Data
GEMINI
38AKS028-044
38AH024-034
With 40RM016-034
Commercial Air-Cooled
Split Systems
50 Hz
63 to 127 kW (18 to 35.8 Nominal Tons)
Features/Benefits
38AKS,38AH
Reliability
40RM016-034
Form 38A-C11PD
38AH series
38AH condensing units feature 2 compressors and 2 refrigeration circuits.
These units can be matched with a
single air handler or two separate air
handlers.
Standard units are designed for
constant volume control. A variable air
volume (VAV) control is available as a
factory-installed option. The VAV units
feature electrically controlled compressor unloading to precisely match unit
capacity to building loads. The VAV
equipped unit has a simple control
interface for connection to a VAV
discharge air control system.
Economy
The 40RM Series packaged air handlers have low initial costs, and they
continue to save money by providing
reduced installation expense and
energy-efficient performance.
Quick installation is ensured by the
multipoise design. Units can be installed in either the horizontal or
vertical configuration without modifications. All units have drain-pan connections on both sides, and pans can be
pitched for right-hand or left-hand
operation with a simple adjustment.
Fan motors and contactors are
prewired and thermostatic expansion
valves (TXVs) are factory-installed on
all 40RM models.
Rugged dependability
40RM units are made to last. The
die-formed galvanized steel panels
ensure structural integrity under all
operating conditions. Galvanized steel
fan housings are securely mounted to
a die-formed galvanized steel deck.
Mechanically bonded coil fins provide
improved heat transfer. Rugged pillowblock bearings are securely fastened to
the solid steel fan shaft with split collets
and clamp locking devices.
Coil flexibility
Model 40RM direct-expansion coils
have galvanized steel casings; inlet and
outlet connections are on the same
end. The coils are designed for use
with Refrigerant 22 and have 3/8-in.
diameter copper tubes mechanically
bonded to aluminum sine-wave fins.
The coils include matched, factoryinstalled TXVs with matching distributor nozzles. Accessory hot water and
steam coils and electric heaters are
also available.
Table of contents
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
Model Number Nomenclature 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . 4
Model Number Nomenclature 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . 5
Model Number Nomenclature 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . 6
Capacity Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Physical Data 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8,9
Physical Data 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10,11
Physical Data 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12,13
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-16
Dimensions 38AKS028, 034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Dimensions 38AKS044 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Dimensions 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensions 40RM016-024 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions 40RM028, 034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22,23
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24-50
38AKS Unit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24,25
38AKS/40RM Combination Ratings . . . . . . . . . . . . . . . . . . . . . . . . .26-31
38AH Unit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32-35
38AH/40RM Combination Ratings . . . . . . . . . . . . . . . . . . . . . . . . . .36-43
40RM Unit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44-50
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51-54
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55-58
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59-61
Typical Control Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . .62-65
Application Data 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66,67
Application Data 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68-70
Application Data 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71-73
Guide Specifications 38AKS Units. . . . . . . . . . . . . . . . . . . . . . . . . . .74-76
Guide Specifications 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . . . .77-79
Guide Specifications 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . .80-82
028
Not Used
Packaging
1 Std. Domestic Packaging
3 Export Packaging - Top
and Bottom Skid
Revision Number
0 Original
Voltage Designation
3 346-3-50
8 230-3-50
9 400-3-50
LEGEND
Al Aluminum
Cu Copper
*Gross capacity based on 36 C air temperature entering condenser and 8 C saturated suction temperature.
Gross capacity based on 95 F air temperature entering condenser and 45 F saturated suction temperature.
Quality Assurance
Certified to ISO 9001:2000
024
A
Compressors
A Standard Compressors One Suction
Pressure-Actuated Unloader on Lead
Compressor
C Variable Air Volume (VAV) Option
Includes 2 Electric Unloaders on Lead
Compressor and Control Box
Modifications
Fan Motors and Labels
A Standard Condenser Fan Motors
and Labels
Packaging
1 Standard Domestic Packaging
Bottom Skid
3 Export Packaging Top and Bottom
Skid
Revision Number
1 Current Revision
LEGEND
Al Aluminum
Cu Copper
Quality Assurance
Certified to ISO 9001:2000
016
GC
Quality Assurance
Certified to ISO 9001:2000
Factory-Installed Options
GC Unpainted, Standard Motor, and
Standard Drive
HC Unpainted, Standard Motor, and
Medium-Static Drive (Not available
to sizes 016-028)
TC Unpainted, Alternate Motor, and
Medium-Static Drive (sizes 016-028)
YC Unpainted, Alternate Motor, and
High-Static Drive*
ED Painted, Standard Motor, and
Standard Drive
FD Painted, Standard Motor, and
Medium-Static Drive
(Not available for sizes 016-028)
RD Painted, Alternate Motor, and
Medium-Static Drive
(sizes 016-028)
WD Painted, Alternate Motor, and
High-Static Drive*
Packaging
3 Export Packaging
Capacity summary
CONDENSING
UNIT
AIRHANDLING
UNIT 40RM
028
38AKS
034
044
024
38AH
028
034
024
028
034
028
034
034
016
024
028
024
028
034
028
034
AIR-HANDLING
UNIT AIRFLOW
L/s
Cfm
3800
8,000
4700
10,000
5650
12,000
4700
10,000
5650
12,000
5650
12,000
2800
6,000
3800
8,000
4700
10,000
3800
8,000
4700
10,000
5650
12,000
4700
10,000
5650
12,000
LEGEND
db Dry Bulb
wb Wet Bulb
SST Saturated Suction Temperature
*System gross capacities are rated according to indoor unit airflow,
35 C air temperature entering condenser, and 20 C wb air temperature entering evaporator.
CONDENSING UNIT
ONLY GROSS CAPACITY
kW**
Btuh
82.8
281,000
94.5
320,000
127.0
429,000
63.0
216,000
73.0
250,000
87.0
297,000
63
97.7
97.7
98.5
97.7
98.5
101.5
125
93.6
93.6
94.2
93.3
94.1
97.3
NOTES:
1. Estimated sound power levels, dB re 1 Picowatt
This data is based upon a limited amount of actual testing with the
estimated sound power data being generated from this data in
accordance with ARI (Air Conditioning and Refrigeration Institute,
U.S.A. Standard) standard 370 for large outdoor refrigerating and
air conditioning equipment.
4000
78.8
78.5
76.0
77.8
78.6
81.5
8000
74.4
74.5
74.9
74.0
74.8
78.1
dB(A)
92.5
92.6
93.2
92.4
93.2
95.6
2. Since this data is estimated, the sound power levels should not be
guaranteed or certified as being the actual sound power levels.
The acoustic center of the unit is located at the geometric center of
the unit.
Cfm
6,000
8,000
10,000
12,000
dB(A)
92.7
96.4
96.2
98.5
63
98.9
102.6
102.5
104.7
1000
85.9
89.6
89.5
91.7
2000
83.9
87.6
87.5
89.7
4000
79.9
83.6
83.5
85.7
NOTE: Since this data is calculated, these sound power levels may be different than the actual sound power levels.
The acoustic center of the unit is located at the geometric center of the unit.
028
82.8
034
94.5
748
818
818
1106
911
1246
R-22
13.8
19.7
29.5
Reciprocating, Semi-Hermetic
1...06E9265
1...06E9275
1...06E9299
6
6
6
24.2
9
9
9.5
100%, 66%, 33%
524
400
538
414
180
Propeller Type Direct Drive
2...16
3...16
762
0.75
7400
11,180
1490
1750
1520
Enhanced Copper Tubes, Lanced Aluminum Fins
2...748
3...670
3...670
3.6
3.6
5.4
17
26
38
2940 50
2200 40
185 20
300 35
43
62
1760 70
1100 70
Fusible Plug
Liquid and Suction Line
100
15 / 8
21 / 8
7/
8
5/
8
044
127.0
21 / 8
028
23.4
034
26.5
044
35.8
1650
1804
1803
2437
2009
2745
R-22
30.5
43.5
65.0
Reciprocating, Semi-Hermetic
1...06E9265
1...06E9275
1...06E9299
6
6
6
1450
20.0
20.0
19.0
100%, 66%, 33%
76
58
78
60
180
Propeller Type Direct Drive
2...950
3...950
30
1.0
15,700
23,700
1490
1750
1520
Enhanced Copper Tubes, Lanced Aluminum Fins
2...19
3...17
3...17
39.2
39.2
58.4
37.7
56.6
84.4
426 7
320 20
27 3
44 5
6.2
9.0
255 10
160 10
Fusible Plug
Liquid and Suction Line
210
15 / 8
21 / 8
7/8
5/
8
21 / 8
10
024
028
Circuit 1
Circuit 2
Circuit 1
034
Circuit 2
Circuit 1
Circuit 2
63
73
87
798.3
872.3
825.6
899.0
R-22
853.0
951.2
9.10
1.36
9.10
1.36
1...06DH824
6
24.3
1...06DA824
6
24.3
100
67*
33
100
524
400
762
1.0
7870
2...748
3.64
17.4
9.10
9.10
1.36
1.36
Reciprocating Semi-Hermetic
1...06DH328
1...06DA328
6
6
24.3
24.3
4.73
11.40
1.36
11.40
1.36
1...06DH328
6
24.3
1...06DA537
6
24.3
100
100
100
67*
67*
33
33
Factory Installed
524
524
400
400
Propeller Type Direct Driven
2...16
762
762
1.0
1.0
7870
7400
3100
Enhanced Copper Tubes, Aluminum Lanced Fin
2...748
3...670
3.64
3.64
17.4
26.0
100
2940 50
2200 140
185 20
300 35
Manual Reset
42
62
21.1 1.6
15.6 1.6
Fusible Plug
Liquid Line, Suction Line, Compressor
100
13/8
5/ 8
*Standard unit single pressure-actuated suction unloader on compressor no. 1.
VAV FIOP double electrically actuated unloaders on compressor
no. 1.
**Typical operating charge with 7.6 m of interconnecting piping.
Storage capacity of condenser coil with coil 80% full of liquid R-22 at
48.8 C.
024
028
Circuit 1
Circuit 2
Circuit 1
034
Circuit 2
Circuit 1
Circuit 2
18
21
25
1760
1923
1820
1982
R-22
1880
2097
20
3
20
3
1...06DH824
6
1450
1...06DA824
6
1450
100
67*
33
100
76
58
30
1.0
16,700
2...19
39.20
37.7
20
20
3
3
Reciprocating Semi-Hermetic
1...06DH328
1...06DA328
6
6
1450
1450
10
25
3
25
3
1...06DH328
6
1450
1...06DA537
6
1450
100
100
100
67*
67*
33
33
Factory Installed
76
76
58
58
Propeller Type Direct Driven
2...950
30
1.0
16,700
3100
Enhanced Copper Tubes, Aluminum Lanced Fin
2...19
39.20
37.7
100
30
1.0
15,700
3...17
39.20
56.6
426 7
320 20
27 3
44 5
Manual Reset
6.0
8.8
70 3
60 3
Fusible Plug
Liquid Line, Suction Line, Compressor
210
13/8
5/ 8
*Standard unit single pressure-actuated suction unloader on compressor no. 1.
VAV FIOP double electrically actuated unloaders on compressor
no. 1.
**Typical operating charge with 25 ft of interconnecting piping.
Storage capacity of condenser coil with coil 80% full of liquid R-22 at
120 F.
11
12
016
52
024
70
028
87
034
105
311/323
102
313/331
102
463/470
148
467/482
148
2...381
2831
2124-3539
2...381
3775
2831-4719
2...457
4719
3539-5899
2...457
5663
4247-7079
2.16
3.73
5.59
7.46
23.8
23.8
23.8
23.8
R-22
1.13/1.13
1.64
2
12/16
591
1.59/1.59
2.04/2.04
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
2999
1.85
2.30
2
2
13/18
15/20
Face...50/50
670
591
2.27/2.27
2.77
2
18/24
591
1207
1.24
1...394
1.24
1...394
1.24
2...335
1.24
2...335
1.39
1...394
1.39
1...394
1.39
2...493
1.39
2...493
1034
52.6
0.052
2...11/8
54.1
0.054
2...11/8
2...13/8
2...5/8
1...21/2
1...11/2
1...2
1...2
1...11/4 ODM/1 IDF
2...13/8
016
15
024
20
028
25
034
30
685/713
225
690/730
225
1020/1050
325
1030/1062
325
2...15
6000
4500-7500
2...15
8000
6000-10,000
2...18
10,000
7500-12,500
2...18
12,000
9000-15,000
2.9
5.0
7.5
10.0
1425
R-22
2.5/2.5
17.67
2
12/16
15
3.5/3.5
4.5/4.5
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
19.88
24.86
2
2
Face...50/50
13/18
15/20
17
15
5.0/5.0
29.83
2
18/24
15
175
13.33
1...10
13.33
1...10
13.33
2...8.5
13.33
2...8.5
15.0
1...10
15.0
1...10
15.0
2...12.5
15.0
2...12.5
150
13.9
1.85
2...11/8
14.3
1.90
2...11/8
2...13/8
2...5/8
1...21/2
1...11/2
1...2
1...2
1
1...1 /4 ODM/1 IDF
Throwaway Factory Supplied
4...16 20 2
4...16 24 2
2...13/8
4...20 24 2
4...20 25 2
Right or Left Side
*Refer to Alternate Fan Motor Data table on page 71 for alternate motor
data.
