Building A5

Lift-B6-2

1) Instruction manual & maintenance record not provide in machine room.


2) Due to distant location of main switch, a emergency stopping device near to
machine
unit is not installed.
3) Electric motor & control arrangements are congested in machine room.
4) Warning notice Danger-Access forbidden to unauthorized persons is to be
posted
outside the machine room door.
5) Machine room platform balustrade in machine room in not completed (No
mid rail).
6) Access ladder going to machine platform is not completed (No proper
handrail).
7) Provide safety sign/soft material for the over head hazard in machine room.
8) The main suspension ropes lacks lubrication.
9) Ferrules shall be installed on rope holes.
10)
The permissible safe working load for the lifting hooks in machine room
to be marked.
11)
Lifting hooks bent and damaged.
12)
Spare battery need to be secure with proper cover.
13)
Rotating parts (main sheave and deflector sheave) should be provided
with
protection guards at all times.
14)
The safety gear that is located under the car is not provided with
electric safety device.
15)
ERD system not working properly.
16)
Sheave slippage need to be check regularly.
17)
Door is not opening properly.
18)
Emergency switch inside the car is damaged.
19)
Landing door on 5th floor is damaged.
20)
Car floor tiles damaged.
21)
Toe guard not provided on 12th floor landing door.
22)
Permanent access ladder in pit to be provided.
23)
Car and counterweight hydraulic buffer is not fitted with electric safety
device.
24)
The horizontal gap between the landing door header and the landing
door jamb shall be
reduced below 6 mm on several floors.
25)
Permanent light and socket outlet is to be provided in pit.
26)
Partition between lifts in pit is not installed (It shall extend at least from
the lowest

point of travel of the car to a height of 2.5 m above the floor of the
lowest landing).
27)
In a pit, the travelling area of the counterweight is not guarded with
rigid screen.
28)
A sign of worn out from the traction sheave grooves, should be
monitored regularly by
the lift maintenance.
29)
Provide additional stop switch in pit that is easily accessible from the
entry point.
30)
Warning notice Dont lean over the balustrade is not displayed the
car top.
31)
Safety rope to double secure the compensation end termination is not
installed.
32)
The closed position of the other unlocked door panel is not fitted with
electric safety
device.
33)
Electric safety device to monitor the position of the hand wheel device
is not fitted.
34)
The elevator is not fitted with ascending car over speed protection
device.
35)
The electric safety device that monitors the excessive stretch or
breakage of governor
rope and tension pulley is not fitted.
36)
Protection against the introduction of objects between the governor
rope and tension
pulley is not fitted.
37)
A water based fire protection system is installed in machine room.
Electrical equipment
must be shielded from water exposure if accidentally activated.

Building A5

Lift-C1

1) Instruction manual & maintenance record not provide in machine room.


2) Due to distant location of main switch, a emergency stopping device near to
machine
unit is not installed.
3) Electric motor & control arrangements are congested in machine room.
4) Warning notice Danger-Access forbidden to unauthorized persons is to be
posted
outside the machine room door.
5) Machine room platform balustrade in machine room in not completed (No
mid rail).
6) Access ladder going to machine platform is not completed (No proper
handrail).
7) Provide safety sign/soft material for the over head hazard in machine room.
8) The main suspension ropes lacks lubrication.
9) Ferrules shall be installed on rope holes.
10)
The permissible safe working load for the lifting hooks in machine room
to be marked.
11)
Tensioner Pulley in machine room need to be corrosion protection
paints.
12)
Spare battery need to be secure with proper cover.
13)
Rotating parts (main sheave and deflector sheave) should be provided
with
protection guards at all times.

