Добро пожаловать в Scribd!
Академический Документы
Профессиональный Документы
Культура Документы
Хобби и ремесла Документы
Личностный рост Документы
s0 | <0 | >60 fesopo~aq >an | as | >as Frame a }o )s 2 [sfefa fz fo 2 toameny | 22 | 2 | 00 casps—sd >e0| <2s | >25 coe the srvetar | Frames fr | | somin | a fo 2 [2 [am fala [Note:i.Ondinary shear walls slo include shesr walls not on the ground and the upper part of the shear walls on the flor ina stracture with frame supported stores 2. tn the intensity of We type C buildings with » hight not geeater than 12m, ordinary civil framed structures with a regular shape (except stadiums and theatres), and Similar industrial framed stcuctures can be graded a8 Grade 3, 6.1.4 Structures with a regular shape should comply with the following requirements? 1. The length of the projecting part of 2 building in plan should not be greater athan its width and also should not be greater than 30% of the total length in the dizeetion of the width. 2. For buildings with setbacks in elevation, the dimension of the setback should be not greater than 25% of the total dimension in that direction. 3. Stiffness of a storey should be not less than 70% of the stiffness of the adjacent upper story, and, also, the total stiffness of three consecutive storcies should not be reduced more than 50% 4. Mass distribution in-plane and arrangement of lateral force resisting members a building should be basically uniform and symmetric. 6.1. § Rational structural system should be selected for reinforced concrete buildings so that no seismic joints are neccessary to he installed. When it is necessary to install seismic joints, minimum clearence of the joints shall comply with the {following requirements: 1. For frame and frame-shear wall buildings, when the building height is not ‘more than 15 m, a length of 70 mm may be taken as the clearance: when the building height is more than 15 m, and in the intensity of WI, W, Ws and IK, the clearance should be increased by 20 mm for every 5, 4, 3 and 2 m increase in height respectively. 2. Seismic joint clearance in a shear wall building may be taken as 70% of the values as set forth in Clause 1 6.1.6 For buildings with superior decoration and high-rise buildings, frame-shesr vwall/shear wall structural system shall be used preferentially 6.1.7 In fame or frame-shear wall structured, frames or shear walls should be arranged in two orthogonal directions, and the center lines of beams and columns or those of the column and the shear wall should coinside with each other eccentricity between the center lines of beams and columns in & frame should not be greater than 1/4 of the column width. 6.1.8 The aspect ratio of the diaphragm, when there are no Iai 1¢ openings between two adjacent shear walls, should not exceed those as set forth in Tab.6.1.8. If the aspect ratio is greater than those in Tab. 6. 1. 8, the effect of in-plane deformation of the diaphragm shall be considered. 6.1.9 When precast floor or roof diaphragms are used in frame-shear wall structures, measures shall be taken to ensure the integrality of diaphragms and reliable connection between diaphragm and shear wall 6.1. 10 Installation of shear walls in frame-shear wall structures shall comply with the following requirements? 8 1. Shear walls should be built through the total height of the building, and the transverse shear wells should be connected with the longitudinal shear walls. 2. Shear walls shall not be placed at locations where large opening on wall is necessary’ the area of the opening on the shear wall should not exceed 1/6 of the wall area, and openings on all stories should be in line vertically. Height of the beam over the opening should be not less than 1/5 of the story height 3. When the building is relatively long, the longitudinal shear wall should not be installed at the end bay of the building, Table 6.1.8 Aspect Ratio of the Diaphragm Between ‘Two Adjacent Shear Walls Toensity of disphengms “Type of diaphragt 7] 7 7 7 Poured in-situ diaphragm or] AO a5 a0 lapped beara and slab . ag | thosld not Precest floor slab 3.0 3.0 S| ita bear and slab in shall not Poured insta beam and slab 2s as 20 the frame supported stories | be ured 6.1.11 In framed structures, distribution of masonry filled walls in both plan and elevation should be uniform and symmetric: the formation of weak story and short column should be avoided. Light-weight walls or panels connected flexibly with the frame should be used as enclosure walls and partition walls in frames of seismic grade Lor 2. 6.1.12 Effect of laternal force resistence of brick filled walls may be considered for grade 2 framed structures with up to 5 stories, grade 3 framed structures with up to 8 stories and all grade 4 framed structures, but they shall comply with the requirements for shear walls as set forth in Article 6.1.8 and Article 6.1.10 in this Section. 6.1.13 Installation of shear walls in shear wall structure shall be in accordance with the following requirements? 1. A relatively long shear wall should be divided uniformly into several short sections by installing of weak connecting beams based on the opening in the wall, and °the height-width ratio of wall section (including walls with small openings and coupled walls) should be not less than 2: 2. When relatively large openings exist in shear walls, the openings should be arranged in 4 vertial line 3. For buildings with a frame supported story in the lower part, stiffness of the story shall be not less than 50% of the stiffness of the adjacent upper storys the ‘number of shear walls on the ground should not be less than 50% of those in the upper stories, and spacing of the shear walls should not be greater than four bays or 24 m, whichever is the smaller. Length-width ratio of the floor diaphragm between the shear walls on the ground shall not exceed the value as set forth in Tab.6. 1.8. [Note:A coupled wall with werk connecting beams refers toa coupled wall for which the stat bending moment of eros section of the wall under seismic action in each story shall not bbe less than 5 times the total restraint moment of the connecting beams in the given story and all upper stories. 6. shaft, longitudinal shear walls at the end bay of building and gable walls, single limb 4 Shear walls in the top story, staircase and lateral force resistant elevator wall, wall with small opening and the bottom portion of the coupled wall (i.e.1/8 of the totel height or the width of the with a frame supported first story, the bottom portion shall not be less than the sb wall, whichever is the greater: for buildings height of the floor level just above the frame supported story) shall comply with related requirements for strengthening portion as set forth in this Chapter ructure, foundation tie 6.1.45 In one of the following cases for framed cams should be installed in the direction of both main axes A. Frames of grede 1 and 2 2. The representative values of gravity loads on column foundations differ areately 3. Comparatively deep-lying foundations, or buried depths of different foundations differ greatly 4. In the range of the main bearing layer of the foundation, there exist weak cohesive soil layers, layers liable to liquefaction, and seriously heterogencous layers. 6.1.16 Shear wall foundations in frame-shear wall structures and foundation of shear walls on the ground in the frame supported story shall have excellent integrality and ability against rotation. 6.1.17 Joint and anchorage of reinforcement shall be in accordance with the following requitements other than those as set forth in the current national standard, “Construetion and Acceptance Code for Reinforced Conerete Structures”. 50 1. Stirrup shall have 195" hook and the straight portion of a stirrup shall not be fess than 10 times of its diameter 5 2, Longitudinal bar joints in beams and columns of a freme and members at the edge of a shear wall should be welded or connected mechanically at all locations of ‘grade 1 structures , at the bottoms of columns in the first story of grade 2 structures land at strengthening portions at the bottom of the shear wall. In other cases, tied joints may be used’ in the range of overlapping of reinforcement, spacing of stirrups shall not be geeater than 100 mm. 3. For grade 1 or 2 structures, anchorage length of the longitudinal reinforcement in heams and columns of the frame and in connecting beams of the shear wall shall be 5 times of the diameter of the longtitudinal reinforcement more than the minimom anchorage length specified in the non-seismic design 4, Joints of distribution reinforcement of the shear wall and joints of the vertical reinforcement in the strengthening portion in the wall bottom of grade 1 or 2 structure shall be welded or connected mechanically, when diameter of the reinforcement is greater than $22. In the other cases, tied joints may be used, but the overlapping location shall be offset for every other reinforcing bar in the strengthening portion. 5. Welded or tied joint should not be placed at the location where maximum bending moment of the member occurs and at the end of beams or columns where stirrups are densely arranged overlapping length in tied joints shall be 10 times and 5 times of reinforcement diameter more than the minimum overlapping length specified in the non-scismie design for grade 1 or 2 structures respectively 6. When the total steel ratio of the longitudinal reinforcement in columns exceeds 3%, stitrups shall be welded. 6.2 Essentials in catculat 6.2.1 Earthquake action effect shall be adjusted for reinforced concrete structures in accordance with the provisions in this Section; checking of eross-section of members shall be in accordance with the requirements as set forth in the related current codes for structural design, if not specified in this Chapter and related ‘Appendices, but the design value of loading capacity shall be divided by the seismic ‘adjusting coefficient for loading capacity specified in the code. Checking of cross-section of members for earthquake resistance need not be performed for structures as set forth in clause 1, Article 4.1.6 in intensity WL 6.2.2 At the joint of the beam and the column in grade 1 or 2 frames, bending moment at the end of the beam or the column shall comply with the following 5equations, except the top story and the column with en axial compression ratio less than 0.15. For grade 1 structures, DM.= 1.12 Min (6.2.24) or DM.=1.15Mi (6.2.22) For grade 2 structures, DM,=1.15Ms (6.2.23) —sum of bending moment design values for cross-section combinition in clockwise or counter-clockwise direction at the ends of columns above and below the jointiin general case, the bending moments at the upp- cr and lower ends of column may be distributed by elastic analysis ‘CMy—sum of bending moment design values for cross-section combination in clockwise or counter-clockwise direction at the ends of beams to the right and left of the joint jctual reinforcement amplification factor of a joint, which may be taken a8 1.1 times the ratio of the sum of actual longitudinal tensile reinforcement areas to that of calculated areas at the ends of beams to the right and left of the joint, or may be determined by analysis and comparison. ‘DMva—sum of bending moments corresponding to seismic bending capacity of normal cross section with actual reinforcement in clockwise or counter-clockwise direction at the ends of beams to the right and left of the joint, which may be determined by actual reinforcement area and standard value of the material strength. 6.2.3 Design value combined bending moment at the bottom of columns on the first story and at the two ends of columns in the frame supported story of grade 1 end 2 frame structures shall be multiplied by an amplification factor of 1. 5 and 1.25 respectively. 6.2.4 Combined shear force design value of cross-sections at the ends of beams, columns, sheer walls and connecting beams in « frame, necessary to be checked for ‘earthquake resistance in accordance with Article 4.1.6 in the code, shall comply with the following equation: V0.6 Cima amgeemnwsine | 08 | te s| : Sind eres os [| 7 Ordinary stirrups, composite stirrups | 0.6~0.8 | 0.8~1.2 2 ‘Spiral sierpe 06 [os-1.0[ 10-1. a Ordinary stirrups, composite stirrups | 0.4~0.6 | 0.6~0.8 | 0.8~1. : Sil wi oa [| os | on (Note: 1) Ondinary straps refer to indivdel rectanguler stirs composite ster are stirrups formed by rectangular stups and rhombi, polygon. round stops ox te bari 2) in the caluation of steel volume sti of composite strups, velume of stirups in the overlapping portion should be deduced 3) For srups of grade Il stel and concrete of srength grade not higher than C40, values in the Table may be multiplied by a reduction factor of 0.85. However the fstor shall not be lees than 0.45 4)When the distance betwee limb of composite trup witha #-shape i nt more than 200 mm andy alo diameter of the trp is nt les than 410, the corresponding values or sical sirup in the ible may be taken <1 The distance between limbs of sirup in the densified zone of columns should be not greater than 200 mm for grade I structures, 250 mm for grade 2 structures and 300 mm for grade 3 or 4 structures respectively, and stirrups should be arranged in two directions for every other longitudinal reinforcing bar for confinement ; when combined tie bar stirrups are used, the tie bar should be intimately clase to the longitudinal reinforcing bur and hooked with the clased stirrup 6.3.42 Amount of stirrups in the non-densified zone of the column should be not less than 50% of chat in the densified zone, and also spacing of stirrups shall be not less than 10 times the longitudinal reinforcement diameter for seismic grade 1 or 2 structures and 15 times for grade 3 structures respectively. 6.3.13 The maximum spacing and minimum diameter of stirrups in the core zone of a joint in the frame should be obtained by using Table 6.3.9 . The steel volume ratio should be not less than 1.0,0.8,and 0.6 % for seismic grade 1, 2, and 3 structures respectively. However, when the axial compression ratiois less than 0.4 , it should be obtained also by using Table 6.3.10. 6.3.14 Filled masonry wall shall be in accordance with the following requirements? 1, When the lateral force resisting effect of filled brick walls is considered, the brick ‘wall shall be laid in plane of the frame and connected firmly with beams and columns. ‘Thickness of the wall shall be not fess than 240 mm and the grade of mortar strength not less than MS. The brick wall should be laid before concreting the frame. Filled walls of other types shall be connected flexibly with columns in the frame, but the top of the wall shall be intimately connected with the frame. 2. For a frame with filed masonry walls 246 reinforcing tie bars shall be placed for every 500 mm along the height of the column in the frame. Length of te bars extending to the filled wall should be the whole length of the filled wall for grade 1 and 2 frames, and shall be not less than 1/S of the wall length but also not less than 700 mm for grade 3 or 4 frames. 