Академический Документы
Профессиональный Документы
Культура Документы
Low Temperature
All-Electric Cold Plate System
TABLE OF CONTENTS
I N T R O D U C T I O N ...........................................................................................................................2
Using Your Operators Manual....................................................................................................2
S Y S T E M S A F E T Y W A R N I N G S ...............................................................................................3
Safety Warnings and Precautions...............................................................................................3
Safety Labels and Locations.......................................................................................................5
Q U I C K S T A R T G U I D E ................................................................................................................7
Refrigeration System Diagram....................................................................................................8
Daily Operating Instructions........................................................................................................9
S Y S T E M S P E C I F I C A T I O N S A N D T E C H N I C A L D A T A .................................................10
R E F R I G E R A T I O N .........................................................................................................................12
All-Electric Cold Plate System....................................................................................................12
Defrost and Cooling Cycle..........................................................................................................15
Preventative Maintenance Checklist..........................................................................................17
O P E R A T O R T R O U B L E S H O O T I N G .........................................................................................20
Troubleshooting Chart................................................................................................................20
B O D Y C A R E A N D M A I N T E N A N C E .......................................................................................22
Fiberglass Maintenance and Repair...........................................................................................22
Other Body Care and Maintenance............................................................................................24
C O L D C H A I N B E S T P R A C T I C E S ...........................................................................................25
G L O S S A R Y .....................................................................................................................................27
W A R R A N T Y ....................................................................................................................................29
S E R V I C E A N D S U P P O R T ..........................................................................................................30
Service Contacts.........................................................................................................................30
Service Record Log.....................................................................................................................31
-1-
INTRODUCTION
USING YOUR OPERATORS MANUAL
This operators manual contains important information about your Johnson Refrigeration System and should
remain with the truck body at all times. The manual has been prepared to assist you in retaining the
dependability, performance, and safety features that are built into a Johnson Refrigerated Truck Body. It is
essential that this body and refrigeration system receive periodic inspections, maintenance, and service parts
replacement.
This manual includes safety checks that the operator must perform periodically. Reading your operators
manual will help you and others avoid personal injury or damage to the system. The information in this manual
will provide the operator with the safest and most effective use of the refrigeration system. Knowing how to
operate your refrigeration system safely and correctly will allow you to train others on the proper operation of
this piece of equipment.
It is important that every Refrigerated Truck Body owner and/or operator have an organized preventative
maintenance program. The United States Department of Transportation requires that the maintenance records
be kept on every commercial highway vehicle. It is to your advantage to be able to show that regularly
scheduled inspection checks have been made on every piece of equipment operated. A regular preventative
maintenance program will assure that you get the most from your Johnson Refrigerated Truck Body. It is
recommended that you use similar preventative maintenance practices with regard to this refrigeration system.
ATTENTION
Read this manual carefully and become familiar with your Johnson Refrigeration System. Know its
applications, its limitations and any hazards involved. Should you have any further questions, contact
Johnson Refrigerated Truck Bodies at (800)922-8360 and ask for the Customer Service Department. This
manual should be kept with the body at all times and should remain with the body when it is sold.
-2-
Safety precautions
Johnson Refrigerated Truck Bodies recommends that all services be performed by a qualified service
technician. However, there are several general safety practices which you should be aware of.
WARNING: Always wear safety glasses or goggles when working with or around the refrigeration system
or battery. Refrigerant or battery acid can cause permanent damage if it comes in contact with your eyes
and/or skin.
WARNING: Keep hands and loose clothing clear of fans, belts and gears at all times when the unit is
operating.
WARNING: Use extreme caution when servicing compressor unit, and when climbing onto, or off of
chassis and equipment.
CAUTION: Exposed coil fins can cause painful lacerations. Use caution when performing service work
on the evaporator or condenser coils, although service work is best left to a qualified service technician.
CAUTION: Disconnect electrical source and use extreme caution if drilling holes in the unit. Drilling into
electrical wiring or refrigerant lines could cause a fire. Never drill into structural components.
WARNING: Unit may start at any time the unit is connected to shore power and the compressor on/off
switch is turned ON.
WARNING: Be sure to disconnect power supply when inspecting any part of the unit.
Electrical hazard
WARNING: Be sure to disconnect unit from shore power before working on the unit. This is an allelectric unit and could present a potential electrical hazard.
-3-
Lift gate
For body applications where there is a side or rear mounted lift gate, please see the manufacturers owners
manual for safety and operational instructions.
Refrigerant
Although fluorocarbon refrigerants are classified as safe, observe caution when working with refrigerants or
around areas where they are being used in the servicing of your unit.
DANGER: Fluorocarbon refrigerants may produce toxic gases. In the presence of an open flame or
electrical short, these gases are severe respiratory irritants capable of causing death.
DANGER: Fluorocarbon refrigerants tend to displace air and can cause oxygen depletion which could
result in death by suffocation. Provide adequate ventilation in enclosed or confined areas.