14)
The safety gear that is located under the car is not provided with
electric safety device.
15)
Toe guard not provided on 12th floor landing door.
16)
Permanent access ladder in pit to be provided.
17)
Car and counterweight hydraulic buffer is not fitted with electric safety
device.
18)
The horizontal gap between the landing door header and the landing
door jamb shall be
reduced below 6 mm on several floors.
19)
Permanent light and socket outlet is to be provided in pit.
20)
Partition between lifts in pit is not installed (It shall extend at least from
the lowest
point of travel of the car to a height of 2.5 m above the floor of the
lowest landing).
21)
In a pit, the travelling area of the counterweight is not guarded with
rigid screen.
22)
A sign of worn out from the traction sheave grooves, should be
monitored regularly by
the lift maintenance.
23)
Provide additional stop switch in pit that is easily accessible from the
entry point.
24)
Warning notice Dont lean over the balustrade is not displayed the
car top.
25)
Safety rope to double secure the compensation end termination is not
installed.
26)
The closed position of the other unlocked door panel is not fitted with
electric safety
device.
27)
Electric safety device to monitor the position of the hand wheel device
is not fitted.
28)
The elevator is not fitted with ascending car over speed protection
device.
29)
The electric safety device that monitors the excessive stretch or
breakage of governor
rope and tension pulley is not fitted.
30)
Protection against the introduction of objects between the governor
rope and tension
pulley is not fitted.
31)
A water based fire protection system is installed in machine room.
Electrical equipment
must be shielded from water exposure if accidentally activated.

Building A5

Lift-C3

1) Instruction manual & maintenance record not provide in machine room.


2) Due to distant location of main switch, a emergency stopping device near to
machine
unit is not installed.

3) Electric motor & control arrangements are congested in machine room.


4) Warning notice Danger-Access forbidden to unauthorized persons is to be
posted
outside the machine room door.
5) Machine room platform balustrade in machine room in not completed (No
mid rail).
6) Access ladder going to machine platform is not completed (No proper
handrail).
7) Provide safety sign/soft material for the over head hazard in machine room.
8) The main suspension ropes lacks lubrication.
9) Ferrules shall be installed on rope holes.
10)
The permissible safe working load for the lifting hooks in machine room
to be marked.
11)
Tensioner Pulley in machine room need to be corrosion protection
paints.
12)
Spare battery need to be secure with proper cover.
13)
Rotating parts (main sheave and deflector sheave) should be provided
with
protection guards at all times.
14)
Flywheel key hole damaged
15)
The safety gear that is located under the car is not provided with
electric safety device.
16)
Emergency alarm switch damaged & alarm ring not working.
17)
Lift pit have water.
18)
Permanent access ladder in pit to be provided.
19)
Car and counterweight hydraulic buffer is not fitted with electric safety
device.
20)
The horizontal gap between the landing door header and the landing
door jamb shall be
reduced below 6 mm on several floors.
21)
Permanent light and socket outlet is to be provided in pit.
22)
Partition between lifts in pit is not installed (It shall extend at least from
the lowest
point of travel of the car to a height of 2.5 m above the floor of the
lowest landing).
23)
In a pit, the travelling area of the counterweight is not guarded with
rigid screen.
24)
A sign of worn out from the traction sheave grooves, should be
monitored regularly by
the lift maintenance.
25)
Provide additional stop switch in pit that is easily accessible from the
entry point.

26)
Warning notice Dont lean over the balustrade is not displayed the
car top.
27)
Safety rope to double secure the compensation end termination is not
installed.
28)
The closed position of the other unlocked door panel is not fitted with
electric safety
device.
29)
Electric safety device to monitor the position of the hand wheel device
is not fitted.
30)
The elevator is not fitted with ascending car over speed protection
device.
31)
The electric safety device that monitors the excessive stretch or
breakage of governor
rope and tension pulley is not fitted.
32)
Protection against the introduction of objects between the governor
rope and tension
pulley is not fitted.
33)
A water based fire protection system is installed in machine room.
Electrical equipment
must be shielded from water exposure if accidentally activated.

Building A6

Lift-B6-1

1) Instruction manual & maintenance record not provide in machine room.