3. When the wall length is greater than 5 m, the top of the wall should be tied with the tie beam; when the height of the wall exceeds 4m, a reinforced concrete horizontal beam should be placed at the middle level ofthe wall to connect the columas on both sides. a6.4 Constructional measures for shear wall structures. 6.4.1 The edge elements, such as wing column (stub return), end column or cenclozed column, shall be installed in the shear wall of grade 1 or 2 and at the strengthening part of the shear wall of grade 3. As for the cross section of the enclosed column, the width is the same as the shear wall thickness and the depth shall be 1.5 to 2.0 times the thickness of the shear wall. For the cross section of the wing column, dimension of the cross scction shall be the same of the enclosed column with an extension on both sides of the shear wall not greater thn twice that of the wing wall thickness. 6.4.2 Thickness of the shear wall panel with wing wall or end column on both sides shall be not less than 160 ram and also not less than 1/20 and 1/25 of the story height for ‘grade 1, and not less than 140 mm and also not less than 1/25 of the story height for arades 2 and 3. 6.4.3 Vertical and lateral distribution reinforcements in a shear wall shall be arranged in two rows forall portions in grade 1, and strengthening portions in grade 2, but should be arranged in two rows for ordinary portions in grade 2 and strengthening portions in grade ‘Boor 4: spacing between tie bas of the distribution reinforcements in two rows shall be not ‘greater than 700 mm and the diameter of tie bars shall be not less than 6 mm. Spacing ‘between tie bars shall be intensified appropriately in the strengthening portion at the bottom. 6.4.4 Arrangement of the vertical and lateral distribution reinforcements in a shear wall shall be both in accordance with the requirements as set forth in Table 6.4.4 minimum steel ratio of distribution reinforcement in ordinary location for comparatively high ‘multi-story buildings of grade 3 on Type IV site shall be not less than 0.20% ‘Table 6.4.4 Requirements for Distribution Reinforcements in Shear Walls Seismic ‘Minimum steel rato %) Maximum | 4g eae, wee | emer structures | Ordinary portion | Strengthening portion | (nm) 1 0.25) 0.25, 2 0.20) 0.25 00 # 34 0.15) 0.20 6.4.5 Reinforcements in edge elements ofthe shear well shall be in accordance with the requirements as set forth in Table 6.4.5. 6.4.6 For connecting beams in the top story, sttrups shall be placed in the range of anchorage length of longitudinal reinforcements ‘Table 6.4.5 Requirements for Reinforcements in Edge Elements of a Shear Wal Siren partion be Ot Kono Simic ahi Minima amon | Sieap or ier | Mini amount | Sirupo endeat | elongata! ‘angina |S = serene | cra he Monson | rénercementthe | imam | Maer ‘emer tlw sa ee al “ Tema | ameter | ign | MEMS | ante | dingtme) 1 0.01546 | rane « | w 2 o.012he 6 | 1 a we | am an o.00see, | 0.05, a aha ey | oo le ‘ oe 6 | one 6 | om Note: A, isthe crow-section aren of enlowd or end columns. The eros section are of enloed ofumns should he used nly foe the wing columns. 6.5 Constructional measures for frame-shear wall structures 6.5.1 Thickness of a shesr wall panel shall be not less than 160 mm, and also not less than 1/20 of the story height. In the perimeter of the wall panel, boundary frame formed by beams (or enclosed beams) and end columns shall be made. When the width of cross section of the boundary beam is not les than 2 times of the wall chickness, the wall thickness shall not be less then 1/20 of its clear height. 6.5.2 Stee! ratio of both vertical and lateral distribution reinforcements in a shear wall panel shall be not less than 0.25%, and the reinforcements shall be arranged in two rows. ‘Spacing of tie bars shall be not greater than 600 ma. 6.5.3 Stirrups in the end column along the overall height of a shear wall shall be arranged in accordance with the requirements for the strengthening portion atthe bottom of the wall asset forth in ‘Tab 6.4.5, 6.5.4 Other constructional messures for frame-shear wall structures shall be in accordance with the related requirements as set forth in section 3 and 4 in this Chapter7.Multi-story brick buildings with framed first story or inner-frames 7.1 General 7.1.1 This chapter is applicable to multi-story clay brick buildings with frame- shear wall in the first story or with inner-frames. It is applicable to other similar unit masonry buildings for reference. 7.1.2 Overall height and number of stories of multi-story brick buildings with framed first story or inner-frames should not exceed the values asset forth in Tab .7.1.2 Table 7.1.2 Limit Value of Overall Height(m)and Number of Stories w * 7 a Type of bing Hein | MP eee | NET ign | NOt | are | NOE eck bing with med | wlslule fist stony Dy) 2) |) -G| Beck badlng wih nee tne and main of 18 | s |e | s fw | a |e | 2 ck baling ih oer | Note:Overall height of «building shall be calculated as in the note of Tab.S. 1.2 7.1.3 Maximum spacing of transverse shear walls in brick buildings with framed first story or inner-frames shall be in secordance with the requirements as set forth in Teb.7.1.3 NOTE: An inner frame is «frame without exterior columns. This kind of structoure is commonly used in Ching. Bearing brick walls are used instead of exterior columns i the inner frame. Table7.1.3 Maximum Spacing of Transverse Shear Walls(m) Tntensity “Type of building W 1 w © ‘ick building with | Unper stories | _Seme ax brick buildings in Tab.5.1.6 framed first story Fi 25 2 18 Brick building with innerframer and 30 30 0 » rmulti-row of eolumns | Brick building with inner-leames end eae ‘Seme sa bricle buildings in Tab.5.1.5 7.1.4 In the first story of brick buildings with framed first story, certain members of shear walls shal be arranged symmetrically along the longitudinal and the transversal direction, and the ratio of lateral drift stiffness of the second story to that of the first story shall be not greater than 3 and 2 in the intensity of Wand Wor I respectively. Reinforced concrete walls should be used as shear walls, and in the intensity of Vand W, filled brick walls and smell-size concrete block walls may he used in the framed structure. 7-4.$ The unit masonry and reinforced conerete structural members in brick buildings with framed first story or inner-frames shall comply with the related requirements as set forth in Chapter § and 6 respectively. Seismic grade of the reinforced concrete structures may be determined as framed structures for the frame in brick buildings with framed first story and inner frames, and as grade 3 for shear walls 7.2. Essentials in caleulation 7.2.1 The base shear method may be used in the seismic ealeulation for brick. buildings with framed first story or inner-frames, and the earthquake action effect shall be adjusted in accordance with the provisions as set forth in this section. 7 directions in the first story of brick buildings with framed first story shall be sd by an amplification factor in the range of 1.2~1.5, based on the ratio of -2 Design value of seismic shear force in the longitudinal and the transversal lateral drift stiffness of the second story to that of the first story. 7.2.3 Design value of seismic shear force in the longitudinal and the transversal codirections in the first story of brick buildings with framed first story shall be fully tndertaken by the shear walls in corresponding direction, and can be distributed in proportion of the lateral dift stiffness of the shear walls 7.2.4 Seismic action effect of frame columns in brick buildings with framed first story may be determined by the following method: 1. Design value of seismic shear force suffered by frame columns may be determined in proportion of the effective lateral drift stiffness of all lateral force resisting members: value of the effective lateral drift stiffness may not be reduced for the frame, and may be taken as 30% for the reinforced concrete wall, and 20% for the clay brick wall 2. Additional axial force induced by the seismic overturning moment shall be considered in the calculation of the axial force of the frame column. The seismic overturning moment carried by the elements in all axes may be determined in proportion of the rotation stiffness of shear walls and frames in the first story. 7.2.5 Design value of seismic shear force for columns in multi-story brick buildings with inner-frames should be determined in accordance with the following ‘equation: vin Be (atten (7.2.5) where V.— Design value of seitmie shear force of colums V— Design value of seismic shear force of story’ $e—Coefficient of type of columns, and may be taken as 0.012 for interior reinforced concrete columns, 0.0075 for composite brick columns in the exterior wall, and 0.005 for unreinforced brick columns (walls); ny—Number of bays between transverse shear walls; ns—Number of spans of the inner-frame: A — Ratio of spacing of lateral shesr walls to the total width of the building and may be taken a8 0.75 when the ratio is less than 0.7 Sis Sa — Coefficients for calculation, and may be taken in accordance with Table 1.2.5. ‘Table 7.2.5 __Coeffieclents for Calealation Total number of sores of the building | 2 [ 3 | 4 | 5 w 20 | 30 | 50 | 75 o 7s | 70 | 68 | 60 66 7.2.6 Seismic checking of brick columns in the exterior wall may be earried out in accordance with Article 8.2.8 in this code. 7.3 Constructional measures Reinforced concrete constructional columns shall be installed in the upper 13. stories of brick buildings with framed first story, based on the total number of stories and in accordance with the provisions as set forth in Chapter 5 of this code Reinforced concrete constructional columns shall be installed at the following. locations in multi-story brick buildings with inner-frames: 1. Four corners of the exterior wall, staircase, and elevator shaft. 2, Both ends of the shear wall and in the exterior longitudinal and transversal wall without composite columns corresponding to the axis of the central row of columns in intensity VI, Wand WW when number of stories is not less than 5, 4, and 3 respectively and in intensity IC 7.3.2 Cross section of constructional column should be not less than 240 mm X 240 mm; longitudinal reinforcement, not less than 49143 and spacing of stirrups, not greater than 200 mm. The constructional column shall be contiected with the zing bbeam in each story. 7.3.3 Cast in-situ or precast monolithic reinforced concrete slab shall be used as the floor in the first story of brick buildings with framed first story and as the roof of multi-story brick buildings with inner-frames. 7.3.4 Ring beams shall be installed in all stories of brick buildings with framed first story or inner-frames having precast reinforced concrete floor and roof diaphragm. When cast in-situ or precast monolithic reinforced concrete floor slab is used, ring beams need not be installed but the floor slab shall be connected reliably with the corresponding constructional columns by reinforcing bers. 7.3.8 The width of a longitudinal window wall in multi-story brick buildings ‘with inner-frames shall be not less then 1.5 m i supported length of the beam on the exterior wall shall be not less than 300 mmi_ and the beam shall be connected with the ring beam. 68. Single-story factory buildings 8.1 Single-story factory buildings with reinforced concrete columns (1) General BLL requirements 1. Height of each span in multi-span factory buildings should be equal fout of the factory building shell be in accordance with the following 2. Attached building of a factory building should not be arranged at the corners of the buildings 3. Seismic joint should be installed in factory buildings with a complicated configuration or attached buildings? width of the joint may be taken as 100~150 mm at the junction of the longitudinal and the transversal spans of a factory building, or 50~90 mm in other cases. 8.1.2 Steel frame should be adopted for skylights projecting on the roof. In the intensity of 11 ~ W, reinforced concrete skylight with rectangular cross-section elements may be used; in the intensity of IK, settled-type shylights may be used Roof and end walls of the skylight should be made of light-weight materials. Frame of the skylight should be installed at first on the third column bay from the end of the factory building 8.1.3 Prestressed concrete oF reinforced concrete roof trusses should be used for factory buildings: steel roof trusses may be used for factory buildings with a span ‘greater than 24 m, or on site of categories Il and IV in intensity WI, and on any site category in intensity IC. If the column bay is 12 m, prestressed concrete brackets, may be installed 8.1.4 In the intensity of Wand IK, rectangular or I-shape cross-section columns cor double limb columns with inclined web bracings should be used for factory buildings, but L-scction columns with thin web and openings or with precast webs should not be used. Rectangular cross-section should be used for columns in a range from the column base to 500 mm above the indoor ground surface, or for the upper part of the step-wise column. Section steel should be used as braces between columns, the inclined angle of which should be not greater then 55" 8.1.5 Light-weight panels or large-size reinforced concrete panels should be used as curtain walls for factory buildings} large-size panels should be used for factory buildings, when spacing of exterior columns is 12 mi light-weight panels should be 68 used for curtain walls of the higher span at the junction of the higher span and the lower span, or for the suspending wall in the intersection of the longtudinal and transversal bents of the building; enclosing mssonry wall should be built as attached walls, but, in the two sides of a single-span factory building, filled walls may be used. 8.1.6 Masonry parti connected with the columns, but measures shall be taken to ensure stability of the ion walls, should be separated from columns, or flexibly wall. Also. on top of the wall, = cast-inssitu reinforced conerete beam shall be placed. 8.1.7 Roof truss should be placed at the end of a factory building instead of gable wall, and the gable wall should not be used as @ bearing wall (1) Essentials in calculation 8.1.8 Seismic checking of crost-sections in transversal and longitudinal directions’ need not be carried out for singlespan factory buildings and multi-spen factory buildings of equal height with gable walls at both ends, the column height of which does not exceed 10 m (except factory buildings with saw-toothed roof), on sites of nal measures of buildings categories Lor Il in the intensity Wl, but the construct shall comply with those as set forth in this section 8.1.9 The following methods may be used for seismic calculation in transversal direction of « factory building? 