PurposeofPDATest(seeAttachment#3forreference):
ObtainPileCapacity
RMX(max.resistanceofpilecapacity)
ObtainDataofPileIntegrity
BTA(piledamagedintegrity)
EquipmentEfficiency
EMX(energytransferfromequipmenthammer)
CompletereportofPDATestresultwillbesubmittedbyContractor
ConclusionfromPDATest(seeTable.1forreference):
Allthetestpilesratioishigherthanone(1)exceptTPL02whichhaveSF=2.5
Thereforetoobtainallpilesratiohigherthanone(1),duringpiledrivingContractorwilluseSF> 3,
whichmeansthatforDynamicFormula(ENR)theminimumrequirementforPuis:
Pu=3x750kN =2250kN (forpileDiameter=400mm)
Pu=3x1550kN =4650kN (forpileDiameter=600mm)
ContractorwillconductPDATestforpileswithSF< 2.5
Table1:ComparisonofPileCapacityforStaticFormula,DynamicFormulaandDynamicTest(PDA)Result
STATICFORMULA
Pallowable(kN)*
PileNo
1
TPL01
TPL02
TPL03
TPL04
TPL05
TPL06
#19E100002
#42E100003
DESIGNCAPACITY(kN)
DYNAMICFORMULA
Pultimate(kN)** s(mm/blow)
h(cm)
1550
1550
750
1550
750
750
1550
1550
9304
3857
2254
8010
3598
2725
7850
3662
Notes:
*)
**)
***)
RefertoS0001311101N,Table4.5
RefertoS0003114002N,Sheet5of10
Seeattachment#3
1.1
6
11.2
2.6
1.2
16.4
2.7
8.6
200
200
150
250
250
250
250
250
DynamicTest(PDA)Result
Remark
SF
Pu(kN)***
Ratio(>1)
6(=3/2)
8(=7/2)
6.00
2.49
3.01
5.17
4.80
3.63
5.06
2.36
2648
1520
1697
2844
1697
1934
3330
3010
1.71
0.98
2.26
1.83
2.26
2.58
2.15
1.94
pass
failed
pass
pass
pass
pass
pass
pass
S-000-1311-101-N R. A
SHEET 90 / 498
ATTACHMENT #1
Table 4.5 Recommended Design Loads of Driven and Jacked Pile Foundations
No.
Area
Pile Type
Axens
Driven
Area-04
Jacked
Utility500
and
UtilityOM
4
Notes: *
**
FOG-01
Pile
Diameter
(mm)
400
600
400
400
Jacked
600
Jacked
400
600
Borehole
BH-05
BH-08
BH-12
BH-03
BH-10
BH-14
BH-04
BH-03
BH-10
BH-14
BH-04
BH-01,
02, 13, 15
Pile Tip
Level
(EL-m)
*Permissible
Structural
Load (kN)
-12.0 to 17.0
-16
15.5 to -20.0
Geotechnical Capacity
(kN)
**Liquefied
Condition
(Adopting SF
= 2.0)
**Static
Condition
(Adopting SF
= 2.5)
Liquefied
Condition
Static
Condition
750
1,550
750
900
1,720
975
900
1,680
900
750
1,550
750
750
1,550
750
750
900
900
750
750
1,550
1,550
1,550
1,550
1,550
750
1,550
750
1,550
900
1,550
750
1,550
750
1,550
-26
15.5 to -20.0
-26
19.0 to -25.0
4.10
ATTACHMENT #2
2.
Pile termination criteria shall be determined using modified Engineering News Record (ENR)
formula (as shown below).
Where:
Ru
ef
Wh
Wp
The criterion shown here is tentatively applied to test piles. Based on the pile load test results,
criterion will be reviewed and finalized.
Other methods such as Wave Equation Analysis can also be applicable for the determination
of pile termination criteria with acceptance of CONTRACTOR.