Units are shipped without refrigerant charge.
13
14
Standard
Mild
Coastal
ENVIRONMENT
Moderate
Severe
Coastal
Coastal
Industrial
Combined
Industrial/Coastal
X
X
X
X
LEGEND
Aluminum
Copper
Family of Coil Protection Options
Epoxy coating Applied to Entire Coil Assembly
Epoxy coating Applied to Fin Stock Material
15
DISCHARGE
PLENUM
RETURN-AIR
GRILLE
SUBBASE
FAN
COIL
UNIT
ECONOMIZER
16
FAN COIL
UNIT
Dimensions 38AKS028,034
NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space
above unit.
3. The approximate operating weight of the unit is:
UNIT
38AKS
028
028C
034
034C
WEIGHT
(lb)
1650
1804
1803
2009
WEIGHT
(kg)
748
818
818
911
418
626
242
364
(189.6) (284.0) (109.8) (165.1)
459
673
272
399
(208.2) (305.3) (123.4) (181.0)
TOTAL
1650
(748.4)
1803
(817.8)
17
Dimensions 38AKS044
NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space
above unit.
3. The approximate operating weight of the unit is:
UNIT
38AKS
044
044C
WEIGHT
(lb)
2437
2745
WEIGHT
(kg)
1106
1246
TOTAL
044
720
(327)
900
(409)
455
(207)
362
(165)
2437
(1106)
18
Dimensions 38AH024-034
NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all
sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space above unit.
3. C in the package number indicates copper coils.
4. Dimensions in [ ] are in millimeters.
5. The approximate operating weight of the unit is shown below.
6. Certified dimensional drawing is available on request.
CORNER WEIGHT lb [kg]
UNIT
38AH
024
024C
028
028C
034
034C
631.6
[286.5]
666.5
[302.3]
658.7
[298.8]
693.0
[314.3]
667.0
[302.5]
718.3
[325.8]
577.6
[262.0]
609.5
[276.5]
602.4
[273.3]
633.8
[287.5]
610.0
[276.7]
656.8
[297.9]
263.1
[119.3]
309.0
[140.2]
267.0
[121.1]
313.0
[142.0]
288.0
[130.7]
344.8
[156.4]
287.7
[130.5]
337.9
[153.3]
291.9
[132.4]
342.2
[155.2]
315.0
[142.9]
377.0
[171.0]
CENTER OF
GRAVITY
A Dim.
in.
[mm]
40.00
[1016]
43.00
[1092]
39.25
[997]
42.25
[1073]
41.00
[1041]
44.00
[1117]
B Dim.
in.
[mm]
32.75
[832]
TOTAL
UNIT WT
lb [kg]
1760
[798.3]
1923
[872.3]
1820
[825.6]
1982
[899.0]
1880
[853.0]
2097
[951.2]
19
Dimensions 40RM016-024
Direction of airflow.
3. Recommended clearance:
Rear: 76 mm (3 in.)
Front: 762 mm (2 ft, 6 in.)
Right side: 762 mm (2 ft, 6 in.)
Left side: 762 mm (2 ft, 6 in.)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
UNIT 40RM
3-Row
Coil
4-Row
Coil
20
016
024
016
024
UNIT WEIGHT
lb (kg)
685 (311)
690 (313)
713 (323)
730 (331)
Dimensions 40RM028,034
CONTROL BOX
CONTROL BOX
Direction of airflow.
3. Recommended clearance:
Rear: 76 mm (3 in.)
Front: 762 mm (2 ft, 6 in.)
Right side: 762 mm (2 ft, 6 in.)
Left side: 762 mm (2 ft, 6 in.)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
UNIT 40RM
3-Row
Coil
4-Row
Coil
028
034
028
034
UNIT WEIGHT
lb (kg)
1020 (463)
1030 (467)
1050 (470)
1062 (482)
21
Selection procedure
38AH024-034/40RM SI
NOTE: This book contains combination ratings for
38AH024-034 units and matching 40RM air handlers. If
the 38AH units are matched with 39 Series air handlers,
use the Carrier AHU (Air-Handling Unit) selection program
software package for combination ratings. If Totaline
P702 water coolers are used, determine the performance
by cross-plotting the condensing unit performance found
in this book against the P702 performance in the P702
product data book. If the 38AH condensing units are
matched with 2 independent 40RM units, cross-plot for
performance ratings or contact Carrier Application Engineering for assistance.
I Determine cooling load, evaporator-air temperature and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . . . . . . . . 60 kW
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . . . . . . . 48 kW
Temperature Air Entering
Condenser (Edb) . . . . . . . . . . . . . . . . . . . 36 C
Temperature Air Entering
Evaporator (db/wb) . . . . . . 26.7 C db, 20 C wb
Evaporator Air Quantity. . . . . . . . . . . . . 3800 L/s
External Static Pressure . . . . . . . . . . . . .150 Pa
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . 18 m (Linear)
II Select condensing unit air-handler combination.
For this example, select a 38AH024 matched with
a 40RM024. This 38AH024/40RM024 condensing unit-air handler combination provides 62.5 kW
of total cooling capacity and 49.2 kW of sensible
capacity at the given conditions. If other temperatures or airflow values are required, interpolate the
values from the combination ratings.
22
38AH024-034/40RM English
NOTE: This book contains combination ratings for
38AH024-034 units and matching 40RM air handlers. If
the 38AH units are matched with 39 Series air handlers,
use the Carrier AHU (Air-Handling Unit) selection program
software package for combination ratings. If Totaline
P702 water coolers are used, determine the performance
by cross-plotting the condensing unit performance found
in this book against the P702 performance in the P702
product data book. If the 38AH condensing units are
matched with 2 independent 40RM units, cross-plot for
performance ratings or contact Carrier Application Engineering for assistance.
I Determine cooling load, evaporator-air temperature and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . . 210,000 Btuh
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . .175,000 Btuh
Temperature Air Entering
Condenser (Edb) . . . . . . . . . . . . . . . . . . . .95 F
Temperature Air Entering
Evaporator (db/wb) . . . . . . . . 80 F db, 67 F wb
Evaporator Air Quantity. . . . . . . . . . . . . 8000 cfm
External Static Pressure . . . . . . . . . . . 1.0 in wg
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . .30 ft (Linear)
II Select condensing unit air-handler combination.
For this example, select a 38AH024 matched with a
40RM024. This 38AH024/40RM024 condensing
unit-air handler combination provides 214,500 Btuh
of total cooling capacity and 179,000 Btuh of sensible
capacity at the given conditions. If other temperatures
or airflow values are required, interpolate the values
from the combination ratings.
23
Performance data
38AKS CONDENSING UNIT RATINGS SI
38AKS028
SST
(C)
6
4
2
0
2
4
6
8
10
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
38AKS044
28
55.3
17.4
41.2
60.4
18.2
42.1
64.4
18.8
42.9
69.9
19.6
43.9
75.6
20.5
45.0
80.2
21.1
45.9
86.4
22.0
47.1
91.2
22.6
48.0
97.9
23.5
49.3
52
38.3
20.4
63.3
42.3
21.5
63.8
45.4
22.4
64.4
49.7
23.7
65.1
54.3
24.9
66.0
57.8
25.9
66.7
62.7
27.2
67.7
66.5
28.2
68.4
71.7
29.5
69.5
38AKS034
SST
(C)
6
4
2
0
2
4
6
8
10
24
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
28
62.4
20.0
42.1
68.7
20.7
42.2
73.3
21.3
42.7
79.5
22.1
43.6
85.9
23.0
44.6
90.9
23.7
45.4
97.8
24.6
46.6
103.0
25.2
47.5
110.0
26.2
48.8
52
40.8
22.2
66.1
46.1
23.7
66.1
50.3
24.8
66.1
56.1
26.2
66.1
62.1
27.6
66.2
66.6
28.7
66.6
72.4
30.1
67.5
76.9
31.2
68.2
83.0
32.7
69.2
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
6
4
2
0
2
4
6
8
10
kW
SDT
SST
TC
LEGEND
Out of Range
Compressor Power
Saturated Discharge Temperature at Compressor (C)
Saturated Suction Temperature (C)
Gross Cooling Capacity (kW)
38AKS028
SST
(F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
38AKS034
SST
(F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
203.0
20.0
110.0
230.0
21.0
110.0
256.0
22.0
112.0
283.0
23.1
114.0
311.0
24.3
117.0
340.0
25.4
119.0
371.0
26.6
122.0
SST
(F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
20
25
30
35
40
45
50
kW
SDT
SST
TC
85
271.0
27.3
109.0
305.0
28.6
109.0
341.0
29.9
109.0
377.0
31.3
111.0
415.0
32.9
113.0
455.0
34.5
115.0
497.0
36.1
117.0
LEGEND
Out of Range
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)
25
61.9 56.1
64.8 59.7
52
SHC
43.4 56.1
50.2 59.7
kW
26.99 25.46
27.74 26.40
68.5 63.3
71.7 67.3
48
SHC
51.0 63.3
59.4 67.3
kW
27.02 25.68
27.83 26.71
TC
65.6 61.0
65.0
52
SHC
50.2 61.0
65.0
kW
27.96 26.75
27.81
Edb
Ewb
kW
Ldb
Lwb
SHC
TC
LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.
26
16
80.5
80.5
19.22
76.4
76.4
20.75
74.1
74.1
21.78
71.9
71.9
22.76
69.6
69.6
23.82
67.2
67.2
25.04
64.7
64.7
26.04
62.5
62.5
27.15
77.4 74.1
44
SHC 47.3 57.9 70.2
67.2 74.1
kW
28.17 26.62 25.68
27.23 26.52
TC
72.5 67.8
72.2
48
SHC
57.1 67.8
72.2
kW
28.03 26.82
27.96
TC
65.3
52
SHC
65.3
kW
27.88
16
87.1
87.1
19.74
82.6
82.6
21.52
80.1
80.1
22.68
77.7
77.7
23.79
75.2
75.2
24.98
72.6
72.6
26.20
70.7
70.7
27.56
4700
20
87.7
65.8
19.78
82.7
63.5
21.54
80.0
62.2
22.66
77.4
61.0
23.74
74.7
59.8
24.87
71.9
58.5
26.04
69.6
21.9
27.30
5900
20
93.5
75.4
20.24
88.0
72.9
22.20
85.1
71.6
23.42
82.2
70.3
24.59
79.2
69.0
25.82
76.2
67.7
26.96
7050
20
98.7
84.4
20.54
92.7
81.7
22.78
89.5
80.3
24.08
86.3
78.9
25.32
83.0
77.4
26.62
79.8
76.0
27.74
16
93.5
93.5
20.24
88.4
88.4
22.25
85.7
85.7
23.51
83.0
83.0
24.73
80.1
80.1
26.02
77.3
77.3
27.20
5900
20
101.6
78.9
22.45
95.9
76.4
24.38
93.0
75.1
25.62
90.2
73.9
26.91
87.3
72.6
28.12
84.2
71.2
29.28
82.0
70.3
30.53
79.0
68.9
31.70
16
93.8
93.8
21.87
89.1
89.1
23.59
86.6
86.6
24.76
84.3
84.3
25.97
81.9
81.9
27.24
79.3
79.3
28.25
76.8
76.8
29.39
74.3
74.3
30.56
3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCkW x 1000
Ldb C: hlwb = hewb
1.20 x L/s
Ldb C = Edb C
77.2 71.5
80.8 76.3
52
SHC
59.0 71.5
68.7 76.3
kW
31.25 29.88
32.12 31.04
Edb
Ewb
kW
Ldb
Lwb
SHC
TC
LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.
7050
20
107.4
88.3
22.88
101.3
85.5
25.00
98.2
84.2
26.32
95.1
82.8
27.70
92.0
81.4
28.89
88.7
79.9
30.20
87.1
79.2
32.64
83.8
77.7
32.85
16
100.9
100.9
22.40
95.7
95.7
24.36
93.0
93.0
25.62
90.4
90.4
26.95
87.7
87.7
28.19
84.9
84.9
29.41
83.0
83.0
30.74
80.2
80.2
31.98
7050
20
128.1
97.5
29.77
122.6
95.1
32.47
119.9
93.9
34.08
116.7
92.4
35.68
112.7
90.6
37.38
109.4
89.2
38.88
106.3
87.8
40.53
103.0
86.3
42.13
16
115.8
115.8
28.82
112.0
112.0
31.27
110.4
110.4
32.72
107.7
107.7
34.26
104.3
104.3
35.94
101.5
101.5
37.41
98.4
98.4
38.72
95.7
95.7
40.33
3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCkW x 1000
Ldb C: hlwb = hewb
1.20 x L/s
Ldb C = Edb C
27
210.5 193.6
219.8 206.1
125 SHC
156.4 188.6
181.2 206.1
kW
26.82 25.59
27.50 26.50
224.0 210.2
224.3
125 SHC
179.5 208.8
224.3
kW
27.80 26.80
27.82
Edb
Ewb
kW
Ldb
Lwb
SHC
TC
LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.