1 the effects of spacial action, torsion and erane truss shall be considered. ‘The seismic ‘or factory buildings with reinforced concrete roof with or without purlins, faction in transversal direction may be calculated as that in planar bents and ‘corresponding adjusting coefficients or seismic shear and bending moment of the bent as set forth in Appendix E in this code may be used. “The building may also be analysed as a multi-mass spacial structure, considering the planar elastic deformation of the rool 2. Factory buildings with a light-weight roof, equal column bays, but lacking a complete bracing system, may be calculated as planar bents. Note: Light-weight roof refers to roof made of moulded stel plates, or corrugated iron sheets, or asbestos tiles and pins. 8.1.10 The following methods may be used for seismic calculation in longitudinal direction of « factory building? 1. Factory buildings with light-weight reinforced concrete roof with or without «purlins and with a considerably complete bracing system may be analysed as multi- ‘mass spacial structures, considering the effect of planar elastic deformation of the roof, effective stiffness of curtain walls and partition walls as well as torsion. If a building is in accordance with the conditions as set forth in Appendix F in this code, corresponding simplified calculation method may be used. 2. Other factory buildings with a light-weight roof may be calculated as longitudinal bent consisting of a row of columns separately 8.1.11 The following methods may be used for seismic calculation of skylight frame on the roof: 1. The base shear method may be used for seismic calculation of reinforced concrete skylight truss with inclined web members in transversal direction. When the span of the skylight frame is greater than 9 m or in the intensity of IK, effect of seismic action of the skylight frame shall be multiplied by an amplification factor, the value of which may be taken as 1.5. 2. Spacial structure analysis method may be used for seismic calculation of skylight frames in the longitudinal direction, considering planar elastic deformation of the roof and effective stiffness of the longitudinal walls. Base shear method may be used in the calculation of longitudinal seismic action for skylight frame in the single span factory building and mult-span factory building of equal height with reinforced concrete roof without purlins, the height of columns of both of which does not exceed 15 m. But the effect of shall be multiplied by the following amplification factors. For the roof in a single span or an exterior span, or in the mid-span having jmic action of the skylight fr longitudinal interior partition walls, gn 1+0.5n (8.1.11) For the roof in other mid-spans, 720.5" (8.1.11.2) where — amplification factor of seismic action effeeti number of spans exceeds 4, ‘n= number of spans in the factory buildin it will be considered as 4 8.1.12 In a fectory building with large column array, the column spacings of ‘which in both direction not less than 12 m, but without a bridge-type crane and column bracings, columns should be square in cross-section. Horizontal seismic action in two major axis directions shall be considered simultaneously in seismic checking of cross-section. 100% of the action in one major axis direction combined ‘with 30% of the action in corresponding perpendicular direction shall be taken as an 0 ‘unfavorable combination in seismic checking. Additional bending moment induced by displacement (p-< effect) shall be considered also. 8.1. 13 In factory buildings with unequal heights, cross-section area of the longitudinal tension reinforcement in the column bracket, supporting the roof on the lower span, shall be determined secording to the following equation: (8.1.13) ‘cross-section area of the longitudinal horizontal tension reinforcement Nodesign value of compression induced by the representative value of gravity load on the surface of the column bracket ‘a—distance between the action point of the gravity load and the near edge fof the lower crane columns when it is less than 0.3hy, 0. hs shall be taken; he Neo design value of horizontal tension in the seismic combination on the clfective height of the largest vertical cross section of the bracket surface, of the column bracket ‘Yee—seismic adjusting coefficient for loading capacity, it may be taken as 1.0. 14 Seismic checking of seismic action effect of inclined member in the cross column bracing and connection joint of the brace and the column may be carried out as set forth in Appendix F. ) Constructional measures 8.1.15 Connection of members and arrangement of bracings in the roof with purling shall be in accordance with the following requirements: 1. Purlins shall be welded tightly with the roof truss (roof beam), and sufficient bearing length of purlins shall be provided. 2, Purlins on the double ridge roof shall be tied with each other at 1/3 of the span. 3. Channel tiles, corrugated iron sheets and asbestos tiles shall be tied with purlins. 4. Arrangement of bracings should comply with the requirements in Table 8.1.15. nTable 8.1.15 Bracing Arrangement for Roof with Purlins a Welt 7 © ne ao. of ning tea in ach ead My of Butdag oni fd atthe ay th ‘Trnaere | One no, of busing | coun tracing ina | One no. of eaing ming cn | aed ich end | bung ont with | ised in each end fheupper | Kiya fncy | engraver than 68 | ty for» bla emit toed tilde on moore ea of | and at the bay wih ‘cel laa acing |colem brcing, and | inualled at exch end of | » building unt with 6 Beene | the ene wh yt | length greater shan 42 oo omen Sie ao. of dana eo lect ‘women upper FA ‘Sod brecing ne wm Vn Sieh end of he sone tower thrd ‘wah sya opening Vera a Sing nthe de ofthe he | When high ofthe end pr of ther era i greater tha 900 mi one feral bring ional Sn sch td ay of Bling ot The By ‘ean bai ne 90. of acing tracing oni) hight bey of « unit Bracing | SPP SHOE | Fan factey hung ere ofthe — in ench ond skylight stotehe ‘One wo, of wating | by cle ane ns | bay of sant i fame | eric ‘nmtlled at every 26 m | feetory beilding {nctory building Wing on [ich tod St Te yt a te fetory boli 8.1.16 Connection of members in the roof without purlins shall be in accordance with the following requirements 1. Large-size roof slabs shall be welded firmly with the roof truss (roof beam), and length of the welding seam in the connection of the roof slab and the roof truss (roof besm) adjacent to the row of columns should be not less than 80 mm. 2. For the end bay of a building unit with 2 skylight, when the intensity is Wi or Mi or for each bay when the intensity is Wand IX, adjacent large-size roof slabs in the direction perpendicular to the roof truss should be welded with each other at their n top surfaces. 3. In the intensity of W and I, angle steel should be used as parts on the bottom of the end of the large-size roof slab, and should be welded firmly with the main reinforcement in the slab 4. For non-standard roof slab, precast. monolithic joint should be used, or the sb should be welded firmly with the roof truss (beam) after cutting the four corners of the slab 5. Anchorage bars of the builtin parts on the top of the end of the roof truss (beam) should be not less than 4610 and 4612 in the intensity of Wand K respectively 6. Arrangement of bracings should be in accordance with the requirements as set forth in Tab 8.1,16~1 and Tab. 8.1.16 ~ 2 for shaft-type skylight in the middle of the building. In the intensity of Wor I, one number of vertical bracing system may be installed at each end of a building unit with thin-web beam roof structure, the span of which is not greater than 15 m. 8.1.17 Wall panels and columns on both sides of the reinforced concrete skylight franie projected on the roof should be connected with each other by bolts. 8.1.18 Cross section and reinforcement of the reinforced conerete roof truss shall he in accordance with the following requirements 1. Reinforcement in the upper chord in the first panel of the truss and the strut at the end of the trapezoid-shaped truss should be not less than 412 and 4614 in the intensity of Wor Wand Wor IX respectively Table 8.1-16-1 Bracing Arrangement for Roofs Without Porlins Sime 1 in the om amie" desig when stance ene | One oof tain nmin ech end by and fovol brcog fated | Baye with clu. Bacngr’ one adie! lc ceike| mech end ty of | bracing ised a each ond of the able Botting: when the tom lth ri ot teen cing on the cneiog for» balding wi n= te the same as that of the upper chord Bee a < 7 3:Cross section dimension ofthe small strut supporting the root slabs atthe end —_ of the upper chord of the truss shouldbe not less than 200 mm % 200 mm and the Sel, AoE | Oma eee small strut height, not greater than 509 mm. Major reinforements in the strat should See rears be TL in shape and not less than 4912 and 4614 inthe intensity of Wor Wand Wor I fer nag red nt | ut, od nt respectively. $6 bars may be used as stirrups with a spacing of 100 mm. Vera Sera at same eae peice was ote | wan oo or ne ‘Table 8.1.16-2 Bracing Arrangement for Roofs Withoot Purlins Having a eeeteele eects aetna Shaft-Type Skylight in the Middle of » Building Seite "ag | rst ae = reese See Soe Tar 7 a ————— ‘One no. of bracing | One 0. of bracing — ne no of tag | ae a 2 | ote a a | ante inthe installed in exch end | bay. end beys with | bay. and bays with tee | ie : Tose acon on fay ttle” |S he cey | Sha ei voy ‘Beane | chord seven Same os in the non. | Seem the tonerer ‘the lower chord ‘cory build sues acre on _ . ‘bracing on the wpper the Vera seine design ah i — |e on on edo he | dt he jf thse ead in he ie pn of te tre | meee ‘epper chord ‘within the range of the skylight” | = One nos of braced | inmalod in erch end J toy of ovina | Vertical bracing in the | Installed in the bay with cranevese bracings on the upper chord with # ae ; incl tm 8 St" “| ee sere So eo ee) factry boing _ i oo Prawn Om to. of bg tae ot oe Seance et | TS JERE one no. of cin | One no. of tracing | OPE tes SE rn oP | ame in he mn | Sa a int en Ah mi ay see ey ea te | ty nde wen [207 0 mt vee ot | Tic} tating [stems acne |” ‘ae, ——__|"__ | so. of bracing in One no. of bracing fod part of |invalled in each end | of 48 min each ed | of 30 min wach end ! Sods era a | OES tl eect ie | Sy tin Se | band “bags | bac “bse st j Ver tang om bah | Ate wm ner | ated rer Sai” | Sing” | megs | ntti 2 7 | side ofthe hi ake with | 22 NY Laight in 8 storages ont | 8.1.19 Suicrups ina column ofa factory building shall be in accordance with the following requirements? 2. Width ofthe cross section of the end strut of the trapezoid-shaped truss should 1. In the following range, confinement reinforement shall’be provided? " 181) Column head: for a length of 500 mm from the top of the column, and also not less than the length of the column cross section. 2) Upper column? from the bracket surface to a distance of 300mm above the crane beam surface of a step-wise column. 3) Bracket of the column (column shoulder)? for the whole lhcight of the bracket. 4) End of the column? from the bottom of the lower column to a distance of 500 mm above the indoor ground surface 5) Ina distence 300 mm above and below the joint of the column, its bracing, and locations, st which the column displacement is constrained by the platform or the built-in interior partition wall 2. Spacing of stirrups in the intensified zone shall be not greater than 100 mm, and the minimum diemeter of the stirrup shall be in accordance with the provisions as set forth in Tab. 8.1.19. ‘Table 8.1.19 Mis ter of Stirrups in the Intensified Zone. Intensity aod typeof i Location of Cues Wor W]Cocgory of or intensified | CeteHory Tor Ul) seein intensity We [sites in intensity We sone sites in intensity | sag category Vor Ul |and all stes in Ossie sites in intensity W_| intensity TE ‘Top and bottom of 2 8 ordinary columns * : ‘Upper column, bracket,and column #8 8 +0 bottom with bracings “Top ofthe column swith bescings and loctions at which the 6 #0 #0 column displacement is conteained 8.1.20 Layout and details of a column bracing in a factory building shall be in 76 accordance with the following requirements: 1. In general, bracing between the upper columns and the lower columns shall be installed in the middle of a building unit. In the case of factory buildings installed with cranes, or in the intensity of Wand DX, additional upper column bracing should also be installed at both ends of a building unit 2. Slenderness ratio of bracing members should not exceed the values as set forth in Tab.8.1.20. ‘Table'8.1.20 Maximum Slenderness Ratio of Inclined 7 is Upper column 250 | 50 | 200 | 160 Lower columa. 200 | a0 | 190 | 160 3. Location of the lower connection joint and constructional measures for the lower column bracing shall be adopted so that the seismic action can be transmitted directly to the foundation otherwise, the unfavorable effect of the bracing reaction fon the column and the foundation shall be considered when the intensity is Wor Wh 4. Gusset plate shall be intalled at the intersection of the diagonal bracing and the thickness of the gusset plate shall be not less than 10 mm. The gusset plate shall be welded with the inclined members, and these members should be welded with the end gusset plate 8.1.21 A horizontal compression member should be installed along the top level of the middle column rows for multi-span factory building with a span not less than 18m in the intensity of W, or along the top level ofall column rows for & multi-span factory building in the intensity of K. The compression member may be taken instead of the horizontal tie rod installed at the support of the trapezoid-shape roof truss. Clearance between the end of the reinforced concrete tie rod and the roof truss shall be filled with concrete, 1,22 Connection joints of the structural members in_a factory building shall be in accordance with the following requirement 1. Roof truss (or beam) should be connected with columns on top by bolts in the intensity of Wl, or by hinge plate in the intensity of , but bolts may also be used’ thickness of the bearing plate at the end of the roof truss (beam) should be 7not less than 16 mm. 2. Anchorage bars in the built-in parts on top of @ column should be 4814 and 4416 in the intensity of Wand I respectively. For columns with bracings, shear plate shall be installed additionally other than builtin parts. '3. Built-in plate shall be put on the top of the wind resistant column in # gable wall, 0 that top of the column can be reliably connected with the upper chord of the tend truss (or upper flange of the roof beam) 4. Built-in parts in the bracket in the middle of a column (column shoulder) supporting the lower-span roof shall be welded with the longitudinal reinforcement subjected to the calculated horizontal tension in the bracket (column shoulder), and the welded bars shall be not less than 2612, 2614 and 2916 in the intensity VI or Wl, Wand IK respectively. 5. Steel angles together with end plate should be used as anchors of the built-in parts at the joint of the bracing and the column at category Ill or IV sites in intensity W, and all sites in intensity IK, and, in other eases, deformed bars of grade fl may be used, but anchorage length shall be not less than 30 times the diameter of the anchor bar. 8.1.23 Brick enclosing wals shall be tied reliably with columns along the height Gncluding wind resistant columns), end of the roof truss (beam), roof slab and gully plate. Eclosing walls above the lower roof level of » factory building with unequal heights and suspended walls in the fersection of the longitudinal and transversal units shall be tied firmly with columns and roof members. 