Вы находитесь на странице: 1из 47

Breezeway_Cover_01_2005.

qxp

12/9/2004

1:14 PM

Page 3

Bulletin BZW05

BREEZEWAY

Wall Mounted Propeller Fans


Direct Drive and Belt Drive

Breezeway Fan
Introduction

Table of Contents

CERTIFIED RATINGS

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

PennBarry certies that the Breezeway


direct drive and belt drive models shown
on pages 12-13, and 18-39 are licensed to
bear the AMCA seal. The ratings shown are
based on tests and procedures performed
in accordance with AMCA publication 211
and AMCA publication 311 and comply with
the requirements of the AMCA Certied
Ratings Program.

General Information . . . . . . . . . . . . . . . . . . . . . . . . 2
Options and Accessories . . . . . . . . . . . . . . . . . . . . . 3
Motor Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Direct Drive Dimensional Data . . . . . . . . . . . . . . . 11
Direct Drive Performance Data:

UL and CSA Certication


Breezeway fans (Models P, BLL, BHM, BHH
& BCH) carry the UL label, UL 705, (ZACT),
File #E28413.

P Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Breezex (BX) . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Breezeway fans (Models P, BLL, BHM, BHH


& BCH) are also certied by the Canadian
Standard Association (File #LR13309).

BC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Belt Drive Dimensional Data . . . . . . . . . . . . . . . . . 16
Belt Drive Performance Data:

FANSIZER
Product Selection Software

BLL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
BHM/BHH . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

FanSizer software allows you to select the best centrifugal or


axial unit for your application. Input CFM and static pressure,
and FanSizer will make the optimum selection. It allows you to
complete job schedules which you can store, modify and print
in seconds. Features include: on-line help, on-screen product
drawings and dimensions, and complete text specications.
In addition, you can convert job schedules to ASCII code for
use with other programs like word processing.

BCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Sound Data Notes . . . . . . . . . . . . . . . . . . . . . . . . . 40
Engineering Notes . . . . . . . . . . . . . . . . . . . . . . . . . 41
Sample Specications . . . . . . . . . . . . . . . . . . . . . 44
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . 45

FANCAD
Library of CAD Drawings
FanCad is a library of drawings for use with computer-aided
design (CAD) systems. FanCads pre-drawn details can save
hours of drafting time. Included are all popular PennBarry fans
and related items.

FanSizer and FanCad are registered trademarks.

Visit Our Web Site


Point your internet web browser to www.PennBarry.com for
up-to-the-minute information including:

On-line catalog
List of nearest PennBarry representatives
Whats New
HVAC Hot Links

2005 PennBarry All rights reserved.


Following publication of this catalog changes may have been made in standard equipment, options and the like that would not be included.
We reserve the right to make changes at any time, without notice, to models, specications, options, availability, etc.
This bulletin illustrates the appearance of PennBarry products at the time of publication and we reserve the right to make changes
in design and construction at anytime without notice. Your local sales representative is the best source for current information.

PENNBARRY

General Information
Breezeway

The Breezeway propeller fan line provides a variety of solutions


to address the needs of wall mounted exhaust and ventilation
applications such as garages, factories, warehouses and other
relatively clean air applications.
Whether steel or cast aluminum, all propellers in the Breezeway
product line are statically and dynamically balanced to AMCA
Standard 204-96, Balance Quality and Vibration Levels for
Fans, to ensure quiet and reliable operation.
Breezeway fans allow one of the broadest motor selections
in the industry. All fans are fully assembled and test run prior
to shipping and belt drive models are pre-set to the specied
RPM.
The following descriptions are provided to help guide
product selection to the most appropriate product for the
application.

BELT DRIVE
BLL An economical product designed
for applications through 14,000 CFM
at static pressures up to 1/2" W.G.
Sizes 24" to 36" are available. Utilizes
fabricated steel propeller, fabricated
steel power assembly and a steel
venturi panel.
BHM Designed for medium duty
exhaust or supply applications with
volumes up to 34,000 CFM and static
pressures up to 3/4" W.G. Available
in sizes 24" to 48". Utilizes a highefciency fabricated steel propeller,
galvanized power assembly, and a
fully developed venturi, integrally spun
into a galvanized panel.

DIRECT DRIVE
P Series Designed for exhaust or
supply in light duty applications up to
6500 CFM and static pressures up to
5/8" W.G. Utilizes a stamped aluminum
propeller with steel hub, zinc-coated
wire guard/power assembly mounted
on RIS vibration isolators attached to
a steel venturi panel. Sizes 10" to 24"
are available.

Breezex (BX) These reversible fans


are designed for applications where
supply and exhaust are required on a
eld-selectable basis. Available through
4600 CFM at static pressure up to 3/8"
W.G. Utilizes a stamped aluminum
propeller with steel hub, a fabricated
power assembly and steel venturi
panel. Motors are base-mounted
TE type. Explosion-proof motors are
available less reversing switch.

BC Series The BC picks up where


the P-Series and BX leave off, available
in 24" to 54" exhaust or supply
congurations through 43,000 CFM at
static pressures up to 3/4" W.G.

PENNBARRY

BHH A heavy duty series of propeller


fans designed for exhaust or supply
applications up to 58,000 CFM and
static pressures up to 1" W.G. The
BHH is a quiet and cost effective
solution to higher volume applications.
Utilizes a high-efciency fabricated
steel propeller, a robust galvanized
power assembly that can handle
high horsepower motors, and a fully
developed venturi integrally spun into
a galvanized panel. Available in sizes
24" to 60".
BCH The most rugged wall propeller
fan in the Breezeway line, the BCH
utilizes a high efciency cast aluminum
air foil propeller, a fabricated steel
power assembly and a heavy gauge
venturi panel. Available in sizes 24"
to 60" with performances through
68,000 CFM and static pressures up
to 1" W.G.

Safety Precautions for Installation


Since Breezeway fans contain rotating parts, PennBarry
recommends the following safety precautions be taken during
installation, operation and maintenance. Install FAN GUARDS
on all non-ducted fan installations to protect people working
around the fan and to protect the fan from foreign objects
coming into contact with moving parts. For proper and safe
operation, fan RPM should not exceed that recommended in
performance tables.

Options and Accessories


Breezeway

PennBarry provides a wide variety of accessories for the Breezeway


propeller fan line. The components shown below can be mixed and
matched to suit the demands of the particular application.

WEATHERSHIELD
GUARD
WALL
SHUTTER

PANEL
FAN

REAR GUARD
(FOR USE WHEN
WALL SLEEVE NOT USED)

WALL MOUNTING
SLEEVE GUARD
(REAR WALL SLEEVE GUARD
SHOWN, FRONT WALL SLEEVEGUARD AVAILABLE)

WEATHERSHIELD
FRONT GUARD
(FOR USE WITH OR WITHOUT SHUTTER)

WALL MOUNTING SLEEVE


WITH ADJUSTABLE
PERIMETER
MOUNTING ANGLE

Weathershield
Weathershields are designed to divert rain and snow from exhaust and supply wall openings.
They are designed to be surface mounted and can be installed in conjunction with wall shutters.
Guards are provided. Standard construction is galvanized steel, painted upon request. In order
to minimize shipping costs, the weathershield will be shipped knocked down for the BHM and
BHH products, unless factory assembly is specied. Other models will be shipped factory
assembled.

Use the tables below to help with space planning and sizing guidelines. Please note the maximum
recommended intake (supply) CFM. This guideline will keep the intake CFM below 500 FPM.
If the intake CFM exceeds the recommended volume, use the next larger fan.

B
C

Dimensional Data
P SERIES

SIZE

BLL*/BCH*/BC

10

12

16

Wo

15 3/4

17 3/4

15 1/4

17 1/4

18 3/8

19 11/16

23 3/4

12 3/8

13 1/8

15 1/2

16 1/8

17 1/4

Max. Rec.
Supply CFM

10

12

16

18

806

1033

1837

2084

*Not Supply

18

20

24

24

30

36

42

23 1/2

25

27 1/2

33 1/4

28 3/4

34 3/4

40 3/4

46 3/4

55

61

67

23

24 1/2

27

32 3/4

28 1/4

34 1/4

40 1/4

46 1/4

54 1/4

60 1/4

66 1/4

30 1/2

27 3/8

31 3/4

36 5/8

41

45 3/4

49 5/8

54 5/8

19 1/2

17 5/8

20 1/4

23 3/8

25 7/8

28 3/8

31

34 1/4

20

24

24

30

36

42

48

54

60

2531

3724

2771

4073

5625

7427

10219

12604

15240

24 13/16 26 9/16

48**

54**

60**

**BCH only

SIZE

BHM/BHH
24

30

36

42

48

54*

60*

Wo

32 3/4

38 3/4

44 3/4

50 3/4

57

63

69

32 1/4

38 1/4

44 1/4

50 1/4

56 1/4

62 3/8

68 3/8

32 1/4

38 1/4

44 1/4

50 1/4

56 1/4

62 3/8

68 3/8

28 1/4

32 1/2

36 3/4

41

45 1/4

49 3/8

53 5/8

Max. Rec.
Supply CFM

24

30

36

42

48

54

60

3611

5080

6799

8768

10986

13509

16233

*BHH only

PENNBARRY

Options and Accessories


Breezeway

Rear and Front Guards

B
B

Protection is available for both the rear motor side (rear guard)
of the fan and the front face (front guard) of the fan. Both
assemblies include a sheet metal sleeve with an attached
guard. The rear guard is long enough to enclose the belt and
pulleys. The front guard is surface mounted and long enough
to enclose a wall shutter, if provided. The guard for either is
removable for maintenance. Standard shipment is knocked
down for BHM and BHH, or optionally available as factory
assembled. Shipment for other models is factory assembled
only. The guards on both conform to OSHA specications.

FRONT GUARD

REAR GUARD

Protection that conforms to OSHA regulations should be installed when fans are located within seven (7) feet of oor and/or
working level, or within reach of personnel. Review OSHA codes for specic details.

Dimensional Data
SIZE

P SERIES

BC/BLL/BCH

10

12

16

18

20

24

24

30

36

42**

48**

54**

60**

28 3/16

34 3/16

40 3/16

46 3/16

54 1/4

60 1/4

66 1/4

13 1/2

16 1/2

16 1/2

20 1/2

25

25

25

SCREEN
CSQ.

1 PIECE 1 PIECE 1 PIECE 1 PIECE 1 PIECE 1 PIECE 1 PIECE 1 PIECE 1 PIECE 1 PIECE 1 PIECE 2 PIECES 2 PIECES
15 1/2

17 1/2

23 1/4

24 3/4

27 1/4

33

28 5/8

34 5/8

40 5/8

46 5/8

54 3/4

60 3/4

66 3/4

*Motor side guard of concentric rings integral to unit. **BCH only

BHM/BHH

SIZE
ASQ.
B FRONT
B REAR
C
SCREEN

24

30

36

42

48

54*

60*

32 3/4
5
20
32 3/8
1 PIECE

38 3/4
5
20
38 3/8
1 PIECE

44 1/4
5
20
44 3/8
1 PIECE

50 1/4
5
22
50 3/8
1 PIECE

56 1/4
5
22
56 3/8
1 PIECE

62 3/8
5
27
62 1/2
2 PIECES

68 3/8
5
27
68 1/2
2 PIECES

*BHH only

Wall Mounting Sleeve Guard / Weathershield Guard


These guards are supplied with the Weathershield and Wall Sleeve. They are fabricated 11 ga. galvanized wire cage suitable
for use for OSHA protection. (Note that guard may be attached to either front or rear of wall sleeve.)
Protection that conforms to OSHA regulations should be installed when fans are located within seven (7) feet of oor and/or
working level, or within reach of personnel. Review OSHA codes for specic details.

Dimensional Data
SIZE
ASQ.
B
SCREEN

BC/BLL/BCH
24

30

36

42*

48*

54*

60*

29
1-1/2
1 PIECE

34-5/8
1-1/2
1 PIECE

40-5/8
1-1/2
1 PIECE

46-5/8
1-1/2
1 PIECE

54-3/4
1-1/2
1 PIECE

60-3/4
1-1/2
2 PIECES

66-3/4
1-1/2
2 PIECES

B
A

*BCH only

SIZE
ASQ.
B
SCREEN
*BHH only

PENNBARRY

BHM/BHH

24

30

36

42

48

54*

60*

32-3/8
1-1/2
1 PIECE

38-3/8
1-1/2
1 PIECE

44-3/8
1-1/2
1 PIECE

50-3/8
1-1/2
1 PIECE

56-3/8
1-1/2
1 PIECE

62-1/2
1-1/2
2 PIECES

68-1/2
1-1/2
2 PIECES

Options and Accessories


Breezeway

Wall Shutters

1-1/48"

Type WSR recessed gravity shutters, the most


popular form of backdraft protection, open when
the fan starts and automatically close shut when
the fan stops. These shutters are used for exhaust
only and are enclosed within a heavy, steel frame
that protects the roll-formed steel blades. Each
blade pivots freely on nylon bearings. Blades
are interconnected with one or more tie-rods
for simultaneous operation. Consult factory for
surface mount shutters, if required.

11/2
C SQ.

AIR
FLOW

EXTRUDED
VINYL

C SQ.
E SQ.

Type EBR is the motorized version of the gravity


WSR. It includes all of the WSR features plus an
enclosed actuator motor for positive opening and
closing of the shutter. The motor is eld wired in
parallel with the fan. Allow a minimum 7" between
the fan and the shutter when motorized. Larger
actuators will be provided with a transformer for
460V.

3"
E SQ.

5"

(BACK OF SHUTTER)

TYPE WSR
RECESS MOUNTING

Shutters required for supply applications are


provided as motorized center-pivot type (not
illustrated.) If standard top-pivot shutter is used
for supply applications, a eld supplied time delay
relay is strongly recommended.

Legend:
1. Flanged Steel Frame
2. Self-Acting Steel Blades
3. Mounting Holes
4. Motor Mounting Assembly

Caution: When a Breezeway fan is selected


for a supply application, fan velocities greater
than 500 FPM can pull water into the structure.
We suggest that a PennBarry Weathershield be
selected in supply applications to help prevent
water penetration when high velocity conditions
cannot be avoided.

3"
9"

5"

TYPE EBR
RECESS MOUNTING
(Specify front guard if required.)

Dimensional Data
SIZE

P SERIES

BLL/BCH/BC

10

12

16

18

20

24

24

30

36

42*

48*

54*

60*

ESQ.

17 1/2

19 1/2

25 1/4

26 3/4

29 1/4

34 3/4

30 1/2

36 1/2

42 1/2

48 1/2

56 1/2

62 1/2

68 1/2

CSQ.

15

17

22 3/4

24 1/4

26 3/4

32 1/4

28

34

40

46

54

60

66

No. of Panels

*BCH only.

SIZE

BHM/BHH
24

30

36

42

48

54*

60*

ESQ.

34 1/2

40 1/2

46 1/2

52 1/2

58 1/2

64 1/2

70 1/2

CSQ.

32

38

44

50

56

62

68

No. of Panels

*BHH only.

PENNBARRY

Options and Accessories


Breezeway

Wall Sleeves
Wall Sleeves effectively add depth to the wall where the fan and several of its
accessories will be installed. This provides more exibility and convenience
to secure these parts, as well as protection and a neat appearance. Standard
construction is galvanized steel. Standard shipment is knocked down for BHM
and BHH, or optionally available as factory assembled. Shipment for other
models is factory assembled only. A guard is provided for either front or rear
installation.

C
MIN.

ASQ.
ESQ.
WoSQ.

FAN AND WALL SHUTTER SHOWN


FOR REFERENCE ONLY

ANGLE
SUPPORT
(BY OTHERS)

Dimensional Data
SIZE
WoSQ.
ASQ.
CMIN.
D
ESQ.

P SERIES

BC/BLL/BCH

10

12

16

18

20

24

24

30

36

42*

48*

54*

60*

15 3/4

17 3/4

23 1/2

25

27 1/2

33

28 3/4

34 3/4

40 3/4

46 3/4

55

61

67

15 1/4

17 1/4

23

24 1/2

27

32 1/2

28 1/4

34 1/4

40 1/4

46 1/4

54 1/4

60 1/4

66 1/4

7 1/2

7 1/2

18 3/4

18 3/4

22 3/4

23

24 3/4

30 3/4

30 3/4

35

38

44

47 1/2

48

48

17 5/8

19 5/8

25 3/8

26 7/8

29 3/8

34 7/8

30 5/8

36 5/8

42 5/8

48 5/8

56 5/8

62 5/8

68 5/8

24

30

36

42

48

54*

60*

32 3/4

38 3/4

44 3/4

50 3/4

57

63

69

32 1/4

38 1/4

44 1/4

50 1/4

56 1/4

62 3/8

68 3/8

*BCH only

SIZE
SQ.

Wo
ASQ.
CMIN.
D
ESQ.

BHM/BHH

36

39

41

41

41

48

48

34 3/8

40 3/8

46 3/8

52 3/8

58 3/8

64 3/8

70 3/8

*BHH only

Breezex Accessories
BREEZEX
MODEL
NUMBER
BX12Q
BX14Q
BX16Q
BX16T
BX18Q
BX18T
BX20Q
BX20T
BX24Q
BX24T

MOTOR OPERATED
SHUTTER

PENNBARRY

REAR GUARD

WEATHERSHIELD

CSQ.

ESQ.

ASQ.

CSQ.

ASQ.

ASQ.

15

18

15 1/8

15 1/8

14 11/16

12 1/2

15 1/4

17 7/8

12 3/8

15

18

16 5/8

16 5/8

16 3/16

12 1/2

16 1/4

19

12 3/4

19

22

19 3/8

19 3/8

18 15/16

12 1/2

19

20

13 7/8

21

24

21 3/8

21 3/8

21 15/16

12 1/2

21

22 3/8

14 1/2

22 3/4

25 3/4

23 3/8

23 3/8

22 15/16

12 1/2

23

23 1/4

15 1/2

26 3/4

29 3/4

27 3/8

27 3/8

26 15/16

13 1/2

27

26 1/8

17 1/4

Refer to appropriate drawings on pages 3, 4 and 5.

FRONT
GUARD

Options and Accessories


Breezeway

Breezeway P Series Slip-In Fan Pak


Provides a ventilation package in one convenient and compact
assembly. The Fan Pak incorporates the Breezeway Type P
direct drive fans with their integral back guards installed in a
galvanized steel sleeve with a self-acting shutter on the exterior
face. (A motorized shutter can be substituted for the standard
shutter when desired.)
A moveable angle frame is positioned on the perimeter of
the sleeve. This adjusts to the wall thickness. When properly
fastened it secures the assembly in the wall opening. Anchor
bolts, lag screws or other appropriate fasteners should be
used to fasten the unit to the inside and outside face of the
wall or mounting frame.
MODEL

WoSQ.

ASQ.

CMIN.

P10

15 3/4

15 1/4

18 3/4

P12

17 3/4

17 1/4

14 3/4

P16

23 1/2

23

22 3/4

P18

25

24 1/2

23

P20

27 1/2

27

24 3/4

P24

33 1/4

32 1/2

24 3/4

Galv. Steel Sleeve with Type P Direct


Drive Fan and Integral Rear Guard

Wall

Movable Permeter Angle Frame


(Adjusts to Wall Thickness)

Wall Shutter
(Self Acting)

Paint and Coatings


In most cases, the standard epoxy nish is sufcient to provide
years of attractive life to your propeller fan. For those cases
where corrosive fumes are encountered or where special
protective nishes are otherwise needed, the Breezeway can
be provided with special coatings. Accessories for BHM/BHH
will be provided assembled, not knocked down, if painting is
specied.

Disconnect Switches
Safety disconnect switches are required under the National
Electric Code whenever an electric power source is controlled
from a switch or panel that is out of sight of the operated
equipment. Factory wiring is not available for explosion proof
motors.

PENNBARRY

Motor Selection
Breezeway

After choosing a fan model, it is important to review the motor


availability charts to verify that the desired voltage, phase and
motor enclosure is available. Some factors affecting motor
selection are discussed below.

Electric Power Considerations


First, determine the nature of the electric power feeding
the motor. Is it single phase or three phase power? Next,
determine the required line voltage. Is it 115V, 230V, 460V?
Then determine the frequency. Is it 60 Hz or 50 Hz?

Fixed Speed Motor Control


Two-speed motors, used in conjunction with external switches
or sensors (gas concentration, odor, temperature, etc.), are
used to adjust the airow through the ventilator by changing
from one xed speed to another. Typical two-speed motor
designation is 2-speed, 2-winding (1800/1200 Nominal RPM).
2-speed, 1-winding motors (1800/900 Nominal RPM) are
available for 3-phase power only. Dual voltage motors are not
available in a 2-speed conguration.

Variable Speed Motor Control

Environmental Considerations
Most clean air fan applications utilize Open Drip-Proof
(ODP) motors. Hazardous environments require Explosion
Proof motors. Explosion Proof motors are rated for NEMA
Class 1, Group D, Div. 1 and Class II, Groups F and G,
Div. 1 applications. Dirty environments require TE motors.
Ambient temperatures above (50 deg C) require special
motor construction. When in doubt, consult your PennBarry
representative or the factory for application assistance.
Caution: Hazardous environments also require special
fan construction suitable for the conditions.

PennBarry Lek-Trol solid state controllers are an economical


way to reduce the high speed of selected P Series motors
by as much as 50%. Check the Lek-Trol availability table
on the following page to verify suitability for the fan model
selected.
Motors suitable for use with eld supplied Frequency Inverters
can be supplied for BLL, BHM, BHH, BC and BCH models.
Contact your PennBarry representative.

High-Efficiency Motors
Motors that comply with the requirements of the energy Policy
Act of 1992 are provided when the required voltage, speed
and enclosure are applicable.

Direct Drive Motor Availability Charts


The following charts list the motors available for each of the direct drive fan models.