WARNING: Fluorocarbon refrigerants evaporate rapidly, freezing anything they contact if accidentally
released into the atmosphere from the liquid state.
Refrigerant oil
Observe the following precautions when working with or around refrigerant oil:
WARNING: Always wear safety glasses or goggles to protect eyes from contact with refrigerant oil.
WARNING: Protect skin and clothing from prolonged or repeated contact with refrigerant oil. Rubber
gloves are recommended.
WARNING: Wash thoroughly immediately after handling refrigerant oil to prevent irritation.
First Aid
Refrigerant
Eyes: For contact with liquid, immediately flush eyes with large amounts of water. Get prompt medical
attention.
Skin: Flush areas with large amounts of warm water. Do not apply heat. Wrap burns with dry, sterile bulky
dressing to protect from infection or injury. Get prompt medical attention.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until arrival of
emergency personnel.
Refrigerant Oil
Eyes: Immediately flush eyes with large amounts of water for at least 15 minutes while holding the eyelids
open. Get prompt medical attention.
Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation
persists.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until arrival of
emergency personnel.
Ingestion: Do not induce vomiting. Immediately contact poison control center or physician.
-4-
Electrical hazard
Locations vary depending on model.
Can be found near all power
receptacles, high voltage tray covers
and interface boards. Indicates a
dangerous hazard which, if not avoided,
will result in death or serious injury by
electrical shock.
DANGER
HIGH VOLTAGE
DISCONNECT SHORE POWER
AND TURN OFF CIRCUIT BREAKER
ON THIS UNIT BEFORE SERVICING
ATTENTION!
Turn Electric On/Off to OFF BEFORE connecting or
disconnecting to shore power.
Not following this procedure can cause damage to the electrical system
-5-
WARNING
DOOR MUST BE FULLY ENGAGED INTO HOLDBACK DEVICE TO
RETAIN DOOR IN THE FULL OPEN POSITION. FAILURE TO
SECURE DOOR INTO HOLDBACK DEVICE MAY RESULT IN THE
DOOR SWINGING SHUT ON THE OPERATOR. DOOR HOLDBACK
DEVICE NEEDS TO BE REPLACED IMMEDIATELY IF DAMAGED.
FOR REPLACEMENT PARTS CONTACT JOHNSON
REFRIGERATED TRUCK BODIES AT 800-922-8360
OVER ALL
HEIGHT
12 6
PUSH
EMERGENCY RELEASE
CHECK OPERATION
FREQUENTLY
ATTENTION:
VACUUM RELIEF PORT
Keep Free From Obstruction
N O T I C E
CAUTION
REQUIRED MAINTENANCE
DISASSEMBLE INTERNAL DOOR
RELEASE HANDLE AND LUBRICATE
THREADS ANNUALLY
OPEN
Located inside every door of body below the T release
handle. All doors are equipped with an inside safety
release feature, so a person can never be locked inside
the body.
-6-
-6-
-7-
Airflow
Cold air
Compressor/condenser
nose mount
Warm air
Eutectic cold plates
Compressor
on/off switch
Cornershell
thermometer
Compressor/condenser
skirt mount
Shore power
outlet
Cord box
a. Compressor on/off switch located on the driver side front cornershell of the body. Switch must be turned
OFF when connecting or disconnecting unit from shore power.
b. Compressor/condenser (nose and skirt mount) unit works as both a motor and a pump that moves
refrigerant through the system.
c. Eutectic cold plates when system is plugged into shore power, refrigerant passes through cold plates
recharging the salt brine/eutectic solution within approximately eight hours.
d. Cornershell thermometer digital thermometer which allows operator to monitor bodys interior air
temperature; located on driver side front cornershell of the body.
e. Shore power outlet 3-Phase/1-Phase outlet used to plug refrigeration system into shore power to be
recharged; located on the driver side front cornershell.
f. Cord box if truck comes with a cord box feature, the line cord is located in the white box on the driver side
of the truck. Cord box cover must be closed and latched in order to activate the ignition cut-out switch,
allowing the truck to be started.
-8-
2. Retrieve the electrical line cord provided inside the chassis cab. If truck
has a cord box feature, line cord can be found on the driver side mounted
to the body sub-floor.
Cord box
On/off switch
5. Let the compressor run for a minimum of eight uninterrupted hours until the
refrigeration plates are recharged. It will then shut off by a pressure switch.
6. Refer to cornershell thermometer to verify the unit has reached the appropriate
temperature before loading your product.
NOTE: The bodys interior air temperature will be higher after loading product.
Cornershell thermometer
7. Before going en route, turn compressor switch to OFF. Unplug and stow power cord.
If truck has a cord box, cover must be fully closed and latched to activate the ignition
cut-out switch, allowing the truck to be started.
