL


Evaporator Air Cfm
Temp (F)
9,000
12,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
72
67
62
72
67
62
72
TC
413.7 382.6 344.5 432.1 399.8 364.9 443.5
85 SHC 208.7 260.9 334.0 234.4 300.7 364.9 257.8
kW
32.85 31.60 30.08 33.58 32.29 30.89 34.04
TC
399.2 368.7 333.6 416.4 384.9 353.6 426.9
95 SHC 203.2 255.4 324.2 229.1 294.7 353.6 252.3
kW
35.19 33.74 32.08 36.00 34.51 33.03 36.50
TC
391.8 361.5 328.0 408.3 377.3 347.7 418.3
100 SHC 200.4 252.5 319.0 226.4 291.7 347.7 249.4
kW
36.36 34.80 33.08 37.21 35.61 34.09 37.72
TC
384.2 354.1 322.2 400.1 369.5 341.7 409.6
105 SHC 197.5 249.6 313.8 223.6 288.5 341.7 246.5
kW
37.55 35.88 34.11 38.44 36.74 35.20 38.97
TC
368.5 339.0 310.2 383.1 353.5 329.2 391.7
115 SHC 191.5 243.6 302.9 217.8 282.1 329.2 240.6
kW
39.77 37.95 36.17 40.68 38.85 37.35 41.21
TC
352.6 323.3 297.2 366.4 337.2 316.0 374.3
125 SHC 185.5 237.4 291.1 212.2 275.5 316.0 234.8
kW
41.94 39.90 38.08 42.91 40.87 39.39 43.45

15,000
67
340.6
307.3
25.42
326.6
301.1
27.31
319.6
298.0
28.28
312.2
294.8
29.18
296.8
288.0
30.80
282.5
281.7
32.43

62
326.0
326.0
24.87
314.3
314.3
26.74
308.3
308.3
27.72
302.3
302.3
28.63
289.3
289.3
30.33
276.9
276.9
32.04

Edb
Ewb
kW
Ldb
Lwb
SHC
TC

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.
3. Formulas:
SHCBtuh
Ldb F = Edb F
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCBtuh
Ldb F: hlwb = hewb
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equivalent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

15,000
67
412.4
338.8
32.80
397.2
332.2
35.10
389.4
328.7
36.24
381.5
325.2
37.41
365.1
318.1
39.57
348.7
310.8
41.67

62
382.2
382.2
31.59
370.5
370.5
33.83
364.4
364.4
34.95
358.2
358.2
36.11
345.2
345.2
38.33
331.7
331.7
40.48

29

Performance data (cont)


38AKS/40RM COMBINATION RATINGS 4-ROW HIGH-CAPACITY COILS SI
38AKS028/40RM024 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air L/s
Temp (C)
2830
3780
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
17
19
22
17
19
22
17
TC
75.4 82.6 90.3 80.3 87.6 95.4 83.4
29
SHC 60.2 48.3 36.1 71.3 56.2 40.6 80.6
kW
21.83 22.91 24.02 22.58 23.64 24.76 23.05
TC
72.0 79.0 86.4 76.6 83.7 91.1 79.6
35
SHC 58.9 47.0 34.9 69.8 55.0 39.5 79.6
kW
23.31 24.51 25.75 24.13 25.32 26.55 24.63
TC
70.3 77.2 84.4 74.6 81.7 89.0 77.7
38
SHC 58.2 46.4 34.4 69.0 54.4 39.0 77.7
kW
24.04 25.28 26.58 24.85 26.12 27.40 25.39
TC
68.6 75.3 82.4 72.8 79.6 86.8 76.2
41
SHC 57.6 45.8 33.8 68.4 53.8 38.4 76.2
kW
24.80 26.11 27.46 25.62 26.96 28.31 26.27
TC
65.2 71.6 78.3 69.1 75.4 82.2 72.8
46
SHC 56.3 44.7 32.6 66.8 52.6 37.3 72.8
kW
26.26 27.68 29.15 27.11 28.52 29.99 27.95
38AKS028/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air L/s
Temp (C)
3540
4720
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
17
19
22
17
19
22
17
TC
77.1 84.3 91.7 81.3 88.3 95.8 85.2
29
SHC 67.1 53.1 38.5 78.8 62.1 43.8 85.2
kW
22.01 23.07 24.15 22.65 23.67 24.75 23.20
TC
73.7 80.4 87.6 77.5 84.2 91.4 81.8
35
SHC 65.8 51.8 37.4 77.5 60.9 42.8 81.8
kW
23.52 24.68 25.87 24.18 25.34 26.51 24.90
TC
71.9 78.6 85.5 75.7 82.1 89.2 80.1
38
SHC 65.1 51.3 36.9 75.7 60.3 42.3 80.1
kW
24.25 25.47 26.71 24.94 26.12 27.39 25.75
TC
70.2 76.6 83.4 74.1 80.0 86.8 78.3
41
SHC 64.4 50.7 36.3 74.1 59.7 41.7 78.3
kW
25.01 26.27 27.57 25.76 26.93 28.24 26.61
TC
66.5 72.7 79.1 70.8 75.7 82.2 74.7
46
SHC 63.0 49.5 35.3 70.8 58.5 40.7 74.7
kW
26.45 27.84 29.26 27.41 28.49 29.92 28.27
38AKS028/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air L/s
Temp (C)
4250
5660
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
17
19
22
17
19
22
17
TC
81.9 89.4 97.2 86.8 93.1 101.0 91.6
29
SHC 76.0 60.0 42.9 86.8 70.8
49.3 91.6
kW
22.84 23.92 25.03 23.51 24.46 25.57 24.21
TC
78.2 85.3 92.8 83.4 88.7 96.2 87.8
35
SHC 74.8 58.8 41.8 83.4 69.5 48.1 87.8
kW
24.40 25.59 26.84 25.26 26.15 27.39 25.98
TC
76.2 83.1 90.6 81.7 86.4 93.8 85.9
38
SHC 73.8 58.2 41.3 81.7 68.9 47.6 85.9
kW
25.14 26.38 27.70 26.10 26.97 28.27 26.84
TC
74.3 81.0 88.2 79.9 84.2 91.4 84.0
41
SHC 72.7 57.6 40.7 79.9 68.3 47.1 84.0
kW
25.92 27.22 28.58 26.99 27.83 29.18 27.77
TC
70.6 76.7 83.6 76.2 79.7 86.5 80.1
46
SHC 70.6 56.3 39.6 76.2 67.0 46.0 80.1
kW
27.44 28.82 30.28 28.68 29.46 30.91 29.54

Edb
Ewb
kW
Ldb
Lwb
SHC
TC

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.

30

22
98.8
45.0
25.26
94.1
44.0
27.05
91.8
43.4
27.92
89.5
42.9
28.81
84.7
41.7
30.52

38AKS034/40RM028 WITH 4-ROW HIGH-CAPACITY COILS


Evaporator Air L/s
Temp (C)
3540
4720
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
17
19
22
17
19
22
17
TC
82.0 89.5 97.4 86.3 93.9 101.8 89.9
29
SHC 69.0 54.8 40.1 81.1 63.7
45.3 89.9
kW
23.75 24.89 26.04 24.40 25.54 26.70 24.96
TC
78.5 85.7 93.3 82.7 89.8 97.4 86.5
35
SHC 67.6 53.5 39.0 79.6 62.5 44.2 86.5
kW
25.19 26.45 27.75 25.93 27.17 28.43 26.59
TC
76.7 83.8 91.1 80.8 87.8 95.2 84.8
38
SHC 66.9 52.9 38.4 78.7 62.0 43.7 84.8
kW
25.88 27.20 28.55 26.67 27.94 29.27 27.39
TC
74.9 81.8 88.9 78.7 85.6 92.9 83.0
41
SHC 66.3 52.3 37.8 78.7 61.4 43.1 83.0
kW
26.61 27.98 29.38 27.39 28.74 30.13 28.22
TC
71.2 77.7 84.5 75.0 81.2 88.2 79.4
46
SHC 64.9 51.0 36.7 75.0 60.1 42.1 79.4
kW
27.99 29.48 31.00 28.88 30.27 31.81 29.86

22
98.6
48.9
25.15
93.8
47.9
26.92
91.4
47.4
27.77
89.0
46.8
28.65
84.2
45.7
30.35

38AKS034/40RM034 WITH 4-ROW HIGH-CAPACITY COILS


Evaporator Air L/s
Temp (C)
4250
5660
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
17
19
22
17
19
22
17
TC
87.2 95.0 103.1 91.6 99.2 107.4 96.6
29
SHC 78.5 61.7
44.4 91.6 72.5
50.8 96.6
kW
24.55 25.70 26.90 25.21 26.34 27.53 25.95
TC
83.4 90.9 98.7 88.1 94.7 102.6 93.0
35
SHC 76.9 60.5 43.3 88.1 71.3
49.7 93.0
kW
26.07 27.35 28.66 26.87 27.99 29.32 27.72
TC
81.5 88.9 96.5 86.4 92.5 100.2 91.1
38
SHC 76.2 59.9 42.7 86.4 70.6
49.1 91.1
kW
26.88 28.15 29.51 27.69 28.80 30.17 28.56
TC
79.6 86.7 94.2 84.6 90.1 97.7 89.1
41
SHC 75.4 59.3 42.1 84.6 70.0 48.6 89.1
kW
27.57 28.97 30.40 28.55 29.63 31.06 29.42
TC
75.5 82.2 89.5 81.0 85.4 92.6 85.1
46
SHC 73.5 58.0 41.0 81.0 68.7 47.4 85.1
kW
28.99 30.49 32.08 30.21 31.18 32.75 31.11

22
103.4
55.3
25.92
98.5
54.3
27.76
96.0
53.7
28.66
93.5
53.2
29.59
88.4
52.1
31.32

38AKS044/40RM034 WITH 4-ROW HIGH-CAPACITY COILS


Evaporator Air L/s
Temp (C)
4250
5660
Air Entering
Condenser
Evaporator Air Ewb (C)
(Edb)
17
19
22
17
19
22
17
TC
101.8 110.9 120.4 107.5 116.6 126.2 111.3
29
SHC
84.1 66.8 49.1 99.1 77.7 55.4 111.3
kW
33.03 34.90 36.81 34.20 36.06 38.02 34.97
TC
97.8 106.5 115.7 102.9 111.7 120.9 107.1
35
SHC 82.6
65.4 47.8 97.1 76.2 54.1 107.1
kW
34.80 36.76 38.83 35.94 37.95 40.03 36.90
TC
95.8 104.3 113.2 100.7 109.3 118.2 105.2
38
SHC 81.8
64.7 47.2 96.2 75.5 53.4 105.2
kW
35.71 37.74 39.87 36.87 38.91 41.05 37.96
TC
93.7 102.1 110.8 98.6 106.8 115.5 103.1
41
SHC 81.0
64.0 46.5 95.2
74.8 52.8 103.1
kW
36.56 38.69 40.89 37.78 39.85 42.05 38.93
TC
89.4 97.3 105.6 93.8 101.7 109.9 98.8
46
SHC 79.4 62.5
45.1 93.8
73.3 51.4 98.8
kW
38.19 40.43 42.74 39.46 41.63 43.95 40.85

4720
19
90.9
63.7
24.14
86.6
62.5
25.80
84.4
61.9
26.60
82.2
61.2
27.46
77.8
60.0
29.06

5900
19
91.0
70.6
24.06
86.6
69.4
25.71
84.4
68.7
26.52
82.1
68.1
27.34
77.7
66.8
28.94

7080
19
95.6
80.7
24.82
91.0
79.4
26.54
88.7
78.7
27.38
86.3
77.9
28.24
81.5
76.4
29.85

5900
19
96.9
72.3
25.98
92.6
71.1
27.65
90.4
70.5
28.43
88.1
69.8
29.23
83.4
68.5
30.76

22
104.8
50.4
27.15
100.2
49.3
28.90
97.8
48.8
29.76
95.4
48.3
30.63
90.4
47.1
32.29

7080
19
101.8
82.6
26.72
97.2
81.2
28.39
94.8
80.6
29.21
92.4
79.9
30.06
87.6
78.4
31.66

22
110.0
56.8
27.91
105.1
55.7
29.73
102.6
55.2
30.58
100.0
54.6
31.49
94.8
53.5
33.21

7080
19
120.2
87.8
36.77
115.1
86.4
38.70
112.5
85.7
39.69
109.9
85.0
40.65
104.6
83.5
42.46

22
129.9
61.4
38.73
124.3
60.1
40.79
121.4
59.5
41.83
118.6
58.8
42.84
112.8
57.5
44.79

3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCkW x 1000
Ldb C: hlwb = hewb
1.20 x L/s

Ldb C = Edb C

where hewb = enthalpy of air entering evaporator coil (kj/kg).


4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
piping sized to the outdoor unit field connections. (Equivalent length is equal
to the actual length plus a 50% allowance for fitting losses.) For other equivalent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

38AKS/40RM COMBINATION RATINGS 4-ROW HIGH-CAPACITY COILS ENGLISH


38AKS028/40RM024 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air Cfm
Temp (F)
6,000
8,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
62
67
72
62
67
72
62
TC
257.4 282.2 308.4 274.1 299.2 325.8 284.9
85
SHC 205.5 164.8 123.1 243.4 191.9 138.8 275.4
kW
21.83 22.91 24.02 22.58 23.64 24.76 23.05
TC
245.9 269.7 295.2 261.5 285.8 311.3 272.0
95
SHC 201.1 160.7 119.4 238.5 188.0 135.0 272.0
kW
23.31 24.51 25.75 24.13 25.32 26.55 24.63
TC
240.1 263.5 288.4 254.7 278.9 303.9 265.3
100
SHC 198.8 158.6 117.4 235.6 185.9 133.2 265.3
kW
24.04 25.28 26.58 24.85 26.12 27.40 25.39
TC
234.4 257.2 281.4 248.5 271.8 296.3 260.1
105
SHC 196.7 156.6 115.5 233.7 183.9 131.2 260.1
kW
24.80 26.11 27.46 25.62 26.96 28.31 26.27
TC
222.7 244.6 267.5 235.9 257.4 280.9 248.8
115
SHC 192.3 152.5 111.5 228.2 179.7 127.5 248.8
kW
26.26 27.68 29.15 27.11 28.52 29.99 27.95
38AKS028/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air Cfm
Temp (F)
7,500
10,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
62
67
72
62
67
72
62
TC
263.5 287.8 313.2 277.6 301.7 327.2 290.9
85
SHC 229.3 181.2 131.6 269.1 212.1 149.7 290.9
kW
22.01 23.07 24.15 22.65 23.67 24.75 23.20
TC
251.6 274.7 299.0 264.8 287.7 312.1 279.3
95
SHC 224.7 177.1 127.8 264.8 208.0 146.1 279.3
kW
23.52 24.68 25.87 24.18 25.34 26.51 24.90
TC
245.7 268.3 292.0 258.5 280.4 304.7 273.5
100
SHC 222.5 175.1 126.0 258.5 206.1 144.4 273.5
kW
24.25 25.47 26.71 24.94 26.12 27.39 25.75
TC
239.6 261.6 284.7 253.0 273.0 296.6 267.5
105
SHC 220.0 173.1 124.1 253.0 204.1 142.6 267.5
kW
25.01 26.27 27.57 25.76 26.93 28.24 26.61
TC
227.1 248.2 270.3 241.9 258.4 280.7 255.1
115
SHC 215.1 169.0 120.5 241.9 199.8 138.9 255.1
kW
26.45 27.84 29.26 27.41 28.49 29.92 28.27
38AKS028/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air Cfm
Temp (F)
9,000
12,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
62
67
72
62
67
72
62
TC
279.7 305.5 332.1 296.4 318.0 345.0 312.8
85
SHC 259.7 204.9 146.4 296.4 241.8 168.3 312.8
kW
22.84 23.92 25.03 23.51 24.46 25.57 24.21
TC
267.2 291.2 317.0 284.9 302.8 328.6 299.8
95
SHC 255.4 200.8 142.6 284.9 237.5 164.4 299.8
kW
24.40 25.59 26.84 25.26 26.15 27.39 25.98
TC
260.4 284.0 309.4 278.9 295.1 320.4 293.4
100
SHC 252.0 198.9 140.9 278.9 235.3 162.6 293.4
kW
25.14 26.38 27.70 26.10 26.97 28.27 26.84
TC
253.7 276.7 301.3 272.8 287.5 312.1 286.8
105
SHC 248.4 196.7 139.0 272.8 233.2 160.9 286.8
kW
25.92 27.22 28.58 26.99 27.83 29.18 27.77
TC
241.1 262.0 285.5 260.3 272.1 295.5 273.6
115
SHC 241.1 192.4 135.2 260.3 228.8 157.2 273.6
kW
27.44 28.82 30.28 28.68 29.46 30.91 29.54

Edb
Ewb
kW
Ldb
Lwb
SHC
TC

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

1. Direct interpolation is permissible. Do not extrapolate.


2. SHC is based on 80 F db air entering indoor coil.

72
337.3
153.8
25.26
321.5
150.2
27.05
313.7
148.3
27.92
305.5
146.4
28.81
289.4
142.6
30.52

38AKS034/40RM028 WITH 4-ROW HIGH-CAPACITY COILS


Evaporator Air Cfm
Temp (F)
7,500
10,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
62
67
72
62
67
72
62
TC
280.1 305.6 332.5 294.8 320.8 347.7 307.1
85
SHC 235.6 187.1 137.0 276.9 217.7 154.8 307.1
kW
23.75 24.89 26.04 24.40 25.54 26.70 24.96
TC
267.9 292.7 318.7 282.5 306.8 332.7 295.4
95
SHC 230.9 182.8 133.3 271.9 213.6 151.0 295.4
kW
25.19 26.45 27.75 25.93 27.17 28.43 26.59
TC
261.8 286.0 311.1 276.0 299.7 325.0 289.5
100
SHC 228.6 180.6 131.1 268.8 211.6 149.2 289.5
kW
25.88 27.20 28.55 26.67 27.94 29.27 27.39
TC
255.7 279.2 303.7 268.8 292.5 317.1 283.4
105
SHC 226.3 178.5 129.1 268.8 209.5 147.4 283.4
kW
26.61 27.98 29.38 27.39 28.74 30.13 28.22
TC
243.0 265.3 288.7 256.2 277.4 301.1 271.0
115
SHC 221.5 174.2 125.2 256.2 205.3 143.6 271.0
kW
27.99 29.48 31.00 28.88 30.27 31.81 29.86

72
336.6
167.2
25.15
320.4
163.5
26.92
312.3
161.7
27.77
304.1
159.7
28.65
287.7
156.2
30.35

38AKS034/40RM034 WITH 4-ROW HIGH-CAPACITY COILS


Evaporator Air Cfm
Temp (F)
9,000
12,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
62
67
72
62
67
72
62
TC
297.9 324.3 352.1 312.9 338.8 366.7 330.1
85
SHC 267.9 210.7 151.5 312.9 247.8 173.3 330.1
kW
24.55 25.70 26.90 25.21 26.34 27.53 25.95
TC
284.9 310.5 337.1 300.9 323.5 350.5 317.7
95
SHC 262.5 206.5 147.7 300.9 243.5 169.7 317.7
kW
26.07 27.35 28.66 26.87 27.99 29.32 27.72
TC
278.3 303.5 329.5 295.0 315.7 342.2 311.0
100
SHC 260.2 204.5 145.9 295.0 241.3 167.8 311.0
kW
26.81 28.15 29.51 27.69 28.80 30.17 28.56
TC
271.7 296.2 321.7 289.0 307.8 333.7 304.3
105
SHC 257.6 202.4 143.9 289.0 239.1 165.8 304.3
kW
27.57 28.97 30.40 28.55 29.63 31.06 29.42
TC
257.9 280.9 305.5 276.5 291.8 316.4 290.6
115
SHC 251.0 198.0 139.9 276.5 234.5 161.9 290.6
kW
28.99 30.49 32.08 30.21 31.18 32.75 31.11

72
353.3
189.0
25.92
336.3
185.4
27.76
327.9
183.6
28.66
319.3
181.8
29.59
301.9
177.9
31.32

38AKS044/40RM034 WITH 4-ROW HIGH-CAPACITY COILS


Evaporator Air Cfm
Temp (F)
9,000
12,000
Air Entering
Condenser
Evaporator Air Ewb (F)
(Edb)
62
67
72
62
67
72
62
TC
347.6 378.8 411.3 367.0 398.3 431.0 380.2
85
SHC 287.1 228.1 167.7 338.3 265.2 189.3 380.2
kW
33.03 34.90 36.81 34.20 36.06 38.02 34.97
TC
334.0 363.8 395.1 351.4 381.6 412.9 365.8
95
SHC 282.2 223.4 163.4 331.7 260.3 184.7 365.8
kW
34.80 36.76 38.83 35.94 37.95 40.03 36.90
TC
327.2 356.3 386.8 344.0 373.1 403.6 359.2
100
SHC 279.4 221.0 161.2 328.7 257.8 182.5 359.2
kW
35.71 37.74 39.87 36.87 38.91 41.05 37.96
TC
319.9 348.7 378.4 336.6 364.6 394.3 352.0
105
SHC 276.5 218.5 159.0 325.2 255.4 180.2 352.0
kW
36.56 38.69 40.89 37.78 39.85 42.05 38.93
TC
305.3 332.4 360.5 320.5 347.2 375.3 337.6
115
SHC 271.1 213.5 153.9 320.5 250.4 175.6 337.6
kW
38.19 40.43 42.74 39.46 41.63 43.95 40.85

10,000
67
310.4
217.4
24.14
295.7
213.4
25.80
288.3
211.4
26.60
280.8
209.2
27.46
265.9
204.9
29.06

12,500
67
310.7
241.2
24.06
295.6
236.9
25.71
288.1
234.7
26.52
280.4
232.5
27.34
265.3
228.1
28.94

15,000
67
326.3
275.6
24.82
310.6
271.3
26.54
302.8
268.8
27.38
294.6
266.0
28.24
278.4
260.8
29.85

12,500
67
331.0
246.9
25.98
316.4
242.9
27.65
308.7
240.7
28.43
300.9
238.5
29.23
285.0
234.0
30.76

72
357.9
172.1
27.15
342.2
168.4
28.90
334.2
166.7
29.76
325.8
164.8
30.63
308.7
160.8
32.29

15,000
67
347.7
282.1
26.72
331.8
277.4
28.39
323.8
275.1
29.21
315.7
272.9
30.06
299.1
267.7
31.66

72
375.8
194.1
27.91
358.8
190.2
29.73
350.3
188.5
30.58
341.5
186.6
31.49
323.6
182.7
33.21

15,000
67
410.6
300.0
36.77
393.1
295.2
38.70
384.3
292.8
39.69
375.4
290.3
40.65
357.2
285.1
42.46

72
443.5
209.8
38.73
424.4
205.3
40.79
414.8
203.2
41.83
405.0
201.0
42.84
385.3
196.5
44.79

3. Formulas:
SHCBtuh
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCBtuh
Ldb F: hlwb = hewb
4.5 x cfm

Ldb F = Edb F

where hewb = enthalpy of air entering evaporator coil (Btuh/lb).


4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equivalent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

31

Performance data (cont)


38AH CONDENSING UNIT RATINGS SI
38AH034

38AH024
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

6
4
2
0
2
4
6
8
10

24
42.9
11.3
35.2
47.0
11.5
35.2
51.4
11.7
35.2
55.5
11.9
35.6
59.9
12.1
36.2
64.3
12.3
36.9
69.2
12.5
37.7
74.1
12.8
38.5
78.9
13.0
39.2

Air Temperature Entering Condenser (C)


28
32
36
40
44
48
40.6 38.0 35.6 33.0 30.6 28.2
11.6 12.1 12.6 13.0 13.4 13.7
39.2 43.2 47.1 51.1 55.2 59.2
44.6 41.8 39.2 36.6 34.0 31.4
11.9 12.5 13.0 13.5 13.9 14.3
39.2 43.2 47.2 51.2 55.2 59.2
48.6 45.8 43.0 40.2 37.4 34.8
12.1 12.8 13.4 14.0 14.5 15.0
39.2 43.2 47.2 51.2 55.2 59.2
52.8 49.8 47.0 44.0 41.2 38.4
12.4 13.1 13.8 14.5 15.0 15.6
39.6 43.5 47.4 51.3 55.3 59.2
57.0 54.0 51.0 48.2 45.2 42.2
12.7 13.5 14.2 14.9 15.5 16.1
40.1 43.9 47.8 51.6 55.5 59.3
61.4 58.2 55.2 52.2 49.0 46.0
13.0 13.8 14.6 15.4 16.0 16.7
40.7 44.4 48.1 51.9 55.6 59.4
66.0 62.8 59.6 56.4 53.2 50.0
13.3 14.1 15.0 15.8 16.5 17.3
41.4 45.1 48.8 52.4 56.2 59.9
70.8 67.4 64.0 60.8 57.4 54.0
13.6 14.5 15.4 16.3 17.1 17.8
42.1 45.8 49.4 53.1 56.8 60.4
75.6 72.0 68.6 65.2 61.6 58.2
13.8 14.8 15.8 16.7 17.6 18.4
42.9 46.5 50.1 53.8 57.4 61.0

52
25.7
14.2
63.2
28.8
14.9
63.2
31.8
15.6
63.2
35.5
16.3
63.2
39.3
16.9
63.2
42.9
17.5
63.1
46.8
18.1
63.6
50.7
18.8
64.1
54.7
19.4
64.7

38AH028
SST
(C)
6
4
2
0
2
4
6
8
10

32

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

24
51.1
13.4
35.4
55.2
13.8
36.0
59.7
14.1
36.5
64.5
14.4
37.1
69.3
14.7
37.8
74.0
15.0
38.8
79.4
15.3
39.6
85.0
15.7
40.5
90.6
16.0
41.5

Air Temperature Entering Condenser (C)


28
32
36
40
44
48
48.6 46.0 43.4 40.8 38.4 36.0
14.0 14.7 15.3 15.9 16.5 17.1
39.3 43.3 47.3 51.2 55.2 59.1
52.8 50.0 47.4 44.8 42.2 39.6
14.3 15.1 15.8 16.5 17.1 17.7
39.8 43.7 47.6 51.4 55.3 59.2
57.0 54.2 51.4 48.6 46.0 43.2
14.7 15.5 16.3 17.0 17.7 18.3
40.3 44.1 47.8 51.6 55.5 59.3
61.6 58.6 55.6 52.8 49.8 47.0
15.1 15.9 16.8 17.5 18.3 19.0
40.9 44.6 48.4 52.1 55.9 59.6
66.2 63.2 60.0 57.0 54.0 51.0
15.5 16.4 17.3 18.1 18.9 19.7
41.7 45.3 49.0 52.7 56.5 60.2
71.0 67.6 64.4 61.2 58.0 54.8
15.9 16.8 17.8 18.7 19.5 20.4
42.4 46.1 49.7 53.4 57.1 60.7
76.2 72.6 69.2 65.8 62.4 59.2
16.3 17.3 18.3 19.2 20.2 21.0
43.3 46.9 50.5 54.1 57.8 61.4
81.6 77.8 74.2 70.6 67.0 63.4
16.6 17.7 18.8 19.8 20.8 21.8
44.1 47.7 51.3 54.9 58.5 62.2
86.8 83.0 79.0 75.2 71.6 67.8
17.0 18.2 19.3 20.4 21.4 22.4
45.0 48.6 52.1 55.7 59.3 62.9

52
33.3
17.7
63.1
37.0
18.4
63.0
40.5
19.1
63.1
43.9
19.8
63.4
47.9
20.6
64.0
51.6
21.3
64.4
55.6
22.2
65.1
59.8
22.9
65.7
64.0
23.6
66.4

SST
(C)
6
4
2
0
2
4
6
8
10

kW
SDT
SST
TC

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Air Temperature Entering Condenser (C)


24
28
32
36
40
44
48
59.8
57.1 54.0 51.1 48.1 45.3 42.4
16.6
17.3 18.1 18.9 19.7 20.4 21.0
35.9
40.0 43.9 47.9 51.9 55.9 59.9
65.5
62.2 59.2 56.0 52.9 49.8 46.8
17.0
17.7 18.6 19.5 20.3 21.0 21.8
36.1
40.1 44.0 48.0 51.9 55.9 59.9
70.8
67.5 64.2 60.8 57.5 54.3 51.0
17.3
18.1 19.1 20.0 21.0 21.7 22.6
36.2
40.3 44.1 48.1 52.0 56.0 59.9
76.4
73.0 69.5 66.0 62.5 59.1 55.7
17.6
18.6 19.5 20.6 21.6 22.5 23.4
36.8
40.7 44.5 48.4 52.2 56.1 60.1
82.2
78.7 75.0 71.4 67.7 64.2 60.6
18.0
19.0 20.1 21.2 22.2 23.2 24.1
37.5
41.3 45.1 48.8 52.7 56.4 60.3
88.0
84.3 80.5 76.8 72.9 69.2 65.5
18.4
19.5 20.7 21.8 22.9 24.0 24.9
38.2
42.0 45.6 49.3 53.0 56.8 60.5
94.4
90.4 86.5 82.4 78.5 74.6 70.6
18.9
20.0 21.2 22.5 23.6 24.7 25.8
39.0
42.8 46.4 50.0 53.7 57.4 61.1
100.8
96.7 92.5 88.2 84.1 80.0 75.8
19.4
20.5 21.8 23.1 24.3 25.5 26.6
39.9
43.7 47.2 50.8 54.5 58.1 61.7
107.3 102.9 98.6 94.1 89.7 85.5 81.1
19.6
20.9 22.3 23.7 25.1 26.3 27.5
40.9
44.5 48.1 51.7 55.3 58.9 62.4

52
39.5
21.8
63.8
43.5
22.7
63.8
47.7
23.5
63.9
52.2
24.5
63.8
57.0
25.3
64.0
61.7
26.2
64.2
66.7
27.1
64.8
71.7
28.0
65.4
76.8
29.0
66.0

LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (C)
Saturated Suction Temperature
Gross Cooling Capacity (kW)

NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.