BC Direct Drive Motor Availability


MODEL
BC24W1
BC24W2
BC24T1
BC24T2
BC24Q
BC30W1
BC30W2
BC30W3
BC30T1
BC30T2
BC30Q1
BC30Q2
BC36W1
BC36W2
BC36T1
BC36Q
BC42W1
BC42W2
BC42T
BC48W1
BC48W2
BC48W3
BC48T1
BC48T2
BC54M
BC54W

PENNBARRY

HP
1/6
1/3
1/2
1
1 1/2
1/3
1/2
3/4
1
1 1/2
3
5
1
1 1/2
3
7 1/2
2
5
5
3
5
7 1/2
7 1/2
10
5
10

690
M

860
W

RPM
1140
T

1725
Q

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

SINGLE PHASE
OPEN
TE
EXP
115/230V
YES
YES
YES
YES
YES
YES
YES
NA
YES
YES
YES
NA
NA
NA
YES
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA

YES
NA
YES
YES
YES
NA
NA
NA
YES
YES
YES
YES
NA
NA
YES
YES
NA
NA
YES
NA
NA
NA
NA
NA
NA
NA

NA
NA
YES
YES
YES
NA
NA
NA
YES
YES
YES
YES
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA

THREE PHASE
OPEN

TE

EXP

2S1W

2S2W

YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES

NA
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES

NA
NA
YES
YES
YES
NA
NA
NA
YES
YES
YES
YES
NA
NA
YES
YES
NA
YES
NA
YES
NA
NA
NA
YES
YES
NA

NA
NA
NA
YES
YES
NA
NA
NA
YES
YES
YES
YES
NA
NA
YES
YES
NA
NA
YES
NA
NA
NA
YES
YES
NA
NA

NA
NA
NA
YES
YES
NA
NA
NA
YES
YES
YES
YES
NA
NA
YES
YES
NA
NA
YES
NA
NA
NA
YES
YES
NA
NA

Motor Selection
Breezeway

P Series Direct Drive Motor Availability


and Lek-Trol Controller Availability
MODEL

NOMINAL RPM

NOM
HP

P10VA

1/30

P10RA

1/12

P12VA

1/12

P12RA

1/4

P16VA

1/3

P16SA

1/2

P16RA

1/2

P16Q1A

3/4

P18VA

1/2

P18RA

3/4

P20TA

3/4

P20SA

P24VA

3/4

1050 1300

115/1/60 ODP

1550 1650

X
X
X
X
X
X
X
X
X
X
X (1)
X
X

(1) Nominal 1140 RPM.

(2) 50/60 Hz.

230/1/60 ODP

AVAIL

LEK-TROL

AVAIL

YES

LT30

NA

YES

LT30

USE TE

YES

LT30

NA

YES

LT50

USE TE

YES

NA

NA

YES

LT50

NA

YES

LT40

YES
YES

TE 115/200/240/1

LEK-TROL

AVAIL

LEK-TROL

NA
LT35

YES (2)

LT30/35*

NA
LT35

YES (2)

LT30/35*

USE TE

NA

YES (2)

NA

LT60

USE TE

NA

YES (2)

NA

NA

NA

NA

NA

YES

NA

NA

USE TE

NA

USE TE

NA

YES (2)

NA

YES

NA

YES

NA

NA

USE TE

NA

USE TE

NA

YES (2)

(3) 60 Hz.

NA

NA

*LT30 - 115
*LT35 - 200/240

Breezex Direct Drive Motor Availability


RPM
MODEL

1140
BX12Q

1725

1/6

BX14Q
BX16T
BX16Q

TE (A), EXPL. PROOF


115V only 115 or 230V

1/3

Y (B)

X
X
1/3

BX24T

X
X

BX24Q

A. Use TE for ODP applications.

EXPL.
PROOF

BX20T

TE (A)

X
X

BX18Q

THREE PHASE,
230/460V

X
X

BX18T

BX20Q

SINGLE PHASE

NOMINAL
HP

Y (C)

B. Uses 1/4 HP

C. Uses 1/2 HP

NEMA Motor Frame Size


SINGLE PHASE
HP

OPEN DRIP PROOF


115 V

230 V

TE
115/230

220V, 230V, 460V or 575V THREE PHASE

EXPL
PROOF

2 SPEED
2 WDG

OPEN
DRIP PRF

TE

EXPL
PROOF

2 SPEED
2 WDG

1/4

48

58

58

48/56

48

48

48

48

1/3

48/56

48/56

56

56

56

56

56

56

1/2

48/56

48/56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

56

145T

1
1 1/2

56

56

145T

184T

56

56

56

182T

145T

145T

182T

182T

56/145T

145T

145T

182T

184T

184T

184T

215T

145T

182T

182T

184T

184T

184T

184T

215T

7 1/2

213T

213T

213T

215T

10

215T

215T

215T

256T

15

254T

254T

254T

284T

20

256T

256T

256T

284T

This chart lists the NEMA frame sizes for


each combination of HP, phase, voltage,
enclosure and speed conguration. Verify
the NEMA frame size for the desired motor
and compare to the maximum motor frame
size listed on the individual fan data page in
this brochure.

On horsepowers less than 1 1/2, motor frame sizes may change due to variations in voltage, special
features and motor manufacturer. Motors shown are ball bearing, continuous duty and 1750 RPM or
1750/1140 RPM for two speed - two winding motors.

PENNBARRY

Motor Selection
Nominal Ampere Ratings

Single Phase

Three Phase

HP

115V

208V

230V

HP

208V

230V

460V

1/6

4.4

2.4

2.2

1/2

2.4

2.2

1.1

1/4

5.8

3.2

2.9

3/4

3.5

3.2

1.6

1/3

7.2

3.6

4.6

4.2

2.1

1/2

9.8

5.4

4.9

1 1/2

6.6

3/4

13.8

7.6

6.9

7.5

6.8

3.4

16

8.8

10.6

9.6

4.8

16.7

15.2

7.6

The above values of full-load currents are for motors running


at usual speeds and motors with normal torque characteristics.
Motors built for especially low speeds or high torques may
have higher full-load currents, and multi-speed motors will
have full-load current varying with speed, in which case the
nameplate current ratings shall be used.
The voltages listed are rated motor voltages. The currents
listed shall be permitted for system voltage ranges of 110 to
120 and 230 to 240 volts.
The table data shown above is from the NEC 2005 edition,
table 430-148.

7 1/2

24.2

22

11

10

30.8

28

14

15

46.2

42

21

20

59.4

54

27

25

74.8

68

34

The above values of full-load currents are typical for motors


running at speeds usual for belted motors and motors with
normal torque characteristics. Motors built for low speeds
(1200 RPM or less) or high torques may require more running
current, and multi-speed motors will have full-load current
varying with speed, in which case the nameplate current
ratings shall be used.
The voltages listed are rated motor voltages. The currents
listed shall be permitted for system voltage ranges of 230 to
240 and 440 to 480 volts.
The table data shown above is from the NEC 2005 edition,
table 430-150.

The amperages given here are approximate values only and represent averages compiled from the tables of leading motor
manufacturers. Overload relay heaters should not be selected on the basis of these tables only. Heaters must be selected in
accordance with the actual motor current as shown on the nameplate. It is also important that ambient temperatures of the
area in which the motor control is located be taken into consideration when making heater selections. Ambient compensated
overload relays are available for abnormal temperature conditions.

10

PENNBARRY

Direct Drive Dimensional Data


Breezeway

TYPE P

Dimensional Data
E

BDIA.

WALL
APPROX. PANEL
OPENING SHIP WT. GAUGE
Wo
(LBS.)

MODEL

BDIA.

CMAX.

GMAX.

P10

15

10 3/4

2 1/2

1 1/4

6 1/2

3/4

15 3/4

12

P12

17

12 1/4

3 1/4

7 1/2

1 7/8

17 3/4

14

18

P16

22 3/4 16 3/4

3 3/4

2 1/4

11 1/4

2 7/8

23 3/4

30

18

P18

24 1/4 18 3/4

3 3/4

9 1/8

3 5/8

25

40

18

P20

26 3/4 20 7/8

3 3/4

1 3/4

12 1/2

3 1/4

27 1/2

50

18

P24

32 1/4

4 1/4

2 3/8

12 7/8 4 11/16

33

76

18

25

18

All wire frames are 11 gauge.

H
H

MAX.

MAX.

BREEZEX BX

Dimensional Data

ASQ.

DIA.

WALL
APPROX.
OPENING SHIP WT.
Wo
(LBS.)

PANEL
GAUGE

MOTOR
PLATE
GAUGE

24

16

10

25

16

10

19 3/4

29

16

10

12 1/2

19 3/4

29

16

10

12 1/2

21 3/4

33

16

10

18 3/4

12 3/4

21 3/4

33

16

10

23

20 3/4

13 1/2

23 3/4

35

16

10

BX20Q

23

20 3/4

12 1/2

23 3/4

35

16

10

BX24T

27

24 3/4

13 1/2

27 3/4

43

16

10

BX24Q

27

24 3/4

13 1/8

27 3/4

43

16

10

ASQ.

BDIA.

CMAX.

BX12Q

14 1/2

12 3/4

12

15 1/4

BX14Q

16 1/2

14 3/4

12

17 1/4

BX16T

19

16 3/4

12 1/2

BX16Q

19

16 3/4

BX18T

21

18 3/4

BX18Q

21

BX20T

MODEL

ASQ.

CMAX.

BREEZEWAY BC

Dimensional Data
BC24-42
MODEL

BDIA.

CMAX.

DMAX.

WALL
OPENING
Wo

APPROX. PANEL WEB


SHIP WT. GAUGE GAUGE
(LBS.)

BC24

28

25

4 1/2

3 1/8

15

28 3/4

80

16

12

BC30

34

31

4 1/2

2 5/8

16

34 3/4

100

16

12

BC36

40

37

4 3/4

16

40 3/4

180

14

10

BC42

46

43

3 13/16

3 1/2

18

46 3/4

260

14

10

BC48

54

49

2 3/4

3 1/2

23

54 3/4

310

14

10

BC54

60

55

24

60 3/4

340

14

10

BC48-54

REVERSE VENTURI DETAIL

PENNBARRY

11

Direct Drive Fan Data


Breezeway

P Series
Features:

Exhaust or supply
Continuous duty, PSC motors
Zinc-coated wire guard designed to OSHA specications
Integral spun steel venturi with welded corners
Statically and dynamically balanced, die-formed aluminum
propeller with steel hub
Integral vibration isolators
Wide variety of available motors (Check Motor Availability
Chart Page 9)

Performance Data
MODEL

HP

TIP
MAX
RPM SPEED
WATTS
(FPM)

FAN CAPACITY IN CUBIC FEET PER MINUTE (CFM)


0.000" SP

0.100" SP

0.125" SP

0.150" SP

0.200" SP

0.250" SP

0.300" SP

0.375" SP

0.500" SP

0.625" SP

CFM SONES CFM SONES CFM SONES CFM SONES CFM SONES CFM SONES CFM SONES CFM SONES CFM SONES CFM SONES

P10VA

1/30

80

1050

2749

753

4.6

531

7.5

457

7.9

385

7.2

239

6.7

P10RA

1/12

115

1550

4058

841

5.8

699

6.5

631

7.3

570

8.5

486

10.8

425

12.5

387

12.9

P12VA

1/12

147

1050

3299 1343

10.7

1177

9.5

1123

9.9

1057

10.5

874

11.1

689

10.1

433

10.0

P12RA

1/4

174

1550

4869 1489

10.3

1367

9.8

1326

10.1

1281

10.5

1160

11.7

1046

13.2

882

15.5

P16VA

1/3

463

1050

4398 2546

9.1

2088

8.8

1859

8.7

1699

8.6

1257

8.3

P16SA

1/2

550

1300

5445 3143

13.7

2933

14.0

2856

14.1

2758

14.3

2495

14.6

2244

15.0

1982

15.3

1671

15.4

P16RA

1/2

724

1550

6492 3555

14.0

3301

14.1

3256

14.1

3211

14.2

3102

14.5

2955

15.3

2736

16.9

2514

P16Q1A

3/4

962

1650

6911

3760

16.3

3557

16.6

3508

16.7

3459

16.7

3358

16.9

3256

17.1

3123

17.6

P18VA

1/2

522

1050

4948 4210

15.2

3845

15.1

3768

15.1

3661

15.1

3370

15.3

3030

15.1

2719

P18RA

3/4

1265

1550

7304 5233

20

4971

21

4971

21

4919

21

4787

22

4633

23

P20TA

3/4

815

1140

5969 4852

16.2

4449

16.4

4318

16.5

4185

16.7

3898

17.1

3570

17.7

P20SA

1415

1300

6807 6063

22

5786

22

5692

21

5597

21

5397

21

5149

P24VA

3/4

1117

1050

6597 6562

14.6

6210

14.6

6136

14.7

6063

14.7

5917

14.7

5758

321

13.2

798

16.9

568

19.6

210

20

18.3

1979

20

1772

21

2864

18.9

2369

22

2032

24

13.6

2215

13.1

4383

25

4029

28

3547

35

3083

34

3278

18.4

2717

20

1969

24

1200

25

21

4835

21

4466

21

3909

22

3121

23

14.9

5576

15.2

5249

15.8

4065

19.3

3654

21

Performance shown is for installation Type A: Free Inlet, Free Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. The sound
ratings shown are for loudness values in fan sones at 50 (1.5m) in a hemispherical free eld per AMCA Standard 301. Values shown are for Installation Type A:
free inlet fan sone levels. Performance ratings include the effect of backguard in the airstream. For models shown on this page, the AMCA Certied Ratings Seal
applies to air and sound. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

12

PENNBARRY

Direct Drive Fan Data


Breezeway

P Series Fan Curves


The fan curves illustrated here show the range of capacities
available for P series direct drive units. Each graph shows
the performance of several models at one particular nominal
speed. Fan curves provide a quick method for selecting a fan
unit based on design point requirements.
The direct drive performance chart on the previous page
provides the tabular data (CFM and static pressure) used to
plot the fan curves. In addition, horsepower, tip speed and
sones are tabulated. Since sound is normally an important
factor in the selection of a fan, an engineer will usually

want to select the slowest unit which meets CFM and SP


requirements.
Please refer to the Motor Selection section to make sure the
motor you select meets your electrical requirements.
Note: Breezeway fans are only one component of a total
system. As such, fan performance is directly affected by the
system. It is critical that system designers determine the actual
system loss to ensure that the actual ow is specied in the
system design.

1050/1140 RPM

1300 RPM

1.200

0.900

1.100
4VA

0.900

STATIC PRESSURE - INCHES W.G.

STATIC PRESSURE - INCHES W.G.

0.800

P2

1.000

0.800
0.700

P2

0TA

0.600
0.500

P18VA

0.400
0.300
0.200

P1

P1

0V
A

0.100

P1

6VA

2V
A

1000

0.600
0.500
P1
6S
A

0.400
0.300
0.200
0.100

0.000
0

P2
0S
A

0.700

2000

3000

4000

5000

6000

0.000

7000

1000

2000

AIR FLOW - CFM

1550 RPM

4000

5000

6000

1650 RPM

0.900

1.400
8R

1.300

1.200
P1

0.700

6R

STATIC PRESSURE - INCHES W.G.

P1

0.800

0.600
0.500

A
2R

P1

0.400

A
0R

P1

STATIC PRESSURE - INCHES W.G.

3000

AIR FLOW - CFM

0.300
0.200

1.100
P1

1.000

6Q

1A

0.900
0.800
0.700
0.600
0.500
0.400
0.300
0.200

0.100

0.100
0.000

0.000
0

1000

2000

3000

4000

5000

1000

AIR FLOW - CFM

2000

3000

4000

AIR FLOW - CFM

Do not select in dashed portion of curves. These regions are not shown in the tabular data.

PENNBARRY

13

Direct Drive Fan Data


Breezeway

Breezex Reversible Fan


Features:
Field reversible supply and exhaust
Includes Reversing Switch (TE, 115V/1PH/60HZ only)
Totally Enclosed (TE) Motor or Explosion Proof motors
available (Check Motor Availability Chart Page 9)
Integral Thermal Overload Protection
Compact Panel Size
Integral spun steel venturi with welded corners
Statically and dynamically balanced, die-formed
aluminum propeller with steel hub

Performance Data (Supply Air)


FAN CAP. IN CUBIC FEET PER MIN. (CFM)
SONES
TIP
@
SPEED 0.000" SP 0.125" SP 0.250" SP 0.375" SP
(FPM)
.125"
CFM
CFM
CFM
CFM

MODEL

HP

FAN
DIA.

RPM

BX12Q

1/6

12"

1725

5423

1400

1260

1050

805

4.0

BX14Q

1/6

14"

1725

6327

2000

1780

1580

1150

11.0

BX16T

1/6

1140

4779

2255

1885

1390

650

7.2

BX16Q

1/3

1725

7231

3035

2760

2550

2250

13.0

BX18T

1/4

BX18Q

1/3

BX20T

1/4

BX20Q

1/3

BX24T

1/3

BX24Q

1/2

16"

18"

20"

24"

1140

5376

3100

2670

2100

820

8.2

1725

8135

3500

3040

2275

1400

12.8

1140

5974

3800

3160

2590

2240

9.3

1725

9039

3750

3440

3200

2560

14.0

1140

7168

4720

4540

3855

3000

14.8

1725

10847

4650

4400

3800

3480

20.0

Performance Data (Air Exhaust)


FAN CAP. IN CUBIC FEET PER MIN. (CFM)
SONES
TIP
@
SPEED 0.000" SP 0.125" SP 0.250" SP 0.375" SP
(FPM)
.125"
CFM
CFM
CFM
CFM

MODEL

HP

FAN
DIA.

RPM

BX12Q

1/6

12"

1725

5423

1125

815

675

530

4.0

BX14Q

1/6

14"

1725

6327

1565

1395

1205

920

11.0

BX16T

1/6

1140

4779

1995

1520

1000

600

7.2

BX16Q

1/3

1725

7231

2530

2345

1835

1430

13.0

BX18T

1/4

1140

5376

2365

2040

1605

625

8.2

BX18Q

1/3

1725

8135

3000

2480

1980

1285

12.8

BX20T

1/4

BX20Q

1/3

BX24T

1/3

BX24Q

1/2

16"

18"

20"

24"

1140

5974

2705

2265

2130

1835

9.3

1725

9039

3070

2835

2540

2245

14.0

1140

7168

3610

3475

2945

2295

14.8

1725

10847

3555

3365

2905

2660

20.0

Performance shown is for installation Type A: Free inlet, Free outlet. Performance ratings do not include the effects
of appurtenances in the airstream. The sone ratings shown are loudness values in fan sones at 5'0" (1.5m) in a
hemispherical free eld calculated per AMCA standard 301. Values shown are for installation Type A: Free inlet fan
sone levels.

14

PENNBARRY

Direct Drive Fan Data


Breezeway

BC Cast Aluminum Propeller Fan


Features:
Exhaust or supply
Fabricated steel power assembly
Statically and dynamically balanced, heavy duty cast aluminum
propeller with taper lock hub
Integral spun steel venturi with welded corners
TE, Explosion Proof and 2-speed motors available
(Check Motor Availability Chart Page 8)

Performance Table
RPM

TIP
SPEED
(FPM)

FAN CAPACITY IN CUBIC FEET PER MINUTE (CFM)

SONES
@
.125"

MODEL

HP

FAN
DIA.

CFM

BHP

CFM

BHP

CFM

BHP

BC24W1

1/2

24"

860

5404

3153

0.15

1988

0.16

1097

0.18

BC24W2

1/2

24"

860

5404

4444

0.40

2306

0.40

BC24T1

1/3

24"

1140

7163

4718

0.33

3957

036

3054

0.36

2273

0.38

BC24T2

24"

1140

7163

7025

0.95

5500

0.94

3800

0.94

2310

0.93

BC24Q

1 1/2

24"

1750

10996

7725

1.15

7380

1.19

6995

1.25

6500

1.28

BC30W1

1/3

30"

860

6754

5641

0.29

3660

0.31

BC30W2

1/2

30"

860

6754

7624

0.41

6372

0.44

4084

0.43

1661

0.42

BC30W3

3/4

30"

860

6754

9034

0.64

7897

0.66

6430

0.67

3238

0.67

BC30T1

30"

1140

8954

10717

0.90

9884

0.97

8969

1.01

7767

1.04

3775

0.97

23.0

BC30T2

1 1/2

30"

1140

8954

12606

1.48

11771

1.50

10922

1.52

10022

1.54

7017

1.51

24.0

BC30Q1

30"

1750

13744

13643

2.28

12782

2.34

12157

2.39

11581

2.47

10164

2.59

36.0

BC30Q2

30"

1750

13744

17110

3.04

16625

3.19

16140

3.34

15600

3.45

14405

3.58

BC36W1

36"

860

8105

11099

0.88

9337

0.92

5963

0.95

2525

1.09

BC36W2

1 1/2

36"

860

8105

13248

1.25

11249

1.34

6912

1.28

BC36T1

36"

1140

10744

18526

2.85

17232

2.94

15820

3.06

13680

3.12

6422

2.99

BC36Q

21040

7.58

0.125" SP

0.2509" SP

0.375" SP

0.500" SP
CFM

BHP

0.750" SP
CFM

BHP

13.1
13.9
18.9
20.0
5445

1.31

33.0
14.4
15.9
16.8

40.0
19.0
21.0
31.0

7 1/2

36"

1750

16496

25430

7.13

24372

7.21

23476

7.30

22719

7.40

BC42W1

42"

860

9456

20033

1.94

18114

2.01

16008

2.06

12931

2.14

48.0

BC42W2

42"

860

9456

23083

3.58

21837

3.70

20394

3.75

18525

3.76

13396

3.75

30.0

BC42T

42"

1140

12535

27644

4.38

26201

4.56

24750

4.67

23297

4.70

19880

4.87

35.0

BC48W1

48"

860

10807

25547

2.74

23003

2.85

20415

2.89

17287

2.90

8499

2.88

31.0

BC48W2

48"

860

10807

30186

3.98

27927

4.08

25555

4.17

22891

4.26

10571

4.47

34.0

BC48W3

7 1/2

48"

860

10807

33416

5.63

31631

5.73

29705

5.83

27640

5.90

22719

5.80

38.0

BC48T1

7 1/2

48"

1140

14326

35342

6.23

33384

6.44

31458

6.59

29638

6.67

25448

6.75

45.0

BC48T2

10

48"

1140

14326

41224

9.18

39622

9.31

37948

9.43

36214

9.56

32477

9.79

48.0

BC54M

54"

690

9755

34071

3.99

31816

4.04

29388

4.06

25491

4.12

12345

3.59

30.0

BC54W

10

54"

860

12158

43437

7.68

41645

7.76

39842

7.81

38091

7.83

32441

7.99

41.0

24.0

Performance shown is for installation Type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances in the airstream. The sone ratings
shown are loudness values in fan sones at 50 (1.5m) in a hemispherical free eld calculated per AMCA standard 301. Values shown are for installation Type A: Free
inlet fan sone levels.