12 Ft Body
14 Ft Body
7062
7937
NOTE: THE BTU PER HOUR LOAD CALCULATION ABOVE IS BASED ON AN AMBIENT OF
MODEL ID#:
16 Ft Body
18 Ft Body
20 Ft Body
22 Ft Body
24 Ft Body
26 Ft Body
8811
9686
10560
11435
12309
13184
110
L100PV1 -V3 - 12
L100PV1 -V3 - 14
L100PV1 -V3 - 16
L100PV1 -V3 - 18
L100PV1 -V3 - 20
L100PV1 -V3 - 22
L100PV1 -V3 - 24
L100PV1 -V3 - 26
12 Ft Body
14 Ft Body
16 Ft Body
18 Ft Body
20 Ft Body
22 Ft Body
24 Ft Body
26 Ft Body
CONDENSING UNIT:
Single Phase
Compressor
Temperature Application
Condensing Unit Model #
Compressor Model #
Minimum Circuit Ampacity
Compressor RLA
Compressor BTU/HR
Capacity @ Ambient
Voltage Rating:
Line Voltage Minimum
Line Voltage Maximum
Oil Type
Oil Quantity
Refrigerant - R404A
Pressure Settings:
Cut IN
Cut Out
Total System Weight
Ambient Operating
Temperature (F)
Plate Specification:
Plate Blower Cabinet Size
Ceiling Plate Size:
Ceiling Plate Size:
Front Wall Plate Size:
Front Wall Plate Size:
Solution Temperature (F)
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
12090
12090
14770
14770
17800
24180
24180
24180
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
`
14#
4#
1921
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
`
14#
4#
2070
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
50 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
14#
4#
2250
14#
4#
2416
14#
4#
2989
14#
4#
3255
14#
4#
3433
14#
4#
3613
110
110
Quantity
Thickness
2-1/8"
Thickness
2-1/8"
NA
30" X 120"
NA
30" X 74"
NA
110
Quantity
Thickness
2-1/8"
NA
2
2
30"
30"
30"
36"
X 74"
X 60"
X 74"
X 74"
110
Quantity
Thickness
2-1/8"
NA
2
2
1
1
30"
30"
30"
36"
X 84"
X 74"
X 74"
X 74"
110
Quantity
Thickness
2-1/8"
NA
2
2
1
1
30"
30"
30"
36"
X 96"
X 84"
X 74"
X 74"
110
Quantity
Thickness
2-1/8"
30"
30"
30"
36"
2
4
1
1
X 74"
X 66"
X 74"
X 74"
Thickness
2-1/8"
NA
NA
2
2
1
1
110
Quantity
30"
30"
30"
36"
Thickness
2-1/8"
NA
2
4
1
1
X 96"
X 66"
X 74"
X 74"
110
Quantity
30" X 84"
NA
30" X 74"
36" X 74"
Quantity
NA
6
0
1
1
30"
30"
30"
36"
X 96"
X 84"
X 74"
X 74"
4
2
1
1
-14
-14
-14
-14
-14
-14
-14
-14
7518
176.6
8323
197.1
9262
218.5
10125
238.1
10803
263.1
11666
282.7
12905
303.9
13846
325.5
7062
252.2
7937
283.4
8811
314.7
9686
345.9
10560
377.1
11435
408.4
12309
439.6
13184
470.8
7518
8323
9262
10125
10803
11666
12905
13846
Total System
BTU/HR Capacity (F)
Condensing Unit
Operating Time
Required
Holdover Available
7.76
8.86
7.86
7.86
7.86
7.86
7.86
7.86
10.65
10.49
10.51
10.45
10.23
10.20
10.48
10.50
- 10 -
All-Electric Low Temperature Cold Plate Refrigeration System, for -5 Operation (up to 96 inch wide bodies)
BODY LENGTH:
TOTAL BTU/HR HEAT
LOAD REQUIREMENT
12 Ft Body
14 Ft Body
16 Ft Body
18 Ft Body
20 Ft Body
22 Ft Body
24 Ft Body
26 Ft Body
6705
7535
8366
9197
10028
10859
11689
12520
NOTE: THE BTU PER HOUR LOAD CALCULATION ABOVE IS BASED ON AN AMBIENT OF
MODEL ID#:
110
L100PV1 -V3 - 12
L100PV1 -V3 - 14
L100PV1 -V3 - 16
L100PV1 -V3 - 18
L100PV1 -V3 - 20
L100PV1 -V3 - 22
L100PV1 -V3 - 24
L100PV1 -V3 - 26
12 Ft Body
14 Ft Body
16 Ft Body
18 Ft Body
20 Ft Body
22 Ft Body
24 Ft Body
26 Ft Body
CONDENSING UNIT:
Single Phase
Compressor
Temperature Application
Condensing Unit Model #
Compressor Model #
Minimum Circuit Ampacity
Compressor RLA
Compressor BTU/HR
Capacity @ Ambient
Voltage Rating:
Line Voltage Minimum
Line Voltage Maximum
Oil Type
Oil Quantity
Refrigerant - R404A
Pressure Settings:
Cut IN
Cut Out
Total System Weight
Ambient Operating
Temperature (F)
Plate Specification:
Plate Blower Cabinet Size
Ceiling Plate Size:
Ceiling Plate Size:
Front Wall Plate Size:
Front Wall Plate Size:
Solution Temperature (F)
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
Single Phase
Compressor
Three Phase
Compressor
13380
13380
21900
21900
21900
21900
21900
21900
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
