Академический Документы
Профессиональный Документы
Культура Документы
Project: Taikisha
Prepared By: PT Berca Carrier Indonesia
06-04-2015
08:36AM
PackagedChillerReport:DoNotEdit
AquaForce
TM
Unit Information
Tag Name:
Model Number:
Quantity:
Manufacturing Source:
Shipping Weight:
Operating Weight:
Unit Length:
Unit Width:
Unit Height:
Merck
30XW0902P
1
Shanghai, China
6190
6003
4695
1070
1947
Evaporator Information
Fluid Type:
Fouling Factor:
Leaving Temperature:
Entering Temperature:
Fluid Flow:
Pressure Drop:
Fresh Water
0.0180
7.0
12.0
46.36
68.9
(sqm-K)/kW
C
C
L/s
kPa
Electrical Information
Unit Voltage:
Standby Power:
Minimum Voltage:
Maximum Voltage:
Power Factor:
Condenser Information
Fluid Type:
Fouling Factor:
Leaving Temperature:
Entering Temperature:
Fluid Flow:
Pressure Drop:
Fresh Water
0.0440
35.0
30.0
54.51
28.1
(sqm-K)/kW
C
C
L/s
kPa
Amps (Un)
Max Unit Current
Draw (RLA)
Max Start Up
Current (ICF)
Nominal Unit
Current Draw (A)
kg
kg
mm
mm
mm
Performance Information
Cooling Capacity:
Heating Capacity:
Total Unit Power:
Cooling Efficiency (E.E.R.):
Heating Efficiency (C.O.P.):
A-Weighted Sound Pressure Level:
972.4
1132.9
164.0
5.93
6.91
81
kW
kW
kW
kW/kW
kW/kW
dbA
V-Ph-Hz
kW
Volts
Volts
Electrical
Circuit 1
434.0
Electrical
Circuit 2
---
984.0
---
288.0
---
Sound pressure level measured in accordance with AHRIStandard 575. Sound pressure level is the free field sound data (the
unit isplaced in free field over a reflecting plane).
Certified in accordance with the AHRI Water-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be
found in the AHRI Directory at www.ahridirectory.org
Page 1 of 1