Академический Документы
Профессиональный Документы
Культура Документы
- Load curves
- Load factors and definitions
- Load types
- Advantages of Interconnected Grid System
Maximum demand
Demand Factor =
Connected Load
(< 1)
P (MW), Q (MVAR)
P ___
Q---
12
18
Time (hours)
24
Consumer A
30
= 0.6
L.F . A =
50
Consumer B
15
L.F .B =
= 0.3
50
MW
2.2
2.1
2.0
1.9
1.8
1.7
1.6
Vacation
Vacation
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Vacation
Vacation
1 2 3 4 5 6
This is not a Monthly load curve; just a daily peak load for a month
Diversity Factor:
As consumers maximum demands are not simultaneous; The
power stations maximum demand is less than the sum of individual
consumers maximum demands.
13.6 kW
12.2 kW
12.4 kW
11 kW
49.2 kW
D. F . =
= 1.23
40 kW
Plant Capacity
Plant Capacity Factor =
Average Demand
Plant Capacity Factor =
Plant Capacity
Reserve capacity = Plant capacity Maximum demand
Station output
Plant Use Factor =
Plant capacity Hours of use
P (MW)
P (MW)
12 16 20 24 T (day hrs)
12 16 20 24 T (duration hrs)
2. Commercial
3. Industrial load: Type dependent; (Low 25 kW, med. 100 kW, high > 500 kW
(i) Large induction motors (ii) other industrial processes; heater,etc
4. Municipal load: (i) Street lighting (night constant) (ii) Water supply &
drainage (off peak re-pumped; improves load factor)
Type of Load
Demand Factor
kW
1.00
kW
0.6
>1 kW
0.5
Residential (lighting)
Commercial (lighting)
Restaurants
0.7
Theaters
0.6
Hotels
0.5
Schools
0.55
Small industry
0.6
Store
0.7
0 -10 HP
0.75
0.65
20 100 HP
0.55
> 100 HP
0.5
Residential
(lighting)
Commercial
(lighting)
General power
service
Between
consumers
3-4
1.5
1.5
Between
Transformers
1.3
1.3
1.3
Between
feeders
1.2
1.2
1.2
Between
substations
1.1
1.1
1.1
P (MW)
Peak Load
- Base Load: is the unvarying load that
occurs almost all the day on the station (>)
- Peak Load: is the various peak
demands over and above the base load (<)
Base Load
0
12 16 20 24 T (day hrs)
Hydro
Steam
P (MW)
P (MW)
12 16 20 24 T (day hrs)
12 16 20 24 T (day hrs)