50 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
50 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
197
253
Ultra 32-3 MAF Polyol Ester
64 OZ
21 lbs
14#
4#
2153
14#
4#
2330
14#
4#
3021
14#
4#
3195
14#
4#
3429
14#
4#
3603
14#
4#
3807
14#
4#
4356
110
Thickness
2-5/8"
110
Quantity
Thickness
2-5/8"
30" X 74"
30" X 60"
30" X 74"
36" X 74"
NA
30" X 120"
NA
30" X 74"
NA
110
Quantity
Thickness
2-5/8"
2
2
1
1
30" X 84"
30" X 74"
30" X 74"
36" X 74"
NA
110
Quantity
Thickness
2-5/8"
Thickness
2-5/8"
2
2
1
1
30" X 74"
30" X 66"
30" X 74"
36" X 74"
NA
NA
2
2
1
1
30"
30"
30"
36"
110
110
Quantity
X 96"
X 84"
X 74"
X 74"
Quantity
Thickness
2-5/8"
2
4
1
1
30" X 96"
30" X 66"
30" X 74"
36" X 74"
NA
110
Quantity
Thickness
2-5/8"
2
4
1
1
30" X 84"
NA
30" X 74"
36" X 74"
110
Quantity
Thickness
2-5/8"
NA
NA
Quantity
NA
6
1
1
30"
36"
30"
36"
X 96"
X 84"
X 74"
X 74"
4
2
2
1
-21
-21
-21
-21
-21
-21
-21
-21
8339
180
9167
201.1
10218
223.1
11336
243.1
12311
268.3
13429
288.3
14476
310.7
17310
379.54
6705
209.5
7535
235.5
8366
261.4
9197
287.4
10028
313.4
10859
339.3
11689
365.3
12520
391.3
8339
9167
10218
11336
12311
13429
14476
17310
7.35
8.26
5.28
5.28
5.28
5.28
5.28
5.28
12.44
12.17
12.21
12.33
12.28
12.37
12.38
13.83
Total System
BTU/HR Capacity (F)
Condensing Unit
Operating Time
Required
Holdover Available
- 11 -
REFRIGERATION
Read this Operators Manual and safety rules before operating your Johnson Refrigeration System.
Compare these images with your refrigeration system to familiarize yourself with the locations of this systems main components.
Save this manual for future reference.
- 12 -
- 13 -
OPERATING INSTRUCTIONS
Turn on:
Press and release the pushbutton located on the driver side cornershell. The gold LED indicator above
pushbutton will turn on to indicate the body interior lights are active. This automatically begins the delay
time duration (40-minute default setting).
NOTE: If the LED indicator flashes at a high rate, the body interior lights will not turn on because the
brake input is active.
Turn off:
To manually turn OFF the body interior lights, press and release the pushbutton. The LED indicator
above pushbutton will also turn off to indicate the body interior lights have been turned off.
The body interior lights and LED indicator will both turn off once the delay time expires.
The body interior lights and LED indicator will both turn off when the brake pedal has been pressed for a
minimum of one second. The LED indicator will then flash 10 times at a high rate to signify that the
brakes have shut down the body interior lights.
3. Wait five seconds to allow the timer to exit programming mode. When the timer has been successfully
programmed, it will flash the LED indicator a number of times to indicate the new MODE setting.
NOTE: If the five seconds expire before entering a new MODE setting, the timer will respond by simply
flashing the current MODE. This feature can be used to verify the current setting.
- 14 -
- 15 -
COOLING CYCLE
The cooling system operates from shore power connection. While this system is activated, the unit must remain
plugged into shore power and uninterrupted throughout the entire duration of the cooling cycle. A minimum of
eight hours continuous compressor run is recommended.
The system consists of one condensing unit with one condenser, either sub floor (a) or nose mount (b), and
eutectic cold plates (c). The condensing unit is controlled by a low pressure cut-out switch, and will run until the
eutectic plates are frozen and the setpoint temperature inside the body is reached. When the cold plates are
fully charged, the compressors will cycle off on the pressure control.
IMPORTANT NOTICE: ONCE COMPRESSOR ON/OFF SWITCH IS TURNED ON, COMPRESSOR MAY
START AT ANY TIME, WHETHER OR NOT TRUCK ENGINE IS RUNNING.
a.)
b.)
c.)