PENNBARRY

15

Belt Drive Dimensional Data


Breezeway

MODEL BLL

MODEL BCH
E
A

A
BDIA.

DMAX.

Dimensions

Dimensions
MODEL

BDIA.

DMAX.

MODEL

BDIA.

DMAX.

BLL24

28

25

16

BCH24

28

25

16

34

31

18

2 1/2

BLL30

34

31

18

2 1/2

BCH30

BLL36

40

37

20

4 3/4

BCH36

40

37

20

4 3/4

BCH42

46

43

22

3 3/4

4 1/2

BCH48

54

49

25

2 3/4

4 3/4

BCH54

60

55

28

BCH60

66

61

28

2 3/4

MODEL BHH

MODEL BHM
D

F
E

Dimensions

16

Dimensions

MODEL

BHM24B

32

25 1/2

BHM30B

38

BHM36B

MAX.

MODEL

BDIA.

DMAX.

26

BHH24B

32

25 1/2

26

31 1/2

26

BHH30B

38

31 1/2

26

44

37 1/2

28

BHH36B

44

37 1/2

28

BHM42B

50

43 1/2

28

BHH42B

50

43 1/2

28

BHM48B

56

49 1/2

28

BHH48B

56

49 1/2

28

BHH54B

62

55 1/2

36

BHH60B

68

61 1/2

36

PENNBARRY

DIA.

Belt Drive Fan Data


Breezeway

Performance Data

Belt Drive Losses

The belt drive models shown on the following pages have


sizes and capacities ranging from below 3,000 CFM to nearly
70,000 CFM, with static pressures from 0" to above 1 1/2".
All models are available in several different horsepower sizes
with a wide range of RPM.

The AMCA Review Committee has developed the chart


shown below for the purpose of estimating belt drive losses.
To calculate total BHP (including drive losses): Find the BHP
of your operating point on the x-axis on the graph below.
Follow the vertical line to the lines indicating the range of drive
losses. Look at the y-axis on the left and nd the drive loss
percentage. Calculate the total BHP by adding the drive loss
to the operating point BHP. For BHPs below 0.3, use 30%.

Each curve graphically displays the range of capacities


available for each model, in most cases beyond the specics
shown in the tabular data. The maximum performance afforded
by each horsepower is indicated by dashed lines and the RPM
is indicated by solid lines.
Refer to the appropriate Motor Availability chart (see Motor
Selection section) to conrm available motors.
The belt drive models have graphs that show both shaded
and unshaded areas. Caution should be used when making
selections in the shaded areas.
The highest RPM shown for a specic horsepower in the
tabular data is the maximum speed that for any point along
the performance curve, the BHP will not exceed the available
horsepower.
Always consider belt drive losses into the BHP calculations
to ensure proper motor selection. PennBarry fan selection
software ALWAYS accounts for these losses. See Belt Drive
Losses section, following, for an explanation of this topic.

Caution: For totally enclosed, explosion proof, multi-speed


and all 1.0 Service Factor motors, fan BHP plus drive losses
should not exceed motor rated HP.
Note: FanSizer software incorporates a drive loss allowance when selecting a
required nominal horsepower.
Reprinted from AMCA publication 203, with the express written permission
from the Air Movement and Control Association, Inc., 30 West University Drive,
Arlington Heights, IL 60004-1983

30

Drive Loss
(% Motor Power Output)

The data provided for each belt drive model includes:


Tabular performance data
Fan curve
Dimensional and physical data

20
15
10
8
6
4
3
2
1.5
1
0.3

Note: Breezeway fans are only one component of a total system. As such,
performance is directly affected by the system. It is critical that system designers
determine actual system losses to ensure that the actual ow is specied in the
system range.

0.4

0.6 0.8

8 10

20

Motor Power Output (BHP)

Range of drive loss for standard


belts. Higher fan speeds tend to
have higher losses than lower fan
speeds at the same horsepower.

Safety Precautions for Installation


Since Breezeway fans contain rotating parts, PennBarry
recommends the following safety precautions be taken
during installation, operation and maintenance. Install FAN
GUARDS on all non-ducted fan installations to protect
people working around the fan and to protect the fan from
foreign objects coming into contact with moving parts. For
proper and safe operation, fan RPM should not exceed
that recommended in performance tables. Installations that
result in EXCESSIVE VIBRATION are unacceptable.

PENNBARRY

17

BLL 24 - Belt Drive Fan Data


Breezeway
3

1.500

28

1.400

STATIC PRESSURE - Inches W.G.

1.200

11

24

1.100

RPM
BHP

RP

10

1.000

48

RP

0.900
91

0.800

2R

25

28

PM

0.700

792

0.600

737

0.500

RP
M
RP
M

1 HP
3/4 H
P

0.400
0.300

1/2 H
P
1/3
1/4 H HP
P

0.200
0.100
0.000

Do not select shaded area.

1.300

1000

2000

3000

4000

16
5000

6000

AIR FLOW - CFM

TIP
HP RPM SPEED
0.000" SP
(FPM) Sones BHP
3043
470
2953
6.3
0.07
3431
530
3330
7.8
0.11
3690
570
3581
8.9
0.13
4078
1/4 630
3958
10.7
0.18
4467
690
4335
14.0
0.23
4661
720
4524
14.9
0.26
4771
737
4631
15.5
0.28
4855
750
4712
16.0
0.30
4985
1/3 770
4838
16.4
0.32
5127
792
4976
16.9
0.35
5179
800
5027
17.1
0.36
5341
825
5184
18.0
0.40
5503
850
5341
19.6
0.43
1/2
5665
875
5498
21
0.47
5827
900
5655
22
0.51
5904
912
5730
22
0.53
5956
920
5781
22
0.55
6118
945
5938
23
0.59
6280
970
6095
23
0.64
3/4
6442
995
6252
23
0.69
6604
1020 6409
24
0.75
6785
1048 6585
25
0.81
6863
1060 6660
26
0.84
7057
1090 6849
29
0.91
1
7186
1110 6974
30
0.96
7277
1124 7062
31
1

0.100" SP
Sones BHP
1541
6.3
0.08
2313
7.5
0.11
2762
8.7
0.14
3345
10.7
0.19
3837
13.4
0.24
4078
14.0
0.28
4209
14.4
0.30
4307
14.8
0.31
4457
15.3
0.34
4620
15.9
0.36
4678
16.1
0.37
4855
16.9
0.41
5031
18.3
0.45
5206
19.5
0.49
5381
20
0.53
5465
21
0.55
5520
21
0.56
5694
22
0.61
5866
22
0.66
6039
22
0.71
6210
23
0.76
6402
24
0.83
6484
25
0.86
6689
28
0.93
6825
29
0.98
6920
29
1.02

7000

Carbon Steel Panel = 16 gauge


Galv. Steel Web = 12 gauge
Est. Shipping Weight = 95 lbs

Wall Opening = 28 3/4 in.sq.


Wall Shutter ID = 28 in.sq.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.150" SP
0.200" SP
0.250" SP
0.300" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP

1786
7.7
0.11
2312
8.7
0.14
3009
10.7
0.19
3620
13.3
0.25
3870
13.9
0.28
4010
14.3
0.30
4116
14.6
0.31
4278
15.1
0.34
4456
15.7
0.37
4520
15.9
0.38
4714
16.7
0.41
4901
17.9
0.45
5088
19.1
0.49
5270
19.9
0.53
5355
20
0.55
5411
21
0.57
5587
21
0.61
5763
22
0.66
5938
22
0.72
6112
23
0.77
6306
24
0.83
6390
25
0.86
6597
27
0.94
6735
28
0.99
6831
29
1.02

1814
8.9
0.14
2601
10.9
0.19
3295
13.2
0.25
3618
13.8
0.28
3798
14.2
0.30
3916
14.6
0.32
4084
15.1
0.34
4266
15.6
0.37
4332
15.8
0.38
4537
16.5
0.42
4739
17.5
0.46
4940
18.7
0.50
5136
19.6
0.54
5226
20
0.56
5286
20
0.57
5473
21
0.62
5659
21
0.67
5837
22
0.72
6014
22
0.77
6211
24
0.84
6295
25
0.87
6505
27
0.94
6644
28
0.99
6742
29
1.03

2527
13.5
0.25
2912
13.9
0.28
3120
14.2
0.30
3277
14.5
0.32
3510
15.0
0.34
3753
15.6
0.37
3840
15.8
0.39
4110
16.5
0.42
4375
17.3
0.46
4598
18.1
0.50
4806
19.0
0.54
4906
19.4
0.57
4972
19.7
0.58
5177
21
0.63
5380
21
0.68
5581
21
0.73
5781
22
0.78
5996
23
0.85
6086
24
0.88
6311
26
0.95
6459
27
1.00
6563
28
1.04

2353
14.7
0.30
2532
15.0
0.32
2806
15.4
0.34
3095
15.9
0.37
3194
16.1
0.38
3500
16.7
0.42
3801
17.4
0.46
4081
17.9
0.51
4354
18.7
0.55
4484
19.1
0.57
4570
19.4
0.59
4836
20
0.63
5071
21
0.68
5280
21
0.74
5488
22
0.79
5718
23
0.86
5816
24
0.88
6059
25
0.96
6221
26
1.01
6333
27
1.05

2502
16.6
0.39
2821
17.2
0.42
3161
17.8
0.46
3482
18.2
0.50
3789
18.8
0.55
3934
19.1
0.57
4031
19.4
0.59
4321
20
0.64
4596
21
0.69
4868
21
0.74
5136
22
0.80
5432
23
0.86
5533
24
0.89
5784
25
0.97
5951
26
1.02
6066
27
1.06

Peak BHP = (RPM/941)^3


Max RPM = 1124 (1 HP)
Max. Motor Frame Size = 56

0.375" SP
Sones BHP

2855
19.4
0.55
3010
19.6
0.57
3121
19.7
0.59
3463
20
0.63
3791
21
0.68
4099
22
0.74
4403
23
0.80
4735
24
0.87
4869
24
0.90
5199
25
0.98
5416
26
1.03
5567
27
1.07

0.500" SP
Sones BHP

3405
0.87
3572
25
0.90
3982
26
0.97
4251
27
1.02
4426
27
1.07

24

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

18

PENNBARRY

Belt Drive Fan Data - BLL 30


Breezeway
21/2

STATIC PRESSURE - Inches W.G.

0.800
0.700

Do not select shaded area.

81

0R

RPM
BHP

PM

75

0.600

34

6R

PM

0.500

65

7R

PM

0.400

57

2R

531

0.300

RP

3/4

0.200
0.100

1/4

1/3
HP

1/2

1H
P

HP

HP

HP

18

0.000
0

31

34

PM

2000

4000

6000

AIR FLOW - CFM

TIP
HP RPM SPEED
0.000" SP
(FPM) Sones BHP
5331
420
3299
8.2
0.13
5648
445
3495
9.0
0.16
5838
460
3613
9.5
0.17
6029
475
3731
10.0
0.19
1/4
6219
490
3848
10.5
0.21
6409
505
3966
11.1
0.23
6600
520
4084
11.7
0.25
6739
531
4170
12.2
0.26
6854
540
4241
12.5
0.28
7108
1/3 560
4398
13.3
0.31
7260
572
4492
13.8
0.33
7488
590
4634
14.7
0.36
7742
610
4791
15.6
0.40
7996
1/2 630
4948
16.6
0.44
8186
645
5066
17.4
0.47
8339
657
5160
18.1
0.50
8377
660
5184
18.3
0.51
8567
675
5301
19.1
0.54
8821
695
5459
19.5
0.59
9011
5576
3/4 710
19.8
0.63
9265
730
5733
20
0.69
9456
745
5851
21
0.73
9595
756
5938
21
0.76
9773
770
6048
21
0.80
10027
1
790
6205
22
0.87
10281
810
6362
23
0.94

0.100" SP
Sones BHP
2695
8.6
0.13
3612
8.9
0.16
3952
9.4
0.18
4265
9.8
0.20
4565
10.4
0.23
4861
10.9
0.25
5127
11.6
0.27
5320
12.0
0.29
5476
12.3
0.30
5819
13.2
0.34
6007
13.7
0.36
6286
14.6
0.39
6594
15.6
0.43
6899
16.6
0.47
7126
17.4
0.50
7299
18.0
0.53
7341
18.2
0.53
7551
19.0
0.57
7830
19.5
0.62
8038
19.9
0.66
8314
20
0.72
8520
21
0.76
8671
21
0.80
8862
21
0.84
9134
22
0.91
9406
22
0.98

8000

10000

Carbon Steel Panel = 16 gauge


Galv. Steel Web = 10 gauge
Est. Shipping Weight = 110 lbs

Wall Opening = 34 3/4 in.sq.


Wall Shutter ID = 34 in.sq.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.150" SP
0.200" SP
0.250" SP
0.300" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
1694
1139
9.3
0.14
9.9
0.15
2296
1581
9.4
0.16
10.1
0.17
2684
1854
9.7
0.17
10.3
0.18
3217
2212
10.1
0.19
10.6
0.20
3861
2576
1404
10.5
0.22
11.1
0.21
12.3
0.23
4211
2978
1665
11.1
0.24
11.6
0.23
12.8
0.25
4543
3508
1939
11.7
0.27
12.1
0.25
13.3
0.27
4767
4029
2138
12.2
0.29
12.4
0.27
13.7
0.28
4948
4306
2344
1431
12.5
0.30
12.7
0.29
13.7
0.29
14.9
0.31
5344
4765
2835
1782
13.3
0.34
13.5
0.33
14.2
0.32
15.4
0.34
5567
5025
3123
1995
13.8
0.36
14.0
0.36
14.8
0.33
15.9
0.36
5884
5389
3676
2324
1540
14.7
0.39
14.9
0.39
15.5
0.37
16.5
0.38
17.6
0.41
6231
5787
4504
2776
1893
15.6
0.44
15.8
0.43
16.3
0.41
17.2
0.42
18.3
0.44
6567
6158
5125
3264
2249
16.6
0.48
16.7
0.48
17.2
0.47
18.1
0.45
19.3
0.48
6801
6422
5466
3621
2522
17.4
0.51
17.5
0.51
17.9
0.51
18.9
0.48
20
0.50
6988
6632
5732
4020
2762
18.0
0.54
18.0
0.54
18.5
0.54
19.5
0.51
21
0.53
7034
6684
5793
4123
2837
18.1
0.54
18.2
0.55
18.7
0.55
19.6
0.51
21
0.53
7265
6943
6097
4704
3208
19.0
0.58
19.0
0.59
19.5
0.59
20
0.56
21
0.56
7571
7270
6497
5509
3692
19.6
0.63
19.6
0.64
19.9
0.64
20
0.62
22
0.60
7799
7504
6793
5862
4067
19.9
0.67
19.9
0.68
20
0.69
21
0.67
22
0.63
8097
7814
7156
6308
4756
20
0.72
20
0.74
21
0.75
21
0.74
22
0.70
8307
8044
7420
6621
5417
21
0.77
21
0.78
21
0.79
21
0.79
22
0.75
8461
8212
7612
6844
5908
21
0.80
21
0.81
21
0.83
22
0.82
22
0.79
8656
8425
7854
7124
6239
22
0.85
22
0.85
22
0.87
22
0.87
22
0.85
8934
8728
8198
7520
6695
22
0.91
22
0.92
22
0.94
22
0.94
23
0.93
9210
9015
8512
7891
7129
23
0.98
23
0.99
23
1.01
23
1.02
23
1.01

Peak BHP = (RPM/741)^3


Max RPM = 842 (1 HP)
Max. Motor Frame Size = 56

0.375" SP
Sones BHP

1675
0.57
1729
22
0.57
1994
23
0.60
2341
23
0.64
2618
23
0.68
2980
23
0.72
3348
23
0.76
3619
24
0.79
3959
24
0.82
4436
24
0.87
5107
24
0.95

0.500" SP
Sones BHP

22

1887
0.87
2136
26
0.90
2487
26
0.96
2842
27
1.01
26

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

PENNBARRY

19

BLL 36 - Belt Drive Fan Data


Breezeway
3

0.700

40

STATIC PRESSURE - Inches W.G.

Do not select shaded area.


0.600

43/4

RPM
BHP

58

2R

0.500

54

PM

3R

PM

0.400

47
0.300

2R

41
381 0 RP
RP M
M

0.200

1H

3/4

1/2

0.100

1/4
0.000
0

2000

37

40

PM

4000

6000

1/3
HP

HP

HP

HP

8000

20
10000

12000

14000

AIR FLOW - CFM

TIP
HP RPM SPEED
0.000" SP
(FPM) Sones BHP
7455
315
2944
7.2
0.14
7691
325
3038
7.7
0.16
7904
334
3122
8.0
0.17
8141
344
3215
8.3
0.19
1/4
8425
356
3327
8.8
0.21
8662
366
3421
9.2
0.22
8898
376
3514
9.7
0.24
9017
381
3561
9.9
0.25
9111
385
3598
10.1
0.26
9230
390
3645
10.4
0.27
1/3
9466
400
3738
10.9
0.29
9703
410
3832
11.4
0.31
9940
420
3925
12.0
0.34
10176
430
4019
12.6
0.36
10413
1/2 440
4112
13.2
0.39
10886
460
4299
14.5
0.44
11170
472
4411
15.3
0.48
11407
482
4505
16.0
0.51
11596
490
4580
16.5
0.54
11833
500
4673
17.2
0.57
3/4
12070
510
4767
17.9
0.60
12425
525
4907
18.7
0.66
12851
543
5075
18.9
0.73
13017
550
5140
19.1
0.76
13490
1
570
5327
19.5
0.84
13774
582
5440
19.8
0.90

0.100" SP
Sones BHP
2524
7.7
0.16
2818
8.0
0.18
3094
8.3
0.19
3521
8.6
0.20
4075
9.0
0.21
4490
9.3
0.22
5239
9.5
0.24
5770
9.6
0.26
6038
9.7
0.27
6268
9.9
0.28
6722
10.2
0.31
7170
10.6
0.33
7619
10.9
0.36
8003
11.5
0.38
8309
12.1
0.41
8914
13.3
0.47
9272
14.2
0.50
9568
14.9
0.53
9804
15.4
0.56
10097
16.2
0.60
10369
16.8
0.63
10776
17.7
0.69
11260
18.4
0.76
11447
18.6
0.79
11979
19.5
0.87
12296
20
0.93

Carbon Steel Panel = 16 gauge


Galv. Steel Web = 10 gauge
Est. Shipping Weight = 180 lbs

Wall Opening = 40 3/4 in.sq.


Wall Shutter ID = 40 in.sq.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.150" SP
0.200" SP
0.250" SP
Sones BHP Sones BHP Sones BHP Sones BHP

2577
8.9
0.22
2936
9.4
0.24
3228
9.8
0.25
3569
10.1
0.26
3780
10.3
0.27
3961
10.4
0.27
4219
10.5
0.28
4639
10.9
0.30
5052
11.3
0.31
5821
11.6
0.34
6730
11.8
0.38
7189
12.3
0.41
8089
13.2
0.47
8626
13.8
0.51
8985
14.6
0.54
9231
15.1
0.57
9535
15.8
0.60
9837
16.5
0.64
10286
17.4
0.69
10819
18.2
0.76
11025
18.6
0.79
11588
19.5
0.88
11913
20
0.94

2798
10.4
0.29
2949
10.6
0.29
3068
10.7
0.30
3216
10.9
0.31
3509
11.4
0.33
3829
11.8
0.34
4252
12.2
0.36
4739
12.6
0.37
5158
13.1
0.39
6368
13.9
0.44
7417
14.3
0.50
7875
14.9
0.53
8238
15.3
0.56
8685
15.8
0.60
9135
16.3
0.64
9751
17.1
0.70
10302
18.0
0.77
10514
18.4
0.80
11115
19.4
0.89
11473
20
0.94

3407
13.8
0.45
3997
15.0
0.50
4361
15.6
0.52
4785
16.1
0.55
5195
16.5
0.56
5619
17.0
0.59
6036
17.5
0.61
6753
18.1
0.65
8471
18.3
0.76
8793
18.6
0.79
9701
19.4
0.89
10238
19.9
0.95

3751
17.1
0.63
4049
17.7
0.66
4344
18.2
0.68
4778
18.9
0.73
5522
19.3
0.77
5901
19.4
0.79
6740
20
0.85
7234
20
0.90

0.300" SP
Sones BHP

4295
19.8
0.85
4503
20
0.87
5087
20
0.94
5508
21
0.98

Peak BHP = (RPM/526)^3


Max RPM = 619 (1 HP)
Max. Motor Frame Size = 56

0.350" SP
Sones BHP

21

4505
1.05

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

20

PENNBARRY

Belt Drive Fan Data - BHM 24B


Breezeway
1.000

STATIC PRESSURE - Inches W.G.

26

32
Do not select shaded area.

0.875

RPM
BHP

89

2R

0.750

PM

0.625

251/2

32

77

6R

0.500

626

0.375

PM

67

4
RP RPM
M

3/4

1/2

0.250
1/4

0.125

HP

1/3

HP

HP

HP

0.000
0

1000

2000

3000

4000

5000

AIR FLOW - CFM

TIP
HP RPM SPEED
0.000" SP
(FPM) Sones BHP
5240
575
3766
8.0
0.20
1/4
5705
626
4100
9.3
0.25
5924
650
4258
10.1
0.28
1/3
6143
674
4415
10.9
0.31
6471
710
4651
13.5
0.37
6790
1/2 745
4880
14.5
0.42
7072
776
5083
14.6
0.48
7337
805
5273
15.0
0.54
7610
835
5469
15.8
0.60
3/4
7883
865
5666
17.4
0.66
8130
892
5843
18.7
0.73

0.100" SP
Sones BHP
4314
6.9
0.21
4900
8.3
0.27
5166
9.1
0.30
5429
10.0
0.33
5820
12.5
0.39
6182
13.7
0.45
6498
14.2
0.50
6791
14.6
0.56
7092
15.4
0.62
7392
16.9
0.69
7661
18.3
0.76

6000

7000

8000

Galv. Panel = 16 gauge


Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

Wall Opening = 32 3/4 in.sq.