38AH CONDENSING UNIT CIRCUIT RATINGS SI


38AH024 CIRCUIT NO. 1 OR 2
Air Temperature Entering Condenser (C)
SST
(C)
24
28
32
36
40
44
48
TC
21.5 20.3 19.0 17.8 16.5 15.3 14.1
6
kW
5.6
5.8
6.1
6.3
6.5
6.7
6.9
SDT 35.2 39.2 43.2 47.1 51.1 55.2 59.2
TC
23.5 22.3 20.9 19.6 18.3 17.0 15.7
4
kW
5.7
5.9
6.2
6.5
6.8
7.0
7.2
SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.2
TC
25.7 24.3 22.9 21.5 20.1 18.7 17.4
2
kW
5.8
6.1
6.4
6.7
7.0
7.3
7.5
SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.2
TC
27.8 26.4 24.9 23.5 22.0 20.6 19.2
0
kW
5.9
6.2
6.6
6.9
7.2
7.5
7.8
SDT 35.6 39.6 43.5 47.4 51.3 55.3 59.2
TC
29.9 28.5 27.0 25.5 24.1 22.6 21.1
2
kW
6.1
6.4
6.7
7.1
7.5
7.8
8.1
SDT 36.2 40.1 43.9 47.8 51.6 55.5 59.3
TC
32.2 30.7 29.1 27.6 26.1 24.5 23.0
4
kW
6.2
6.5
6.9
7.3
7.7
8.0
8.4
SDT 36.9 40.7 44.4 48.1 51.9 55.6 59.4
TC
34.6 33.0 31.4 29.8 28.2 26.6 25.0
6
kW
6.3
6.6
7.1
7.5
7.9
8.3
8.6
SDT 37.7 41.4 45.1 48.8 52.4 56.2 59.9
TC
37.0 35.4 33.7 32.0 30.4 28.7 27.0
8
kW
6.4
6.8
7.2
7.7
8.1
8.5
8.9
SDT 38.5 42.1 45.8 49.4 53.1 56.8 60.4
TC
39.5 37.8 36.0 34.3 32.6 30.8 29.1
10
kW
6.5
6.9
7.4
7.9
8.4
8.8
9.2
SDT 39.2 42.9 46.5 50.1 53.8 57.4 61.0
38AH028 CIRCUIT NO. 1 OR 2
Air Temperature Entering Condenser (C)
SST
(C)
24
28
32
36
40
44
48
TC
25.5 24.3 23.0 21.7 20.4 19.2 18.0
6
kW
6.7
7.0
7.3
7.7
8.0
8.3
8.5
SDT 35.4 39.3 43.3 47.3 51.2 55.2 59.1
TC
27.6 26.4 25.0 23.7 22.4 21.1 19.8
4
kW
6.9
7.2
7.5
7.9
8.2
8.5
8.9
SDT 36.0 39.8 43.7 47.6 51.4 55.3 59.2
TC
29.8 28.5 27.1 25.7 24.3 23.0 21.6
2
kW
7.0
7.4
7.8
8.1
8.5
8.8
9.2
SDT 36.5 40.3 44.1 47.8 51.6 55.5 59.3
TC
32.2 30.8 29.3 27.8 26.4 24.9 23.5
0
kW
7.2
7.6
8.0
8.4
8.8
9.1
9.5
SDT 37.1 40.9 44.6 48.4 52.1 55.9 59.6
TC
34.7 33.1 31.6 30.0 28.5 27.0 25.5
2
kW
7.4
7.8
8.2
8.6
9.1
9.5
9.8
SDT 37.8 41.7 45.3 49.0 52.7 56.5 60.2
TC
37.0 35.5 33.8 32.2 30.6 29.0 27.4
4
kW
7.5
7.9
8.4
8.9
9.3
9.8 10.2
SDT 38.8 42.4 46.1 49.7 53.4 57.1 60.7
TC
39.7 38.1 36.3 34.6 32.9 31.2 29.6
6
kW
7.7
8.1
8.6
9.2
9.6 10.1 10.5
SDT 39.6 43.3 46.9 50.5 54.1 57.8 61.4
TC
42.5 40.8 38.9 37.1 35.3 33.5 31.7
8
kW
7.8
8.3
8.9
9.4
9.9 10.4 10.9
SDT 40.5 44.1 47.7 51.3 54.9 58.5 62.2
TC
45.3 43.4 41.5 39.5 37.6 35.8 33.9
10
kW
8.0
8.5
9.1
9.7 10.2 10.7 11.2
SDT 41.5 45.0 48.6 52.1 55.7 59.3 62.9
kW
SDT
SST
TC

LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (C)
Saturated Suction Temperature
Gross Cooling Capacity (kW)

52
12.8
7.1
63.2
14.4
7.5
63.2
15.9
7.8
63.2
17.7
8.2
63.2
19.7
8.5
63.2
21.4
8.8
63.1
23.4
9.1
63.6
25.4
9.4
64.1
27.3
9.7
64.7

38AH034 CIRCUIT NO. 1


Air Temperature Entering Condenser (C)
SST
(C)
24
28
32
36
40
44
48
TC
25.0 23.7 22.3 21.0 19.6 18.3 17.0
6
kW
6.7
7.0
7.3
7.7
8.0
8.3
8.5
SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.3
TC
27.5 26.0 24.6 23.1 21.7 20.3 18.9
4
kW
6.8
7.1
7.5
7.9
8.2
8.5
8.9
SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.3
TC
29.9 28.4 26.8 25.2 23.7 22.2 20.7
2
kW
6.9
7.2
7.7
8.1
8.5
8.8
9.2
SDT 35.1 39.2 43.2 47.3 51.3 55.3 59.3
TC
32.4 30.8 29.2 27.6 25.9 24.4 22.8
0
kW
7.0
7.4
7.8
8.3
8.7
9.1
9.5
SDT 35.5 39.5 43.4 47.4 51.3 55.3 59.3
TC
35.0 33.4 31.7 30.0 28.3 26.7 25.0
2
kW
7.1
7.5
8.0
8.5
8.9
9.3
9.7
SDT 36.1 39.9 43.8 47.6 51.5 55.3 59.2
TC
37.7 35.9 34.2 32.5 30.7 29.0 27.3
4
kW
7.2
7.7
8.2
8.7
9.1
9.6 10.0
SDT 36.6 40.4 44.1 47.8 51.6 55.4 59.2
TC
40.6 38.7 36.9 35.0 33.2 31.4 29.6
6
kW
7.3
7.8
8.3
8.9
9.4
9.8 10.3
SDT 37.2 41.1 44.7 48.4 52.1 55.9 59.6
TC
43.5 41.5 39.6 37.6 35.7 33.8 31.9
8
kW
7.5
8.0
8.5
9.1
9.6 10.1 10.6
SDT 38.2 41.9 45.5 49.1 52.8 56.5 60.1
TC
46.3 44.3 42.3 40.2 38.2 36.3 34.3
10
kW
7.6
8.1
8.7
9.3
9.9 10.4 10.9
SDT 39.1 42.7 46.3 49.9 53.5 57.1 60.7

52
15.6
8.9
63.2
17.4
9.2
63.2
19.1
9.6
63.4
21.2
9.9
63.2
23.4
10.2
63.0
25.5
10.5
62.9
27.7
10.9
63.4
29.9
11.2
63.8
32.3
11.5
64.3

52
16.7
8.9
63.1
18.5
9.2
63.0
20.3
9.5
63.1
22.0
9.9
63.4
23.9
10.3
64.0
25.8
10.7
64.4
27.8
11.1
65.1
29.9
11.4
65.7
32.0
11.8
66.4

38AH034 CIRCUIT NO. 2


Air Temperature Entering Condenser (C)
SST
(C)
24
28
32
36
40
44
48
TC
34.8 33.4 31.7 30.1 28.5 27.0 25.4
6
kW
9.9 10.3 10.8 11.2 11.7 12.1 12.5
SDT 36.7 40.7 44.6 48.6 52.6 56.5 60.5
TC
38.0 36.2 34.6 32.9 31.2 29.5 27.9
4
kW
10.2 10.6 11.1 11.6 12.1 12.5 12.9
SDT 36.9 41.0 44.8 48.7 52.6 56.6 60.5
TC
40.9 39.1 37.4 35.6 33.8 32.1 30.3
2
kW
10.4 10.9 11.4 11.9 12.5 12.9 13.4
SDT 37.3 41.3 45.0 48.8 52.7 56.6 60.5
TC
44.0 42.2 40.3 38.4 36.6 34.7 32.9
0
kW
10.6 11.2 11.7 12.3 12.9 13.4 13.9
SDT 38.1 41.8 45.6 49.3 53.1 56.9 60.8
TC
47.2 45.3 43.3 41.4 39.4 37.5 35.6
2
kW
10.9 11.5 12.1 12.7 13.3 13.9 14.4
SDT 38.8 42.7 46.3 50.0 53.8 57.5 61.3
TC
50.4 48.4 46.3 44.3 42.2 40.2 38.2
4
kW
11.2 11.8 12.5 13.1 13.8 14.4 14.9
SDT 39.8 43.5 47.1 50.8 54.4 58.1 61.8
TC
53.9 51.7 49.6 47.4 45.3 43.2 41.0
6
kW
11.6 12.2 12.9 13.6 14.2 14.9 15.5
SDT 40.7 44.4 48.0 51.6 55.2 58.9 62.5
TC
57.4 55.2 52.9 50.6 48.4 46.2 43.9
8
kW
11.9 12.5 13.3 14.0 14.7 15.4 16.0
SDT 41.7 45.4 48.9 52.5 56.1 59.7 63.3
TC
61.0 58.6 56.3 53.9 51.5 49.2 46.8
10
kW
12.1 12.8 13.6 14.4 15.2 15.9 16.6
SDT 42.8 46.3 49.9 53.4 57.0 60.6 64.1

52
23.9
13.0
64.4
26.1
13.4
64.5
28.6
13.9
64.3
31.0
14.5
64.4
33.6
15.1
65.0
36.1
15.7
65.4
38.9
16.2
66.2
41.7
16.8
66.9
44.5
17.4
67.7

NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.

33

Performance data (cont)


38AH CONDENSING UNIT RATINGS ENGLISH
38AH034

38AH024
SST
(F)
20
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Air Temperature Entering Condenser (F)


75
85
95
100
105
115
125
141.8 130.6 119.0 113.2 107.4
96.2
84.8
11.4
11.7
12.4
12.7
12.9 13.3
13.8
95.0 105.0 115.0 120.0 125.0 135.0 145.0
161.6 149.4 136.8 130.6 124.4 112.0
99.6
11.7
12.1
12.9
13.3
13.6
14.2
14.8
95.0 105.0 115.0 120.0 125.0 135.0 145.0
181.6 168.2 154.8 148.0 141.4 128.0 114.6
11.9
12.5
13.5
13.9
14.3
15.0
15.8
95.0 105.0 115.0 120.0 125.0 135.0 145.0
202.4 188.4 174.4 167.4 160.4 146.4 132.4
12.2
12.9
14.0
14.5
14.9
15.8
16.6
97.0 107.0 116.0 121.0 126.0 135.0 145.0
223.0 208.0 194.0 186.8 179.6 165.0 150.5
12.5
13.4
14.5
15.0
15.6
16.5
17.5
98.0 108.0 117.0 122.0 126.0 136.0 146.0
247.6 232.0 216.0 208.0 200.0 184.4 168.6
12.8
13.8
15.0
15.6
16.2
17.3
18.4
101.0 110.0 119.0 123.0 128.0 137.0 146.0
268.0 254.0 236.0 228.0 220.0 204.0 188.0
13.1
14.2
15.6
16.2
16.8
18.0
19.3
103.0 112.0 121.0 125.0 130.0 139.0 148.0

38AH028
SST
(F)
20
25
30
35
40
45
50

34

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

75
168.4
13.5
95.0
189.0
13.9
97.0
210.2
14.3
98.0
231.6
14.8
99.0
256.8
15.1
102.0
284.0
15.7
104.0
306.0
16.0
106.0

Air Temperature Entering Condenser (F)


85
95
100
105
115
125
157.6 145.6 139.8 134.0 122.8 111.4
14.1
15.0
15.4
15.8
16.6
17.4
105.0 115.0 120.0 125.0 135.0 145.0
177.4 164.6 158.4 152.2 140.2 128.0
14.6
15.7
16.1
16.6
17.4
18.3
106.0 116.0 121.0 126.0 135.0 145.0
197.4 183.8 177.2 170.6 157.4 144.2
15.2
16.3
16.8
17.3
18.3
19.3
107.0 117.0 121.0 126.0 136.0 146.0
220.0 204.0 197.6 190.4 176.4 162.6
15.7
17.0
17.6
18.1
19.2
20.3
109.0 118.0 123.0 128.0 137.0 147.0
242.0 226.0 218.0 210.0 195.2 179.8
16.3
17.7
18.3
18.9
20.2
21.5
111.0 120.0 125.0 129.0 138.0 147.0
266.0 250.0 242.0 232.0 216.0 199.0
16.9
18.3
19.0
19.7
21.0
22.3
113.0 122.0 127.0 131.0 140.0 149.0
292.0 272.0 264.0 256.0 238.0 221.0
17.4
19.0
19.8
20.6
22.0
23.5
115.0 124.0 129.0 133.0 142.0 151.0

SST
(F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

20
25
30
35
40
45
50

kW
SDT
SST
TC

75
198.0
16.6
97.0
223.5
17.1
97.0
249.4
17.6
97.0
276.2
18.0
99.0
304.5
18.7
101.0
335.0
19.3
103.0
367.0
19.7
106.0

Air Temperature Entering Condenser (F)


85
95
100
105
115
125
185.5 171.2 164.4 157.6 144.4 131.0
17.4
18.5
19.0
19.5
20.4
21.4
107.0 117.0 122.0 127.0 137.0 147.0
209.4 194.4 187.0 179.6 165.3 150.8
18.1
19.3
19.8
20.5
21.5
22.6
107.0 117.0 122.0 127.0 137.0 147.0
234.3 217.7 210.0 202.3 186.0 170.2
18.7
20.1
20.7
21.3
22.5
23.8
107.0 117.0 122.0 127.0 137.0 147.0
260.0 243.0 235.5 226.5 209.8 193.2
19.4
20.8
21.5
22.2
23.6
25.0
109.0 118.0 123.0 128.0 137.0 147.0
287.0 269.0 260.0 251.0 233.5 215.8
20.0
21.7
22.4
23.2
24.7
26.2
110.0 119.0 124.0 129.0 138.0 147.0
316.0 297.0 287.0 278.0 259.0 240.0
20.7
22.6
23.3
24.2
25.8
27.4
112.0 121.0 126.0 130.0 140.0 149.0
346.0 325.0 314.0 305.0 283.0 262.0
21.4
23.4
24.3
25.2
27.0
28.8
115.0 124.0 128.0 133.0 141.0 150.0

LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature
Gross Cooling Capacity (1000 Btuh)

NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.

38AH CONDENSING UNIT CIRCUIT RATINGS ENGLISH


38AH024 CIRCUIT NO. 1 OR 2
Air Temperature Entering Condenser (F)
SST
(F)
75
85
95
100
105
115
125
TC
70.9
65.3
59.5
56.6
53.7
48.1
42.4
kW
5.7
5.9
6.2
6.3
6.5
6.7
6.9
20
SDT
95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC
80.8
74.7
68.4
65.3
62.2
56.0
49.8
25
kW
5.8
6.1
6.5
6.7
6.8
7.1
7.4
SDT
95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC
90.8
84.1
77.4
74.0
70.7
64.0
57.3
30
kW
6.0
6.3
6.7
7.0
7.2
7.5
7.9
SDT
95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC
101.2
94.2
87.2
83.7
80.2
73.2
66.2
35
kW
6.1
6.5
7.0
7.2
7.5
7.9
8.3
SDT
97.0 107.0 116.0 121.0 126.0 135.0 145.0
TC
111.5 104.0
97.0
93.4
89.8
82.5
75.3
40
kW
6.3
6.7
7.3
7.5
7.8
8.3
8.8
SDT
98.0 108.0 117.0 122.0 126.0 136.0 146.0
TC
123.8 116.0 108.0 104.0 100.0
92.2
84.3
45
kW
6.4
6.9
7.5
7.8
8.1
8.6
9.2
SDT 101.0 110.0 119.0 123.0 128.0 137.0 146.0
TC
134.0 127.0 118.0 114.0 110.0 102.0
94.0
50
kW
6.6
7.1
7.8
8.1
8.4
9.0
9.6
SDT 103.0 112.0 121.0 125.0 130.0 139.0 148.0

38AH034 CIRCUIT NO. 1


Air Temperature Entering Condenser (F)
SST
(F)
75
85
95
100
105
115
125
TC
82.4
76.5
70.2
67.1
64.0
58.0
51.9
20
kW
6.7
7.0
7.5
7.7
7.9
8.3
8.7
SDT
95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC
93.8
87.4
80.4
77.0
73.6
67.0
60.3
25
kW
6.9
7.3
7.8
8.0
8.3
8.7
9.2
SDT
95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC
105.4
98.3
90.7
87.0
83.3
76.0
68.7
30
kW
7.0
7.5
8.1
8.4
8.6
9.1
9.7
SDT
95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC
117.2 110.0 102.0
98.5
94.5
86.8
79.2
35
kW
7.1
7.7
8.3
8.6
8.9
9.5
10.1
SDT
97.0 106.0 116.0 121.0 126.0 135.0 145.0
TC
130.5 122.0 114.0 110.0 106.0
97.5
89.3
40
kW
7.3
7.9
8.6
8.9
9.2
9.9
10.5
SDT
97.0 107.0 116.0 121.0 126.0 135.0 145.0
TC
145.0 135.0 127.0 122.0 118.0 109.0 100.0
45
kW
7.4
8.1
8.9
9.2
9.6
10.3
11.0
SDT
99.0 109.0 118.0 123.0 127.0 137.0 147.0
TC
158.0 149.0 139.0 134.0 130.0 120.0 110.5
50
kW
7.6
8.3
9.2
9.5
9.9
10.7
11.5
SDT 102.0 111.0 120.0 125.0 129.0 138.0 147.0

38AH028 CIRCUIT NO. 1 OR 2


Air Temperature Entering Condenser (F)
SST
(F)
75
85
95
100
105
115
125
TC
84.2
78.8
72.8
69.9
67.0
61.4
55.7
20
kW
6.7
7.0
7.5
7.7
7.9
8.3
8.7
SDT
95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC
94.5
88.7
82.3
79.2
76.1
70.1
64.0
25
kW
6.9
7.3
7.8
8.1
8.3
8.7
9.2
SDT
97.0 106.0 116.0 121.0 126.0 135.0 145.0
TC
105.1
98.7
91.9
88.6
85.3
78.7
72.1
30
kW
7.2
7.6
8.2
8.4
8.7
9.2
9.7
SDT
98.0 107.0 117.0 121.0 126.0 136.0 146.0
TC
115.8 110.0 102.0
98.8
95.2
88.2
81.3
35
kW
7.4
7.9
8.5
8.8
9.1
9.6
10.2
SDT
99.0 109.0 118.0 123.0 128.0 137.0 147.0
TC
128.4 121.0 113.0 109.0 105.0
97.6
89.9
40
kW
7.6
8.2
8.8
9.2
9.5
10.1
10.7
SDT 102.0 111.0 120.0 125.0 129.0 138.0 147.0
TC
142.0 133.0 125.0 121.0 116.0 108.0
99.5
45
kW
7.8
8.4
9.2
9.5
9.9
10.5
11.2
SDT 104.0 113.0 122.0 127.0 131.0 140.0 149.0
TC
153.0 146.0 136.0 132.0 128.0 119.0 110.5
50
kW
8.0
8.7
9.5
9.9
10.3
11.0
11.8
SDT 106.0 115.0 124.0 129.0 133.0 142.0 151.0

38AH034 CIRCUIT NO. 2


Air Temperature Entering Condenser (F)
SST
(F)
75
85
95
100
105
115
125
TC
115.6 109.0 101.0
97.3
93.6
86.4
79.1
20
kW
9.9
10.4
11.0
11.3
11.6
12.1
12.7
SDT
98.0 108.0 118.0 123.0 128.0 138.0 148.0
129.7 122.0 114.0 110.0 106.0
98.3
90.5
TC
25
kW
10.2
10.8
11.5
11.8
12.2
12.8
13.5
SDT
98.0 108.0 118.0 123.0 128.0 138.0 148.0
TC
144.0 136.0 127.0 123.0 119.0 110.0 101.5
30
kW
10.6
11.2
12.0
12.3
12.7
13.4
14.1
SDT
98.0 109.0 118.0 123.0 128.0 138.0 148.0
TC
159.0 150.0 141.0 137.0 132.0 123.0 114.0
35
kW
10.9
11.7
12.5
12.9
13.3
14.1
14.9
SDT 101.0 111.0 120.0 125.0 129.0 139.0 149.0
TC
174.0 165.0 155.0 150.0 145.0 136.0 126.5
40
kW
11.4
12.1
13.1
13.5
14.0
14.8
15.7
SDT 104.0 113.0 122.0 127.0 131.0 140.0 149.0
TC
190.0 181.0 170.0 165.0 160.0 150.0 140.0
45
kW
11.9
12.6
13.7
14.1
14.6
15.5
16.4
SDT 106.0 115.0 124.0 129.0 133.0 142.0 151.0
TC
209.0 197.0 186.0 180.0 175.0 163.0 151.5
50
kW
12.1
13.1
14.2
14.8
15.3
16.3
17.4
SDT 110.0 118.0 127.0 131.0 136.0 144.0 153.0

LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature
Gross Cooling Capacity (1000 Btuh)

NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.

kW
SDT
SST
TC

35

Performance data (cont)