- 16 -
PREVENTATIVE MAINTENANCE
It is important that every refrigerated truck body owner and/or operator have an organized preventative
maintenance program. A closely followed preventative maintenance program will help to keep your
Johnson Refrigeration System in top operating condition. The following general schedule is provided
to assist in monitoring that maintenance.
EN ROUTE OBSERVATIONS
En route inspections are recommended every four hours for the prevention of damage to the cargo.
9 Body temperature reading should be within 5 to 8F of the thermostat setting. If the body temperature is
not within 5 to 8F, it indicates one of the following:
a) The unit has not had sufficient time to pull down to setpoint temperature (i.e. warm load,
improperly pre-cooled body, length of time on route, frequency of door openings, etc.)
b) Frost or ice accumulation on cold plates exceeds build-up on plate surface. Manual cold
plate defrost is required.
c) Unit may be low on refrigerant charge. If bubbles appear in the liquid line sight glass,
refrigerant may be low. Maintenance check of system charge required.
(Also refer to Operator Troubleshooting section of this manual)
Cargo area inspection
Johnson Refrigeration Systems are designed to maintain the required temperature for product being carried
during time of transit. To assist the unit in performing this function, operators should:
9 Inspect the body for proper insulation.
9 Inspect outside of body for loose or improperly sealed doors.
9 Inspect inside of body for damaged walls and clogged defrost drain tubes. Any damage to the wall or
insulation must be repaired (see Body Care and Maintenance section of this manual)
9 Be sure loads are at the proper carrying temperature when you pick them up.
9 Supervise loading to make sure there is sufficient air space around the load for proper air circulation.
DAILY OBSERVATIONS
Condenser surface
9 Remove any debris that may have lodged itself into the condenser fins while en route (i.e. leaves,
branches, wrappers, bags, etc.)
Line cord inspection
9 View line cord for any cuts, nicks, chafing or abrasions that may indicate damage to the line cord wires.
9 While condensing unit is operating, feel line cord ends. If cord ends are hot to the touch, disconnect
power supply and check the electrical connections of the line cord wires to the contact prongs.
9 View line cord ends and plug-ins (flanged inlet), and male plug prongs for any burnt spots on connector
contacts. Replace components with any damaged or burnt contacts before operating equipment.
Cold plate defrost
To prevent frost build-up on the surface of the plates, run cold plate defrost brush mounted above curbside door
on body interior (feature optional) across plates surface daily. Avoid contact with refrigeration piping and
valves. It is not recommended to use scrapers on plates. Expansion valves could be jarred in the process,
resulting in a refrigerant leak. It could also result in scraping the surface or puncturing the plates.
A cold plate manual defrost is recommended to be performed once a week, and is required when frost
accumulation exceeds build-up on plate surface.
9 To conduct a manual defrost, complete the following:
1. Compressor on/off switch should be OFF.
2. Unplug power supply.
3. Unload product and open all body doors. (NOTE: Ambient air temperature must be above
freezing.)
4. Place a fan in rear door opening directing warm airflow onto plates or use water hose with a
sprayer using warm water directed onto plates. (IMPORTANT NOTICE: Water temperature
should not exceed 110F as excessive heat build-up in the plates can create expansion beyond
what the plates are designed. Do not use a high pressure wash system. Doing so could
- 17 -
damage plate surface, piping or valves. Use only standard household water pressure. Do not
direct water flow at evaporator unit, electrical enclosures, or light fixtures.)
5. When plates are defrosted, flush out floor and shelving, sanitizing as required.
6. Dry interior of body and plates with a fan.
9 After defrost, complete the following:
1. Compressor on/off switch should be OFF.
2. Plug in power cord.
3. Turn compressor on/off switch to ON. When unit starts, observe for 1-2 minutes before leaving.
MONTHLY OBSERVATIONS
Exterior condenser fins
9 Check for exterior condenser fins that may be bent. Fins that are bent need to be combed out or
straightened to allow airflow through condenser.
9 Remove any accumulated dirt and/or debris by running water across the surface of the fins.
NOTE: Do not use a high pressure wash system to clean condensing unit. Doing so will damage
condenser fins. Use only standard household water pressure.
Compartment
9 Open compressor compartment door or roof top service cover and check for any oil stains or signs of oil
leaks. If stains are present contact Johnson Refrigerated Truck Bodies or a qualified service technician
for further steps.
Holdover plate system
9 Check for frost or ice build-up on holdover plates. If build-up exceeds on the plate surface, the
system needs to be defrosted.
9 Upon system defrost, inspect condition of holdover plates for any external leaks.
9 Check all plate fittings and piping.
9 Check all holdover plate mounting brackets and support channels inspecting for loose fasteners or
clamping fixture failures.
QUARTERLY OBSERVATIONS
Refrigeration system
9 On the condensing unit, clean the condenser coil with a garden hose sprayer. Take care not to
damage the aluminum fins. Clean condenser coils will prolong the life of your compressors, and allow
your system to operate more efficiently.