28
62
256.3
256.3
20.81
247.1
247.1
22.57
241.6
241.6
23.37
236.6
236.6
24.08
226.7
226.7
25.65
216.1
216.1
27.23
248.9 236.5
258.1 251.7
115 SHC
207.9 236.1
243.6 251.7
kW
27.17 26.32
27.80 27.36
TC
224.6
125 SHC
224.5
kW
27.84
62
280.8
280.8
21.90
270.0
270.0
23.67
264.2
264.2
24.55
258.4
258.4
25.35
246.9
246.9
27.03
10,000
67
276.2
226.0
21.70
264.4
220.6
23.41
258.0
217.6
24.22
251.7
214.8
24.96
239.4
209.2
26.52
12,500
67
295.7
261.4
22.56
282.2
255.5
24.26
275.3
252.5
25.13
268.2
249.4
25.92
254.2
243.3
27.53
15,000
67
312.9
295.1
23.33
297.8
288.5
25.01
290.5
285.3
25.92
282.6
281.8
26.76
62
302.9
302.9
22.88
290.3
290.3
24.64
284.0
284.0
25.58
277.3
277.3
26.45
263.9
263.9
28.20
12,500
67
321.0
272.4
24.68
308.1
266.8
26.45
301.5
263.9
27.38
295.0
261.1
28.22
280.9
254.9
29.82
267.3
249.0
31.37
62
301.3
301.3
23.93
291.0
291.0
25.65
285.4
285.4
26.57
280.3
280.3
27.40
268.6
268.6
29.06
257.2
257.2
30.67
3. Formulas:
SHCBtuh
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCBtuh
Ldb F: hlwb = hewb
4.5 x cfm
Ldb F = Edb F
272.5 263.3
249.4 263.3
kW
32.83 30.99 29.93
31.73 31.10
15,000
67
340.6
307.3
25.42
326.6
301.1
27.31
319.6
298.0
28.28
312.2
294.8
29.18
296.8
288.0
30.80
282.5
281.7
32.43
62
326.0
326.0
24.87
314.3
314.3
26.74
308.3
308.3
27.72
302.3
302.3
28.63
289.3
289.3
30.33
276.9
276.9
32.04
Edb
Ewb
kW
Ldb
Lwb
SHC
TC
LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.
3. Formulas:
SHCBtuh
Ldb F = Edb F
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCBtuh
Ldb F: hlwb = hewb
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equivalent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.
15,000
67
412.4
338.8
32.80
397.2
332.2
35.10
389.4
328.7
36.24
381.5
325.2
37.41
365.1
318.1
39.57
348.7
310.8
41.67
62
382.2
382.2
31.59
370.5
370.5
33.83
364.4
364.4
34.95
358.2
358.2
36.11
345.2
345.2
38.33
331.7
331.7
40.48
29
Edb
Ewb
kW
Ldb
Lwb
SHC
TC
LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.
30
22
98.8
45.0
25.26
94.1
44.0
27.05
91.8
43.4
27.92
89.5
42.9
28.81
84.7
41.7
30.52
22
98.6
48.9
25.15
93.8
47.9
26.92
91.4
47.4
27.77
89.0
46.8
28.65
84.2
45.7
30.35
22
103.4
55.3
25.92
98.5
54.3
27.76
96.0
53.7
28.66
93.5
53.2
29.59
88.4
52.1
31.32
4720
19
90.9
63.7
24.14
86.6
62.5
25.80
84.4
61.9
26.60
82.2
61.2
27.46
77.8
60.0
29.06
5900
19
91.0
70.6
24.06
86.6
69.4
25.71
84.4
68.7
26.52
82.1
68.1
27.34
77.7
66.8
28.94
7080
19
95.6
80.7
24.82
91.0
79.4
26.54
88.7
78.7
27.38
86.3
77.9
28.24
81.5
76.4
29.85
5900
19
96.9
72.3
25.98
92.6
71.1
27.65
90.4
70.5
28.43
88.1
69.8
29.23
83.4
68.5
30.76
22
104.8
50.4
27.15
100.2
49.3
28.90
97.8
48.8
29.76
95.4
48.3
30.63
90.4
47.1
32.29
7080
19
101.8
82.6
26.72
97.2
81.2
28.39
94.8
80.6
29.21
92.4
79.9
30.06
87.6
78.4
31.66
22
110.0
56.8
27.91
105.1
55.7
29.73
102.6
55.2
30.58
100.0
54.6
31.49
94.8
53.5
33.21
7080
19
120.2
87.8
36.77
115.1
86.4
38.70
112.5
85.7
39.69
109.9
85.0
40.65
104.6
83.5
42.46
22
129.9
61.4
38.73
124.3
60.1
40.79
121.4
59.5
41.83
118.6
58.8
42.84
112.8
57.5
44.79
3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCkW x 1000
Ldb C: hlwb = hewb
1.20 x L/s
Ldb C = Edb C
Edb
Ewb
kW
Ldb
Lwb
SHC
TC
LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Leaving Dry Bulb
Leaving Wet Bulb
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross
72
337.3
153.8
25.26
321.5
150.2
27.05
313.7
148.3
27.92
305.5
146.4
28.81
289.4
142.6
30.52
72
336.6
167.2
25.15
320.4
163.5
26.92
312.3
161.7
27.77
304.1
159.7
28.65
287.7
156.2
30.35
72
353.3
189.0
25.92
336.3
185.4
27.76
327.9
183.6
28.66
319.3
181.8
29.59
301.9
177.9
31.32
10,000
67
310.4
217.4
24.14
295.7
213.4
25.80
288.3
211.4
26.60
280.8
209.2
27.46
265.9
204.9
29.06
12,500
67
310.7
241.2
24.06
295.6
236.9
25.71
288.1
234.7
26.52
280.4
232.5
27.34
265.3
228.1
28.94
15,000
67
326.3
275.6
24.82
310.6
271.3
26.54
302.8
268.8
27.38
294.6
266.0
28.24
278.4
260.8
29.85
12,500
67
331.0
246.9
25.98
316.4
242.9
27.65
308.7
240.7
28.43
300.9
238.5
29.23
285.0
234.0
30.76
72
357.9
172.1
27.15
342.2
168.4
28.90
334.2
166.7
29.76
325.8
164.8
30.63
308.7
160.8
32.29
15,000
67
347.7
282.1
26.72
331.8
277.4
28.39
323.8
275.1
29.21
315.7
272.9
30.06
299.1
267.7
31.66
72
375.8
194.1
27.91
358.8
190.2
29.73
350.3
188.5
30.58
341.5
186.6
31.49
323.6
182.7
33.21
15,000
67
410.6
300.0
36.77
393.1
295.2
38.70
384.3
292.8
39.69
375.4
290.3
40.65
357.2
285.1
42.46
72
443.5
209.8
38.73
424.4
205.3
40.79
414.8
203.2
41.83
405.0
201.0
42.84
385.3
196.5
44.79
3. Formulas:
SHCBtuh
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
coil (hlwb)
TCBtuh
Ldb F: hlwb = hewb
4.5 x cfm
Ldb F = Edb F
31
38AH024
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
6
4
2
0
2
4
6
8
10
24
42.9
11.3
35.2
47.0
11.5
35.2
51.4
11.7
35.2
55.5
11.9
35.6
59.9
12.1
36.2
64.3
12.3
36.9
69.2
12.5
37.7
74.1
12.8
38.5
78.9
13.0
39.2
52
25.7
14.2
63.2
28.8
14.9
63.2
31.8
15.6
63.2
35.5
16.3
63.2
39.3
16.9
63.2
42.9
17.5
63.1
46.8
18.1
63.6
50.7
18.8
64.1
54.7
19.4
64.7
38AH028
SST
(C)
6
4
2
0
2
4
6
8
10
32
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
24
51.1
13.4
35.4
55.2
13.8
36.0
59.7
14.1
36.5
64.5
14.4
37.1
69.3
14.7
37.8
74.0
15.0
38.8
79.4
15.3
39.6
85.0
15.7
40.5
90.6
16.0
41.5
52
33.3
17.7
63.1
37.0
18.4
63.0
40.5
19.1
63.1
43.9
19.8
63.4
47.9
20.6
64.0
51.6
21.3
64.4
55.6
22.2
65.1
59.8
22.9
65.7
64.0
23.6
66.4
SST
(C)
6
4
2
0
2
4
6
8
10
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
52
39.5
21.8
63.8
43.5
22.7
63.8
47.7
23.5
63.9
52.2
24.5
63.8
57.0
25.3
64.0
61.7
26.2
64.2
66.7
27.1
64.8
71.7
28.0
65.4
76.8
29.0
66.0
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (C)
Saturated Suction Temperature
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (C)
Saturated Suction Temperature
Gross Cooling Capacity (kW)
52
12.8
7.1
63.2
14.4
7.5
63.2
15.9
7.8
63.2
17.7
8.2
63.2
19.7
8.5
63.2
21.4
8.8
63.1
23.4
9.1
63.6
25.4
9.4
64.1
27.3
9.7
64.7
52
15.6
8.9
63.2
17.4
9.2
63.2
19.1
9.6
63.4
21.2
9.9
63.2
23.4
10.2
63.0
25.5
10.5
62.9
27.7
10.9
63.4
29.9
11.2
63.8
32.3
11.5
64.3
52
16.7
8.9
63.1
18.5
9.2
63.0
20.3
9.5
63.1
22.0
9.9
63.4
23.9
10.3
64.0
25.8
10.7
64.4
27.8
11.1
65.1
29.9
11.4
65.7
32.0
11.8
66.4
52
23.9
13.0
64.4
26.1
13.4
64.5
28.6
13.9
64.3
31.0
14.5
64.4
33.6
15.1
65.0
36.1
15.7
65.4
38.9
16.2
66.2
41.7
16.8
66.9
44.5
17.4
67.7
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
33
38AH024
SST
(F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
38AH028
SST
(F)
20
25
30
35
40
45
50
34
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
75
168.4
13.5
95.0
189.0
13.9
97.0
210.2
14.3
98.0
231.6
14.8
99.0
256.8
15.1
102.0
284.0
15.7
104.0
306.0
16.0
106.0
SST
(F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
20
25
30
35
40
45
50
kW
SDT
SST
TC
75
198.0
16.6
97.0
223.5
17.1
97.0
249.4
17.6
97.0
276.2
18.0
99.0
304.5
18.7
101.0
335.0
19.3
103.0
367.0
19.7
106.0
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature
Gross Cooling Capacity (1000 Btuh)
NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature
Gross Cooling Capacity (1000 Btuh)
NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
kW
SDT
SST
TC
35
16
59.2
59.2
11.89
57.6
57.6
12.77
56.0
56.0
13.51
54.4
54.4
14.52
52.5
52.5
15.36
50.8
50.8
16.16
49.0
49.0
17.15
47.1
47.1
18.14
16
66.3
66.3
12.32
64.5
64.5
13.20
62.6
62.6
14.08
60.7
60.7
15.10
58.7
58.7
16.06
56.7
56.7
17.00
54.6
54.6
17.99
52.5
52.5
18.97
3500
20
64.9
48.3
12.24
63.0
47.3
13.11
61.1
46.3
13.95
59.1
45.3
14.96
57.1
44.3
15.88
55.0
43.2
16.76
52.9
42.1
17.73
50.7
41.0
18.70
4700
20
71.3
58.3
12.63
69.2
57.3
13.50
66.9
56.2
14.46
64.6
55.2
15.46
62.4
54.2
16.49
60.0
53.1
17.47
57.5
21.9
18.43
55.1
50.8
19.38
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
36
5900
20
76.1
67.6
12.92
73.7
66.6
13.78
71.2
65.5
14.83
68.7
64.3
15.83
66.4
63.3
16.94
63.7
62.1
18.00
61.0
60.9
18.95
58.4
58.1
19.89
16
72.2
72.2
12.68
70.2
70.2
13.56
68.1
68.1
14.56
66.0
66.0
15.58
64.0
64.0
16.66
61.7
61.7
17.72
59.4
59.4
18.71
57.1
57.1
19.69
4700
20
77.9
61.3
15.20
75.9
60.4
16.28
73.6
59.3
17.38
71.4
58.3
18.52
69.0
57.2
19.60
66.7
56.1
20.76
64.3
21.9
21.70
61.5
53.7
23.52
16
71.6
71.6
14.75
70.0
70.0
15.96
68.2
68.2
16.95
66.3
66.3
18.01
64.3
64.3
19.02
62.4
62.4
20.19
60.4
60.4
21.17
58.1
58.1
22.76
5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
16
78.2
78.2
15.22
76.4
76.4
16.31
74.3
74.3
17.43
72.2
72.2
18.60
70.1
70.1
19.74
67.9
67.9
20.92
65.7
65.7
21.89
63.0
63.0
23.87
16
84.3
84.3
15.63
82.2
82.2
16.63
79.7
79.7
17.86
77.5
77.5
19.13
75.1
75.1
20.36
72.6
72.6
21.53
70.1
70.1
22.49
67.0
67.0
24.76
5900
20
83.5
70.9
15.60
81.3
69.9
16.58
78.6
68.7
17.77
76.2
67.7
19.00
73.6
66.5
20.18
71.0
65.3
21.32
68.4
64.2
22.25
65.1
62.8
24.34
7050
20
88.5
79.8
15.95
86.0
78.7
16.84
82.9
77.4
18.11
80.3
76.2
19.41
77.5
74.9
20.66
74.6
73.6
21.79
71.8
72.4
22.72
68.1
68.1
25.02
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