38AH/40RM COMBINATION RATINGS STANDARD 3-ROW COIL SI
38AH024 AND 40RM016 WITH STANDARD 3-ROW COIL
Temp (C)
Evaporator Air L/s
Air
2100
2800
Entering
Evaporator Air Ewb (C)
Condenser
22
20
16
22
20
16
22
(Edb)
TC
63.9 59.4 53.2 67.3 62.9 56.9 69.8
24 SHC
32.7 37.7 53.2 36.4 43.2 56.9 40.1
kW
12.18 11.90 11.52 12.39 12.11 11.75 12.54
TC
62.2 57.6 51.7 65.4 61.0 55.3 67.8
28 SHC
32.0 36.9 51.7 35.7 42.4 55.3 39.4
kW
13.06 12.78 12.40 13.26 12.99 12.63 13.41
TC
60.4 56.0 50.3 63.5 59.2 53.7 65.8
32 SHC
31.4 36.2 50.3 35.0 41.5 53.7 38.7
kW
13.89 13.51 13.01 14.16 13.79 13.31 14.36
TC
58.6 54.2 48.8 61.5 57.3 52.1 63.7
36 SHC
30.7 35.4 48.8 34.2 40.6 52.1 38.0
kW
14.91 14.51 14.02 15.17 14.79 14.32 15.37
TC
56.7 52.3 47.0 59.5 55.2 50.3 61.7
40 SHC
30.0 34.6 47.0 33.5 39.7 50.3 37.3
kW
15.84 15.34 14.74 16.15 15.67 15.10 16.40
TC
54.8 50.5 45.5 57.3 53.2 48.6 59.5
44 SHC
29.2 33.8 45.5 32.8 38.8 48.6 36.5
kW
16.73 16.11 15.40 17.09 16.50 15.84 17.40
TC
52.8 48.6 43.8 55.1 51.1 46.8 57.2
48 SHC
28.5 32.9 43.8 32.0 37.8 46.8 35.7
kW
17.72 17.09 16.38 18.07 17.47 16.82 18.39
TC
50.8 46.6 42.1 53.0 49.0 44.9 55.0
52 SHC
27.7 32.1 42.1 31.2 36.9 44.9 35.0
kW
18.71 18.07 17.37 19.05 18.44 17.81 19.37
38AH024 AND 40RM024 WITH STANDARD 3-ROW COIL
Temp (C)
Evaporator Air L/s
Air
2900
3800
Entering
Evaporator Air Ewb (C)
Condenser
22
20
16
22
20
16
22
(Edb)
TC
71.3 66.0 59.9 74.4 68.9 63.5 76.4
24 SHC
38.0 45.1 59.9 43.1 52.1 63.5 47.6
kW
12.63 12.31 11.93 12.82 12.48 12.15 12.94
TC
69.2 64.0 58.1 72.2 66.9 61.7 74.1
28 SHC
37.2 44.3 58.1 42.3 51.2 61.7 46.8
kW
13.50 13.18 12.81 13.69 13.35 13.03 13.81
TC
67.1 62.0 56.4 69.9 64.7 59.9 71.7
32 SHC
36.3 43.5 56.4 41.5 50.2 59.9 45.9
kW
14.48 14.03 13.55 14.72 14.27 13.84 14.87
TC
65.0 59.9 54.7 67.5 62.5 58.0 69.2
36 SHC
35.5 42.6 54.7 40.6 49.2 58.0 45.1
kW
15.49 15.03 14.55 15.72 15.27 14.86 15.87
TC
62.9 57.8 52.7 65.4 60.4 56.1 67.0
40 SHC
34.7 41.8 52.7 39.8 48.3 56.1 44.3
kW
16.54 15.96 15.38 16.82 16.26 15.76 17.00
TC
60.6 55.6 50.9 62.9 58.1 54.1 64.4
44 SHC
33.8 40.9 50.9 39.0 47.3 54.1 43.4
kW
17.56 16.84 16.17 17.89 17.20 16.63 18.10
TC
58.2 53.4 48.9 60.4 55.8 52.1 61.8
48 SHC
32.8 40.0 48.9 38.0 46.2 52.1 42.5
kW
18.54 17.80 17.14 18.86 18.17 17.61 19.07
TC
56.0 51.1 46.9 58.0 53.5 50.0 59.3
52 SHC
31.9 39.0 46.9 37.2 45.2 50.0 41.6
kW
19.51 18.76 18.12 19.82 19.12 18.60 20.02

16
59.2
59.2
11.89
57.6
57.6
12.77
56.0
56.0
13.51
54.4
54.4
14.52
52.5
52.5
15.36
50.8
50.8
16.16
49.0
49.0
17.15
47.1
47.1
18.14

38AH024 AND 40RM028 WITH STANDARD 3-ROW COIL


Temp (C)
Evaporator Air L/s
Air
3500
4700
Entering
Evaporator Air Ewb (C)
Condenser
22
20
16
22
20
16
22
(Edb)
TC
77.3 70.6 65.0 79.7 73.4 68.9 81.2
24 SHC
43.2 51.6 65.0 49.3 60.1 68.9 55.2
kW
13.00 12.58 12.24 13.14 12.76 12.48 13.24
TC
75.1 68.1 63.1 77.4 71.1 67.0 78.8
28 SHC
42.4 50.9 63.1 48.5 59.1 67.0 54.4
kW
13.87 13.43 13.12 14.01 13.62 13.36 14.10
TC
72.8 65.5 61.1 74.8 68.7 65.0 76.1
32 SHC
41.5 50.2 61.1 47.6 58.1 65.0 53.5
kW
14.97 14.34 13.96 15.15 14.62 14.29 15.26
TC
70.4 62.9 59.1 72.2 66.3 62.9 73.4
36 SHC
40.6 49.5 59.1 46.7 57.0 62.9 52.5
kW
15.98 15.30 14.96 16.15 15.61 15.30 16.26
TC
68.3 60.4 57.1 69.9 64.0 60.9 71.1
40 SHC
39.9 48.8 57.1 45.9 56.0 60.9 51.8
kW
17.15 16.25 15.88 17.34 16.66 16.31 17.47
TC
65.8 57.7 55.0 67.2 61.4 58.7 68.3
44 SHC
38.9 48.0 55.0 44.9 54.9 58.7 50.8
kW
18.30 17.14 16.76 18.50 17.67 17.28 18.65
TC
63.2 55.0 52.8 64.4 58.8 56.4 65.4
48 SHC
38.0 47.2 52.8 43.9 53.8 56.4 49.8
kW
19.28 18.04 17.72 19.46 18.62 18.26 19.60
TC
60.8 52.3 50.7 61.8 56.3 54.2 62.7
52 SHC
37.1 46.5 50.7 43.0 52.7 54.2 48.9
kW
20.25 18.94 18.69 20.41 19.55 19.24 20.54

16
66.3
66.3
12.32
64.5
64.5
13.20
62.6
62.6
14.08
60.7
60.7
15.10
58.7
58.7
16.06
56.7
56.7
17.00
54.6
54.6
17.99
52.5
52.5
18.97

38AH028 AND 40RM024 WITH STANDARD 3-ROW COIL


Temp (C)
Evaporator Air L/s
Air
2900
3800
Entering
Evaporator Air Ewb (C)
Condenser
22
20
16
22
20
16
22
(Edb)
TC
77.4 71.9 64.7 81.1 75.1 68.6 83.5
24 SHC
40.4 47.5 64.7 45.5 54.9 68.6 50.1
kW
15.16 14.77 14.25 15.42 14.99 14.53 15.59
TC
75.6 70.1 63.2 79.1 73.2 67.0 81.3
28 SHC
39.7 46.8 63.2 44.8 54.0 67.0 49.3
kW
16.26 15.96 15.58 16.46 16.14 15.79 16.59
TC
73.4 68.1 61.6 76.7 71.1 65.3 78.8
32 SHC
38.8 45.9 61.6 43.9 53.1 65.3 48.4
kW
17.36 16.95 16.44 17.62 17.18 16.72 17.79
TC
71.3 66.0 59.8 74.4 68.9 63.4 76.4
36 SHC
38.0 45.1 59.8 43.1 52.1 63.4 47.6
kW
18.51 17.98 17.36 18.82 18.27 17.72 19.02
TC
69.1 63.9 58.0 72.1 66.7 61.5 74.0
40 SHC
37.1 44.2 58.0 42.2 51.1 61.5 46.7
kW
19.61 18.96 18.23 19.98 19.32 18.67 20.22
TC
66.9 61.7 56.2 69.6 64.5 59.6 71.4
44 SHC
36.2 43.4 56.2 41.4 50.1 59.6 45.8
kW
20.78 20.11 19.39 21.15 20.47 19.84 21.38
TC
64.7 59.6 54.4 67.3 62.3 57.8 68.9
48 SHC
35.4 42.5 54.4 40.5 49.1 57.8 45.0
kW
21.75 21.06 20.35 22.10 21.42 20.80 22.33
TC
62.0 57.2 52.4 64.3 59.6 55.6 65.7
52 SHC
34.3 41.5 52.4 39.4 47.9 55.6 43.9
kW
23.63 22.55 21.49 24.15 23.10 22.20 24.48

3500
20
64.9
48.3
12.24
63.0
47.3
13.11
61.1
46.3
13.95
59.1
45.3
14.96
57.1
44.3
15.88
55.0
43.2
16.76
52.9
42.1
17.73
50.7
41.0
18.70

4700
20
71.3
58.3
12.63
69.2
57.3
13.50
66.9
56.2
14.46
64.6
55.2
15.46
62.4
54.2
16.49
60.0
53.1
17.47
57.5
21.9
18.43
55.1
50.8
19.38

LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.

36

5900
20
76.1
67.6
12.92
73.7
66.6
13.78
71.2
65.5
14.83
68.7
64.3
15.83
66.4
63.3
16.94
63.7
62.1
18.00
61.0
60.9
18.95
58.4
58.1
19.89

16
72.2
72.2
12.68
70.2
70.2
13.56
68.1
68.1
14.56
66.0
66.0
15.58
64.0
64.0
16.66
61.7
61.7
17.72
59.4
59.4
18.71
57.1
57.1
19.69

4700
20
77.9
61.3
15.20
75.9
60.4
16.28
73.6
59.3
17.38
71.4
58.3
18.52
69.0
57.2
19.60
66.7
56.1
20.76
64.3
21.9
21.70
61.5
53.7
23.52

16
71.6
71.6
14.75
70.0
70.0
15.96
68.2
68.2
16.95
66.3
66.3
18.01
64.3
64.3
19.02
62.4
62.4
20.19
60.4
60.4
21.17
58.1
58.1
22.76

5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb

hldb = hedb

total capacity (kW)


1.20 x 10-3 x (L/s)

where hewb = enthalpy of air entering evaporator coil (kJ/kg).


6. Combination ratings are based on a 1.1 C line loss. For a close-coupled system (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe
Sizes table are based on 1.1 C line loss.

38AH/40RM COMBINATION RATINGS STANDARD 3-ROW COIL SI (cont)


38AH028 AND 40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air L/s
Temp (C)
Air
3500
4700
Entering
Evaporator Air Ewb (C)
Condenser
22
20
16
22
20
16
22
(Edb)
TC
84.1 78.3 70.6 87.3 80.6 74.8 89.3
24 SHC
45.8 53.8 70.6 52.0 63.2 74.8 57.9
kW
15.64 15.22 14.67 15.87 15.39 14.97 16.01
TC
82.1 75.9 68.9 85.0 78.4 73.0 86.9
28 SHC
45.0 53.1 68.9 51.2 62.3 73.0 57.1
kW
16.63 16.28 15.89 16.79 16.42 16.12 16.89
TC
79.6 73.2 67.0 82.3 75.9 70.9 83.9
32 SHC
44.1 52.3 67.0 50.2 61.2 70.9 56.1
kW
17.85 17.35 16.86 18.06 17.56 17.17 18.19
TC
77.4 70.6 65.0 79.9 73.5 68.9 81.4
36 SHC
43.3 51.6 65.0 49.4 60.1 68.9 55.2
kW
19.12 18.44 17.88 19.37 18.73 18.27 19.52
TC
75.0 67.9 63.0 77.2 71.0 66.8 78.7
40 SHC
42.4 50.9 63.0 48.4 59.1 66.8 54.3
kW
20.35 19.46 18.84 20.63 19.85 19.33 20.81
TC
72.5 65.2 60.9 74.5 68.5 64.7 75.9
44 SHC
41.4 50.1 60.9 47.5 58.0 64.7 53.4
kW
21.52 20.56 20.00 21.78 20.99 20.50 21.96
TC
70.1 62.6 58.9 71.9 66.0 62.6 73.1
48 SHC
40.6 49.4 58.9 46.6 56.9 62.6 52.4
kW
22.49 21.46 20.96 22.73 21.92 21.47 22.90
TC
67.0 59.4 56.5 68.5 62.9 60.1 69.5
52 SHC
39.4 48.5 56.5 45.4 55.6 60.1 51.2
kW
24.77 23.07 22.41 25.10 23.84 23.21 25.33
38AH028 AND 40RM034 WITH STANDARD 3-ROW COIL
Temp (C)
Evaporator Air L/s
Air
4250
5650
Entering
Evaporator Air Ewb (C)
Condenser
22
20
16
22
20
16
22
(Edb)
TC
90.2 81.9 75.9 92.7 85.5 80.5 94.4
24 SHC
50.5 61.0 75.9 58.3 70.8 80.5 65.4
kW
16.07 15.48 15.05 16.25 15.73 15.38 16.37
TC
87.8 79.6 73.9 90.2 83.1 78.5 91.7
28 SHC
49.6 60.0 73.9 57.4 69.7 78.5 64.5
kW
16.95 16.49 16.17 17.08 16.68 16.43 17.16
TC
85.0 76.9 71.7 87.1 80.2 76.1 88.5
32 SHC
48.5 58.9 71.7 56.3 68.4 76.1 63.4
kW
18.27 17.64 17.23 18.43 17.89 17.58 18.55
TC
82.5 74.4 69.5 84.4 77.6 73.9 85.8
36 SHC
47.6 57.9 69.5 55.4 67.3 73.9 62.5
kW
19.63 18.82 18.33 19.82 19.14 18.77 19.96
TC
79.9 71.7 67.3 81.5 74.9 71.6 82.7
40 SHC
46.5 56.8 67.3 54.4 66.1 71.6 61.5
kW
20.96 19.94 19.38 21.17 20.33 19.92 21.32
TC
77.1 69.0 65.0 78.6 72.1 69.2 79.7
44 SHC
45.5 55.6 65.0 53.3 64.9 69.2 60.5
kW
22.12 21.07 20.53 22.31 21.46 21.08 22.45
TC
74.4 66.4 62.7 75.7 69.4 66.8 76.7
48 SHC
44.4 54.6 62.7 52.3 63.7 66.8 59.5
kW
23.08 21.99 21.48 23.25 22.39 22.04 23.38
TC
70.9 63.2 60.0 71.8 65.9 63.8 72.6
52 SHC
43.1 53.2 60.0 51.0 62.2 63.8 58.2
kW
25.63 23.91 23.19 25.85 24.51 24.05 26.03

16
78.2
78.2
15.22
76.4
76.4
16.31
74.3
74.3
17.43
72.2
72.2
18.60
70.1
70.1
19.74
67.9
67.9
20.92
65.7
65.7
21.89
63.0
63.0
23.87

38AH034 AND 40RM028 WITH STANDARD 3-ROW COIL


Evaporator Air L/s
Temp (C)
Air
35000
4700
Entering
Evaporator Air Ewb (C)
Condenser
22
20
16
22
20
16
22
(Edb)
TC
93.1 88.9 78.1 97.3 90.2 82.5 99.8
24 SHC
49.1 56.8 78.1 55.5 67.3 82.5 61.4
kW
18.80 18.47 17.63 19.13 18.57 17.97 19.32
TC
90.8 86.1 76.1 94.8 87.7 80.4 97.2
28 SHC
48.2 56.0 76.1 54.6 66.2 80.4 60.5
kW
20.03 19.66 18.86 20.35 19.79 19.21 20.54
TC
88.5 83.4 74.2 92.2 85.3 78.5 94.4
32 SHC
47.4 55.2 74.2 53.7 65.2 78.5 59.6
kW
21.40 20.89 19.97 21.77 21.08 20.40 21.99
TC
86.0 80.5 72.1 89.4 82.6 76.4 91.5
36 SHC
46.5 54.4 72.1 52.7 64.0 76.4 58.6
kW
22.88 22.30 21.44 23.23 22.52 21.87 23.44
TC
83.6 77.6 70.1 86.7 80.0 74.2 88.7
40 SHC
45.6 53.6 70.1 51.8 62.9 74.2 57.7
kW
24.24 23.49 22.55 24.63 23.79 23.07 24.87
TC
81.1 74.7 67.9 84.0 77.3 72.1 85.8
44 SHC
44.6 52.8 67.9 50.8 61.8 72.1 56.7
kW
25.66 24.72 23.71 26.09 25.11 24.32 26.35
TC
78.4 71.7 65.7 80.9 74.5 69.8 82.6
48 SHC
43.6 51.9 65.7 49.7 60.6 69.8 55.6
kW
27.17 25.99 24.94 27.62 26.49 25.65 27.91
TC
75.8 68.7 63.4 78.2 71.8 67.4 79.7
52 SHC
42.7 51.1 63.4 48.8 59.4 67.4 54.7
kW
28.74 27.45 26.51 29.16 28.01 27.23 29.44

16
84.3
84.3
15.63
82.2
82.2
16.63
79.7
79.7
17.86
77.5
77.5
19.13
75.1
75.1
20.36
72.6
72.6
21.53
70.1
70.1
22.49
67.0
67.0
24.76

38AH034 AND 40RM034 WITH STANDARD 3-ROW COIL


Temp (C)
Evaporator Air L/s
Air
4250
5650
Entering
Evaporator Air Ewb (C)
Condenser
22
20
16
22
20
16
22
(Edb)
TC
100.3 92.2 84.4 103.9 96.2 89.4 106.2
24 SHC
54.4 65.3 84.4 62.2 75.4 89.4 69.3
kW
19.36 18.73 18.12 19.65 19.04 18.51 19.82
TC
97.8 89.6 82.1 101.2 93.4 87.1 103.3
28 SHC
53.4 64.2 82.1 61.2 74.2 87.1 68.3
kW
20.59 19.93 19.34 20.86 20.24 19.74 21.02
TC
95.1 86.9 80.0 98.2 90.7 84.8 100.1
32 SHC
52.4 63.1 80.0 60.2 73.0 84.8 67.3
kW
22.06 21.24 20.55 22.37 21.62 21.03 22.56
TC
92.3 84.1 77.6 95.1 87.7 82.4 96.9
36 SHC
51.3 61.9 77.6 59.1 71.7 82.4 66.2
kW
23.53 22.67 22.01 23.82 23.05 22.50 24.00
TC
89.6 81.3 75.3 92.1 84.8 80.0 93.8
40 SHC
50.3 60.7 75.3 58.1 70.5 80.0 65.2
kW
24.99 23.95 23.20 25.30 24.39 23.78 25.51
TC
86.8 78.5 72.9 89.1 81.9 77.5 90.6
44 SHC
49.2 59.6 72.9 57.0 69.2 77.5 64.1
kW
26.50 25.28 24.45 26.84 25.78 25.13 27.07
TC
83.7 75.5 70.4 85.6 78.7 74.9 87.0
48 SHC
48.0 58.3 70.4 55.8 67.8 74.9 62.9
kW
28.11 26.66 25.77 28.45 27.24 26.55 28.70
TC
80.9 72.6 67.9 82.6 75.8 72.3 83.9
52 SHC
46.9 57.1 67.9 54.7 66.5 72.3 61.9
kW
29.65 28.16 27.31 29.97 28.74 28.11 30.20

5900
20
83.5
70.9
15.60
81.3
69.9
16.58
78.6
68.7
17.77
76.2
67.7
19.00
73.6
66.5
20.18
71.0
65.3
21.32
68.4
64.2
22.25
65.1
62.8
24.34

7050
20
88.5
79.8
15.95
86.0
78.7
16.84
82.9
77.4
18.11
80.3
76.2
19.41
77.5
74.9
20.66
74.6
73.6
21.79
71.8
72.4
22.72
68.1
68.1
25.02

LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.

5900
20
93.5
75.3
18.83
90.9
74.2
20.04
88.3
73.1
21.38
85.6
71.9
22.83
82.9
70.7
24.15
80.2
69.5
25.53
77.2
68.1
26.97
74.5
66.9
28.50

16
86.2
86.2
18.26
84.1
84.1
19.50
82.1
82.1
20.76
79.9
79.9
22.24
77.7
77.7
23.50
75.5
75.5
24.83
73.1
73.1
26.24
70.7
70.7
27.83

7050
20
99.5
84.8
19.30
96.7
83.5
20.50
93.8
82.2
21.93
90.8
80.9
23.37
87.8
79.5
24.77
84.8
78.2
26.21
81.5
76.7
27.72
78.5
75.4
29.22

16
93.4
93.4
18.82
91.1
91.1
20.06
88.8
88.8
21.43
86.2
86.2
22.90
83.8
83.8
24.26
81.2
81.2
25.68
78.5
78.5
27.19
75.9
75.9
28.75

5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb

hldb = hedb

total capacity (kW)


1.20 x 10-3 x (L/s)

where hewb = enthalpy of air entering evaporator coil (kJ/kg).


6. Combination ratings are based on a 1.1 C line loss. For a close-coupled system (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe
Sizes table are based on 1.1 C line loss.

37

Performance data (cont)


38AH/40RM COMBINATION RATINGS STANDARD 3-ROW COIL ENGLISH
38AH024 AND 40RM016 WITH STANDARD 3-ROW COIL
Temp (F)
Evaporator Air Cfm
Air
4500
6000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
211.3 191.6 173.6 221.7 203.6 186.3 229.2
85 SHC 106.1 131.1 166.6 118.5 151.3 186.3 130.3
kW
13.46 13.13 12.83 13.63 13.33 13.04 13.75
TC
202.6 184.4 167.6 211.9 195.4 179.6 218.9
95 SHC 103.0 127.9 161.4 114.9 147.4 179.6 126.6
kW
14.70 14.28 13.90 14.91 14.53 14.17 15.06
TC
198.0 180.5 164.3 206.8 191.0 175.8 213.5
100 SHC 101.4 126.1 158.5 112.9 145.2 175.8 124.7
kW
15.32 14.82 14.36 15.57 15.12 14.69 15.75
TC
193.2 176.4 160.8 201.5 186.4 172.0 208.0
105 SHC
99.7 124.3 155.4 111.0 143.0 172.0 122.7
kW
16.00 15.51 15.05 16.25 15.80 15.38 16.43
TC
183.5 167.7 153.1 191.0 177.0 163.7 197.0
115 SHC
96.3 120.4 148.6 107.0 138.5 163.7 118.8
kW
17.26 16.61 16.01 17.57 17.00 16.45 17.82
TC
173.2 158.7 145.1 179.8 167.2 155.1 185.4
125 SHC
92.7 116.3 141.6 102.8 133.7 155.1 114.6
kW
18.63 17.91 17.23 18.96 18.33 17.73 19.23
38AH024 AND 40RM024 WITH STANDARD 3-ROW COIL
Evaporator Air Cfm
Temp (F)
Air
6,000
8,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
234.5 214.7 196.5 244.6 224.8 209.7 249.6
85 SHC 123.6 158.1 191.1 140.2 183.3 209.7 154.6
kW
13.84 13.51 13.21 14.01 13.68 13.43 14.09
TC
223.9 205.4 188.9 233.0 214.5 201.4 237.2
95 SHC 119.5 154.3 184.5 136.0 179.0 201.4 150.2
kW
15.18 14.76 14.38 15.39 14.96 14.67 15.48
TC
218.4 200.4 184.7 227.0 209.1 196.9 230.9
100 SHC 117.4 152.2 180.9 133.9 176.7 196.9 148.0
kW
15.89 15.39 14.94 16.14 15.63 15.29 16.25
TC
212.7 195.4 180.4 220.9 203.5 192.4 224.4
105 SHC 115.3 150.2 177.1 131.7 174.4 192.4 145.7
kW
16.57 16.06 15.62 16.82 16.30 15.98 16.92
TC
201.6 185.1 171.4 209.2 192.5 183.0 212.1
115 SHC 111.0 145.9 169.3 127.4 169.7 183.0 141.4
kW
18.01 17.33 16.76 18.32 17.6 17.24 18.44
TC
189.8 174.3 162.0 196.6 180.8 173.1 198.9
125 SHC 106.5 141.5 161.1 122.8 164.8 173.1 136.7
kW
19.45 18.68 18.07 19.79 19.01 18.62 19.90

62
195.4
195.4
13.19
188.3
188.3
14.37
184.4
184.4
14.93
180.3
180.3
15.62
171.8
171.8
16.78
162.9
162.9
18.11

38AH024 AND 40RM028 WITH STANDARD 3-ROW COIL


Temp (F)
Evaporator Air Cfm
Air
7,500
10,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
252.4 229.4 214.3 261.8 239.0 229.0 266.4
85 SHC 140.1 181.8 212.5 160.6 212.9 229.0 180.5
kW
14.14 13.76 13.50 14.30 13.92 13.75 14.37
TC
240.2 218.3 205.3 248.7 227.1 219.4 252.6
95 SHC 135.6 177.3 204.2 155.9 208.0 219.4 175.9
kW
15.55 15.05 14.76 15.74 15.25 15.08 15.83
TC
234.0 212.6 200.5 242.1 221.0 214.3 245.7
100 SHC 133.3 175.0 199.9 153.6 205.5 214.3 173.6
kW
16.34 15.73 15.39 16.56 15.97 15.78 16.67
TC
227.7 206.7 195.6 235.3 214.8 209.1 238.6
105 SHC 131.0 172.6 195.3 151.2 202.9 209.1 171.2
kW
17.01 16.40 16.07 17.24 16.63 16.47 17.34
TC
215.5 195.1 185.6 222.6 202.6 198.8 225.4
115 SHC 126.6 167.9 186.2 146.8 197.9 198.8 166.8
kW
18.58 17.74 17.35 18.87 18.05 17.89 18.99
TC
202.4 182.9 175.0 208.8 189.8 187.7 211.2
125 SHC 121.8 163.0 176.5 141.9 189.8 187.7 162.1
kW
20.08 19.11 18.72 20.40 19.45 19.35 20.52

62
220.2
220.2
13.60
211.5
211.5
14.90
206.8
206.8
15.57
202.0
202.0
16.26
192.3
192.3
17.63
182.0
182.0
19.07

38AH028 AND 40RM024 WITH STANDARD 3-ROW COIL


Evaporator Air Cfm
Temp (F)
Air
6,000
8,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
256.2 235.7 215.7 267.1 247.0 228.8 273.1
85 SHC 131.8 166.7 207.8 148.3 192.7 228.8 162.9
kW
16.65 16.14 15.64 16.93 16.42 15.97 17.08
TC
246.0 225.8 206.6 256.5 236.5 219.8 262.0
95 SHC 127.9 162.6 200.0 144.5 188.3 219.8 159.0
kW
18.20 17.70 17.22 18.46 17.96 17.54 18.60
TC
240.9 220.9 202.1 251.2 231.3 215.3 256.5
100 SHC 126.0 160.6 196.1 142.6 186.1 215.3 157.0
kW
18.97 18.38 17.84 19.27 18.69 18.22 19.42
TC
234.4 215.6 198.2 243.9 225.2 210.7 248.5
105 SHC 123.5 158.5 192.7 139.9 183.5 210.7 154.2
kW
19.79 19.10 18.47 20.13 19.45 18.93 20.30
TC
223.6 205.8 189.8 232.3 214.5 201.9 236.3
115 SHC 119.4 154.4 185.3 135.8 179.0 201.9 149.9
kW
21.29 20.61 19.99 21.63 20.94 20.46 21.78
TC
196.6 180.3 167.0 203.9 187.4 178.6 206.6
125 SHC 109.1 144.0 165.5 125.5 167.5 178.6 139.4
kW
23.11 22.43 21.88 23.41 22.72 22.36 23.52

7500
67
211.4
169.2
13.46
202.5
164.7
14.69
197.8
162.4
15.31
192.9
160.0
15.99
183.0
155.0
17.24
172.5
149.8
18.60

10,000
67
232.7
206.1
13.81
221.8
201.1
15.13
216.2
198.6
15.83
210.4
195.9
16.51
199.1
190.8
17.91
187.1
185.3
19.32

LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.

