Contactors, Relays, Starters

Starters
2. Type designation
NQ3- P

Code of structure characteristic:


P means with buttons

Code of power grade of the bracket

NQ3
DOL Electromagnetic Starter

Design code name

1. General
1.1 NQ3 series electromagnetic starter
( "starter" for short hereinafter) applies mainly to
circuit with AC current of 50Hz (or 60Hz),
rated operational voltage of 660V
and rated controlled power up to 11kW
(current up to 22A)
for using to control the direct start
and halt of the electromotor to protect the motor
from overload and phase failure.
1.2 The starter conforms to standards IEC/EN60947-4-1

Electromagnetic starter

Characteristic code of the enterprise

3. Technical data
Altitude: not exceeding 2000m;
Temperature of ambient air: -5~+40
Rated control supply voltage (AC 50Hz):
24V, 36V, 48V, 110V, 127V, 220V, 380V, 415V
Mechanical life: 1,000,000 circles;
Electric life: 500,000 circles;
IP55

F-15

> >>

Contactors, Relays, Starters

Starters
Table 1 Basic Model and main technical parameter of the starter

Rated working
current (A)

Model

Maximum rated Power (kW)


AC-3
660V

380V

220V

Model of
equipped
AC contactor

TOR matched

Range of
setting current
A

0.1~0.16
0.16~0.25
0.25~0.4
0.4~0.63
0.63~1
NQ3-5.5P

12

7.5

5.5

NC1-1810

NR2-25
1~1.6
1.25~2
1.6~2.5
2.5~4

4~6
5.5~8
7~10
9~13
NQ3-11P

22

15

11

5.5

NC1-3210

12~18
17~25

4. Overall and mounting dimension (mm)


NQ3-5.5P

NQ3-5.5P

spec sign

36
110
220
380

STOP

130

Rated Voltage V 50Hz spec sign

START

166max

Ie A

0.1
0.1 60.2
60.2 5
5 0.6
0.63 1
31
1.2 2
5
4
4 6
8
7 10
9 13
12 18
17 25

Standard EN60947-4-1
IEC60947-4-1
degree of protection IP55
ZHEJIANGCHINTELECTRICSCO.,LTD

125max

60

36

96max

> >>

F-16

Contactors, Relays, Starters

Starters
NQ3-11P

NQ3-11P

specsign

196max

Rated Voltage V 50Hz specsign

36
110
220
380

Standard

150

Ie A

0.6 1
31
1.2 2
5
4
4 6
8
7 10
9 13
12 18
17 25
23 32

EN60947-4-1
IEC60947-4-1

degree of protection

IP55

ZHE JIANG CHINT ELECTRICSCO.,LTD

60

130max

116max

36

5. Wiring Diagram
L1 L3 L5

L1 L3 L5
FU1

FU1

1 3

1 3

5
FR

KM

FR

2 4
1 3
2 4
U V

6
5
6
W

A1
KM
A2

KM

FR
2 4
1 3

6
5

2 4
U V

6
W

FR

A1
KM
A2

KM

Control supply voltage is as the same as


the main circuit voltage (three-phrase)

Control supply voltage is not as the same as


the main circuit voltage (three-phrase)

FU1

FU1

1 3

KM
2 4
1 3

6
5

2 4 6
U1 U2

A1
KM
A2

FR

KM

KM

Control supply voltage is as the same as


the main circuit voltage (single-phrase)

> >>

Connect to other supply

1 3 5

FR

F-17

KM

FR

connect to other supply

FR

2 4
1 3

6
5

2 4 6
U1 U2

A1
KM
A2

KM

Control supply voltage is not as the same as


the main circuit voltage (single-phrase)

Contactors, Relays, Starters

Starters
6. Picture
NQ3-5.5P

NQ3-11P

> >>

F-18