8.1.24 Ring beams in the brick enclosing walls shall be in accordance with the following requirements? 1. Poured in-situ reinforced concrete ring beams shall be installed at the following positions: 1) One number of ring beam shall be installed on both levels of upper chord at the end of the trapezoid-shape roof truss and top of the column, but only one ring beam can be installed if height of the end part of the truss is not greater than 900 mm, 2) In the intensities of WI and KX, a ring beam shall be added on the top level of the window in an interval of 4 m approximately, based on the principle that beams in the upper part should be more densely placed than in the lower part 3) A reinforced concrete beam shall be installed on the gable wall along the roof level, and shal be connected with the ring beam at the level of the upper chord at the end of the roof truss. 2. Width of the eross section of the ring beam should be same as the wall % 1 1 t t t thickness and height of the beam shall be not less than 180mm. Reinforcement of the team shall be not less, than 4412 and 4614 in the intensity of I~ Wand I respectively. '3. Longitudinal reinforcement in the ring beam on top of the column at the comer of the factory and in the range of the end bay should be not less than 4#14 and 4416 in the intensity of Vi~ Wand DX respectively: stirrup diameter in the range of Im on both sides of the corner should be not less than #8, and spacing of stirrups should be not greater than 100 mm. In ring beams at the corner, not less than 3 shall horizontal diagonal bars, with a diameter same as that of the longitudinal b additionally be installed. 14. Ring bear shall be firmly connected with the columa or roof truss. The beam on the gable wall shall be tied with the roof slabs. Anchor tie bars for the ‘connection of the ring beam on the top of the column and the column should be not less than 4612, the anchorage length of which should be not less than 35 times the reinforcement diameter 8.1.25 Poured in-situ joint shall be used for the precast foundation beam under the brick enclosing wall at site of category [Mor IV in intensity W, and all sites in intensity IK: if strip footing is otherwise used, @ continuous poured in-situ reinforced concrete ring beam shall be placed at the top level of the column foundation and reinforcement of the beam shall not be less than 4 $12. 8.1.26 Poured in-situ wall beams should be used’ if precast wall beams are used, the bottom of the beam shall be tied firmly with the top of the brick wall and anchored in the column. Wall beams adjacent to the comer of a factory building shall be flexibly connected with each other, 8.1.27 In the intensities of Wand I, large-size reinforced conerete wall panels should be flexibly connected with the column of the roof truss in # factory building 8.2 Single-story factory buildings with brick columns (1) General 8.2.1 This section is applicable to the following medium- and small-size factory buildings with brick bearing columns (piers) 1, Single-span and multi-span (of equal height) workshop and warehouse. without bridge crane. 2, Buildings with a span not greater than 15m and a height from top level of the n —column to the ground not greater than 6.6 m in the intensity of I~ WI. 3. Buildings with « spen not greater than 12 m and an elevation at top of the column is not greater than 4.5 min the intensity of I 8.2.2 Plan and elevation layout of «factory building should be in accordance with the related provisions as set forth in section 8.1, but installation of the seismic joint should comply with the following requirements 1. A seismic joint need not be installed in a factory building with a light-weight roof 2. A seismic joint should be installed between the factory building with reinforced concrete roof and the annex building, and width of the joint may be taken ‘a8 50~70 mm. Note: Lightowei lightoweight stel troses, corrugated iron sheets or asbestos tiles. roof mentioned in this section refers as wood roof and other roofs with 8.2.3 Structural system of a factory building shall be in accordance with the following requirements 1. Light-weight roof should be used in intensity VI - Wand shall be used in intensity I 2. Cross-shaped section may be used for unreinforced brick columns in the intensity of Vand Wi composite brick columns shall be used at category I and Il sites in the intensity of Wi composite brick columns and reinforced concrete columns should be used for exterior and middle columns respectively at category fl and IV sites in the intensity of Hand all sites in the intensity of IK 3. Shear walls, subject to longitudinal seismic action and of the same height as the column, may be installed between brick columns in the longitudinal row of factory building. Brick shear wall shall be Isid zigzag in courses with the brick column and shall have # foundation. A through horizontal compression member shall be placed on top of the column withou brick shear walls in the building with a reinforced concrete roof sith puslins at estogory Ml and IV sites in the intensity of W. 4, Bearing gable walls shall be installed at both ends of the building 5. Transverse interior partition walls should be made as shear walls. Light- ‘weight walls should be used as non-bearing partition walls. When lightweight walls ‘are not used, additional seismic shesr induced by the partition wall on the column and its connection joine with the roof truss shall be considered : 4m (IL) Essentials in calculation 8.2.4 Seismic checking for single-span buildings and multi-span factory buildings ‘of equal heights. with gable walls at both ends, and clevation of the column top of which is not greater than 4.5m, may not be carried out at category 1 or Il sites in the intensity of W, but the conseructional measures for these buildings shall comply with provisions as set forth in this section. 8.2.5 The following methods may be used in the seismic calculation of factory buildings in transverse direction: 1. Fectory buildings with a light-weight roof may be calculated as planar bent. 2. Factory buildings with a reinforced concrete roof may be celculated as planar jal action, and the seismic action effect should be adjusted as set bents cosidering sp forth in Appendix E. 8.2.6 Longitudinal seismic computation for # factory building may be carried out swith reference to the related provisions as set forth in Section 8.1 based on the type of the roof structure 8.2.7 Transverse seismic computation for the truss-type reinforced concrete skylight frame with diagonal web members projecting on the roof may be conducted with reference to the provisions specified in Article 8.1.11 in this chapter, 8.2.8 Seismic checking of brick columns subject to eccentric compression shall conform to the following requirements: 1. Overall eccentricity of non-reinforced brick columns, produced by the standard value of seismic action and the representative value of gravity load should not exceed 0.9 times the distance from the centroid of the cross section to the edge of the section in the direction where the vertical force exists: seismic adjusting coefficient for load capacity may be taken as 0.9 2, Reinforcement of the composite brick column shall be determined by joni seismic adjusting coefficient for load capacity in this case may be taken as (IL) Constructional measures 8.2.9 Arrangement of bracing in a wood roof should be in accordance with the requirements as set forth in Tab. 8.2.9, and bracing of the roof with steel trusses, corrugated iron sheets or asbestos tiles may be installed according to provisions for a roof without sheathings as set forth in Table 8.2.9; bracing shall be connected with atthe roof truss and the skylight frame by bolts. jgement of Bracing in 2 Wood Roof Ta yee a | oe | oo fe Hato] wan | AEE | TEA | oat sere srieh| peshngs One re ne noite 8 | Ono. aed "8 | ad ite in the nd | One so ited in teoe yar torh | the second inp — wh fie aft | both nah of « unt Thaceg on | Same ts inthe | ahylat tutte [ithe bung snd MO | ecient, || Sung | 20m" nea =a or i meme vio] seat oa ‘building teow Taste Ee bie So er | see tennmeane [nm oy se Sect often chord in added oe ‘One no. installed in the fiest bay at Tracing ox | One noid in the Get by a bth racing} bth sides | ends ofthe hyiht ofl sean State Traverse Trvme’ | bracing’ en | For hgh of coserale rg apn rte arangeren fring forthe (he appr | wo ame mathew age Sek"ende of the shat an ‘eral of 20 m 8.2.10 Constructional measures for reinforced concrete roofs shall conform to the related provisions as set forth in Section 8.1 11 A poured in-situ closed ring beam shal be placed slong the exterior wall and the bearing interior walls at the top of the column in a factory building. In the 2 — intensity of Wand Kt, a ring beam shal be also added at an interval of 3~4 m along height of the wall. Depth of the ring beam shall not be less than 180 mm and its reinforcement not less than 4812. Foundation ring beam shall also be installed, when the subsoil is weak cohesive soil, liquefaetion-potential soil, newly filled soil or a ‘ously non-uniformly disteibuted soll layer. 8.2.12 A poured in-situ reinforced concrete beam shall be placed on the gable ‘wall along the roof level and anchored with the roof members. Cross-section area and reinforcement of the buttress of the gable wall should not be less than those of the bent column respectively. The buttress shall be equal in height with the gable wall land connected with the beam on the gable wall or other roof members. 8.2.13 The ring beam on top of the wall or bearing plate on top of the column shall be connected firmly with roof truss (beam) by bolts or welding. Thickness of the bearing plate on top of the column shall be not less than 240 mm, and two layers of reinforcement mesh with a diameter of not less than #8 and spacing not greater than 100 mm shall be placed on the plate. The ring beam on top of the wall and the bearing plate on top of the column shall be poured at the same time. In the intensity of I, spacing of stirrups in the ring beam shall be not greater than 100 mm, and arranged in a distance of 500 mm on both sides of the bearing plate 8.2.14 Span of the hyperbolic brick arch should not be greater than 15m, 12m, and 9'm in the intensity of VI, Wand IX respectively. Tie bars shall be installed at the foot of the arch and anchored in the reinforced concrete ring beam. Hyperbolic brick arch structure shall not be used when the subsoil is weak cohesive soil, liquefactiompotential soil, newly filled soil or a seriously non-uniformly distributed soil layer. 8.3. Single-story steel factory buildings (1) General 8.3:1 This section is applicable to single-story factory buildings with singl for inultispan of equal height and bearing steel columns and roof trusses Requirements of the plan layout and reinforced concrete roof may be refered to the provisions as set forth in section 8.1 8.3.2 Structural system of the factory building shall conform to the following requirements! 1. Rigid frame or frames, the trusses of which is firmly connected with the ecolumns, should be used in the transverse direction of the building. 2. Overall stability and local stability of the structure and members of the factory building shall be ensured. ‘3. Welding joint of members shall not be located in the maximum stress zone where plastic hinge may occur. 4. Damage to joints, such as bracing joints, connection joints at column foot ‘and joints of the roof truss and the column, shall not occur prior to yielding of the whole cross section of the member: '5. Bracing members shall be made of material in a whole piece. 18.3.3 Enclosing wells of a factory building shall be in accordance with the following requirements? 1. Precast reinforced concrete panels or light-weight panels, flexibly connected the column, should be used as enclosing walls in the intensity of Wh and Wy however filled brick walls shall not be used. If masonry enclosing walls are used in the intensity of W, measures shall be taken s0 that the wall does not prevent the horizontal displacement of column rows in the longitudinal direction 2. Light-weight panels should be used as enclosing walls in the intensity of (CI) Essentials in calculation {8.3.4 In the calculation of seismic action for factory buildings, the weight and stiffness of enclosing wall shall be in accordance with the following provisions 1. Overall weight of the val shall be considered for light-weight panels or precast reinforced conerete panels, flexibly connected with columns, but effect of stiffness may not be considered 2. Overall weight of unit masonry enclosing walls, not preventing the horizontal displacement of column rows in the longitudinal direction, may be considered only in the seismic calculation in transverse direction, and effect of stiffness may not be considered in the seismic calculation in both longitudinal and transverse directions 3. Overall weight of unit masonry walls intimately close to the column end tied with the column shall be considered, but only 40% of stiffness in the direction parallel to the wall shall be considered in the caculation, 8.3.5 The following methods may be used in the seismic calculation of a factory in transverse direction: 1. Factory buildings with light-weight panels or large-size pinels, flexibly connected with the column, may be calculated as planar bents when the columns are a buil ‘ t t uniformly spaced. ‘The roof deformation should be considered, when the spacing of columns is not uniformly spaced. Therefore, spacial action analysis should be performed considering the roof deformation. 2. Calculation for the factory building with unit masonry enclosing walls may be carried out with reference to Artie 8.1.9 8.3.6 The following methods may be used in the seismic computation of a factory building in longitudinal direction? 1. Factory buildings with light-weight panels or large-size panels, flexibly connected with the column, may be calculated as single-mass system, and distribution of seismic action to rows of column shall be determined according to the following principles? 1) Seismic action may be distributed in proportion of the stiffness of rows of column for buildings with a reinforced conerete roof without purlins 2) For buildings with a light-weight roof or a reinforced concrete roof with purlins, seismic action may be distributed in proportion of the representative values of ‘gravity fond subjected by rows of column or by calculation based on an individual row cof column, whichever is greater shall be used 2. Longitudinal seismic action for buildings with unit masonry enclosing walls laid close to the column may refer to the provisions specified in Article 8.1.10. 