38

12,500
67
248.1
240.6
14.07
235.7
235.2
15.45
229.4
229.4
16.21
223.0
223.0
16.88
210.6
210.6
18.38
197.4
197.4
19.83

62
241.2
241.2
13.95
230.9
230.9
15.34
225.6
225.6
16.10
220.1
220.1
16.79
209.5
209.5
18.33
197.9
197.9
19.86

10,000
67
255.0
216.3
16.63
244.5
211.5
18.16
239.3
209.1
18.92
232.6
206.1
19.72
221.6
201.0
21.22
193.9
188.4
23.00

62
239.4
239.4
16.24
230.4
230.4
17.81
225.9
225.9
18.53
220.8
220.8
19.29
211.6
211.6
20.83
187.8
187.8
22.74

5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb

hldb = hedb

total capacity (Btuh)


4.5 cfm

where hewb = enthalpy of air entering evaporator coil


6. Combination ratings are based on a 2 F line loss. For a close-coupled system (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes
table are based on 2 F line loss.

38AH/40RM COMBINATION RATINGS STANDARD 3-ROW COIL ENGLISH (cont)


38AH028 AND 40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air Cfm
Temp (F)
Air
7,500
10,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
275.2 252.7 234.7 285.3 262.8 249.2 290.6
85 SHC 148.5 191.1 231.2 168.8 222.6 249.2 188.5
kW
17.13 16.57 16.12 17.38 16.82 16.48 17.52
TC
264.5 241.8 225.1 274.3 251.6 239.7 279.2
95 SHC 144.5 186.7 222.4 164.9 218.0 239.7 184.7
kW
18.66 18.09 17.68 18.91 18.34 18.04 19.03
TC
259.1 236.3 220.3 268.7 246.0 235.0 273.5
100 SHC 142.6 184.5 218.0 163.0 215.7 235.0 182.8
kW
19.50 18.83 18.37 19.78 19.12 18.79 19.92
TC
251.2 229.6 215.2 260.0 238.6 229.2 264.3
105 SHC 139.7 181.8 213.4 159.9 212.7 229.2 179.8
kW
20.40 19.61 19.09 20.72 19.94 19.60 20.87
TC
239.3 218.3 205.6 247.4 226.7 219.2 251.1
115 SHC 135.3 177.2 204.6 155.5 207.8 219.2 175.4
kW
21.89 21.09 20.60 22.21 21.41 21.12 22.35
TC
210.1 189.8 180.9 217.0 197.1 194.0 219.6
125 SHC 124.6 1165.7 181.9 144.8 195.7 194.0 164.9
kW
23.67 22.82 22.45 23.96 23.13 23.00 24.07
38AH028 AND 40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air Cfm
Temp (F)
Air
9,000
12,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
291.7 266.7 251.6 300.7 276.9 267.5 305.2
85 SHC 162.4 214.9 249.7 189.9 251.2 267.5 211.7
kW
17.54 16.92 16.54 17.77 17.17 16.94 17.88
TC
280.4 255.1 241.3 289.1 265.1 257.4 293.2
95 SHC 158.1 210.3 240.4 186.0 246.5 257.4 207.7
kW
19.06 18.43 18.08 19.28 18.68 18.48 19.38
TC
274.7 249.3 236.2 283.2 259.2 252.3 287.2
100 SHC 156.0 208.0 235.8 184.0 244.1 252.3 205.7
kW
19.95 19.21 18.83 20.20 19.50 19.30 20.32
TC
265.5 241.5 229.0 273.2 250.6 245.1 276.7
105 SHC 152.5 204.9 230.1 180.6 240.6 245.1 202.2
kW
20.92 20.04 19.62 21.20 20.38 20.18 21.32
TC
252.4 229.1 219.2 259.4 237.6 234.0 262.2
115 SHC 147.5 200.0 220.4 175.9 235.4 234.0 197.5
kW
22.40 21.50 21.12 22.67 21.83 21.69 22.78
TC
221.1 198.5 192.2 226.8 206.2 206.4 228.9
125 SHC 135.6 187.9 195.9 164.9 206.2 206.4 186.3
kW
24.13 23.19 22.92 24.37 23.51 23.52 24.45

62
261.4
261.4
16.78
251.9
251.9
18.35
247.2
247.2
19.15
240.8
240.8
20.02
230.4
230.4
21.55
204.6
204.6
23.44

38AH034 AND 40RM028 WITH STANDARD 3-ROW COIL


Evaporator Air Cfm
Temp (F)
Air
7,500
10,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
307.8 283.0 258.8 320.5 295.3 274.6 327.8
85 SHC 160.5 203.4 253.3 181.2 236.0 274.6 200.9
kW
20.50 19.90 19.32 20.81 20.20 19.70 20.99
TC
295.9 271.4 249.2 307.9 283.1 264.9 314.6
95 SHC 156.1 198.7 244.5 176.8 231.0 264.9 196.5
kW
22.57 21.78 21.06 22.95 22.15 21.57 23.17
TC
289.5 265.4 244.4 301.0 276.7 259.9 307.3
100 SHC 153.7 196.3 240.2 174.3 228.3 259.9 194.1
kW
23.38 22.58 21.88 23.77 22.96 22.40 23.98
TC
283.7 259.5 239.3 295.0 270.6 254.8 301.0
105 SHC 151.6 193.9 235.4 172.2 225.8 254.8 192.0
kW
24.41 23.52 22.77 24.83 23.93 23.34 25.05
TC
271.0 247.4 229.4 281.4 257.8 244.5 286.8
115 SHC 146.9 189.0 226.4 167.5 220.6 244.5 187.3
kW
26.32 25.30 24.52 26.77 25.75 25.18 27.00
TC
257.9 234.9 219.0 267.5 244.6 233.7 272.3
125 SHC 142.1 184.0 216.8 162.6 215.2 233.7 182.4
kW
28.29 27.15 26.36 28.76 27.63 27.09 29.00

62
280.5
280.5
17.26
270.3
270.3
18.81
265.2
265.2
19.68
257.4
257.4
20.62
245.8
245.8
22.14
217.6
217.6
23.98

38AH034 AND 40RM034 WITH STANDARD 3-ROW COIL


Evaporator Air Cfm
Temp (F)
Air
9,000
12,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
328.6 301.1 279.6 340.3 313.3 297.3 346.7
85 SHC 176.4 228.6 275.2 203.3 265.9 297.3 225.6
kW
21.00 20.34 19.82 21.29 20.64 20.25 21.44
TC
315.5 288.3 268.9 326.5 300.0 286.3 332.2
95 SHC 171.4 223.5 265.4 198.6 260.5 286.3 220.7
kW
23.19 22.32 21.70 23.55 22.70 22.26 23.73
TC
308.2 281.5 263.3 318.6 292.8 280.4 324.0
100 SHC 168.7 220.8 260.4 196.0 257.6 280.4 218.0
kW
24.01 23.12 22.51 24.35 23.49 23.08 24.53
TC
302.1 275.2 257.8 312.3 286.4 275.0 317.5
105 SHC 166.3 218.3 255.4 193.9 255.0 275.0 215.8
kW
25.09 24.10 23.45 25.47 24.51 24.09 25.66
TC
287.9 261.8 246.6 297.3 272.3 263.2 301.8
115 SHC 161.0 213.0 245.2 188.8 249.4 263.2 210.6
kW
27.05 25.92 25.26 27.45 26.37 25.98 27.65
TC
273.5 247.9 234.8 282.0 257.8 251.1

125 SHC 155.5 207.5 234.6 183.6 243.5 251.1

kW
29.06 27.79 27.14 29.48 28.28 27.95

12,500
67
271.7
250.9
17.04
260.6
246.1
18.56
255.0
243.6
19.38
247.1
240.2
20.25
234.9
234.8
21.73
205.1
221.8
23.46

15,000
67
286.3
283.4
17.41
274.5
274.5
18.91
268.7
268.7
19.78
259.5
259.5
20.70
246.2
246.2
22.16
214.4
214.4
23.85

LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.

12,500
67
305.2
265.5
20.44
292.9
260.2
22.47
286.3
257.3
23.28
280.3
254.6
24.28
267.2
248.9
26.15
253.7
243.1
28.08

62
288.2
288.2
20.03
278.2
278.2
22.00
272.9
272.9
22.83
267.8
267.8
23.82
257.2
257.2
25.72
246.0
246.0
27.70

15,000
67
324.0
300.0
20.89
310.4
294.0
23.03
303.0
290.8
23.83
296.6
287.9
24.89
282.1
281.6
26.80
267.4
267.4
28.76

62
311.8
311.8
20.60
300.5
300.5
22.71
294.4
294.0
23.55
288.9
288.9
24.60
276.7
276.7
26.56
264.1
264.1
28.59

5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb

hldb = hedb

total capacity (Btuh)


4.5 cfm

where hewb = enthalpy of air entering evaporator coil


6. Combination ratings are based on a 2 F line loss. For a close-coupled system (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes
table are based on 2 F line loss.

39

Performance data (cont)


38AH/40RM COMBINATION RATINGS HIGH-CAPACITY 4-ROW COIL SI
38AH024 AND 40RM016 WITH HIGH-CAPACITY 4-ROW COIL
Temp (C)
Evaporator Air L/s
Air
2100
2800
Entering
Evaporator Air Ewb (C)
Condenser
22
19
17
22
19
17
22
(Edb)
TC
64.9 59.5 54.3 68.5 63.0 57.8 71.0
29 SHC
31.2 38.2 44.9 34.5 43.5 52.2 37.5
kW
13.92 13.52 13.11 14.16 13.78 13.37 14.32
TC
62.1 56.8 51.8 65.3 60.1 55.0 67.6
35 SHC
30.1 37.0 43.8 33.3 42.3 50.6 36.3
kW
15.26 14.75 14.25 15.56 15.08 14.57 15.76
TC
61.2 55.5 50.6 63.8 58.6 53.7 65.9
38 SHC
29.8 36.4 43.1 32.7 41.7 50.1 35.7
kW
16.18 15.36 14.81 16.22 15.70 15.17 16.44
TC
59.1 54.0 49.3 62.1 57.1 52.3 64.2
41 SHC
28.8 35.8 42.6 32.1 41.2 49.4 35.2
kW
16.54 15.95 15.35 16.88 16.32 15.73 17.11
TC
56.0 51.3 46.7 58.8 54.0 49.4 60.6
46 SHC
27.6 34.7 41.4 30.9 39.9 48.1 33.9
kW
17.78 17.11 16.43 18.18 17.50 16.85 18.41
38AH024 AND 40RM024 WITH HIGH-CAPACITY 4-ROW COIL
Temp (C)
Evaporator Air L/s
Air
2830
3780
Entering
Evaporator Air Ewb (C)
Condenser
22
19
17
22
19
17
22
(Edb)
TC
70.6 64.9 59.4 73.7 67.9 62.4 75.7
29 SHC 34.7 44.3 53.5 38.9 51.0 62.4 42.8
kW
14.33 13.95 13.54 14.53 14.16 13.77 14.65
TC
67.4 61.9 56.7 70.2 64.6 60.6 72.0
35 SHC 33.6 43.2 52.2 37.7 49.8 60.6 41.6
kW
15.76 15.28 14.78 15.98 15.53 15.28 16.13
TC
65.8 60.3 55.1 68.4 62.9 58.4 70.1
38 SHC 33.0 42.5 51.5 37.1 49.2 58.4 40.9
kW
16.46 15.91 15.35 16.69 16.17 15.70 16.85
TC
64.1 58.7 53.7 66.6 61.2 57.1 68.2
41 SHC 32.4 41.9 50.8 36.5 48.6 57.1 40.3
kW
17.12 16.53 15.93 17.38 16.81 16.34 17.55
TC
60.6 55.5 50.8 62.9 57.8 54.4 64.4
46 SHC 31.1 40.7 49.3 35.3 47.3 54.4 39.1
kW
18.41 17.73 17.06 18.71 18.04 17.58 18.91

17
60.2
58.0
13.57
57.3
56.2
14.80
55.8
55.8
15.40
54.5
54.5
16.00
51.9
51.9
17.21

38AH024 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL


Temp (C)
Evaporator Air L/s
Air
3540
4720
Entering
Evaporator Air Ewb (C)
Condenser
22
19
17
22
19
17
22
(Edb)
TC
75.3 69.3 63.6 78.0 72.0 68.1 79.9
29 SHC
39.3 51.1 61.7 44.4 59.3 68.1 49.1
kW
14.64 14.27 13.87 14.82 14.45 14.18 14.94
TC
71.7 66.0 60.6 74.3 68.5 65.2 76.0
35 SHC
38.1 49.9 60.6 43.2 58.0 65.2 47.9
kW
16.13 15.65 15.17 16.34 15.88 15.58 16.48
TC
70.0 64.3 59.1 72.4 66.4 63.8 73.9
38 SHC
37.5 49.2 59.1 42.5 57.2 63.8 47.3
kW
16.85 16.33 15.80 17.08 16.48 16.27 17.21
TC
68.1 62.6 57.9 70.5 64.6 62.3 71.9
41 SHC
36.9 48.6 57.9 41.8 56.5 62.3 46.5
kW
17.56 16.98 16.45 17.80 17.15 16.94 17.94
TC
64.5 59.2 55.2 66.5 61.2 59.4 67.8
46 SHC
35.6 47.3 55.2 40.5 55.1 59.4 45.3
kW
18.93 18.25 17.70 19.17 18.50 18.26 19.33

17
66.7
66.6
14.22
63.1
63.1
15.38
61.7
61.7
16.04
60.3
60.3
16.69
57.4
57.4
17.97

38AH028 AND 40RM024 WITH HIGH-CAPACITY 4-ROW COIL


Temp (C)
Evaporator Air L/s
Air
2830
3780
Entering
Evaporator Air Ewb (C)
Condenser
22
19
17
22
19
17
22
(Edb)
TC
78.1 71.8 65.6 81.8 75.4 69.2 84.4
29 SHC
37.6 47.2 56.4 41.8 54.0 65.4 45.7
kW
17.38 16.84 16.29 17.67 17.16 16.62 17.88
TC
74.7 68.6 62.8 78.2 72.0 66.3 80.5
35 SHC
36.3 45.9 55.1 40.5 52.7 63.8 44.4
kW
18.95 18.31 17.67 19.31 18.69 18.07 19.54
TC
73.0 67.0 61.3 76.4 70.3 64.7 78.5
38 SHC
35.7 45.2 54.4 39.9 52.0 63.0 43.7
kW
19.72 19.03 18.35 20.11 19.43 18.76 20.34
TC
71.3 65.5 59.9 74.5 68.6 63.0 76.5
41 SHC
35.0 44.6 53.7 39.2 51.4 62.5 43.1
kW
20.48 19.74 19.01 20.90 20.15 19.43 21.12
TC
67.9 62.3 57.0 70.7 65.0 60.0 72.5
46 SHC
33.7 43.3 52.4 37.9 50.0 60.0 41.7
kW
22.03 21.21 20.38 22.45 21.62 20.85 22.70

3500
19
65.5
48.4
13.96
62.4
47.3
15.28
60.7
46.7
15.92
59.1
46.0
16.54
55.7
44.7
17.74

4720
19
69.8
57.3
14.29
66.0
55.8
15.58
64.7
55.3
16.35
62.6
54.5
16.91
59.1
53.2
18.18

LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.

40

5900
19
73.8
66.6
14.58
69.9
65.1
15.95
68.1
64.2
16.67
66.3
63.5
17.36
62.6
61.5
18.68

17
71.5
71.5
14.41
68.6
68.6
15.88
67.0
67.0
16.58
65.4
65.4
17.28
62.2
62.2
18.63

4720
19
77.8
60.3
17.38
74.2
58.9
18.91
72.4
58.2
19.66
70.5
57.5
20.39
66.9
56.1
21.89

17
72.0
72.0
16.85
69.2
69.2
18.36
67.8
67.8
19.12
66.4
66.4
19.86
63.5
63.5
21.39

5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb

hldb = hedb

total capacity (kW)


1.20 x 10-3 x (L/s)

where hewb = enthalpy of air entering evaporator coil (kJ/kg).


6. Combination ratings are based on a 1.1 C line loss. For a close-coupled system (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe
Sizes table are based on 1.1 C line loss.

38AH/40RM COMBINATION RATINGS HIGH-CAPACITY 4-ROW COIL SI (cont)


38AH028 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air L/s
Temp (C)
Air
3500
4700
Entering
Evaporator Air Ewb (C)
Condenser
22
19
17
22
19
17
22
(Edb)
TC
83.7 77.1 70.8 87.1 80.3 74.5 89.3
29 SHC
41.9 53.9 65.4 47.1 62.3 74.5 51.9
kW
17.85 17.34 16.79 18.11 17.59 17.09 18.28
TC
80.0 73.6 67.5 83.1 76.6 71.6 85.1
35 SHC
40.5 52.6 63.8 45.7 60.9 71.6 50.5
kW
19.53 18.89 18.23 19.81 19.20 18.66 20.00
TC
78.1 71.8 65.9 81.1 74.7 70.2 83.0
38 SHC
39.9 51.9 63.0 45.0 60.2 70.2 49.8
kW
20.34 19.64 18.94 20.64 19.97 19.45 20.85
TC
76.2 70.1 64.3 79.0 72.9 68.7 81.0
41 SHC
39.2 51.2 62.3 44.3 59.5 68.7 49.1
kW
21.13 20.37 19.63 21.45 20.73 20.20 21.68
TC
72.4 66.5 61.0 75.0 69.1 66.7 76.7
46 SHC
37.9 49.8 61.0 43.0 58.1 66.7 47.7
kW
22.72 21.88 21.05 23.11 22.27 22.38 23.34
38AH028 AND 40RM034 WITH HIGH-CAPACITY 4-ROW COIL
Temp (C)
Evaporator Air L/s
Air
4250
5660
Entering
Evaporator Air Ewb (C)
Condenser
22
19
17
22
19
17
22
(Edb)
TC
88.2 81.2 74.6 91.3 84.3 80.8 93.3
29 SHC
45.7 60.2 73.0 51.9 70.1 80.8 57.6
kW
18.23 17.70 17.16 18.48 17.96 17.72 18.66
TC
84.2 77.5 71.5 87.1 80.4 76.8 88.9
35 SHC
44.4 58.8 71.5 50.5 68.6 76.8 56.2
kW
19.97 19.33 18.70 20.26 19.63 19.24 20.44
TC
82.2 75.6 70.0 85.0 78.4 75.2 86.7
38 SHC
43.7 58.1 70.0 49.8 67.9 75.2 55.5
kW
20.81 20.12 19.46 21.13 20.43 20.06 21.29
TC
80.2 73.7 68.6 82.8 76.3 73.6 84.4
41 SHC
43.0 57.4 68.6 49.1 67.1 73.6 54.8
kW
21.64 20.90 20.23 21.96 21.21 20.86 22.14
TC
76.1 70.0 66.6 78.4 72.2 70.4 79.9
46 SHC
41.6 56.0 62.0 47.7 65.4 70.4 53.4
kW
23.33 22.47 21.97 23.63 22.79 22.50 23.83

17
78.6
78.6
17.45
75.5
75.5
19.06
73.9
73.9
19.86
72.3
72.3
20.64
69.1
69.1
22.26

38AH034 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL


Evaporator Air L/s
Temp (C)
Air
3500
4700
Entering
Evaporator Air Ewb (C)
Condenser
22
19
17
22
19
17
22
(Edb)
TC
93.3 85.7 78.5 97.6 89.9 82.8 100.3
29 SHC
45.6 57.6 69.0 50.9 66.1 79.5
55.7
kW
22.08 21.29 20.50 22.53 21.74 20.97 22.83
TC
89.5 82.2 75.2 93.3 86.0 79.5 95.9
35 SHC
44.2 56.1 67.4 49.4 64.5 77.1 54.2
kW
23.91 23.00 22.08 24.37 23.48 22.63 24.70
TC
87.5 80.3 73.5 91.2 84.0 78.3 93.7
38 SHC
43.5 55.3 66.7 48.6 63.8 76.4 53.4
kW
24.80 23.82 22.87 25.28 24.33 23.56 25.62
TC
85.4 78.4 71.8 89.0 82.0 76.2 91.4
41 SHC
42.7 54.6 65.9 47.8 63.0 74.8 52.7
kW
25.70 24.67 23.67 26.21 25.21 24.33 26.57
TC
81.3 74.7 68.4 84.6 78.0 72.7 86.9
46 SHC
41.2 53.1 64.3 46.4 61.5 72.3 51.2
kW
27.46 26.34 25.23 28.03 26.93 25.98 28.40

17
84.0
84.0
17.91
80.7
80.7
19.63
78.9
78.9
20.46
77.1
77.1
21.28
73.6
73.6
22.95

38AH034 AND 40RM034 WITH HIGH-CAPACITY 4-ROW COIL


Temp (C)
Evaporator Air L/s
Air
4250
5660
Entering
Evaporator Air Ewb (C)
Condenser
22
19
17
22
19
17
22
(Edb)
TC
98.9 91.0 83.5 102.9 95.0 88.6 105.6
29 SHC
49.6 64.0 77.6
55.9 74.1 87.6
61.6
kW
22.70 21.89 21.08 23.12 22.33 21.61 23.40
TC
94.7 87.1 80.0 98.5 90.8 85.4 100.8
35 SHC
48.1 62.5 76.0 54.3 72.6 85.4
60.1
kW
24.58 23.66 22.75 25.06 24.14 23.43 25.34
TC
92.6 85.1 78.2 96.2 88.6 83.3 98.4
38 SHC
47.3 61.8 74.7 53.6 71.8 83.3 59.3
kW
25.50 24.53 23.57 25.99 25.01 24.22 26.28
TC
90.4 83.1 76.7 93.8 86.4 81.6 96.0
41 SHC
46.6 61.0 73.6 52.8 70.9 81.6 58.5
kW
26.44 25.42 24.45 26.94 25.91 25.13 27.24
TC
86.1 79.1 73.2 89.1 81.8 78.2 91.1
46 SHC
45.1 59.5 71.2 51.2 68.3 78.2 56.9
kW
28.30 27.16 26.10 28.80 27.57 26.95 29.11

5900
19
82.5
69.9
17.77
78.6
68.4
19.40
76.7
67.7
20.20
74.8
67.0
20.97
70.7
65.2
22.50

7080
19
86.3
78.8
18.12
82.0
77.2
19.76
80.0
76.3
20.57
78.0
75.3
21.39
73.9
73.1
23.01

LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.

5900
19
92.6
73.9
22.04
88.5
72.3
23.82
86.5
71.5
24.69
84.4
70.7
25.58
80.1
69.0
27.28

17
87.2
86.7
21.51
83.3
83.3
23.10
81.6
81.6
23.96
79.9
79.9
24.86
76.6
76.6
26.63

7080
19
97.5
83.3
22.60
93.0
81.5
24.41
90.8
80.6
25.30
88.6
79.7
26.21
84.1
77.7
27.99

17
93.0
93.0
22.06
89.9
89.9
24.03
87.7
87.7
24.84
85.9
85.9
25.77
82.1
82.1
27.60

5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb

hldb = hedb

total capacity (kW)


1.20 x 10-3 x (L/s)

where hewb = enthalpy of air entering evaporator coil (kJ/kg).


6. Combination ratings are based on a 1.1 C line loss. For a close-coupled system (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe
Sizes table are based on 1.1 C line loss.

41

Performance data (cont)


38AH/40RM COMBINATION RATINGS HIGH-CAPACITY 4-ROW COIL ENGLISH
38AH024 AND 40RM016 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Evaporator Air Cfm
Air
4500
6000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
221.8 203.3 185.6 234.0 215.3 197.3 242.4
85 SHC 106.7 130.4 153.4 117.7 148.7 178.2 128.1
kW
13.92 13.52 13.11 14.16 13.78 13.37 14.32
TC
212.2 194.1 177.0 223.2 205.3 187.7 231.0
95 SHC 102.8 126.3 149.4 113.6 144.6 172.7 124.1
kW
15.26 14.75 14.25 15.56 15.08 14.57 15.76
TC
209.1 189.4 172.7 217.8 200.2 183.4 225.2
100 SHC 101.7 124.4 147.2 111.6 142.5 171.0 122.1
kW
16.18 15.36 14.81 16.22 15.70 15.17 16.44
TC
201.7 184.5 168.3 212.1 195.1 178.5 219.2
105 SHC
98.3 122.3 145.4 109.5 140.6 168.7 120.1
kW
16.54 15.95 15.35 16.88 16.32 15.73 17.11
TC
191.3 175.0 159.5 200.8 184.4 168.9 206.9
115 SHC
94.4 118.4 141.3 105.6 136.4 164.2 115.8
kW
17.78 17.11 16.43 18.18 17.50 16.85 18.41
38AH024 AND 40RM024 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Evaporator Air Cfm
Air
6,000
8,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
241.2 221.6 203.0 251.8 231.8 213.2 258.5
85 SHC 118.7 151.5 182.7 133.0 174.3 213.2 146.1
kW
14.33 13.95 13.54 14.53 14.16 13.77 14.65
TC
230.3 211.4 193.6 239.8 220.6 207.0 245.9
95 SHC 114.7 147.4 178.4 128.8 169.9 207.0 142.0
kW
15.76 15.28 14.78 15.98 15.53 15.28 16.13
TC
224.7 206.1 188.2 233.6 214.9 199.4 239.5
100 SHC 112.7 145.3 175.8 126.7 168.1 199.4 139.7
kW
16.46 15.91 15.35 16.69 16.17 15.70 16.85
TC
218.9 200.6 183.3 227.4 209.1 195.1 233.1
105 SHC 110.6 143.1 173.4 124.7 165.9 195.1 137.8
kW
17.12 16.53 15.93 17.38 16.81 16.34 17.55
TC
207.0 189.6 173.5 214.8 197.5 186.0 220.0
115 SHC 106.3 138.9 168.5 120.5 161.5 186.0 133.6
kW
18.41 17.73 17.06 18.71 18.04 17.58 18.91

62
205.5
198.2
13.57
195.6
191.8
14.80
190.7
190.7
15.40
186.2
186.2
16.00
177.3
177.3
17.21

38AH024 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL


Temp (F)
Evaporator Air Cfm
Air
7,500
10,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
257.1 236.6 217.2 266.5 245.9 232.4 272.7
85 SHC 134.3 174.6 210.8 151.6 202.4 232.4 167.7
kW
14.64 14.27 13.87 14.82 14.45 14.18 14.94
TC
245.0 225.2 207.0 253.8 234.0 222.7 259.5
95 SHC 130.1 170.3 207.0 147.5 198.0 222.7 163.7
kW
16.13 15.65 15.17 16.34 15.88 15.58 16.48
TC
238.9 219.5 202.0 247.4 226.8 217.7 252.5
100 SHC 128.1 168.0 202.0 145.2 195.4 217.7 161.4
kW
16.85 16.33 15.80 17.08 16.48 16.27 17.21
TC
232.7 213.7 197.8 240.7 220.6 212.7 245.6
105 SHC 126.0 165.8 197.8 142.9 193.0 212.7 158.8
kW
17.56 16.98 16.45 17.80 17.15 16.94 17.94
TC
220.2 202.0 188.4 227.0 208.9 202.7 231.7
115 SHC 121.6 161.5 188.4 138.3 188.2 202.7 154.8
kW
18.93 18.25 17.70 19.17 18.50 18.26 19.33

62
227.7
227.6
14.22
215.5
215.5
15.38
210.8
210.8
16.04
205.8
205.8
16.69
195.9
195.9
17.97

38AH028 AND 40RM024 WITH HIGH-CAPACITY 4-ROW COIL


Temp (F)
Evaporator Air Cfm
Air
6,000
8,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
266.7 245.1 224.2 279.5 257.5 236.4 288.2
85 SHC 128.3 161.2 192.7 142.7 184.5 223.3 156.1
kW
17.38 16.84 16.29 17.67 17.16 16.62 17.88
TC
255.2 234.3 214.3 267.1 246.1 226.3 274.9
95 SHC 123.9 156.6 188.0 138.3 180.0 218.0 151.6
kW
18.95 18.31 17.67 19.31 18.69 18.07 19.54
TC
249.4 229.0 209.5 260.9 240.2 220.9 268.1
100 SHC 121.8 154.5 185.7 136.2 177.7 215.1 149.3
kW
19.72 19.03 18.35 20.11 19.43 18.76 20.34
TC
243.5 223.6 204.5 254.6 234.2 215.2 261.2
105 SHC 119.5 152.2 183.5 133.9 175.4 213.3 147.1
kW
20.48 19.74 19.01 20.90 20.15 19.43 21.12
TC
231.8 212.7 194.7 241.5 222.1 205.1 247.6
115 SHC 115.2 147.8 179.0 129.4 170.8 205.1 142.5
kW
22.03 21.21 20.38 22.45 21.62 20.85 22.70

7500
67
223.6
165.2
13.96
213.0
161.5
15.28
207.3
159.4
15.92
201.7
157.0
16.54
190.3
152.7
17.74

10,000
67
238.5
195.6
14.29
225.5
190.4
15.58
220.9
188.8
16.35
213.9
186.1
16.91
202.0
181.8
18.18

LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.