5900
20
93.5
75.3
18.83
90.9
74.2
20.04
88.3
73.1
21.38
85.6
71.9
22.83
82.9
70.7
24.15
80.2
69.5
25.53
77.2
68.1
26.97
74.5
66.9
28.50
16
86.2
86.2
18.26
84.1
84.1
19.50
82.1
82.1
20.76
79.9
79.9
22.24
77.7
77.7
23.50
75.5
75.5
24.83
73.1
73.1
26.24
70.7
70.7
27.83
7050
20
99.5
84.8
19.30
96.7
83.5
20.50
93.8
82.2
21.93
90.8
80.9
23.37
87.8
79.5
24.77
84.8
78.2
26.21
81.5
76.7
27.72
78.5
75.4
29.22
16
93.4
93.4
18.82
91.1
91.1
20.06
88.8
88.8
21.43
86.2
86.2
22.90
83.8
83.8
24.26
81.2
81.2
25.68
78.5
78.5
27.19
75.9
75.9
28.75
5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
37
62
195.4
195.4
13.19
188.3
188.3
14.37
184.4
184.4
14.93
180.3
180.3
15.62
171.8
171.8
16.78
162.9
162.9
18.11
62
220.2
220.2
13.60
211.5
211.5
14.90
206.8
206.8
15.57
202.0
202.0
16.26
192.3
192.3
17.63
182.0
182.0
19.07
7500
67
211.4
169.2
13.46
202.5
164.7
14.69
197.8
162.4
15.31
192.9
160.0
15.99
183.0
155.0
17.24
172.5
149.8
18.60
10,000
67
232.7
206.1
13.81
221.8
201.1
15.13
216.2
198.6
15.83
210.4
195.9
16.51
199.1
190.8
17.91
187.1
185.3
19.32
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
38
12,500
67
248.1
240.6
14.07
235.7
235.2
15.45
229.4
229.4
16.21
223.0
223.0
16.88
210.6
210.6
18.38
197.4
197.4
19.83
62
241.2
241.2
13.95
230.9
230.9
15.34
225.6
225.6
16.10
220.1
220.1
16.79
209.5
209.5
18.33
197.9
197.9
19.86
10,000
67
255.0
216.3
16.63
244.5
211.5
18.16
239.3
209.1
18.92
232.6
206.1
19.72
221.6
201.0
21.22
193.9
188.4
23.00
62
239.4
239.4
16.24
230.4
230.4
17.81
225.9
225.9
18.53
220.8
220.8
19.29
211.6
211.6
20.83
187.8
187.8
22.74
5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
62
261.4
261.4
16.78
251.9
251.9
18.35
247.2
247.2
19.15
240.8
240.8
20.02
230.4
230.4
21.55
204.6
204.6
23.44
62
280.5
280.5
17.26
270.3
270.3
18.81
265.2
265.2
19.68
257.4
257.4
20.62
245.8
245.8
22.14
217.6
217.6
23.98
kW
29.06 27.79 27.14 29.48 28.28 27.95
12,500
67
271.7
250.9
17.04
260.6
246.1
18.56
255.0
243.6
19.38
247.1
240.2
20.25
234.9
234.8
21.73
205.1
221.8
23.46
15,000
67
286.3
283.4
17.41
274.5
274.5
18.91
268.7
268.7
19.78
259.5
259.5
20.70
246.2
246.2
22.16
214.4
214.4
23.85
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
12,500
67
305.2
265.5
20.44
292.9
260.2
22.47
286.3
257.3
23.28
280.3
254.6
24.28
267.2
248.9
26.15
253.7
243.1
28.08
62
288.2
288.2
20.03
278.2
278.2
22.00
272.9
272.9
22.83
267.8
267.8
23.82
257.2
257.2
25.72
246.0
246.0
27.70
15,000
67
324.0
300.0
20.89
310.4
294.0
23.03
303.0
290.8
23.83
296.6
287.9
24.89
282.1
281.6
26.80
267.4
267.4
28.76
62
311.8
311.8
20.60
300.5
300.5
22.71
294.4
294.0
23.55
288.9
288.9
24.60
276.7
276.7
26.56
264.1
264.1
28.59
5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
39
17
60.2
58.0
13.57
57.3
56.2
14.80
55.8
55.8
15.40
54.5
54.5
16.00
51.9
51.9
17.21
17
66.7
66.6
14.22
63.1
63.1
15.38
61.7
61.7
16.04
60.3
60.3
16.69
57.4
57.4
17.97
3500
19
65.5
48.4
13.96
62.4
47.3
15.28
60.7
46.7
15.92
59.1
46.0
16.54
55.7
44.7
17.74
4720
19
69.8
57.3
14.29
66.0
55.8
15.58
64.7
55.3
16.35
62.6
54.5
16.91
59.1
53.2
18.18
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
40
5900
19
73.8
66.6
14.58
69.9
65.1
15.95
68.1
64.2
16.67
66.3
63.5
17.36
62.6
61.5
18.68
17
71.5
71.5
14.41
68.6
68.6
15.88
67.0
67.0
16.58
65.4
65.4
17.28
62.2
62.2
18.63
4720
19
77.8
60.3
17.38
74.2
58.9
18.91
72.4
58.2
19.66
70.5
57.5
20.39
66.9
56.1
21.89
17
72.0
72.0
16.85
69.2
69.2
18.36
67.8
67.8
19.12
66.4
66.4
19.86
63.5
63.5
21.39
5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
17
78.6
78.6
17.45
75.5
75.5
19.06
73.9
73.9
19.86
72.3
72.3
20.64
69.1
69.1
22.26
17
84.0
84.0
17.91
80.7
80.7
19.63
78.9
78.9
20.46
77.1
77.1
21.28
73.6
73.6
22.95
5900
19
82.5
69.9
17.77
78.6
68.4
19.40
76.7
67.7
20.20
74.8
67.0
20.97
70.7
65.2
22.50
7080
19
86.3
78.8
18.12
82.0
77.2
19.76
80.0
76.3
20.57
78.0
75.3
21.39
73.9
73.1
23.01
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
5900
19
92.6
73.9
22.04
88.5
72.3
23.82
86.5
71.5
24.69
84.4
70.7
25.58
80.1
69.0
27.28
17
87.2
86.7
21.51
83.3
83.3
23.10
81.6
81.6
23.96
79.9
79.9
24.86
76.6
76.6
26.63
7080
19
97.5
83.3
22.60
93.0
81.5
24.41
90.8
80.6
25.30
88.6
79.7
26.21
84.1
77.7
27.99
17
93.0
93.0
22.06
89.9
89.9
24.03
87.7
87.7
24.84
85.9
85.9
25.77
82.1
82.1
27.60
5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
41
62
205.5
198.2
13.57
195.6
191.8
14.80
190.7
190.7
15.40
186.2
186.2
16.00
177.3
177.3
17.21
62
227.7
227.6
14.22
215.5
215.5
15.38
210.8
210.8
16.04
205.8
205.8
16.69
195.9
195.9
17.97
7500
67
223.6
165.2
13.96
213.0
161.5
15.28
207.3
159.4
15.92
201.7
157.0
16.54
190.3
152.7
17.74
10,000
67
238.5
195.6
14.29
225.5
190.4
15.58
220.9
188.8
16.35
213.9
186.1
16.91
202.0
181.8
18.18
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
42
12,500
67
252.2
227.4
14.58
238.9
222.3
15.95
232.6
219.3
16.67
226.5
216.8
17.36
213.6
210.1
18.68
62
244.3
244.3
14.41
234.2
234.2
15.88
228.8
228.8
16.58
223.3
223.3
17.28
212.3
212.3
18.63
10,000
67
265.9
205.9
17.38
253.4
201.2
18.91
247.2
198.9
19.66
240.9
196.4
20.39
228.4
191.6
21.89
62
245.9
245.9
16.85
236.3
236.3
18.36
231.5
231.5
19.12
226.7
226.7
19.86
216.9
216.9
21.39
5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
62
268.6
268.6
17.45
257.8
257.8
19.06
252.4
252.4
19.86
246.9
246.9
20.64
236.1
236.1
22.26
62
287.0
287.0
17.91
275.5
275.5
19.63
269.5
269.5
20.46
263.5
263.5
21.28
251.2
251.2
22.95
12,500
67
281.7
238.7
17.77
268.5
233.6
19.40
262.0
231.2
20.20
255.4
228.8
20.97
241.4
222.7
22.50
15,000
67
294.6
269.2
18.12
280.0
263.6
19.76
273.4
260.6
20.57
266.5
257.1
21.39
252.5
249.8
23.01
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
12,500
67
316.4
252.2
22.04
302.4
246.8
23.82
295.4
244.2
24.69
288.2
241.6
25.58
273.4
235.7
27.28
62
297.8
296.2
21.51
284.3
284.3
23.10
278.7
278.6
23.96
273.0
273.0
24.86
261.4
261.4
26.63
15,000
67
333.0
284.4
22.60
317.7
278.3
24.41
310.2
275.3
25.30
302.6
272.1
26.21
287.3
265.3
27.99
62
317.7
317.7
22.06
306.9
306.9
24.03
299.6
299.6
24.84
293.3
293.3
25.77
280.5
280.5
27.60
5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
43
AIRFLOW
(L/s)
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050
016
024
028
034
1-ROW
STEAM*
Cap.
(kW)
Ldb
117
129
140
135
140
146
149
166
183
164
180
196
61
53
48
53
46
41
50
44
41
47
41
38
2-ROW
HOT WATER COIL
Water
Cap.
Ldb
Flow
(kW)
(L/s)
120
62
2.6
137
55
3.0
154
51
3.3
150
58
3.3
170
52
3.7
191
49
4.1
189
60
4.1
218
53
4.7
247
50
5.4
215
57
4.7
247
51
5.4
278
48
6.0
PD
(kPa)
13.3
16.2
19.5
15.6
18.6
22.3
16.9
20.8
25.4
18.5
22.8
27.7
UNIT
40RM
AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
016
024
028
034
1-ROW
STEAM*
Cap.
Ldb
Cap.
402
458
479
458
487
499
511
575
626
560
621
670
141
129
118
129
115
105
122
112
106
117
107
101
412.0
471.0
529.0
506.0
584.0
652.0
649.0
752.0
842.0
735.0
850.0
950.0
2-ROW
HOT WATER COIL
Water
Ldb
Flow
(Gpm)
145
41.2
133
47.1
125
52.9
138
50.6
128
58.4
120
65.2
140
64.9
130
75.2
122
84.2
136
73.5
126
85.0
119
95.0
PD
4.5
5.5
6.6
5.1
6.3
7.5
5.7
7.1
8.5
6.2
7.8
9.3
LEGEND
Cap. Capacity (kW)
Ldb Leaving-Air Dry-Bulb Temp (C)
PD
Pressure Drop (kPa)
LEGEND
Cap. Capacity (Btuh in thousands)
Ldb Leaving-Air Dry-Bulb Temp (F)
PD
Pressure Drop (ft water)
*Based on 34.5 kPag steam, 15.6 C entering-air temperature. All steam coils are
non-freeze type.
Based on 93.3 C entering-water temperature, 11.1 C water temperature drop,
15.6 C entering-air temperature.
NOTES:
1. Maximum operating limits for heating coils: 138 kPag at 126.7 C.
*Based on 5 psig steam, 60 F entering-air temperature. All steam coils are nonfreeze type.
Based on 200 F entering-water temperature, 20 F water temperature drop, 60 F
entering-air temperature.
NOTES:
1. Maximum operating limits for heating coils: 20 psig at 260 F.
Capacity (kW)
1.23 x 10-3 x L/s
3. See Heating Correction Factors table.
Capacity (Btuh)
1.1 x cfm
3. See Heating Correction Factors table.
11
16
Steam Pressure
(kPag)
0
14
35
4
1.07
1.10
1.14
STEAM COIL
Entering-Air Temp (C)
10
16
20
0.99
0.91
0.86
1.02
0.95
0.90
1.07
0.99
0.95
25
0.43
0.58
0.73
0.89
1.04
0.35
0.51
0.66
0.82
0.97
0.26
0.42
0.58
0.74
0.90
25
0.80
0.84
0.89
NOTE: Multiply capacity given in the Coil Accessory Heating Capacities table by
the correction factor for conditions at which unit is actually operating. Correct
leaving-air temperature using formula in Note 2 of Coil Accessory Heating Capacities table.
44
Water Temp
Drop
(F)
10
20
30
Steam Pressure
(psig)
0
2
5
40
1.06
1.09
1.13
STEAM COIL
Entering-Air Temp (F)
50
60
70
0.98
0.91
0.85
1.02
0.95
0.89
1.06
1.00
0.93
80
0.41
0.58
0.75
0.92
1.09
0.33
0.51
0.68
0.85
1.02
0.24
0.43
0.60
0.78
0.95
80
0.78
0.82
0.87
NOTE: Multiply capacity given in the Coil Accessory Heating Capacities table by
the correction factor for conditions at which unit is actually operating. Correct
leaving-air temperature using formula in Note 2 of Coil Accessory Heating Capacities table.