Est. Shipping Weight = 120 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
3992
6.7
0.22
4625
3612
8.0
0.28
7.3
0.30
4906
4007
8.7
0.31
7.9
0.32
5184
4329
9.6
0.34
8.7
0.35
5591
4824
4235
12.0
0.39
10.3
0.41
9.5
0.43
5977
5273
4728
13.2
0.45
11.6
0.47
10.5
0.48
6314
5659
5142
13.8
0.51
12.3
0.53
11.4
0.54
6625
6005
5542
14.2
0.56
13.0
0.58
12.2
0.59
6933
6355
5921
15.2
0.63
14.0
0.65
13.2
0.66
7238
6700
6295
5114
16.7
0.70
15.5
0.72
14.7
0.73
12.9
0.78
7512
7005
6619
5515
18.2
0.76
17.0
0.78
16.1
0.80
13.9
0.83

Peak BHP = (RPM/934)^3


Max RPM = 946 (3/4 HP)
Max. Motor Frame Size = 184T

0.625" SP
Sones BHP

0.750" SP
Sones BHP

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

PENNBARRY

21

BHH 24B - Belt Drive Fan Data


Breezeway
1.000
Do not select shaded area.

11

0.900

M
RP

0.700

26

32

RPM
BHP

5R

98

0.600

PM

0.500

251/2

32

0R

86
PM

0.400
0.300

11

0.000

2000

4000

6000

AIR FLOW - CFM

8000

0.100

5
3

3/4
HP

H
/2

0.200

1H

STATIC PRESSURE - Inches W.G.

28

0.800

10000

12000

Galv. Panel = 16 gauge


Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

Wall Opening = 32 3/4 in.sq.


Est. Shipping Weight = 130 lbs.

Peak BHP = (RPM/962)^3


Max RPM = 1216 (1.5 HP)
Max. Motor Frame Size = 184T

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


TIP
RPM SPEED
0.000" SP
0.100" SP
0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
0.625" SP
(FPM) Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
7156
6506
6322
5734
5244
800
5236
12.9 0.432 13.3 0.464 13.1 0.473 12.4 0.505 11.9 0.527
7424
6797
6631
6064
5623
3/4 830
5432
13.6 0.482 14.1 0.515 13.9 0.524 13.3 0.557 12.9 0.580
7692
7088
6936
6391
5997
860
5629
14.4 0.536 14.9 0.571 14.8 0.579 14.2 0.613 13.8 0.636
8363
7807
7668
7192
6857
5814
935
6120
16.7 0.689 17.4 0.727 17.3 0.736 16.8 0.770 16.3 0.794 15.5 0.862
8453
7902
7765
7298
6966
5973
945
6185
17.1 0.711 17.7 0.750 17.7 0.759 17.2 0.793 16.7 0.817 15.9 0.882
8542
7997
7861
7403
7075
6103
955
6250
17.4 0.734 18.1 0.773 18.2 0.782 17.6 0.816 17.2 0.841 16.3 0.906
1
8632
8093
7958
7508
7183
6232
965
6316
17.7 0.757 18.5 0.796 18.6 0.806 18.1 0.840 17.6 0.865 16.7 0.931
8721
8188
8054
7612
7291
6361
975
6381
18.1 0.781 18.8 0.821
19
0.830 18.5 0.864 18.1 0.890 17.1 0.956
8810
8282
8150
7717
7399
6488
985
6447
18.5 0.805 19.2 0.845 19.3 0.855
19
0.889 18.6 0.915 17.6 0.981
9034
8519
8390
7976
7666
6805
5535
1010 6610
19.3 0.868
20
0.909
20
0.919
20
0.953 19.7 0.979 18.9 1.047 18.8 1.154
9213
8708
8582
8183
7879
7056
5879
1030 6741
20
0.921
21
0.963
21
0.973
21
1.006
21
1.03
19.9 1.102 19.7 1.202
9392
8897
8773
8389
8090
7304
6218
1050 6872
21
0.976
22
1.018
2
1.029
22
1.062
22
1.089
21
1.159
21
1.251
9571
9085
8963
8594
8300
7550
6553
1 1/2 1070 7003
22
1.033
23
1.076
23
1.087
24
1.119
24
1.147
24
1.218
24
1.302
9750
9272
9153
8795
8510
7791
682
1090 7134
23
1.092
24
1.136
25
1.147
25
1.179
25
1.207
25
1.279
26
1.354
9929
9460
9343
8991
8718
8012
7141
1110 7265
25
1.153
26
1.198
26
1.209
26
1.242
26
1.270
26
1.342
27
1.419
10090
9628
9513
9167
8905
8211
7372
6167
1128 7383
25
1.210
26
1.255
27
1.267
27
1.301
27
1.328
27
1.401
28
1.478
27
1.609
HP

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

22

PENNBARRY

Belt Drive Fan Data - BHM 30B


Breezeway

STATIC PRESSURE - Inches W.G.

1.200
90

1.000

Do not select shaded area.


2R

81

26

8R
PM

0.800

71
2
66 RPM
4R
PM

0.600

578

0.400

2H
P
1 1/

50
4672 RPM
RPM

3/4
1/2

1H
P

HP

HP
1/3
1/4 HP
HP

311/2

38

2H

RP

0.200

0.000

38

RPM
BHP

PM

2000

4000

6000

3
8000

10000

12000

14000

16000

AIR FLOW - CFM


Galv. Panel = 16 gauge
Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

TIP
RPM SPEED
0.000" SP
(FPM) Sones BHP
6596
400
3248
5.9
0.16
1/4
7701
467
3792
7.4
0.25
7998
485
3177
7.8
0.28
1/3
8278
502
4076
8.2
0.31
8658
525
4263
8.7
0.36
9070
1/2 550
4466
9.3
0.41
9532
578
4693
10.0
0.48
10142
615
4994
11.0
0.58
10637
3/4 645
5237
12.0
0.67
10950
664
5392
12.7
0.73
11296
685
5562
13.5
0.80
11544
1
700
5684
14.0
0.85
11742
712
5781
14.5
0.90
12203
740
6009
15.6
1.00
12781
775
6293
16.9
1.15
1 1/2
13193
800
6496
18.0
1.27
13490
818
6642
18.9
1.36
13935
845
6861
20
1.50
14265
865
7024
21
1.60
2
14595
885
7186
22
1.72
14875
902
7324
23
1.82
HP

0.100" SP
Sones BHP
4400
6.7
0.17
5988
7.9
0.27
6384
8.3
0.30
6729
8.7
0.33
7190
9.3
0.37
7683
9.9
0.43
8228
10.6
0.50
8938
11.6
0.59
9506
12.5
0.68
9858
13.1
0.75
10238
13.8
0.82
10508
14.3
0.87
10723
14.7
0.92
11223
15.7
1.03
11845
17.0
1.18
12286
18.1
1.29
12603
18.9
1.38
13077
20
1.52
13427
21
1.63
13775
22
1.75
14071
22
1.85

Wall Opening = 38 3/4 in.sq.


Est. Shipping Weight = 140 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
3413
7.6
0.19
5403
8.2
0.27
5832
8.6
0.30
6231
3853
8.9
0.33
10.8
0.37
6760
5180
9.5
0.38
10.4
0.40
7296
5831
10.1
0.43
10.8
0.45
7860
6526
5476
10.8
0.50
11.4
0.51
12.2
0.55
8592
7413
6521
11.8
0.60
12.4
0.61
12.9
0.63
9176
8114
7266
12.7
0.69
13.2
0.70
13.7
0.71
9542
8550
7726
13.3
0.75
13.8
0.76
14.2
0.77
9944
9011
8227
4761
14
0.82
14.6
0.84
14.7
0.85
17.1
0.93
10229
9316
8580
6383
14.5
0.88
15.0
0.89
15.1
0.90
16.5
0.99
10456
9558
8860
6854
14.9
0.92
15.4
0.94
15.5
0.95
16.6
1.02
10978
10119
9505
7653
15.8
1.03
16.3
1.05
16.5
1.06
17.2
1.10
11611
10810
10261
8531
17.1
1.18
17.5
1.20
17.8
1.21
18.2
1.25
12060
11299
10766
9144
6827
18.1
1.30
18.5
1.32
18.8
1.33
19
1.36
21
1.51
12382
11648
11127
9577
7769
18.9
1.39
19.2
1.41
19.4
1.42
19.7
1.45
21
1.55
12862
12168
11663
10219
8595
20
1.53
20
1.55
20
1.56
21
1.59
21
1.65
13217
12550
12057
10688
9103
21
1.64
21
1.66
21
1.67
21
1.70
22
1.75
13570
12930
12449
11152
9605
22
1.75
22
1.77
22
1.78
22
1.81
23
1.86
13870
13252
12780
11543
10026
22
1.85
22
1.87
23
1.89
23
1.92
23
1.96

Peak BHP = (RPM/700)^3


Max RPM = 956 (2 HP)
Max. Motor Frame Size = 184T

0.625" SP
Sones BHP

0.750" SP
Sones BHP

6291
2.01
8157
25
2.13

26

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

PENNBARRY

23

BHH 30B - Belt Drive Fan Data


Breezeway

STATIC PRESSURE - Inches W.G.

1.500
Do not select shaded area.

105

3R

1.250

918

1.000

RPM
BHP

PM

26

38

RP

3 HP

0.750

311/2

38

2 HP

0.500

0.250

5
0.000

3
0

2000

4000

6000

8000

10000

12000

14000

16000

18000

AIR FLOW - CFM

Galv. Panel = 16 gauge


Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

TIP
0.000" SP
HP RPM SPEED
(FPM) Sones BHP
13962
840
6821
20
1.43
14377
865
7024
21
1.57
2
14876
895
7267
23
1.73
15258
918
7454
24
1.87
15790
950
7714
25
2.07
16205
975
7917
26
2.24
16621
3 1000 8120
27
2.42
17036
1025 8323
28
2.60
17502
1053 8550
29
2.82

0.100" SP
Sones BHP
13142
21
1.47
13581
22
1.60
14106
23
1.77
14508
24
1.91
15065
25
2.11
15499
26
2.28
15932
27
2.46
16365
28
2.65
16848
30
2.87

Wall Opening = 38 3/4 in.sq.


Est. Shipping Weight = 150 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
12916
12215
11724
10103
8338
21
1.48
22
1.50
22
1.51
22
1.54
22
1.63
13369
12688
12217
10719
9030
22
1.61
22
1.63
23
1.65
23
1.67
23
1.74
13910
13252
12803
11451
9793
23
1.78
24
1.81
24
1.82
24
1.85
24
1.89
14320
13682
13249
12005
10377
24
1.92
24
1.94
24
1.96
25
1.99
25
2.03
14884
14276
13863
12765
11176
25
2.12
26
2.15
26
2.17
26
2.20
26
2.23
15322
14738
14335
13284
11790
26
2.29
26
2.32
27
2.34
27
2.37
27
2.40
15760
15197
14805
13786
12407
27
2.47
27
2.50
28
2.52
28
2.56
28
2.59
16197
15655
15272
14283
13018
28
2.66
28
2.69
29
2.71
29
2.75
29
2.78
16684
16165
15792
14837
13694
30
2.88
30
2.91
30
2.93
30
2.97
30
3.01

Peak BHP = (RPM/708)^3


Max RPM = 1105 (3 HP)
Max. Motor Frame Size = 184T

0.625" SP
Sones BHP

0.750" SP
Sones BHP

7494
2.09
9645
26
2.34
10298
27
2.48
10933
28
2.64
11568
29
2.83
12268
30
3.05

7566
29
2.76
10091
30
2.97
10895
31
3.16

26

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

24

PENNBARRY

Belt Drive Fan Data - BHM 36B


Breezeway
0.750
64

STATIC PRESSURE - Inches W.G.

0.625

58

2R

0.500

472
411

0.250

357

RPM
BHP

PM

44

PM

50

0.375

Do not select shaded area.


1R

2 HP

6R

PM

RP

27

1 1/2 HP

371/2

44

1 HP

RPM

3/4 HP

RPM

1/2 HP

0.125

1/3 HP

5
0.000

4000

8000

12000

16000

20000

AIR FLOW - CFM

Galv. Panel = 14 gauge


Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

TIP
RPM SPEED
0.000" SP
(FPM) Sones BHP
9201
300
2910
5.6
0.20
1/3
10949
357
3463
7.4
0.34
11808
385
3735
8.4
0.42
1/2
12605
411
3987
9.4
0.51
13495
440
4268
10.5
0.63
3/4
14476
472
4578
11.8
0.77
14875
485
4705
12.3
0.84
15182
1
495
4802
12.8
0.89
15519
506
4908
13.3
0.95
16255
530
5141
14.3
1.10
17022
5384
1 1/2 555
15.4
1.26
17850
582
5645
16.7
1.45
18402
600
5820
17.6
1.59
18862
615
5966
18.3
1.71
2
19322
630
6111
19.1
1.84
19660
641
6218
19.6
1.94
HP

0.100" SP
Sones BHP
3649
5.5
0.22
7970
6.6
0.35
9332
7.6
0.43
10419
8.5
0.53
11559
9.7
0.65
12665
11.0
0.80
13110
11.7
0.86
13450
12.2
0.92
13823
12.7
0.98
14631
1.12
14.0
15477
15.3
1.28
16397
16.7
1.47
17006
17.7
1.61
17511
18.5
1.73
18014
19.3
1.86
18383
19.9
1.96

Wall Opening = 44 3/4 in.sq.


Est. Shipping Weight = 180 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP

6540
6.7
0.36
8185
7.5
0.44
9498
8.3
0.53
10865
9.4
0.64
12143
10.8
0.80
12654
11.5
0.87
13030
12.0
0.93
13412
12.5
0.99
14238
13.8
1.13
15091
15.2
1.29
16003
16.7
1.48
16607
17.7
1.62
17115
18.6
1.74
17628
19.4
1.87
18003
20
1.97

3974
9.6
0.57
7683
9.5
0.68
9512
10.4
0.81
10249
10.9
0.87
10766
11.3
0.92
11328
11.9
0.98
12505
13.1
1.13
13681
14.6
1.29
14765
16.2
1.50
15477
17.3
1.65
16065
18.2
1.78
16616
19.2
1.91
16998
19.9
2.01

5505
11.8
0.86
8188
11.4
0.93
8747
11.8
0.97
9306
12.1
1.01
10778
12.9
1.14
12118
14.1
1.30
13469
15.7
1.49
14339
16.8
1.63
15053
17.8
1.76
15679
18.8
1.89
16121
19.5
2.00

4962
16.6
1.40
7231
17.1
1.62
10392
16.7
1.74
11159
17.3
1.83
11994
18.0
1.93
12691
18.5
2.03

21

Peak BHP = (RPM/495)^3


Max RPM = 665 (2 HP)
Max. Motor Frame Size = 215T

0.625" SP
Sones BHP

0.750" SP
Sones BHP

5738
2.16

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

PENNBARRY

25

BHH 36B - Belt Drive Fan Data


Breezeway
1.500
Do not select shaded area.
RPM
BHP

STATIC PRESSURE - Inches W.G.

1.250
90

1.000

75

0.750

9R

662

0.500

1R

27

44

PM

PM

371/2

44
5 HP

RP
M

3 HP
2 HP

0.250

5
3

0.000
0

4000

8000

12000

16000

20000

24000

28000

AIR FLOW - CFM

Galv. Panel = 14 gauge


Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

HP

TIP
RPM SPEED
0.000" SP
(FPM) Sones BHP
17640
600
5820
17.3
1.47
18228
620
6014
18.1
1.62
18816
640
6208
18.9
1.78
19462
662
6421
19.8
1.97
20139
685
6645
21
2.18
20727
705
6839
22
2.38
21315
725
7033
23
2.58
21756
740
7178
23
2.75
22314
759
7362
24
2.97
23226
790
7663
26
3.34
24108
820
7954
27
3.74
24990
850
8245
29
4.17
25872
880
8536
30
4.62
26489
901
8740
31
4.96

0.100" SP
Sones BHP
16310
17.8
1.50
16964
18.5
1.65
17615
19.3
1.81
18327
20
2.00
19064
21
2.22
19682
22
2.41
20299
23
2.62
20760
24
2.79
21344
25
3.01
22293
26
3.39
23210
28
3.78
24123
29
4.21
25035
31
4.67
25672
32
5.01

Wall Opening = 44 3/4 in.sq.


Est. Shipping Weight = 190 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
15889
14627
13470
9971
18.1
1.51
18.4
1.54
18.7
1.55
19.2
1.61
16557
15387
14347
11251
18.8
1.66
19.1
1.69
19.4
1.70
19.9
1.76
17220
16079
15148
12174
19.5
1.82
19.9
1.86
20
1.87
21
1.92
17946
16834
16011
13196
20
2.01
21
2.05
21
2.07
21
2.11
18699
17617
16901
14257
10010
21
2.23
22
2.26
22
2.29
22
2.33
24
2.41
19351
18292
17613
15164
12442
22
2.42
23
2.46
23
2.49
23
2.53
24
2.60
20001
18963
18303
16060
13413
23
2.63
24
2.67
24
2.70
24
2.74
25
2.81
20486
19463
18817
16724
14103
24
2.80
25
2.84
25
2.86
25
2.91
26
2.97
21098
20100
19464
17556
14986
25
3.02
26
3.05
26
3.08
26
3.13
27
3.19
22060
21134
20511
18796
16418
26
3.40
27
3.44
27
3.46
27
3.52
28
3.57
22985
22128
21516
19968
17777
28
3.79
29
3.83
29
3.86
29
3.93
30
3.98
23907
23114
22520
21105
19114
30
4.22
30
4.26
31
4.29
31
4.36
31
4.41
24826
24095
23521
22143
20427
31
4.68
32
4.72
32
4.75
32
4.83
32
4.87
25467
24778
24218
22864
21261
32
5.02
33
5.06
34
5.09
34
5.17
34
5.22

Peak BHP = (RPM/511)^3


Max RPM = 929 (5 HP)
Max. Motor Frame Size = 215T

0.625" SP
Sones BHP

0.750" SP
Sones BHP

14027
29
3.65
15431
30
4.05
16820
32
4.48
18208
33
4.94
19163
34
5.29

14229
33
4.58
16060
34
5.03
17029
35
5.37

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

26

PENNBARRY

Belt Drive Fan Data - BHM 42B


Breezeway
0.750

STATIC PRESSURE - Inches W.G.

Do not select shaded area.


RPM
BHP

0.625

576

0.500

502
0.375

2H

PM
11

/2 H

0.000
0

4000

1H
P
3/4
HP
1/2
HP
1/3
HP

279 RPM

0.125

431/2

50

396 R
PM
370 R
PM
322 R
PM

0.250

27

3H
P

RPM

456 R

50

RPM

8000

12000

5
3
16000

20000

24000

28000

AIR FLOW - CFM

Galv. Panel = 14 gauge


Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

TIP
RPM SPEED
0.000" SP
(FPM) Sones BHP
12463
260
2930
7.3
0.29
1/3
13374
279
3144
8.3
0.35
14381
300
3381
9.3
0.44
1/2
15436
322
3629
10.4
0.55
16778
350
3944
12.0
0.70
3/4
17737
370
4170
13.1
0.83
18216
380
4283
13.7
0.90
18695
1
390
4395
14.2
0.97
18983
396
4463
14.5
1.01
20134
420
4733
15.8
1.21
21092
1 1/2 440
4959
17.1
1.39
21859
456
5139
18.2
1.55
22531
470
5297
19.1
1.70
23250
485
5466
20
1.86
2
23729
495
5579
21
1.98
24065
502
5658
21
2.07
25167
525
5917
23
2.36
26126
545
6142
24
2.64
3
26845
560
6311
25
2.87
27612
576
6492
26
3.12
HP

0.100" SP
Sones BHP
7191
6.5
0.30
8659
7.5
0.36
10292
8.8
0.45
11854
10.1
0.56
13727
11.9
0.72
14950
13.2
0.84
15518
13.8
0.91
16081
14.3
0.98
16417
14.7
1.02
17749
16.1
1.21
18844
17.4
1.39
19702
18.5
1.55
20449
19.4
1.70
21243
20
1.86
21771
21
1.98
22139
21
2.07
23344
23
2.37
24385
24
2.65
25162
25
2.88
25988
26
3.13

Wall Opening = 50 3/4 in.sq.


Est. Shipping Weight = 225 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.200" SP
0.250" SP
0.300" SP
0.375" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP

8779
8.3
0.45
10477
9.7
0.55
12550
11.5
0.72
13949
12.8
0.85
14638
13.5
0.92
15266
14.2
0.99
15638
14.6
1.04
17075
16.2
1.23
18201
17.5
1.41
19093
18.6
1.56
19867
19.5
1.70
20690
20
1.86
21234
21
1.98
21609
22
2.06
22837
23
2.36
23896
24
2.65
24687
25
2.87
25526
27
3.13

10376
11.6
0.86
11145
12.3
0.92
11885
12.9
0.98
12360
13.4
1.02
14238
15.1
1.22
15682
16.7
1.42
16808
18.1
1.59
17782
19.2
1.75
18791
20
1.92
19415
21
2.03
19849
22
2.11
21242
23
2.40
22374
25
2.68
23216
26
2.90
24107
27
3.14

12097
14.4
1.24
13601
15.8
1.40
14865
17.2
1.57
15951
18.4
1.72
17040
19.8
1.90
17751
21
2.03
18244
21
2.12
19848
23
2.43
21182
25
2.72
22114
26
2.94
23099
27
3.18

12943
16.6
1.60
13992
17.6
1.72
15139
19.0
1.88
15930
20
2.00
16478
21
2.09
18215
23
2.40
19639
24
2.71
20692
25
2.95
21804
27
3.21

13791
20
2.14
15608
22
2.40
17144
24
2.67
18325
25
2.90
19564
27
3.16

Peak BHP = (RPM/388)^3


Max RPM = 583 (3 HP)
Max. Motor Frame Size = 215T

0.500" SP
Sones BHP

0.625" SP
Sones BHP

15578
27
3.25

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

PENNBARRY

27

BHH 42B - Belt Drive Fan Data


Breezeway
1.200
Do not select shaded area.
RPM
BHP

STATIC PRESSURE - Inches W.G.