42

12,500
67
252.2
227.4
14.58
238.9
222.3
15.95
232.6
219.3
16.67
226.5
216.8
17.36
213.6
210.1
18.68

62
244.3
244.3
14.41
234.2
234.2
15.88
228.8
228.8
16.58
223.3
223.3
17.28
212.3
212.3
18.63

10,000
67
265.9
205.9
17.38
253.4
201.2
18.91
247.2
198.9
19.66
240.9
196.4
20.39
228.4
191.6
21.89

62
245.9
245.9
16.85
236.3
236.3
18.36
231.5
231.5
19.12
226.7
226.7
19.86
216.9
216.9
21.39

5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb

hldb = hedb

total capacity (Btuh)


4.5 cfm

where hewb = enthalpy of air entering evaporator coil


6. Combination ratings are based on a 2 F line loss. For a close-coupled system (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes
table are based on 2 F line loss.

38AH/40RM COMBINATION RATINGS HIGH-CAPACITY 4-ROW COIL ENGLISH (cont)


38AH028 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL
Evaporator Air Cfm
Temp (F)
Air
7,500
10,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
285.9 263.2 241.7 297.4 274.3 254.4 304.8
85 SHC 143.0 184.1 223.3 160.7 212.8 254.4 177.1
kW
17.85 17.34 16.79 18.11 17.59 17.09 18.28
TC
273.4 251.4 230.4 283.7 261.6 244.6 290.6
95 SHC 138.5 179.5 218.0 156.1 207.9 244.6 172.4
kW
19.53 18.89 18.23 19.81 19.20 18.66 20.00
TC
266.9 245.3 225.0 276.9 255.2 239.9 283.5
100 SHC 136.2 177.1 215.3 153.7 205.6 239.9 170.0
kW
20.34 19.64 18.94 20.64 19.97 19.45 20.85
TC
260.3 239.3 219.6 269.9 248.8 234.7 276.5
105 SHC 133.9 174.8 212.9 151.3 203.2 234.7 167.8
kW
21.13 20.37 19.63 21.45 20.73 20.20 21.68
TC
247.1 227.1 208.3 256.1 235.9 227.7 261.9
115 SHC 129.3 170.1 208.3 146.8 198.4 227.7 163.1
kW
22.72 21.88 21.05 23.11 22.27 22.38 23.34
38AH028 AND 40RM034 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Evaporator Air Cfm
Air
9,000
12,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
301.1 277.2 254.8 311.7 287.8 275.9 318.8
85 SHC 156.2 205.6 249.4 177.2 239.4 275.9 196.8
kW
18.23 17.70 17.16 18.48 17.96 17.72 18.66
TC
287.5 264.6 244.2 297.5 274.5 262.4 303.7
95 SHC 151.5 200.9 244.2 172.5 234.3 262.4 191.9
kW
19.97 19.33 18.70 20.26 19.63 19.24 20.44
TC
280.7 258.2 239.1 290.3 267.7 256.9 296.0
100 SHC 149.2 198.4 239.1 170.1 231.9 256.9 189.4
kW
20.81 20.12 19.46 21.13 20.43 20.06 21.29
TC
273.8 251.8 234.2 282.9 260.7 251.5 288.4
105 SHC 146.7 196.0 234.2 167.7 229.2 251.5 187.2
kW
21.64 20.90 20.23 21.96 21.21 20.86 22.14
TC
259.9 239.0 227.5 267.9 246.6 240.4 272.9
115 SHC 142.1 191.4 211.8 162.9 223.5 240.4 182.4
kW
23.33 22.47 21.97 23.63 22.79 22.50 23.83

62
268.6
268.6
17.45
257.8
257.8
19.06
252.4
252.4
19.86
246.9
246.9
20.64
236.1
236.1
22.26

38AH034 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL


Evaporator Air Cfm
Temp (F)
Air
7,500
10,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
318.7 292.7 268.2 333.2 307.0 282.7 342.6
85 SHC 155.8 196.5 235.8 173.7 225.6 271.4 190.2
kW
22.08 21.29 20.50 22.53 21.74 20.97 22.83
TC
305.5 280.6 256.7 318.6 293.6 271.4 327.6
95 SHC 150.9 191.6 230.3 168.6 220.4 263.4 185.1
kW
23.91 23.00 22.08 24.37 23.48 22.63 24.70
TC
298.8 274.2 251.1 311.3 286.8 267.4 319.9
100 SHC 148.4 189.0 227.7 166.0 217.8 260.9 182.5
kW
24.80 23.82 22.87 25.28 24.33 23.56 25.62
TC
291.8 267.8 245.3 303.9 280.0 260.3 312.2
105 SHC 145.8 186.4 224.9 163.4 215.2 255.3 179.9
kW
25.70 24.67 23.67 26.21 25.21 24.33 26.57
TC
277.7 255.0 233.7 289.1 266.4 248.4 296.6
115 SHC 140.8 181.4 219.5 158.4 210.0 247.1 174.9
kW
27.46 26.34 25.23 28.03 26.93 25.98 28.40

62
287.0
287.0
17.91
275.5
275.5
19.63
269.5
269.5
20.46
263.5
263.5
21.28
251.2
251.2
22.95

38AH034 AND 40RM034 WITH HIGH-CAPACITY 4-ROW COIL


Temp (F)
Evaporator Air Cfm
Air
9,000
12,000
Entering
Evaporator Air Ewb (F)
Condenser
72
67
62
72
67
62
72
(Edb)
TC
337.9 310.7 285.0 351.6 324.3 302.5 360.6
85 SHC 169.4 218.7 264.9 190.8 253.2 299.1 210.5
kW
22.70 21.89 21.08 23.12 22.33 21.61 23.40
TC
323.5 297.4 273.2 336.2 310.0 291.7 344.3
95 SHC 164.3 213.6 259.5 185.4 247.8 291.7 205.1
kW
24.58 23.66 22.75 25.06 24.14 23.43 25.34
TC
316.2 290.7 267.1 328.5 302.6 284.3 336.0
100 SHC 161.6 210.9 255.2 182.9 245.1 284.3 202.4
kW
25.50 24.53 23.57 25.99 25.01 24.22 26.28
TC
308.8 283.9 261.8 320.5 295.2 278.5 327.8
105 SHC 159.0 208.3 251.5 180.3 242.3 278.5 199.8
kW
26.44 25.42 24.45 26.94 25.91 25.13 27.24
TC
294.0 270.2 249.9 304.3 279.3 267.0 311.0
115 SHC 153.9 203.1 243.2 174.9 233.1 267.0 194.5
kW
28.30 27.16 26.10 28.80 27.57 26.95 29.11

12,500
67
281.7
238.7
17.77
268.5
233.6
19.40
262.0
231.2
20.20
255.4
228.8
20.97
241.4
222.7
22.50

15,000
67
294.6
269.2
18.12
280.0
263.6
19.76
273.4
260.6
20.57
266.5
257.1
21.39
252.5
249.8
23.01

LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.

12,500
67
316.4
252.2
22.04
302.4
246.8
23.82
295.4
244.2
24.69
288.2
241.6
25.58
273.4
235.7
27.28

62
297.8
296.2
21.51
284.3
284.3
23.10
278.7
278.6
23.96
273.0
273.0
24.86
261.4
261.4
26.63

15,000
67
333.0
284.4
22.60
317.7
278.3
24.41
310.2
275.3
25.30
302.6
272.1
26.21
287.3
265.3
27.99

62
317.7
317.7
22.06
306.9
306.9
24.03
299.6
299.6
24.84
293.3
293.3
25.77
280.5
280.5
27.60

5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb

hldb = hedb

total capacity (Btuh)


4.5 cfm

where hewb = enthalpy of air entering evaporator coil


6. Combination ratings are based on a 2 F line loss. For a close-coupled system (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes
table are based on 2 F line loss.

43

Performance data (cont)


40RM HYDRONIC HEATING CAPACITIES SI
UNIT
40RM

AIRFLOW
(L/s)
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050

016

024

028

034

1-ROW
STEAM*
Cap.
(kW)

Ldb

117
129
140
135
140
146
149
166
183
164
180
196

61
53
48
53
46
41
50
44
41
47
41
38

2-ROW
HOT WATER COIL
Water
Cap.
Ldb
Flow
(kW)
(L/s)
120
62
2.6
137
55
3.0
154
51
3.3
150
58
3.3
170
52
3.7
191
49
4.1
189
60
4.1
218
53
4.7
247
50
5.4
215
57
4.7
247
51
5.4
278
48
6.0

40RM HYDRONIC HEATING CAPACITIES ENGLISH

PD
(kPa)
13.3
16.2
19.5
15.6
18.6
22.3
16.9
20.8
25.4
18.5
22.8
27.7

UNIT
40RM

AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

016

024

028

034

1-ROW
STEAM*
Cap.

Ldb

Cap.

402
458
479
458
487
499
511
575
626
560
621
670

141
129
118
129
115
105
122
112
106
117
107
101

412.0
471.0
529.0
506.0
584.0
652.0
649.0
752.0
842.0
735.0
850.0
950.0

2-ROW
HOT WATER COIL
Water
Ldb
Flow
(Gpm)
145
41.2
133
47.1
125
52.9
138
50.6
128
58.4
120
65.2
140
64.9
130
75.2
122
84.2
136
73.5
126
85.0
119
95.0

PD
4.5
5.5
6.6
5.1
6.3
7.5
5.7
7.1
8.5
6.2
7.8
9.3

LEGEND
Cap. Capacity (kW)
Ldb Leaving-Air Dry-Bulb Temp (C)
PD
Pressure Drop (kPa)

LEGEND
Cap. Capacity (Btuh in thousands)
Ldb Leaving-Air Dry-Bulb Temp (F)
PD
Pressure Drop (ft water)

*Based on 34.5 kPag steam, 15.6 C entering-air temperature. All steam coils are
non-freeze type.
Based on 93.3 C entering-water temperature, 11.1 C water temperature drop,
15.6 C entering-air temperature.
NOTES:
1. Maximum operating limits for heating coils: 138 kPag at 126.7 C.

*Based on 5 psig steam, 60 F entering-air temperature. All steam coils are nonfreeze type.
Based on 200 F entering-water temperature, 20 F water temperature drop, 60 F
entering-air temperature.
NOTES:
1. Maximum operating limits for heating coils: 20 psig at 260 F.

Capacity (kW)
1.23 x 10-3 x L/s
3. See Heating Correction Factors table.

Capacity (Btuh)
1.1 x cfm
3. See Heating Correction Factors table.

2. Leaving db = ent db (C) +

2. Leaving db = ent db (F) +

40RM HEATING CORRECTION FACTORS SI


Water Temp
Drop
(C)

11

16

Steam Pressure
(kPag)
0
14
35

HOT WATER COIL


Ent Water
Entering-Air Temp (C)
Temp
4
10
16
20
(C)
60
0.72
0.64
0.55
0.50
70
0.87
0.79
0.71
0.65
80
1.02
0.94
0.86
0.80
90
1.17
1.09
1.01
0.95
100
1.32
1.24
1.16
1.10
60
0.65
0.56
0.48
0.42
70
0.80
0.72
0.63
0.58
80
0.95
0.87
0.79
0.73
90
1.10
1.02
0.94
0.89
100
1.26
1.18
1.09
1.04
60
0.56
0.48
0.39
0.33
70
0.72
0.63
0.55
0.49
80
0.87
0.79
0.70
0.65
90
1.02
0.94
0.86
0.81
100
1.18
1.10
1.02
0.97

4
1.07
1.10
1.14

STEAM COIL
Entering-Air Temp (C)
10
16
20
0.99
0.91
0.86
1.02
0.95
0.90
1.07
0.99
0.95

40RM HEATING CORRECTION FACTORS ENGLISH

25
0.43
0.58
0.73
0.89
1.04
0.35
0.51
0.66
0.82
0.97
0.26
0.42
0.58
0.74
0.90

25
0.80
0.84
0.89

NOTE: Multiply capacity given in the Coil Accessory Heating Capacities table by
the correction factor for conditions at which unit is actually operating. Correct
leaving-air temperature using formula in Note 2 of Coil Accessory Heating Capacities table.

44

Water Temp
Drop
(F)

10

20

30

Steam Pressure
(psig)
0
2
5

HOT WATER COIL


Ent Water
Entering-Air Temp (F)
Temp
40
50
60
70
(F)
140
0.72
0.64
0.57
0.49
160
0.89
0.81
0.74
0.66
180
1.06
0.98
0.90
0.83
200
1.22
1.15
1.07
1.00
220
1.39
1.32
1.24
1.17
140
0.64
0.57
0.49
0.41
160
0.81
0.74
0.66
0.58
180
0.98
0.91
0.83
0.75
200
1.15
1.08
1.00
0.93
220
1.32
1.25
1.17
1.10
140
0.56
0.49
0.41
0.33
160
0.74
0.66
0.58
0.51
180
0.91
0.83
0.76
0.68
200
1.08
1.00
0.93
0.85
220
1.25
1.18
1.10
1.03

40
1.06
1.09
1.13

STEAM COIL
Entering-Air Temp (F)
50
60
70
0.98
0.91
0.85
1.02
0.95
0.89
1.06
1.00
0.93

80
0.41
0.58
0.75
0.92
1.09
0.33
0.51
0.68
0.85
1.02
0.24
0.43
0.60
0.78
0.95

80
0.78
0.82
0.87

NOTE: Multiply capacity given in the Coil Accessory Heating Capacities table by
the correction factor for conditions at which unit is actually operating. Correct
leaving-air temperature using formula in Note 2 of Coil Accessory Heating Capacities table.

40RM WITH STANDARD COIL FAN PERFORMANCE DATA 0-300 Pa ESP SI

40RM016

2120
2500
2830
3210
3540

r/s
7.13
8.13
9.03
10.07
10.99

kW
0.44
0.68
0.96
1.37
1.81

r/s
7.91
8.80
9.63
10.62
11.50

kW
0.52
0.78
1.07
1.48
1.93

EXTERNAL STATIC PRESSURE (Pa)


100
150
200
r/s
kW
r/s
kW
r/s
kW
9.50
0.74
10.94
0.99
12.17
1.25
10.15
1.00
11.48
1.27
12.70
1.57
10.81
1.30
12.01
1.58
13.18
1.90
11.66
1.73
12.71
2.01
13.77
2.35
12.45
2.20
13.40
2.49
14.35
2.83

40RM024

2830
3300
3780
4250
4720

8.86
10.14
11.43
12.74
14.05

0.94
1.44
2.11
2.96
4.01

9.48
10.69
11.93
13.19
14.47

1.04
1.56
2.25
3.12
4.19

10.65
11.70
12.84
14.02
15.23

1.26
1.81
2.52
3.43
4.54

11.84
12.71
13.71
14.81
15.96

1.53
2.08
2.81
3.74
4.88

13.01
13.73
14.60
15.59
16.66

1.85
2.41
3.14
4.08
5.24

14.10
14.74
15.49
16.37
17.36

2.19
2.77
3.51
4.45
5.62

15.08
15.71
16.39
17.17
18.07

2.53
3.15
3.91
4.85
6.03

40RM028

3540
4130
4720
5310
5900

7.60
8.68
9.78
10.89
12.00

0.96
1.47
2.15
3.01
4.07

8.16
9.18
10.23
11.30
12.38

1.09
1.62
2.32
3.20
4.29

9.27
10.13
11.07
12.06
13.09

1.38
1.94
2.67
3.59
4.72

10.34
11.07
11.89
12.80
13.75

1.68
2.29
3.05
4.00
5.17

11.30
11.99
12.72
13.53
14.41

1.97
2.63
3.45
4.43
5.63

12.15
12.84
13.53
14.27
15.07

2.28
2.97
3.84
4.88
6.11

12.97
13.60
14.29
14.99
15.74

2.68
3.32
4.23
5.33
6.61

40RM034

4250
4960
5660
6370
7080

8.68
9.93
11.21
12.51
13.82

1.48
2.35
3.45
4.85
6.59

9.17
10.38
11.63
12.89
14.17

1.68
2.53
3.66
5.08
6.85

10.27
11.21
12.38
13.58
14.81

2.07
2.90
4.07
5.54
7.36

11.27
11.99
13.08
14.22
15.40

2.41
3.28
4.49
6.01
7.88

12.19
12.78
13.76
14.83
15.97

2.77
3.68
4.93
6.49
8.40

13.03
13.56
14.45
15.44
16.52

3.13
4.10
5.39
6.99
8.94

13.81
14.32
15.14
16.05
17.06

3.50
4.51
5.87
7.51
9.49

600
r/s
19.47
19.65
19.97

kW
3.57
4.12
4.69

UNIT
(Std 3-Row
Coil)

AIRFLOW
(L/s)

50

250
r/s
kW
13.26
1.51
13.78
1.87
14.25
2.24
14.80
2.71
15.31
3.20

300
r/s
kW
14.26
1.77
14.76
2.18
15.23
2.58
15.76
3.09
16.24
3.60

See legend and notes on page 49.

40RM WITH STANDARD COIL FAN PERFORMANCE DATA 350-600 Pa ESP SI

40RM016

2120
2500
2830
3210
3540

r/s
15.20
15.67
16.13
16.66
17.13

kW
2.05
2.49
2.92
3.48
4.02

r/s
16.12
16.53
16.97
17.50
17.97

EXTERNAL STATIC PRESSURE (Pa)


450
500
kW
r/s
kW
r/s
kW
2.33
16.98
2.62
17.83
2.92
2.80
17.35
3.12
18.13
3.44
3.27
17.77
3.62
18.53
3.97
3.87
18.29
4.26
19.03
4.65
4.45
18.75
4.88
19.50
5.30

40RM024

2830
3300
3780
4250
4720

15.90
16.50
17.13
17.88
18.77

2.86
3.53
4.32
5.30
6.52

16.75
17.33
17.97
18.67
19.43

3.18
3.91
4.76
5.76
6.99

17.53
18.17
18.83
19.48

3.52
4.32
5.22
6.24

18.30
18.92
19.55

3.89
4.70
5.67

19.03
19.60

4.23
5.10

40RM028

3540
4130
4720
5310
5900

13.85
14.31
14.99
15.68
16.39

3.29
3.71
4.62
5.77
7.10

14.50
15.01
15.65
16.34
17.03

3.80
4.17
5.02
6.20
7.60

15.22
15.74
16.27
16.95
17.64

4.40
4.79
5.46
6.64
8.08

15.83
16.33
16.88
17.53
18.22

5.13
5.37
5.97
7.09
8.57

16.42
17.00
17.50
18.09

5.74
6.04
6.57
7.58

40RM034

4250
4960
5660
6370
7080

14.43
15.04
15.81
16.66
17.61

3.88
4.92
6.34
8.04
10.06

14.98
15.71
16.47
17.27
18.16

4.36
5.32
6.81
8.57
10.64

15.84
16.33
17.10
17.88

4.96
5.74
7.28
9.10

16.48
16.93
17.69

5.50
6.20
7.74

17.16
17.51
18.26

6.21
6.70
8.21

17.96
18.09

7.26
7.29

UNIT
(Std 3-Row
Coil)

AIRFLOW
(L/s)

350

400

550
r/s
18.67
18.90
19.26
19.75

kW
3.24
3.77
4.33
5.04

See legend and notes on page 49.

45

Performance data (cont)


40RM WITH STANDARD COIL FAN PERFORMANCE DATA 0.0-1.2 in. wg ESP ENGLISH
0.0
Rpm Bhp
428
0.59
488
0.92
542
1.29
604
1.83
660
2.42

0.2
Rpm Bhp
475
0.70
528
1.04
578
1.43
637
1.99
690
2.59

EXTERNAL STATIC PRESSURE (in. wg)


0.4
0.6
0.8
Rpm Bhp Rpm
Bhp
Rpm
Bhp
570
0.99
656
1.33
730
1.68
609
1.34
689
1.71
762
2.11
649
1.74
721
2.11
791
2.55
700
2.32
763
2.70
826
3.15
747
2.95
804
3.34
861
3.79

Rpm
796
827
855
888
919

Bhp
2.02
2.51
3.00
3.64
4.29

Rpm
856
886
914
946
975

Bhp
2.38
2.92
3.46
4.15
4.83

40RM024

6,000
7,000
8,000
9,000
10,000

532
608
686
764
843

1.25
1.93
2.83
3.97
5.38

569
641
716
791
868

1.39
2.09
3.01
4.18
5.62

639
702
770
841
914

1.69
2.42
3.38
4.59
6.09

711
763
823
888
957

2.06
2.80
3.77
5.02
6.55

781
824
876
935
1000

2.48
3.23
4.21
5.47
7.02

846
885
930
982
1042

2.93
3.71
4.70
5.96
7.53

905
943
983
1030
1084

3.39
4.23
5.24
6.51
8.08

40RM028

7,500
8,750
10,000
11,250
12,500

456
521
587
653
720

1.29
1.98
2.88
4.03
5.46

490
551
614
678
743

1.47
2.18
3.11
4.29
5.75

556
608
664
724
785

1.85
2.61
3.59
4.82
6.33

621
664
714
768
825

2.25
3.07
4.09
5.37
6.93

678
720
763
812
865

2.64
3.53
4.62
5.95
7.55

729
770
812
856
904

3.06
3.99
5.15
6.54
8.20

778
816
857
899
944

3.60
4.45
5.68
7.14
8.86

40RM034

9,000
10,500
12,000
13,500
15,000

521
596
673
751
829

1.99
3.16
4.63
6.51
8.84

550
623
698
773
850

2.25
3.40
4.90
6.82
9.19

616
672
743
815
888

2.77
3.89
5.45
7.44
9.88

676
720
785
853
924

3.23
4.40
6.02
8.06
10.57

731
767
826
890
958

3.72
4.94
6.62
8.71
11.27

782
814
867
927
991

4.20
5.50
7.23
9.38
11.99

829
859
908
963
1024

4.70
6.05
7.87
10.07
12.73

UNIT
(Std 3-Row
Coil)

AIRFLOW
(Cfm)

40RM016

4,500
5,300
6,000
6,800
7,500

1.0

1.2

See legend and notes on page 49.

40RM WITH STANDARD COIL FAN PERFORMANCE DATA 1.4-2.4 in. wg ESP ENGLISH

40RM016

4,500
5,300
6,000
6,800
7,500

Rpm
912
940
968
1000
1028

Bhp
2.75
3.33
3.92
4.67
5.39

Rpm
967
992
1018
1050
1078

EXTERNAL STATIC PRESSURE (in. wg)


1.8
2.0
Bhp
Rpm
Bhp
Rpm
Bhp
3.13
1019
3.52
1070
3.92
3.75
1041
4.18
1088
4.61
4.38
1066
4.85
1112
5.32
5.19
1097
5.71
1142
6.23
5.97
1125
6.54
1170
7.11

40RM024

6,000
7,000
8,000
9,000
10,000

954
990
1028
1073
1126

3.83
4.74
5.79
7.11
8.75

1005
1040
1078
1120
1166

4.27
5.24
6.38
7.72
9.37

40RM028

7,500
8,750
10,000
11,250
12,500

831
859
900
941
984

4.41
4.97
6.20
7.73
9.53

870
901
939
980
1022

40RM034

9,000
10,500
12,000
13,500
15,000

866
902
949
1000
1057

5.20
6.60
8.50
10.78
13.49

899
942
988
1036
1090

UNIT
(Std 3-Row
Coil)

AIRFLOW
(Cfm)

See legend and notes on page 49.