9 While the compressors are operating, check oil sight glass. The oil level should be to full.
9 While the compressors are operating, check the liquid line sight glass. The fluid should be clear and the
moisture indicator should be green.
9 Check all wiring and capillary tubes of the controls. Be sure they are not chafing or rubbing against
anything.
9 Check the system for any oil spots. This would indicate the possible start of a small leak.
SIX-MONTH OBSERVATIONS
With condensing unit unplugged:
9 Remove roof top condensing unit service cover.
9 Remove any foreign debris (i.e. leaves, branches, dirt, ice, snow, etc.) from inside of condensing unit
compartment.
9 Look for signs of oil stains/leaks on compressor frame, hoses or floor of condensing unit compartment.
9 Check condenser fan motor and blade for cracks, nicks or contact points to condenser fan shroud.
9 Inspect copper tubing and/or hoses for chafing, rubbing, loose clamps, etc.
9 Check to see that discharge line thermostat is secured to the high side copper pipe on the compressor.
9 Inspect condenser frame for excessive corrosion, rust, cracks, loose or missing bolts/fasteners.
WARNING: To reduce the risk of serious physical injury, never reach into the
condensing unit compartment or condensing unit while the system is plugged into shore
power. Always disconnect power supply when servicing condensing unit. Servicing of
the condensing unit is only to be conducted by a certified refrigeration technician.
- 18 -
- 19 -
OPERATOR TROUBLESHOOTING
USING TROUBLESHOOTING CHART
If you are experiencing a problem that is not listed in this chart, contact JRTB Customer Service to speak with
an engineer. When you have checked all the possible causes and you are still experiencing the problem, see a
qualified service technician.
IMPORTANT NOTICE: Before performing any repair service or procedure, please refer to the Johnson
Refrigerated Truck Bodies Service Manual.
Troubleshooting Chart
Compressor will
not start or run
on shore power.
1. No AC power to body.
2. Compressor on/off switch is in OFF
position.
3. System is off on pressure it is satisfied to
setpoint.
4. Loss of Freon.
5. Pump down switch in pump down position.
Eutectic cold
plates not
operating
properly.
Body temperature
does not read
within 5-8 of
desired
temperature.
- 20 -
Condensing unit
starts, but does
not continue to
run.
For 3-Phase
compressors that
have power, but
will not start.
- 21 -
FINISH PROTECTION
The Johnson fiberglass body has a beautiful, natural glass finish that will stay this way if washed periodically
with common strength soap and water (NOTE: heavy doses of acetone or lacquer should not be used.) High
caustic soaps and solutions will cause premature color fade and panel surface deterioration. It is acceptable to
use a hot water pressure washer system for cleaning; however to prevent premature deterioration of exterior
finish, the water pressure against the surface of the panel should not be extreme. Mild to moderate amounts of
pressure are efficient to apply soap and remove surface dirt.
For good finish protection, we recommend applying a coat of wax one or two times a year. Waxing helps
protect against every day elements and ultra violet rays which cause surface deterioration and fading. Many
automotive or fiberglass boat waxes can be used. Check the product label for recommended surfaces and
application.
A mild, abrasive rubbing compound is recommended to be used with wax. Johnson Refrigerated Truck Bodies
uses a product manufactured by Maguire. Any fiberglass boat or automobile parts supplier should be able to
provide this or an equivalent product for you.
FIBERGLASS REPAIR
Exterior walls, interior walls and floor
Johnson Refrigerated Truck Bodies are extremely durable, but occasional accidents do occur. If so, repairs are
simple, amazingly inexpensive and easily done in your own shop. Fiberglass repair kits from local boat or
hardware stores are readily available. Observe all manufacturers instructions, which include safety
precautions.
Exterior fiberglass sheet
(Rub Rails, Fenders, Doors and Corners)
If a fracture ever appears, it should be repaired as soon as possible.
1. Sand entire area to remove all foreign matter, and rough up to assure a
good bond
2. Fill voided foam area with a urethane based foam product
3. Allow foam to dry, and trim excess foam to within 1/4 of exterior of finished
sheet
4. Sand area again to assure a good bond
5. Feather thickness of sheet
6. Fill area with Mar glass to within 1/8 of exterior of finished sheet
7. Allow to harden and sand
8. Cut oversized strips of fiberglass mat to cover area (approximately 2 larger
than damaged area and about 3-4 strips)
9. Lay mat on clean cardboard
10. Saturate mat with resin and catalyst mixture
11. Place coated mat into hole
12. Remove all air bubbles from the layers of wet mat with brush or roller
13. Allow to dry
After area has hardened:
1. Sand, flush and feather edges to original liner
2. Prime and paint as needed
- 22 -
Fiberglass floor
If a definite fracture or crack appears, it can be repaired in the same manner as you
would the liner.