1.000

27

50

0.800

683 RPM
0.600

0.400

431/2

50

5H
P

575 RPM

3H

0.200

5
3

0.000

5000

10000

15000

20000

25000

30000

35000

AIR FLOW - CFM


Galv. Panel = 14 gauge
Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

HP

TIP
RPM SPEED
0.000" SP
(FPM) Sones BHP
25530
525
5917
22
2.31
26017
535
6029
23
2.45
26746
550
6199
24
2.66
27475
565
6368
25
2.88
27962
575
6480
26
3.04
29178
600
6762
27
3.45
30393
625
7044
29
3.90
31366
645
7269
30
4.28
32338
665
7495
32
4.70
33214
683
7697
33
5.09

0.100" SP
Sones BHP
23361
23
2.36
23879
23
2.50
24653
24
2.71
25433
25
2.94
25955
26
3.09
27255
28
3.51
28547
29
3.96
29577
31
4.35
30604
32
4.76
31525
33
5.16

Wall Opening = 50 3/4 in.sq.


Est. Shipping Weight = 245 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.200" SP
0.250" SP
0.300" SP
0.375" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
22879
21213
19799
18129
15429
23
2.36
23
2.39
23
2.41
22
2.38
21
2.37
23406
21805
20484
18860
16244
23
2.50
24
2.53
23
2.55
23
2.52
22
2.51
24193
22687
21499
19941
17450
24
2.71
25
2.74
24
2.78
24
2.75
23
2.72
24977
23561
22405
20989
18635
25
2.94
25
2.96
26
3.00
25
2.99
24
2.95
25497
24141
23005
21681
19384
26
3.10
26
3.11
26
3.15
26
3.16
25
3.12
26794
25527
24488
23387
21221
28
3.52
28
3.53
28
3.56
28
3.61
27
3.56
28086
26867
25953
24908
23001
29
3.98
29
3.99
30
4.01
30
4.06
29
4.05
29130
27931
27113
26100
24387
31
4.37
31
4.38
31
4.39
31
4.44
31
4.46
30170
28989
28227
27281
25753
32
4.78
32
4.80
32
4.80
32
4.85
33
4.91
31102
29936
29194
28334
26900
33
5.17
34
5.20
34
5.20
34
5.23
34
5.31

Peak BHP = (RPM/387)^3


Max RPM = 699 (5 HP)
Max. Motor Frame Size = 215T

0.500" SP
Sones BHP

0.625" SP
Sones BHP

17224
26
3.57
19342
28
4.00
20935
30
4.39
22461
32
4.82
23788
33
5.24

18633
31
4.92
20347
33
5.22

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

28

PENNBARRY

Belt Drive Fan Data - BHM 48B


Breezeway
0.500

STATIC PRESSURE - Inches W.G.

Do not select shaded area.


RPM
BHP

56

0.375
442 RPM

0.250

3H
P

385 RPM

2H
P

349 RPM

11

/2

304 RPM
283 RPM
246 RPM

0.125

27

1/2

HP

491/2

56

HP

1H
3/4 P
HP

5
2

0.000
0

5000

10000

15000

20000

25000

30000

35000

AIR FLOW - CFM


Galv. Panel = 14 gauge
Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

TIP
RPM SPEED
0.000" SP
(FPM) Sones BHP
17535
225
2882
6.5
0.43
1/2
19171
246
3151
7.6
0.56
20652
265
3395
8.6
0.70
3/4
22055
283
3625
9.5
0.85
22990
295
3779
10.2
0.96
1
23691
304
3894
10.7
1.05
24938
320
4099
11.6
1.23
26107
1 1/2 335
4291
12.6
1.41
27198
349
4471
13.5
1.59
28445
365
4676
14.5
1.82
29225
2
375
4804
15.1
1.97
30004
385
4932
15.7
2.13
31173
400
5124
16.8
2.39
32342
415
5316
17.9
2.67
3
33511
430
5508
19.0
2.97
34446
442
5662
19.8
3.23
HP

0.100" SP
Sones BHP

13913
8.7
0.55
16061
9.2
0.69
17972
9.7
0.84
19220
10.1
0.95
20174
10.4
1.04
21854
10.9
1.23
23377
11.5
1.42
24641
12.2
1.61
26072
13.3
1.84
26959
13.9
2.00
27843
14.6
2.16
29161
15.7
2.42
30470
16.7
2.71
31737
17.9
3.01
32720
18.7
3.27

Wall Opening = 57 in.sq.


Est. Shipping Weight = 235 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.200" SP
0.250" SP
0.300" SP
0.375" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP

14144
10.0
0.68
16473
10.7
0.83
17819
11.0
0.95
18783
11.3
1.04
20470
11.8
1.21
22037
12.4
1.39
23517
12.8
1.59
25182
13.3
1.83
26178
13.7
1.99
27082
14.3
2.16
28428
15.4
2.42
29764
16.4
2.71
31090
17.4
3.01
32146
18.3
3.27

17862
14.9
1.37
19805
15.6
1.56
21638
15.7
1.79
22739
15.9
1.95
23809
16.2
2.11
25394
16.7
2.36
26955
17.2
2.64
28539
17.9
2.95
29804
18.5
3.23

20037
17.7
1.92
21473
18.1
2.09
23272
18.3
2.35
24963
18.5
2.64
26572
19.0
2.93
27843
19.4
3.19

Peak BHP = (RPM/298)^3


Max RPM = 450 (3 HP)
Max. Motor Frame Size = 215T

0.500" SP
Sones BHP

0.625" SP
Sones BHP

22557
20
2.61
24552
20
2.92
25929
21
3.18

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

PENNBARRY

29

BHH 48B - Belt Drive Fan Data


Breezeway
1.000

27

56
Do not select shaded area.

STATIC PRESSURE - Inches W.G.

0.875

RPM
BHP

0.750

621 R

PM

0.625

491/2

56
541 R

71

PM

0.500

456 RP

0.375

/2

HP

5H
P

0.250

3H

0.125
0.000
0

10000

20000

30000

AIR FLOW - CFM

TIP
RPM SPEED
0.000" SP
(FPM) Sones BHP
30576
400
5124
16.9
2.15
32105
420
5380
18.2
2.49
3
33634
440
5636
19.4
2.87
34857
456
5842
20
3.19
36309
475
6085
22
3.61
37838
495
6341
23
4.08
39367
515
6597
5
24
4.60
40514
530
6789
25
5.01
41355
541
6930
26
5.33
42807
560
7174
27
5.91
44336
580
7430
29
6.57
45865
7686
7 1/2 600
31
7.27
46629
610
7814
31
7.64
47470
621
7955
32
8.06
HP

0.100" SP
Sones BHP
27854
17.0
2.20
29500
18.3
2.54
31136
19.7
2.91
32437
21
3.23
33975
22
3.65
35586
24
4.12
37191
25
4.63
38397
26
5.05
39281
27
5.36
40803
28
5.95
42401
29
6.60
43995
31
7.31
44790
32
7.68
45663
33
8.10

40000

50000

Galv. Panel = 14 gauge


Galv. Mtr. Plate = 12 gauge
Galv. Structure = 12 gauge

Wall Opening = 57 in.sq.


Est. Shipping Weight = 255 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.125" SP
0.200" SP
0.250" SP
0.300" SP
0.375" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
27180
24367
20747
17.0
2.21
17.1
2.20
17.3
2.15
28881
26638
23551
19909
18.4
2.55
18.5
2.54
18.7
2.48
19.2
2.50
30544
28614
26332
22985
19.8
2.93
20
2.92
20
2.92
21
2.86
31866
30030
28331
25224
21
3.25
21
3.26
21
3.26
22
3.16
33427
31697
30349
27882
23178
22
3.67
23
3.69
23
3.68
23
3.64
24
3.62
35061
33434
32263
30476
26131
24
4.14
24
4.18
24
4.16
24
4.17
25
4.06
36685
35156
34031
32689
28930
25
4.65
26
4.71
26
4.69
26
4.69
27
4.57
37899
36426
35345
34248
31025
26
5.07
27
5.13
27
5.12
27
5.10
28
5.05
38786
37344
36303
35232
32527
27
5.38
28
5.45
28
5.45
28
5.43
29
5.43
40315
38921
37948
36913
34884
28
5.96
29
6.03
29
6.05
30
6.03
30
6.04
41918
40572
39667
38668
36987
30
6.61
31
6.69
31
6.73
31
6.71
32
6.69
43527
42214
41347
40408
38959
31
7.32
32
7.39
33
7.44
33
7.44
33
7.40
44330
43032
42180
41273
39848
32
7.69
33
7.76
34
7.81
34
7.82
34
7.79
45211
43930
43093
42221
40821
33
8.11
34
8.18
35
8.23
35
8.25
35
8.22

Peak BHP = (RPM/307)^3


Max RPM = 624 (7.5 HP)
Max. Motor Frame Size = 215T

0.500" SP
Sones BHP

0.625" SP
Sones BHP

21858
32
5.05
25495
31
5.34
28531
32
5.91
31355
34
6.51
34154
35
7.26
35549
36
7.69
37068
37
8.19

27558
39
7.29
29378
39
7.66
31169
40
8.07

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

30

PENNBARRY

Belt Drive Fan Data - BHH 54B


Breezeway
2.000

62

STATIC PRESSURE - Inches W.G.

Do not select shaded area.


1.750

35

RPM
BHP

1.500

60

8R

1.250

55

PM

1.000

48

0.750

2R

PM
10 H
P

PM

7 1/2

405

RP
M
353
R
P
320
M
RPM
27
260 9 RPM
RPM

0.500
0.250

HP

5 HP

5
3

3/4 HP
0.000

10000

3
2 H HP
1 HP 1 1/2 P
HP
20000

30000

40000

50000

AIR FLOW - CFM

HP

TIP
RPM SPEED
0.000" SP
(FPM) Sones BHP

0.125" SP
Sones BHP

20273
9.4
0.62
21963
10.8
0.79
22807
11.5
0.88
23568
12.2
0.97
24919
13.5
1.15
26186
14.7
1.33
27031
15.5
1.47
28298
16.8
1.68
29143
17.7
1.84
29819
18.4
1.97
31255
19.9
2.26
32522
21
2.55
33367
22
2.76
34211
22
2.97
35901
24
3.43
37168
25
3.81
38435
27
4.21
39702
28
4.64
40716
30
5.01
42236
31
5.59
43503
33
6.11
44771
35
6.66
46038
37
7.24
46629
37
7.52
47305
39
7.85
48150
40
8.28
48994
41
8.72
49839
43
9.18
50684
45
9.66
51360
46
10.05

13846
9.3
0.67
16686
10.7
0.85
17862
11.4
0.95
18956
12.1
1.05
20748
13.5
1.24
22338
14.7
1.44
23335
15.5
1.58
24816
16.7
1.80
25794
17.6
1.96
26572
18.4
2.09
28212
19.9
2.40
29641
21
2.69
30581
22
2.90
31517
23
3.12
33377
24
3.59
34763
26
3.98
36143
27
4.39
37516
29
4.83
38611
30
5.21
40247
32
5.80
41580
33
6.33
42902
35
6.88
44220
37
7.47
44835
38
7.76
45536
39
8.09
46412
41
8.52
47287
42
8.97
48160
44
9.43
49033
45
9.91
49731
47
10.31

240

3458

260

3747

270

3891

279

4020

295

4251

1 1/2 310

4467

320

4611

335

4827

345

4971

353

5087

370

5332

385

5548

395

5692

405

5836

425

6124

440

6340

455

6557

470

6773

482

6946

500

7205

3/4

515

7421

7 1/2 530

7637

545

7853

552

7954

560

8070

570

8214

580

8358

590

8502

600

8646

608

8761

10

551/2

62

2R

Galv. Panel = 14 gauge


Galv. Mtr. Plate = 10 gauge
Galv. Structure = 12 gauge

Wall Opening = 63 in.sq.


Est. Shipping Weight = 430 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.250" SP
0.375" SP
0.500" SP
0.625" SP
0.750" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP

9672
13.1
1.23
13544
14.3
1.45
15836
15.1
1.60
18801
16.4
1.83
20561
1.74
1.99
21732
18.1
2.13
23868
19.6
2.45
25647
21
2.76
26861
22
2.98
28023
23
3.21
30180
26
3.71
31751
27
4.11
33245
28
4.53
34726
30
4.97
35903
31
5.34
37655
33
5.94
39104
35
6.47
40544
37
7.03
41969
39
7.63
42628
40
7.92
43379
41
8.26
44315
42
8.70
45248
44
9.16
46178
46
9.63
47106
47
10.11
47847
49
10.51

10459
17.8
2.14
14133
19.2
2.44
17818
21
2.78
20090
22
3.01
22082
23
3.25
25594
25
3.73
27673
27
4.13
29448
29
4.56
31225
30
5.03
32683
31
5.42
34753
33
6.05
36372
35
6.61
37975
37
7.20
39497
39
7.80
40194
40
8.09
40988
41
8.43
41976
42
8.87
42960
44
9.33
43940
46
9.80
44915
48
10.29
45693
49
10.69

11754
3.25
15735
24
3.70
19524
26
4.14
22949
28
4.60
25918
29
5.07
28044
31
5.45
30842
33
6.06
32784
35
6.62
34541
37
7.21
36335
39
7.84
37187
40
8.14
38154
41
8.50
39331
42
8.96
40417
44
9.44
41497
46
9.93
42570
48
10.44
43425
49
10.87

Peak BHP = (RPM/273)^3


Max RPM = 623 (10 HP)
Max. Motor Frame Size = 284T

0.875" SP
Sones BHP

1.000" SP
Sones BHP

16686
7.82
18122
37
8.07
20234
38
8.46
22838
39
8.96
25350
41
9.47
27654
43
10.00
29928
45
10.54
31726
46
10.99

17516
9.46
19344
42
9.85
21981
44
10.41
24064
45
10.86

22

13413
4.59
16236
28
4.99
19369
29
5.42
23683
32
6.09
27069
34
6.68
29784
36
7.26
32424
38
7.87
33507
39
8.16
34618
40
8.52
35969
42
8.98
37149
43
9.45
38320
45
9.95
39482
47
10.46
40462
48
10.88
27

14887
6.08
17823
32
6.57
21732
34
7.21
25320
37
7.88
26917
38
8.20
28723
39
8.58
30734
41
9.05
32522
42
9.52
34290
44
9.99
36038
46
10.49
37167
47
10.91
31

36

40

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

PENNBARRY

31

BHH 60B - Belt Drive Fan Data


Breezeway
1.750
Do not select shaded area.

STATIC PRESSURE - Inches W.G.

53
48

1.000
42

PM

5R

PM

68

PM

0.750
356

7 1/2
RP

HP

5 HP

310
281 RPM
R
245 PM
228 RPM
RPM

3 HP
2 HP
1 HP 1 1/2 H
P
3/4 HP

0.000
0

10000

20000

30000

40000

50000

60000

AIR FLOW - CFM

HP

TIP
RPM SPEED
0.000" SP
(FPM) Sones BHP

0.125" SP
Sones BHP

22971
9.8
0.62
24940
11.3
0.79
25706
11.9
0.86
26800
12.8
0.98
28440
14.2
1.17
29534
15.1
1.31
30737
16.2
1.48
31722
17.1
1.62
32816
18.0
1.80
33910
19.1
1.98
35551
20
2.28
36644
21
2.50
37738
23
2.73
38942
24
3.00
40473
26
3.37
42114
28
3.80
43755
29
4.26
45395
30
4.75
46271
31
5.03
48130
33
5.66
49771
35
6.26
50865
36
6.69
51959
38
7.13
53053
38
7.59
54146
39
8.07
55240
40
8.56
56334
41
9.08
57428
43
9.62
57975
43
9.90
58413
44
10.13

13646
9.9
0.66
17920
11.4
0.84
19088
12.0
0.92
20709
12.9
1.04
22938
14.3
1.24
24360
15.2
1.39
25903
16.2
1.57
27132
17.1
1.72
28483
18.1
1.91
29822
19.1
2.10
31808
21
2.42
33118
22
2.65
34366
23
2.88
35715
24
3.16
37421
27
3.53
39237
28
3.97
41042
29
4.44
42837
30
4.94
43790
31
5.23
45809
33
5.87
47543
35
6.48
48684
36
6.91
49824
38
7.35
50962
38
7.81
52098
39
8.30
53233
40
8.80
54366
41
9.33
55497
43
9.87
56062
43
10.15
56514
44
10.38

210

3356

228

3643

235

3755

245

3915

260

4155

1 1/2 270

4315

281

4490

290

4634

300

4794

3/4

310

4954

325

5194

335

5353

345

5513

356

5689

370

5913

385

6152

400

6392

415

6632

423

6760

440

7031

455

7271

7 1/2 465

7431

475

7591

485

7750

495

7910

505

8070

515

8230

525

8390

530

8469

534

8533

611/2

10 HP

3R

0.250

35

4R

1.250

0.500

68

RPM
BHP

1.500

10

Galv. Panel = 14 gauge


Galv. Mtr. Plate = 10 gauge
Galv. Structure = 12 gauge

Wall Opening = 69 in.sq.


Est. Shipping Weight = 460 lbs.

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


0.250" SP
0.375" SP
0.500" SP
0.625" SP
0.750" SP
Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP

7039
14.4
1.26
8721
15.4
1.37
13611
16.5
1.57
17165
17.3
1.74
20158
18.3
1.95
22604
19.3
2.14
25787
21
2.43
27430
22
2.66
29049
23
2.90
30753
25
3.18
32769
27
3.58
34896
29
4.04
36989
30
4.53
39032
31
5.05
40112
32
5.35
42387
34
6.01
44374
36
6.64
45690
38
7.08
46998
38
7.54
48244
39
8.02
49473
40
8.51
50697
41
9.01
51917
42
9.54
53133
44
10.19
53739
44
10.38
54224
45
10.61

9625
2.41
11830
21
2.59
17018
22
2.91
21343
24
3.21
25420
26
3.66
28868
28
4.08
31906
30
4.53
34361
32
5.05
35652
33
5.34
38243
35
6.01
40397
37
6.65
41818
38
7.11
43228
40
7.58
44627
41
8.07
46000
42
8.58
47361
43
9.10
48714
44
9.65
50058
45
10.22
50728
46
10.51
51262
46
10.74

Peak BHP = (RPM/240)^3


Max RPM = 545 (10 HP)
Max. Motor Frame Size = 284T

0.875" SP
Sones BHP

1.000" SP
Sones BHP

12956
8.17
14457
38
8.55
16290
39
8.95
19170
41
9.38
25029
43
10.20
27189
44
10.54
28771
44
10.80

13321
9.84
14831
42
10.26
15589
43
10.48
16301
44
10.66

20

10303
3.60
13045
25
3.94
20298
28
4.53
25852
30
5.10
28149
31
5.45
32323
34
6.11
35623
36
6.68
37356
38
7.11
38994
39
7.57
40614
40
8.05
42219
42
8.55
42715
43
9.09
45158
44
9.64
46591
46
10.22
47303
46
10.52
47871
47
10.76
23

11718
5.07
13036
29
5.29
18846
32
5.90
25763
34
6.69
29197
36
7.19
32061
38
7.72
34588
39
8.22
36818
41
8.68
39019
42
9.15
40959
44
9.66
42606
45
10.23
43423
46
10.52
44074
47
10.76
28

12895
6.68
14568
34
7.01
17146
36
7.38
22517
37
8.01
26877
39
8.61
30715
41
9.17
33599
43
9.81
36441
44
10.47
37599
45
10.74
38497
46
10.95
33

36

41

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

32

PENNBARRY

Belt Drive Fan Data - BCH 24


Breezeway
3

STATIC PRESSURE - Inches W.G.

2.400

28

Do not select shaded area.

RPM
BHP

2.000
16

59

1.600

RP

28

15

05

1.200

M
13
1
12 0 RP
22 M
RP
M
106
3R
924 PM
858 RP
RP M
M

0.800

0.400

2 HP
1 1/

2000

16

2H

3/4

1/3
1
1/4 HP HP /2 HP

0.000
0

25

RP

4000

HP

1H

6000

AIR FLOW - CFM

8000

10000

Carbon Steel Panel = 16 gauge


Carbon Stl. Mtr. Plate = 10 gauge
Carbon Steel Tube = 16 gauge

Wall Opening = 28 3/4 in.sq.


Wall Shutter ID = 28 in.sq.
Est. Shipping Weight = 100 lbs.