46

1.4

1.6

5.10
5.59
6.74
8.32
10.19

1052
1090
1130
1169

913
944
976
1017
1058

4.72
5.80
7.00
8.37

5.90
6.42
7.33
8.90
10.84

1098
1135
1173

950
980
1013
1052
1093

5.22
6.30
7.60

6.88
7.20
8.00
9.51
11.49

5.85
7.14
9.14
11.49
14.28

950
980
1026
1073

6.65
7.70
9.76
12.21

989
1016
1062

7.38
8.31
10.38

2.2
Rpm
1120
1134
1156
1185

1142
1176

985
1020
1050
1086

1029
1051
1095

2.4
Bhp
4.35
5.06
5.80
6.76

5.67
6.84

7.70
8.10
8.82
10.16

8.32
8.99
11.01

Rpm
1168
1179
1198

1077
1085

Bhp
4.79
5.52
6.29

9.74
9.77

FAN PERFORMANCE DATA 40RM WITH HIGH-CAPACITY COIL


0-300 Pa ESP SI
UNIT
40RM
(High-Capacity
4-Row Coil)

AIRFLOW
(L/s)

EXTERNAL STATIC PRESSURE (Pa)


100
150
200

50

250

300

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

016

2120
2500
2830
3210
3540

7.28
8.32
9.25
10.33
11.29

0.45
0.71
1.00
1.42
1.88

8.05
8.97
9.83
10.85
11.77

0.54
0.80
1.10
1.54
2.01

9.60
10.29
10.99
11.87
12.69

0.75
1.02
1.33
1.78
2.27

11.00
11.59
12.16
12.90
13.62

1.00
1.30
1.62
2.07
2.56

12.21
12.78
13.29
13.93
14.56

1.26
1.59
1.93
2.40
2.90

13.28
13.84
14.34
14.93
15.49

1.51
1.89
2.27
2.76
3.27

14.27
14.80
15.30
15.87
16.40

1.78
2.19
2.60
3.14
3.67

024

2830
3300
3780
4250
4720

9.03
10.34
11.67
13.01
14.36

0.96
1.48
2.17
3.05
4.15

9.62
10.86
12.14
13.44
14.75

1.06
1.60
2.31
3.21
4.32

10.77
11.85
13.02
14.23
15.48

1.29
1.85
2.58
3.51
4.66

11.94
12.84
13.88
15.00
16.18

1.56
2.12
2.87
3.82
4.99

13.08
13.85
14.75
15.77
16.87

1.87
2.45
3.20
4.16
5.35

14.15
14.84
15.63
16.54
17.56

2.20
2.80
3.56
4.53
5.73

15.12
15.78
16.50
17.32
18.26

2.54
3.18
3.96
4.94
6.14

028

3540
4130
4720
5310
5900

7.94
9.08
10.24
11.42
12.60

1.04
1.59
2.33
3.26
4.42

8.51
9.57
10.68
11.81
12.96

1.18
1.75
2.51
3.46
4.64

9.65
10.55
11.53
12.57
13.65

1.48
2.10
2.88
3.88
5.09

10.73
11.52
12.39
13.33
14.33

1.79
2.46
3.29
4.32
5.57

11.68
12.45
13.24
14.09
15.01

2.10
2.81
3.70
4.77
6.07

12.53
13.28
14.05
14.85
15.70

2.46
3.17
4.11
5.24
6.58

13.40
14.04
14.80
15.58
16.38

2.95
3.55
4.51
5.70
7.10

034

4250
4960
5660
6370
7080

8.99
10.33
11.68
13.04
14.42

1.62
2.51
3.68
5.18
7.05

9.49
10.77
12.07
13.40
14.74

1.78
2.70
3.90
5.42
7.31

10.44
11.59
12.81
14.07
15.36

2.12
3.08
4.33
5.90
7.84

11.39
12.40
13.52
14.71
15.94

2.49
3.49
4.77
6.39
8.38

12.32
13.22
14.23
15.34
16.51

2.86
3.92
5.25
6.90
8.93

13.18
14.03
14.95
15.97
17.08

3.22
4.35
5.74
7.44
9.51

13.95
14.79
15.66
16.61
17.65

3.59
4.78
6.23
7.98
10.10

See legend and notes on page 49.

FAN PERFORMANCE DATA 40RM WITH HIGH-CAPACITY COIL


350-600 Pa ESP SI
UNIT
40RM
(High-Capacity
4-Row Coil)

AIRFLOW
(L/s)

350

EXTERNAL STATIC PRESSURE (Pa)


450
500

400

550

600

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

016

2120
2500
2830
3210
3540

15.21
15.69
16.18
16.75
17.26

2.05
2.49
2.94
3.52
4.09

16.11
16.54
17.01
17.57
18.07

2.33
2.80
3.28
3.90
4.50

16.98
17.35
17.79
18.34
18.84

2.62
3.12
3.63
4.29
4.93

17.83
18.14
18.54
19.08
19.57

2.93
3.44
3.97
4.67
5.35

18.66
18.90
19.27
19.78

3.24
3.77
4.33
5.06

19.47
19.64
19.97

3.57
4.11
4.69

024

2830
3300
3780
4250
4720

16.01
16.67
17.35
18.11
18.96

2.88
3.57
4.39
5.37
6.58

16.85
17.50
18.17
18.88
19.67

3.22
3.96
4.82
5.83
7.05

17.64
18.28
18.95
19.63

3.56
4.36
5.27
6.31

18.39
19.03
19.68

3.91
4.75
5.72

19.12
19.73

4.26
5.15

028

3540
4130
4720
5310
5900

14.57
14.76
15.49
16.26
17.04

3.97
3.99
4.92
6.15
7.61

14.95
15.51
16.15
16.91
17.68

4.41
4.57
5.37
6.61
8.11

15.67
16.36
16.78
17.51
18.28

5.07
5.46
5.88
7.08
8.62

16.50
17.00
17.42
18.10

5.59
6.04
6.50
7.58

034

4250
4960
5660
6370
7080

14.68
15.51
16.35
17.24
18.22

4.00
5.20
6.72
8.54
10.70

15.38
16.17
17.01
17.87

4.49
5.63
7.21
9.10

16.12
16.80
17.64

5.14
6.09
7.69

17.00
17.41
18.23

6.15
6.61
8.18

See legend and notes on page 49.

47

Performance data (cont)


FAN PERFORMANCE DATA 40RM WITH HIGH-CAPACITY COIL
0.0-1.2 in. wg ESP ENGLISH
UNIT
40RM
(High-Capacity
4-Row Coil)

AIRFLOW
(Cfm)

0.0

EXTERNAL STATIC PRESSURE (in. wg)


0.4
0.6
0.8

0.2

1.0

1.2

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

016

4,500
5,300
6,000
6,800
7,500

437
499
555
620
677

0.61
0.95
1.34
1.91
2.52

483
538
590
651
706

0.72
1.07
1.48
2.06
2.69

576
617
659
712
761

1.01
1.37
1.79
2.39
3.04

660
696
730
774
817

1.35
1.74
2.17
2.78
3.44

732
767
798
836
873

1.69
2.13
2.59
3.22
3.89

797
830
860
896
929

2.03
2.53
3.04
3.71
4.39

856
888
918
952
984

2.38
2.94
3.49
4.21
4.93

024

6,000
7,000
8,000
9,000
10,000

542
620
700
781
862

1.29
1.99
2.92
4.10
5.56

577
652
728
806
885

1.42
2.15
3.10
4.30
5.79

646
711
781
854
929

1.72
2.48
3.46
4.71
6.24

716
771
833
900
971

2.09
2.85
3.85
5.13
6.70

785
831
885
946
1012

2.51
3.28
4.29
5.58
7.18

849
890
938
993
1054

2.95
3.76
4.78
6.08
7.69

907
947
990
1039
1096

3.40
4.27
5.32
6.62
8.24

028

7,500
8,750
10,000
11,250
12,500

476
545
615
685
756

1.39
2.14
3.12
4.37
5.92

510
574
641
709
778

1.58
2.35
3.36
4.64
6.22

579
633
692
754
819

1.99
2.81
3.87
5.20
6.83

644
691
743
800
860

2.40
3.29
4.41
5.79
7.47

701
747
794
845
901

2.81
3.77
4.96
6.40
8.14

752
797
843
891
942

3.29
4.25
5.51
7.02
8.83

804
842
888
935
983

3.96
4.76
6.05
7.64
9.52

034

9,000
10,500
12,000
13,500
15,000

539
620
701
783
865

2.18
3.37
4.94
6.95
9.45

569
646
724
804
884

2.39
3.62
5.22
7.27
9.81

626
695
769
844
921

2.85
4.13
5.80
7.91
10.52

683
744
811
883
956

3.34
4.68
6.40
8.57
11.24

739
793
854
920
991

3.83
5.25
7.04
9.26
11.98

791
842
897
958
1025

4.32
5.83
7.69
9.97
12.75

837
888
940
996
1059

4.82
6.41
8.36
10.71
13.54

See legend and notes on page 49.

FAN PERFORMANCE DATA 40RM WITH HIGH-CAPACITY COIL


1.4-2.4 in. wg ESP ENGLISH
UNIT
40RM
(High-Capacity
4-Row Coil)

AIRFLOW
(Cfm)

1.6

EXTERNAL STATIC PRESSURE (in. wg)


1.8
2.0

2.2

2.4

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

016

4,500
5,300
6,000
6,800
7,500

912
942
971
1005
1036

2.75
3.34
3.95
4.72
5.48

967
992
1020
1054
1084

3.12
3.76
4.40
5.23
6.04

1019
1041
1067
1101
1131

3.52
4.18
4.86
5.75
6.61

1070
1088
1112
1145
1174

3.92
4.61
5.33
6.27
7.17

1120
1134
1156
1187

4.35
5.06
5.81
6.79

1168
1179
1198

4.79
5.52
6.29

024

6,000
7,000
8,000
9,000
10,000

961
1000
1041
1086
1138

3.86
4.79
5.88
7.21
8.83

1011
1050
1090
1133
1180

4.31
5.32
6.47
7.82
9.46

1058
1097
1137
1178

4.77
5.85
7.07
8.47

1104
1142
1181

5.24
6.38
7.67

1147
1184

5.71
6.91

028

7,500
8,750
10,000
11,250
12,500

874
886
930
976
1023

5.33
5.36
6.60
8.25
10.20

897
930
969
1014
1061

5.91
6.13
7.20
8.86
10.88

940
982
1007
1051
1097

6.80
7.32
7.89
9.49
11.56

990
1020
1045
1086

7.50
8.10
8.71
10.17

034

9,000
10,500
12,000
13,500
15,000

881
930
981
1035
1093

5.37
6.97
9.02
11.45
14.35

923
970
1021
1072

6.03
7.55
9.67
12.20

967
1008
1058

6.89
8.17
10.32

1020
1045
1094

8.25
8.86
10.97

See legend and notes on page 49.

48

1.4

LEGEND AND NOTES FOR STANDARD AND HIGH-CAPACITY COIL


FAN PERFORMANCE DATA TABLES (SI)
LEGEND
ESP External Static Pressure

Bold indicates field-supplied drive is required.


Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables to complete the selection.
NOTES:
1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and
034; 20 r/s for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 51-mm
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. The medium-static drive and standard motor combination is not
available for 016-028 sizes. Use alternate motor if medium-static
drive is required for these sizes.

FACTORY-SUPPLIED FILTER PRESSURE DROP


SI
UNIT
40RM
016
40RM
024
40RM
028
40RM
034

AIRFLOW
(L/s)
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050

PRESSURE DROP
(Pa)
20
30
42
32
47
64
36
55
76
47
71
98

LEGEND AND NOTES FOR STANDARD AND HIGH-CAPACITY COIL


FAN PERFORMANCE DATA TABLES (English)
LEGEND
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure

FACTORY-SUPPLIED FILTER PRESSURE DROP


ENGLISH

Bold indicates field-supplied drive is required.


Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables to complete selection.

UNIT

NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. The medium-static drive and standard motor combination is not
available for 016-028 sizes. Use alternate motor if medium-static
drive is required for these sizes.

40RM
016
40RM
024
40RM
028
40RM
034

AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

PRESSURE DROP
(in. wg)
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40

49

Performance data (cont)


40RM PLENUM ACCESSORY AIR THROW DATA
SI (m)

40RM PLENUM ACCESSORY AIR THROW DATA


ENGLISH (Ft)

UNIT
40RM

AIRFLOW
(L/s)

Straight

VANE DEFLECTION
221/2

45

UNIT
40RM

AIRFLOW
(Cfm)

Straight

VANE DEFLECTION
221/2

45

016
024
028
034

2800
3800
4700
5650

15.41
18.17
23.26
25.97

13.25
15.44
19.89
22.00

9.55
11.20
14.38
15.89

016
024
028
034

6,000
8,000
10,000
12,000

50
60
76
85

43
51
65
72

31
37
47
52

NOTE: Throw distances shown are for 0.381 m/sec terminal velocity. Use the following multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(m/sec)
0.254
0.508
0.762

NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following
multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150

THROW FACTOR
X 1.50
X 0.75
X 0.50

THROW FACTOR
X 1.50
X 0.75
X 0.50

40RM ACCESSORY PRESSURE DROP SI (Pa)


UNIT
40RM
016

024

028

034

AIRFLOW
(L/s)

DISCHARGE
PLENUM

RETURN AIR
GRILLE

2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050

24
39
56
41
64
91
37
59
86
50
80
114

2
5
7
5
10
15
5
7
12
7
12
17

Hot Water
36
57
82
60
93
132
67
109
157
92
147
210

HEATING COILS
Steam
36
57
82
60
93
132
67
109
157
92
147
210

Electric
14
24
37
26
43
65
22
39
60
32
56
85

ECONOMIZER
15
22
37
23
43
69
15
22
35
20
35
52

40RM ACCESSORY PRESSURE DROP ENGLISH (in. wg)


UNIT
40RM
016

024

028

034

50

AIRFLOW
(Cfm)

DISCHARGE
PLENUM

RETURN AIR
GRILLE

4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

0.10
0.16
0.23
0.16
0.26
0.37
0.15
0.24
0.34
0.20
0.32
0.46

0.01
0.02
0.03
0.02
0.04
0.06
0.02
0.03
0.05
0.03
0.05
0.07

Hot Water
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

HEATING COILS
Steam
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

Electric
0.06
0.10
0.15
0.10
0.17
0.26
0.09
0.16
0.24
0.13
0.22
0.34

ECONOMIZER
0.06
0.09
0.15
0.09
0.17
0.28
0.06
0.09
0.14
0.08
0.14
0.21

Typical piping and wiring


ROOFTOP INSTALLATION 38AKS028-044

LEGEND
TXV Thermostatic Expansion Valve
Piping
*Field supplied.
Double riser may be required. See Application Data on page 66.

NOTES:
1. All piping must follow standard refrigerant piping techniques.
Refer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for, or to include all details for,
a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

51

Typical piping and wiring (cont)


GROUND-LEVEL INSTALLATION 38AKS028-044

LEGEND
TXV Thermostatic Expansion Valve
Piping
*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.

52

ROOFTOP INSTALLATION 38AH024-034

LEGEND
LLSV Liquid Line Solenoid Valve
TXV Thermostatic Expansion Valve
Piping
Double Riser Piping (If Required)
*Field supplied.
If double suction riser is required for piping system, size pipe
diameter of 3 ft (.9144 m) (maximum) riser according to application data on page 68.

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer
to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a specific
installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

53

Typical piping and wiring (cont)


GROUND LEVEL INSTALLATION 38AH024-034

LEGEND
TXV Thermostatic Expansion Valve
Piping
*Field supplied.

54

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer
to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a specific
installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.

Electrical data
38AKS028-044
UNIT
38AKS
028
034

044

NOMINAL VOLTAGE
(V-Ph-Hz)
346-3-50
230-3-50
400-3-50
346-3-50
230-3-50
400-3-50
346-3-50
230-3-50
400-3-50

VOLTAGE RANGE*
Min
Max
311
380
198
254
342
440
311
380
198
254
342
440
311
380
198
254
342
440

LEGEND
Full Load Amps
Heating, Air Conditioning, Refrigeration
Locked Rotor Amps
Minimum Circuit Amps per
NEC Section 430-24
MOCP Maximum Overcurrent Protection
NEC National Electrical Code (U.S.A. Standard)
RLA Rated Load Amps (Compressor)
FLA
HACR
LRA
MCA

COMPRESSOR
RLA
LRA
44.9
155
76.9
205
43.6
223
53.9
176
85.9
220
50.0
253
79.5
240
105.1
327
65.4
345

FAN MOTOR
Qty
FLA (ea)
2
4.4
2
6.4
2
3.0
2
4.4
2
6.4
2
3.0
3
4.4
3
6.4
3
3.0

POWER SUPPLY
MCA
MOCP
64.9
100
109.0
175
60.5
100
76.1
125
120.2
200
68.5
110
112.6
175
150.6
250
90.8
150

NOTES:
1. MCA and MOCP values are calculated in accordance with NEC
(National Electric Code) (U.S.A. Standard), Article 440.
2. Motor FLA and RLA values are established in accordance with UL
(Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. 230-v and 346-v units are part-wind-start units; the value under
compressor LRA is for the first winding energized. The 400-v units
are across-the-line-start units; value shown is for all windings
energized.

*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum
limits.
Fuse or HACR circuit breaker.

FIELD POWER WIRE SIZE


UNIT
38AKS
028
034
044

VOLTAGE
(3 Ph, 50 Hz)
346
230
400
346
230
400
346
230
400

FIELD POWER WIRE SIZE


TB1 WILL ACCEPT
14 to 2/0 AWG
14 to 2/0 AWG
6 AWG to 350 kcmil
14 to 2/0 AWG
14 to 2/0 AWG
6 AWG to 350 kcmil
14 to 2/0 AWG

LEGEND
AWG American Wire Gage
kcmil Thousand circular mils (formerly MCM)
TB
Terminal Block

55

Electrical data (cont)


38AH024-034
UNIT
38AH

024
028
034

VOLTAGE
RANGE*

COMPRESSOR

NOMINAL
VOLTAGE
(V-Ph-Hz)

Min

Max

230-3-50
346-3-50
400-3-50
230-3-50
346-3-50
400-3-50
230-3-50
346-3-50
400-3-50

198
311
342
198
311
342
198
311
342

254
380
440
254
380
440
254
380
440

RLA
Ckt 1
Ckt 2
39.3
39.3
24.0
24.0
18.0
18.0
43.6
43.6
26.4
26.4
22.1
22.1
43.6
63.6
26.4
34.3
22.1
30.0

FAN MOTORS (Qty 2)

LRA
Ckt 1
Ckt 2
128
128
93
93
99
99
143
143
104
104
114
114
143
200
104
145
114
120

LEGEND
Full Load Amps
Maximum Instantaneous Current Flow During Starting.
(The point in the starting sequence where the sum of
the LRA for the starting compressor, plus the total RLA
for all running compressors, plus the total FLA for all
running fan motors is maximum.)
LRA Locked Rotor Amps
MCA Minimum Circuit Amps (complies with National Electrical Code [NEC] Section 430-24) (U.S.A. Standard)
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps

FLA
(ea)

Nominal
Hp

Nominal
kW

0.75

0.75

0.75

6.3
4.4
3.0
6.3
4.4
3.0
6.3
4.4
3.0

POWER SUPPLY
MCA

MOCP

ICF

101.0
62.8
46.5
110.7
68.2
55.7
135.7
78.1
65.6

125
80
60
150
90
70
175
110
90

268.8
194.8
204.0
298.8
216.8
234.0
355.8
257.8
240.0

*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum.
All fans are protected by a single circuit breaker.
NOTES:
1. MCA and MOCP values are calculated in accordance with NEC
(National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Laboratories) Standard 1995 (U.S.A. standard).

FLA
ICF

40RM STANDARD MOTORS


UNIT
40RM
016
024
028
034

VOLTAGE RANGE

NOMINAL
VOLTAGE
(V*-Ph-Hz)

Min

Max

230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50

207
360
207
360
207
360
207
360

253
440
253
440
253
440
253
440

Nominal
kW
2.16
2.16
3.73
3.73
5.59
5.59
7.46
7.46

LEGEND
Full Load Amps
Minimum Circuit Amps (complies with National Electrical
Code [NEC] Section 430-24) (U.S.A. Standard)
MOCP Maximum Overcurrent Protection
FLA
MCA

*Motors are designed for satisfactory operation within 10% of nominal


voltages shown. Voltages should not exceed the limits shown in the
Voltage Range column.
NOTES:
1. MCA and MOCP values are calculated in accordance with NEC
(National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the percent voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
Average Voltage = 393 + 403 + 396
3
1192
=
3
= 397

56

FAN MOTOR
Nominal
Hp
2.9
2.9
5.0
5.0
7.5
7.5
10.0
10.0

POWER SUPPLY
FLA

MCA

MOCP

7.5
3.4
13.2
7.6
19.8
11.4
28.0
16.1

9.4
4.3
16.5
9.5
24.8
14.3
35.0
20.1

15
15
25
15
40
25
60
30

Determine maximum deviation from average voltage.


(AB) 397 393 = 4 v
(BC) 403 397 = 6 v
(AC) 397 396 = 1 v
Maximum deviation is 6 v.
Determine percent voltage imbalance.
6
% Voltage Imbalance = 100 x
397
= 1.5%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.

40RM ALTERNATE MOTORS


UNIT
40RM
016
024
028

VOLTAGE RANGE
V*-PH-Hz
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50

Min

Max

207
360
207
360
207
360

253
440
253
440
253
440

LEGEND
FLA
Full Load Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Range column.
NOTES:
1. Minimum circuit amp and MOCP values are calculated in accordance with NEC (National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the percent voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
Average Voltage =

Nominal
kW
3.73
3.73
5.59
5.59
7.46
7.46

FAN MOTOR
Nominal
Hp
5.0
5.0
7.5
7.5
10.0
10.0

POWER SUPPLY
FLA

MCA

MOCP

13.2
7.6
19.8
11.4
28.0
16.1

16.5
9.5
24.8
14.3
35.0
20.1

25
15
40
25
60
30

Determine maximum deviation from average voltage.


(AB) 397 393 = 4 v
(BC) 403 397 = 6 v
(AC) 397 396 = 1 v
Maximum deviation is 6 v.
Determine percent voltage imbalance.
6
% Voltage Imbalance = 100 x
397
= 1.5%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.

393 + 403 + 396


3
1192
3

= 397

40RM FAN CONTACTOR COIL


UNIT
40RM

VOLTAGE
(vac)

016-034

24

MAXIMUM
HOLDING
VA
10

57

Electrical data (cont)


40RM ELECTRIC HEATER ACCESSORY DATA
UNIT
40RM

FAN MOTOR

HEATER
PART NO.

V-PH-Hz

CAELHEAT016A00

240-3-50

CAELHEAT017A00

400-3-50

CAELHEAT019A00

240-3-50

CAELHEAT020A00

400-3-50

CAELHEAT022A00

240-3-50

CAELHEAT023A00

400-3-50

CAELHEAT025A00

240-3-50

CAELHEAT026A00

400-3-50

CAELHEAT028A00

240-3-50

CAELHEAT029A00

400-3-50

CAELHEAT031A00

240-3-50

CAELHEAT032A00

400-3-50

CAELHEAT034A00

240-3-50

CAELHEAT035A00

400-3-50

CAELHEAT037A00

240-3-50

CAELHEAT038A00

400-3-50

016,024

028,034

FLA
Hp
MCA
MOCP

Hp

kW

FLA

2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0

2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46

7.5
13.2
19.8
3.4
7.6
11.4
7.5
13.2
19.8
3.4
7.6
11.4
7.5
13.2
19.8
3.4
7.6
11.4
7.5
13.2
19.8
3.4
7.6
11.4
19.8
28.0
11.4
16.1
19.8
28.0
11.4
16.1
19.8
28.0
11.4
16.1
19.8
28.0
11.4
16.1

Nominal
Capacity
(kW)
10
10
10
10
10
10
20
20
20
20
20
20
30
30
30
30
30
30
50
50
50
50
50
50
20
20
20
20
40
40
40
40
50
50
50
50
70
70
70
70

LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection

240
480

58

200
0.694

208
0.751

ACTUAL HEATER VOLTAGE


230
240
400
440
0.918
1

0.694
0.84

Stage 1

Stage 2

Total

10.0
10.0
10.0
6.9
6.9
6.9
19.9
19.9
19.9
13.9
13.9
13.9
20.0
20.0
20.0
13.9
13.9
13.9
30.0
30.0
30.0
20.8
20.8
20.8
20.0
20.0
13.9
13.9
20.0
20.0
13.9
13.9
30.0
30.0
20.8
20.8
40.0
40.0
27.8
27.8

10.0
10.0
10.0
6.9
6.9
6.9
20.0
20.0
20.0
13.9
13.9
13.9

20.0
20.0
13.9
13.9
20.0
20.0
13.9
13.9
30.0
30.0
20.8
20.8

10.0
10.0
10.0
6.9
6.9
6.9
19.9
19.9
19.9
13.9
13.9
13.9
30.0
30.0
30.0
20.8
20.8
20.8
50.0
50.0
50.0
34.7
34.7
34.7
19.9
19.9
13.9
13.9
40.0
40.0
27.8
27.8
50.0
50.0
34.7
34.7
70.0
70.0
48.6
48.6

FLA
24.1
24.1
24.1
10.0
10.0
10.0
47.9
47.9
47.9
20.0
20.0
20.0
72.2
72.2
72.2
30.1
30.1
30.1
120.3
120.3
120.3
50.1
50.1
50.1
47.9
47.9
20.0
20.0
96.2
96.2
39.9
39.9
120.3
120.3
50.1
50.1
168.4
168.4
70.2
70.2

MCA*

MOCP*

39.4
46.6
54.8
16.8
22.0
26.8
69.2
76.3
84.6
29.3
45.1
49.2
99.6
106.7
115.0
41.8
47.1
51.8
159.7
166.9
175.1
66.9
72.1
76.9
84.6
94.8
39.3
45.2
145.9
153.3
64.1
70.0
175.1
185.4
76.9
82.8
193.1
203.4
84.4
90.3

40
50
60
20
25
35
70
80
90
30
50
50
100
110
125
50
50
60
175
175
200
70
80
80
90
110
40
50
150
175
70
80
200
200
80
90
200
225
90
100

NOTES:
1. Electric resistance heaters are rated at 240 v and 480 v. To determine heater capacity (kW) at unit nameplate voltage multiply the
capacity (kW) by the factor shown in the table below.
2. The following equation converts kW of heat energy to Btuh: kW x
3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 480 Pa (1.9 in. wg).
5. MCA and MOCP values apply to both standard and alternate
factory-supplied motors.
6. Approximate shipping weight for CAELHEAT016A00-026A00 is
27 kg (60 lb) each. Approximate shipping weight for
CAELHEAT028A00-038A00 is 34 kg (75 lb) each.

*Values shown are for single-point connection of electric heat accessory and air handler.