40RM016
2120
2500
2830
3210
3540
r/s
7.13
8.13
9.03
10.07
10.99
kW
0.44
0.68
0.96
1.37
1.81
r/s
7.91
8.80
9.63
10.62
11.50
kW
0.52
0.78
1.07
1.48
1.93
40RM024
2830
3300
3780
4250
4720
8.86
10.14
11.43
12.74
14.05
0.94
1.44
2.11
2.96
4.01
9.48
10.69
11.93
13.19
14.47
1.04
1.56
2.25
3.12
4.19
10.65
11.70
12.84
14.02
15.23
1.26
1.81
2.52
3.43
4.54
11.84
12.71
13.71
14.81
15.96
1.53
2.08
2.81
3.74
4.88
13.01
13.73
14.60
15.59
16.66
1.85
2.41
3.14
4.08
5.24
14.10
14.74
15.49
16.37
17.36
2.19
2.77
3.51
4.45
5.62
15.08
15.71
16.39
17.17
18.07
2.53
3.15
3.91
4.85
6.03
40RM028
3540
4130
4720
5310
5900
7.60
8.68
9.78
10.89
12.00
0.96
1.47
2.15
3.01
4.07
8.16
9.18
10.23
11.30
12.38
1.09
1.62
2.32
3.20
4.29
9.27
10.13
11.07
12.06
13.09
1.38
1.94
2.67
3.59
4.72
10.34
11.07
11.89
12.80
13.75
1.68
2.29
3.05
4.00
5.17
11.30
11.99
12.72
13.53
14.41
1.97
2.63
3.45
4.43
5.63
12.15
12.84
13.53
14.27
15.07
2.28
2.97
3.84
4.88
6.11
12.97
13.60
14.29
14.99
15.74
2.68
3.32
4.23
5.33
6.61
40RM034
4250
4960
5660
6370
7080
8.68
9.93
11.21
12.51
13.82
1.48
2.35
3.45
4.85
6.59
9.17
10.38
11.63
12.89
14.17
1.68
2.53
3.66
5.08
6.85
10.27
11.21
12.38
13.58
14.81
2.07
2.90
4.07
5.54
7.36
11.27
11.99
13.08
14.22
15.40
2.41
3.28
4.49
6.01
7.88
12.19
12.78
13.76
14.83
15.97
2.77
3.68
4.93
6.49
8.40
13.03
13.56
14.45
15.44
16.52
3.13
4.10
5.39
6.99
8.94
13.81
14.32
15.14
16.05
17.06
3.50
4.51
5.87
7.51
9.49
600
r/s
19.47
19.65
19.97
kW
3.57
4.12
4.69
UNIT
(Std 3-Row
Coil)
AIRFLOW
(L/s)
50
250
r/s
kW
13.26
1.51
13.78
1.87
14.25
2.24
14.80
2.71
15.31
3.20
300
r/s
kW
14.26
1.77
14.76
2.18
15.23
2.58
15.76
3.09
16.24
3.60
40RM016
2120
2500
2830
3210
3540
r/s
15.20
15.67
16.13
16.66
17.13
kW
2.05
2.49
2.92
3.48
4.02
r/s
16.12
16.53
16.97
17.50
17.97
40RM024
2830
3300
3780
4250
4720
15.90
16.50
17.13
17.88
18.77
2.86
3.53
4.32
5.30
6.52
16.75
17.33
17.97
18.67
19.43
3.18
3.91
4.76
5.76
6.99
17.53
18.17
18.83
19.48
3.52
4.32
5.22
6.24
18.30
18.92
19.55
3.89
4.70
5.67
19.03
19.60
4.23
5.10
40RM028
3540
4130
4720
5310
5900
13.85
14.31
14.99
15.68
16.39
3.29
3.71
4.62
5.77
7.10
14.50
15.01
15.65
16.34
17.03
3.80
4.17
5.02
6.20
7.60
15.22
15.74
16.27
16.95
17.64
4.40
4.79
5.46
6.64
8.08
15.83
16.33
16.88
17.53
18.22
5.13
5.37
5.97
7.09
8.57
16.42
17.00
17.50
18.09
5.74
6.04
6.57
7.58
40RM034
4250
4960
5660
6370
7080
14.43
15.04
15.81
16.66
17.61
3.88
4.92
6.34
8.04
10.06
14.98
15.71
16.47
17.27
18.16
4.36
5.32
6.81
8.57
10.64
15.84
16.33
17.10
17.88
4.96
5.74
7.28
9.10
16.48
16.93
17.69
5.50
6.20
7.74
17.16
17.51
18.26
6.21
6.70
8.21
17.96
18.09
7.26
7.29
UNIT
(Std 3-Row
Coil)
AIRFLOW
(L/s)
350
400
550
r/s
18.67
18.90
19.26
19.75
kW
3.24
3.77
4.33
5.04
45
0.2
Rpm Bhp
475
0.70
528
1.04
578
1.43
637
1.99
690
2.59
Rpm
796
827
855
888
919
Bhp
2.02
2.51
3.00
3.64
4.29
Rpm
856
886
914
946
975
Bhp
2.38
2.92
3.46
4.15
4.83
40RM024
6,000
7,000
8,000
9,000
10,000
532
608
686
764
843
1.25
1.93
2.83
3.97
5.38
569
641
716
791
868
1.39
2.09
3.01
4.18
5.62
639
702
770
841
914
1.69
2.42
3.38
4.59
6.09
711
763
823
888
957
2.06
2.80
3.77
5.02
6.55
781
824
876
935
1000
2.48
3.23
4.21
5.47
7.02
846
885
930
982
1042
2.93
3.71
4.70
5.96
7.53
905
943
983
1030
1084
3.39
4.23
5.24
6.51
8.08
40RM028
7,500
8,750
10,000
11,250
12,500
456
521
587
653
720
1.29
1.98
2.88
4.03
5.46
490
551
614
678
743
1.47
2.18
3.11
4.29
5.75
556
608
664
724
785
1.85
2.61
3.59
4.82
6.33
621
664
714
768
825
2.25
3.07
4.09
5.37
6.93
678
720
763
812
865
2.64
3.53
4.62
5.95
7.55
729
770
812
856
904
3.06
3.99
5.15
6.54
8.20
778
816
857
899
944
3.60
4.45
5.68
7.14
8.86
40RM034
9,000
10,500
12,000
13,500
15,000
521
596
673
751
829
1.99
3.16
4.63
6.51
8.84
550
623
698
773
850
2.25
3.40
4.90
6.82
9.19
616
672
743
815
888
2.77
3.89
5.45
7.44
9.88
676
720
785
853
924
3.23
4.40
6.02
8.06
10.57
731
767
826
890
958
3.72
4.94
6.62
8.71
11.27
782
814
867
927
991
4.20
5.50
7.23
9.38
11.99
829
859
908
963
1024
4.70
6.05
7.87
10.07
12.73
UNIT
(Std 3-Row
Coil)
AIRFLOW
(Cfm)
40RM016
4,500
5,300
6,000
6,800
7,500
1.0
1.2
40RM WITH STANDARD COIL FAN PERFORMANCE DATA 1.4-2.4 in. wg ESP ENGLISH
40RM016
4,500
5,300
6,000
6,800
7,500
Rpm
912
940
968
1000
1028
Bhp
2.75
3.33
3.92
4.67
5.39
Rpm
967
992
1018
1050
1078
40RM024
6,000
7,000
8,000
9,000
10,000
954
990
1028
1073
1126
3.83
4.74
5.79
7.11
8.75
1005
1040
1078
1120
1166
4.27
5.24
6.38
7.72
9.37
40RM028
7,500
8,750
10,000
11,250
12,500
831
859
900
941
984
4.41
4.97
6.20
7.73
9.53
870
901
939
980
1022
40RM034
9,000
10,500
12,000
13,500
15,000
866
902
949
1000
1057
5.20
6.60
8.50
10.78
13.49
899
942
988
1036
1090
UNIT
(Std 3-Row
Coil)
AIRFLOW
(Cfm)
46
1.4
1.6
5.10
5.59
6.74
8.32
10.19
1052
1090
1130
1169
913
944
976
1017
1058
4.72
5.80
7.00
8.37
5.90
6.42
7.33
8.90
10.84
1098
1135
1173
950
980
1013
1052
1093
5.22
6.30
7.60
6.88
7.20
8.00
9.51
11.49
5.85
7.14
9.14
11.49
14.28
950
980
1026
1073
6.65
7.70
9.76
12.21
989
1016
1062
7.38
8.31
10.38
2.2
Rpm
1120
1134
1156
1185
1142
1176
985
1020
1050
1086
1029
1051
1095
2.4
Bhp
4.35
5.06
5.80
6.76
5.67
6.84
7.70
8.10
8.82
10.16
8.32
8.99
11.01
Rpm
1168
1179
1198
1077
1085
Bhp
4.79
5.52
6.29
9.74
9.77
AIRFLOW
(L/s)
50
250
300
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
016
2120
2500
2830
3210
3540
7.28
8.32
9.25
10.33
11.29
0.45
0.71
1.00
1.42
1.88
8.05
8.97
9.83
10.85
11.77
0.54
0.80
1.10
1.54
2.01
9.60
10.29
10.99
11.87
12.69
0.75
1.02
1.33
1.78
2.27
11.00
11.59
12.16
12.90
13.62
1.00
1.30
1.62
2.07
2.56
12.21
12.78
13.29
13.93
14.56
1.26
1.59
1.93
2.40
2.90
13.28
13.84
14.34
14.93
15.49
1.51
1.89
2.27
2.76
3.27
14.27
14.80
15.30
15.87
16.40
1.78
2.19
2.60
3.14
3.67
024
2830
3300
3780
4250
4720
9.03
10.34
11.67
13.01
14.36
0.96
1.48
2.17
3.05
4.15
9.62
10.86
12.14
13.44
14.75
1.06
1.60
2.31
3.21
4.32
10.77
11.85
13.02
14.23
15.48
1.29
1.85
2.58
3.51
4.66
11.94
12.84
13.88
15.00
16.18
1.56
2.12
2.87
3.82
4.99
13.08
13.85
14.75
15.77
16.87
1.87
2.45
3.20
4.16
5.35
14.15
14.84
15.63
16.54
17.56
2.20
2.80
3.56
4.53
5.73
15.12
15.78
16.50
17.32
18.26
2.54
3.18
3.96
4.94
6.14
028
3540
4130
4720
5310
5900
7.94
9.08
10.24
11.42
12.60
1.04
1.59
2.33
3.26
4.42
8.51
9.57
10.68
11.81
12.96
1.18
1.75
2.51
3.46
4.64
9.65
10.55
11.53
12.57
13.65
1.48
2.10
2.88
3.88
5.09
10.73
11.52
12.39
13.33
14.33
1.79
2.46
3.29
4.32
5.57
11.68
12.45
13.24
14.09
15.01
2.10
2.81
3.70
4.77
6.07
12.53
13.28
14.05
14.85
15.70
2.46
3.17
4.11
5.24
6.58
13.40
14.04
14.80
15.58
16.38
2.95
3.55
4.51
5.70
7.10
034
4250
4960
5660
6370
7080
8.99
10.33
11.68
13.04
14.42
1.62
2.51
3.68
5.18
7.05
9.49
10.77
12.07
13.40
14.74
1.78
2.70
3.90
5.42
7.31
10.44
11.59
12.81
14.07
15.36
2.12
3.08
4.33
5.90
7.84
11.39
12.40
13.52
14.71
15.94
2.49
3.49
4.77
6.39
8.38
12.32
13.22
14.23
15.34
16.51
2.86
3.92
5.25
6.90
8.93
13.18
14.03
14.95
15.97
17.08
3.22
4.35
5.74
7.44
9.51
13.95
14.79
15.66
16.61
17.65
3.59
4.78
6.23
7.98
10.10
AIRFLOW
(L/s)
350
400
550
600
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
016
2120
2500
2830
3210
3540
15.21
15.69
16.18
16.75
17.26
2.05
2.49
2.94
3.52
4.09
16.11
16.54
17.01
17.57
18.07
2.33
2.80
3.28
3.90
4.50
16.98
17.35
17.79
18.34
18.84
2.62
3.12
3.63
4.29
4.93
17.83
18.14
18.54
19.08
19.57
2.93
3.44
3.97
4.67
5.35
18.66
18.90
19.27
19.78
3.24
3.77
4.33
5.06
19.47
19.64
19.97
3.57
4.11
4.69
024
2830
3300
3780
4250
4720
16.01
16.67
17.35
18.11
18.96
2.88
3.57
4.39
5.37
6.58
16.85
17.50
18.17
18.88
19.67
3.22
3.96
4.82
5.83
7.05
17.64
18.28
18.95
19.63
3.56
4.36
5.27
6.31
18.39
19.03
19.68
3.91
4.75
5.72
19.12
19.73
4.26
5.15
028
3540
4130
4720
5310
5900
14.57
14.76
15.49
16.26
17.04
3.97
3.99
4.92
6.15
7.61
14.95
15.51
16.15
16.91
17.68
4.41
4.57
5.37
6.61
8.11
15.67
16.36
16.78
17.51
18.28
5.07
5.46
5.88
7.08
8.62
16.50
17.00
17.42
18.10
5.59
6.04
6.50
7.58
034
4250
4960
5660
6370
7080
14.68
15.51
16.35
17.24
18.22
4.00
5.20
6.72
8.54
10.70
15.38
16.17
17.01
17.87
4.49
5.63
7.21
9.10
16.12
16.80
17.64
5.14
6.09
7.69
17.00
17.41
18.23
6.15
6.61
8.18
47
AIRFLOW
(Cfm)
0.0
0.2
1.0
1.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
016
4,500
5,300
6,000
6,800
7,500
437
499
555
620
677
0.61
0.95
1.34
1.91
2.52
483
538
590
651
706
0.72
1.07
1.48
2.06
2.69
576
617
659
712
761
1.01
1.37
1.79
2.39
3.04
660
696
730
774
817
1.35
1.74
2.17
2.78
3.44
732
767
798
836
873
1.69
2.13
2.59
3.22
3.89
797
830
860
896
929
2.03
2.53
3.04
3.71
4.39
856
888
918
952
984
2.38
2.94
3.49
4.21
4.93
024
6,000
7,000
8,000
9,000
10,000
542
620
700
781
862
1.29
1.99
2.92
4.10
5.56
577
652
728
806
885
1.42
2.15
3.10
4.30
5.79
646
711
781
854
929
1.72
2.48
3.46
4.71
6.24
716
771
833
900
971
2.09
2.85
3.85
5.13
6.70
785
831
885
946
1012
2.51
3.28
4.29
5.58
7.18
849
890
938
993
1054
2.95
3.76
4.78
6.08
7.69
907
947
990
1039
1096
3.40
4.27
5.32
6.62
8.24
028
7,500
8,750
10,000
11,250
12,500
476
545
615
685
756
1.39
2.14
3.12
4.37
5.92
510
574
641
709
778
1.58
2.35
3.36
4.64
6.22
579
633
692
754
819
1.99
2.81
3.87
5.20
6.83
644
691
743
800
860
2.40
3.29
4.41
5.79
7.47
701
747
794