Peak BHP = (RPM/1108)^3


Max RPM = 1659 (2 HP)
Max. Motor Frame Size = 145T

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


TIP
0.100" SP
0.125" SP
0.150" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
0.625" SP
0.750" SP
RPM SPEED 0.000" SP
(FPM) Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
2851
515
3236
5.6
0.06
3516
2617
2075
635
3990
8.3
0.11
8.0
0.12
8.1
0.12
1/4
4429
3851
3636
3402
2586
800
5027
12.5 0.22 12.2 0.24 12.2 0.24 12.1 0.25 12.2 0.24
4751
4210
4059
3845
3295
2446
858
5391
13.7 0.28 13.4 0.29 13.3 0.30 13.3 0.30 13.3 0.30 13.7 0.29
4817
4284
4145
3935
3434
2595
870
5466
14.0 0.29 13.7 0.31 13.6 0.31 13.5 0.31 13.6 0.31 13.9 0.31
5039
4528
4403
4231
3809
3086
1/3 910
5718
15.0 0.33 14.7 0.35 14.7 0.35 14.6 0.35 14.6 0.36 14.8 0.35
5116
4612
4489
4332
3930
3261
924
5806
15.4 0.34 15.1 0.37 15.0 0.37 14.9 0.37 15.0 0.38 15.1 0.37
5149
4649
4526
4376
3977
3335
930
5843
15.6 0.35 15.2 0.37 15.2 0.37 15.1 0.38 15.1 0.38 15.3 0.37
5537
5065
4956
4842
4510
4102
1/2 1000 6283
16.9 0.44 16.7 0.46 16.6 0.46 16.6 0.46 16.4 0.47 16.6 0.48
5886
5434
5338
5231
4974
4625
3147
1063 6679
18.2 0.52 18.0 0.55 17.9 0.56 17.9 0.56 17.8 0.56 17.9 0.57 18.5 0.56
5924
5475
5379
5274
5025
4679
3233
1070 6723
18.4 0.53 18.2 0.56 18.1 0.57 18.1 0.57 18.0 0.57 18.0 0.58 18.7 0.57
6423
5998
5909
5820
5624
5355
4337
2659
1160 7288
21
0.68
21
0.71
21
0.72
21
0.73
20
0.73
20
0.74
21
0.73
22
0.75
3/4
6644
6228
6143
6057
5871
5645
4800
3265
1200 7540
22
0.75
22
0.78
22
0.79
22
0.80
22
0.80
22
0.81
22
0.83
23
0.81
6766
6355
6271
6187
6007
5802
5000
3566
1222 7678
23
0.79
22
0.83
22
0.84
22
0.84
22
0.85
22
0.85
23
0.87
23
0.85
6810
6401
6318
6234
6056
5860
5072
3665
1230 7728
23
0.81
22
0.84
22
0.85
22
0.86
22
0.86
22
0.87
23
0.89
23
0.86
6921
6516
6434
6352
6178
5996
5250
3909
1250 7854
23
0.85
23
0.88
23
0.89
23
0.90
23
0.91
23
0.91
23
0.93
24
0.91
1
7143
6745
6666
6586
6422
6245
5573
4403
1290 8105
24
0.93
24
0.97
24
0.98
24
0.94
24
1.00
24
1.00
24
1.02
25
1.00
7253
6859
6781
6703
6543
6369
5727
4652
3173
1310 8231
25
0.98
24
1.01
24
1.02
25
1.03
25
1.04
25
1.04
25
1.07
26
1.04
26
1.07
7309
6917
6839
6761
6603
6431
5803
4776
3325
1320 8294
25
1.00
25
1.04
25
1.05
25
1.05
25
1.07
25
1.07
25
1.09
26
1.07
27
1.09
7586
7202
7127
7052
6902
6739
6181
5365
4034
1370 8608
27
1.12
27
1.16
27
1.17
27
1.17
27
1.19
27
1.19
27
1.22
27
1.22
28
1.19
1 1/2
8029
7660
7586
7515
7373
7227
6771
6122
5020
3703
1450 9111
31
1.33
31
1.37
31
1.38
31
1.39
31
1.40
31
1.42
31
1.43
31
1.46
31
1.42
32
1.44
8333
7978
7900
7831
7695
7559
7166
6554
5687
4471
1505 9456
33
1.48
33
1.52
33
1.53
33
1.54
33
1.56
33
1.58
33
1.59
33
1.62
34
1.60
35
1.58
8416
8064
7985
7918
7783
7648
7273
6669
5862
4655
1520 9550
34
1.53
34
1.57
34
1.58
34
1.59
34
1.61
34
1.63
34
1.63
34
1.67
34
1.66
35
1.63
8582
8237
8156
8090
7957
7825
7463
6897
6205
5018
1550 9739
34
1.62
34
1.66
34
1.67
34
1.68
34
1.70
34
1.72
34
1.73
34
1.77
35
1.78
35
1.73
2
8859
8525
8441
8376
8248
8119
7774
7272
6656
5643
1600 10053
35
1.78
35
1.83
35
1.84
35
1.85
35
1.87
35
1.89
35
1.90
35
1.94
35
1.96
36
1.90
9186
8864
8783
8713
8589
8465
8137
7708
7146
6351
1659 10424
37
1.99
37
2.03
37
2.04
37
2.05
37
2.08
37
2.10
37
2.12
37
2.15
37
2.18
37
2.15
HP

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

PENNBARRY

33

BCH 30 - Belt Drive Fan Data


Breezeway
21/2

2.400

34

STATIC PRESSURE - Inches W.G.

2.200

Do not select shaded area.


RPM
BHP

2.000
1.800

14

98

1.600

RP

1.400

13

06

1.200

11

84

1.000

0.600
0.400
0.200

RP

3H
P

1/4 HP

0.000
0

31

103
1
962 RPM
RP
M
837
727 RPM
RPM
676
RPM

0.800

34
RP

2000

4000

1/2 H
P

6000

2H
P
11
1 HP /2 HP
3/4 H
P
8000

AIR FLOW - CFM

18

10000

12000

14000

Carbon Steel Panel = 16 gauge


Carbon Stl. Mtr. Plate = 10 gauge
Carbon Steel Tube = 16 gauge

Wall Opening = 34 3/4 in.sq.


Wall Shutter ID = 34 in.sq.
Est. Shipping Weight = 165 lbs.

Peak BHP = (RPM/877)^3


Max RPM = 1498 (3 HP)
Max. Motor Frame Size = 145T

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


TIP
0.100" SP
0.125" SP
0.150" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
0.625" SP
0.750" SP
RPM SPEED 0.000" SP
(FPM) Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
3891
410
3220
5.9
0.07
4555
480
3770
7.7
0.10
1/4
5884
4335
3853
3247
620
4869
12.0 0.23 13.0 0.23 13.9 0.22 13.4 0.23
6415
5035
4625
4171
676
5309
13.9 0.29 14.6 0.30 15.2 0.29 16.2 0.29
6543
5083
4676
4233
680
5341
14.0 0.30 14.8 0.30 15.3 0.30 16.3 0.29
1/3
6899
5637
5276
4886
3951
727
5710
15.7 0.36 16.3 0.37 16.8 0.37 17.5 0.36 17.8 0.37
6927
5672
5314
4926
4005
730
5733
15.8 0.37 16.4 0.38 16.9 0.37 17.6 0.37 18.0 0.38
1/2
7943
6957
6583
6275
5609
4817
837
6574
20
0.55
20
0.57
21
0.57
21
0.57
22
0.55
23
0.56
7971
6993
6618
6310
5649
4865
840
6597
20
0.56
20
0.58
21
0.58
21
0.57
22
0.56
23
0.57
3/4
9129
8335
8089
7753
7192
6618
4798
962
7556
26
0.84
26
0.86
26
0.87
26
0.87
27
0.86
28
0.85
29
0.87
9205
8421
8177
7851
7287
6721
4946
970
7618
26
0.86
26
0.88
26
0.89
26
0.89
27
0.88
28
0.87
29
0.89
9395
8634
8395
8096
7525
6978
5311
990
7775
27
0.92
27
0.94
27
0.95
27
0.95
28
0.94
29
0.93
30
0.94
1
9585
8847
8613
8339
7760
7233
5655
1010 7933
28
0.97
28
0.99
28
1.00
28
1.01
29
1.00
30
0.99
32
0.99
9784
9069
8840
8592
8006
7498
5994
1031 8097
29
1.04
29
1.06
29
1.07
29
1.07
30
1.07
31
1.05
33
1.04
9869
9164
8937
8700
8110
7611
6138
1040 8168
30
1.06
30
1.08
30
1.09
30
1.10
30
1.10
31
1.08
34
1.07
10391
9739
9527
9311
8757
8272
6986
1095 8600
33
1.24
32
1.26
32
1.27
32
1.28
32
1.28
33
1.27
37
1.23
1 1/2
10819
10204
10005
9798
9310
8803
7598
6076
1140 8954
35
1.40
35
1.42
35
1.43
35
1.44
35
1.45
36
1.44
39
1.40
39
1.44
11236
10658
10469
10270
9843
9314
8180
6817
1184 9299
38
1.57
38
1.58
38
1.60
38
1.61
37
1.62
38
1.62
41
1.58
43
1.59
11293
10719
10532
10335
9915
9383
8258
6913
1190 9346
38
1.59
38
1.61
38
1.62
38
1.63
38
1.65
38
1.65
41
1.60
44
1.61
11862
11333
11155
10973
10595
10108
9023
7862
6343
2 1250 9817
42
1.85
41
1.85
41
1.87
41
1.88
41
1.91
41
1.91
44
1.87
48
1.82
46
1.91
12394
11904
11733
11563
11202
10791
9713
8634
7334
1306 10257
45
2.11
45
2.11
45
2.13
45
2.14
44
2.17
44
2.18
47
2.15
50
2.10
51
2.14
12479
11995
11826
11656
11299
10899
9821
8755
7480
1315 10328
46
2.15
45
2.15
45
2.17
45
2.18
45
2.21
45
2.23
47
2.20
51
2.15
52
2.18
12906
12441
12287
12124
11783
11435
10356
9353
8200
6777
1360 10681
48
2.38
48
2.38
48
2.39
48
2.41
48
2.44
48
2.46
50
2.44
53
2.39
57
2.38
54
2.46
13476
13030
12900
12743
12423
12090
11058
10123
9106
7861
3 1420 11153
52
2.71
52
2.71
52
2.72
52
2.73
52
2.77
52
2.79
53
2.79
56
2.74
60
2.68
60
2.76
13855
13422
13307
13155
12846
12523
11522
10629
9651
8508
1460 11467
55
2.94
54
2.94
54
2.95
54
2.97
54
3.00
54
3.03
55
3.04
58
2.99
62
2.93
64
2.96
14216
13793
13687
13544
13247
12932
11975
11096
10161
9113
1498 11765
57
3.18
57
3.18
57
3.18
57
3.20
57
3.23
57
3.26
57
3.29
60
3.24
64
3.19
68
3.17
HP

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

34

PENNBARRY

Belt Drive Fan Data - BCH 36


Breezeway
2.400

STATIC PRESSURE - Inches W.G.

2.200

40

Do not select shaded area.

2.000

12

37

1.800

4 3/4

RPM
BHP

RP

1.600

104

2R

1.400

40

PM

1.200
908

1.000

824

0.800

RPM

RPM

717
R
669 PM
RPM
582 R
PM

0.600
0.400

3H
P
2H
11
P
1 H /2 HP
3/4
P
1/2 H HP
P

0.200

20

0.000
0

37

5H
P

4000

8000

12000

16000

AIR FLOW - CFM

20000

24000

Carbon Steel Panel = 16 gauge


Carbon Stl. Mtr. Plate = 10 gauge
Carbon Steel Tube = 16 gauge

Wall Opening = 40 3/4 in.sq.


Wall Shutter ID = 40 in.sq.
Est. Shipping Weight = 195 lbs.

Peak BHP = (RPM/676)^3


Max RPM = 1237 (5 HP)
Max. Motor Frame Size = 184T

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


TIP
0.100" SP
0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
0.625" SP
0.750" SP
1.000" SP
RPM SPEED 0.000" SP
(FPM) Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
7092
4515
2979
370
3487
6.5
0.13
6.3
0.15
6.3
0.14
9009
7349
6728
3907
1/2 470
4430
9.6
0.27
8.8
0.30
8.9
0.30
8.9
0.28
11156
9923
9564
8148
7038
582
5485
13.8 0.50 12.8 0.55 12.6 0.56 12.3 0.57 12.3 0.56
11310
10099
9744
8381
7303
590
5561
14.1 0.52 13.2 0.57 12.9 0.58 12.5 0.60 12.5 0.59
3/4
12824
11791
11496
10499
9638
6917
669
6305
17.3 0.76 16.5 0.82 16.2 0.83 15.2 0.86 15.0 0.87 15.0 0.84
13035
12021
11736
10764
9950
7415
680
6409
17.7 0.80 16.9 0.86 16.7 0.87 15.6 0.90 15.4 0.91 15.4 0.89
1
13744
12790
12533
11648
10982
8759
4743
717
6758
19.3 0.94 18.6 1.00 18.4 1.02 16.8 1.05 16.6 1.07 16.8 1.06 16.0 0.95
13802
12852
12596
11719
11055
8859
4855
720
6786
19.4 0.95 18.7 1.02 18.5 1.03 17.0 1.06 16.7 1.08 16.9 1.07 16.1 0.96
14185
13265
13016
12184
11544
9478
5959
740
6974
20
1.03 19.6 1.10 19.4 1.11 17.9 1.15 17.4 1.17 17.5 1.17 16.9 1.09
14760
13882
13643
12858
12269
10361
7869
4152
7257
1 1/2 770
22
1.16
21
1.23
21
1.25 19.5 1.29 18.6 1.31 18.4 1.32 18.3 1.28 17.2 1.17
15336
14496
14266
13525
12985
11246
9137
5242
800
7540
23
1.31
22
1.38
22
1.39
21
1.44 19.8 1.46 19.2 1.49 19.7 1.45 18.2 1.32
15796
14986
14762
14054
13546
11936
9984
6433
824
7766
24
1.43
23
1.50
23
1.52
22
1.56
21
1.59 19.9 1.62
21
1.60 19.1 1.49
15911
15108
14886
14186
13682
12106
10184
6847
830
7823
24
1.46
23
1.53
23
1.55
23
1.60
21
1.62
20
1.66
21
1.64 19.4 1.54
16294
15514
15297
14624
14132
12670
10811
8236
4773
850
8011
25
1.57
24
1.64
24
1.66
24
1.71
22
1.74
21
1.78
21
1.77
21
1.70 19.1 1.57
2
16869
16120
15913
15277
14801
13495
11692
9655
5879
880
8294
26
1.74
26
1.82
25
1.84
25
1.89
24
1.92
22
1.97
22
1.97
22
1.93
20
1.76
17406
16680
16485
15876
15421
14180
12523
10718
7416
908
8558
27
1.91
27
1.99
27
2.01
26
2.07
25
2.10
23
2.16
23
2.17
24
2.14
21
2.01
17636
16919
16729
16128
15686
14471
12876
11120
8248
920
8671
28
1.99
27
2.07
27
2.09
27
2.15
26
2.18
23
2.24
23
2.26
25
2.23
22
2.13
18019
17318
17136
16548
16124
14954
13456
11780
9493
940
8859
29
2.12
28
2.20
28
2.23
28
2.28
27
2.32
24
2.38
24
2.41
25
2.39
24
2.32
18594
17915
17744
17174
16779
15670
14307
12667
10811
5115
970
9142
3
30
2.33
30
2.42
30
2.44
29
2.50
29
2.53
25
2.61
24
2.65
25
2.64
26
2.58
22
2.33
19170
18510
18346
17798
17430
16380
15146
13552
11921
6181
1000 9425
32
2.55
31
2.64
31
2.67
31
2.73
30
2.77
27
2.85
26
2.90
26
2.90
28
2.86
23
2.56
19975
19342
19184
18667
18313
17329
16216
14787
13270
8122
1042 9821
32
2.89
31
2.98
31
3.00
31
3.07
30
3.11
28
3.20
27
3.26
27
3.29
27
3.26
25
3.01
20128
19500
19343
18832
18481
17508
16411
15017
13506
8670
1050 9896
32
2.95
31
3.05
31
3.07
31
3.14
31
3.18
29
3.27
27
3.33
27
3.36
27
3.34
25
3.11
20511
19895
19741
19244
18899
17955
16896
15586
14094
10059
1070 10085
32
3.12
32
3.22
31
3.25
31
3.31
31
3.36
29
3.45
28
3.52
27
3.55
28
3.55
27
3.38
21087
20487
20338
19860
19524
18621
17616
16431
14981
11650
1100 10367
5
33
3.39
32
3.50
32
3.52
32
3.59
31
3.64
30
3.73
29
3.81
28
3.86
28
3.86
28
3.74
22045
21472
21329
20881
20561
19721
18804
17764
16444
13607
1150 10838
35
3.88
35
3.98
34
4.01
34
4.09
34
4.13
33
4.24
31
4.33
30
4.39
29
4.42
30
4.34
23713
23180
23047
22647
22350
21605
20765
19867
18889
16317
1237 11658
40
4.83
39
4.94
39
4.97
38
5.05
38
5.10
36
5.23
35
5.33
33
5.41
32
5.48
31
5.48
Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.
HP

PENNBARRY

35

BCH 42 - Belt Drive Fan Data


Breezeway
2.400

33/4

STATIC PRESSURE - Inches W.G.

2.200

11

14

2.000

46

Do not select shaded area.

41/2

RPM
BHP

RP

1.800

990

1.600

RP

1.400

833

1.200
1.000

727

0.800

71

/2

RPM

RPM
57
535 3 RPM
RPM

0.400

3/4 H

0.200
0.000

HP

5H
P

659

0.600

43

46
RP

6000

2H
1
1 H 1/2 H P
P
P
12000

3H
P

22
18000

AIR FLOW - CFM

24000

30000

Carbon Steel Panel = 16 gauge


Carbon Stl. Mtr. Plate = 10 gauge
Carbon Steel Tube = 16 gauge

Wall Opening = 46 3/4 in.sq.


Wall Shutter ID = 46 in.sq.
Est. Shipping Weight = 215 lbs.

Peak BHP = (RPM/676)^3


Max RPM = 1114 (7.5 HP)
Max. Motor Frame Size = 184T

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


TIP
0.100" SP
0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
0.625" SP
0.750" SP
1.000" SP
RPM SPEED 0.000" SP
(FPM) Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
12749
10762
10220
7903
5659
460
5058
12.8 0.51 12.2 0.54 12.0 0.55 11.5 0.55 11.5 0.53
3/4
14828
13175
12709
11145
9817
4583
535
5883
16.9 0.80 16.4 0.84 16.2 0.85 15.7 0.87 15.3 0.86 15.3 0.81
14967
13333
12871
11341
10051
4956
540
5938
17.2 0.82 16.6 0.86 16.5 0.87 16.0 0.89 15.6 0.89 15.6 0.83
15660
14114
13676
12307
11143
7102
1
565
6212
18.3 0.94 17.8 0.98 17.7 0.99 17.2 1.02 16.8 1.02 16.9 0.98
15881
14357
13932
12613
11464
7869
573
6300
18.7 0.98 18.2 1.02 18.1 1.03 17.6 1.06 17.2 1.06 17.2 1.03
16075
14570
14155
12864
11744
8249
580
6377
19.0 1.02 18.6 1.06 18.4 1.07 17.9 1.10 17.5 1.10 17.5 1.07
1 1/2
18265
16940
16609
15498
14740
12200
8897
659
7246
23
1.49
23
1.54
23
1.55
22
1.59
22
1.61
21
1.62
22
1.56
18570
17267
16941
15857
15112
12710
9540
670
7367
23
1.57
23
1.62
23
1.63
23
1.66
22
1.69
21
1.70
23
1.65
19401
18154
17842
16828
16115
13970
11132
6610
2
700
7697
25
1.79
25
1.84
25
1.86
24
1.89
24
1.91
23
1.94
23
1.91
28
1.82
20150
18949
18648
17693
17006
15042
12481
8914
727
7994
25
2.01
24
2.06
24
2.07
24
2.11
23
2.13
23
2.17
22
2.16
24
2.08
20510
19330
19035
18107
17432
15552
13101
10174
740
8137
24
2.11
24
2.17
24
2.18
23
2.22
23
2.25
23
2.29
22
2.28
23
2.21
21064
19915
19628
18740
18083
16328
14043
11251
760
8357
25
2.29
24
2.35
24
236
24
2.40
24
2.43
23
2.48
23
2.48
23
2.42
3
21896
20791
20514
19683
19051
17472
15393
12830
9083
790
8687
26
2.57
26
2.63
26
2.65
25
2.69
25
2.71
24
2.78
23
2.79
23
2.75
24
2.66
23088
22039
21777
20991
20423
18925
17114
14915
12350
833
9159
29
3.02
28
3.08
28
3.09
27
3.14
27
3.17
26
3.23
24
3.27
24
3.25
24
3.19
23282
22242
21982
21203
20645
19160
17390
15245
12722
840
9236
30
3.09
29
3.16
29
3.17
28
3.22
27
3.25
26
3.31
25
3.35
24
3.34
24
3.28
24391
23398
23150
22406
21905
20487
18948
17078
14785
7958
880
9676
32
3.56
31
3.62
31
3.64
30
3.69
29
3.72
28
3.79
27
3.84
26
3.86
25
3.82
24
3.60
24945
23975
23732
23004
22519
21144
19714
17887
15745
9429
900
9896
33
3.80
32
3.87
32
3.89
31
3.94
30
3.97
29
4.04
28
4.11
26
4.13
26
4.10
25
3.90
5
25776
24837
24603
23898
23429
22121
20780
19082
17161
12375
930 10226
34
4.20
33
4.27
33
4..28
32
4.34
32
4.37
30
4.44
29
4.52
27
4.55
27
4.54
26
4.38
26608
25698
25471
24789
24334
23090
21791
20260
18546
14161
960 10556
36
4.62
3`5 4.69
34
4.71
34
4.76
33
4.79
32
4.87
30
4.95
29
4.99
28
5.01
27
4.88
27439
26557
26337
25675
25234
24052
22792
21420
19758
15746
990 10886
37
5.06
36
5.14
36
5.16
35
5.21
34
5.25
33
5.33
32
5.41
30
5.47
29
5.49
28
5.40
27717
26843
26625
25970
25533
24371
23123
21803
20158
16266
1000 10996
38
5.22
37
5.29
36
5.31
35
5.37
35
5.40
33
5.49
32
5.57
30
5.63
29
5.66
29
5.58
28271
27415
27201
26559
26131
25007
23783
22560
20953
17259
1020 11215
39
5.54
37
5.61
37
5.63
36
5.69
36
5.73
34
5.82
33
5.89
31
5.97
30
6.00
29
5.95
28825
27986
27776
27146
26726
25640
24440
23240
21739
18218
1040 11435
40
5.87
38
5.95
38
5.97
37
6.02
37
6.06
35
6.15
34
6.24
32
6.32
31
6.35
30
6.32
7 1/2
29657
28841
28637
28025
27616
26584
25418
24252
22906
19635
1070 11765
41
6.39
40
6.47
39
6.49
39
6.55
38
6.59
37
6.69
35
6.77
34
6.85
32
6.91
31
6.91
30350
29552
29353
28755
28356
27359
26227
25088
23868
20798
1095 12040
42
6.85
41
6.93
41
6.95
40
7.01
39
7.05
38
7.16
36
7.24
35
7.33
33
7.40
31
7.43
30876
30092
29896
29309
28917
27937
26839
25719
24592
21638
1114 12249
43
7.21
42
7.30
42
7.32
41
7.38
40
7.42
39
7.52
37
7.61
36
7.70
34
7.78
32
7.83
Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.
HP

36

PENNBARRY

Belt Drive Fan Data - BCH 48


Breezeway
23/4

2.400
2.200

10

49

2.000

STATIC PRESSURE - Inches W.G.

Do not select shaded area.


RPM
BHP

RP

1.800

962

RP

1.600
1.400

840

1.200

707

1.000

54

RP

10
RPM

71

/2

0.800

616
RP
559 M
RPM
486
RPM
0.400

HP

HP

5H
P

3H
P
2
1 1/ HP
2
1 HP HP

0.200
0

49

0.600

0.000

4 3/4

54

8000

16000

25

24000

AIR FLOW - CFM

32000

40000

Carbon Steel Panel = 16 gauge


Wall Opening = 55 in.sq.
Carbon Stl. Mtr. Plate = 10 gauge Wall Shutter ID = 54 in.sq.
Carbon Steel Tube = 16 gauge
Est. Shipping Weight = 295 lbs.