HEATER RATING
VOLTAGE

ELECTRIC HEATER(S)
Actual Capacity (kW)

460

0.918

480

Controls
Operating sequence 38AKS028-044
When space thermostat calls for cooling, the no. 1 condenser fan and compressor starts after control module
(CM) initial time delay of 7 seconds. If an optional airflow
switch is used, compressor and no. 1 condensing fan will
not start until sufficient indoor airflow has closed the
switch. After 7 seconds the compressor starts and the liquid line solenoid valve (for solenoid drop control) opens.
The crankcase heater is deenergized. If the head pressure
reaches 1793 kPag (260 psig), the second condenser fan
starts.
If cooling demand is low, suction pressure at the compressor drops. As the pressure drops, the compressor
unloads 1 or 2 banks of cylinders, as required. If cooling
demand is high and 2-stage operation is used, the second
step of the thermostat activates the capacity control liquid
line solenoid which activates the second stage evaporator
coil. The compressor cylinders load or unload in response
to compressor suction pressure to meet evaporator load.
For two and a half minutes after the compressor starts,
the low-pressure switch (LPS) ignored. If the LPS trips during the first 2 minutes of operation, the compressor
remains operational. If a high-pressure switch (HPS) trips
at any time, or the LPS trips after 21/2 minutes, the compressor cannot restart until the 3-minute CM anti-short
cycle timer expires.
As the space cooling load is satisfied, the second stage of
the thermostat opens, and closes the field-supplied capacity control liquid line solenoid valve to deactivate the second stage coil. The compressor adjusts the number of
active cylinders to meet the new load. When the space
temperature is satisfied, the first stage of the thermostat
opens and the control relay and opens. This closes the
solenoid drop control valve. The compressor stops and the
crankcase heater is energized, preventing refrigerant from
migrating to the compressor during the off cycle (solenoid
drop refrigerant control). The CM anti-short-cycling timer
is energized and runs for approximately 3 minutes. During
this time, the compressor is not able to restart.
38AH024-034 standard constant volume unit with
2-stage cooling thermostat Seven seconds after a
thermostat call for the first stage of cooling, compressor
no. 1 and the outdoor fans start. The no. 2 fan only starts
if the outdoor ambient temperature is above (21.1 C) 70 F.
The oil-pressure switch and the low-pressure switch are bypassed for the 1 and 21/2 minutes, respectively. If either
the low-pressure switch or oil pressure switch remain open
after the delay, the unit shuts down and goes into alarm
mode. The indoor-fan motor starts immediately whenever there is a call for cooling. If a liquid line solenoid valve
has been installed (for refrigerant control during the off cycle), then the solenoid valve for compressor no. 1 opens
immediately upon a call for cooling.
On standard units, compressor no. 1 operates either fully loaded or at one step of unloading, depending on the
suction pressure, which is dependent on the evaporator
load conditions.
As the cooling demand increases, the thermostat calls
for the second stage of cooling. Within 7 seconds from a
call for the second stage of cooling, compressor no. 2

starts. The oil switch and low-pressure switch for circuit


no. 2 are bypassed during start-up.
As the cooling load is satisfied, the thermostat stops the
call for the second stage of cooling, which in turn deenergizes compressor no. 2, closes the no. 2 liquid line solenoid (if installed) and energizes the compressor no. 2
crankcase heater.
If the space temperature continues to decrease, then the
thermostat stops the call for the first stage of cooling,
which then deenergizes compressor no. 1 and the outdoor
fans, closes the no. 1 liquid line solenoid valve (if installed),
and energizes the compressor no. 1 crankcase heater.
The unit controls prevent both compressors from reenergizing within 3 minutes from a previous call for operation.
If the unit safeties trip during operation, refer to the
Installation, Start-Up and Service instructions. To reset the
lockout mode, cycle the unit power.
NOTE: If the thermostat fan switch is in the auto position,
the indoor fan cycles on and off as the thermostat calls for
cooling (or heating). If the switch is in the continuous position, the fan runs when the outdoor unit is powered.
38AH024-034 optional variable air volume unit
with ModuPanel control The ModuPanel control
regulates up to 10 stages of cooling to maintain a leavingair temperature for variable air volume (VAV) applications.
When connected to one 38AH condensing unit, only
6 stages are used. See the table on page 60 for unit loading and compressor operating sequence.
When the timeclock connected to the panel closes, the
indoor-fan contactor is energized through a field-supplied
relay. (The relay must be a pilot-duty SPST relay with
115-v coil and 30 va maximum coil draw.) After the time
delays programmed into the ModuPanel control have
elapsed, and with the leaving air above the set point, the
stages of mechanical cooling are sequenced as follows:
1. Stage 1 starts compressor no. 1 with 2 banks of cylinders unloaded (1/3 loaded). Both unloader solenoids
are energized.
2. Stage 2 loads one bank of compressor no. 1 cylinders
(2/3 loaded) by deenergizing unloader solenoid no. 1.
3. Stage 3 loads the second bank of compressor no. 1
by deenergizing unloader solenoid no. 2.
4. Stage 4 starts compressor no. 2 and unloads 2 banks
of compressor no. 1 cylinders unloaded (1/3 loaded).
Both unloader solenoids are energized.
5. Stage 5 loads one bank of compressor no. 1 cylinders
(2/3 loaded) by deenergizing unloader solenoid no. 1.
6. Stage 6 loads one bank of compressor no. 1 cylinders
(fully loaded) by deenergizing unloader solenoid no. 2.

59

Controls (cont)
Two 38AH024-034 optional variable air volume
units with a single ModuPanel control The
ModuPanel control regulates up to 10 stages of cooling to
maintain a leaving-air temperature for variable air volume
(VAV) applications. When connected to two 38AH condensing units, all 10 stages are used. See the table below
for unit loading and compressor operating sequence.
When the timeclock connected to the panel closes, the
indoor-fan contactor is energized through a field-supplied
relay. (The relay must be a pilot-duty SPST relay with
115-v coil and 30 va maximum coil draw.) After the time
delays programmed into the ModuPanel control have
elapsed, and with the leaving air above the set point, the
stages of mechanical cooling are sequenced as follows:
1. Stage 1 starts unit no. 1 compressor no. 1 with
2 banks of cylinders unloaded (1/3 loaded). Both
unloader solenoids are energized.
2. Stage 2 loads one bank of unit no. 1 compressor
no. 1 cylinders (2/3 loaded) by deenergizing unloader
solenoid no. 1.
3. Stage 3 turns off unit no. 1 compressor no. 1 and
starts compressor no. 2 fully loaded.
4. Stage 4 starts unit no. 1 compressor no. 1 with 2
banks of cylinders unloaded (1/3 loaded). Both
unloader solenoids are energized.
5. Stage 5 loads one bank of unit no. 1 compressor
no. 1 cylinders (2/3 loaded) by deenergizing unloader
solenoid no. 1.
6. Stage 6 loads one bank of unit no. 1 compressor
no. 1 cylinders (fully loaded) by deenergizing unloader
solenoid no. 2.

7. Stage 7 starts unit no. 2 compressor no. 1 with 2


banks of cylinders unloaded (1/3 loaded). Both
unloader solenoids are energized.
8. Stage 8 turns off unit no. 2 compressor no. 1 and
starts compressor no. 2 fully loaded.
9. Stage 9 starts unit no. 2 compressor no. 1 with
2 banks of cylinders unloaded (1/3 loaded). Both
unloader solenoids are energized.
10. Stage 10 loads 2 banks of unit no. 2 compressor
no. 1 cylinders (fully loaded) by deenergizing both
unloader solenoids.
Restart Manual reset of the 24-v control circuit is required if unit is shut down by any of the safety devices. Applicable devices include the high pressure switch (HPS),
low-pressure switch (LPS), oil-pressure switch (OPS), and
compressor overtemperature protection (COTP) switch.
To restart the unit after the unit has been shut down, raise
the thermostat set point above the space temperature
(thereby removing the call for cooling) and then lower the
set point back to the desired setting.
If unit circuit breakers trip during unit shutdown, they
must be reset manually.

Causes of complete unit shutdown:

interruption of supplied power


open compressor overtemperature protection (COTP)
compressor electrical overload protection (CB1 or CB2)
open high-pressure or low-pressure safety switches
open oil pressure switch

38AH UNIT LOADING SEQUENCE WITH MODUPANEL CONTROL


STAGE

NO. CYLINDERS

1
2
3
4
5
6

2
4
6
8
10
12

LOADED CYLINDERS
Compressor No. 1
Compressor No. 2
2

2
6
4
6
6
6

CAPACITY STEP (%)


17
33
50
67
83
100

LOADING SEQUENCE, TWO 38AH CONDENSING UNITS WITH MODUPANEL CONTROL

60

STAGE

NO. CYLINDERS

1
2
3
4
5
6
7
8
9
10

2
4
6
8
10
12
14
18
20
24

UNIT 1 LOADED CYLINDERS


Compressor
Compressor
No. 1
No. 2
2

6
2
6
4
6
6
6
6
6
6
6
6
6
6
6

UNIT 2 LOADED CYLINDERS


Compressor
Compressor
No. 1
No. 2

6
2
6
6
6

CAPACITY STEP (%)


8
17
25
33
41
50
58
75
83
100

CARRIER CONTROLS

DEBONAIR COMMERCIAL PROGRAMMABLE


THERMOSTAT

COMMERCIAL ELECTRONIC THERMOSTAT

Carrier

Pm
COOL

AUTO
HEAT

PREMIERLINK COMMUNICATING CONTROLS

61

Typical control wiring schematic


38AKS028-044

62

38AKS028-044 (cont)

AFS
ATS
C
CB
CH
CM
COMP
CR
EQUIP
FC
FCPS
FM
FR
FU
GND
HPS
LLSV
LPS
MM
MMF
MMPT

LEGEND
Airflow Switch
Air Temperature Switch
Contactor, Compressor
Circuit Breaker
Crankcase Heater
Control Module
Compressor
Control Relay
Equipment
Fan Contactor
Fan Cycling Pressure Switch
Fan Motor
Fan Relay
Fuse
Ground
High-Pressure Switch
Liquid Line Solenoid Valve
Low-Pressure Switch
Motormaster
Motormaster Fuse
Motormaster Pressure Transducer

NEC
OPS
TB
TC
TDR
TRAN

National Electrical Code


(U.S.A. Standard)
Oil Pressure Switch
Terminal Block
Thermostat-Cooling
Time Delay Relay
Transformer
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Marked Splice
Unmarked Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Indicates Common Potential, Does Not Represent Wiring

63

Typical control wiring schematic (cont)


38AH024-034

SEE MODUPANEL ACCESSORY INSTALLATION FOR SCHEMATIC

64

38AH024-034 (cont)

ATS
C

CB

CH

CM

COMP
COTP
CR

EQUIP
FC

FIOP
FM

FR

FU

GND
HPS
IFC

LLSV
LPS
MM

MMF
MMPT
MPR
NEC
OPS

LEGEND
Air Temperature Switch
Contactor, Compressor
Circuit Breaker
Crankcase Heater
Control Module
Compressor
Compressor Overtemperature
Protection
Control Relay
Equipment
Fan Contactor
Factory-Installed Option
Fan Motor
Fan Relay
Fuseblock
Ground
High-Pressure Switch
Indoor-Fan Contactor
Liquid Line SolenoidValve
Low-Pressure Switch
Motormaster
Fuse
Pressure Transducer
ModuPanel Relay
National Electrical Code (U.S.A. Standard)
Oil Pressure Switch

PL
TB
TRAN
U
VAV

Plug Assembly
Terminal Block
Transformer
Unloader
Variable Air Volume
Plug
Receptacle
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Marked Splice
Unmarked Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Indicates Common Potential,
Does Not Represent Wiring

65

Application data 38AKS units


Installation
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit
cycling, and less part-load operation.
When selecting vapor line sizes, oil return should be
evaluated, particularly at part-load conditions.
The evaporator fan must always be operating when outdoor fan is operating.
Unit cycles should be limited to 3 or less.
Multiple outdoor units may be used with a single indoor
unit. This involves multiple refrigeration circuits.
IMPORTANT: When application is in a variable air volume (VAV) system, total building load is not the sum of
the individual peak loads. If individual peak loads are
summed, the equipment tends to be oversized for the
load.

MINIMUM OUTDOOR-AIR OPERATING


TEMPERATURE
COMUNIT PRESSOR
38AKS CAPACITY
(%)

028
034
044

SATURATED
CONDENSING
TEMPERATURE
C
32
27
21
32
27
21
32
27
21

100
67
33
100
67
33
100
67
33

F
90
80
70
90
80
70
90
80
70

MAXIMUM LIQUID LIFT


MAXIMUM LIQUID LIFT
m
ft
23
76
20
67
23
76

UNIT 38AKS

To minimize return-air temperature extremes, use the


equipment room as a return-air plenum when applying
VAV systems with supply-to-return air recycle as used with
Carrier VVT (variable volume and temperature) Control
Systems.
Indoor equipment should be selected at no less than
40 L/s per kW (300 cfm/ton).

MIN OUTDOOR
TEMPERATURE
With
Base
Low Ambient
Unit
Control
C
F
C
F
6
31
1.7
35
1
34
1
30
1
34 29
20
5.5
42
3.9 25
1
30
1.7
35

028
034
044

SUCTION LINE PIPING

IMPORTANT: Condensing units applied in VVT or VAV


systems must have a field-supplied and installed accumulator. Order part number 38AK500410 from Service
Parts.
OPERATING LIMITS
Maximum Outdoor Ambient
Minimum Cooling Load
Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
Minimum Discharge
Superheat

66

46 C (115 F)
Additional head pressure control may be required below
1.7 C (35 F) outdoor ambient.
12.8 C (55 F)
35 C (95 F)
1.1 to 12.8 C (30 to 55 F)
146 C (295 F)
15.6 C (60 F)

LEGEND
A
B
C
D

Suction riser without trap


Suction riser with trap
Suction line to condensing unit
Short vertical riser:
38AKS028 15/8 in. OD
38AKS034,044 21/8 in. OD

REFRIGERANT PIPE SIZES (Single Suction Risers)


UNIT
38AKS
028
034
044

LENGTH OF INTERCONNECTING PIPING m (ft)


7.9-15.2 (26-50)
15.5-22.8 (51-75)
23.2-30.5 (76-100)
L
S
L
S
L
S
7/
7/
7/
21/8*
21/8*
21 / 8 *
8
8
8
7/8
7/8
21 / 8
21 / 8
11 / 8
21 / 8
7/8
21 / 8
11 / 8
25/8*
11 / 8
25 / 8 *

4.9-7.6 (16-25)
L
S
7/
15 / 8
8
7/
21 / 8
8
7/8
21 / 8

LEGEND
L Liquid Line
S Suction Line

30.8-60.9 (101-200)
L
S
7/
21 / 8 *
8
11 / 8
25 / 8 *
11 / 8
25 / 8 *

NOTE: All line sizes are inches OD.


*IMPORTANT If condensing unit is above air handler, a double
suction riser is required. See table below for sizing.

REFRIGERANT PIPING SIZES (Double Suction Risers)


UNIT
38AKS
028
034
044

7.9-15.2 (26-50)
A
B
C
15 / 8
15 / 8
21 / 8

LENGTH OF INTERCONNECTING PIPING m (ft)


15.5-22.8 (51-75)
23.2-30.5 (76-100)
A
B
C
A
B
C
15 / 8
15 / 8
21 / 8
15 / 8
15 / 8
21 / 8

15 / 8
21 / 8
25 / 8
15 / 8
21 / 8
25 / 8

30.8-60.9 (101-200)
A
B
C
15 / 8
15 / 8
21 / 8
15 / 8
21 / 8
25 / 8
15 / 8
21 / 8
25 / 8

NOTE: A, B, C dimensions relate to reference diagram.

Multiple condensing unit arrangements*

38AKS028-044

38AKS028-044

38AKS028-044 ONLY
Space for Service and Airflow
*For clearances between controls and grounded surfaces,
check local codes.
Observe minimum recommended space requirements.
38AKS
028-044

DIMENSIONS m (ft)
A
B
1.2 (4)
1.2 (4)

67

Application data 38AH units


Installation
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling, and less part-load operation.
When selecting vapor line sizes, oil return must be evaluated, particularly at part-load conditions.
The indoor fan must always be operating when outdoor
unit is operating.
IMPORTANT: When application is in a VAV (variable
air volume) system, total building load is not the sum of
the individual peak loads. If individual peak loads are
summed, the equipment tends to be oversized for the
load.
To minimize return-air temperature extremes, use the
equipment room as a return-air plenum when applying
VVT (variable volume temperature) systems with supplyto-return air recycle as used with Carrier VVT control
systems.
Ductwork should be sized according to unit size, not
building load.

To minimize the possibility of air recirculation, avoid the


use of concentric supply/return grilles.
Indoor equipment should be selected at no less than
40 L/s per kW (300 cfm/ton).
IMPORTANT: Condensing units applied in VVT or
VAV systems must have field-supplied and installed accumulators. Order 2 part number --KH--73LZ-001
from
Service Parts (1 required for each refrigerant
OPERATING LIMITS
Maximum Outdoor Ambient
Minimum Outdoor Ambient
Minimum Return-Air Temperature
Maximum Return-Air Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge Temperature
Minimum Discharge Superheat

UNLOADING SEQUENCES
UNIT
38AH
024
028
034

CAPACITY/STAGE (%)
CV Units (Standard)*
VAV Units (Optional)
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 85, 43, 28
100, 85, 71, 43, 28, 14

LEGEND
CV Constant Volume
VAV Variable Air Volume
*Additional unloading available with field-installed accessory unloader.
NOTE: Capacities are based on 7.2 C (45 F) saturated suction temperature and 35 C
(95 F) outdoor air temperature.

MINIMUM OUTDOOR-AIR OPERATING


TEMPERATURE AND UNLOADING SEQUENCES
UNIT
38AH

024

028

034

SYSTEM
CAPACITY (%)
100
83
67
50
33
17
100
83
67
50
33
17
100
85
71
43
28
14

MINIMUM OUTDOOR-AIR TEMP


Standard Unit
Low Ambient Control
C
F
C
F
29
20
29
20
*
*
11.7
53
29
20
29
20
*
*
29
20
29
20
*
*
10.0
50
29
20
29
20
*
*
29
20
29
20
*
*
9.4
49
29
20
29
20
*
*

*Motormaster V cannot be used with 2 unloaders.


VAV or accessory unloader on Circuit 1.
NOTE: Minimum outdoor-air operating temperature is based on 32 C (90 F) saturated condensing
temperature and 100% capacity.

68

52 C (125 F)
See Minimum Outdoor-Air
Operating Temperature
table below.
12.8 C (55 F)
35 C (95 F)
6.6 to 10.0 C (20 to 50 F)
135 C (275 F)
15.6 C (60 F)

REFRIGERANT PIPE SIZES


SINGLE SUCTION RISERS
UNIT
38AH

0-25 (0-7.6)

LENGTH OF INTERCONNECTING PIPING, FOR EACH CIRCUIT FT (M)


25-50 (7.6-15.2)
50-75 (15.2-22.9)
75-100 (22.9-30.5)
L
S
L
S
L
S
5/8
5/8
5/8
13 / 8
13 / 8
13 / 8
5/
5/
5/
13 / 8
13 / 8
13 / 8
8
8
8

100-200 (30.5-61.0)
L
S
7/8
15/8*
7/
15/8*
8

024 Ckt 1
Ckt 2

L
1/
2
1/
2

S
11 / 8
11 / 8

028 Ckt 1
Ckt 2

1/2
1/
2

11 / 8
11 / 8

5/8
5/
8

13 / 8
13 / 8

5/8
5/
8

13 / 8
13 / 8

5/8
5/
8

13 / 8
13 / 8

7/8
7/
8

15/8*
15/8*

034 Ckt 1
Ckt 2

1/
2
5/8

11 / 8
13 / 8

5/
8
5/8

13 / 8
15 / 8

5/
8
5/8

13 / 8
15 / 8

5/
8
7/8

13 / 8
15 / 8

7/
8
7/8

15/8*
21/8*

LEGEND
L Liquid Line
S Suction Line
*Double suction riser required if evaporator is below condensing unit
and 2 unloaders are used on that circuit.
Double suction riser required if evaporator is below condensing unit
and compressor is equipped with 2 unloaders. Note the only time
circuit no. 2 may be equipped with 2 unloaders is if it is serving its own
air handler and the unit does not require low ambient operation
(Motormaster control).

NOTES:
1. All line sizes are inches OD.
2. Standard unit comes with one pressure-operated unloader on circuit no. 1. If unit serves one air handler, an additional unloader
may be field installed on circuit no. 1 compressor only. If the unit
serves 2 separate air handlers and low ambient operation is
required (Motormaster V control), each circuits compressor may
only be equipped with one unloader.
3. Equivalent line sizes in mm follow:
in.
1/2
5/8
7/
8
11/8

mm
12.7
15.9
22.2
28.6

in.
13/8
15/8
21/8

mm
34.9
41.3
54.0

DOUBLE SUCTION RISERS


UNIT
38AH
024 Ckt 1
Ckt 2

LENGTH OF INTERCONNECTING PIPING FT (M)


100-200 (30.5-61.0)
A
B
C
13/8
15/8
11/8
13/8
13/8
15/8

028 Ckt 1
Ckt 2

11/8
11/8

13/8
13/8

15/8
15/8

034 Ckt 1
Ckt 2

11/8
13/8

13/8
15/8

15/8
21/8

MAXIMUM LIQUID LIFT


UNIT
38AH
024
028
034

MAXIMUM LIQUID LIFT


PER CIRCUIT M (Ft)
23.2 ( 76)
22.3 ( 73)
30.5 (100)

LEGEND
Suction Riser without Trap
Suction Riser with Trap
Suction Line to Condensing Unit
Pipe Diameter to be Same Size as Riser A

69

Application data 38AH units (cont)


MULTIPLE CONDENSING UNIT ARRANGEMENTS

Space for Service and Airflow


*For clearances between controls and grounded surfaces, check local codes.
38AH
024
028
034

70

DIMENSIONS m (ft)
A
B
1.2 (4)

1.2 (4)

Application data 40RM units


Operating limits
Maximum fan speed
40RM016,024 . . . . . . . . . . . . . . . .20 r/s (1200 rpm)
Maximum fan speed
40RM028,034 . . . . . . . . . . . . . . 18.3 r/s (1100 rpm)

General
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling,
and less part-load operation. Equipment should be selected
to perform at no less than 40 L/s per kW (300 cfm/ton).

The air handler fan must always be operating when the


condensing unit is operating.
Ductwork should be sized according to unit size, not building load. For larger units with two fans, a split duct transition
is recommended at the fan outlets, but a plenum can be used
with slight reduction in external static pressure capability.
For variable air volume (VAV) systems with supply-toreturn air recycling, use the equipment room as a return air
plenum.

FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA


UNIT
40RM

COIL
TYPE

TXV
Qty...Part No.*

DISTRIBUTOR
Qty...Part No.

016

3 Row
4 Row

2...TDEBX8
2...TDEBX8

2...1116
2...1126

FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
12...1/4
16...1/4

024

3 Row
4 Row

2...TDEBX11
2...TDEBX11

2...1116
2...1126

13...1/4
18...3/16

2...E8
2...C8

028

3 Row
4 Row

2...TDEBX11
2...TDEBX11

2...1126
2...1126

15...1/4
20...3/16

2...C10
2...C15

034

3 Row
4 Row

2...TDEBX16
2...TDEBX16

2...1126
2...1126

18...1/4
24...3/16

2...C12
2...C17

NOZZLE
Qty...Part No.
2...E6
2...C6

*Danfoss part numbers shown.


Sporlan Valve Co. part numbers shown.
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.

40RM FAN MOTOR DATA


STANDARD MOTOR SI
UNIT
40RM
230-3-50 and 400-3-50
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)

STANDARD MOTOR ENGLISH

016

024

028

034

23.75
2.16
56Y
22.2

23.75
3.73
184T
28.6

23.75
5.59
S213T
34.9

23.75
7.46
S215T
34.9

NEMA National Electrical Manufacturers Association (U.S.A.)


ALTERNATE MOTOR SI
UNIT
40RM
230-3-50 and 400-3-50
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)

UNIT
40RM
230-3-50 and 400-3-50
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

016

024

028

034

1425
2.9
56Y
7/8

1425
5.0
184T
11 / 8

1425
7.5
S213T
13 / 8

1425
10.0
S215T
13/8

NEMA National Electrical Manufacturers Association (U.S.A.)


ALTERNATE MOTOR ENGLISH

016

024

028

23.75
3.73
S184T
28.6

23.75
5.59
S213T
34.9

23.75
7.46
S215T
34.9

NEMA National Electrical Manufacturers Association (U.S.A.)

UNIT
40RM
230-3-50 and 400-3-50
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

016

024

028

1425
5.0
S184T
11/8

1425
7.5
S213T
13/8

1425
10.0
S215T
13/8

NEMA National Electrical Manufacturers Association (U.S.A.)