2) Due to distant location of main switch, a emergency stopping device near to
machine
unit is not installed.
3) Electric motor & control arrangements are congested in machine room.
4) Warning notice Danger-Access forbidden to unauthorized persons is to be
posted
outside the machine room door.
5) Machine room platform balustrade in machine room in not completed (No
mid rail).
6) Access ladder going to machine platform is not completed (No proper
handrail).
7) Provide safety sign/soft material for the over head hazard in machine room.
8) The main suspension ropes lacks lubrication.
9) The permissible safe working load for the lifting hooks in machine room to be
marked.
10)
Tensioner Pulley in machine room need to be corrosion protection
paints.
11)
Spare battery need to be secure with proper cover.
12)
Rotating parts (main sheave and deflector sheave) should be provided
with
protection guards at all times.
13)
Sheave slippage need to be check regularly.
14)
Water leakage from duct pipe line, need to be rectify.
15)
The safety gear that is located under the car is not provided with
electric safety device.
16)
Lift fire man switch not working.
17)
Floor button not working on 10 th and 11 th floor.
18)
Permanent access ladder in pit to be provided.
19)
Counter weight extension plate missing.

20)
Car and counterweight hydraulic buffer is not fitted with electric safety
device.
21)
The horizontal gap between the landing door header and the landing
door jamb shall be
reduced below 6 mm on several floors.
22)
Permanent light and socket outlet is to be provided in pit.
23)
Partition between lifts in pit is not installed (It shall extend at least from
the lowest
point of travel of the car to a height of 2.5 m above the floor of the
lowest landing).
24)
In a pit, the travelling area of the counterweight is not guarded with
rigid screen.
25)
A sign of worn out from the traction sheave grooves, should be
monitored regularly by
the lift maintenance.
26)
Provide additional stop switch in pit that is easily accessible from the
entry point.
27)
Warning notice Dont lean over the balustrade is not displayed the
car top.
28)
The closed position of the other unlocked door panel is not fitted with
electric safety
device.
29)
Electric safety device to monitor the position of the hand wheel device
is not fitted.
30)
The elevator is not fitted with ascending car over speed protection
device.
31)
The electric safety device that monitors the excessive stretch or
breakage of governor
rope and tension pulley is not fitted.
32)
Protection against the introduction of objects between the governor
rope and tension
pulley is not fitted.
33)
A water based fire protection system is installed in machine room.
Electrical equipment
must be shielded from water exposure if accidentally activated.
34)
Counterweight to buffer clearance is less.
35)
Permanent light and socket outlet is to be provided in it.

Building A6

Lift-C1

1) Instruction manual & maintenance record not provide in machine room


2) Due to distant location of main switch, a emergency stopping device near to
machine
unit is not installed.
3) Electric motor & control arrangements are congested in machine room.
4) Warning notice Danger-Access forbidden to unauthorized persons is to be
posted
outside the machine room door.
5) Machine room platform balustrade in machine room in not completed (No
mid rail).
6) Access ladder going to machine platform is not completed (No proper
handrail).
7) Provide safety sign/soft material for the over head hazard in machine room.
8) The main suspension ropes lacks lubrication.
9) The permissible safe working load for the lifting hooks in machine room to be
marked.

10)
Tensioner Pulley in machine room need to be corrosion protection
paints.
11)
Spare battery need to be secure with proper cover.
12)
Rotating parts (main sheave and deflector sheave) should be provided
with
protection guards at all times.
13)
Water leakage from duct pipe line, need to be rectify.
14)
The safety gear that is located under the car is not provided with
electric safety device.
15)
ERD system battery not working properly.
16)
Lift fire man switch not working.
17)
Permanent access ladder in pit to be provided.
18)
Counterweight to buffer clearance is less.
19)
Counter weight extension plate missing.
20)
Car and counterweight hydraulic buffer is not fitted with electric safety
device.
21)
The horizontal gap between the landing door header and the landing
door jamb shall be
reduced below 6 mm on several floors.
22)
Permanent light and socket outlet is to be provided in pit.
23)
Partition between lifts in pit is not installed (It shall extend at least from
the lowest
point of travel of the car to a height of 2.5 m above the floor of the
lowest landing).
24)
In a pit, the travelling area of the counterweight is not guarded with
rigid screen.
25)
A sign of worn out from the traction sheave grooves, should be
monitored regularly by
the lift maintenance.
26)
Provide additional stop switch in pit that is easily accessible from the
entry point.
27)
Warning notice Dont lean over the balustrade is not displayed the
car top.
28)
The closed position of the other unlocked door panel is not fitted with
electric safety
device.
29)
Electric safety device to monitor the position of the hand wheel device
is not fitted.
30)
The elevator is not fitted with ascending car over speed protection
device.
31)
The electric safety device that monitors the excessive stretch or
breakage of governor
rope and tension pulley is not fitted.