Peak BHP = (RPM/555)^3


Max RPM = 1049 (10 HP)
Max. Motor Frame Size = 286T

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


TIP
0.100" SP
0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
0.625" SP
0.750" SP
1.000" SP
RPM SPEED 0.000" SP
(FPM) Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
16306
13155
12208
8806
3537
400
5027
9.9
0.56
9.9
0.59
9.9
0.59
9.5
0.57
9.2
0.54
17936
15132
14335
11467
9128
1
440
5529
15.0 0.74 15.4 0.78 14.4 0.79 15.8 0.78 15.8 0.74
19811
17327
16629
14313
12435
486
6107
14.2 1.00 14.2 1.04 14.2 1.05 14.2 1.06 14.0 1.04
19974
17514
16824
14541
12696
4341
490
6158
14.5 1.02 14.5 1.07 14.5 1.08 14.5 1.09 14.2 1.07 13.0 0.99
21401
19137
18509
16477
14930
8629
1 1/2 525
6597
16.8 1.26 16.7 1.31 16.6 1.32 16.7 1.34 16.8 1.33 15.5 1.23
22787
20693
20102
18259
16890
12841
559
7025
19.4 1.52 19.2 1.57 19.1 1.58 18.9 1.62 19.5 1.62 19.0 1.55
23236
21188
20613
18825
17507
13573
5388
570
7163
20
1.61
20
1.66
20
1.68 19.8 1.71
20
1.72
20
1.66 19.4 1.55
24459
22521
21995
20312
19111
15541
8970
2
600
7540
23
1.87
22
1.93
22
1.95
22
1.99
22
2.00
23
1.96
22
1.82
25111
23228
22726
21096
19948
16573
11910
616
7741
24
2.03
24
2.09
24
2.10
24
2.15
23
2.16
24
2.14
24
2.02
25274
23404
22909
21290
20156
16830
12683
620
7791
25
2.07
24
2.13
24
2.14
24
2.19
24
2.21
25
2.18
25
2.08
26905
25159
24700
23220
22176
19286
15793
8604
3
660
8294
29
2.49
28
2.56
28
2.58
28
2.62
28
2.65
29
2.66
29
2.58
29
2.41
28820
27203
26775
25424
24474
21930
18861
15556
7493
707
8884
32
3.06
31
3.14
30
3.15
30
3.20
29
3.24
29
3.28
30
3.23
29
3.12
29
2.95
28943
27333
26907
25563
24619
22090
19054
15793
7796
710
8922
32
3.10
31
3.18
31
3.19
30
3.24
29
3.28
29
3.32
30
3.27
29
3.16
28
2.98
31389
29921
29527
28328
27470
25238
22721
19765
16597
770
9676
35
3.96
34
4.04
34
4.06
33
4.11
32
4.15
31
4.23
30
4.22
29
4.14
29
4.01
5
33019
31627
31260
30138
29332
27243
24976
22338
19453
8006
810 10179
37
4.61
36
4.69
36
4.71
35
4.77
34
4.81
32
4.90
31
4.93
30
4.87
29
4.77
27
4.44
34242
32900
32554
31472
30715
28716
26577
24204
21423
11532
840 10556
39
5.14
38
5.23
37
5.25
36
5.31
36
5.35
34
5.44
32
5.49
31
5.47
31
5.37
29
4.97
34650
33323
32984
31915
31173
29204
27104
24780
22074
12914
850 10681
40
5.33
38
5.41
38
5.43
37
5.50
36
5.54
35
5.63
33
5.69
32
5.67
31
5.58
29
5.18
36280
35014
34697
33679
32997
31137
29188
27051
24641
19252
890 11184
42
6.11
41
6.20
40
6.23
39
6.29
39
6.34
37
6.44
35
6.52
33
6.53
33
6.47
32
6.20
37096
35857
35547
34557
33891
32091
30202
28165
25901
20780
7 1/2 910 11435
43
6.54
42
6.63
42
6.65
40
6.72
40
6.76
38
6.87
36
6.96
34
6.99
34
6.94
33
6.69
38726
37539
37243
36306
35668
33969
32181
30286
28223
23428
950 11938
46
7.44
44
7.53
44
7.56
43
7.63
42
7.67
40
7.79
38
7.89
36
7.94
35
7.93
35
7.73
39216
38043
37750
36828
36198
34529
32770
30915
28904
24218
962 12089
46
7.72
45
7.82
45
7.84
43
7.92
43
7.96
41
8.08
39
8.18
37
8.25
36
8.24
35
8.05
39542
38379
38089
37176
36551
34902
33161
31333
29355
24741
970 12189
47
7.91
45
8.01
45
8.04
44
8.11
43
8.16
41
8.27
39
8.38
37
8.45
36
8.45
35
8.27
40357
39218
38933
38045
37433
35830
34135
32372
30476
26038
990 12441
48
8.41
47
8.52
46
8.54
45
8.62
44
8.66
42
8.78
40
8.89
39
8.98
37
9.00
36
8.84
41376
40265
39987
39128
38531
36984
35344
33647
31821
27646
10 1015 12755
50
9.07
48
9.17
48
9.20
47
9.27
46
9.32
44
9.45
42
9.56
40
9.67
38
9.70
37
9.58
42191
41102
40830
39992
39406
37903
36305
34641
32878
28916
1035 13006
51
9.61
50
9.72
49
9.75
48
9.83
47
9.88
45 10.00 43 10.12 41 10.23 39 10.27 38 10.19
42762
41687
41419
40596
40018
38544
36971
35333
33614
29797
1049 13182
52 10.01 51 10.12 50 10.14 49 10.22 48 10.28 46 10.40 44 10.52 42 10.63 40 10.69 38 10.63
HP

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

PENNBARRY

37

BCH 54 - Belt Drive Fan Data


Breezeway
3

2.600

60

STATIC PRESSURE - Inches W.G.

2.400
10

74

2.200

959

1.600

870

1.400
1.200

759

1.000
0.800

RP

60

0.400

15
RPM

0.200
0

55

RPM

639 R
PM
55
505 R 7 RPM
PM
440 RP
M

0.600

0.000

RPM
BHP

RP

2.000
1.800

Do not select shaded area.

8000

10
71

/2

5H
P
1 1/2 2
H
1 HP HP P

16000

HP

HP

HP

3H
P

24000

28

32000

AIR FLOW - CFM

40000

48000

56000

Carbon Steel Panel = 16 gauge


Carbon Stl. Mtr. Plate = 10 gauge
Carbon Steel Tube = 16 gauge

Wall Opening = 61 in.sq.


Wall Shutter ID = 60 in.sq.
Est. Shipping Weight = 335 lbs.

Peak BHP = (RPM/416)^3


Max RPM = 1074 (15 HP)
Max. Motor Frame Size = 286T

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


TIP
0.100" SP
0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
0.625" SP
0.750" SP
1.000" SP
RPM SPEED 0.000" SP
(FPM) Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
15731
10711
8686
300
4241
8.5
0.33
7.5
0.34
7.4 0.333
17828
13961
12337
1
340
4807
10.7 0.47
9.8
0.49
9.4
0.49
23072
20334
19647
16439
13927
440
6220
16.9 1.03 16.2 1.05 16.0 1.05 15.1 1.07 14.7 1.05
23596
20918
20252
17268
14922
450
6362
17.6 1.10 16.8 1.12 16.6 1.12 15.8 1.14 15.3 1.12
1 1/2
26480
24108
23498
21572
19462
13255
505
7139
21
1.55
20
1.58 19.9 1.58 19.3 1.59 18.9 1.61 18.0 1.52
26743
24397
23789
21945
19872
13984
510
7210
21
1.0
20
1.62
20
1.63 19.6 1.64 19.2 1.65 18.3 1.58
2
29207
27083
26515
24879
23548
18852
557
7874
26
2.08
25
2.11
25
2.12
24
2.13
23
2.14
23
2.14
29365
27253
26688
25062
23773
19101
560
7917
26
2.11
25
2.14
25
2.15
24
2.16
24
2.17
24
2.17
3
33507
31696
31201
29735
28796
25495
21360
639
9034
37
3.14
37
3.16
37
3.18
35
3.21
34
3.21
34
3.24
36
3.22
34084
32309
31822
30375
29452
26371
22322
16821
650
9189
37
3.30
37
3.33
37
3.34
35
3.38
34
3.38
34
3.41
35
3.40
34
3.22
36706
35075
34631
33276
32403
30173
26351
22451
5
700
9896
37
4.13
36
4.15
36
4.16
35
4.21
34
4.22
32
4.23
32
4.29
32
4.22
39800
38296
37916
36666
35833
33840
31118
27481
23812
759 10730
37
5.26
35
5.28
35
5.29
34
5.34
33
5.37
32
5.38
30
5.42
29
5.49
28
5.36
40376
38894
38524
37293
34672
34512
31962
28407
24912
770 10886
37
5.49
36
5.52
35
5.52
34
5.57
34
5.61
32
5.61
31
5.65
30
5.72
29
5.62
42998
41607
41259
40129
39357
37490
35590
32519
29211
20950
7 1/2 820 11592
40
6.63
39
6.66
38
6.66
37
6.71
36
6.75
35
6.78
33
6.80
32
6.86
31
6.89
29
6.45
45620
44308
43981
42941
42214
40426
38682
36426
33323
26849
870 12299
43
7.92
42
7.95
41
7.96
40
7.99
39
8.03
38
8.10
36
8.10
35
8.15
34
8.22
33
8.04
46145
44848
44524
43501
42782
41009
39295
37180
34145
27855
880 12441
44
8.20
42
8.23
42
8.23
41
8.27
40
8.31
38
8.38
36
8.38
35
8.43
34
8.49
33
8.36
47193
45925
45608
44619
43916
42171
40504
38678
35762
29844
900 12723
45
8.77
44
8.80
43
8.80
42
8.84
41
8.88
39
8.96
37
8.96
36
9.00
35
9.06
34
8.99
48242
47002
46691
45734
45047
43328
41697
39992
37354
31628
10 920 13006
47
9.37
45
9.40
45
9.40
43
9.43
42
9.47
40
9.58
39
9.58
37
9.61
36
9.66
35
9.66
49291
48077
47773
46847
46174
44492
42884
41234
38913
33197
940 13289
48
9.99
46 10.02 46 10.03 45 10.06 44 10.10 42 10.20 40 10.21 38 10.24 37 10.29 36 10.36
50287
49097
48800
47901
47242
45593
44007
42407
40353
34671
959 13558
49 10.61 47 10.64 47 10.65 46 10.67 45 10.71 43 10.82 41 10.85 39 10.86 38 10.91 37 11.07
50864
49687
49393
48511
47859
46229
44654
43083
41181
35599
970 13713
50 10.98 48 11.01 48 11.02 46 11.04 45 11.08 43 11.19 41 11.22 40 11.23 38 11.28
37
11.4
51913
50760
50472
49607
48979
47382
45827
44307
42675
37271
990 13996
51 11.67 49 11.70 49 11.71 48 11.73 47 11.77 44 11.88 42 11.93 41 11.93 39 11.98
38 12.13
52961
51831
51549
50702
50096
48531
46996
45510
43945
38924
1010 14279
52 12.40 50 12.43 50 12.43 49 12.46 48 12.49 46 12.60 44 12.67 42 12.67 40 12.71 39 12.85
15
54010
52902
52625
51794
51211
49676
48159
46703
45187
40553
1030 14561
54 13.15 52 13.18 51 13.19 50 13.21 49 13.24 47 13.35 45 13.44 43 13.44 41 13.47 40 13.60
55059
53972
53700
52885
52323
50817
49318
47890
46422
42154
1050 14844
55 13.93 53 13.96 53 13.97 52 13.99 51 14.02 48 14.13 46 14.24 44 14.24 42 14.26 41 14.38
56317
55255
54989
54192
53655
52183
50711
49307
47895
44056
1074 15183
57 14.91 55 14.94 55 14.94 53 14.97 52 14.99 50 15.11 48 15.22 46 15.23 44 15.24 42 15.35
HP

Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.

38

PENNBARRY

Belt Drive Fan Data - BCH 60


Breezeway
3.200

23/4

3.000
2.800

STATIC PRESSURE - Inches W.G.

66
78

2.600

72

2.400

Do not select shaded area.

0R

RPM
BHP

PM

1R

2.200

PM

2.000

66

1.800
1.600

57

1R

1.400

PM

62

9R

PM

20

1.200
1.000

15

498
RP
M
41
365 9 RPM
331 RPM
RPM

0.800
0.600
0.400
0.200

1 1/2

0.000
0

10000

10

71

20000

2
HP HP

5H
P
3H
P
30000

61

HP

HP

HP

/2 H

40000

AIR FLOW - CFM

28
50000

60000

70000

Carbon Steel Panel = 16 gauge


Carbon Stl. Mtr. Plate = 10 gauge
Carbon Steel Tube = 16 gauge

Wall Opening = 67 in.sq.


Wall Shutter ID = 66 in.sq.
Est. Shipping Weight = 420 lbs.

Peak BHP = (RPM/246)^3


Max RPM = 780 (20 HP)
Max. Motor Frame Size = 286T

FAN CAPACITY - CUBIC FEET PER MINUTE (CFM)


TIP
0.100" SP
0.125" SP
0.200" SP
0.250" SP
0.375" SP
0.500" SP
0.625" SP
0.750" SP
1.000" SP
RPM SPEED 0.000" SP
(FPM) Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP Sones BHP
21063
15681
13828
241
3786
10.2 0.59
9.7
0.62
9.8
0.62
23598
18983
17597
1 1/2 270
4241
12.4 083 11.6 0.86 11.7 0.87
28929
25548
24423
21005
17965
331
5199
18.0 1.52 16.9 1.57 16.6 1.58 16.7 1.60 17.1 1.60
29716
26485
25389
22081
19435
340
5341
18.9 1.65 17.8 1.70 17.4 1.71 17.4 1.74 17.7 1.74
2
31901
28976
28034
24948
22847
365
5733
21
2.04
20
2.10
20
2.11 19.6 2.14 19.8 2.15
32338
29461
28557
25515
23476
370
5812
22
2.12
21
2.19
21
2.20
20
2.23
20
2.24
3
36620
34154
33453
30927
29128
24180
419
6582
26
3.08
25
3.16
25
3.17
24
3.21
24
3.23
24
3.25
37582
35196
34513
32108
30360
25766
430
6754
27
3.33
26
3.41
26
3.43
25
3.47
24
3.49
24
3.52
5
43525
41530
40977
39208
37731
33957
29964
18028
498
7823
33
5.18
31
5.27
31
5.29
30
5.35
30
5.37
28
5.43
27
5.47
25
5.38
44574
42626
42105
40378
38997
35318
31527
24750
510
8011
34
5.56
33
5.65
32
5.68
31
5.74
31
5.77
29
5.83
28
5.87
27
5.75
47632
45810
45354
43761
42643
39218
35774
31807
19636
7 1/2 545
8561
37
6.78
36
6.89
35
6.91
34
6.98
34
7.02
32
7.09
30
7.15
30
7.16
28
7.06
49905
48165
47731
46250
45222
42053
38752
35350
30653
571
8969
39
7.80
38
7.91
38
7.94
37
8.01
36
8.05
34
8.13
32
8.19
31
8.24
31
8.20
50692
48979
48551
47108
46095
43022
39775
36488
32359
580
9111
40
8.18
39
8.29
38
8.31
37
8.38
37
8.43
35
8.51
33
8.58
32
8.63
31
8.62
52440
50784
50370
49007
48028
45159
42030
38914
35274
600
9425
42
9.05
40
9.16
40
9.19
39
9.27
38
9.31
37
9.41
34
9.48
33
9.54
33
9.56
10
53751
52135
51732
50426
49471
46748
43703
40651
37385
615
9660
43
9.75
42
9.86
41
9.89
40
9.97
40 10.02 38 10.12 36 10.19 34 10.26 34 10.30
54974
53395
53000
51745
50812
48221
45251
42257
39168
22607
629
9880
44 10.43 43 10.55 43 10.58 42 10.66 41 10.71 39 10.81 37 10.89 35 10.96 34 11.02
33 10.86
55936
54384
53996
52780
51862
49373
46459
43508
40554
27400
640 10053
45 10.99 44 11.11
44 11.14 43 11.22 42 11.27 40 11.38 38 11.46 36 11.54 35 11.60
34 11.23
57684
56179
55802
54655
53765
51453
48631
45775
42946
35529
660 10367
47 12.05 46 12.17 45 12.20 44 12.29 44 12.34 42 12.47 39 12.55 37 12.63 36 12.70 36 12.67
59432
57971
57606
56510
55660
53501
50779
48017
45256
38871
15 680 10681
49 13.18 47 13.30 47 13.34 46 13.43 45 13.48 44 13.62 41 13.71 39 13.79 37 13.86 37 13.91
61180
59761
59406
58342
57548
55450
52907
50234
47537
41763
700 10996
51 14.37 49 14.50 49 14.54 48 14.64 47 14.69 45 14.83 43 14.93 41 15.02 39 15.10 38 15.19
63015
61637
61293
60260
59522
57486
55124
52539
49919
44554
721 11325
53 15.71 52 15.84 51 15.88 50 15.98 50 16.04 48 16.18 45 16.29 43 16.38 41 16.47 39 16.59
63802
62441
62101
61080
60366
58355
56068
53517
50932
45694
730 11467
54 16.30 53 16.44 53 16.47 51 16.58 51 16.64 49 16.78 47 16.90 44 16.99 42 17.08 40 17.22
65112
63779
63446
62446
61770
59800
57636
55136
52610
47579
745 11702
56 17.33 55 17.47 55 17.50 54 17.61 53 17.68 51 17.82 49 17.95 47 18.04 44 18.13 42 18.29
66424
65117
64790
63810
63156
61239
59195
56744
54276
49345
20 760 11938
59 18.40 57 18.54 57 18.57 56 18.68 55 18.75 53 18.90 51 19.04 49 19.13 46 19.23 43 19.39
67735
66453
66133
65171
64531
62675
60746
58343
55931
51083
775 12174
61 19.51 59 19.65 59 19.69 58 19.80 57 19.87 55 20.02 53 20.17 51 20.27 49 20.37 45 20.54
68172
66898
66580
65625
64988
63152
61262
58874
56480
51660
780 12252
62 19.89 60 20.03 60 20.07 59 20.18 58 20.25 56 20.41 54 20.56 52 20.66 49 20.76 45 20.93
Performance shown is for installation Type A: Free Inlet, Free Outlet. Power rating (BHP) does not include drive losses. The sound ratings shown are for loudness values
in fan sones at 5'0" (1.5m) in a hemispherical free eld per AMCA standard 301. Values shown are for installation Type A: Free inlet fan sone levels. Performance ratings
do not include the effects of appurtenances in the airstream. For further information on sound classication, see page 40. For accessories, see pages 3 thru 7.
HP

PENNBARRY

39

Sound Data Notes


Breezeway

Sound Power Levels

(100 watts), the brightness level changed dramatically.

Since any mechanical device generates some sound energy


into the air, fans will create some noise. Because of the great
number of factors inuencing sound output it is invalid to
compare fans based on RPM, tip speed or outlet velocity. The
only accurate basis of comparison is the sound power level
generated by the fan at the required point of operation.

Similarly, the same sound power level (acoustical energy)


produces greatly different sound pressure levels (noise).

Having sound power levels for a specic fan at a specic


operating point allows the system designer to determine the
theoretical sound pressure level at any point in the occupied
space. AMCA Publication 303 and the ASHRAE Guides
provide more information on this process. Another typical
application of sound power levels is to compare similar fans.
Generally differences of 6 dB in the 63 Hz band and 3 dB in
all other bands are considered insignicant.
System designers use many methods to predict acoustic
acceptability of an occupied space.
The A-weighted sound pressure level provides a single
number that corresponds well to the human judgement of
relative loudness. OSHA bases their requirements regarding
exposure to noise on A-weighted sound pressure levels. The
disadvantage of this method is that A-weighted sound pressure
levels do not provide information as to the quality of the sound.
Noise Criteria (NC) curves are also widely used. To determine
the NC level, the sound power spectrum is compared to
dened limits. Other methods include RC curves, Sones, SIL
and Noise Rating Curves.
Each method relies on sound pressure level information
because the human ear hears sound pressure uctuations,
not sound power (watts). Sound pressure is a function of the
attenuation of the space and the distance from the source.
Consider a 100 watt light bulb. It provides adequate light for
a closet, but not for a classroom, and in a stadium it would
be imperceptible. While the light source was the same power

Sound power levels shown in this catalog were measured


and certied using AMCA standard 300 Reverberant Room
Method for Sound Testing of Fans. The values shown are for
the eight octave bands dened in this standard, which agree
with ANSI 61.11-1986. One-third octave band sound power
levels shown are rated in decibels (dB) using 10-12 watts as
a reference.

Sone Ratings
In addition to sound power levels, PennBarry has provided
sone ratings to allow designers to make an educated judgment
as to the noise level a fan will develop in a space. Sone
ratings are a loudness index developed from sound power
level data. The calculation is at 5 from the fan inlet and in
front of a reecting plane (hard wall). Sones are weighted
similarly to the A-weighting scale in that more weight is given
to frequencies that people can hear well and less weight to
frequencies that people do not hear well. A signicant feature
of the sone scale is that it is linear rather than logarithmic.
This means that 40 sones is 33% louder than 30 sones, as
opposed to 40 dB being twice as loud as 30 dB.
Since the sone rating is determined from well defined
assumptions and is linear in nature, it is ideal for comparing
different fans moving air at the same CFM and SP. When using
sones for this purpose, differences of 3 sones are considered
negligible. The suggested loudness level chart below is a
practical guideline for acceptable installed performance.
The sone values shown in this catalog are based on the sound
power levels determined above, and calculated in accordance
with AMCA Standard 301 Methods for Calculating Fan Sound
Ratings from Laboratory Test Data.

Sound Classification Guide


SUGGESTED LOUDNESS LEVEL
AREA SONE
LEVEL

NOISE
CRITERIA
NC

dBA (1)

Up to 9

32 to 54

35 to 60

Bingo Hall, Auction Room, Hotel Ballroom, Social Club, Reception Room, Apartment House, Professional Ofce, Supervisor Ofce,
Courtroom, School and Classroom, Hospital Ward, Operating Room, Correction Facility.