8.3.7 Similar sectional area may be taken for diagonal rods in the longitudinal and transverse horizontal bracings on the upper and lower chord of the roof truss, and the straight compression member may be designed by using the same strength as the diagonal tension member. Load capacity of the bracing joint shall not be less than the capacity of the member, calculated on the basis of the yielding strength of the whole cross-section; sectional area of the diagonal member of the vertical bracing at the end ‘of the roof truss, and in the middle of the span, may be taken as 1.2 times that of the diagonal member'of the horizontal bracing. CHL) Construction measures 8.3.8 Arrangement of bracing for roofs with purlins should be in accordance with the requirements as set forth in Tab.8.1.15 8.3.9 Slenderness ratio of the column shall not exceed the values as set forth in Tab.8.9.9. 8.3.10 Ratio of width to thickness ofall limb plates of the column cross-section shall not exceed the values as set forth in Tab.8.3.10 in the intensity of I 86‘Table 8.3.9 Maximum Slenderness Ratio of the Column q Steel grade <0.20 720.20 (0285(Grede 3) 120 150(1- 0) 16M 16M steel 100 12001-») Note i the ratio of design vale of combined axial compression and lond cxpacty of steel columns scalulated on the basis ofthe yielding strength 8.3.11 Appropriate meesures shall be taken at the column foot to prove trans: mission of internal force of the column, calculated on the basis of the yielding strength of the whole cross-section 8.3. 12 Cross welding seam shall be strictly prohibited for use in welding members. ‘Table 8.3.10 Maximum Ratlo of Witdth to Thickness of Restraint condition and location Steal grade r [ewes on both sides Renting on bo sien ee om one side) (Upper column) (Lower column) (@235(Grade 9) 2 70 6 16M, 16a see! 10 8 «6 86 9. Single-story spacious buildings 9.1 General 9.1.1 This chapter is applicable to public buildings composed of a considerable spacious hall with a single story and annex buildings, such as cinemas, theaters, clubs, auditoriums, and cafeterias. 9.1.2 Seismic joint should not be installed between a hall and its lobby or back hall, and also may not be installed between a hall and its annex buildings on both sides, but their connection shall be strengthened. 9.4.3 Reinforced concrete structure shall be used for the hall in a single-story spacious building in the intensity of IC. Also, reinforced concrete structures should be used for the hall in the following eases? 1. Having @ canopy, or with a span-greater than 21 m, or elevation at the column top of which is grester than 10m, in the intensity of Wh 2. Having « canopy, of with a span greater than 18 m, or elevation at the column top of which is greater than 8 m, in the intensity of 9.1.4 For other requirements for the hall , refer to the provisions specified in Chapter 8 . The annex buildings shall conform to the related provisions as set forth in this code. 9.2 Essentials in calculation 9.2.1 In the seismic calculation of single-story spacious buildings, the building may be divided into several separate units, such as the lobby, the back hall, the hall, and rooms on both sides of the hall. The calculation may be conducted secording to related provisions as set forth in this code, but the interaction effect of these units shall be considered 9.2.2 In the determination of the natural period of the single-story spacious building, the effect of the spacial integrality action of the roof and the effect of the annex buildings shall be considered 9.2.3 Seismic calculation in the transversal direction for single-story spacious buildings should be in accordance with the following principles? 1. For the hall without ennex buildings on both sides, a typical bay may be selected for calculation from the part of building with a canopy and the part without ¢ canopy respectively. If the building is in accordance with the provisions as set forth in Chapter 8, space action may also be considered 2. In the case of a hall with annex buildings on both sides, appropriate acalculation methods shall be selected, according to the structural type of the annex buildings. 9.2.4 Standard value of the horizontal longitudinal seismic action of the hall in a single-story spacious building may be evaluated as follows? Fra dain (9.2.4.) where Fin—standard value of the horizontal longitudinal seismic action on the Jongitudinal wall or the row of colums on one side of the hall ra —representative value of equivalent gravity load, including half of the ‘weight of the roof of the hall and that of the annex buildings , 50% of the standard value of snow load and reduced weight of the longitudinal wall of the row of columns on one side 9.2.5 Scismic checking of out-of-plane cross section shall be carried out for the buttress of the large gable wall in the intensity of Wand IX 9.3 Constructional measures 9.3.1 Roof detail of the hall shall be in accordance with the provisions as set forth in Chapter 8 9.3.2 Composite brick columns should be adopted instead of brick columns for a hall, and reinforcement in the column head shall be anchored in the reinforced concrete ring beam beneath the roof trusst longitudinal reinforcement in the composite column shall be determined by calculation, and shall not be less than 412 and 6414 at category Il or IV sites in the intensity of VI, or all sites in the intensity of W, and not less than 6614 in the intensity of Wand IX forall sites. 9.3.3 Transverse walls in the stage shall be in accordance with the following requirements? 1. Constructional columns or reinforced concrete columns shall be installed on the two sides of the transverse wall and at both ends of the wall in front of the stage. 2. Reinforced concrete beam shall be installed on the transverse wall along the roof of the hall, and depth of its eross section should be not less than 180 mm. The beam shall be reliably connected with the roof members. 3. Steuts shall be installed at intervals of 4_m on the bearing wall above the sirder in front of the stage in the intensity of to WI. Also, wall beam shall be placed slong the height of the wall at 3 m interval. Cross section, reinforcement content, and connection of the strut with the wall shall conform to the requirements for constructional columas in multi-story unit masonry buildings. 44. Brick wall on the girder in front of the stage should not be used for bearing ro Aoads in the intensity of DC 9.3.4 A poured in-situ ring beam shal be placed at the top of the column (wall) of the hall, and an additional ring beam should be placed at an interval of about 3 m along the height of the wall. When height at the end part of the trapezoid-shaped roof truss is greater than 900 mm, a ring beam shall be added also at che elevation of the upper chord, and its depth of cross section should be not less than 180 mm, and ‘width should be the same as thickness of the wall. Its reinforcement content shall ot be less than 4912. Stirrup spacing should not be greater than 200 mm 9.3.5 When no seismic joint is installed between the hall and the ennex building, 1 closed ring beam shall be placed at the same elevation and tied at the connection of the hall and the annex building. 2416 tie bars shall be installed at the connection of walls at 500 m interval along the height of the wall, and the bars should extend into the wall not less than 1m on both sides. 9.3.6 Cantilever canopy shall be reliably anchored, and measures shall be taken to prevent overturning of the canopy 9.3.7 Reinforced concrete beams shall be placed on the gable wall along the roof and shall be tied with the roof members. Constructional columns or composite brick Columns shall be installed in the gable wall, the cross section area and reinforcement content of which should not be less then those of the bent column or brick column in the longitudinal wall . These columns shall extend to the apex of the gable wall and be connected with the beam on the gable wall 9.3.8 Operation platform or floor diaphragm shall be used for the horizontal bracing of the large gables connected with the back wall of the stage, and at the junction of the hall and the lobby. ro10. Earth, wood and stone buildings 10.1 Earth buildings in villages and towns 10.1.1 This scetion is applicable to buildings with bearing adobe, lime-earth and rammed earth walls, as well as earth caves and earth arch houses in the intensity of Virol Note: 1, Limeearth walls refer to walls made of earth added with lime (or other cementitious matetals) and walls made of edobe added with tim 2. Earth caves include both caves cut from undisturbed earth cif and caves with an rch ro! laid by adobe 10.1.2 Earth buildings should be of one story only. In the intensity of Vand W, buildings with lime-earth walls may be of two stories, but total height of the building shall be not greater than 6 m. Height of the single-story earth building from the ‘ground surface to the eave should be not greater than 2.5 m , and span of a room not greater than 9.2 m. Clear span of the earth cave should be not greater than 2.5 m. 10.1.3 Transverse wall shall be installed in each bay of an earth building. Beams shall not be laid on earth wells without bearing plate. Bearing walls made of different kinds of material should not be used in the same building 10.1.4 Light-weight roofing materials shall be used. Double-slope roof or arch- shaped roof should be adopted for buildings with bearing gable wall. On the wall, bearing wood plate shall be installed to support purlins. On top of the wall, ring ‘beam or bearing wood plate shall be installed. Purlins on gable wall shall extend out ‘of the wall, Purlins on the interior wal shall be overlapped entirely or connected with ‘wood plates or swallow-talied connection shall be used. Members of the wood roof shall be connected with each other by nails, clevis pin and lead wire 10.1.5 Interior and exterior earth walls shall be laid alternately or rammed in each layer. Ia the four corners of the exterior wall and the intersection of the exterior wall end the interior wall, @ layer of tying materials, ©. g., bamboo bundles, or branches of trees or twigs of the chaste tree, should be laid at an interval of 300 mm along height of the wall. 10.1.6 Foundation of all types of earth buildings shall be rammed firmly and a ‘water-proof layer should be put beneath the wal. 10.1.7 Adobe should be moulded by wet-provess, using cohesive soil as raw ‘material and straw and reed shall be added in the soil as tying materials, Adobe shall be laid horizontally, and mud paste or mud-lime mortar should be used in laying 90 walls, 10.1.8 Ring beam shall be installed in each story of buildings with lime-earth walls, and shall pass through sll transverse walls, A step-wise buttress should be added at each side of the gable wall up to the top of the interior longitudinal wall. 10.1.9 In earth-arch buidings, the multi-span arch structure shall be arranged continuously. Each arch shall be supported on the stable ground or earth wall Thickness of the arch should be 300~ 400 mm. The arch shall be laid by use of formwork and not be laid by inclined laying method without formwork. Above the exterior bearing wall and on top of the arch, no doors or windows shall be installed. 10.1.10 In the construction of earth caves, sites where land-slides or slumping are liable to occur should be avoided. Soil of the earth cliff, {rom which the cave is cut, shall be dense and stable , and the cliff shall be smooth in slope, with no ‘obvious vertical joints. In front of the cliff cave, no adobe wall or walls of other materials should be laid as the front wall. Caves at differnt elevations should not be made, otherwise sufficient spacing shall be kept for such caves, and they should not be in line vertically 10.2 Wood buildings in villages and towns 10.2. 1 This section is applicable to buildings with mortised wood frames, buildings with wood trusses and wood columns , and buildings with wood columns and wood beams. 10.2.2 Irregular configuration shall be avoided in the plan of wood buildings. In 1 building, wood columns and brick columns or walls shall not be used simultaneously for bearing purpose. 10,2. 3 Buildings with wood trusses and wood columns and buildings with mortised wood frames should not exceed two stories, and total height of the building should not exceed 6 m. Buildings with wood columns and beams should be of single- story, and the height of the building should not exceed 3 m. 10.2.4 Three-bay wood frame with four columns should be used for spacious buildings of considerable large span, such 3 auditoriums, theaters and’ cereal warehouses 10.2.5 Arrangement of roof bracing of the wood truss shall be in accordance with, 3 8.2 , but the roof bracings on both ends of the building shall be installed in the end bay. 10.2.6 Top of the column shall be mortised to the lower chord of the truss and connected by means of clevis pin. In the intensity of Wand IX, foot of the column a the related requirements as set forth in sectshall be anchored in the foundation by use of iron parts 10.2.7 Diagonal bracing shall be installed between the wood columa and the truss (or beam) in a spacious building. Diagonal bracing shall be installed also in ‘non-seismic partition walls in houses with considerable transverse walls, Bracing need rnot be used in buildings with mortised wood frames. Diagonal bracing should be ‘made of wood plates and extend to the upper chord of the truss. 10.2.8 In the longitudinal direction of buildings with mortised wood frames, = piece of wood shall be installed at both the upper and lower ends of the wood columns passing through and connected with the other columa, and 1~2 diagonal column braces shall be installed in each row of columns in the longitudinal direction. 10.2.9 Diagonal braces and bracing members of the roof shall be connected with main structural members by bolts. Except for the mortised members, other wood ‘members should be connected by bolt. 10.2.10 Enclosing wall shall be tied reliably with the wood structure. Enclosing walls laid by adobes or bricks should be placed on the exterior side of wood column: land the wood columns shall not be enclosed completely by the wall 10.3. Stone buildings 10.3.1 This section is applicable to buildings with regularly coursed rubble bearing walls or randomly coursed rubble bearing walls (with or without bearing stone plates) Inid by mortar in the intensity of I~. 10.3.2 Height of each story of multi-story stone'buildings should not exceed 3 im, and the total height and the number of stories should not exceed the values as set forth in Tab 10.3.2: ‘Table 10.3.2 Limit Value for Total Height (m)and Number of Stories of Molti-story Stone Building Tatensity W W w Type of wall Touat | No.of | Totat | No.of | Total | No.of aight | stores | tight | storie | height | stories Processed end semisprocessed rubble wall masonry (without| 16 | 5 [| a3 | 4 | 10 | 3 bearing stone pate) Coarse rubble and random rubble wall masonry (with| 19 | 4 | x | 3 | 7 | 2 bes 2 ing stone plate) | { — Note:Determinatiom of the totl eight of the building i specified in the Note of Tab. 6.1.2. 