630 KVA
415 V
876.49 A
Derating Factors
a) Variation of ground temperature
(of cond. Temp 90 deg C for XLPE)
b) Variation of soil thermal resistivity
(3 cables in trefoil)
c) Group rating factor for 3 group of
cables in trefoil formation and touching
each other
d) Rating factor for depth of laying
0.91 ----------> a
1.11 ----------> b
0.88 ----------> c
0.91 ----------> d
0.81
457.02 A
800 KVA
415 V
1113.00 A
Derating Factors
a) Variation of ambient temperature
to 50 deg C
b) Group rating factor for 2 ckt. of cables in
trefoil formation to top tire with
horizontal formation.
1 ----------> a
0.98 ----------> b
0.98
93443440-Power-Cable-Sizing
708.54 A
Page 1 of 8
250 KVA
415 V
347.81 A
Derating Factors
a) Variation of ambient temperature
to 50 deg C
b) Group rating factor for 2 ckt. of cables in
trefoil formation to top tire with
horizontal formation.
1 ----------> a
0.98 ----------> b
0.98
708.54 A
100 KVA
415 V
139.12 A
Derating Factors
a) Variation of ambient temperature
to 50 deg C
b) Group rating factor for 2 ckt. of cables in
trefoil formation to top tire with
horizontal formation.
1 ----------> a
0.98 ----------> b
0.98
93443440-Power-Cable-Sizing
451.78 A
Page 2 of 8
150 KW
415 V
260.86 A
Derating Factors
a) Variation of ambient temperature
to 50 deg C
b) Group rating factor for multi core cables
with 6 cables in rack, laid in
horizontal formation.
1 ----------> a
0.93 ----------> b
0.93
428.73 A
ohms/km
ohms/km
ohms/km
km
ohms
Note: Starting is not critical becasuse
Volts
of Delta / Star start
< 3% (permissible limit)
6. Cable sizing for 15kW Jockey Pump Motor for Fire Fighting System
Rating of the equipment
Voltage
Full Load current at power factor 0.8
30 KW
415 V
52.17 A
ohms/km
ohms/km
ohms/km
km
182.601074 A
24.4211 Volts
5.88% < 20% (permissible limit)
43.08 KW
415 V
74.92 A
ohms/km
ohms/km
ohms/km
km
ohms
Volts
< 3% (permissible limit)
3.7 KW
415 V
6.43 A
93443440-Power-Cable-Sizing
4C x 16 sq.mm. AL PVC
1 nos.
Page 4 of 8
38.6070842 A
6.8969 Volts
1.66% < 20% (permissible limit)
9. Cable sizing for Air Handling Unit (A.H.U.) for Air Conditioning
Rating of the equipment
Voltage
Full Load current at power factor 0.8
3.7 KW
415 V
6.43 A
4C x 16 sq.mm. AL PVC
1 nos.
2.29
0.097
2.2921
0.045
0.1031
1.1495
0.28%
ohms/km
ohms/km
ohms/km
km
ohms
Volts
< 3% (permissible limit)
38.6070842 A
6.8969 Volts
1.66% < 20% (permissible limit)
10. Cable sizing for Winter Heating Unit for Air Conditioning
Rating of the equipment
Voltage
Full Load current at power factor 0.8
Cable type considered
Rated continuous current when
laid in air
93443440-Power-Cable-Sizing
9 KW
415 V
15.65 A
4C x 6 sq.mm. AL PVC
30 A
Page 5 of 8
(Non - Motor)
4C x 6 sq.mm. AL PVC
1 nos.
3.69
0.0942
3.6912
0.045
0.1661
4.5028
1.09%
ohms/km
ohms/km
ohms/km
km
ohms
Volts
< 3% (permissible limit)
11. Cable sizing for Ventilation Fan (Axail Flow type) for Exhaust Ventilation
Rating of the equipment
Voltage
Full Load current at power factor 0.8
0.74 KW
415 V
1.29 A
93443440-Power-Cable-Sizing
ohms/km
ohms/km
ohms/km
km
ohms
Volts
< 3% (permissible limit)
7.72141685 A
13.6426 Volts
3.29% < 20% (permissible limit)
Page 6 of 8
0.72 KW
415 V
1.25 A
ohms/km
ohms/km
ohms/km
km
ohms
Volts
< 3% (permissible limit)
7.5127299 A
13.2739 Volts
3.20% < 20% (permissible limit)
415 V
100.00 A
6
0.373
0.8
7.173
415
12.47
kW (3 KW each)
kW
kW (20 nos. of heater out of 35 nos. running)
kW
V
A
1.1
0.0827
1.1031
0.5
0.5516
11.9167
2.87%
93443440-Power-Cable-Sizing
ohms/km
ohms/km
ohms/km
km
(Actual Length is 255m max.)
ohms
Volts
< 3% (permissible limit)
17.692 A
16.90 Volts
4.1% < 20% (permissible limit)
Page 8 of 8