Moderately
Quiet Sound

9.1 to 13

55 to 59

61 to 65

Lobby/Corridor, Spectator Area, Chicken House, Greenhouse, General Open Ofce, Restaurant, Night Club, Department Store, Ticket
Sales Ofce, Casino, Spa, Control Room, Rail, Bus, Plane, Bowling Alley, Print Shop, Drafting Ofce, Convention Hall

Average

13.1 to 18

60 to 64

66 to 70

Washroom & Toilet, Retail Shop, Bus Terminal Lounge, Foremans Ofce, Cocktail Lounge, Ofce Hall & Corridor, Tabulation &
Computation Ofce, Kitchen Cafeteria, Hotel Garage, Computer Room, Warehouse, Battery Charging Room

Commercial

18.1 to 50

65 to 78

71 to 84

General Storage Area, Restaurant Banquet Room, Swimming Pool, Supermarket, Hotel Kitchen and Laundry, Welding Booth,
Department Store Main Floor, Paint Booth, Heat Treating Plant, Tool Maintenance Area

High Sound

50.1 Plus

78.1 to 85+

84.1 to
90+ (2)

Manufacturing Area, Heavy Machine Foundry, Assembly Line, Machine Shops, Punch Press Shop, Light Machine Area, Boiler Room,
Emergency Generator Room, Pump House, Power Plant, Transformer, Steel Mill, Engine Test Room, Compressor Room, Steel Stamping

Ext. Heavy
Industrial

TYPES OF AREAS

Notes: (1) dBA range of A-weighted sound levels, in decibels.

(2)

Sound levels this high subject to OSHA Standards for safety, as well as state
and local ordinances. Sound attenuation provisions should be considered.
Source: ASHRAE, AMCA Publications

40

PENNBARRY

Engineering Notes
Breezeway

Fan Laws

Interaction of Fan Curves and System Curves

The following section includes engineering and technical data,


guidelines and system explanations related to air moving
and control devices. Fan laws and system descriptions are
consistent with industry standards, denitions and accepted
practices. This information is provided to assist system
designers in sizing, selecting and dening their air moving
and control systems as well as explaining variables inherent
in system design.

A ventilation system using a Breezeway may consist of a fan


with duct connected to the inlet side. Control dampers, grilles,
registers and duct ttings may also be part of the system.
The fan is the component in the system which provides
energy to the airstream to overcome the resistance to ow
off the other components. The determination of the pressure
loss or resistance to ow, for the individual components
can be obtained from the component manufacturers. The
determination of pressure losses for ductwork and branch
ductwork design is well documented in standard handbooks,
such as the ASHRAE Handbook of Fundamentals.

There are nine fan laws, three are of prime importance to the
understanding of ventilation systems. These, together with an
appreciation of fan types, should help avoid most problems
with poor airow performance. These three laws assume the
same fan operating with air at a constant density.

The fan curve shown in Figure 1 is a typical fan performance


curve, developed through the actual testing of a fan in an
air tunnel. The fan is run at constant speed and constant air
density. When the fan is installed in the eld, then it becomes
part of the system. System curves are developed by using eld
tested data and applying fan laws. The point of intersection of
the system curve and the fan performance curve determines
the actual ow volume. If the system resistance has been
accurately determined, and the fan properly selected, the
performance curves will intersect at the system design point
(point A).

1. Airow and fan speed are directly proportional.

CFM2 = RPM2
CFM1 RPM1
CFM1 is the original ow rate in cu. ft. per minute.
CFM2 is the desired ow rate in cu. ft. per minute.
RPM1 is the original rotational speed of the fan.
RPM2 is the desired rotational speed of the fan.

2. Pressure varies as the square of the fan speed


or airow.
2

3. Power varies as the cube of fan speed.

BHP1

[ ]
RPM2
RPM1

A
TE
M

1.375

YS

1.125

FAN CURVE

1.000

0.875

TS

P1 is the original static pressure.


P2 is the desired static pressure.

BHP2

UNDER ESTIMATED S.P.


RESULTS IN HIGH STATIC
LOW C.F.M.

1.500

SYSTEM
DESIGN
POINT

DU
C

[ ]
RPM2
RPM1

Static Pressure - Inches W.G.

P2
=
P1

Figure 1
Interaction of System Curves and Fan Curve

0.750

0.625

OVER ESTIMATED S.P.


RESULTS IN LOW STATIC
HIGH C.F.M.

0.500
0.375
0.125
0

200

400

600

800

1000

1200

1400

1600

1800

2000

CFM

PENNBARRY

41

Engineering Notes
Breezeway

If the system resistance has been underestimated, then fan


curves and system curves will not intersect at the system
design point. They will intersect at lower CFM (point B). If the
system resistance has been overestimated, then the fan curve
system curve will intersect at a higher CFM than the system
design point (point C). (See Figure 1)

Effect of Change in Density, Altitude and Temperature


Correction Factors
The resistance of a duct system is dependent upon the density
of the gas owing through the system. A gas density of 0.075
lb/ft3 is standard in the fan industry.
Pressure and horsepower vary directly as the ratio of the gas
density at the fan inlet to standard density. This density ratio
must always be considered when selecting fans. To select
a fan, pressure should be corrected to standard air density,
0.075 lb/ft3, 70F. at sea level. Static pressure at operating
condition x correction factor=static pressure at standard.
Refer to Table 1.

Table 1
Correction Factors
Unity Basis = Standard Air Density of 0.075 lb/ft3
At sea level (29.92 in. Hg barometric pressure) this is equivalent to
dry air at 70F.
ALTITUDE (FEET) WITH BAROMETRIC PRESSURE (Inches Hg)
TEMP
F

- 40

0'

500' 1000' 1500' 2000' 2500' 3000' 3500' 4000' 4500' 5000'

29.92 29.38 28.86 28.33 27.82 27.31 26.82 26.32 25.84 25.36 24.9

0.79 0.81 0.82 0.84 0.85 0.87 0.88

0.87 0.88

40

0.94 0.96 0.98

70

0.9

1.02 1.04 1.06 1.08

100

1.06 1.08

0.92 0.93 0.95


1

1.02 1.04

1.01 1.03 1.05 1.07 1.09 1.11 1.13

1.02 1.04 1.06 1.08

80

1.1

0.9

0.92 0.93 0.95 0.97 0.99

1.1

1.1

1.12 1.14 1.16 1.18

1.12 1.14 1.16 1.18

1.12 1.14 1.16 1.18

1.2

1.2

1.2
1.22

1.22 1.25 1.27

Horsepower at standard correction factor = horsepower at


operating condition. Motors should be sized for highest density
conditions at which it is expected to operate.

damper is part of external static pressure, and should be


accounted for when estimating system static pressure. Use
a motorized backdraft damper when the fan has a variable
speed controller.

System Effect
A System Effect Factor is a pressure loss which recognizes
the effect of fan inlet restrictions, fan outlet restrictions or other
conditions inuencing fan performance when installed in the
system. Figure 2 illustrates decient fan/system performance
resulting from one or more undesirable ow conditions. It is
assumed that the system pressure losses, shown in system
curve A, have been accurately determined, and a suitable fan
selected for operation at Point 1. However, no allowance has
been made for the effect of the system connections on the
fans performance. To compensate for this System Effect, it
will be necessary to add a System Effect Factor (SEF) to the
calculated system pressure losses to determine the actual
system curve. The SEF for any given conguration is velocity
dependent and will, therefore, vary across the range of ow
volumes for the fan.
In Figure 2, the point of intersection between the fan
performance curve and the actual system curve B is Point
4. The actual ow volume will, therefore, be decient by the
difference from 1-4. To achieve design ow volume, an SEF
equal to the pressure difference between Point 1 and 2 should
have been added to the calculated system pressure losses and
the fan selected to operate at Point 2. Note that because the
System Effect is velocity related, the difference represented
between Points 1 and 2 is greater than the difference between
Points 3 and 4.
The SEF includes only the effect of the system conguration
on the fans performance.

Figure 2
CURVE B - ACTUAL DUCT
SYSTEM WITH SYSTEM
EFFECT
CURVE A - CALCULATED DUCT
SYSTEM WITH NO ALLOWANCE
FOR SYSTEM EFFECT

Inlet System Effect

42

PENNBARRY

SYSTEM EFFECT LOSS AT


DESIGN VOLUME

DESIGN PRESSURE

The most common installation problem is ductwork connection


to the inlet side of the fan. Here are several design criteria
for connecting ductwork to the fan. Keep a straight duct run
twice the diameter of the inlet size immediately before the
inlet of the fan. This will give the air a chance to straighten
out before entering the fan. Fan inlet swirl and non-uniform
inlet ow can often be corrected by inlet straightening vanes
or guide vanes. Restricted fan inlets located too close to walls,
obstructions or restrictions caused by a plenum or cabinet, will
decrease the useable performance of a fan. Cabinet clearance
effect or plenum effect must be considered a component
part of the entire system; the pressure losses through the
cabinet or plenum effect is considered as a System Effect
when determining system characteristics. The backdraft

SYSTEM
EFFECT AT
ACTUAL
FLOW
VOLUME

FAN CATALOG
PRESSURE-VOLUME
CURVE

DEFICIENT
PERFORMANCE

DESIGN VOLUME
Decient Fan/Duct System Performance System Effect Ignored

Engineering Notes
Breezeway

Inlet Duct Elbows

Inlet Turning Vanes

Non-uniform ow into a fan inlet is the most common cause


of decient fan performance. An elbow located at, or in
close proximity to the fan inlet will not allow the air to enter
the impeller uniformly. The result is less than cataloged air
performance.

Where space limitations prevent the use of optimum fan inlet


connections, more uniform ow can be achieved by the use
of turning vanes in the inlet elbow.

Inlet Vortex (Spin or Swirl)

Numerous variations of turning vanes are available from a


single curved sheet metal vane to multi-bladed airfoil vanes.
The pressure drop through these devices must be added to
the system pressure losses.

Another major cause of reduced performance is an inlet


duct condition that produces a vortex or spin in the airstream
entering a fan inlet.

Spark Resistant Construction

The ideal inlet condition is one which allows the air to enter
axially and uniformly without spin in either direction. A spin
in the same direction as the impeller rotation (pre-rotation)
reduces the pressure volume curve by an amount dependent
upon the intensity of the vortex. The effect is similar to the
change in the pressure volume curve achieved by inlet vanes
installed in a fan inlet; the vanes induce a controlled spin in the
direction of impeller rotation reducing the volume ow rate.
A counter-rotating vortex at the inlet may result in a slight
increase in the pressure-volume curve but the horsepower
will increase substantially.

AMCA standards offer the following denitions and notes


concerning spark resistant construction:
C The fan shall be constructed so that a shift in the
impeller or shaft will not permit two ferrous parts of
the fan to rub or strike.
B The fan shall have a non-ferrous impeller and nonferrous ring about the opening through which the
shaft passes. Ferrous hubs, shafts and hardware
are allowed, provided construction is such that a shift
in impeller or shaft will not permit two ferrous parts
of the fan to rub or strike. Steps must also be taken
to insure that the impeller, bearings, and shaft are
adequately attached and/or restrained to prevent a
lateral or axial shift in these components.

Notes: 1) No bearings, drive components or electrical components shall be placed in the air or gas stream unless they are constructed or enclosed in such a manner
that failure of the component cannot ignite the surrounding gas stream.
2) The user shall electrically ground on all fan parts.
3) For this standard, non-ferrous shall be any material with less than 5% iron or any other material with demonstrated ability to be spark resistant.
4) The use of aluminum or aluminum alloys in the presence of steel which has been allowed to rust requires special consideration. Research by the
U.S.Bureau of Mines and others has shown that aluminum impellers rubbing on rusty steel may cause high-intensity sparking.

The use of the above standard in no way implies a guarantee of safety for any level of spark resistance. Spark resistant
construction does not protect against ignition of explosive gases caused by catastrophic failure or from any airstream material
that may be present in a system.

Metric Equivalents
Many PennBarry products are specied and installed overseas. For your convenience,
the table below provides conversion factors from English to Metric.
CATEGORY
VOLUME FLOW
PRESSURE
POWER
TEMPERATURE
HEAT
TIP SPEED
SPEED
VELOCITY

DIMENSIONS

AMCA STANDARD /
ENGLISH UNIT

x CONVERSION
FACTOR

= METRIC (SI) UNIT

CFM
Inches (wg)
H.P.
Fahrenheit (F)
Btu
Ft/M
RPM
Ft/M
Inches
Feet
Square Feet
Cubic Feet

0.00047195
248.36
745.7
(F + 459.67)/1.8
1.055
0.00508
0.016
0.00508
25.4
0.3048
0.0929
0.0283

cu. meter per sec. (m3/s)


pascal (Pa or N/m2)
watt (W or J/s)
kelvin
kilojoules (kj)
meter per second (m/s)
rev. per second (rps)
meter per second (m/s)
millimeter (mm)
meter (m)
square meter (m2)
cubic meter (m3)

PENNBARRY

43

Sample Specifications
Breezeway

P Series

Type BHM

Direct drive Axial Panel exhaust or supply fan shall be


Breezeway P manufactured by PennBarry, Richardson,
Texas. Motors are rigidly mounted on a heavy gauge
wire basket/rear guard of concentric rings meeting OSHA
specication. Vibration isolation is provided between the
motor/guard assembly and a coated steel fan panel featuring
welded corners, pre-punched mounting holes, and a deeply
spun venturi. Statically balanced propellers are die formed
aluminum. Motors shall be continuous duty, multi-speed (for
applicable models) and permanently lubricated. Each fan
shall bear the AMCA Licensed Ratings Seal for Air and Sound
Performance, and shall be UL and CSA Listed.

Belt driven Axial Panel exhaust or supply fan shall be


Breezeway BHM manufactured by PennBarry, Richardson,
Texas. A heavy gauge motor mounting panel is fastened to
heavy gauge structural channel framework laterally supported
and fastened onto a galvanized steel fan panel featuring
toggle-lock corners, pre-punched mounting holes, and a
deeply spun reverse venturi. Statically balanced propellers
shall be coated heavy gage steel, utilizing a fully welded,
coated heavy gage steel spider. Motors shall be continuous
duty, ball bearing design, and positively cooled, furnished at
the specied voltage, phase, and enclosure. Shafts shall be
turned, ground, polished, and rust protected. Heavy duty ball
bearings are rated for a minimum L50 life exceeding 200,000
hours. Pulleys shall be adjustable, cast iron, machined, keyed,
securely attached and sized for 150% of the horsepower at
its rated maximum speed. Each fan shall bear the AMCA
Licensed Ratings Seal for Air and Sound Performance, and
shall be UL and CSA Listed.

Breezex
Direct drive Axial Panel exhaust or supply fan shall be
Breezeway BX manufactured by PennBarry, Richardson,
Texas. Motors are installed on a heavy gauge mounting plate
welded to a formed heavy wall tubular frame, welded onto a
coated steel fan panel featuring welded corners, pre-punched
mounting holes, and a deeply spun venturi. Statically balanced
propellers are aluminum. Motors shall be Totally Enclosed
(TE), continuous duty, ball bearing design, include thermal
overload protection and be reversible. A reversing switch shall
be supplied. (Explosion Proof, Cls. 1, Div. 1, Grp. D, optionally
available; reversing switch by others.)

Type BC
Direct drive Axial Panel exhaust or supply fan shall be
Breezeway BC manufactured by PennBarry, Richardson,
Texas. A heavy gauge motor mounting platform is supported
by formed integral stiffening flanges and welded onto a
coated steel fan panel featuring welded corners, pre-punched
mounting holes, and a deeply spun venturi. Statically balanced
propellers shall be cast aluminum and airfoil shaped. Motors
shall be continuous duty, ball bearing design, positively cooled
and furnished at the specied voltage and phase.

Type BLL
Belt driven Axial Panel exhaust fan shall be Breezeway BLL
manufactured by PennBarry, Richardson, Texas. A heavy
gauge motor mounting platform is supported by formed
integral stiffening anges and welded onto a coated steel fan
panel featuring welded corners, pre-punched mounting holes,
and a deeply spun venturi. Statically balanced propellers
shall be heavy gage steel. Motors shall be continuous duty,
ball bearing design, and positively cooled, furnished at the
specied voltage, phase, and enclosure. Shafts shall be
turned, ground, polished, & rust protected. Heavy duty ball
bearings are rated for a minimum L50 life exceeding 200,000
hours. Pulleys shall be adjustable, cast iron, machined, keyed,
securely attached and sized for 150% of the horsepower at
its rated maximum speed. Each fan shall bear the AMCA
Licensed Ratings Seal for Air and Sound Performance, and
shall be UL and CSA Listed.

44

PENNBARRY

Type BHH
Belt driven Axial Panel exhaust or supply fan shall be
Breezeway BHH manufactured by PennBarry, Richardson,
Texas. A heavy gauge motor mounting panel is fastened to
heavy gauge structural channel framework laterally supported
and fastened onto a galvanized steel fan panel featuring
toggle-lock corners, pre-punched mounting holes, and a
deeply spun reverse venturi. Statically balanced propellers
shall be coated heavy gage steel, utilizing a fully welded,
coated heavy gage steel spider. Motors shall be continuous
duty, ball bearing design and positively cooled, furnished at
the specied voltage, phase and enclosure. Shafts shall be
turned, ground, polished and rust protected. Heavy duty ball
bearings are rated for a minimum L50 life exceeding 200,000
hours. Pulleys shall be adjustable, cast iron, machined, keyed,
securely attached and sized for 150% of the horsepower at
its rated maximum speed. Each fan shall bear the AMCA
Licensed Ratings Seal for Air and Sound Performance, and
shall be UL and CSA Listed.

Type BCH
Belt driven Axial Panel exhaust fan shall be Breezeway BCH
manufactured by PennBarry, Richardson, Texas. A heavy
gauge motor mounting panel is welded to heavy gauge
structural angle and tubular welded framework laterally
supported and welded onto a coated steel fan panel featuring
welded corners, pre-punched mounting holes and a deeply
spun venturi. Statically balanced propellers shall be cast
aluminum and airfoil shaped. Motors shall be continuous
duty, ball bearing design, positively cooled and furnished at
the specied voltage, phase and enclosure. Shafts shall be
turned, ground, polished and rust protected. Heavy duty ball
bearings are rated for a minimum L50 life exceeding 200,000
hours. Pulleys shall be adjustable, cast iron, machined, keyed,
securely attached and sized for 150% of the horsepower at
its rated maximum speed. Each fan shall bear the AMCA
Licensed Ratings Seal for Air and Sound Performance, and
shall be UL and CSA Listed.

One Year Limited Warranty


Breezeway Fan

What Products Are Covered


PennBarry Commercial and Industrial Fans (each, a PennBarry Product)

One Year Limited Warranty For PennBarry Products


PennBarry warrants to the original commercial purchaser that the PennBarry Products will be free from defects in material and
workmanship for a period of one (1) year from the date of shipment.

Exclusive Remedy
PennBarry will, at its option, repair or replace (without removal or installation) the affected components of any defective PennBarry
Product; repair or replace (without removal or installation) the entire defective PennBarry Product; or refund the invoiced price
of the PennBarry Product. In all cases, a reasonable time period must be allowed for warranty repairs to be completed.

What You Must Do


In order to make a claim under these warranties:
1. You must be the original commercial purchaser of the PennBarry Product.
2. You must promptly notify us within the warranty period of any defect and provide us with any substantiation that we may
reasonably request.
3. The PennBarry Product must have been installed and maintained in accordance with good industry practice and any specic
PennBarry recommendations.

Exclusions
These warranties do not cover defects caused by:
1. Improper design or operation of the system into which the PennBarry Product is incorporated.
2. Improper installation.
3. Accident, abuse or misuse.
4. Unreasonable use (including any use for non-commercial purposes, failure to provide reasonable and necessary maintenance
as specied by PennBarry, misapplication and operation in excess of stated performance characteristics).
5. Components not manufactured by PennBarry.

Limitations
1.

2.
3.

In all cases, PennBarry reserves the right to fully satisfy its obligations under the Limited Warranties by refunding the
invoiced price of the defective PennBarry Product (or, if the PennBarry Product has been discontinued, of the most nearly
comparable current product).
PennBarry reserves the right to furnish a substitute or replacement component or product in the event a PennBarry Product
or any component of the product is discontinued or otherwise unavailable.
PennBarrys only obligation with respect to components not manufactured by PennBarry shall be to pass through the
warranty made by the manufacturer of the defective component.

General
The foregoing warranties are exclusive and in lieu of all other warranties except that of title, whether written, oral or
implied, in fact or in law (including any warranty of merchantability or tness for a particular purpose).
PennBarry hereby disclaims any liability for special, punitive, indirect, incidental or consequential damages, including
without limitation lost prots or revenues, loss of use of equipment, cost of capital, cost of substitute products,
facilities or services, downtime, shutdown or slowdown costs.
The remedies of the original commercial purchaser set forth herein are exclusive and the liability of PennBarry with respect
to the PennBarry Products, whether in contract, tort, warranty, strict liability or other legal theory shall not exceed the invoiced
price charged by PennBarry to its customer for the affected PennBarry Product at the time the claim is made.
Inquiries regarding these warranties should be sent to: PennBarry, 1401 North Plano Road, Richardson, TX 75081.

PENNBARRY

45

Breezeway_Cover_01_2005.qxp

12/9/2004

1:14 PM

Page 2

OTHER PENNBARRY PRODUCTS


CENTRIFUGAL PRODUCTS

Domex

Fumex Fatrap

Zephyr

Dynamo

Centrifugal
Roof Exhausters

Kitchen Hood Centrifugal


Roof Exhausters

Ceiling and Inline Fans

Centrifugal Blowers

Centrex Inliner

LC Dynafan

ESI

Fume Exhaust

Centrifugal Inline Fans

Low Contour Centrifugal


Roof Exhausters

Efficient Silent
Inline Fan

Curb Mounted
Centrifugal Fans

AXIAL / GRAVITY PRODUCTS

Breezeway

HI-EX

Tubeaxial

Vaneaxial

Propeller Wall Fans

Power Roof Ventilator

Inline Fans

Inline Fans

Powered Airette

Airette

Domex Axial

Axcentrix

Axial Roof Ventilators

Gravity Intake/Relief Hood

Axial Roof Ventilators

Bifurcator Fan

For more information contact your local PennBarry Sales


Manufacturer Representative or visit us at www.PennBarry.com

2005 PennBarry

All Rights Reserved.

February 2005

Вам также может понравиться