If an entire area of the floor wears thin, repair as follows:
1. Sand entire area to remove all foreign matter and rough up to assure a
good bond
2. Cut strips of fiberglass mat to cover area
3. Coat area with resin (mixed according to manufacturers instructions)
4. Lay pre-cut pieces of fiberglass mat over fresh resin
5. Apply additional resin to completely saturate top of mat
6. Use paint roller to smooth the surface and remove the air bubbles
If grit for a non-slip surface is desired:
1. Sprinkle grit on repaired area while resin is still wet
2. Allow to harden
3. Recoat area with mixed resin and catalyst to lock in grit
PROPER AIRFLOW
Proper airflow is critical to maintaining required product temperature. Even with optimal system performance,
obstructions create poor air circulation and uneven temperature distribution, risking damage to your product.
Truck body interior must be kept clean to prevent contamination and obstruction of airflow. Clear body floor of all debris to
prevent circulation blockage, and check evaporator unit regularly to make sure it is free of debris.
Keep floor beneath product open so warm air can return back through cooling system. Block pallets help provide an airflow
channel by forming additional space between body floor and cargo.
Johnsons inverted tread airflow flooring option is designed to ensure sufficient airflow on the
underside of the product. The inverted channels provide a means for air to pass beneath the
product, while the foam insulation below the floor acts as a barrier to keep body floor cool.
Secure pallet loads with plastic netting instead of stretch film, which severely restricts proper
ventilation. Avoid using slip sheets or hand stacking as these are not favorable methods for adequate airflow.
Load product evenly to provide passable airways between top of the cargo and body ceiling when loading. Do not block
system warm air intake/cold air discharge, or load product tightly against walls or doors. This restricts airflow and will
negatively affect system cooling efficiency.
- 26 -
GLOSSARY
This glossary is published for informational purposes only, and the information being furnished herein should
not be considered as all-inclusive or meant to cover all contingencies.
NOTE: Additional terms not found in the glossary may be located in the Index section of this manual.
1-Phase plug 30-amp, 250-volt AC power. Three prong, twist-lock connector, located on line cord end.
NEMA #L6-30 plug and receptacle. 1-Phase systems are offered as a special option.
3-Phase plug 30-amp, 250-volt AC power. Four prong, twist lock connector, located on line cord end. NEMA
#L15-30 plug and receptacle. 3-Phase systems are offered as the standard option.
Air temperature vs. product temperature The United States Food and Drug Administration requires that
frozen products be kept at a temperature in which they remain a frozen solid. This concept is often confused
with the air temperature, which is defined as a measure of the heat content in the air. The air temperature may
fluctuate due to door openings and/or other factors, but the product temperature must remain freezing.
Ambient air temperature is the temperature of the outdoor air surrounding the body.
Amp is the abbreviation for ampere, and the basic measuring unit of electrical current.
Arcing is caused by routinely plugging and unplugging unit from shore power while the compressor on/off
switch is left ON, and can have detrimental effects on your electronic equipment. Arcing damage on the
electrical components of this system can be indicated by burnt spots on electrical connections of the line cord
wires, connector contacts and prongs. (See the Operator Troubleshooting section of this manual.)
Body interior light switches can be used to control the bodys interior lights. The ON/OFF switch is located to
the right of the curbside door on body interior. The Grote switch is mounted on the driver side front cornershell;
gold LED light above pushbutton indicates the body interior lights are turned ON. The bodys interior lights turn
off automatically after delay time has expired (40-minute default setting) or when the brake pedal is depressed.
BTU (British thermal unit) is a common unit of measure for heat, and is equivalent to the amount of heat
energy required to heat one pound of water one degree Fahrenheit. For example, raising the temperature of
one pound of water from 40 degrees to 41 degrees would take one BTU. This form of measure is referred in
the capacity of this refrigeration system.
BTU capacity of this refrigeration system is based on the application criteria used to calculate the heat load that
the system is required to absorb and expel. BTU capacity of the system is referred to as the number of BTUs
per hour of heat that can be removed from the cargo area.
Coil is a cooling or heating element made of pipe or tube, formed into a helical or serpentine shape that may be
equipped with thin metal fins to aid heat transfer.
Cold plate defrost Prevent frost build-up on the surface of the plates by running cold plate defrost brush
mounted above curbside door on body interior (feature optional) across plates surface daily. A cold plate
manual defrost is recommended to be performed once a week, and is required when frost accumulation
exceeds build-up on plate surface.
Compressor/condensing unit is both a motor and a pump that moves refrigerant through the system. A vapor
compression pump uses a scroll method to compress refrigerant gas and send it to the condenser. The
condenser is a heat exchanger which removes heat from the hot compressed gas and allows it to condense into
a liquid. As a whole, this unit acts like the heart of the cooling system. It is controlled by a low pressure cut-out
switch, and will run until the eutectic plates are frozen and the setpoint temperature inside the body is reached.