10.3.3 Spacing of seinmic transverse walls in multi-story stone buildings should rot exceed the values as set forth in Tab. 10.3.3. ‘Table 10.3.3 Spacing of Seismic Transverse Walls in Multi-Story Stone Buildings(m) Typect tor and ok ae = i 1 7 Poured iwaitu or precast focareal ee ; 7 oral 10.3.4 Poured in-situ or precast monolithic reinforced conerete floor and roof should be used in multi-story stone buildings. 10.3.5 Seismic checking of cross-section of the rubble wall may refer to section 5.2. Shear strength of the wall shall be determined on the basis of test date 10.3.6 Reinforced concrete constructional columns shall be installed in the following positions in multi-story stone buildings 1, Four corners of the exterior wall and the staircase 2. Intersections of interior and exterior walls in every other bay in the intensity of Wand WE, and in esch bay in the intensity of 10.3.7 Horizontal sectional area of the opening in a seismic transverse wall shall bbe not greater than one third of the total sectional area. 10.3.8 Ring beams shall be installed on the longitudinal and transverse walls in each story, the height of the eross section of which shall not be less than 120 mm, and the width should be the same as the wall thickness. Longitudinal reinforcement in the beam shall be not less than 410, and spacing of stirrups should be not greater than 200 mm 10.3.9 At the intersection of the longitudinal wall and transverse wall , where no constructional columns are installed, bonders without bearing plates inserted shell be laid, and tying steel mesh shall be laid at an interval of about S00 mm along the height of the wall. Extended length of the mesh in the intersection of walls on each side should be not less than 1 m. Pafort 10.3.10 For other related constructional requirements, refer to provisions as set Chapter 5 11. Chimneys and water towers 11.1 Chimneys 11.1.4 This section is applieable to ordinary free standing brick chimneys and reinforced concrete chimneys. Reinforced brick chimneys may be used for category Ml cor WV sites in the intensity of WL, and at category I and II sites in the intensity of WE ‘or Wl, when the height of chimneys does not exceed 60 m. Reinforced concrete chimneys should be used for category Mand NV sites in the intensity of W and all categories of sites in the intensity of IX, when the height of chimney exceeds 60 m land also for chimneys of significance. Chimneys at category I snd Il sites in the intensity of VI may be designed according to the related provisions es set forth in the non-seismic design. Note: 1. Chimneys of significance refer to those equivalent to type 1 buildings. 2. Ordinary chimaneys refer to chimneys without atteched water tank, 11.1.2 Seismic checking of cross section need not be carried out for the following. chimneys, but the detail of these chimneys shall comply with the provisions as set forth in this section. 1. Chimneys at category I and Il sites in the intensity of Wf 2. Brick chimneys at category Ml and WV sites in the intensity of MW and at category I and Tisites in the intensity of WL, when the height of chimneys greater than 60 m. 3. Reinforced conctete chimneys at category Ml and IV sites in the intensity of MW, and at category I and II sites in the intensity of W, when the height of chimneys is not greater than 210 m and wind load not less than 0.7 KN/m*. 11.1.3 The following methods may be used in the seismic design of chimneys in the horizontal direction? 1. The simplified methods as set forth in Article 11. 1.4 may be used for chimneys not higher than 100 m. 2. Response spectrum method of the mode analysis should be used for chimneys ion of the first three modes, the first 3 other than those above mentioned. Com 5 modes and the first 5~7 modes may be considered for chimneys below 150 m, between 150~200 m, and higher than 210 m respectively. 11.1.4 When the simplified method is used in the seismic design for free standing chimneys, the following provisions shall be complied with in the ealeulation of action ‘effect induced by the standard value of the horizontal seismic action? 95' ( ' 4 1, Fundamental natural period of ordinary free standing chimneys may be determined by the following equations? i } whei deter where My For brick chimneys not higher than 60 m, T,=0.26 + 0.0024H"/d aaa) For reinforced concrete chimneys not higher than 150 m, T,=0.45+ 0.0011 H*/d (n.a.4-2) se Ty~fundamental natural period of the chimney (s) H—height of the chimney, measured from top surface of the foundation (m)s d—external diameter of the cross section at half height of the chimney shaft (m) 2. Seismic bending moment and shear force at base of the chimney shall be srmined according to the following equations? Mo™ eiGaHlo (1.1.4-3) Vo= qa Qn.1.4=4) bending moment induced by the standard value of horizontal seismic action at the base of the chimney’ a, —horizontal seismic effect coefficient corresponding to the fundamental natural period of the chimney, and it shall be determined as set forth in Article 4.1.43 Gy standard value of the dead load of the chimneys H,— height from top surface of the foundation to the center of gravity of the chimney? V,—shear force induced by the standard value of horizontal seismic action at the base of the chimney’ (odified coefficient of base shear of the chimney from Tab-11.1-4 It may be taken Table 11.1.4 Modified Coefficient of the Base Shear of Chimney Characteristic period Fundamental period, Tals) Tas) os [io [as [20 | 25 | so 0.20 ve | 110 | 110 | 008 | oa | 0.75 0.25 0.78 | 1.00 | 1.10 | 1.05 | 0.95 | 0.85 0.30 0.65 | 0.90'| 1.10 | 1.10 } 1.00 | 0.95 0.40 0.60 | 0.80 | 1.00 | 2.30 | 1.15 | 1.05 0.85 0.85 | 0.70 | 0.85 | 1.00 | 1.10 | 1.10 0.65, 0.85 | 0.65 | 0.75 | 0.90 | 1.05 | 1.10 0.85 0.55 | 0.60 | 0.70 | 0.80 | 0.90 | 1.00 43,Seiamie bending moment and shear force of cross sections of the chimney may [A Ir OTT eal Lt . He \ (©)Sheae Height of the ceoss section in esleulations M; —bending moment of the cross o.28v. (a)Sketch diagram of chimney (b)Bending moment section in calevlation; Vi—sheat force of the calelated cross section Fig. 11.1.4 Distribution of Seismic Action Effect of the Chimney 11.1.5 Vertical seismic action on the chimney shall be determined as set forth in Articles 4.1.1 and 4.3.14 amplificetion factor for the vertical seismic action effect may be taken 35 2.5. 11.1.6 Additional seismic bending moment shall be considered for reinforced conerete chimneys: thermal stress of the shaft wall need not be considered in seismic checking of cross section, but effect of temperature on physico-mechanical properties ‘of materials shall be considered, and seismic adjusting coefficient for load capacity of the chimney may be taken as 0.9. 11.1.7 Minimum requirements of reinforcement in the upper part of brick chimneys shall be in accordance with those as set forth in Tab. 11.1.7, and half of the reinforcenent should extend to the lower parti when there is thermal reinforcement in the masonry shaft, total smount of the hoop reinforcement may be reduced appropriately Me chimneys, and en additional reinforced concrete ring beam should be placed at 2/3 of ‘A reinforced concrete ring beam shall be installed at the top part of brick the ‘otal height in the intensity of WW. Depth of the cross section of the ring beam should be not less than 180 mm, and width not less than 2/3 of thickness of the shaft ‘wall and not less than 240 mm, Longitudinal reinforcement should be not less than 4812, and spacing of stirrups shall be not greater than 250 mm 7Table 11.1.7 Minimum Requirements of Reinforcement of Reinforcement in the Upper Part of Brick Chimneys Intensity end ype of Reinforce: | Category ll and | Category I and | Category Ml and WV sites in intensity ment | V sites in| M sites. in| Wand category I and Il sites in incensryit "intensity nensity “Toa gh when HID RE Rinfowe | From0.8 Hothe top | from 0.4 H to the to, when H> 30 Vertical | Not less than reinforce | 6#8,spacing 500| Not len than 6410, spacing 600700 mm men | ~700 mm Hoop reinlorce #8500 mm #86300 mm 11.1.9 Hook shall be made at the end of reinforcement in brick chimneys. Overlapping length of reinforcement shall be not less than 40 times of the reinforcement diameter. In the overlapping zone, reinforcements should be tied firmly by lead wire; vertical reinforcements passing through the chimney shall be ‘anchored in the ring beam on the top, while those not passing through the chimney ‘shall be anchored in the holes made in advance in the wall, which shall be filled with mortar after placing the reinforcement. 11.1.10 Seismic resistant joint shall be made between the reinforced concrete chimney and the smoke flue, the width of which shall be in accordance with the following requirement 1. 50 mm may be taken as the width when height of the smoke flue is not higher than 15m 2. When height of the smoke flue exceeds 15 m,# value of 15 mm should be added to the width of the joint for every 5 m,4 m;3 m,and 2 m increase in height, corresponding to intensity Vi, Wh, Wand IX respectively 11.2 Water towers 11.2.1 This section is applicable to ordinary free standing water towers. Water oe : towers with a capacity not greater than 20 m? may be supported by brick columns at category I and Il sites in the intensity of Wf and W respectively: while water towers ‘with a capacity not greater than 50 m® may be supported by a brick cylinder shaft at all sites in the intensity of Wand Wand st category I and | sites in the intensity of WE reinforced concrete water tower or steel water tower should be used at category I andNV sites in the intensity of WE and at all categories of site in the intensity of I and for water towers of significance 11.2.2 Seismic checking of eross section of the following members in s water tower need not be carried out, but they shall be in accordance with the constructional requirements in this section: 41. The water tank of the tower , but not including the lower ring beam of the tank, supported by the tower frame at category II and IV sites in intensity Wl and at all categories of sites in intensity IX 2. Reinforced concrete supporting frame: shaft wall of the tank with a capacity less than 50 m*, supported by a brick cylinder shaft, not higher than 20 m + columns and beams of the tank with « capscity less than 20 m? and not higher than 7m supported by brick cloumns, at category I and Il sites in intensity WI 3. Reinforced conerete cylindrical shaft well supporting the tank at all categories of sites in intensity Wand at category I and If sites in intensity W 11.2.3 In seismic checking of cross section of the tank, both full losd and no load conditions shall be considered. For frame-supported tanks and polygonal tanks, checking shall be cerried out in the normal and diagonal directions respectively. Calculation of vertical seismic action for relatively high water towers may refer to Article 4.3.1 11.2.4 The following methods may be used in the seismic calculation for water towers in horizontal dreetion: 1. For frame-supported water towers and other similar water towers, the base bending moment induced by the corresponding standard value of horizontal seis action may be determined according to the following equation? M,= eG. faGe) He (1.2.4) where M, —bending moment induced by the standard value of the seismic action at the base f a water tower! mncal seismic effect coefficient corresponding to the fundamental natural period of the water tower} it shall be determined according to Article 4.1 the representative value of gravity load of the tank? i¢ shall be 9determined according to Article 4.1.3 5 equivalent coefficient of bending moment; it may be taken as 0.35 for bearing structures with equal stiffness, and it may be appropriately reduced for bearing structures with varied stiffness, but shall be not less than 0.25; Gu-representative value of gravity load of bearing structure and attached platform of the water towers H.height from top surface of the foundation to center of gravity of the tank. 2. The base shear method may be used for relatively low tanks supported by a cylinder shaft. 3. The response spectrum method for mode analysis may be used for a relatively high water tower supported by a brick cylinder shaft or for water towers in which the ratio of height to diameter of the shaft is greater than 3.5. 11.2.8. Integrated foundation or ring-shaped foundation should be used for foundation of the water tower supported by columns at category [l ~ IV sites. Foundation tie beans shall be used for the connection of isolated foundations. 11.2.6 Water towers supported by a reinforced concrete cylinder shaft shall comply with the following constructional requirements? 1. For vertical reinforcement in the cylinder shaft wall, diameter of the reinforcement shall be not less than $12, spacing not less than 200 mm, and ‘overlapping length not less than 40 times of the reinforcement diameter. Overlapping locations shall be placed alternatively. Number of joints of reinforcement in the same horizontal cross section shall be not more then 1/4 of the total number of reinforcement. 2. Reinforced concrete portal frame should be installed for the door opening at the lower part of the eylinder shaft 3. Reinforcement for strengthening purpose, not less than 2412, shall be placed surrounding the sides of the window openings of the cylinder shaft 11.2.7 Frame supported reinforced concrete water tower shall be in accordance with the following conctructional requirements 1. Transverse beams of the frame shall have considerable large stiffness, and the stirrups in the beam shall be closed and comply with requirements as set forth in clause 1 of Article 6.1.17 , and the spacing of stirrups shall be not grester than 200 mm. Also, spacing of stirrups at the end of the beam, in a range equal to depth of the beam, shall be not greater than 100 mm 100 2. Within a zone of 800 mm, below the bottom of the tank and a zone of 800 mm above top surface of the foundation, as wel asin a zone above and under the joint of the beam and the column with a distance equal to width of the column, but not less then 1/6 of the elear height of the column, stirrup spacing of the column shall be not greater than 100 mm stirrup diameter of the column shall be not less than #8 in intensity Wor Ik '3, Brackets shall be added at ends of the ring beam under the tank and of the transverse beams. For water towers higher than 20 m and in intensity WH or IK, « horizontal reinforced concrete diagonal bracing should be install at an intervals of ‘about 10 m along elevation of the tower, and cross section of the brace should be not less than that of the column of the suppoting frame. 11.2.8 Water tank supported by a brick eylinder shaft shall be in accor the following constructional requirements? 1. Reinforcement content in the brick cylinder shaft wall shall be determined by calculation, and the reinforcing zone and minimum reinforcement content shall be in ice with accordance with the requirements as set forth in Teble. 