PERFORMANCE STANDARD
AG-SCEq-13
Fire Water Pumps
A
Rev
October 2004
Yudi PP
Date
REMARKS
Prepared
Checked
Approved
1. SCE DECSRIPTION
Installation
SCE ID
SCE Category
SCE Name
Main Function
Boundary
XXX
XXSCEq-13
Safety Critical Equipment
Firewater Pumps
To ensure timely delivery of sufficient fire water to specified end user points
Firewater Pump (with Driver and power supply, P-8402 A/B), Jok and Fire Water Ring main
List of Equipment Tags is available at Separate documents
Page 2 of 10
2. FUNCTIONALITY
PS ID
AG-SCEq-13-01
Function
To
ensure
timely
delivery of sufficient
fire water to specified
end user points
Performance Requirements
Firewater pump will Auto start at the following conditions :
a)
b)
Assurance Strategy
Perform
Preventive
Maintenance
to
all
components of the pump assembly in accordance with the
manufacturers recommendations or at least as stated at
Table 5-5.1. of NFPA 25.
AG-SCEq-13-02
AG-SCEq-13-03
Page 3 of 10
Function
Performance Requirements
control room
Record all the conformance and conformance
status using checklist, perform corrective action as
required.
AG-SCEq-13-04
Assurance Strategy
Confirm
performance
standard
by
Periodic
testing
Page 4 of 10
Function
Performance Requirements
Assurance Strategy
status using
required
checklist,
perform
corrective
action
as
During Periodic
of over speed trip against
Page 5 of 10
Function
Performance Requirements
-
AG-SCEq-13-08
Fire
ring
main
To
distribute firewater at
pressures and flows
sufficient for all end
users under normal and
impaired
ring
main
conditions.
Assurance Strategy
Page 6 of 10
3. RELIABILITY/AVAILABILITY
PS ID
XXX-SCEq-1309
Performance Requirements
Fire water pump must be available at all times to deliver 100% demand.
Assurance Strategy
Operation and Maintenance :
Periodic
functional
testing
for
fire
water
pumps
Page 7 of 10
4. SURVIVABILITY
PS ID
XXX-SCEq13-10
Event
Fire, explosion
and
others
major accident
events
Component
All
Performance Requirements
System to survive all major accidental events and remain
functioning until installation evacuated for Evacuation
duration 30 mins
Assurance Strategy
Operation and Maintenance:
Confirm by inspection that measures/enclosures
provided to protect the Fire water pumps and Fire Ring
main remain in good condition
Page 8 of 10
5. DEPEDENCY
Related SCE
Performance Requirements
Assurance Tasks
Page 9 of 10
Page 10 of 10