845
901
2.81
3.77
4.96
6.40
8.14
752
797
843
891
942
3.29
4.25
5.51
7.02
8.83
804
842
888
935
983
3.96
4.76
6.05
7.64
9.52
034
9,000
10,500
12,000
13,500
15,000
539
620
701
783
865
2.18
3.37
4.94
6.95
9.45
569
646
724
804
884
2.39
3.62
5.22
7.27
9.81
626
695
769
844
921
2.85
4.13
5.80
7.91
10.52
683
744
811
883
956
3.34
4.68
6.40
8.57
11.24
739
793
854
920
991
3.83
5.25
7.04
9.26
11.98
791
842
897
958
1025
4.32
5.83
7.69
9.97
12.75
837
888
940
996
1059
4.82
6.41
8.36
10.71
13.54
AIRFLOW
(Cfm)
1.6
2.2
2.4
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
016
4,500
5,300
6,000
6,800
7,500
912
942
971
1005
1036
2.75
3.34
3.95
4.72
5.48
967
992
1020
1054
1084
3.12
3.76
4.40
5.23
6.04
1019
1041
1067
1101
1131
3.52
4.18
4.86
5.75
6.61
1070
1088
1112
1145
1174
3.92
4.61
5.33
6.27
7.17
1120
1134
1156
1187
4.35
5.06
5.81
6.79
1168
1179
1198
4.79
5.52
6.29
024
6,000
7,000
8,000
9,000
10,000
961
1000
1041
1086
1138
3.86
4.79
5.88
7.21
8.83
1011
1050
1090
1133
1180
4.31
5.32
6.47
7.82
9.46
1058
1097
1137
1178
4.77
5.85
7.07
8.47
1104
1142
1181
5.24
6.38
7.67
1147
1184
5.71
6.91
028
7,500
8,750
10,000
11,250
12,500
874
886
930
976
1023
5.33
5.36
6.60
8.25
10.20
897
930
969
1014
1061
5.91
6.13
7.20
8.86
10.88
940
982
1007
1051
1097
6.80
7.32
7.89
9.49
11.56
990
1020
1045
1086
7.50
8.10
8.71
10.17
034
9,000
10,500
12,000
13,500
15,000
881
930
981
1035
1093
5.37
6.97
9.02
11.45
14.35
923
970
1021
1072
6.03
7.55
9.67
12.20
967
1008
1058
6.89
8.17
10.32
1020
1045
1094
8.25
8.86
10.97
48
1.4
AIRFLOW
(L/s)
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050
PRESSURE DROP
(Pa)
20
30
42
32
47
64
36
55
76
47
71
98
UNIT
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. The medium-static drive and standard motor combination is not
available for 016-028 sizes. Use alternate motor if medium-static
drive is required for these sizes.
40RM
016
40RM
024
40RM
028
40RM
034
AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
PRESSURE DROP
(in. wg)
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40
49
UNIT
40RM
AIRFLOW
(L/s)
Straight
VANE DEFLECTION
221/2
45
UNIT
40RM
AIRFLOW
(Cfm)
Straight
VANE DEFLECTION
221/2
45
016
024
028
034
2800
3800
4700
5650
15.41
18.17
23.26
25.97
13.25
15.44
19.89
22.00
9.55
11.20
14.38
15.89
016
024
028
034
6,000
8,000
10,000
12,000
50
60
76
85
43
51
65
72
31
37
47
52
NOTE: Throw distances shown are for 0.381 m/sec terminal velocity. Use the following multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(m/sec)
0.254
0.508
0.762
NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following
multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150
THROW FACTOR
X 1.50
X 0.75
X 0.50
THROW FACTOR
X 1.50
X 0.75
X 0.50
024
028
034
AIRFLOW
(L/s)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050
24
39
56
41
64
91
37
59
86
50
80
114
2
5
7
5
10
15
5
7
12
7
12
17
Hot Water
36
57
82
60
93
132
67
109
157
92
147
210
HEATING COILS
Steam
36
57
82
60
93
132
67
109
157
92
147
210
Electric
14
24
37
26
43
65
22
39
60
32
56
85
ECONOMIZER
15
22
37
23
43
69
15
22
35
20
35
52
024
028
034
50
AIRFLOW
(Cfm)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
0.10
0.16
0.23
0.16
0.26
0.37
0.15
0.24
0.34
0.20
0.32
0.46
0.01
0.02
0.03
0.02
0.04
0.06
0.02
0.03
0.05
0.03
0.05
0.07
Hot Water
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85
HEATING COILS
Steam
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85
Electric
0.06
0.10
0.15
0.10
0.17
0.26
0.09
0.16
0.24
0.13
0.22
0.34
ECONOMIZER
0.06
0.09
0.15
0.09
0.17
0.28
0.06
0.09
0.14
0.08
0.14
0.21
LEGEND
TXV Thermostatic Expansion Valve
Piping
*Field supplied.
Double riser may be required. See Application Data on page 66.
NOTES:
1. All piping must follow standard refrigerant piping techniques.
Refer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for, or to include all details for,
a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
51
LEGEND
TXV Thermostatic Expansion Valve
Piping
*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
52
LEGEND
LLSV Liquid Line Solenoid Valve
TXV Thermostatic Expansion Valve
Piping
Double Riser Piping (If Required)
*Field supplied.
If double suction riser is required for piping system, size pipe
diameter of 3 ft (.9144 m) (maximum) riser according to application data on page 68.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer
to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a specific
installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
53
LEGEND
TXV Thermostatic Expansion Valve
Piping
*Field supplied.
54
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer
to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a specific
installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.
Electrical data
38AKS028-044
UNIT
38AKS
028
034
044
NOMINAL VOLTAGE
(V-Ph-Hz)
346-3-50
230-3-50
400-3-50
346-3-50
230-3-50
400-3-50
346-3-50
230-3-50
400-3-50
VOLTAGE RANGE*
Min
Max
311
380
198
254
342
440
311
380
198
254
342
440
311
380
198
254
342
440
LEGEND
Full Load Amps
Heating, Air Conditioning, Refrigeration
Locked Rotor Amps
Minimum Circuit Amps per
NEC Section 430-24
MOCP Maximum Overcurrent Protection
NEC National Electrical Code (U.S.A. Standard)
RLA Rated Load Amps (Compressor)
FLA
HACR
LRA
MCA
COMPRESSOR
RLA
LRA
44.9
155
76.9
205
43.6
223
53.9
176
85.9
220
50.0
253
79.5
240
105.1
327
65.4
345
FAN MOTOR
Qty
FLA (ea)
2
4.4
2
6.4
2
3.0
2
4.4
2
6.4
2
3.0
3
4.4
3
6.4
3
3.0
POWER SUPPLY
MCA
MOCP
64.9
100
109.0
175
60.5
100
76.1
125
120.2
200
68.5
110
112.6
175
150.6
250
90.8
150
NOTES:
1. MCA and MOCP values are calculated in accordance with NEC
(National Electric Code) (U.S.A. Standard), Article 440.
2. Motor FLA and RLA values are established in accordance with UL
(Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. 230-v and 346-v units are part-wind-start units; the value under
compressor LRA is for the first winding energized. The 400-v units
are across-the-line-start units; value shown is for all windings
energized.
*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum
limits.
Fuse or HACR circuit breaker.
VOLTAGE
(3 Ph, 50 Hz)
346
230
400
346
230
400
346
230
400
LEGEND
AWG American Wire Gage
kcmil Thousand circular mils (formerly MCM)
TB
Terminal Block
55
024
028
034
VOLTAGE
RANGE*
COMPRESSOR
NOMINAL
VOLTAGE
(V-Ph-Hz)
Min
Max
230-3-50
346-3-50
400-3-50
230-3-50
346-3-50
400-3-50
230-3-50
346-3-50
400-3-50
198
311
342
198
311
342
198
311
342
254
380
440
254
380
440
254
380
440
RLA
Ckt 1
Ckt 2
39.3
39.3
24.0
24.0
18.0
18.0
43.6
43.6
26.4
26.4
22.1
22.1
43.6
63.6
26.4
34.3
22.1
30.0
LRA
Ckt 1
Ckt 2
128
128
93
93
99
99
143
143
104
104
114
114
143
200
104
145
114
120
LEGEND
Full Load Amps
Maximum Instantaneous Current Flow During Starting.
(The point in the starting sequence where the sum of
the LRA for the starting compressor, plus the total RLA
for all running compressors, plus the total FLA for all
running fan motors is maximum.)
LRA Locked Rotor Amps
MCA Minimum Circuit Amps (complies with National Electrical Code [NEC] Section 430-24) (U.S.A. Standard)
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
FLA
(ea)
Nominal
Hp
Nominal
kW
0.75
0.75
0.75
6.3
4.4
3.0
6.3
4.4
3.0
6.3
4.4
3.0
POWER SUPPLY
MCA
MOCP
ICF
101.0
62.8
46.5
110.7
68.2
55.7
135.7
78.1
65.6
125
80
60
150
90
70
175
110
90
268.8
194.8
204.0
298.8
216.8
234.0
355.8
257.8
240.0
*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum.
All fans are protected by a single circuit breaker.
NOTES:
1. MCA and MOCP values are calculated in accordance with NEC
(National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Laboratories) Standard 1995 (U.S.A. standard).
FLA
ICF
VOLTAGE RANGE
NOMINAL
VOLTAGE
(V*-Ph-Hz)
Min
Max
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
207
360
207
360
207
360
207
360
253
440
253
440
253
440
253
440
Nominal
kW
2.16
2.16
3.73
3.73
5.59
5.59
7.46
7.46
LEGEND
Full Load Amps
Minimum Circuit Amps (complies with National Electrical
Code [NEC] Section 430-24) (U.S.A. Standard)
MOCP Maximum Overcurrent Protection
FLA
MCA
56
FAN MOTOR
Nominal
Hp
2.9
2.9
5.0
5.0
7.5
7.5
10.0
10.0
POWER SUPPLY
FLA
MCA
MOCP
7.5
3.4
13.2
7.6
19.8
11.4
28.0
16.1
9.4
4.3
16.5
9.5
24.8
14.3
35.0
20.1
15
15
25
15
40
25
60
30
VOLTAGE RANGE
V*-PH-Hz
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
Min
Max
207
360
207
360
207
360
253
440
253
440
253
440
LEGEND
FLA
Full Load Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Range column.
NOTES:
1. Minimum circuit amp and MOCP values are calculated in accordance with NEC (National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the percent voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
Average Voltage =
Nominal
kW
3.73
3.73
5.59
5.59
7.46
7.46
FAN MOTOR
Nominal
Hp
5.0
5.0
7.5
7.5
10.0
10.0
POWER SUPPLY
FLA
MCA
MOCP
13.2
7.6
19.8
11.4
28.0
16.1
16.5
9.5
24.8
14.3
35.0
20.1
25
15
40
25
60
30
= 397
VOLTAGE
(vac)
016-034
24
MAXIMUM
HOLDING
VA
10
57
FAN MOTOR
HEATER
PART NO.