32)
Protection against the introduction of objects between the governor
rope and tension
pulley is not fitted.
33)
A water based fire protection system is installed in machine room.
Electrical equipment
must be shielded from water exposure if accidentally activated.
34)
Landing hall button B2 floor is not installed.
35)
Cleaning is necessary in pit.
36)
Fire system is not working.
37)
Permanent light and socket outlet is to be provided in it.

Building A6

Lift-C3

1) Instruction manual & maintenance record not provide in machine room

2) Due to distant location of main switch, a emergency stopping device near to


machine
unit is not installed.
3) Electric motor & control arrangements are congested in machine room.
4) Warning notice Danger-Access forbidden to unauthorized persons is to be
posted
outside the machine room door.
5) Machine room platform balustrade in machine room in not completed (No
mid rail).
6) Access ladder going to machine platform is not completed (No proper
handrail).
7) Provide safety sign/soft material for the over head hazard in machine room.
8) The main suspension ropes lacks lubrication.
9) The permissible safe working load for the lifting hooks in machine room to be
marked.
10)
Tensioner Pulley in machine room need to be corrosion protection
paints.
11)
Spare battery need to be secure with proper cover.
12)
Rotating parts (main sheave and deflector sheave) should be provided
with
protection guards at all times.
13)
Water leakage from duct pipe line, need to be rectify.
14)
The safety gear that is located under the car is not provided with
electric safety device.
15)
ERD system battery not working properly.
16)
During inspection mode ERD activation light not working.
17)
Lift fire man switch not working.
18)
Permanent access ladder in pit to be provided.
19)
Counterweight to buffer clearance is less.
20)
Toe guard is missing at 10 th floor landing door.
21)
Counter weight extension plate missing.
22)
Car and counterweight hydraulic buffer is not fitted with electric safety
device.
23)
The horizontal gap between the landing door header and the landing
door jamb shall be
reduced below 6 mm on several floors.
24)
Permanent light and socket outlet is to be provided in pit.
25)
Partition between lifts in pit is not installed (It shall extend at least from
the lowest
point of travel of the car to a height of 2.5 m above the floor of the
lowest landing).
26)
In a pit, the travelling area of the counterweight is not guarded with
rigid screen.

27)
A sign of worn out from the traction sheave grooves, should be
monitored regularly by
the lift maintenance.
28)
Provide additional stop switch in pit that is easily accessible from the
entry point.
29)
Warning notice Dont lean over the balustrade is not displayed the
car top.
30)
The closed position of the other unlocked door panel is not fitted with
electric safety
device.
31)
Electric safety device to monitor the position of the hand wheel device
is not fitted.
32)
The elevator is not fitted with ascending car over speed protection
device.
33)
The electric safety device that monitors the excessive stretch or
breakage of governor
rope and tension pulley is not fitted.
34)
Protection against the introduction of objects between the governor
rope and tension
pulley is not fitted.
35)
A water based fire protection system is installed in machine room.
Electrical equipment
must be shielded from water exposure if accidentally activated.
36)
Cleaning is necessary in pit.
37)
Fire system is not working.
38)
Permanent light and socket outlet is to be provided in it.
39)
In pit area, Car & counter weight safety switches not working.
40)
In pit area, Car & counter weight buffer system not working properly.