11.2.8 ‘Table 11.2.8 Requirements for Reinforcement of the Brick Cylinder Shaft Wall __Brick Cylinder Shaft Walt category of i Gatenory Hf and W aives in the intensity of W end category 1 and Tl sites in the intensity of sites in the intensity of W a Category V sites in the intensity ‘of Wand category I and It Reinforcement Height of the | From the bottom 190.6 Hof the | 5 ight ofthe shaft teinforcing one | shalt Vera Not less than 6412, spacing $00 | Not less than 6412, spacing $00 reinforcement in |W ee the masonry Reinforcement in | 1912 for each channel, spacing | 1414 for each channel, spacing the vertical | 1000 mm, and not less than 6 {1000 mm, end not less then 6 channel 0 ro. Hoop reinforce $8, spacing 360 mm #8, spacing 250 mm2. Overlapping and anchorage of reinforcement of the shaft wall shall be in accordance with Article 11.1.9. 3. Not less than four constructional columns should be installed in the cylinder shaft wall at category land IV sites in intensity Wand at category I and [sites in intensity WL, and cross section of the constructional column should not be less than 240 ‘mm X 240 mm. Other detail requirements shall be in accordance with Article 8.3.2, 4. Ring beam should be placed at an interval of 4 m along the height of the shaft, and the depth of the cross section of the beam should be not less than 180 mm, width not less than 2/3 of thickness of the shaft wall, and also not less than 240 mm, ‘The longitudinal reinforcement content shall be not less than 4#12, and stirrup spacing of which not greater than 250 mm. 5. Reinforced concrete ring beams shall be installed at the upper and lower bounds of the door opening in the lower part of the brick shaft . Reinforced concrete ‘or brick door frames should be installed at the two sides of the door opening’ as for cother openings, 348 steel bars shall be placed at both upper and lower bounds of ‘openings. Also, length of both ends of the bars, extending into the shaft wall, shall be not less than 1 m. 102 Appendix A Glossary of terms intensity of « region denotes the maximum seismic intensity, probably encountered in the region in a certain future period under ordinary site conditions, ic. the intensity specified in the current "Chinese Seismic Intensity Zoning Map”. basis for Eortification intensity is the intensity, approved by the State authority, the fortification of buildings in a region against earthguake Site is an area approximately equivalent co a factory ares, 8 residential area or a village, where a specified building exists. Sites of the same category shall have similar response spectral characteristics. fis the statistical average value of the ratio of maximum Selsmic effect coeffick acceleration response to gravitational acceleration of the single-mass elastic structure under an earthquake action, Design near-earthguake and design far-eathquake are design earthquakes classified according to the focal distance in the same fortification intensity. When the fortification intensity is IK and above, only near-eerthquake is considered. Representative value of gravity load in selsmle design represents the sum of standard value of permanent load on the structure or member and combination value of related varied loads, in the fundamental combinstion of calculation of the standard value of seismic action and effect of the structural member action in the seismic design Combination value coefficient is determined on the basis of the combination probability during an earthquake. Adjusting coefficient for seismic action effect is the coefficient used to adjust the seismic action effect (bending moment, shear, axial force , and deformation) in the design of structure or a member, considering the effect of simplification of the structural model in calculation, and redistribution of elasto-plastic internel forces or other factors in the seismic analysis 103Appendix B Seismic checking of cross section in the core zone of frame joints B.1 Design value of shear force Design vale of shear force combination in the core zone ofa joint in a freme shall be determined by the following equations? 1.05 Muacy _ hse Tite ae Oh 1.054j3Msyy _ htve~ a: e - oi Rta OH For grade 1 structures? V) : L055 May hi . For grade 2 stuctures!—V, = 4082 My Fe -2) fon in a core zone of the joint j+ Where Vj-design value of shear force combi hueffective depth of the beam cross section’ if depths of cross section of the beam on both sides of the joint are unequal, the average value may be taken’ ‘aj-distence from the resultant of the compression reinforcement of the beam to the compression zone edge’ He-caleulated height of the column. The distance between the reflection points of columns above and beneath the joint may be taken as the caleulated height? iy—eross section depth of the beam: if depths of cross-section of the beam on both sides of the joint are unequal, the average value may be taken, B.2 Width for the checking of cross section in the core zone. 1. When cross section width of the besm in the direction of checking is not less than 1/2 of the eross section width of the side column, the cross section width of the column on that side may be taken as the width for the checking of cross section in the core zone} when itis smaller than 1/2 of the cross section width of the column, the smaller value of the results obtained by the following equations may be taken: By 0.5 he (B-3) Babe (B-4) where b/— width for the checking of cross section in the core zone of a joints C ‘he cross section depth of the columa in the direction of checking cross section width of the beams {b,— cross section width of the column in the direction of checking. 2. If the center line of a beam does not coincide with that of a column, the smaller value of the value obtained in clause | and that determined by the following equation may be taken as the width for the checking of cross seetion in the core zone? b,=0.5(bs + b,) +0.25h,—€ (B-5) where e— the eccentric distance between the center lines of the beam and the columa B.3 Seismic checking of cross section Following expressions shall be used in seismic checking of eross section in the core zone of joint J? Visziy (0.3 nfs) 8) he VSL (OA pfibhs 0.19 Bt SrA where 4)—the restraint effect coefficient of eross beamsi1- may be taken as gif B-7), cross section width of each beam on the four sides is not less than 1/2 of cross section width of the column on that side and, also, depth of the secondary beam is not less than 3/4 of that of the major beamior 1.0 may be taken as 7, for other casesi 1h, —eross section depth in the core zone of joint j, and the cross section depth of the column in the checking direction may be taken as yi 1 seismic adjusting coefficient for load capacity, 0. 85 may be taken as jal compression of the upper column corresponding to the design value ‘of shear combination, and its value shall be not greater than 50% of the pfoduct of sectional area of the column and design value of the concrete compressive strength Jodesign value of tensile strength of the stirrup: ‘Avg —total sectional area of limbs of stirrups in the same direction in the range cof checking width in the core zone. s—spacing of stirrups. 10sAppendix C Seismic checking of frames with filled brick walls C1 Lateral drift stiffness If lateral resistance is considered in frames with filled brick walls, the lateral drift stiffness may be determined by the following equations: Kier Kit Ke (ca) Ky 7 3 BBels/ [Hi pe + Wed) (cay OnL/ALHE (ca) where Kie—lateral drift stiffness of the frame with filled wallst K,—total lateral drift stiffness of the framet K.—total lateral drift stifiness of the filled walls, but Kw is not considered {or filled walls, when the ratio of opening area in the wall to the wall surface area is greater than 60%} dar-stifiness reduced coefficient:1.0,0.6 and 0.3 may be taken as gx for the upper, middle and lower stories respectively: stories of the building may be divided into three approximately equal parts as upper, middle , and lower stories: E,—elasticity modulus of the filled brick wall H—height of the filled brik wall: y—shear effect coefficient: ‘Ac, [horizontal sectional area and moment of inertia of the filled wall respectively: if opening exists in the wall, the sum of the corresponding values of the wall on both sides of the opening may be taken (see Fig. C~1, the indices t, b represent top and bottom of the filled wall respectively) ims $—opening effect coefficients; they may be taken as follows! For walls without opening, «4 vn = For wals with opening, hy co goa «-9) (c-8) 108 Ay tt a Fig. C1. Sectional Area and Moment of Inerticof Filled Walls with Opening €.2 Seismic action effect 1. Design value of shear of combination of stories shall be distributed in proportion to interstory drift stiffness of each frame and frame with filled walls, but the design value of shear force, carried by the frame without filled walls, should not be less than the corresponding design value, carried by the part of frame in the frame with filled walls (not including the additional shear induced by the filled wall). 2, In the caleulation of axial compression and shear on the column in the frame with filled walls, additional axial compression and shear force, induced by the inflled ‘wall, shall be considered , and these values may be determined by the following equations: Ni= VeHi/t «-n Vie Ve (c-8) where Ni—design value of additional axial compressive force on the column in the framet Ve—design value of shear force, corried by the filled wall; if filled walls exist on both sides of the column, the greater design value of these walls may be taken as V. story height of the frame I—span of the frames ‘Ve-design value of additional shear force on the column in a frame. C.3 Seismie checking of eross section ‘The following expressions shall be used in seismic checking of eross section of a frame with filled walls Vues BM i+ Mie) /Het 5 Fare SfetAwe cs) 1070.4 Vn B(Min* MhY He (C10) where Vie-—design value of shear force carried by the frame with filled walls: Jardesign value of seismic shear strength of the brick wall: it’ shall be taken in accordance with Article 5.2.43 ‘Aqo—ealculated horizontal cross section area of the brick wall; 25 times the actual sectional area may be taken as Ay. for walls with no opening, ‘while the net sectional area may be taken a8 Awe for walls with ‘opening, but the portion of the wall, the width of which is less than 1/4 of the height of the opening, is not considered; Ms,, Mic—uesign values of load capacity of the normal eross section subject to eccentric compression at the upper end and lower end of the frame column respectively: values ofM3 and Mi, may be taken according to the related equations for non-scismic design as set forth in the current national standard, “Design Code for Reinforced Concrete Structures”, but equal signs shall be used H_—caleulated height of the columnif filled walls exist at both sides of the column, 2/3 of the clear height of the column may be taken as Hetif half filled walls exist at both sides or filled wall exists only on one sidey clear height of the column may be taken as Hei ‘Yauseiamic adjusting coefficient for load capacity of the frame column 0.8 may be taken a5 Yar ‘Yaee—seismic adjusting coefficient for load capacity of filled brick walls; 0.9 may be taken as Yare: 108 Appendix D Seismic design of diaphragm of frame supported story. in shear wall structures 1, Following expressions should be used in seismic checking of cross section of the frame supported floor slab in shear wall structures vic(0-1fed oa) VS /(0.6/,.) (02) where Vreombined design value of shear force in the frame supported slabs transmitted from the shear walls not on the ground to those con the ground bc—width of the frame supported slab; tthickness of the frame supported slabs ‘A,-sectional area of total reinforcements in the frame supported floor (including beams and slabs), passing through the shear walls on the ground ‘Yas—seismic adjusting coefficient for load capacity 85 may be taken as Yee. 2. Frame supported floor slab shall be poured in-situ, its thickness should be not less than 180 mm, grade of concrete strength should be not less than C30. Two layers of bi-axial reinforcement shall be placed in the slab, and steel ratio in each direction shall be not less than 0.25% 3. Boundary beams shall be installed along the edge of the frame supported floor slab and perimeter of the opening. The width of the beam should not be less than 2 times the slab thickness, and longitudinal steel ratio shall be not less than 1%. Joint of reinforcement in the beam should be welded. Reinforcement in the floor slab shall bbe anchored in the boundary beams 4. When the plan dimension of a building is considerably long or irregular shape, of internal forces of shear walls differ considerably, bending capacity in-plane of the frame supported slab shall be checked also. In checking, interaction of the reinforcement in the tension zone of the floor slab and the reinforement in the boundary beams may be considered. 109Appendix E ‘Adjustment of seismic action effect on transverse planar bent in single- story factory buildings B.1 Adjostment of the fundamental natural period In the calculation of transverse seismic action of the factory building, based on planar bent model, fixing effect of the connection between longitudinal wall, roof ‘russ , and column shall be considered for the fundamental natural period of the bent, which may be adjusted as set forth in the following? ‘Table E.1 Adjusting Coefficient for Reinforced Concrete Columns (Except Those at the Intersection of the Higher Span and Lower Span), Considering the Effect of Spacial Action and Torsion Roo enh n) Tye | Gable wat Jesol as | «2 | 48 | s+ | 60 | 06 | x2 | 70 | e | 20 | 96 Beading equ ease |]! (P75 Baadings of seat | 1 | 1 [o.sl.asles. soles oo.ele.seo.e.c0 Botdinas with sale |, oe Beda wit s.15|.20[2.25|10f.20]s90)1.20]1.35.35|1.25|1.98 Boling, whee aslo. aso.so.osfo 91.00. o0]105]1.06]1.10 noatees| eee |! |! aslo 1.05.05). =e] sine wen, [seme fore | oie ath seg | maton eal serge | 1 | 1 fo.sf.soo.1e.cos.00-o}.os oho}. 18 ie ‘ene eadings with » ele |, oo|1o5|, 10-2] 1.16f2.15|1.16|2.20]1.20. 2025] tral tanc end iol1-20ssl1.15.18.20}1.20 2s no 1, For bents composed of reinforced concrete roof truss and reinforced concrete columns of steel columns, 80% of the calculated period value is taken when longitudinal walls exist while 90% is taken when no longitudinal walls exist 2. For bents composed of reinforced concrete roof truss(or composite truss)and brick columns, 90% of the calculated period value is taken. 