71

Application data 40RM units (cont)


40RM DRIVE DATA
STANDARD DRIVE SI
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(mm)

HIGH-STATIC DRIVE SI

016

024

028

034

86.4111.8

109.2134.6

109.2134.6

109.2134.6

2.5

3.0

3.0

3.0

229
36.5
1A
1074

218
36.5
1B
1062

279
49.2
2B
1113

279
49.2
2B
1113

10.3
9.011.6
20.0

13.3
11.914.6
20.0

10.4
9.311.5
18.3

10.4
9.311.5
18.3

0.265

0.230

0.180

0.180

265313

232279

169240

169240

MEDIUM-STATIC DRIVE SI
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(mm)

72

016

024

028

034

94.0119.4

101.6127.0

109.2134.6

109.2134.6

3.0

2.5

3.0

3.0

201
36.5
1B
1011

178
36.5
2A
922

239
49.2
2B
1011

239
49.2
2B
1011

12.6
11.114.1
20.0

15.3
13.617.0
20.0

12.1
10.913.4
18.3

12.1
10.913.4
18.3

0.252

0.340

0.210

0.210

232279

232279

169240

169240

UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(mm)

016

024

028

034

101.6127.0

101.6127.0

109.2134.6

109.2134.6

3.0

3.0

3.0

3.0

178
36.5
2A
998

163
36.5
2A
871

203
49.2
2B
935

218
49.2
2B
960

15.3
13.617.0
20.0

16.7
14.918.6
20.0

14.3
12.815.7
18.3

13.3
11.914.6
18.3

0.283

0.308

0.247

0.230

207255

169240

232279

169240

40RM DRIVE DATA (cont)


STANDARD DRIVE ENGLISH
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

HIGH-STATIC DRIVE ENGLISH

016

024

028

034

3.4-4.4

4.3-5.3

4.3-5.3

4.3-5.3

2.5

3.0

3.0

3.0

9.0
17/16
1A
42.3

8.6
17/16
1B
41.8

11.0
115/16
2B
43.8

11.0
115/16
2B
43.8

618
538697
1200

795
713878
1200

622
557687
1100

622
557687
1100

15.9

13.8

10.8

10.8

10.4412.32

9.1210.99

6.679.43

6.679.43

UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

016

024

028

034

4.0-5.0

4.0-5.0

4.3-5.3

4.3-5.3

3.0

3.0

3.0

3.0

7.0
17/16
2A
39.3

6.4
17/16
2A
34.3

8.0
115/16
2B
36.8

8.6
115/16
2B
37.8

916
8141018
1200

1002
8911113
1200

855
766944
1100

795
713878
1100

17.0

18.5

14.8

13.8

9.1610.99

8.1610.02

6.679.43

6.679.43

MEDIUM-STATIC DRIVE ENGLISH


UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

016

024

028

034

3.7-4.7

4.0-5.0

4.3-5.3

4.3-5.3

3.0

2.5

3.0

3.0

7.9
17/16
1B
39.8

7.0
17/16
2A
36.8

9.4
115/16
2B
39.8

9.4
115/16
2B
39.8

756
667848
1200

916
8141018
1200

728
652803
1100

728
652803
1100

15.1

20.4

12.6

12.6

9.1610.99

9.1610.99

6.679.43

6.679.43

73

Guide specifications 38AKS units


Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 82.8 to 127.0 kW (23.5 to 35.8 Tons),
Nominal
Carrier Model Number: 38AKS
Part 1 General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable
for on-the-ground or rooftop installation. Unit shall
consist of a semi-hermetic reciprocating compressor,
an air-cooled coil, propeller-type condenser fans, and
a control box. Unit shall discharge supply air upward
as shown on contract drawings. Unit shall be used in
a refrigeration circuit to match a packaged airhandling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard
360 (U.S.A. standard).
B. Unit shall be manufactured in a facility registered to
ISO 9001:2000 manufacturing quality standard.
C. Unit construction shall comply with ANSI/ASHRAE
15 latest revision safety code and comply with NEC
(U.S.A. standards).
D. Unit shall be constructed in accordance with UL
standards (U.S.A.).
E. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(U.S.A.) (scribed specimen).
F. Air-cooled condenser coils shall be leak tested at
1034 kPa (150 psig) and pressure tested at 3310 kPa
(480 psig).
1.03 DELIVERY, STORAGE AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled per unit manufacturers
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be
all factory wiring, piping, controls, compressor, holding charge (R-22), and special features required prior
to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized
steel, bonderized and coated with a prepainted,
baked enamel finish.
2. End unit access panel shall be hinged for compressor and control box service access.
3. Lifting holes shall be provided to facilitate
rigging.

74

C. Fans:
1. Condenser fans shall be direct-driven propeller
type, discharging air vertically upward.
2. Condenser fan motors shall be totally enclosed,
3-phase type with class B insulation and with
permanently lubricated bearings.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressor:
1. Compressor shall be reciprocating, serviceable,
semi-hermetic type.
2. Compressor shall be equipped with an automatically reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an
insert-type, factory-sized crankcase heater to
control oil dilution.
3. Compressor shall be mounted on spring vibration isolators with an isolation efficiency of no
less than 95%.
4. Compressor speed shall not exceed 24.2 r/s
(1450 rpm).
5. Compressor shall unload using suction cutoff
unloading (electrical solenoid unloading shall be
available as an accessory).
E. Condenser Coil:
1. Condenser coil shall be air cooled, circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins
mechanically bonded to internally grooved,
seamless copper tubes which are then cleaned,
dehydrated, and sealed. Epoxy phenolic fin coating shall be available as an option.
3. Coil shall be protected by a sheet metal casing to
eliminate the need for wind baffles for low ambient temperature operation.
4. Coil shall be protected to avoid damage due to
the elements and vandalism.
F. Refrigeration Components:
Refrigeration circuit components shall include hot gas
muffler, high-side pressure relief device, liquid line shutoff valve, suction and discharge shutoff valves, holding
charge of refrigerant R-22, and compressor oil.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Three-minute recycle protection to prevent
compressor short-cycling.
c. Lockout on auto-reset safety until reset from
thermostat.

d. Capacity control on the compressor shall be


by suction cutoff unloaders in response to
compressor suction pressure. Electric
solenoid unloading shall be available as an
accessory.
e. A solenoid valve shall be provided for solenoid drop control.
f. Head pressure control to 6 C (31 F) by fan
cycling. One condenser fan shall be cycled by
discharge pressure to maintain proper head
pressure.
g. Winter start control to prevent nuisance tripouts at low ambient temperatures.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at control circuit power supply)
a. High discharge-pressure cutout.
b. Low suction-pressure cutout.
c. Condenser fan motors to be protected
against overload or single-phase condition by
internal overloads.
Manual reset at the unit
a. Low oil-pressure cutout.
b. Compressor electrical overload protection
through the use of definite-purpose contactors and calibrated, ambient-compensated,
magnetic-trip circuit breakers. Circuit breakers shall open all 3 phases in the event of an
overload in any one of the phases or a
single-phase condition.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed
at a suction temperature of
. The power consumption at full load shall
kW.
not exceed
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of
or greater at conditions of:
entering-air temperature at the
evaporator at
wet bulb and
dry
bulb, and air entering the condensing unit at
.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
v, 3-ph, 50 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
v to
v.
2. Unit electrical power shall be single point
connection.
3. Unit control circuit shall contain a 24-v transformer for unit control, with capacity to operate
an indoor fan interlock.
J. Special Features:
1. Low-Ambient Control:
Control shall regulate fan motor speed in
response to the saturated condensing temperature

2.

3.

4.

5.

6.

7.

of the unit. The control shall be capable of maintaining a condensing temperature of 37.8 C
(100 F) 5.6 C (10 F) with outdoor temperatures at 28 C (20 F). (Motor change required.)
Electric Solenoid Unloader:
Unloader valve piston, coil, and hardware shall
be supplied to convert any pressure-operated
compressor unloader to 220-v electric unloading. Accessory ModuPanel control box or fieldsupplied step controller shall be provided for
electrical unloading.
Hot-Gas Bypass:
A hot-gas bypass valve and a pilot line solenoid
valve shall be provided for low-load operation of
the refrigeration system.
Part-Winding Start:
Part-winding start shall be provided to reduce
inrush current and locked rotor amps on
start-up.
Gage Panel:
A gage panel package shall be provided which
includes a suction and discharge pressure gage
for the refrigerant circuit.
ModuPanel Control Box:
Control box shall be provided to allow system to
operate as a VAV (variable air volume) system.
Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive
coastal environments. Coating shall be
applied to the aluminum fin stock prior to the
fin stamping process to create an inert barrier
between the aluminum fin and copper tube.
Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.
b. Copper-Fin Coils:
Shall be constructed of copper-fins mechanically bonded to copper-tubes All copper construction shall provide protection in moderate
coastal environments.
c. E-Coated Aluminum-Fin Coils:
Shall have a flexible epoxy polymer coating
uniformly applied to all coil surface areas
without material bridging between fins.
Coating process shall ensure complete coil
encapsulation. Color shall be high gloss
black with gloss requirements of 60 of 65
to 90% per ASTM D523-89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior
hardness characteristics of 2H per ASTM
D3363-92A and cross hatch adhesion of
4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in./lb (ASTM
D2794-93). Humidity and water immersion
resistance shall be up to a minimum of 1000
75

Guide specifications 38AKS units (cont)


and 250 hours respectively (ASTM D224792 and ASTM D870-92). Corrosion durability shall be confirmed through testing to no
less than 1000 hours salt spray per ASTM
B117-90. Coil construction shall be aluminum fins mechanically bonded to copper
tubes. (U.S.A. standards.)
d. E-Coated Copper-Fin Coils:
Shall have a flexible epoxy polymer coating
uniformly applied to all coil surface areas
without material bridging between fins.
Coating process shall ensure complete coil
encapsulation. Color shall be high gloss
black with gloss requirements of 60 of 65
to 90% per ASTM D523-89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior
hardness characteristics of 2H per ASTM
D3363-92A and cross hatch adhesion of
4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in./lb (ASTM
D2794-93). Humidity and water immersion
resistance shall be up to a minimum of 1000
and 250 hours respectively (ASTM D224792 and ASTM D870-92). Corrosion durability shall be confirmed through testing to no
less than 1000 hours salt spray per ASTM
B117-90. Coil construction shall be copperfins mechanically bonded to copper tubes
with copper tube sheets. Galvanized steel

76

tube sheets shall not be acceptable. A polymer strip shall prevent coil assembly from
contacting sheet metal coil pan to maintain
coating integrity and minimize corrosion
potential between the coil and pan. (U.S.A.
standards.)
8. Thermostat Controls:
a. Debonair programmable multi-stage thermostat with 7-day clock, holiday scheduling,
large Thermoglow display, remote sensor
capability, and Title 24 compliance.
b. Commercial Electronic Thermostat with
7-day timeclock, auto-changeover, multistage capability, and large LCD temperature
display.
c. Non-programmable thermostat with fan
switch subbase.
d. Carrier PremierLink Controls:
This control will function with CCN and
ComfortVIEW software. It shall also be
compatible with ComfortLink controllers.
It shall be ASHRAE 62-99 (U.S.A.) compliant and Internet ready. It shall accept a CO2
sensor in the conditioned space and be
Demand Control Ventilation (DCV) ready.
The communication rate must be 38.4K or
faster. It shall include an integrated economizer controller.

Guide specifications 38AH units


Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 63 to 87 kW (18 to 25 Tons), Nominal
Carrier Model Number: 38AH
Part 1 General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit
shall have 2 independent refrigeration circuits and
shall consist of dual semi-hermetic reciprocating
compressors, air-cooled coils, propeller-type condenser fans, and a control box. Unit shall discharge
supply air upward as shown on contract drawings.
Unit shall be used in refrigeration circuit matched
with a packaged fan-coil unit or direct-expansion
cooler.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard
365 (U.S.A. standard).
B. Unit construction shall comply with latest edition of
ANSI/ASHRAE and with NEC (U.S.A. standard).
C. Unit shall be manufactured in a facility registered to
ISO 9001:2000 manufacturing quality standard.
D. Unit shall be constructed in accordance with UL
standards (U.S.A.).
E. Unit cabinet shall be capable of withstanding
500-hour salt-spray exposure per ASTM B117
(U.S.A) (scribed specimen).
F. Air-cooled condenser coils shall be leak tested
at 1034 kPa (150 psig) and pressure tested at
3310 kPa (480 psig).
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled per unit manufacturers
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER)
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory assembled, single-piece, air-cooled condensing unit. Contained within the unit enclosure shall be
all factory wiring, piping, controls, compressors,
holding charge, and special features required prior
to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized
steel, bonderized and coated with a prepainted,
baked enamel finish.
2. Unit access panels shall be hinged for control
box service access.
3. Lifting holes shall be provided to facilitate
rigging.

C. Fans:
1. Condenser fans shall be direct-drive propeller
type, discharging air vertically upward.
2. Condenser fan motors shall be 3-phase type
with class B insulation and permanently lubricated bearings.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. Compressors shall be manufactured by the condensing unit manufacturer, and shall be serviceable, reciprocating, semi-hermetic type.
2. Compressors shall be equipped with an automatically reversible oil pump, operating oil
charge, suction and discharge shutoff valves,
and an insert-type factory-sized crankcase
heater to control oil dilution.
3. Compressors shall be mounted on spring vibration isolators with an isolation efficiency of no
less than 95%.
4. Compressor speed shall not exceed 24.3 r/s
(1460 rpm).
5. Lead compressor shall unload using suction cutoff unloading (electrical solenoid unloading shall
be available as an accessory).
E. Condenser Coils:
1. Condenser coils shall be air cooled, circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins
mechanically bonded to internally grooved,
seamless copper tubes which are then cleaned,
dehydrated, and sealed. Copper fins, E-Coated
or pre-coated aluminum fins shall be available
as options.
F. Refrigeration Components:
Refrigeration circuit components shall include hot
gas muffler, high-side pressure relief device, liquid
line shutoff valve, suction and discharge shutoff
valves, holding charge, and compressor oil.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Three-minute recycle protection to prevent
compressor short-cycling.
c. Lockout on auto-reset safety until reset from
thermostat.
d. Capacity control on the lead compressor
shall be by suction cutoff unloaders in
response to compressor suction pressure.
Electric solenoid unloading shall be available
as an accessory.

77

Guide specifications 38AH units (cont)


e. Head pressure control for mild ambient temperature operation by fan cycling. One
condenser fan shall be cycled by ambient temperature to maintain proper head pressure.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at thermostat)
a. High discharge-temperature cutout.
b. Low suction-pressure cutout.
c. Condenser fan motors to be protected
against overloads or single-phase condition
by internal overloads.
d. Low oil-pressure cutout.
Manual reset at the unit
a. Electrical overload protection through the
use of definite-purpose contactors and calibrated, ambient compensated, magnetic trip
circuit breakers. Circuit breakers shall open
all 3 phases in the event of an overload
in any one of the phases or a single-phase
condition.
b. High discharge-pressure cutout.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed __________ at a suction temperature
of __________ . The power consumption at full
load shall not exceed __________ kW.
2. The combination of the condensing unit and
the evaporator or fan coil unit shall have a total
net cooling capacity of __________ or greater at
an airflow rate of __________ entering-air temperature at the evaporator at __________ wet
bulb and __________ dry bulb, and air entering
the condensing unit at __________ .
3. The system shall have an EER of __________ or
greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
_____ v, 3-ph, 50 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
_____ v to _____ v.
2. Unit electrical power shall be single point
connection.
3. Unit control circuit shall be 230 v for 400 v and
230 v units, or 200 v for 346 v units.
J. Special Features:
Certain standard features are not applicable when
the features designated * are specified. For assistance in amending the specifications, your local
Carrier Sales Office should be contacted.
1. VAV (Variable Air Volume) Modification:
Unit shall be supplied from the factory with necessary wiring modifications for connection to a
field-supplied VAV discharge air controller. The
VAV modification shall include 2 electric
unloaders on the lead compressor.

78

2. Optional Condenser Coil Materials:


a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive
coastal environments. Coating shall be
applied to the aluminum fin stock prior to
the fin stamping process to create an inert
barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize galvanic action between dissimilar
metals.
b. Copper-Fin Coils:
Shall be constructed of copper fins mechanically bonded to copper tubes and copper
tube sheets. Galvanized steel tube sheets
shall not be acceptable. All copper construction shall provide protection in moderate
coastal applications.
A polymer strip shall prevent the coil assembly from contacting the sheet metal coil pan
to minimize the potential for galvanic corrosion between the coil and the pan. All copper construction shall provide protection in
moderate coastal environments.
c. E-Coated Aluminum-Fin Coils:
Shall be constructed of aluminum fins
mechanically bonded to copper tubes. Coating process shall have a flexible epoxy polymer coating uniformly applied to all coil
surfaces without material bridging between
the fins. The coating process shall ensure
complete coil encapsulation. Color shall be
high-gloss black with gloss at 60 angle of
65% to 90% per ASTM D523-89. Uniform
dry film thickness shall be 0.8 mil to 1.2 mil
on all surfaces, including the fin edges.
Superior hardness characteristics shall meet
those requirements of 2H, per ASTM
D3363-92A. Cross-hatch adhesion shall
meet the requirements of 4B-5B, per ASTM
D3359-93. Impact resistance shall be up to
160 in./lb, per ASTM D2794-93. Humidity
resistance shall be up to a minimum of
1000 hours per ASTM D2247-92. Water
immersion resistance shall be up to a minimum of 250 hours per ASTM D870-92.
Durability shall be confirmed through testing
to no less than 1000 hours of salt spray per
ASTM B117-90 (U.S.A. standards).
d. E-Coated Copper Fin Coils:
Shall be copper fins mechanically bonded to
copper tubes with copper tube sheets. Coating process shall have a flexible epoxy polymer coating uniformly applied to all coil
surfaces without material bridging between
the fins. The coating process shall ensure
complete coil encapsulation. Shall be highgloss black with gloss at 60 angle of 65% to
90% per ASTM D523-89. Uniform dry film

thickness shall be 0.8 mil to 1.2 mil on all


surfaces, including the fin edges. Superior
hardness characteristics shall meet those
requirements of 2H, per ASTM D336392A. Cross-hatch adhesion shall meet the
requirements of 4B-5B, per ASTM D335993. Impact resistance shall be up to
150 in./lb, per ASTM D2794-93. Humidity
resistance shall be up to a minimum of
1000 hours per ASTM D2247-92. Water
immersion resistance shall be up to a minimum of 250 hours per ASTM D980-92.
Durability shall be confirmed through testing
to no less than 1000 hours of salt spray per
ASTM B117-90 (U.S.A. standards).
* 3. Unloader Conversion Kit:
Unloader valve, piston, and hardware shall be
supplied to convert any pressure-operated compressor unloader to electrical unloading. Accessory ModuPanel or field-supplied step
controller shall be provided for electrical
unloading.
* 4. Gage Panel:
A gage panel package shall be provided which
includes a suction and discharge pressure gage
for each refrigerant circuit.
5. Thermostat Controls:
a. Debonair programmable multi-stage thermostat with 7-day clock, holiday scheduling,
large Thermoglow display, remote sensor
capability, and Title 24 compliance.

6.

7.

* 8.

* 9.

b. Commercial Electronic Thermostat with


7-day timeclock, auto-changeover, multistage capability, and large LCD temperature
display.
c. Non-programmable thermostat with fan
switch subbase.
d. Carrier PremierLink Controls:
This control will function with CCN and
ComfortVIEW software. It shall also be
compatible with ComfortLink controllers.
It shall be ASHRAE 62-99 (U.S.A.) compliant and Internet ready. It shall accept a CO2
sensor in the conditioned space and be
Demand Control Ventilation (DCV) ready.
The communication rate must be 38.4K or
faster. It shall include an integrated economizer controller.
Electric Unloader Package:
Electric unloader shall provide an additional
step of electric unloading.
Pressure Unloader Package:
Pressure unloader shall provide an additional
step of pressure unloading.
ModuPanel Control:
Control shall provide 10-step microprocessorbased control for variable air volume applications.
Low Ambient Control:
Control shall maintain correct condensing pressure at low ambient temperatures.

79

Guide specifications 40RM units


Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
Size Range: 2831 to 5663 L/s (6000 to 12,000 Cfm),
Nominal Airflow
52 to 105 kW (15 to 30 Tons),
Nominal Cooling
Carrier Model Number: 40RM
Part 1 General
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multiposition
design and shall be capable of horizontal or vertical
(upflow) installation on a floor or in a ceiling, with or
without ductwork. (Only vertical units are to be
applied without ductwork).
B. Unit shall be used in a refrigerant circuit with a
matching air-cooled condensing unit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance
with ASHRAE 15 Safety Code for Mechanical
Refrigeration (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL
(U.S.A.) and ETL, Canada standards.
C. Unit insulation and adhesive shall comply with
NFPA 90A (U.S.A.) requirements for flame spread
and smoke generation. Insulation shall contain a
U.S.A. EPA-registered immobilized antimicrobial
agent to effectively resist the growth of bacteria and
fungi as proven by tests in accordance with ASTM
standards G21 and 22 (U.S.A.).
D. Unit shall be manufactured in a facility registered to
the ISO 9001:2000 manufacturing quality standard.
E. Direct-expansion coils shall be burst tested at
2999 kPag (435 psig) and leak tested at 1034 kPag
(150 psig).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturers
recommendations.
Part 2 Products
2.01 EQUIPMENT
A. General:
Indoor mounted, draw-thru, packaged air-handling
unit that can be used in a suspended horizontal configuration or vertical (upflow) configuration. Unit
shall consist of forward-curved belt-driven centrifugal
fan(s), motor and drive assembly, prewired fan
motor contactor, factory-installed refrigerant metering devices, cooling coil, 51 mm (2-in.) disposable
air filters, and condensate drain pans for vertical or
horizontal configurations.
B. Base Unit:
1. Cabinet shall be constructed of mill-galvanized
steel.
2. Cabinet panels shall be fully insulated with
12.7-mm (1/2-in.) fire-retardant material.
Insulation shall contain a U.S.A. EPA-registered

80

C.

D.

E.

F.

immobilized antimicrobial agent to effectively


resist the growth of bacteria and fungi as
proven by tests in accordance with ASTM
standards G21 and 22 (U.S.A.).
3. Unit shall contain corrosion resistant condensate drain pans for both vertical and horizontal
applications. Drain pans shall have connections
on right and left sides of unit to facilitate field
connection. Drain pans shall have the ability to
be sloped toward the right or left side of the
unit to prevent standing water from accumulating in pans.
4. Unit shall have factory-supplied 51-mm (2-in.)
throwaway-type filters installed upstream from
the cooling coil. Filter access shall be from
either the right or left side of the unit.
Coils:
Coils shall consist of 3 rows (standard) or 4 rows
(high capacity) of 3/8-in. copper tubes with sinewave aluminum fins bonded to the tubes by mechanical expansion. Coil tubing shall be internally rifled
to maximize heat transfer. Suction and liquid line
connections shall be made on the same side of the
coil. Direct-expansion coils shall feature factoryinstalled thermostatic expansion valves (TXVs) for
refrigerant control. The TXVs shall be capable of
external adjustment.
Operating Characteristics:
Unit shall be capable of providing _____ L/s (cfm)
airflow at an external static pressure of _____ kPag
(in. wg).
Motor:
Fan motor of the size and electrical characteristics
specified on the equipment schedule shall be factory
supplied and installed.
Special Features:
1. Alternate Motor and Drive:
An alternate motor and/or medium- or highstatic drive shall be available to meet the airflow
and external static pressure requirements specified on the equipment schedule.
2. High-Capacity Coil:
High-capacity coil consisting of 4 rows of
3/ -in. copper tubes with sine-wave aluminum
8
fins bonded to the tubes by mechanical expansion. Coil tubing shall be internally rifled to
maximize heat transfer. Suction and liquid line
connections shall be made on the same side of
the coil. Direct-expansion coils shall feature
factory-installed thermostatic expansion valves
(TXVs) for refrigerant control. The TXVs shall
be capable of external adjustment.
3. Painted Cabinet:
Where conditions require, units shall be painted
with an American Sterling Gray finish.

4. Hot Water Coil:


Coil shall be 2-row, U-bend coil with copper
tubes and aluminum plate fans bonded to the
tubes by mechanical expansion. Coil shall be
mounted in a galvanized steel housing that shall
be fastened to the units fan deck for blow-thru
heating operation. Coil shall have maximum
working pressure of 1034 kPag (150 psig).
5. Steam Distributing Coil:
Coil shall consist of 1 row of copper tubes with
aluminum plate fins, and shall have inner steam
distributing tubes. Coil shall be mounted in a galvanized steel housing that shall be fastened to the
units fan deck for blow-thru heating operation.
Coil shall have maximum working pressure of
138 kpag at 126 C (20 psig at 260 F).
6. Electric Heaters:
Heaters for nominal 230 or 400-volt, 3-phase
power supply shall be factory-supplied for field
installation as shown on the equipment drawings. Electric heat assembly shall be ETL (U.S.A.)
and ETL, Canada agency approved, and shall
have single-point power wiring. Heater assembly
shall include contactors with 24-v coils, power
wiring, 24-v control wiring terminal blocks, and
a hinged access panel. Electric heaters shall not
be used with discharge plenum.
7. Air Discharge Plenum:
Plenum shall be provided to provide free-blow
air distribution for vertical floor-mounted units.
A grille with moveable vanes for horizontal or
vertical airflow adjustment shall be included.
Plenum shall be field-assembled and fieldinstalled on the units fan deck for blow-thru air
distribution. Plenum shall not be used with electric heaters.
8. Return-Air Grille:
Grille shall be factory supplied for field installation on the units return air opening.
9. Unit Subbase:
Subbase assembly shall be factory supplied for
field installation. Subbase shall elevate floormounted vertical units to provide access for correct condensate drain connection.
10. Economizer:
Economizer for ventilation or free cooling
shall be factory provided for field installation.
For free cooling applications, economizer shall
be compatible with factory-supplied thermostat;
economizer dampers shall open when outdoor
air enthalpy is suitable for free cooling. Economizer shall be compatible with separate CO2
sensor accessory; economizer dampers shall
open when indoor CO2 level rises above predetermined set point. Economizer shall include
enthalpy control and damper actuator with
controls.

11. Thermostat Controls:


a. Debonair programmable multi-stage thermostat with 7-day clock, holiday scheduling,
large Thermoglow display, remote sensor
capability, and Title 24 compliance.
b. Carrier PremierLink Controls:
This control will function with CCN and
ComfortVIEW software. It shall also be
compatible with ComfortLink controllers.
It shall be ASHRAE 62-99 (U.S.A.) compliant and Internet ready. It shall accept a CO2
sensor in the conditioned space and be
Demand Control Ventilation (DCV) ready.
The communication rate must be 38.4K or
faster. It shall include an integrated economizer controller.
c. Commercial Electronic Thermostat with
7-day timeclock, auto-changeover, multistage capability, and large LCD temperature
display.
d. Non-programmable thermostat with fan
switch subbase.
12. Overhead Suspension Brackets:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
13. CO2 Sensor:
Sensor shall provide the ability to signal the
economizer to open when the space CO2 level
exceeds the predetermined set point. Sensor
shall have the capability of being connected to
comfort system relay pack or to economizer
using field-supplied and installed Honeywell dc
adapter no. Q769C1004.
14. Condensate Drain Trap:
Trap shall have transparent, serviceable design
for easy cleaning. Kit shall include overflow
shutoff switch and wiring harness for connection to an alarm if desired.
15. UV-C Germicidal Lamps:
a. UV-C emitters and fixtures shall be specifically designed for use inside an HVAC system. An ASME nozzled test apparatus using
a 45 F (7.2 C) airstream moving at not less
than 400 fpm (189 liters/sec.) shall measure
individual lamp output. Lamp output at
253.7 nm shall not be less than 10W/cm2
per inch of arc length measured at a distance
of one meter.
b. UV-C power supplies shall be high efficiency, electric type which are matched to
the emitters and are capable of producing
the specified output intensity with an input
power no more than 80 watts.
c. Emitters and fixtures shall be installed in
sufficient quantity and arranged so as to
provide an equal distribution of UV-C energy
on the coil and drain pan.

81

Guide specifications 40RM units (cont)


e. Emitters and fixtures shall be
installed at right angles to the conforming
lines of the coil fins, such that through incident angle reflection, UV-C energy strikes
all target surfaces of the coil, drain pan,
and the available line of sight airstream.

d. The minimum UV-C energy striking the


leading edge of the coil fins shall be not less
than 820 W/cm2 at the closest point and
through placement, not less than 60% of
that value at the farthest point. Equal
amounts are to strike the drain pan, either
directly or indirectly through reflection.

Carrier Corporation Syracuse, New York 13221

7-04

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 2
Pg 82
Catalog No. 003-80020
Printed in U.S.A.
Form 38A-C11PD
Replaces: 38A-C9PD