V-PH-Hz
CAELHEAT016A00
240-3-50
CAELHEAT017A00
400-3-50
CAELHEAT019A00
240-3-50
CAELHEAT020A00
400-3-50
CAELHEAT022A00
240-3-50
CAELHEAT023A00
400-3-50
CAELHEAT025A00
240-3-50
CAELHEAT026A00
400-3-50
CAELHEAT028A00
240-3-50
CAELHEAT029A00
400-3-50
CAELHEAT031A00
240-3-50
CAELHEAT032A00
400-3-50
CAELHEAT034A00
240-3-50
CAELHEAT035A00
400-3-50
CAELHEAT037A00
240-3-50
CAELHEAT038A00
400-3-50
016,024
028,034
FLA
Hp
MCA
MOCP
Hp
kW
FLA
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
7.5
13.2
19.8
3.4
7.6
11.4
7.5
13.2
19.8
3.4
7.6
11.4
7.5
13.2
19.8
3.4
7.6
11.4
7.5
13.2
19.8
3.4
7.6
11.4
19.8
28.0
11.4
16.1
19.8
28.0
11.4
16.1
19.8
28.0
11.4
16.1
19.8
28.0
11.4
16.1
Nominal
Capacity
(kW)
10
10
10
10
10
10
20
20
20
20
20
20
30
30
30
30
30
30
50
50
50
50
50
50
20
20
20
20
40
40
40
40
50
50
50
50
70
70
70
70
LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection
240
480
58
200
0.694
208
0.751
0.694
0.84
Stage 1
Stage 2
Total
10.0
10.0
10.0
6.9
6.9
6.9
19.9
19.9
19.9
13.9
13.9
13.9
20.0
20.0
20.0
13.9
13.9
13.9
30.0
30.0
30.0
20.8
20.8
20.8
20.0
20.0
13.9
13.9
20.0
20.0
13.9
13.9
30.0
30.0
20.8
20.8
40.0
40.0
27.8
27.8
10.0
10.0
10.0
6.9
6.9
6.9
20.0
20.0
20.0
13.9
13.9
13.9
20.0
20.0
13.9
13.9
20.0
20.0
13.9
13.9
30.0
30.0
20.8
20.8
10.0
10.0
10.0
6.9
6.9
6.9
19.9
19.9
19.9
13.9
13.9
13.9
30.0
30.0
30.0
20.8
20.8
20.8
50.0
50.0
50.0
34.7
34.7
34.7
19.9
19.9
13.9
13.9
40.0
40.0
27.8
27.8
50.0
50.0
34.7
34.7
70.0
70.0
48.6
48.6
FLA
24.1
24.1
24.1
10.0
10.0
10.0
47.9
47.9
47.9
20.0
20.0
20.0
72.2
72.2
72.2
30.1
30.1
30.1
120.3
120.3
120.3
50.1
50.1
50.1
47.9
47.9
20.0
20.0
96.2
96.2
39.9
39.9
120.3
120.3
50.1
50.1
168.4
168.4
70.2
70.2
MCA*
MOCP*
39.4
46.6
54.8
16.8
22.0
26.8
69.2
76.3
84.6
29.3
45.1
49.2
99.6
106.7
115.0
41.8
47.1
51.8
159.7
166.9
175.1
66.9
72.1
76.9
84.6
94.8
39.3
45.2
145.9
153.3
64.1
70.0
175.1
185.4
76.9
82.8
193.1
203.4
84.4
90.3
40
50
60
20
25
35
70
80
90
30
50
50
100
110
125
50
50
60
175
175
200
70
80
80
90
110
40
50
150
175
70
80
200
200
80
90
200
225
90
100
NOTES:
1. Electric resistance heaters are rated at 240 v and 480 v. To determine heater capacity (kW) at unit nameplate voltage multiply the
capacity (kW) by the factor shown in the table below.
2. The following equation converts kW of heat energy to Btuh: kW x
3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 480 Pa (1.9 in. wg).
5. MCA and MOCP values apply to both standard and alternate
factory-supplied motors.
6. Approximate shipping weight for CAELHEAT016A00-026A00 is
27 kg (60 lb) each. Approximate shipping weight for
CAELHEAT028A00-038A00 is 34 kg (75 lb) each.
*Values shown are for single-point connection of electric heat accessory and air handler.
HEATER RATING
VOLTAGE
ELECTRIC HEATER(S)
Actual Capacity (kW)
460
0.918
480
Controls
Operating sequence 38AKS028-044
When space thermostat calls for cooling, the no. 1 condenser fan and compressor starts after control module
(CM) initial time delay of 7 seconds. If an optional airflow
switch is used, compressor and no. 1 condensing fan will
not start until sufficient indoor airflow has closed the
switch. After 7 seconds the compressor starts and the liquid line solenoid valve (for solenoid drop control) opens.
The crankcase heater is deenergized. If the head pressure
reaches 1793 kPag (260 psig), the second condenser fan
starts.
If cooling demand is low, suction pressure at the compressor drops. As the pressure drops, the compressor
unloads 1 or 2 banks of cylinders, as required. If cooling
demand is high and 2-stage operation is used, the second
step of the thermostat activates the capacity control liquid
line solenoid which activates the second stage evaporator
coil. The compressor cylinders load or unload in response
to compressor suction pressure to meet evaporator load.
For two and a half minutes after the compressor starts,
the low-pressure switch (LPS) ignored. If the LPS trips during the first 2 minutes of operation, the compressor
remains operational. If a high-pressure switch (HPS) trips
at any time, or the LPS trips after 21/2 minutes, the compressor cannot restart until the 3-minute CM anti-short
cycle timer expires.
As the space cooling load is satisfied, the second stage of
the thermostat opens, and closes the field-supplied capacity control liquid line solenoid valve to deactivate the second stage coil. The compressor adjusts the number of
active cylinders to meet the new load. When the space
temperature is satisfied, the first stage of the thermostat
opens and the control relay and opens. This closes the
solenoid drop control valve. The compressor stops and the
crankcase heater is energized, preventing refrigerant from
migrating to the compressor during the off cycle (solenoid
drop refrigerant control). The CM anti-short-cycling timer
is energized and runs for approximately 3 minutes. During
this time, the compressor is not able to restart.
38AH024-034 standard constant volume unit with
2-stage cooling thermostat Seven seconds after a
thermostat call for the first stage of cooling, compressor
no. 1 and the outdoor fans start. The no. 2 fan only starts
if the outdoor ambient temperature is above (21.1 C) 70 F.
The oil-pressure switch and the low-pressure switch are bypassed for the 1 and 21/2 minutes, respectively. If either
the low-pressure switch or oil pressure switch remain open
after the delay, the unit shuts down and goes into alarm
mode. The indoor-fan motor starts immediately whenever there is a call for cooling. If a liquid line solenoid valve
has been installed (for refrigerant control during the off cycle), then the solenoid valve for compressor no. 1 opens
immediately upon a call for cooling.
On standard units, compressor no. 1 operates either fully loaded or at one step of unloading, depending on the
suction pressure, which is dependent on the evaporator
load conditions.
As the cooling demand increases, the thermostat calls
for the second stage of cooling. Within 7 seconds from a
call for the second stage of cooling, compressor no. 2
59
Controls (cont)
Two 38AH024-034 optional variable air volume
units with a single ModuPanel control The
ModuPanel control regulates up to 10 stages of cooling to
maintain a leaving-air temperature for variable air volume
(VAV) applications. When connected to two 38AH condensing units, all 10 stages are used. See the table below
for unit loading and compressor operating sequence.
When the timeclock connected to the panel closes, the
indoor-fan contactor is energized through a field-supplied
relay. (The relay must be a pilot-duty SPST relay with
115-v coil and 30 va maximum coil draw.) After the time
delays programmed into the ModuPanel control have
elapsed, and with the leaving air above the set point, the
stages of mechanical cooling are sequenced as follows:
1. Stage 1 starts unit no. 1 compressor no. 1 with
2 banks of cylinders unloaded (1/3 loaded). Both
unloader solenoids are energized.
2. Stage 2 loads one bank of unit no. 1 compressor
no. 1 cylinders (2/3 loaded) by deenergizing unloader
solenoid no. 1.
3. Stage 3 turns off unit no. 1 compressor no. 1 and
starts compressor no. 2 fully loaded.
4. Stage 4 starts unit no. 1 compressor no. 1 with 2
banks of cylinders unloaded (1/3 loaded). Both
unloader solenoids are energized.
5. Stage 5 loads one bank of unit no. 1 compressor
no. 1 cylinders (2/3 loaded) by deenergizing unloader
solenoid no. 1.
6. Stage 6 loads one bank of unit no. 1 compressor
no. 1 cylinders (fully loaded) by deenergizing unloader
solenoid no. 2.
NO. CYLINDERS
1
2
3
4
5
6
2
4
6
8
10
12
LOADED CYLINDERS
Compressor No. 1
Compressor No. 2
2
2
6
4
6
6
6
60
STAGE
NO. CYLINDERS
1
2
3
4
5
6
7
8
9
10
2
4
6
8
10
12
14
18
20
24
6
2
6
4
6
6
6
6
6
6
6
6
6
6
6
6
2
6
6
6
CARRIER CONTROLS
Carrier
Pm
COOL
AUTO
HEAT
61
62
38AKS028-044 (cont)
AFS
ATS
C
CB
CH
CM
COMP
CR
EQUIP
FC
FCPS
FM
FR
FU
GND
HPS
LLSV
LPS
MM
MMF
MMPT
LEGEND
Airflow Switch
Air Temperature Switch
Contactor, Compressor
Circuit Breaker
Crankcase Heater
Control Module
Compressor
Control Relay
Equipment
Fan Contactor
Fan Cycling Pressure Switch
Fan Motor
Fan Relay
Fuse
Ground
High-Pressure Switch
Liquid Line Solenoid Valve
Low-Pressure Switch
Motormaster
Motormaster Fuse
Motormaster Pressure Transducer
NEC
OPS
TB
TC
TDR
TRAN
63
64
38AH024-034 (cont)
ATS
C
CB
CH
CM
COMP
COTP
CR
EQUIP
FC
FIOP
FM
FR
FU
GND
HPS
IFC
LLSV
LPS
MM
MMF
MMPT
MPR
NEC
OPS
LEGEND
Air Temperature Switch
Contactor, Compressor
Circuit Breaker
Crankcase Heater
Control Module
Compressor
Compressor Overtemperature
Protection
Control Relay
Equipment
Fan Contactor
Factory-Installed Option
Fan Motor
Fan Relay
Fuseblock
Ground
High-Pressure Switch
Indoor-Fan Contactor
Liquid Line SolenoidValve
Low-Pressure Switch
Motormaster
Fuse
Pressure Transducer
ModuPanel Relay
National Electrical Code (U.S.A. Standard)
Oil Pressure Switch
PL
TB
TRAN
U
VAV
Plug Assembly
Terminal Block
Transformer
Unloader
Variable Air Volume
Plug
Receptacle
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Marked Splice
Unmarked Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Indicates Common Potential,
Does Not Represent Wiring
65
028
034
044
SATURATED
CONDENSING
TEMPERATURE
C
32
27
21
32
27
21
32
27
21
100
67
33
100
67
33
100
67
33
F
90
80
70
90
80
70
90
80
70
UNIT 38AKS
MIN OUTDOOR
TEMPERATURE
With
Base
Low Ambient
Unit
Control
C
F
C
F
6
31
1.7
35
1
34
1
30
1
34 29
20
5.5
42
3.9 25
1
30
1.7
35
028
034
044
66
46 C (115 F)
Additional head pressure control may be required below
1.7 C (35 F) outdoor ambient.
12.8 C (55 F)
35 C (95 F)
1.1 to 12.8 C (30 to 55 F)
146 C (295 F)
15.6 C (60 F)
LEGEND
A
B
C
D
4.9-7.6 (16-25)
L
S
7/
15 / 8
8
7/
21 / 8
8
7/8
21 / 8
LEGEND
L Liquid Line
S Suction Line
30.8-60.9 (101-200)
L
S
7/
21 / 8 *
8
11 / 8
25 / 8 *
11 / 8
25 / 8 *
7.9-15.2 (26-50)
A
B
C
15 / 8
15 / 8
21 / 8
15 / 8
21 / 8
25 / 8
15 / 8
21 / 8
25 / 8
30.8-60.9 (101-200)
A
B
C
15 / 8
15 / 8
21 / 8
15 / 8
21 / 8
25 / 8
15 / 8
21 / 8
25 / 8
38AKS028-044
38AKS028-044
38AKS028-044 ONLY
Space for Service and Airflow
*For clearances between controls and grounded surfaces,
check local codes.
Observe minimum recommended space requirements.
38AKS
028-044
DIMENSIONS m (ft)
A
B
1.2 (4)
1.2 (4)
67
UNLOADING SEQUENCES
UNIT
38AH
024
028
034
CAPACITY/STAGE (%)
CV Units (Standard)*
VAV Units (Optional)
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 85, 43, 28
100, 85, 71, 43, 28, 14
LEGEND
CV Constant Volume
VAV Variable Air Volume
*Additional unloading available with field-installed accessory unloader.
NOTE: Capacities are based on 7.2 C (45 F) saturated suction temperature and 35 C
(95 F) outdoor air temperature.