- 27 -
Compressor on/off switch is located on the driver side cornershell of the body. Switch must be turned OFF
when connecting or disconnecting unit to shore power.
Cooling system consists of a condensing unit with one condenser and eutectic cold plates. It operates from
shore power connection, and will run until the eutectic plates are recharged.
Cord box if truck comes with a cord box feature, the line cord can be found in this white box on the driver side
of the truck mounted to the body sub-floor. Cord box cover must be fully closed and latched in order to activate
the ignition cut-out switch, allowing the truck to be started.
Cornershell thermometer is the digital thermometer which allows operator to monitor bodys interior air
temperature only when system is connected to shore power during the pre-cooling process. Located on driver
side front cornershell of the body.
Door strip curtains are flexible vinyl curtains used to reduce air exchange between the refrigerated
compartment and the outside during door openings.
Eutectic cold plates act like the blue ice packs in a picnic cooler and absorb heat to maintain setpoint
temperature levels in the body. When the system is plugged into shore power, refrigerant passes through the
plates recharging the salt brine/eutectic solution after approximately eight hours.
Fahrenheit (F) is a unit of temperature measurement used in the United States and with this refrigeration system.
Fiberglass reinforced plastic (FRP) is a composite material made of a plastic matrix reinforced by fine fibers
made of glass.
Hertz (Hz) is a unit of frequency equal to one cycle per second.
Horsepower (HP) is a unit of power equivalent to 746 watts or 550 foot-pounds per second.
Line cord 25-foot, 30-amp 1-Phase or 3-Phase electrical cord provided inside the cab of the truck to connect
unit to shore power when recharging electric refrigeration system.
Low temperature refrigeration system is designed to maintain the temperature of your product.
Pre-cooling 1) To cool down an empty temperature controlled area to the desired product temperature prior to
loading. 2) To cool product to a desired temperature before loading into the truck body.
Recharging the system is used in reference to plugging the unit into shore power to re-energize the capacity of
the refrigeration cold plates.
Refrigerant is the medium of heat transfer in a refrigeration system which absorbs heat by evaporating at a low
temperature and releases heat by condensing at a higher temperature.
Refrigerant oil is a special oil used to lubricate compressors in refrigerant systems.
Refrigeration is defined as the removal and the relocation of heat.
Shore power also known as dockside power, refers to the electrical power source in which a trucks
refrigeration system can be plugged in and recharged overnight.
Shore power outlet is a standard 3-Phase outlet used to plug refrigeration system into shore power to be
recharged; located on the driver side cornershell.
Volt The basic measuring unit of electrical potential.
Watt The basic measuring unit or electrical power.
- 28 -
WARRANTY
OWNERS WARRANTY RESPONSIBILITES
As the refrigerated truck body owner, you are responsible for the performance of the preventative maintenance
outlined in this Operators Manual.
As the refrigerated truck body owner, you should be aware that Johnson Refrigerated Truck Bodies may deny
you warranty coverage if your refrigerated truck body, or a part or component, has failed due to abuse, neglect,
improper maintenance, or unapproved modifications.
You are responsible for contacting Johnson Refrigerated Truck Bodies prior to any warranty work being done on
your refrigerated truck body. Johnson Refrigerated Truck Bodies has to provide prior approval for warranty
work before a qualified service technician performs any repairs.
Terms of the Johnson Refrigerated Truck Bodies warranty are available on request. If you have any questions
regarding your warranty, please contact Johnson Refrigerated Truck Bodies and ask to speak with the
Customer Service Department at (800) 922-8360.
WARNING
PRIOR TO CONDUCTING WARRANTY REPAIR
WORK ON THIS BODY OR REFRIGERATION
SYSTEM, PRE-APPROVED AUTHORIZATION MUST
BE GRANTED BY MANUFACTURER OR THE
MANUFACTURERS WARRENTY WILL BE VOID. TO
OBTAIN PRE-APPROVED AUTHORIZATION
CONTACT JOHNSON TRUCK BODIES AT
800-922-8360
- 29 -
SERVICE CONTACTS
Headquarters and Manufacturing Plant
215 E Allen Street
Rice Lake, WI 54868
Toll Free: 800.922.8360
Local: 715.234.7071
Fax: 715.234.4628
Sales Department Email: jtbsales@johnsontruckbodies.com
Web: www.johnsontruckbodies.com
FleetWise Service Repair
Toll Free: 800.FLT.WISE (358.9473)
FleetWise@johnsontruckbodies.com
Parts Orders
Genuine Johnson Truck Bodies Parts Orders
Toll Free: 800.922.8360 Ext. 3
Warranty Claims
Toll-Free: 800.922.8360 Ext. 420
Fax: 717.236.3742
Email: pmonroe@johnsontruckbodies.com
- 30 -
MILEAGE
DESCRIPTION