3. For bents composed of wood truss, stecl-wood truss or light-weight steel truss ani brick columns, the calculated period value is takene 5.2 Adjusti 14 torsion effect 1. In the adjustment of seismic shear and bending moment on bent columns in & cocfficient considering the spacial action singlestory factory building with reinforced concrete roof, fundamental natural period shall be determined as set forth in Article E.1, and shall be in accordance with the following conditions: (1) For intensity Wor Mi (2) When ratio of the roof length to the total span of the factory building unit is less than 8, or total span of the factory is greater than 12 mi (3) When the thickness of the gable wall or transverse wall isnot less than 240 mm (IB), horizontal sectional area of the opening is not more than 50% of the total sectional area of the wall, and the gable wall is well connected with the roof system (4) When the height of the column is not greater chan 15 m. Note: 1). Roof leith refers to the spacing of the gable walls (or tranaverse walls with & Ibeight up tothe top of column) ifthe gable wall (or the transverse walls with heieth up to the top of eolumn) only exists et one end, then the distance from the bent under considerstion to the geble wall (or the transverse wall with # height up tothe tp of ealumn) shall be taken. 2). In factory buildings with unequal-height spans, in which the height ofthe higher span differs considerably with that of the lower span, the total span may not include the span ofthe lower one 2. Shear force and bending moment on the-bent column shall be multiplied by corresponding adjusting coefficients, and the value of adjusting coefficient for reinforced concrete columns. other than those at the intersection of the higher bay and the lower bay, may be taken in accordance with Table E.1 while those for brick columns in buildings with gable walls at both ends may be taken in accordance with Table E.2. m1Table £.2 Adjust the Effect of Spacial Action Diatance between gable walls at both ends (mm) zu] [|] ee] «| | o | 66 | 7 Type of roof Rein *22t | 20 | 0.15 | 0.80 | 0.85 | 0.88 | 0.20 | 0.96 | 0.95 | 1.00 without pules| Reinforced concrete roof with poli 0.75 | 0.80 | 0.90 | 0.98 | 0.95 | 1.00 | 1.06 | 1.05 | 1.10 3. Seismic shear and bending moment determined by the base shear method for the cross sections of the reinforced concrete column above the bracket , supporting the oof of the lower span,in the intersection of the higher span and lower span, shall be ‘multiplied by an amplification factor, which may be determined by the following equat (ey where amplification factor of seismic shear and bending moment {special ection effect coefficient at the intersection of the higher and the lower spansit may be taken in eccordance with Tab. E. ‘iy —number of higher spansi rn. —number of spans for calculationif lower spans only exist on one side, total number of lower spans shall be taken as n.tif lower spans exist on both sides, sum of the total number of lower spans and number of higher spans shall be taken: Gethe representative value of total gra ‘of the roof of the lower spans on one side of th and lower spansi Grx—tepresentative value of total gravity load concentrated at the elevation of the higher span. y load concentrated at the elevation ersection of the higher the column top E.3 Amplification factor for seismic action effect induced by the crane truss Seismic shear and bending moment, induced by the crane truss, on the cross- section of upper column at the elevation of the top of the crane beam in single-story factory buildings with reinforced concrete columns shall be multiplied by the amplification factor as set forth in Tab.E.4, when the simplified method, such a8 the nz bese shear method, is used ‘Table E. 3. Spacial Action Effect Coefficient for the Relnforced Concrete Upper Column in the Intersection of the Higher and the Lower Span hos aon Renta (oD eae no 6 eM Talings with treed con | nble was at | / ooh. amp. 06 an, [tot ee coer wate | abt pia el has = eS a rte rol ith Baia ti ble wall ot 1 ‘Table E. 4 Amplification Factor for Seismic Shear and Bending Moment Induced by the Crane Truss ee ee cotomns | MEMESTOE | clamae allswstain | 2.0 as 20 Reinfornd corte oat |” 7 without putin ‘ole walletone | 1.5 20 25 Reinforced concrete ral ih prion usAppendix F Seismic checking of single-story factory buildings with reinforced concrete columns in the longitudinal direction F. 1 Fundamental natural period in the longitudinal direction In the calculation of seismic action on factory buildings with reinforced concrete columns (single span or multi-span of equal height) in the longitudinal direction, based on this Appendix, the fundamental period in this direction may be determined by the following equations, if elevation of the column top is not greater than 15 m and the average span is not greater than 30 m. 1. For factory buildings with brick enclosing walls, it may be calculated according to the following equation T.=0, 23+0, 00025. VP FD .—roof type coefficient; it may be taken as 1.0 for reinforced concrete roof truss with large-size roof slab, and 0.85 for steel roof trussi span of the factory building (m); the average value of all spans for smulti-span factory buildings may be taken ; ‘H-—distaince from the top surface of foundation to the top of column (m) 2. For open or semi-open factory buildings, or those in which wall panels are flexibly connected with columns, it may be calculated also as set forth in multiplied by the following enclosing wall effect coefficient = 2.6- 0.0021 VIP (F.2) where Ya enclosing wall effect coefficient} if itis less than 1. 0, 1. 0 shall be where se | and taken as g2- F.2 Selemie action on a row of columns 1. In factory buildings with a reinforced concrete roof and multi-span of equal height, standard value of seismic action at the elevation of column top forall rows of columns in the longitudinal direction may be determined by the following equations. (F. 3) (F.4) smic action at the elevation at top of the where F\—standard value of longitudinal ith row of columns: a.—horizontal seismic effect coefficient corresponding to longitudinal fundamental natural period of the factory building: it shall be mu determined as set forth in Article 4.1.4 Ga—representative value of total equivalent gravitional load on row of columns in the building unit; it shal include the representative value of ‘gravity lod of the roof, determined as set forth in Article 4.1.3, 70% fof the weight of longitudinal walls, 50% of the weight of transverse walls and gable walls, and the reduced weight of columns (if crane exists, 10% of the column weight is used: if no crane exists, 50% of the column weight is used) i total lateral drift stiffness of the coluran top of the ith column row, and it shall include the total sum of drift stiffness of the interior columns in the ith column row and that of the column bracings of the upper and lower columns and the reduced lateral drift stiffness of the longitudinal wall; the reduced coefficient for the lateral drift stiffness of the brick enclosing wall, placed outside of columns, may be taken as 0.2~0.6 according to the Isteral drift of row of columns: K.—adjusted lateral drift stiffness of the column top in the # th column row: vorthe enclosing wall effect coefficient for the lateral drift stiffness of row of columns and it may be taken as set forth in Tab. F. 1. For factory buildings with 4 or 5 spans, having longitudinal brick enclosing wall, Prof the 3rd row of columns, counted from the exterior row, may be taken as 1.15 times the corresponding value in Tab-F. Yr the column bracing effect coefficient for the lateral drift stiffness of row of columns, and may be taken as 1.0 for exterior row of columns, when there is brick enclosing wall in the longitudinal direction, and gy of the ‘middle row of columns may be taken as set forth in Tab.F.2 2. Standard value of longitudinal seismic action at the elevation of top of the crane beam on the row of columns in multi-span factory buildings of equal-height spans with reinforced concrete roof may be determined by the following equation’ (F.5) where Fy—standard value of longitudinal seismic action at the elevation of top of the crane beam on the i th row of columns: Gamtepresentative value of equivalent gravity load, concentrated at the elevation of top of the erane beam on the ith row of columns, and it ‘shall include the representative value of gravity load of the crane beam and the suspended items, determined by Article 4.1.3 , as well as 40% of the weight of the column’ us“Ha-the height to the top of erane beam on the ith row of columns: H,-~ the height to the top of the column in the ith row Table F. Enclosing Wall Effect Coefficient ‘Type of encloine Tow felon nd pe of vot Mid row of clan Rat wihon pri Real vik pen ick wll ck a eer z seth forthe | Greuumes | Moakygh in] Wat kylie ] No yt in| Wit by ‘ck | iene ie escerae [inthe esti | she eaerr [in the eatnir 240mm of 370 — ‘on vn ‘oon foam |e 0.5 7 Ls a Le «fe fees [ss ne x Lt wf[o fee [ ne he ie eae oar ems |raeinls |nsft= a ha ne No excting wall. | tema si | ogo | ont ni foe Le Table F. 2 Bracing Effect Coefficient for the Middle Row of Columns in Factory Buildings with Longitudinal Brick Enclosing Wall Namber of bays of celuma with bing etl in hele | lower ont of clan he mide row of lune Senders rai of the digs brace beween the No bscng o_[ am [ania [aim ieo] io Onatoony [ee foe | ro |r | ia a Troclama bey 7)? few pow | F-.3 Seismic action effect on column bracing and its checking 1. Horizontal displacement of the column bracing, the slenderness ratio of the diagonal member of which is not greater than 200, under the action of a unit lateral force may be determined by the following equation: 1 ry (F. 6) displacement at the applied point of a unit later where force: n6 $i—stability coefficient for axial compression on a diagonal member in the # ‘th panel, it shall be taken as set forth in the’current national standard, ‘Design Code for Steel Structures" } relative displacement of the ith panel under the action of a unit lateral force, considering only when the load is subjected by the tie member 2. Cross section of a diagonal member with a slenderness ratio not grester than 200 may be checked only for tension, but the unloading effect of the compression member shall be considered, and the tension may be determined by the following equation: t 4 _y, : NTT pais ae where Ni—design value of axial tension in the checking of tension strength for the diagonal member of the bracing in the ith panel; ‘1.—total length of the inclined brace in the ith paneli ‘unloading coefficient for comprestion members: it may be taken as 0.7, 0.6 or 0.5 when the slenderneds ratio of the member is 60, 100 and £200 respectively ‘y—design value of seismic shear subjected by the bracing in the ith panels s.—elear distance between columns where the bracing is located. 3. For the longitudinal column row without wall laid closely outside the columns, bracing between the upper columns and bracing between the lower columns in the same column row should be designed with the same lateral load capacity. F4 Seismic checking of the anchor bar in the built-in plate at a joint ‘The eross section area of the anchor bar in the built-in plate at the end joint of column bracing may be taken as 1.25 times the value obtained from checking by the following expressions? es en efeasua cra 40000 fF an‘Yay seismic adjusting coefficient of load capacity, it may be taken as 1. 05 N-—diagonal tension of the builtin plate, it may be teken as 1.05 times the axial force of the diagonal member of the bracing , calculated according to the yielding strength of the whole cross section ‘eccentric distance between the diagonal tension and the resultant action line ‘of anchor barsi it shall be less than 20% of the distance between anchor bars in the outer rows? jagonal tension and its horizontal projections ingle between the p—eccentric effect coefficient ‘s—distance between anchor bars of the outer rows (mm)i $a—bending deformation effect coefficient of the built-in plates 1—thiekness of the built-in plate (mm); d—diameter of the anchor bar (mm) {effect coefficient of the number of rows of anchor bars in the checking direction: 1.0, 0.9 or 0.85 may be taken as {for the 2nd, 3rd or 4th rows of anchor bars respectively f.—shear effect coefficient for anchor barsi if itis greater than 0.7, then 0.7 shall be taken, 18 Appendix G Explanation of words in this code L.The following verbal forms are used to indicate different requirements to be followed in the implementation of the code. (2) Verbal forms used to indicate requirements most strictly and unavoidably to be followed: “must”, in affirmative form + “strictly prohibited”, in negative form. (2) Verbal forms used to indicate requirements strictly to be followed, or to be followed in normal condition? “shall”, in affirmative form: "shall not” in negative form (3) Verbal forms used to indicate that. among several possibilities one is recommended to be selected, and to be selected at first when it is allowable? “should” or “may” in affirmative form} “should not” or “need not” in negative form, 2. When provisions are strictly to be followed in accordance with specified standard, code or other related regulations, it shall be written as: “shall be---in As for provisions not strictly to be followed in accordance with specified standard, code accordance with~"-~-" or “shall comply with requirements as set forth in- or other related regulations, it shall be written as? “refer to 9Additional Notes Editor in chief, list of participating organizations and chief members in drafting this code? in Chef China Academy of Building Research ding of this co Institute of Engineering Mechanics (IEM), State Seismology Bureau Beijing Municipal Building Design Institute General Design and Research Institute, Ministry of Mechanical and Electronic Industry China Northwest Building Design Institute ‘Tongji University Northwest Electric Power Design Institute, Ministry of Energy Source Professional Design Institute, Ministry of Railway ‘Academy of Building Research, Ministry of Metall No.6 Design Institute, Ministry of Mechanical and Blectronic Industry 1 Industry Harbin Building Engineering Institute Shanghai Institute of Building Material Industry ‘Sichuan Provincial Acsdemy of Building Research Beijing Municipal Institute of Reconnaissence Tianjin Municipal Institute of Building Design Beijing General Design Institute of Steel and Iron Industry China Southwest Institute of Building Design Xian Institute of Metallurgical Industry Buildings No.2 Design Institute, Ministry of Mechanical and Electroine Industry No.7 Desiga Institute, Ministry of Mechanical and Electronic Industry Taiyuan University of Technology Chinese Overseas University Qinghua University ‘Academy of Railway Engineering, Ministry of Railway Liaoning Provincial Institute of Building Research Dalian University of Technology Coal Industry Planning Design Institute, Ministry of Energy Sources [No.4 Planning and Design Institute, Ministry of Aerospace Industry 120 (Chief members in the drafting: Gong Sit iy Minchuan Li Dubai Lie Huishan Song Shaoxien Shi Yeoxin in Quan Wei Lian ie June ‘how Bingthang Hu Qingchang Yin Zhiginn Zhou Xiyun Wo Mingshun hone. Yieun Dai Guoying Wang Guangiun Huang Cunhan Li Shuthen Dong Jincheng Liv Ji Qiso Tienmin Wen Liengmo Xu Shanon Bai Aodons Liu Mushong Tong Yuesheng Shea Jumin Yu Andong Aen Xing eng Xiang Chea Linsho ‘Translated by: Lu Rongiian ‘Checked by: ‘Ye Yaoxian mamReMAE (CIP) RE ERI, E/E RAL. AOR BREA AERE, 1994, 12 ISBN 7-80005-259-1, Lm 1, ®t 1, Bem AARRiT. MLRRET RHA IE 1. TU284-85 RMR RibmamnuMR oR) SKF AL 1994 ORL) =A SN 7.40005 250:1/7 + on