024
028
034
SYSTEM
CAPACITY (%)
100
83
67
50
33
17
100
83
67
50
33
17
100
85
71
43
28
14
68
52 C (125 F)
See Minimum Outdoor-Air
Operating Temperature
table below.
12.8 C (55 F)
35 C (95 F)
6.6 to 10.0 C (20 to 50 F)
135 C (275 F)
15.6 C (60 F)
0-25 (0-7.6)
100-200 (30.5-61.0)
L
S
7/8
15/8*
7/
15/8*
8
024 Ckt 1
Ckt 2
L
1/
2
1/
2
S
11 / 8
11 / 8
028 Ckt 1
Ckt 2
1/2
1/
2
11 / 8
11 / 8
5/8
5/
8
13 / 8
13 / 8
5/8
5/
8
13 / 8
13 / 8
5/8
5/
8
13 / 8
13 / 8
7/8
7/
8
15/8*
15/8*
034 Ckt 1
Ckt 2
1/
2
5/8
11 / 8
13 / 8
5/
8
5/8
13 / 8
15 / 8
5/
8
5/8
13 / 8
15 / 8
5/
8
7/8
13 / 8
15 / 8
7/
8
7/8
15/8*
21/8*
LEGEND
L Liquid Line
S Suction Line
*Double suction riser required if evaporator is below condensing unit
and 2 unloaders are used on that circuit.
Double suction riser required if evaporator is below condensing unit
and compressor is equipped with 2 unloaders. Note the only time
circuit no. 2 may be equipped with 2 unloaders is if it is serving its own
air handler and the unit does not require low ambient operation
(Motormaster control).
NOTES:
1. All line sizes are inches OD.
2. Standard unit comes with one pressure-operated unloader on circuit no. 1. If unit serves one air handler, an additional unloader
may be field installed on circuit no. 1 compressor only. If the unit
serves 2 separate air handlers and low ambient operation is
required (Motormaster V control), each circuits compressor may
only be equipped with one unloader.
3. Equivalent line sizes in mm follow:
in.
1/2
5/8
7/
8
11/8
mm
12.7
15.9
22.2
28.6
in.
13/8
15/8
21/8
mm
34.9
41.3
54.0
028 Ckt 1
Ckt 2
11/8
11/8
13/8
13/8
15/8
15/8
034 Ckt 1
Ckt 2
11/8
13/8
13/8
15/8
15/8
21/8
LEGEND
Suction Riser without Trap
Suction Riser with Trap
Suction Line to Condensing Unit
Pipe Diameter to be Same Size as Riser A
69
70
DIMENSIONS m (ft)
A
B
1.2 (4)
1.2 (4)
General
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling,
and less part-load operation. Equipment should be selected
to perform at no less than 40 L/s per kW (300 cfm/ton).
COIL
TYPE
TXV
Qty...Part No.*
DISTRIBUTOR
Qty...Part No.
016
3 Row
4 Row
2...TDEBX8
2...TDEBX8
2...1116
2...1126
FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
12...1/4
16...1/4
024
3 Row
4 Row
2...TDEBX11
2...TDEBX11
2...1116
2...1126
13...1/4
18...3/16
2...E8
2...C8
028
3 Row
4 Row
2...TDEBX11
2...TDEBX11
2...1126
2...1126
15...1/4
20...3/16
2...C10
2...C15
034
3 Row
4 Row
2...TDEBX16
2...TDEBX16
2...1126
2...1126
18...1/4
24...3/16
2...C12
2...C17
NOZZLE
Qty...Part No.
2...E6
2...C6
016
024
028
034
23.75
2.16
56Y
22.2
23.75
3.73
184T
28.6
23.75
5.59
S213T
34.9
23.75
7.46
S215T
34.9
UNIT
40RM
230-3-50 and 400-3-50
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
016
024
028
034
1425
2.9
56Y
7/8
1425
5.0
184T
11 / 8
1425
7.5
S213T
13 / 8
1425
10.0
S215T
13/8
016
024
028
23.75
3.73
S184T
28.6
23.75
5.59
S213T
34.9
23.75
7.46
S215T
34.9
UNIT
40RM
230-3-50 and 400-3-50
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
016
024
028
1425
5.0
S184T
11/8
1425
7.5
S213T
13/8
1425
10.0
S215T
13/8
71
HIGH-STATIC DRIVE SI
016
024
028
034
86.4111.8
109.2134.6
109.2134.6
109.2134.6
2.5
3.0
3.0
3.0
229
36.5
1A
1074
218
36.5
1B
1062
279
49.2
2B
1113
279
49.2
2B
1113
10.3
9.011.6
20.0
13.3
11.914.6
20.0
10.4
9.311.5
18.3
10.4
9.311.5
18.3
0.265
0.230
0.180
0.180
265313
232279
169240
169240
MEDIUM-STATIC DRIVE SI
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(mm)
72
016
024
028
034
94.0119.4
101.6127.0
109.2134.6
109.2134.6
3.0
2.5
3.0
3.0
201
36.5
1B
1011
178
36.5
2A
922
239
49.2
2B
1011
239
49.2
2B
1011
12.6
11.114.1
20.0
15.3
13.617.0
20.0
12.1
10.913.4
18.3
12.1
10.913.4
18.3
0.252
0.340
0.210
0.210
232279
232279
169240
169240
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(mm)
016
024
028
034
101.6127.0
101.6127.0
109.2134.6
109.2134.6
3.0
3.0
3.0
3.0
178
36.5
2A
998
163
36.5
2A
871
203
49.2
2B
935
218
49.2
2B
960
15.3
13.617.0
20.0
16.7
14.918.6
20.0
14.3
12.815.7
18.3
13.3
11.914.6
18.3
0.283
0.308
0.247
0.230
207255
169240
232279
169240
016
024
028
034
3.4-4.4
4.3-5.3
4.3-5.3
4.3-5.3
2.5
3.0
3.0
3.0
9.0
17/16
1A
42.3
8.6
17/16
1B
41.8
11.0
115/16
2B
43.8
11.0
115/16
2B
43.8
618
538697
1200
795
713878
1200
622
557687
1100
622
557687
1100
15.9
13.8
10.8
10.8
10.4412.32
9.1210.99
6.679.43
6.679.43
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)
016
024
028
034
4.0-5.0
4.0-5.0
4.3-5.3
4.3-5.3
3.0
3.0
3.0
3.0
7.0
17/16
2A
39.3
6.4
17/16
2A
34.3
8.0
115/16
2B
36.8
8.6
115/16
2B
37.8
916
8141018
1200
1002
8911113
1200
855
766944
1100
795
713878
1100
17.0
18.5
14.8
13.8
9.1610.99
8.1610.02
6.679.43
6.679.43
016
024
028
034
3.7-4.7
4.0-5.0
4.3-5.3
4.3-5.3
3.0
2.5
3.0
3.0
7.9
17/16
1B
39.8
7.0
17/16
2A
36.8
9.4
115/16
2B
39.8
9.4
115/16
2B
39.8
756
667848
1200
916
8141018
1200
728
652803
1100
728
652803
1100
15.1
20.4
12.6
12.6
9.1610.99
9.1610.99
6.679.43
6.679.43
73
74
C. Fans:
1. Condenser fans shall be direct-driven propeller
type, discharging air vertically upward.
2. Condenser fan motors shall be totally enclosed,
3-phase type with class B insulation and with
permanently lubricated bearings.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressor:
1. Compressor shall be reciprocating, serviceable,
semi-hermetic type.
2. Compressor shall be equipped with an automatically reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an
insert-type, factory-sized crankcase heater to
control oil dilution.
3. Compressor shall be mounted on spring vibration isolators with an isolation efficiency of no
less than 95%.
4. Compressor speed shall not exceed 24.2 r/s
(1450 rpm).
5. Compressor shall unload using suction cutoff
unloading (electrical solenoid unloading shall be
available as an accessory).
E. Condenser Coil:
1. Condenser coil shall be air cooled, circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins
mechanically bonded to internally grooved,
seamless copper tubes which are then cleaned,
dehydrated, and sealed. Epoxy phenolic fin coating shall be available as an option.
3. Coil shall be protected by a sheet metal casing to
eliminate the need for wind baffles for low ambient temperature operation.
4. Coil shall be protected to avoid damage due to
the elements and vandalism.
F. Refrigeration Components:
Refrigeration circuit components shall include hot gas
muffler, high-side pressure relief device, liquid line shutoff valve, suction and discharge shutoff valves, holding
charge of refrigerant R-22, and compressor oil.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Three-minute recycle protection to prevent
compressor short-cycling.
c. Lockout on auto-reset safety until reset from
thermostat.
2.
3.
4.
5.
6.
7.
of the unit. The control shall be capable of maintaining a condensing temperature of 37.8 C
(100 F) 5.6 C (10 F) with outdoor temperatures at 28 C (20 F). (Motor change required.)
Electric Solenoid Unloader:
Unloader valve piston, coil, and hardware shall
be supplied to convert any pressure-operated
compressor unloader to 220-v electric unloading. Accessory ModuPanel control box or fieldsupplied step controller shall be provided for
electrical unloading.
Hot-Gas Bypass:
A hot-gas bypass valve and a pilot line solenoid
valve shall be provided for low-load operation of
the refrigeration system.
Part-Winding Start:
Part-winding start shall be provided to reduce
inrush current and locked rotor amps on
start-up.
Gage Panel:
A gage panel package shall be provided which
includes a suction and discharge pressure gage
for the refrigerant circuit.
ModuPanel Control Box:
Control box shall be provided to allow system to
operate as a VAV (variable air volume) system.
Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive
coastal environments. Coating shall be
applied to the aluminum fin stock prior to the
fin stamping process to create an inert barrier
between the aluminum fin and copper tube.
Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.
b. Copper-Fin Coils:
Shall be constructed of copper-fins mechanically bonded to copper-tubes All copper construction shall provide protection in moderate
coastal environments.
c. E-Coated Aluminum-Fin Coils:
Shall have a flexible epoxy polymer coating
uniformly applied to all coil surface areas
without material bridging between fins.
Coating process shall ensure complete coil
encapsulation. Color shall be high gloss
black with gloss requirements of 60 of 65
to 90% per ASTM D523-89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior
hardness characteristics of 2H per ASTM
D3363-92A and cross hatch adhesion of
4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in./lb (ASTM
D2794-93). Humidity and water immersion
resistance shall be up to a minimum of 1000
75
76
tube sheets shall not be acceptable. A polymer strip shall prevent coil assembly from
contacting sheet metal coil pan to maintain
coating integrity and minimize corrosion
potential between the coil and pan. (U.S.A.
standards.)
8. Thermostat Controls:
a. Debonair programmable multi-stage thermostat with 7-day clock, holiday scheduling,
large Thermoglow display, remote sensor
capability, and Title 24 compliance.
b. Commercial Electronic Thermostat with
7-day timeclock, auto-changeover, multistage capability, and large LCD temperature
display.
c. Non-programmable thermostat with fan
switch subbase.
d. Carrier PremierLink Controls:
This control will function with CCN and
ComfortVIEW software. It shall also be
compatible with ComfortLink controllers.
It shall be ASHRAE 62-99 (U.S.A.) compliant and Internet ready. It shall accept a CO2
sensor in the conditioned space and be
Demand Control Ventilation (DCV) ready.
The communication rate must be 38.4K or
faster. It shall include an integrated economizer controller.
C. Fans:
1. Condenser fans shall be direct-drive propeller
type, discharging air vertically upward.
2. Condenser fan motors shall be 3-phase type
with class B insulation and permanently lubricated bearings.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. Compressors shall be manufactured by the condensing unit manufacturer, and shall be serviceable, reciprocating, semi-hermetic type.
2. Compressors shall be equipped with an automatically reversible oil pump, operating oil
charge, suction and discharge shutoff valves,
and an insert-type factory-sized crankcase
heater to control oil dilution.
3. Compressors shall be mounted on spring vibration isolators with an isolation efficiency of no
less than 95%.
4. Compressor speed shall not exceed 24.3 r/s
(1460 rpm).
5. Lead compressor shall unload using suction cutoff unloading (electrical solenoid unloading shall
be available as an accessory).
E. Condenser Coils:
1. Condenser coils shall be air cooled, circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins
mechanically bonded to internally grooved,
seamless copper tubes which are then cleaned,
dehydrated, and sealed. Copper fins, E-Coated
or pre-coated aluminum fins shall be available
as options.
F. Refrigeration Components:
Refrigeration circuit components shall include hot
gas muffler, high-side pressure relief device, liquid
line shutoff valve, suction and discharge shutoff
valves, holding charge, and compressor oil.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Three-minute recycle protection to prevent
compressor short-cycling.
c. Lockout on auto-reset safety until reset from
thermostat.
d. Capacity control on the lead compressor
shall be by suction cutoff unloaders in
response to compressor suction pressure.
Electric solenoid unloading shall be available
as an accessory.
77
78
6.
7.
* 8.
* 9.
79
80
C.
D.
E.
F.
81
7-04
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 2
Pg 82
Catalog No. 003-80020
Printed in U.S.A.
Form 38A-C11PD
Replaces: 38A-C9PD
Tab 3a 1a